2013 National Fire Alarm and
Signaling Code Changes
![Page 2: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/2.jpg)
2013 NFPA 72 Changes
Fire Alarm System Documentation Requirements – Chapter 7
Proper documentation is required to properly install and maintain the system:
Design layout documentationShop DrawingsRecord (As-Built) drawingsOM ManualsElectronic Site Specific Software
04/08/23 2
![Page 3: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/3.jpg)
X
2013 NFPA 72 Changes
New Systems• Design• Acceptance• Completion
7.1.1 – Documentation of new systems shall comply with the minimum requirements of this chapter.
Existing Systems• Alteration• Maintenance• Testing
7.1.2-Documentation of the alteration of existing systems shall comply with the minimum requirements of this chapter.
Fire Alarm System Documentation Requirements – Chapter 7
04/08/23 3
![Page 4: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/4.jpg)
X
2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.1
• Written Narrative
• Riser Diagram
• Floor Plan
• Sequence of Operation
• Equipment Technical Data Sheets
• Manufacturers Published Instructions
04/08/23 4
![Page 5: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/5.jpg)
X
2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.1
• Battery Calculations
• Voltage Drop Calculations
• Completed Record of Completion
• Completed Record of Inspection and Testing
• Site Specific Software (Electronic Copy)
• Record (As-Built) Drawings
04/08/23 5
![Page 6: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/6.jpg)
X
2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.2
• The person responsible for the design (layout) shall be identified on the system design documents.
Minimum Documentation Required – 7.2.3
• All fire alarm drawings shall use symbols described in NFPA 170, Standard for Fire Safety and Emergency Symbols
04/08/23 6
![Page 7: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/7.jpg)
X
2013 NFPA 72 Changes
04/08/23 7
![Page 8: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/8.jpg)
X
2013 NFPA 72 Changes
04/08/23 8
![Page 9: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/9.jpg)
X
2013 NFPA 72 Changes
Design Documentation Audible Notification
• Design sound pressure levels indicated
• Ambient noise indicated
• Audible design sound pressure levels
Design Documentation Visible Notification
• Designation of rooms that will have visible notification
• Performance based design alternatives for strobe design
04/08/23 9
![Page 10: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/10.jpg)
X
2013 NFPA 72 Changes
Records Retention
• Keep all test records for 1 year, and all must be available to AHJ
• Design documentation must be kept for the life of the system
• All new systems require a records cabinet at the FACU or another approved location, all documentation must be stored there
• A copy of site specific, non volatile, non-erasable, non-rewritable software must be provided the Owner
04/08/23 10
![Page 11: 130906 fire alarm_2013_nfpa_72_changes[1]](https://reader034.vdocuments.us/reader034/viewer/2022051816/54620f3fb1af9fbc4d8b4fba/html5/thumbnails/11.jpg)
2013 NFPA 72 ChangesCONCLUSION . . .