*Horizontal Conversion for these furnaces may be left or right side rotation. For VENT SIZING INFORMATION see: USA National Fuel Gas Code ........ ANSI Z223.1/NFPA 54 (latest version) CANADA Natural Gas Installation Code ..... CAN/CGA-B149.1 (latest version) Propane Installation Code ............ CAN/CGA-B149.2 (latest version) USA/CANADA ALTERNATE — Category I Venting Guide ................................. Pub. No. 18-CH23D1-2 *UD2A040A9242A *UD2A060A9362A *UD2B060A9362A *UD2B080A9362A *UD2B080A9482A *UD2B100A9362A *UD2C100A9482A *UD2C100A9602A *UD2D100A9602A *UD2C120A9542A *UD2D120A9602A *UD2D140A9602A *DD2A040A9242A *DD2A060A9362A *DD2B060A9362A *DD2B080A9362A *DD2B100A9482A *DD2C100A9482A *DD2C100A9602A *DD2D120A9602A *DD22D140A602A Upflow / Horizontal and Downflow / Horizontal Gas-Fired Furnaces, 2 - Stage, “Fan Assisted Combustion System” ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. Installer’s Guide * First letter may be “A” or “T” A341789P02 Upflow / Horizontal* Downflow / Horizontal* 18-CD19D2-22

Upload: others

Post on 17-Mar-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

*Horizontal Conversion for these furnaces may be left or right side rotation.

For VENT SIZING INFORMATION see:USA —National Fuel Gas Code ........ ANSI Z223.1/NFPA 54 (latest version)

CANADA —Natural Gas Installation Code ..... CAN/CGA-B149.1 (latest version)Propane Installation Code ............ CAN/CGA-B149.2 (latest version)

USA/CANADA ALTERNATE —Category I Venting Guide .................................Pub. No. 18-CH23D1-2

*UD2A040A9242A *UD2A060A9362A *UD2B060A9362A*UD2B080A9362A *UD2B080A9482A *UD2B100A9362A*UD2C100A9482A *UD2C100A9602A *UD2D100A9602A*UD2C120A9542A *UD2D120A9602A *UD2D140A9602A*DD2A040A9242A *DD2A060A9362A *DD2B060A9362A*DD2B080A9362A *DD2B100A9482A *DD2C100A9482A*DD2C100A9602A *DD2D120A9602A *DD22D140A602A

Upflow / Horizontal and Downflow / HorizontalGas-Fired Furnaces, 2 - Stage,“Fan Assisted Combustion System”

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.Please return to service information pack upon completion of work.

Installer’s Guide

* First letter may be “A” or “T”

A341789P02

Upflow / Horizontal* Downflow / Horizontal*

1 8 - CD1 9 D2 - 2 2

Page 2: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

© 2010 Trane All Rights Reserved 18-CD19D2-22

Installer’s GuideThe following safety practices and precautions must befollowed during the installation, servicing, and operation ofthis furnace.

1. Use only with the type of gas approved for this furnace.Refer to the furnace rating plate.

2. Install this furnace only in a location and position asspecified in “Location and Clearances” (page 3), of theseinstructions.

3. Provide adequate combustion and ventilation air to thefurnace space as specified in “Air for Combustion andVentilation” (pages 7-8), of these instructions.

4. Combustion products must be discharged outdoors.Connect this furnace to an approved vent system only, asspecified in the “Venting” section (pages 13-14), of theseinstructions.

5. Never test for gas leaks with an open flame. Use acommercially available soap solution made specificallyfor the detection of leaks to check all connections, asspecified in “Gas Piping” (page 19), of theseinstructions.

6. Always install the furnace to operate within the furnace’sintended temperature-rise range with a duct systemwhich has an external static pressure within the allow-able range, as specified on the unit rating plate. Airflowwith temperature rise for cfm versus static is shown inthe Service Facts accompanying this furnace.

7. When a furnace is installed so that supply ducts carry aircirculated by the furnace to areas outside the spacecontaining the furnace, the return air shall also behandled by a duct(s) sealed to the furnace casing andterminating outside the space containing the furnace.

8. A gas-fired furnace for installation in a residentialgarage must be installed as specified in “Location andClearances” section (page 3), of these instructions.

9. The furnace may be used for temporary heating ofbuildings or structures under construction only when thefollowing conditions have been met:a. The furnace venting system must be complete andinstalled per manufacturers instructions.b. The furnace is controlled only by a room thermostat(no field jumpers).c. The furnace return air duct must be complete andsealed to the furnace and clean air filters are in place.d. The furnace input rate and temperature rise must beverified to be within nameplate marking.e. 100% of the furnace combustion air requirementmust come from outside the structure.f. The furnace return air temperature range is between55 and 80 degrees Fahrenheit.g. Clean the furnace, duct work, and components uponsubstantial completion of the construction process, andverify furnace operating conditions including ignition,input rate, temperature rise and venting, according to themanufacturer's instructions.

10. This product must be gas piped by a Licensed Plumber orGas Fitter in the Commonwealth of Massachusetts.

SAFETY SECTION

▲ WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result inserious injury, death or property damage.

Improper servicing could result in dangerous operation,serious injury, death, or property damage.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.

7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.

8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

▲ WARNING!

Safety signal words are used to designate a degree or level ofseriousness associated with a particular hazard. The signalwords for safety markings are WARNING and CAUTION.

a. WARNING indicates a potentially hazardous situationwhich, if not avoided, could result in death or seriousinjury.

b. CAUTION indicates a potentially hazardous situationwhich, if not avoided, may result in minor or moderateinjury. It is also used to alert against unsafe practicesand hazards involving only property damage.

Page 3: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 3

Installer’s Guide

INSTALLATION INSTRUCTIONS 3General Installation Instructions 3Locations And Clearances 3Outline Drawings 4-5Upflow Installation 6Downflow Installation 6Air For Combustion And Ventilation 7Duct Connections 8Return Air Filters 9-13Typical Upflow Return Air Filter Installations 9Alternate Upflow Filter Clip / Bracket Installation 12Typical Downflow Furnace return Air Filter Installations 12General Venting Instructions 13Venting Into A Masonry Chimney 13Electrical Connections 14-15Field Wiring Diagrams 15-18Gas Piping 19Sequence Of Operation 19

Start Up And Adjustment 20Preliminary Inspections 20Combustion And Input Check 20High Altitude Derate 22Lighting Instructions 22Control And Safety Switch Adjustment 23

Abnormal Conditions 23

IFC Error Flash Code 24

ContentsGENERAL INSTALLATION INSTRUCTIONSThe manufacturer assumes no responsibility for equipmentinstalled in violation of any code or regulation.

It is recommended that Manual J of the Air ConditioningContractors Association (ACCA) or A.R.I. 230 be followed inestimating heating requirements. When estimating heatingrequirements for installation at Altitudes above 2000 ft.,remember the gas input must be reduced (See GAS INPUTADJUSTMENT).

Material in this shipment has been inspected at thefactory and released to the transportation agencywithout known damage. Inspect exterior of carton forevidence of rough handling in shipment. Unpackcarefully after moving equipment to approximatelocation. If damage to contents is found, report thedamage immediately to the delivering agency.

Codes and local utility requirements governing the installa-tion of gas fired equipment, wiring, plumbing, and flueconnections must be adhered to. In the absence of local codes,the installation must conform with latest edition of theNational Fuel Gas Code ANSI Z223.1 • National InstallationCode, CAN/CGA B149.1. The latest code may be obtainedfrom the American Gas Association Laboratories, 400 N.Capitol St. NW, Washington D.C. 20001.1-800-699-9277 or www.aga.org

These furnaces have been classified as Fan AssistedCombustion system CATEGORY I furnaces as required byANSI Z21.47 “latest edition” and CAN/CGA 2.3. Thereforethey do not require any special provisions for venting otherthan what is indicated in these instructions. (Category Idefined on page 13).

These furnaces may be twinned. They shall havecommon returns with equal pressure drops or ductswith equivalent lengths and sizes. See Field WiringDiagrams for Twinning on page 17 for proper hookup.

▲ CAUTION!To prevent shortening its service life, the furnace should notbe used as a “Construction Heater” during the finishingphases of construction until the requirements listed in item9, a-g of the safety section of this publication have been met.Condensate in the presence of chlorides and fluorides frompaint, varnish, stains, adhesives, cleaning compounds, andcement create a corrosive condition which may cause rapiddeterioration of the heat exchanger.

▲ WARNING!These furnaces are not approved or intended for installationin manufactured (mobile) housing, trailers, or recreationalvehicles. Failure to follow this warning could result inproperty damage, personal injury, or death.

▲ CAUTION!Do not install the furnace in a corrosive or contaminatedatmosphere.

LOCATION AND CLEARANCESThe location of the furnace is normally selected by thearchitect, the builder, or the installer. However, before thefurnace is moved into place, be sure to consider the followingrequirements:

1. Is the location selected as near the chimney or vent andas centralized for heat distribution as practical?

2. Do all clearances between the furnace and enclosureequal or exceed the minimums stated in Clearance Tableon the Outline Drawings.

3. Is there sufficient space for servicing the furnace andother equipment? A minimum of 24 inches front accessi-bility to the furnace must be provided. Any access door orpanel must permit removal of the largest component.

4. Are there at least 3 inches of clearance between thefurnace combustion air openings in the front panel andany closed panel or door provided?

5. Are the ventilation and combustion air openings largeenough and will they remain unobstructed? If outside airis used, are the openings set above the highest snowaccumulation level? (See the Air for Combustion andVentilation section)

6. Allow sufficient height in supply plenum above the furnaceto provide for cooling coil installation, if the cooling coil isnot installed at the time of this furnace installation.

7. A furnace shall be installed so electrical components areprotected from water.

8. If the furnace is installed in a residential garage, itmust be installed so that the burners, and the ignitionsource are located not less than 18 inches above the floorand the furnace must be located or protected to avoidphysical damage from vehicles.

Page 4: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

4 18-CD19D2-22

Installer’s Guide

Fro

m D

wg.

21C

3416

99 S

h. 1

Rev

. 4

*UD

2 O

UTL

INE

DR

AW

ING

(ALL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

MO

DE

LD

IM "

A"

DIM

"B

"D

IM "

C"

DIM

"D

"

*UD

2A04

0A92

42A

*UD

2A06

0A93

62A

14-1

/2"

9-5/

8"13

-1/4

"13

"

*UD

2B06

0A93

62A

*UD

2B08

0A93

62A

*UD

2B08

0A94

82A

*UD

2B10

0A94

82A

17-1

/2"

9-5/

8"16

-1/4

"16

"

*UD

2C10

0A94

82A

*UD

2C10

0A96

02A

*UD

2C12

0A95

42A

21"

13-1

/16"

19-3

/4"

19-1

/2"

*UD

2D10

0A96

02A

*UD

2D12

0A96

02A

*UD

2D14

0A96

02A

24-1

/2"

15-5

/16"

23-1

/4"

23"

*

- T

he F

irst L

ette

r M

ay B

e "A

" or

"T

"

Page 5: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 5

Installer’s Guide

Fro

m D

wg.

21C

3417

00 S

h. 1

Rev

. 0

*DD

2 O

UTL

INE

DR

AW

ING

(ALL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

MO

DE

LD

IM "

A"

DIM

"B

"D

IM "

C"

DIM

"D

"

*DD

2A04

0A92

42A

*DD

2A06

0A93

62A

14-1

/2"

9-5/

8"13

-1/4

"13

"

*DD

2B06

0A93

62A

*DD

2B08

0A93

62A

*DD

2B08

0A94

82A

*DD

2B10

0A94

82A

17-1

/2"

9-5/

8"16

-1/4

"16

"

*DD

2C10

0A94

82A

*DD

2C10

0A96

02A

21"

13-1

/16"

19-3

/4"

19-1

/2"

*DD

2D12

0A96

02A

*DD

2D14

0A96

02A

24-1

/2"

15-5

/16"

23-1

/4"

23"

*

- T

he F

irst L

ette

r M

ay B

e "A

" or

"T

"

Page 6: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

6 18-CD19D2-22

Installer’s Guide

123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456123456789012345678901234567890121234567890123456

FURNACEFRONT

A (width)B (depth)

CD

3

CASED COIL CONNECTIONBRACKET FOR DOWNFLOWFURNACE IN HORIZONTAL

4

5

UPFLOWFURNACE

CASEDCOIL

SCREWS(BOTH SIDES)

STANDOFFS(BOTH SIDES)

STANDOFFS (4) DRILL SCREWS (4)

FOR VERTICALINSTALLATIONS:

1

2

UPFLOW INSTALLATIONStandoffs and screws (See Figure 1 on page 6) are includedwith the cased coils for attachment to the furnace. There areclearance alignment holes near the bottom of the coil wrapperand drill screws are used to engage the furnace top flange.The standoff is inserted into the cabinet alignment hole. Thedrill screws are inserted through the standoffs then screwedinto the furnace flange. The coil is always placed downstreamof the furnace airflow. These instructions apply only if the coilis on top of an upflow furnace.

DOWNFLOW INSTALLATION

▲ WARNING!Do not install the furnace directly on carpeting, tile or othercombustible material other than wood flooring. For verticaldownflow application, subbase (BAYBASE205) must beused between the furnace and combustible flooring. Whenthe downflow furnace is installed vertically with a cased coil,a subbase is not required.

Required floor opening: (DOWNFLOW)See Figure 3 and Table 1

TABLE 1

CABINETWIDTH

RETURNDUCT WIDTH

FLOOR OPENING PLENUM OPENING

"A" "B" "C" "D"14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8"

17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"

21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"

24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"

HORIZONTAL INSTALLATIONThe coil and furnace must be fully supported when used in thehorizontal position.

Three brackets (with screws) are included with downflowfurnaces for installation to stabilize and secure the furnace andTXC cased coil in the horizontal position. See Figure 4.

IMPORTANT:The 2/4TXC cased coil must be placed downstream of thefurnace. In horizontal installations, the apex of the coilmay point either toward or away from the furnace. Seethe 2/4TXC coil Installer's Guide for more details.

The cased coil is secured to the furnace and both the furnaceand the cased coil must be properly supported. The bracketsmount using the rear screws on the coil case and use the screwsprovided to secure the bracket to the furnace. The remainingbracket is placed as close to center as possible (horizontally)between the coil case front and the furnace bottom channel (fordownflow/horizontal furnace). Use four of the screws providedto secure the bracket.

This furnace may be installed in an attic or crawl space in thehorizontal position by placing the furnace on the left or rightside (as viewed from the front in the upright position). Thehorizontal furnace installation in an attic should be on aservice platform large enough to allow for proper clearanceson all sides and service access to the front of the furnace (SeeClearance Table on Outline Drawings and Figure 5).

If the furnace is suspended using perforated steel strap(plumber’s strap), it must be supported at all four cornersand in the middle at the front of the furnace.

TYPICAL ATTIC PLATFORM INSTALLATION(UPFLOW/HORIZONTAL FURNACE SHOWN)

Page 7: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 7

Installer’s Guide

50 CU. FT. OR MOREPER 1000 BTU/HR. INPUTALL EQUIP. INSTALLED

UNCONFINED7

CONFINED8

Typical Suspended Installation(Upflow/Horizontal Furnace Shown)

6

The forward most screw on the side of the furnace may beused to connect the strapping (See Figure 6). Line contact isonly permissible between lines formed by the intersection ofthe top and two sides of the furnace casing and the buildingjoists, studs, or framing.

A cutout is provided on both sides of the downflow furnacecabinet to allow a 90° elbow to be attached inside the cabinetand the vent piping to connect there. In horizontal, thedownflow furnace may be vented through the top of thecabinet if needed. In vertical configuration, the downflowfurnace may be vented using the side cabinet cutouts. Thisventing configuration could be used if an electronic air cleaneris installed.

When the downflow furnace is vented through the leftside of the furnace cabinet in horizontal or verticalconfiguration, Type B vent pipe must be used within thecabinet.

AIR FOR COMBUSTION AND VENTILATIONAdequate flow of combustion and ventilating air must not beobstructed from reaching the furnace. Air openings providedin the furnace casing must be kept free of obstructions whichrestrict the flow of air. Airflow restrictions affect the efficiencyand safe operation of the furnace. Keep this in mind shouldyou choose to remodel or change the area which contains yourfurnace. Furnaces must have a free flow of air for properperformance.

Provisions for combustion and ventilation air shall be madein accordance with “latest edition” of Section 5.3, Air forCombustion and Ventilation, of the National Fuel Gas Code,ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149Installation Codes, and applicable provisions of the localbuilding codes. Special conditions created by mechanicalexhausting of air and fireplaces must be considered to avoidunsatisfactory furnace operation.

Furnace locations may be in “confined space” or “unconfinedspace”. Unconfined space is defined in Table 2 and Figure 7.These spaces may have adequate air by infiltration to provide

LESS THAN 50 CU. FT.PER 1000 BTU/HR. INPUTALL EQUIP. INSTALLED

Confined spaces are installations with less than 50 cu. ft. ofspace per 1000 BUT/hr input from all equipment installed.Air for combustion and ventilation requirements can besupplied from inside the building as in Figure 9 or from theoutdoors, as in Figure 10.

1. All air from inside the building as in Figure 9: Theconfined space shall be provided with two permanentopenings communicating directly with an additionalroom(s) of sufficient volume so that the combined volumeof all spaces meets the criteria for an unconfined space.The total input of all gas utilization equipment installedin the combined space shall be considered in making thisdetermination. Refer to Table 3, for minimum openareas required.

2. All air from outdoors as in Figure 10: The confined spaceshall be provided with two permanent openings, onecommencing within 12 inches of the top and one com-mencing within 12 inches of the bottom of the enclosure.The openings shall communicate directly, or by ducts,with the outdoors or spaces (crawl or attic) that freelycommunicate with the outdoors. Refer to Table 3, forminimum open areas required.

3. The following types of installations will require use ofOUTDOOR AIR for combustion, due to chemical exposures:* Commercial buildings* Buildings with indoor pools* Furnaces installed in commercial laundry rooms* Furnaces installed in hobby or craft rooms* Furnaces installed near chemical storage areas.

Exposure to the following substances in the combustion airsupply will also require OUTDOOR AIR for combustion:* Permanent wave solutions* Chlorinated waxes and cleaners* Chlorine based swimming pool chemicals* Water softening chemicals* Deicing salts or chemicals* Carbon Tetrachloride* Halogen type refrigerants* Cleaning solvents (such as perchloroethylene)* Printing inks, paint removers, varnish, etc.* Hydrochloric acid* Cements and glues* Antistatic fabric softeners for clothes dryers* Masonry acid washing materials

air for combustion, ventilation, and dilution of flue gases.Buildings with tight construction (for example, weatherstripping, heavily insulated, caulked, vapor barrier, etc.), mayneed additional air provided as described for confined space.

Page 8: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

8 18-CD19D2-22

Installer’s Guide

0

9

TABLE 2

MINIMUM AREA IN SQUARE FEET FORUNCONFINED SPACE INSTALLATIONS

FURNACEMAXIMUM BTUH/

INPUT RATING

WITH 8 FOOT CEILINGMINIMUM AREA IN SQUARE FEET

OF UNCONFINED SPACE

40,00060,00080,000100,000120,000140,000

250375500625750875

TABLE 3

MINIMUM FREE AREA IN SQUARE INCHESEACH OPENING (FURNACE ONLY)

FurnaceMaximum

BTUH/INPUTRating

Air FromInside

Air From Outside

Vertical Duct

Horizontal Duct

40,00060,00080,000100,000120,000140,000

100100100100120140

101520253035

203040506070

DUCT CONNECTIONSAir duct systems should be installed in accordance withstandards for air conditioning systems, National FireProtection Association Pamphlet No. 90. They should besized in accordance with ACCA Manual D or whichever isapplicable. Check on controls to make certain they are correctfor the electrical supply.

Central furnaces, when used in connection with cooling units,shall be installed in parallel or on the upstream side of thecooling units to avoid condensation in the heating element,unless the furnace has been specifically approved for down-stream installation. With a parallel flow arrangement, thedampers or other means used to control flow of air shall beadequate to prevent chilled air from entering the furnace, andif manually operated, must be equipped with means toprevent operation of either unit unless the damper is in fullheat or cool position.

On any job, flexible connections of nonflammable materialmay be used for return air and discharge connections toprevent transmission of vibration. Though these units havebeen specifically designed for quiet, vibration free operation,air ducts can act as sounding boards and could, if poorlyinstalled, amplify the slightest vibration to the annoyancelevel.

When the furnace is located in a utility room adjacent to theliving area, the system should be carefully designed withreturns which minimize noise transmission through thereturn air grille. Although these winter air conditioners aredesigned with large blowers operating at moderate speeds,any blower moving a high volume of air will produce audiblenoise which could be objectionable when the unit is locatedvery close to a living area. It is often advisable to route thereturn air ducts under the floor or through the attic. Suchdesign permits the installation of air return remote from theliving area (i.e. central hall).

When the furnace is installed so that the supply ducts carryair circulated by the furnace to areas outside the spacecontaining the furnace, the return air shall also be handled bya duct(s) sealed to the furnace and terminating outside thespace containing the furnace.

Minimum return air “entering temperature” for thefurnace is 55° F.

Where there is no complete return duct system, the returnconnection must be run full size from the furnace to a locationoutside the utility room, basement, attic, or crawl space.

DO NOT install return air through the back of thefurnace cabinet.

Page 9: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 9

Installer’s GuideRETURN AIR DUCT CONNECTION

NOTE:On upflow 5 or 6 ton airflow models where the airflowrequirement exceeds 1800 CFM - Models will requirereturn air openings and filters on: (1) both sides; or (2)one side and the bottom; or (3) just the bottom.

All return air duct systems should provide for installation ofreturn air filters.

1. Determine the appropriate position to set the furnace inorder to connect to the existing supply and returnductwork.

2. For side return installations on upflow models, removethe insulation around the opening in the blowercompartment.

3. The side panels on upflow furnaces include locatingnotches which may be used as guides for cutting anopening for return air. Refer to Figure 12 and the outlinedrawing on page 4 for duct connection dimensions forvarious furnaces.

4. If a 3/4" flange is to be used for attaching the air inletduct, add to cut where indicated by dashed lines inFigure 12. Cut corners diagonally and bend outward toform flange.

5. If flanges are not required, and a filter frame is installed,cut along knockout guidelines.

6. Upflow Furnaces: Use the optional filter rack on eitherside or on the bottom if the filter is to be used within thefurnace cabinet.

When the upflow furnace is installed in the horizontalright or left application and a return duct is attached tothe top side as shown in Figure 11, install the filter in aremote location.

7. Connect the duct work to the furnace. See OutlineDrawing for supply and return duct size and location.Flexible duct connectors are recommended to connectboth supply and return air ducts to the furnace.If only the front of the furnace is accessible, it is recom-mended that both supply and return air plenums areremovable.

8. When replacing a furnace, old duct work should becleaned out. Thin cloths should be placed over theregisters and the furnace fan should be run for 10 min-utes. Don’t forget to remove the cloths before you startthe furnace.

Return Air Filters(Filter and filter rack are not supplied with

unit)TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONSThese furnaces require high velocity type air filters. Theoptional filters may be located within the furnace blowercompartment for UPFLOW furnaces in either a BOTTOM orSIDE (left side or right side) return air inlet. Some optionalfilters may need to be trimmed for side or bottom filter use.

NOTE:

On upflow 5 or 6 ton airflow models where the airflowrequirement exceeds 1800 CFM - Models will requirereturn air openings and filters on: (1) both sides; or (2)one side and the bottom; or (3) just the bottom.

The furnace and the blower filter rack installation can be seenin Figure 13.

*SEE OUTLINE DRAWING

w

LOCATINGNOTCHESPROVIDEDFOR SIDERETURNCUTOUT

*

**

* CUT OUTFORSIDE

FILTER

FRONTof Furnace

▲ WARNING!TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE SERVICING FILTERS.

▲ WARNING!Do not install the filter in the return duct directly above the furnace in horizontal applications. Install the filter remotely. Installing the filter directly above the furnace in horizontal applications may cause property damage, serious injury or death.

Do not install the filter in the return duct directly abovethe furnace in horizontal applications.

When the upflow furnace is installed in the horizontalright or left application and a close coupled (less than36") return duct is attached to the bottom side of thefurnace as shown in Figure 11, securely attach a 1/2"mesh metal hardware cloth protective screen to theinside bottom of the filter grill to prevent personalinjury from contacting moving parts when reachinginto the return opening to replace the filter.

Close coupled (less than 36") return (filter directlybeneath bottom side return) is not recommended due tonoise considerations.

Downflow Furnaces: Brackets are factory supplied tomount filters in the return air duct work.

FILTER

REMOVE FILTER FROM UPFLOWFURNACE WHEN RETURN DUCT ISATTACHED TO FURNACE TOP SIDE(HORIZONTAL LEFT OR RIGHTAPPLICATIONS) AS SHOWN.

Close coupled (less than 36")return (filter directly beneath bottomside return) not recommended due tonoise considerations. If used, securelyattach 1/2" mesh metal hardware clothprotective screen to the inside bottom offilter grill.

q

Page 10: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

10 18-CD19D2-22

Installer’s Guide

e

The optional furnace filter in the bottom or side configurationcan be removed by simply turning the two latches on theblower door and tilting the door forward.

The filter rails are spring loaded for automatic adjustment toallow standard size, locally obtainable replacement filters.The filter rack itself slides to adjust to the required widthneeded for bottom or side return.

TABLE 4

UPFLOW FURNACE RETURN AIR FILTERS

CABINETWIDTH QTY* CABINET

BOTTOM FILTERCABINET

SIDE FILTER

14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"

17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"

21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"

24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"

**NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom

VIEWENGAGEMENTHOLE DETAIL

(Typical both sidesand blower deck)

Blower DeckEngagement

Hole

FilterRackFurnace

CabinetSide

Filter RackRetainingScrew/Pin

Engagement Hole For

Bottom Return

Filter RackInstallation With

t

y

NOTE: The narrow 14.5" width furnace cabinet prevents useof the filter rack for right side return. Pre-drill clearanceholes and then attach filter clips with the screws provided.The filter clip with the leaf spring mounts in the rear of thecabinet

OPTIONAL FILTER RACK INSTALLATION FOR BOTTOMRETURNWith the filter removed, the filter rack is compressed andthen inserted into the bottom of the furnace. The retainingscrew/pin on each side inserts into engagement holes at thebottom of the furnace cabinet side. See Figures 13, 14 & 16.

NOTE: Remove the bottom front channel to install the filterrack in the 14-1/2" width cabinet furnaces.

Optional Filter Rack Accessory Kit

r

Airf low

BAYRACK960A

BOTTOM FILTER RACK INSTALLATION

Airf low

e

Page 11: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 11

Installer’s Guide

FilterRackAssembly

FurnaceBlowerDeck

Filter RackRetainingScrew/Pin

Engagement Hole For

Return

Filter RackInstallation WithSide

FurnaceCabinet

Side

BLOWERDECK

i

BOTTOM ENGAGEMENT

Bottom Panel

FilterRack

FurnaceCabinet

Side

Filter RackRetainingScrew/Pin

Engagement Hole For

Bottom Return

Filter RackInstallation With

u

OPTIONAL FILTER RACK INSTALLATION FOR SIDERETURN AIR ON UPFLOW FURNACES (Left or Right)If side air return is desired, the following instructions shouldbe used:

a. Open or remove the blower door.

b. Leave the bottom panel in place. (Some modelsrequire field supplied bottom panels.)

c. After the side cutout is made following the directionsin the “Return Air Duct Connections” section onpages 8 and 9; compress the filter rack and reinstall inthe side of the furnace. Confirm that the upperretaining pin/screw locks into the engagement hole inthe blower deck and the lower pin/screw rests againstthe side of the bottom panel. See Figures 14, 15, &17-20.

d. Install the furnace filter on the side. See Figures 14,15, & 17-20.

Airflow

a

Typical Horizontal Filter Installation

TABLE 5Cabinet Width Left Side Bottom Right Side

14.5 X1 X2 Use Alternate Filter Clips Only

17.5 X X X

21 X X X

24.5 X X X

1. UC1B060C has 10x7 blower which requires use of alternate filterclips for left side filter. "K1" and later use the filter rack.2. Remove bottom front channel to install or reposition filter rack.X - All Models

RETAININGPIN

(Both Sides)

SPRINGS

SIDECUTOUT

FILTERRACKRAILS

BOTTOMPANEL

INSTALLED

AirflowAirflow

Typical Upflow Left Side Return Filter Rack Installation

o

RETAININGPIN

(Both Sides)

SPRINGS

SIDECUTOUT

FILTERRACKRAILS

BOTTOMPANEL

INSTALLED

AirflowAirflow

p

Typical Upflow Right Side Return Filter Rack Installation

Optional door kitBAYFLTR206

Page 12: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

12 18-CD19D2-22

Installer’s GuideRETURN AIR FILTERS FOR UPFLOW FURNACEIN HORIZONTAL CONFIGURATIONWhen the Upflow Furnace is installed in a horizontal configu-ration, the filter must never be installed inside or outside thecabinet directly above the blower assembly. See Figure 11(page 9). Remote filter grilles may be used for homeownerconvenience or the filters may be installed in the duct workupstream of the furnace. See Figures 11 (page 9) and 21 (page11).

ALTERNATE UPFLOWFILTER CLIP / BRACKET INSTALLATION - KIT09224

1. Determine the location to be used. The furnace cabinethas dimples for location of the alternate furnace clips(Side return only). Pre-drill clearance holes with a3/16" drill. Bottom return holes are pre-drilled.

2. Install the clips in front and rear of the desired locationusing the screws provided. The filter clip with the leafspring mounts in the rear of the cabinet. See Figure 22.

REAR

SIDE

CUT-OUT

ALTERNATE FILTERCLIPS LOCATION

s

UNITSIZE

RETURN AIR

BOTTOM SIDE

14-1/2" CUT ON LINE DO NOT CUT

17-1/2" DO NOT CUT DO NOT CUT

21" DO NOT CUT CUT ON LINE

24-1/2" DO NOT CUT CUT ON LINE

Airflow

Airflow

d

TABLE 6

INSTALLING THE OPTIONAL FILTERThe filter may need to be cut to fit the unit depending on thelocation of the return air filter.

A score line and the words “CUT HERE” are located on theend of the filter. If your application requires cutting the filter,do so as indicted by the score mark.

TYPICAL DOWNFLOW FURNACERETURN AIR FILTER INSTALLATIONS

Two high velocity type air filters are required for each down-flow furnace. Downflow furnace filters must be locatedoutside the furnace cabinet. Typical installations are shownin Figures 23 and 24. Tables 7 and 8 (page 13) provideinformation for installation of the filter retaining bracketsshipped with downflow furnaces.

f

Optional horizontal filter conversion kits are BAYFLTR203for 17 1/2" width cabinets, BAYFLTR204 for 21" widthcabinets, and BAYFLTR205 for 24" width cabinets. Theseinclude filters and brackets necessary for horizontal filters.In addition, optional door kit BAYFLTR206 is also available.See Figures 21 and 24.

CABINETWIDTH

RETURNDUCTWIDTH

FILTER ACCESSOPENING -

DIMENSION "A"

FILTER ACCESSOPENING -

DIMENSION "B"14-1/2" 13-1/4" 12" 14"17-1/2" 16-1/4" 15" 14"

21" 19-3/4" 19-1/2" 14"24-1/2" 23-1/4" 22" 14"

TABLE 7

TABLE 8

CABINETWIDTH

FILTERSIZE

FILTER BRACKETLOCATION *

14-1/2" 2 - 14X20X1 12-7/8"17-1/2" 2 - 16X20X1 14-3/8"

21" 2 - 16X20X1 13-1/8"24-1/2" 2 - 16X20X1 11-5/8"

* Location dimension is from end of duct to the screw holes for the bracket.

Optional door kitBAYFLTR206

Page 13: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 13

Installer’s GuideGENERAL VENTING INSTRUCTIONS

VENT PIPINGThese furnaces have been classified as Fan-Assisted Com-bustion System, Category I furnaces under the “latestedition” provisions of ANSI Z21.47 and CAN/CGA 2.3standards. Category I furnaces operate with a non-positivevent static pressure and with a flue loss of not less than 17percent.

NOTE:If desired, a side wall termination can be accomplishedthrough the use of an “add-on” draft inducer. The inducermust be installed according to the inducer manufacturer’sinstructions. Set the barometric pressure relief to achieve-0.02 inch water column.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.

7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.

8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

▲ WARNING!

NOTE:When the downflow furnace is vented through the left side ofthe furnace cabinet using the provided cutout, Type B ventpiping must be used.

The furnace shall be connected to a factory built chimney orvent complying with a recognized standard, or a masonry orconcrete chimney lined with a lining material acceptable tothe authority having jurisdiction.

▲ WARNING!Furnace venting into an unlined masonry chimney orconcrete chimney is prohibited. Failure to follow thiswarning could result in property damage, personal injury, ordeath.

VENTING INTO A MASONRY CHIMNEYIf the chimney is oversized, the liner is inadequate, or flue-gascondensation is a problem in your area, consider using thechimney as a pathway or chase for type “B” vent or flexiblevent liner. If flexible liner material is used, size the vent us-ing the “B” vent tables, then reduce the maximum capacity by20% (multiply 0.80 times the maximum capacity). MasonryChimney Kit BAYVENT800B may be used with these fur-naces (Upflow model furnaces only) to allow venting into amasonry chimney. Refer to the BAYVENT800B Installer’sGuide for application requirements.

Internal Masonry ChimneysVenting of fan assisted appliances into a lined, internalmasonry chimney is allowed only if it is common vented withat least one natural draft appliance; OR, if the chimney islined with type “B”, double wall vent or suitable flexible linermaterial (See Table 9).

▲ WARNING!The chimney liner must be thoroughly inspected to insureno cracks or other potential areas for flue gas leaks arepresent in the liner. Liner leaks will result in early deteriora-tion of the chimney.

Failure to follow this warning could result in carbon monox-ide poisoning or death.

NOTE:The following section does not apply if BAYVENT800B(Masonry Chimney Vent Kit) is used. All instructions withthe kit must be followed.

TABLE 9MASONRY CHIMNEY VENTING

Tile Lined Chimney Chimney Lining

Type Furnace Internal External “B” VentFlexible

Metal Liner

Single FanAssist No No Yes Yes*

Fan Assist+

Fan AssistNo No Yes Yes*

Fan Assist+

NaturalYes No Yes Yes*

* Flexible chimney liner size is determined by using the type “B” vent size forthe available BTUH input, then reducing the maximum capacity by 20%(multiply maximum capacity times 0.80). The minimum capacity is the sameas shown in the “B” vent tables.

Page 14: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

14 18-CD19D2-22

Installer’s Guide

Maximum Vent or TileLined Chimney Flow Area

*Drafthood outlet diameter, flue collar diameter, or listed appliance categorized ventdiameter.

ELECTRICAL CONNECTIONS

▲ WARNING!The cabinet must have an uninterrupted or unbroken groundaccording to National Electrical Code, ANSI/NFPA 70 –“latest edition” and Canadian Electrical Code, CSA C22.1 orlocal codes to minimize personal injury if an electrical faultshould occur. A failure to follow this warning could result inan electrical shock, fire, injury, or death.

▲ CAUTION!The integrated furnace control is polarity sensitive. The hotleg of the 115 VAC power must be connected to the BLACKfield lead.

▲ WARNING!To prevent injury or death due to electrical shock or contactwith moving parts, lock unit disconnect switch in the openposition before servicing the unit. Failure to follow thiswarning could result in electrical shock, personal injury, ordeath.

πππππ(D*)2

4= X 7

g

External Masonry ChimneyVenting of fan assisted appliances into external chimneys(one or more walls exposed to outdoor temperatures), requiresthe chimney be lined with type “B”, double wall vent orsuitable flexible chimney liner material. This applies in allcombinations of common venting as well as for fan assistedappliances vented alone.

▲ WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the ventingsystem being placed into operation could result in carbonmonoxide poisoning or death.

The following installation practices are recommended tominimize corrosion caused by condensation of flue products inthe furnace and flue gas system.

1. Avoid an excessive number of bends.

2. Horizontal runs should pitch upward at least 1/4" per foot.

3. Horizontal runs should be as short as possible.

4. All vent pipe or connectors should be securely supportedand must be inserted into, but not beyond the inside wallat the chimney vent.

5. When vent connections must pass through walls orpartitions of combustible material, a thimble must beused and installed according to local codes.

6. Vent pipe through the roof should be extended to a heightdetermined by National Fuel Gas Code or local codes. Itshould be capped properly to prevent rain water fromentering the vent. Roof exit should be waterproofed.

7. Use type “B” double wall vent when vent pipe is routedthrough cool spaces (below 60° F.).

TABLE 10

8. Where long periods of airflow are desired for comfort, uselong fan cycles instead of continuous airflow.

9. Apply other good venting practices as stated in theventing section of the National Fuel Gas CodeANSI Z223.1 “latest edition”.

10. Vent connectors serving appliance vented bynatural draft or non-positive pressure shall not beconnected into any portion of a mechanized draftsystem operating under positive pressure.

11. Horizontal pipe runs must be supported by hangers,straps or other suitable material in intervals at aminimum of every 3 feet of pipe.

12. A furnace shall not be connected to a chimney or flueserving a separate appliance designed to burn solid fuel.

13. The flow area of the largest section of vertical vent orchimney shall not exceed 7 times the smallest listedappliance categorized vent area, flue collar area, or drafthood outlet area unless designed in accordance withapproved engineering methods.

GAS VENT TERMINATION

ROOF PITCH MINIMUM HEIGHT

FLAT TO 7/12OVER 7/12 TO 8/12OVER 8/12 TO 9/12OVER 9/12 TO 10/12OVER 10/12 TO 11/12OVER 11/12 TO 12/12OVER 12/12 TO 14/12OVER 14/12 TO 16/12OVER 16/12 TO 18/12OVER 18/12 TO 20/12OVER 20/12 TO 22/12

1.0 FEET *1.5 FEET2.0 FEET2.5 FEET3.25 FEET4.0 FEET5.0 FEET6.0 FEET7.0 FEET7.5 FEET8.0 FEET

* THIS REQUIREMENT COVERS MOST INSTALLATIONS

Page 15: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 15

Installer’s Guide

SEE NOTE 6

From Dwg. B341486 Rev. 1

2 STAGE FURNACE

TWIN

SEE NOTE 7

JUMPER W1 TO W2ON BOTH UNITS.

2ND STAGE WILL FIRE10 MINUTES AFTER 1ST.

SEE NOTE 8

B/C B/CTO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE2 STAGE HEATING

USING A 1 STAGE HEATING THERMOSTATNO COOLING

SEE NOTE 6

From Dwg. B342024 Rev. 0

2 STAGE FURNACE

TWIN

SEE NOTE 7

B/CB/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE2 STAGE HEATING

USING A 2 STAGE HEATING THERMOSTATNO COOLING

Make wiring connections to the unit as indicated on enclosedwiring diagram. As with all gas appliances using electricalpower, this furnace shall be connected into a permanently liveelectric circuit. It is recommended that it be provided with aseparate “circuit protection device” electric circuit. Thefurnace must be electrically grounded in accordance with localcodes or in the absence of local codes with the NationalElectrical Code, ANSI/NFPA 70 “latest edition” or CanadianElectrical Code, CSA C22.1, if an external electrical source isutilized.

All field supplied wiring must conform with the temperaturelimitation for Type T wire [63° F. (35° C)], when installed inaccordance with these instructions and wiring diagramssupplied with the furnace. A disconnecting means must belocated within sight from, and readily accessible to, thefurnace.

Refer to the SERVICE FACTS literature for unit wiringdiagrams in addition to the diagram inside the blower door.

Page 16: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

16 18-CD19D2-22

Installer’s Guide

OUTDOOR UNIT (NO TRANSFORMER)

SEE NOTE 6

From Dwg. B342019 Rev. 0

SEE NOTE 8

FIELD ADDED JUMPER (NOTE 9)

2 STAGE FURNACE

TWIN

SEE NOTE 7

B/CB/C TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE2 STAGE HEATING, 1 STAGE COOLING

USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)

SEE NOTE 6

From Dwg. B342021 Rev. 0

2 STAGE FURNACE

TWIN

SEE NOTE 7

OUTDOOR UNIT (NO TRANSFORMER)

SEE NOTE 8

B/CB/C TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE2 STAGE HEATING, 1 STAGE COOLING

USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)

Page 17: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 17

Installer’s GuideTWINNINGThese furnaces may be twinned. Twinning requires that twofurnaces with the same configuration, capacity, and airflowmust be used. They shall have common returns with equalpressure drops or ducts with equivalent lengths and sizes.See Field Wiring Diagrams below and on the following pagefor proper hookup.

TWIN TWIN

TWINNING CONNECTION DIAGRAMFOR TWINNING UD/DD-R FURNACES

1 STAGE HEAT / 1 STAGE COOLING THERMOSTAT

1 STAGEHEATING / COOLING

THERMOSTAT FURNACE NO. 1 FURNACE NO. 2

BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS

FROM TWIN CONNECTION.

SEE NOTE 4

OUTDOOR UNIT NO. 1(NO TRANSFORMER)

OUTDOOR UNIT NO. 1(WITH TRANSFORMER)

SEE NOTE 3

RC

ISOLATION RELAY(FIELD SUPPLIED)

ALTERNATE CONNECTION

R1

R1

SEE NOTE 5

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 4

JUMPER W1 TO W2ON BOTH UNITS.

2ND STAGE WILL FIRE10 MINUTES AFTER 1ST.

B/CB/CB/CFrom Dwg. 21B341487 Rev. 1

Page 18: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18 18-CD19D2-22

Installer’s Guide

TWIN TWIN

TWINNING CONNECTION DIAGRAMFOR TWINNING UD/DD-R FURNACES

2 STAGE HEAT / 1 STAGE COOLING THERMOSTAT

2 STAGE HEATING1 STAGE COOLING

THERMOSTAT FURNACE NO. 1 FURNACE NO. 2

BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS

FROM TWIN CONNECTION.

SEE NOTE 4

OUTDOOR UNIT NO. 1(NO TRANSFORMER)

OUTDOOR UNIT NO. 1(WITH TRANSFORMER)

SEE NOTE 3

RC

ISOLATION RELAY(FIELD SUPPLIED)

ALTERNATE CONNECTION

R2

R2

SEE NOTE 5

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 4

ISOLATION RELAYSEE NOTE 4

R1R1

B/C B/C B/CFrom Dwg. 21B341488 Rev. 1

TWIN TWIN

TWINNING CONNECTION DIAGRAMFOR TWINNING UD/DD-R FURNACES

2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT

2 STAGE HEATING2 STAGE COOLING

THERMOSTAT FURNACE NO. 1 FURNACE NO. 2

BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS

FROM TWIN CONNECTION.

SEE NOTE 4

OUTDOOR UNIT NO. 1(NO TRANSFORMER)

OUTDOOR UNIT NO. 2(NO TRANSFORMER)

SEE NOTE 3

R2

R2

SEE NOTE 5

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 4

ISOLATION RELAYSEE NOTE 4

R1R1

OUTDOOR UNIT (WITH TRANSFORMER)

SEE NOTE 3

RC

ISOLATION RELAY(FIELD SUPPLIED)

ALTERNATE CONNECTION

B/CB/CB/C

From Dwg. 21B341489 Rev. 1

Page 19: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 19

Installer’s Guide

h

▲ WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result inserious injury, death or property damage.

Never test for gas leaks with an open flame. Use a com-mercially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, personalinjury, or loss of life.

▲ WARNING!TO PREVENT AN EXPLOSION OR POSSIBLE INJURY,DEATH AND EQUIPMENT DAMAGE, DO NOT STORECOMBUSTIBLE MATERIALS, GASOLINE OR OTHERFLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.

GAS PIPING

▲ WARNING!FIRE - EXPLOSION HAZARDDO NOT RUN FLEXIBLE GAS LINE THROUGH THE FUR-NACE CABINET WALL. FAILURE TO FOLLOW THIS WARN-ING COULD RESULT IN PROPERTY DAMAGE, SERIOUSPERSONAL INJURY, OR DEATH.

This unit is shipped standard for left side installation of gaspiping. A piping knockout is also provided in the right side foran alternate piping arrangement. The installation of pipingshall be in accordance with piping codes and the regulationsof the local gas company. Pipe joint compound must be resis-tant to the chemical reaction with liquefied petroleum gases.Refer to piping Table 12 for delivery sizes.NOTE: Refer to local codes and the National Fuel GasCode, current edition, for gas pipe requirements.

The furnace and its individual shut-off valve must be discon-nected from the gas supply piping system during any pressuretesting of that system at test pressures in excess of 1/2 psig.

The furnace and its individual shut-off valve must be discon-nected from the gas supply piping system during any pressuretesting of that system at test pressures in excess of 1/2 psig.

The furnace must be isolated from the gas supply piping byclosing its individual manual shut-off valve during anypressure testing of the gas supply piping system at testpressures equal to or less than 1/2 psig.

NOTE:Maximum pressure to the gas valve for natural gas is13.8" W.C. Minimum pressure is 5.0" W.C. Maximumpressure to the gas valve for propane is 13.8" W.C. Mini-mum pressure is 11.0" W.C.

All gas fittings must be checked for leaks using a soapysolution before lighting the furnace. DO NOT CHECKWITH AN OPEN FLAME!

The following warning complies with State of California law, Proposition 65.

Hazardous Gases!

Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.

▲ WARNING!

SEQUENCE OF OPERATIONThermostat call for heat (2-stage thermostat)Call for 1st stage only:R and W1 thermostat contacts close signaling the controlmodule to run its self-check routine. After the control modulehas verified that the 1st stage pressure switch contacts areopen and the limit switch(es) contacts are closed, the draftblower will be energized.

As the induced draft blower comes up to speed, the pressureswitch contacts will close and the ignitor warm up period willbegin. The ignitor will heat for approx. 20 seconds, then thegas valve is energized in 1st stage to permit gas flow to theburners. The flame sensor confirms that ignition has beenachieved within the 4 second ignition trial period.

As the flame sensor confirms that ignition has been achieved,the delay to fan ON period begins timing and after approx.45 seconds the indoor blower motor will be energized at lowspeed and will continue to run during the heating cycle.

TOP VIEW

AUTOMATIC GAS VALVEWITH MANUAL SHUTOFF

LEFT SIDE PIPING (STANDARD)

TOP VIEW OF RIGHT SIDE PIPING

RIGHT SIDE PIPING (OPTIONAL)

DRIP LEG

DRIP LEG

IMPORTANT:A sediment trap must be installed in the gas linebefore the furnace gas valve. The sediment trapmust be located as close to the furnace cabinet aspractical.

Page 20: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

20 18-CD19D2-22

Installer’s GuideCall for 2nd stage after 1st stage:R and W2 thermostat contacts close signaling a call for 2ndstage heat. After a 30 second delay, the induced draft blowerwill be energized on high speed and the 2nd stage pressureswitch contacts will close allowing the gas valve to be energizedin 2nd stage and the indoor blower motor in high speed.

2nd stage satisfied, 1st stage still called:R and W2 thermostat contacts open signaling that 2nd stageheating requirements are satisfied. The induced draft bloweris reduced to low speed allowing the 2nd stage pressureswitch contacts to open and the gas valve is reduced to 1ststage. After approx. 30 seconds the indoor blower motor isreduced to low speed.

1st stage satisfied:R and W1 thermostat contacts open signaling that 1st stageheating requirements are satisfied. The gas valve will closeand the induced draft blower will be de-energized. The indoorblower motor will continue to run for the fan off period (Fieldselectable at 60, 100, 140 or 180 seconds - Factory setting is100 seconds), then will be de-energized by the control module.

Thermostat call for heat (1-stage Thermostat)R and W1/W2 (jumpered) thermostat contacts close signalinga call for heat. 1st stage sequence of operation remains thesame as above. 2nd stage heat has a 10 minute delay fromthe time of 1st stage ignition.

Thermostat satisfied:R and W1/W2 (jumpered) contacts open signaling the controlmodule to close the gas valve and de-energize the induceddraft blower. The indoor blower motor will continue tooperate at high heat speed for approx. 30 seconds after theflames are extinguished and then is switched to low heatspeed for the remaining FAN-OFF period.

▲ WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result inserious injury, death or property damage.

Never test for gas leaks with an open flame. Use a com-mercially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, personalinjury, or loss of life.

START UP AND ADJUSTMENTPRELIMINARY INSPECTIONSWith gas and electrical power “OFF”

1. Duct connections are properly sealed

2. Filters are in place

3. Venting is properly assembled

4. Blower door is in place

Turn knob on main gas valve within the unit to the “OFF”position. Turn the external gas valve to “ON”. Purge the airfrom the gas lines. After purging, check all gas connections forleaks with a soapy solution — DO NOT CHECK WITH ANOPEN FLAME. Allow 5 minutes for any gas that mighthave escaped to dissipate. LP Gas, being heavier than air,may require forced ventilation. Turn the knob on the gasvalve in the unit to the “ON” position.

COMBUSTION AND INPUT CHECK1. Make sure all gas appliances are off except the furnace.

2. Clock the gas meter with the furnace operating (deter-mine the dial rating of the meter) for one revolution.

3. Match the “Sec” column in the gas flow (in cfh) Table 15with the time clocked.

4. Read the “Flow” column opposite the number of secondsclocked.

5. Use the following factors if necessary:

For 1 Cu. Ft. Dial Gas Flow CFH =Chart Flow Reading ÷ 2

For 1/2 Cu Ft. Dial Gas Flow CFH =Chart Flow Reading ÷ 4

For 5 Cu. Ft. Dial Gas Flow CFH =10X Chart Flow Reading ÷ 4

6. Multiply the final figure by the heating value of the gasobtained from the utility company and compare to thenameplate rating. This must not exceed the nameplaterating.

Gas Valve AdjustmentChanges can be made by adjusting the manifold pressure

(See Table 11), or changing orifices (orifice change maynot always be required). To adjust the manifold pres-sure:

1. Turn off all electrical power to the system.

2. Attach a manifold pressure gauge with flexible tubing tothe outlet pressure boss marked “OUT P” on White-Rodgers gas valve model 36G or 36J. See Figure 27 forWhite-Rodgers gas valve model 36J. See Figure 28 forWhite-Rodgers gas valve model 36G.

3. Loosen (Do Not remove) the pressure tap test set screwone turn with 3/32" hex wrench.

a. The pressure tap adjustment kit (KIT07611)contains a 3/32" hex wrence, a 5/16" hose and aconnector and can be ordered through Global Parts.

4. Turn on system power and energize valve.

5. Adjust 1st stage gas heat by removing the low (LO)adjustment regulator cover screw.

a. To increase outlet pressure, turn the regulator adjustscrew clockwise.

b. To decrease outlet pressure, turn the regulator adjustscrew counterclockwise.

c. Adjust regulator until pressure shown on manometermatches the pressure specified in Table 11.

1. The input of no more than nameplate rating and noless than 93% of the nameplate rating, unless the unitis derated for high altitude.

d. Replace and tighten the regulator cover screw securely.

6. Adjust 2nd stage gas heat by removing the high (HI)adjustment regulator cover screw.

a. To increase outlet pressure, turn the regulator adjustscrew clockwise.

b. To decrease outlet pressure, turn the regulator adjustscrew counterclockwise.

c. Adjust regulator until pressure shown on manometermatches the pressure specified in Table 11.

1. The input of no more than nameplate rating and noless than 93% of the nameplate rating, unless the unitis derated for high altitude.

d. Replace and tighten the regulator cover screw securely.

Page 21: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 21

Installer’s Guide

j

White-Rodgers 36G

Gas Valve On / OffToggle Switch

1st Stage (LO)ManifoldPressureAdjustment

2nd Stage (HI)ManifoldPressureAdjustment

k

White-Rodgers 36J

2nd Stage (HI) ManifoldPressure Adjustment

Gas Valve On / OffToggle Switch

1st Stage (LO)Manifold PressureAdjustmentOutlet

PressureBoss

Inlet PressureBoss

7. Cycle the valve several times to verify regulator setting.

a. Repeat steps 5-7 if needed.

8. Turn off all electrical power to the system.

9. Remove the manometer and flexible tubing and tightenthe pressure tap screw.

10. Using a leak detection solution or soap suds, check forleaks at the pressure outlet boss and pressure tap testscrew.

11. Turn on system power and check operation of the unit.

▲ CAUTION!Replace and/or tighten all plugs removed or loosened whenadjusting gas pressure. Leak check the fittings beforeplacing the furnace into regular service. Failure to followthis warning could result in fire, explosion, or propertydamage.

For LP gases, the final manifold pressure setting shall be10.5" W.C. with an input of no more than the nameplaterating and no less than 93% of the nameplate rating, unlessthe unit is derated for altitude.

Table 13 lists the main burner orifices shipped with thefurnace. If a change of orifices is required to correct the inputrate, refer to Table 14.

TABLE 11

FINAL MANIFOLD PRESSURE SETTINGS (inches w.c.)

FUEL 2nd Stage Max. 1st Stage Max.

NATURAL GAS 3.5" W.C. 1.7" W.C.

LP GAS 10.5" W.C. 6.0" W.C.

TABLE 12

NATURAL GAS ONLY

TABLE OF CUBIC FEET PER HOUR OF GASFOR VARIOUS PIPE SIZES AND LENGTHS

PIPESIZE

LENGTH OF PIPE

10 20 30 40 50 60 70

1/2 132 92 73 63 56 50 46

3/4 278 190 152 130 115 105 96

1 520 350 285 245 215 195 180

1-1/4 1050 730 590 520 440 400 370

This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas

TABLE 13

ORIFICE SIZES

INPUTRATINGBTUH

NUMBEROF

BURNERS

MAIN BURNER ORIFICEDRILL SIZE

NAT. GAS LP GAS

40,00060,00080,000100,000120,000140,000

234567

454545454545

565656565656

TABLE 14

PART NUMBERS FOR REPLACEMENT ORIFICESDRILLSIZE

PARTNUMBER

DRILLSIZE

PARTNUMBER

44454647484950

ORF00501ORF00644ORF00909ORF00910ORF01099ORF00503ORF00493

545556575859

ORF00555ORF00693ORF00907ORF00908ORF01338ORF01339

Page 22: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

22 18-CD19D2-22

Installer’s GuideTABLE 15

GAS FLOW IN CUBIC FEET PER HOUR2 CUBIC FOOT DIAL

SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW8 900 29 248 50 144 82 889 800 30 240 51 141 84 8610 720 31 232 52 138 86 8411 655 32 225 53 136 88 8212 600 33 218 54 133 90 8013 555 34 212 55 131 92 7814 514 35 206 56 129 94 7615 480 36 200 57 126 96 7516 450 37 195 58 124 98 7317 424 38 189 59 122 100 7218 400 39 185 60 120 104 6919 379 40 180 62 116 108 6720 360 41 176 64 112 112 6421 343 42 172 66 109 116 6222 327 43 167 68 106 120 6023 313 44 164 70 103 124 5824 300 45 160 72 100 128 5625 288 46 157 74 97 132 5426 277 47 153 76 95 136 5327 267 48 150 78 92 140 5128 257 49 147 80 90 144 50

HIGH ALTITUDE DERATEInput ratings (BTUH) of these furnaces are based on sea leveloperation and should not be changed at elevations up to 2,000ft.

If the installation is 2,000 ft. or above, the furnace input rate(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.The furnace input rate shall be checked by clocking the gasflow rate (CFH) and multiplying by the heating value ob-tained from the local utility supplier for the gas being deliv-ered at the installed altitude. Input rate changes can bemade by adjusting the manifold pressure (min 3.0 - max 3.7in. W.C. - Natural Gas) or changing orifices (orifice changemay not always be required). If the desired input rate can notbe achieved with a change in manifold pressure, then theorifices must be changed. LP installations will require anorifice change.

IMPORTANT:Re-install the propane orifices to the same depth as theorifices supplied with the equipment.

See Table 16 for help in selecting orifices if orifice change isrequired. Furnace input rate and temperature rise should bechecked again after changing orifices to confirm the properrate for the altitude.

Installations above 4,000 feet may require a pressure switchchange. If required, use the BAYHALT*** Kit (High AltitudeAccessory Kit) listed in PRODUCT DATA.Installation of this furnace at altitudes above 2,000 ft.(610m) shall be in accordance with the local codes, or in theabsence of local codes, the National Fuel Gas Code, ANSIZ223.1/ NFPA 54 or National Standard of Canada, NaturalGas and Propane Installation Code, CSA 149.1. Installation ofthis furnace at altitudes above 2,000 ft. (610m) shall be madein accordance with the listed high Altitude Conversion Kitavailable with this furnace.

TABLE 16

OrificeTwist Drill

Size IfInstalledAt SeaLevel

ALTITUDE ABOVE SEA LEVEL

and Orifice Required At Other Elevations

2000 3000 4000 5000 6000 7000 8000 9000 10000424344454647

424445464748

434445474748

434445474749

434546474849

444547484849

444647484950

454748494950

464748495051

474850505152

5455565758

5455565859

5555565960

5555575960

5556576061

5556576062

5556586162

5656596263

5656596363

5657606364

From National Fuel Gas Code - Table F-4

LIGHTING INSTRUCTIONS

▲ WARNING!DO NOT attempt to manually light the burner. Failure tofollow this warning could result in property damage, per-sonal injury or death.

▲ WARNING!EXPLOSION HAZARD!PROPANE GAS IS HEAVIER THAN AIR AND MAY COL-LECT IN ANY LOW AREAS OR CONFINED SPACES. INADDITION, ODORANT FADE MAY MAKE THE GASUNDETECTABLE EXCEPT WITH A WARNING DEVICE. IFTHE GAS FURNACE IS INSTALLED IN A BASEMENT, ANEXCAVATED AREA OR A CONFINED SPACE, IT ISSTRONGLY RECOMMENDED TO CONTACT A GASSUPPLIER TO INSTALL A GAS DETECTING WARNINGDEVICE IN CASE OF A GAS LEAK.

NOTE: The manufacturer of your furnace does NOT test anydetectors and makes no representations regarding anybrand or type of detector.

Lighting instructions appear on each unit. Each instal-lation must be checked out at the time of initial start upto insure proper operation of all components. Checkout should include putting the unit through one com-plete cycle as outlined below.

Turn on the main electrical supply and set the thermostatabove the indicated temperature. The ignitor will automati-cally heat, then the gas valve is energized to permit the flowof gas to the burners. After ignition and flame is established,the flame control module monitors the flame and suppliespower to the gas valve until the thermostat is satisfied.

TO SHUT OFFFor complete shutdown: Move the control switch on the maingas valve to the “OFF” position (See Figure 27 and 28).Disconnect the electrical supply to the unit.

▲ CAUTION!If this is done during the cold weather months, provisionsmust be taken to prevent freeze-up of all water pipes andwater receptacles. Failure to follow this warning could resultin property damage.

Page 23: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

18-CD19D2-22 23

Installer’s GuideWhenever your house is to be vacant, arrange to havesomeone inspect your house for proper temperature.This is very important in below freezing weather. If forany reason your furnace should fail to operate damagecould result, such as frozen water pipes.

CONTROL AND SAFETY SWITCHADJUSTMENTLIMIT SWITCH CHECK OUTThe limit switch is a safety device designed to close the gasvalve should the furnace become overheated. Since properoperation of this switch is important to the safety of the unit,it must be checked out on initial start up by the in-staller.

To check for proper operation of the limit switches, set thethermostat to a temperature higher than the indicatedtemperature to bring on the gas valve. Restrict the airflow byblocking the return air or by disconnecting the blower. Whenthe furnace reaches the maximum outlet temperature asshown on the rating plate, the burners must shut off. If theydo not shut off after a reasonable time and overheating isevident, a faulty limit switch is probable and the limit switchmust be replaced. After checking the operation of the limitcontrol, be sure to remove the paper or cardboard from thereturn air inlet, or reconnect the blower.

▲ WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the ventingsystem being placed into operation could result in carbonmonoxide poisoning or death.

AIRFLOW ADJUSTMENTCheck inlet and outlet air temperatures to make sure theyare within the ranges specified on the furnace rating name-plate. If the airflow needs to be increased or decreased, seethe wiring diagram for information on changing the speed ofthe blower motor.

▲ WARNING!Disconnect power to the unit before removing the blowerdoor. Failure to follow this warning could result in propertydamage, personal injury or death.

This unit is equipped with a blower door switch which cutspower to the blower and gas valve causing shutdown when thedoor is removed. Operation with the door removed or ajar canpermit the escape of dangerous fumes. All panels must besecurely closed at all times for safe operation of the furnace.

NOTE:Direct drive motors have bearings which are permanentlylubricated and under normal use, lubrication is not recom-mended.

INDOOR BLOWER TIMINGThe control module controls the indoor blower. The blowerstarts approximately 45 seconds after ignition. The FAN-OFF period is approximately 100 seconds from the interrup-tion of gas flow.

ROOM AIR THERMOSTATHEAT ANTICIPATOR ADJUSTMENTSet the thermostat heat anticipator according to the currentflow measured, or the settings found in the notes on thefurnace wiring diagram (found inside the furnace casing).

INSTRUCTIONS TO THE OWNERSIn the event that electrical, fuel, or mechanical failuresoccur, the owner should immediately turn the gassupply off at the manual gas valve, located in the burnercompartment (See Figure 26). Also turn off electricalpower to the furnace and contact the service agencydesignated by your dealer.

▲ WARNING!Should overheating occur, or the gas supply fail to shut off,shut off the gas valve to the unit before shutting off theelectrical supply. Failure to follow this warning could resultin property damage, personal injury, or death.

Carbon monoxide, fire or smoke can cause serious bodilyinjury, death, and/or property damage.

A variety of potential sources of carbon monoxide can be foundin a building or dwelling such as gas-fired clothes dryers, gascooking stoves, water heaters, furnaces and fireplaces. TheU.S. Consumer Product Safety Commission recommendsthat users of gas-burning appliances install carbon monoxidedetectors as well as fire and smoke detectors per the manu-facturers installation instructions to help alert dwellingoccupants of the presence of fire, smoke or unsafe levels ofcarbon monoxide. These devises should be listed by Under-writers Laboratories, Inc. Standards for Single and MultipleStation Carbon Monoxide Alarms, UL 2034 or CSA Interna-tional Standard, Residential Carbon Monoxide AlarmingDevices, CSA 6.19

NOTE:The manufacturer of your furnace does not test any detec-tors and makes no representations regarding any brand ortype of detector.

OPERATING INFORMATIONFLAME ROLL-OUT DEVICEAll models are equipped with a thermal control device on theburner cover. In case of flame roll-out, the device will thecause the circuit to open which shuts off all flow of gas.

ABNORMAL CONDITIONS1. EXCESSIVE COMBUSTION VENT

PRESSURE OR FLUE BLOCKAGEIf pressure against the induced draft blower outletbecomes excessive, the pressure switch will shut off thegas valve until acceptable combustion pressure is againavailable.

2. LOSS OF FLAME OR GAS SUPPLY FAILUREIf loss of flame occurs during a heating cycle (when flameis not present at the sensor), the control module will retrythe ignition sequence up to two times after the sensorcools. If ignition is not achieved, it will lockout thefurnace.

3. POWER FAILUREIf there is a power failure during a heating cycle, thesystem will restart the ignition sequence automaticallywhen power is restored, if the thermostat still calls forheat.

4. INDUCED DRAFT BLOWER FAILUREIf pressure is not sensed by the pressure switch, it willnot allow the gas valve to open, therefore the unit will notstart. If failure occurs during a running cycle, the pres-sure switch will cause the gas valve to close and shut theunit down.

Page 24: 18- CD19D2- 22 Installer’s Guide · 2021. 2. 24. · 18-CD19D2-22 3 Installer’s Guide INSTALLATION INSTRUCTIONS 3 General Installation Instructions 3 Locations And Clearances

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the rightto change design and specifications without notice.

Trane6200 Troup HighwayTyler, TX 75707

For more information contactyour local dealer (distributor)

Installer’s Guide

▲ WARNING!

The following warning complies with State of California law, Proposition 65.

This product contains fiberglass wool insulation!

Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.

PRECAUTIONARY MEASURES

● Avoid breathing fiberglass dust.

● Use a NIOSH approved dust/mist respirator.

● Avoid contact with the skin or eyes. Wear long-sleeved,loose-fitting clothing, gloves, and eye protection.

● Wash clothes separately from other clothing: rinsewasher thoroughly.

● Operations such as sawing, blowing, tear-out, andspraying may generate fiber concentrations requiringadditional respiratory protection. Use the appropriateNIOSH approved respirator in these situations.

FIRST AID MEASURES

Eye Contact – Flush eyes with water to remove dust.If symptoms persist, seek medical attention.

Skin Contact – Wash affected areas gently with soap and warm water after handling.

Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.

— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch;do not use any phone in your building.

• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

— Installation and service must be performed by a qualified installer, service agency or the gas supplier.

▲ WARNING!

INTEGRATED FURNACE CONTROL ERROR FLASH CODESFlashing Slow --- Normal - No call for HeatFlashing Fast --- Normal - Call for HeatContinuous ON --- Replace IFCContinuous OFF --- Check Power2 Flashes --- System Lockout (Retries or Recycles exceeded)

3 Flashes ---

Draft Pressure Error - Possible problems a) Venting problem b) Pressure seitch problem c) Inducer problem

4 Flashes --- Open High Limit Device5 Flashes --- Flame sensed when no flame should be present6 Flashes --- 115 Volt AC power reversed or Poor Grounding7 Flashes --- Gas valve circuit error8 Flashes --- Low flame sense signal

9 Flashes ---Check Ignitor circuit and Line "N" to 24VAC"Common" voltage (< 2volts)(possible grounding problem)

Literature Order Number 18-CD19D2-22

File Number 18-CD19D2-22

Supersedes 18-CD19D2-21

Date 03/10