2013 NFPA 72 Changes

Fire Alarm System Documentation Requirements – Chapter 7

Proper documentation is required to properly install and maintain the system:

Design layout documentationShop DrawingsRecord (As-Built) drawingsOM ManualsElectronic Site Specific Software

04/08/23 2

Page 3: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

New Systems• Design• Acceptance• Completion

7.1.1 – Documentation of new systems shall comply with the minimum requirements of this chapter.

Existing Systems• Alteration• Maintenance• Testing

7.1.2-Documentation of the alteration of existing systems shall comply with the minimum requirements of this chapter.

Fire Alarm System Documentation Requirements – Chapter 7

04/08/23 3

Page 4: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

Minimum Documentation Required – 7.2.1

• Written Narrative

• Riser Diagram

• Floor Plan

• Sequence of Operation

• Equipment Technical Data Sheets

• Manufacturers Published Instructions

04/08/23 4

Page 5: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

Minimum Documentation Required – 7.2.1

• Battery Calculations

• Voltage Drop Calculations

• Completed Record of Completion

• Completed Record of Inspection and Testing

• Site Specific Software (Electronic Copy)

• Record (As-Built) Drawings

04/08/23 5

Page 6: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

Minimum Documentation Required – 7.2.2

• The person responsible for the design (layout) shall be identified on the system design documents.

Minimum Documentation Required – 7.2.3

• All fire alarm drawings shall use symbols described in NFPA 170, Standard for Fire Safety and Emergency Symbols

04/08/23 6

Page 7: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

04/08/23 7

Page 8: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

04/08/23 8

Page 9: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

Design Documentation Audible Notification

• Design sound pressure levels indicated

• Ambient noise indicated

• Audible design sound pressure levels

Design Documentation Visible Notification

• Designation of rooms that will have visible notification

• Performance based design alternatives for strobe design

04/08/23 9

Page 10: 130906 fire alarm_2013_nfpa_72_changes[1]

X

2013 NFPA 72 Changes

Records Retention

• Keep all test records for 1 year, and all must be available to AHJ

• Design documentation must be kept for the life of the system

• All new systems require a records cabinet at the FACU or another approved location, all documentation must be stored there

• A copy of site specific, non volatile, non-erasable, non-rewritable software must be provided the Owner