Contents 0

3

3 - Zelio Control - modular and industrial measurement and control relays

Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/2

Modular measurement and control relays� 3-phase supply control relays RM17 TG

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/9

� Multifunction 3-phase supply control relays RM17 T����00

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/10

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/17

� Mutifunction 3-phase supply control relays RM35 TF

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/18

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/21

� 3-phase supply and motor temperature control relays RM35 TM

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/22

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/27

� 3-phase voltage control relays RM17 UB3 and RM35 UB3

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/28

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/33

� Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/34

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/38

� Multifunction voltage control relays RM35 UA

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/40

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/43

� Current control relays RM17 JC

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/44

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/47

� Current control relays RM35 JA

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/48

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/51

� Level control relays RM35 L

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/52

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/57

� 3-phase and single-phase pump control relays RM35 BA

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/64

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/68

� Frequency control relay RM35 HZ

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/70

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/73

� Speed control relays RM35 S

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/74

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/79

� Temperature control relays RM35 ATp for elevator machine rooms

and 3-phase supplies

� Presentation, characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/82

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/85

3/1

3

Industrial measurement and control relays� 3-phase supply control relays RM4 T

� Presentation, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/88

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/92

� Voltage control relays RM4 U

� Presentation, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/94

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/95

� Voltage measurement relays RM4 U

� Presentation, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/98

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/100

� Current measurement relays RM4 J

� Presentation, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/104

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/106

� Liquid level control relays RM4 L

� Presentation, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/110

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/112

� Plug-in liquid level control relays RM 84 870

� Functions, references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/116

� Plug-in liquid level control relays RM 84 870, combined fill/empty functions

� Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/118

� References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/119

3/2

3

Selection guide 3 Zelio Control - modular and industrial measurement and control relays 3

Application Control of 3-phase supplies

Functions - Phase sequence- Phase failure- Asymmetry

- Phase sequence- Phase failure- Undervoltage

- Phase sequence- Phase failure- Asymmetry- Overvoltage and undervoltage

- Phase sequence- Phase failure- Motor temperature

Modular type (17.5 or 35 mm width)

Values controlled � 208…480 V� 208…440 V

� 208…480 V � 208…480 V� 220…480 V

� 208…480 V

Output 1 or 2 C/O contacts 1 C/O 1 or 2 C/O contacts 2 N/O contacts

Size 17.5 mm 17.5 mm 17.5 or 35 mm 35 mm

Modular type relay RM17 TG�0RM17 TT00RM17 TA00

RM17 TU00 RM17 TE00RM35 TF30

RM35 TM�50MW

Pages 3/6 to 3/17 3/10 to 3/17 3/10 to 3/21 3/22 to 3/27

Industrial type (22.5 or 45 mm width)

Values controlled � 220…440 V� 220…240 V� 380…440 V

� 220…440 V� 220…240 V� 380…440 V

– –

Output 1 or 2 C/O contacts 2 C/O contacts – –

Size 22.5 mm 22.5 mm – –

Industrial type relay RM4 TG20RM4 TA��

RM4 TU��

RM4 TR��

– –

Pages 3/88 to 3/93 3/88 to 3/93 – –

3/3

3

33

Voltage control Current control

3-phase Single-phase and d.c. Integrated current transformer

- Overvoltage and undervoltage between phases- Overvoltage and undervoltage between phases and neutral- Absence of neutral / phase

- Overvoltage or undervoltage- Self-powered

- Overvoltage and undervoltage in window mode- Self-powered

- Overvoltage or undervoltage

- Overcurrent - Overcurrent or undercurrent

� 220…480 V� 208…480 V� 120…277 V

� 9…15 V�/� 20…80 V�/� 65…260 V

�/� 20…80 V�/� 65…260 V

�/� 0,05…5 V�/� 1…100 V�/� 15…600 V

2…20 A 2…500 mA0.15…15 A

1 C/O contactor1 C/O contact+ 1 C/O contact

1 C/O contact 1 C/O contact 2 C/O contacts 1 C/O contact 2 C/O contacts

17.5 or 35 mm 17.5 mm 17.5 mm 35 mm 17.5 mm 35 mm

RM17 UB310RM35 UB3���

RM17 UAS1� RM17 UBE1� RM35 UA1�MW RM17 JC00MW RM35 JA3�MW

3/28 to 3/33 3/34 to 3/39 3/34 to 3/39 3/40 to 3/43 3/44 to 3/47 3/48 to 3/51

– – �/� 80…220 V�/� 160…300 V

0.05…5 V1…100 V30…500 V

– 3 mA...1 A0.3…15 A

– – 2 C/O contacts 2 C/O contacts – 1 or 2 C/O contacts

– – 22.5 mm 22.5 mm – 22.5 or 45 mm

– – RM4 UB3� RM4 UA3�RM4 UA1�

– RM4 JA01RM4 JA3�

– – 3/94 to 3/97 3/98 to 3/103 – 3/104 to 3/109

3/4

3

Selection guide (continued) 3 Zelio Control - modular and industrial measurement and control relays 3

Application Level control

Functions By resistive probes By discrete sensor

- Empty or fill - Empty or fill- Input for discrete sensor AON: Contact/PNP/NPN

Modular type (35 mm width)

Values controlled 0.25…5 kΩ5…100 kΩ0.05…1 MΩ

Output 2 C/O contacts 1 C/O contact

Size 35 mm 35 mm

Modular type relay RM35 LM33MW RM35 LV14MW

Pages 3/52 to 3/57 3/52 to 3/57

Industrial type (22,5 or 39 mm width)

Values controlled 2.5…50 kΩ5…100 kΩ25…500 kΩ

5…100 kΩ –

Output 1 or 2 C/O contacts 1 or 2 C/O contacts –

Size 22.5 mm 39 mm (plug-in 8 or 11-pin) –

Industrial type relay RM4 L RM 84 –

Pages 3/110 to 3/115 3/116 to 3/119 –

3/5

3

3

Pump control Frequency control Speed control Temperature control for elevator machine rooms and 3-phase supplies

3-phase and single-phase - Over-frequency and under-frequency

- Over or under operating rate / speed

- Machine room temperature - Machine room temperature- Phase failure and phase sequence

- Overcurrent and undercurrent- Phase sequenceon 3-phase supply- Phase failure on 3-phase supply

Current: 1…10 A3-phase � 208…480 VSingle-phase � 230 V

Mains supply: 50 or 60 HzHigh threshold: - 2…+ 10 HzLow threshold: - 10…+ 2 Hz

Time controlled between pulses:0.05…0.5 s, 0.1…1 s,0.5…5 s, 1…10 s0.1…1 min, 0.5…5 min, 1…10 min

TemperatureLow threshold: - 1…11 °CHigh threshold: 34…46 °C

TemperatureLow threshold: - 1…11 °CHigh threshold: 34…46 °C3-phase supplies: � 208…480 V

1 C/O contact 1 C/O contact+ 1 C/O contact

1 C/O contact 1 C/O contact or 2 N/O contacts

2 N/O contacts

35 mm 35 mm 35 mm 35 mm 35 mm

RM35 BA10 RM35 HZ21FM RM35 S0MW RM35 ATL0MWRM35 ATR5MW

RM35 ATW5MW

3/64 to 3/69 3/70 to 3/73 3/74 to 3/79 3/82 to 3/85 3/82 to 3/85

– – – – –

– – – – –

– –

– – – – –

– – – – –

3/6

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

3-phase supply control relaysRM17 TG

PresentationRM17 TG�0 measurement and control relays for 3-phase supplies monitor the correct sequencing of phases L1, L2 and L3, as well as the total loss of one or more of these phases.

These control relays accept different nominal 3-phase voltage values:� � 208…480 V for RM17 TG00,� � 208…440 V for RM17 TG20.

They monitor their own power supply, measured as a true rms value.

Control status is indicated by a LED.

The relays are designed for clip-on mounting on � rail

Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

DescriptionRM17 TG00 RM17 TG20

1 Spring for clip-on mounting on 35 mm � rail.

R Yellow LED: indicates relay output state.

RM17 TG�0

1056

62

L1 L2 L3

12 11 14

R

1

L1 L2 L3

24 21 22

12 11 14

R

1

Operation:page 3/7

Characteristics:page 3/8

References, dimensions :page 3/9

3/7

3

Operation 3 Zelio Control - modular measurement and control relays 3

3-phase supply control relays RM17 TG

Operating principle3-phase supply control relays monitor: � Correct sequencing of phases L1, L2 and L3.

Fault signalling is by LED.

Phase control relays: RM17 TG����0The relay monitors its own power supply.

The relay monitors:� Correct sequencing of the three phases,� Total loss of one or more of the phases.

When phase sequence and voltages are correct (> � 183 V), the output relay(s) is/are closed and the yellow LED is on.In the event of a sequencing fault or total loss of one or more phases (detected as soon as one of the voltages drops below 100 V) the relay opens instantly and the LED goes out.

On energisation of the device with a fault measured, the relay stays open.

Function diagram

Tr: response time on appearance of a fault.

100 %

0 %

100 %

0 %

100 %

0 %

R - R1/R2

Tr Tr Tr Tr

L3

L2

Phase L1

Phase L2

Phase L3

Relays

Presentation, description :page 3/6

Characteristics:page 3/8

References, dimensions :page 3/9

3/8

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

3-phase supply control relays RM17 TG

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ���� : 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Relay state indicator Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRelay type RM17 TG00 RM17 TG20

Rated supply voltage Un V � 208…480 � 208…440Operating range V � 183…528 � 183…484Voltage limits Of the power supply circuit - 12 %, + 10 %

Frequency Of the power supply circuit Hz 50/60 Hz ± 10 %Galvanic isolation, supply/measurement NoMaximum power consumption VA ��1.8

Immunity to microbreaks ms 60

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4 NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Input and measurement circuit characteristicsGuaranteed detection threshold for phase failure V < � 100

Frequency of the measured signal

Hz 50…60 ± 10 %

Output characteristicsOutput type 1 C/O contact 2 C/O contactsContact type Cadmium-freeNominal current A 5

Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 V

Electrical durability 1 x 105 operating cycles 1 x 104 operating cyclesMechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13Max. response time in the event of a fault ms 100Delay on pick-up ms 500

Presentation, description :page 3/6

Operation:page 3/7

References, dimensions :page 3/9

3/9

3

References,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

3-phase supply control relays RM17 TG

ReferencesFunction Rated 3-phase

supply voltage Output Reference Weight

V kg� Phase sequence� Phase failure

� 208…480 1 C/O 5 A RM17 TG00 0.080

� 208…440 2 C/O 5 A RM17 TG20 0.085

Dimensions SchemesRM17 TG����0 RM17 TG00 RM17 TG20

mm/In.

Application schemeExample

RM17 TG00

1056

61

RM17 TG20

1056

62

17,50.69

90/3

.54

72/2.83

2,8

0.11

76/2.99

72,5/2.85

12 1411

11

12 14

L1 L2 L3

L1 L3L2

R

L1 L3L224

11 14

22 21

12

2111

12 14 24

L1 L2 L3

22

R1 R2

111412

212422

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

L3L2L1

RM17 TG20

N

fault Start

Stop

Presentation, description :page 3/6

Operation:page 3/7

Characteristicspage 3/8

3/10

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Presentation RM17 TT, RM17 TA, RM17 TU and RM17 TE multifunction control relays monitor the following on 3-phase supplies:

RM17 TT RM17 TA RM17 TU RM17 TE

Sequence of phases L1, L2 and L3.Phase failure with regenerationAsymmetryUndervoltageOvervoltage and undervoltage

Function performed

Function not performed

These control relays accept different nominal 3-phase voltage values: � 208… 480 V.They monitor their own supply voltage, measured as a true rms value.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail

Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

DescriptionRM17 TT00 RM17 TA00

1 Voltage range selector switch (208, 220, 380, 400, 415, 440 and 480 V).

2 Time delay adjustment potentiometer. Tt

3a Asymmetry threshold setting potentiometer. Asy

3b Undervoltage setting potentiometer. <U3c Undervoltage/overvoltage setting

potentiometer. ΔU4 Asymmetry threshold setting

potentiometer. AsyRM17 TU00 RM17 TE00

5 Spring for clip-on mounting on 35 mm � rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM17 T�00

1056

67

L1 L2 L3

12 11 14

MWG

1

5

UnR

L1 L2 L3

12 11 14

123a

5

UnR

L1 L2 L3

12 11 14

123b

5

UnR

L1 L2 L3

12 11 14

123c4

5

UnR

Operation:pages 3/11 to 3/14

Characteristics:pages 3/15 and 3/16

References, dimensions :page 3/17

3/11

3

Operation 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Operating principle3-phase supply control relays monitor: � The correct sequence of phases L1, L2, L3.� Phase failure, including in the case of voltage regeneration� Undervoltage from - 2…- 20 % of the supply voltage Un, � Overvoltage from 2…20 % of the supply voltage Un,� Asymmetry from 5…15 % of the supply voltage Un.

Fault signalling is by LED.

���� Voltage selector switch :� Set the switch to the 3-phase supply voltage Un.� The position of this switch is only taken into account on energisation of the device.� If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the voltage selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

Phase control relay with voltage regeneration: RM17 TT00���� The relay monitors its own supply voltage Un:� The relay monitors:

- correct sequence of the three phases,- failure of at least one of the three phases (U measured < 0.7 x Un).

� In the event of a sequencing or phase failure fault, the relay opens instantly.� On energisation of the device with a fault measured, the relay stays open.

Function diagram

� Function: � Sequence of phases L1, L2, L3.� Phase failure.

11-1211-14

30 % Un 30 % Un30 % Un

L3

L2

Phase L3

Phase L2

Phase L1

Relays

Presentation, description :page 3/10

Characteristics:pages 3/15 and 3/16

References, dimensions :page 3/17

3/12

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Phase and asymmetry control relay: RM17 TA00���� The relay monitors its own supply voltage Un:� The relay monitors:

- correct sequence of the three phases,- failure of at least one of the three phases (U measured < 0.7 x Un),- asymmetry adjustable from 5…15 % of Un.

� In the event of a sequencing or phase failure fault, the relay opens instantly.� In the event of an asymmetry fault, the relay opens at the end of the time delay set by the user.� On energisation of the device with a fault measured, the relay stays open.

Function diagram

� Function: � Sequence of phases L1, L2, L3.� Phase failure,� Asymmetry. Asy.

Tt : time delay after crossing of threshold (adjustable on front panel).

L2

L3

0 %

Tt Tt

11-1211-14

Phase L3

Phase L2

Phase L1

HysteresisAsymmetry

Relays

Presentation, description :page 3/10

Characteristics:pages 3/15 and 3/16

References, dimensions :page 3/17

3/13

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Phase + undervoltage control relays: RM17 TU00���� The relay monitors its own supply voltage Un:� The relay monitors:

- correct sequence of the three phases,- failure of at least one of the three phases (U measured < 0.7 x Un), - undervoltage adjustable from - 2…- 20 % of Un (- 2… - 12 % in the range

� 3 x 208 V and - 2 %…- 17 % in the range � 3 x 220 V due to the minimum voltage� 183 V).� In the event of a sequencing or phase failure fault, the relay opens instantly.� In the event of a voltage fault, the relay opens at the end of the time delay set by the user.� On energisation of the device with a fault measured, the relay stays open.

Function diagrams

� Function: ��Sequence of phases L1, L2, L3.��Phase failure.

� Undervoltage control. U<

Tt : time delay after crossing of threshold (adjustable on front panel)

11-1211-14

30 % Un 30 % Un30 % Un

L3

L2

Phase L3

Phase L2

Phase L1

Relays

L1/L2/L3

L1L2L3

L2L3

L1

Tt Tt

<U

11-1211-14

ThresholdHysteresis

Relays

Phases

Presentation, description :page 3/10

Characteristics:pages 3/15 and 3/16

References, dimensions :page 3/17

3/14

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Phase + asymmetry + undervoltage/overvoltage control relay: RM17 TE00���� The relay monitors its own supply voltage Un:� The relay monitors:

- correct sequence of the three phases,- failure of at least one of the three phases (U measured < 0.7 x Un),- asymmetry adjustable from 5…15 % of Un,- the overvoltage and undervoltage difference in window mode, adjustable from

2…20 % of UnUn 208 V 220 V 380, 400, 415, 440 V 480 V

Voltage threshold (%) < - 12…- 2 - 17…- 2 - 20…- 2 - 20…- 2> + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 10

� In the event of a sequencing or phase failure fault, the relay opens instantly.� In the event of an asymmetry or voltage fault, the relay opens at the end of the time delay set by the user.On energisation of the device with a fault measured, the relay stays open.

Function diagrams

� Function: ��Sequence of phases L1, L2, L3.��Phase failure,��Asymmetry. Asy.

Tt : time delay after crossing of threshold (adjustable on front panel)

� Control of overvoltage and undervoltage in window mode. U> / U<

Tt : time delay after crossing of threshold (adjustable on front panel)

L2

L3

0 %

Tt Tt

11-1211-14

Phase L3

Phase L2

Phase L1

HysteresisAsymmetry

Relays

<U

>U

L1/L2/L3

L1

L2

L3

Tt Tt

11-1211-14

Tt

Threshold

Hysteresis

Hysteresis

Threshold

Relays

Presentation, description :page 3/10

Characteristics:pages 3/15 and 3/16

References, dimensions :page 3/17

3/15

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz

Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400

Insulation test voltageConforming to IEC 60664-1/60255-5

Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LED (flashes during the time delay on crossing the threshold)Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V � 208…480Operating range V � 183…528Voltage limits Of the power supply circuit - 12 %, + 10 %

Frequency Of the power supply circuit Hz 50/60 Hz ± 10 %Galvanic isolation, supply/measurement NoMaximum power consumption at Un VA ��1.8

Immunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Presentation, description :page 3/10

Operation:pages 3/11 to 3/14

References, dimensions :page 3/17

3/16

3

Characteristics (continued) 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

Measurement circuit and input characteristicsMeasurement range V � 183…528

Phase-phase voltage selection V 208, 220, 380, 400, 415, 440 , 480

Frequency of the measured signal 50…60 Hz ± 10 %

Maximum measuring cycle ms 150/measurement as true rms value

Adjustment of voltage threshold 2…20 % of Un selected (- 2…- 12 % in the range 3 x� 208 V, - 2…- 17 % in the range 3 x� 220 V / + 2…+ 10 % in the range 3 x � 480 V)

Fixed hysteresis 2 % of Un

Adjustment of asymmetry threshold 5…15 % of Un selected

Fixed hysteresis 2 % of Un

Setting accuracy ± 10 % of the full scale value

Repeat accuracy (with constant parameters) ± 0.5 %

Measurement error with voltage variation V < 1 % over the whole range

Measurement error with temperature variation < 0.05 % / °C

Maximum regeneration (phase failure) 0.7 Un

Time delay characteristicsTime delay on crossing the threshold s 0.1…10, 0 + 10 %

Repeat accuracy (with constant parameters) ± 3 %

Reset time ms 1500

Response time in the event of a fault ms < 200

Delay on pick-up ms 500

Output characteristicsType of output 1 C/O contact

Contact type Cadmium-free

Nominal current A 5

Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250

Minimum breaking current mA 10/ � 5 V

Maximum breaking current A �/� 5

Electrical durability 1 x 105 operating cycles

Mechanical durability 30 x 106 operating cycles

Maximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

Presentation, description :page 3/10

Operation:pages 3/11 to 3/14

References, dimensions :page 3/17

3/17

3

References,dimensions,scheme 3

Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM17 T�00

ReferencesFunction Rated 3-phase

supply voltage Output Reference Weight

V kg� Phase sequence� Phase failure

� 208…480 1 C/O5 A

RM17 TT00 0.080

� Phase sequence� Phase failure� Asymmetry

� 208…480 1 C/O5 A

RM17 TA00 0.080

� Phase sequence� Phase failure� Undervoltage

� 208…480 1 C/O5 A

RM17 TU00 0.080

� Phase sequence� Phase failure� Asymmetry� Undervoltage and

overvoltage in window mode

� 208…480 1 C/O5 A

RM17 TE00 0.080

Dimensions SchemeRM17 T����00 RM17 T����00

mm/In.

RM17 TT00 RM17 TA00

1056

66

1056

63

RM17 TU00 RM17 TE00

1056

65

1056

67

2,8

0.11

17,50.69

90/3

.54

L1 L2 L3

12 11 14

72/2.83

76/2.99

72,5/2.85

12 1411

11

12 14

L1 L2 L3

L1 L3L2

R

Presentation, description :page 3/10

Operation:pages 3/11 to 3/14

Characteristics:pages 3/15 and 3/16

3/18

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM35 TF

PresentationMeasurement and control relay RM35 TF30 monitors the following on 3-phase supplies: the correct sequencing of phases L1, L2 and L3, failure of one or more of these phases, asymmetry, as well as overvoltage and undervoltage with independent settings.

Multi-voltage product.

This control relay accepts different nominal 3-phase voltage values: � 220… 480 V.

It monitors its own supply voltage, measured as a true rms value.

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relay is designed for clip-on mounting on � rail.

Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

DescriptionRM35 TF

1 Voltage range selector switch (220, 380, 400, 415, 440 and 480 V).

2 Overvoltage setting potentiometer. >U3 Undervoltage setting potentiometer. <U4 Asymmetry threshold setting potentiometer.

Asym5 Time delay adjustment potentiometer. Tt6 Spring for clip-on mounting on 35 mm � rail.

Def. Yellow LED: indicates fault present status (on for asymmetry, flashing for overvoltage and undervoltage).

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 TF30

1056

70

L1

12 22 21 2411 14

L3L2

Def.

Un

R

12345

6

Operation:page 3/19

Characteristics:page 3/20

References, dimensions :page 3/21

3/19

3

Operation 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM35 TF

Operating principle3-phase supply control relay RM35 TF30 monitors: � The correct sequence of phases L1, L2, L3.� Phase failure,� Undervoltage and overvoltage in window mode:Un 220 V 380, 400, 415, 440 V 480 V

Voltage threshold (%) < - 12…- 2 - 20…- 2 - 20…- 2> + 2…+ 20 + 2…+ 20 + 2…+ 10

� Asymmetry from 5…15 % of the supply voltage Un.

Fault signalling is by LED.

���� Voltage selector switch :� Set the switch to the 3-phase supply voltage Un.� The position of this switch is only taken into account on energisation of the device.� If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the voltage selected at the time of energisation preceding the change of position.� The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

���� The relay monitors its own supply voltage Un:� The relay monitors:

- correct sequence of the three phases,- failure of at least one of the three phases (U measured < 0.7 x Un),- asymmetry, adjustable from 5 to 15 % of Un,- the undervoltage, adjustable from - 2…- 20 % of Un

(- 2…- 12 % in the range � 3 x 220 V)- the overvoltage, adjustable from + 2…+ 20 % of Un

(+ 2…+ 10 % in the range � 3 x 480 V due to the maximum voltage � 528 V).� In the event of a sequencing or phase failure fault, the relay opens instantly.� In the event of an asymmetry or voltage fault, the relay opens at the end of the time delay set by the user.� On energisation of the device with a fault measured, the relay stays open.

Function diagrams

� Function: ��Sequence of phases L1, L2, L3.��Phase failure,��Asymmetry.

Tt: time delay after crossing of threshold (adjustable on front panel)

� Control of overvoltage and undervoltage in window mode. <U<

Tt: time delay after crossing of threshold (adjustable on front panel)

L2

L3

0 %

Tt Tt

Phase L3

Phase L2

Phase L1

HysteresisAsymmetry

Relay

<U

>U

L1/L2/L3

L1

L2

L3

Tt Tt Tt

Threshold

Hysteresis

Hysteresis

Threshold

Relay

Presentation, description :page 3/18

Characteristics:page 3/20

References, dimensions :page 3/21

3/20

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM35 TF

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-27 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to IEC 60664-1, 60255-5

> 500 MΩ, � 500 V

Rated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plasticPower ON indicator Green LED (this LED is off in the event of phase failure)

Relay state indicator Yellow LED (this LED flashes during the time delay on crossing the threshold)Fault indication Yellow LED

- this LED lights up in the event of asymmetry,- this LED flashes in the event of overvoltage or undervoltage

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V � 3 x 220… 3 x 480Operating range V � 194…528

Voltage limits Of the power supply circuit - 12 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement No

Maximum power consumption VA ��2.9 Immunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Input and measurement circuit characteristicsMeasurement range V � 194…528

Phase-phase voltage selection V 220, 380, 400, 415, 440, 480Guaranteed detection threshold for phase failure V 194Frequency of the measured signal Hz 50…60 ± 10 %

Maximum measuring cycle ms 140/measurement as true rms valueAdjustment of voltage threshold 2…20 % of Un selected

(- 12…- 2 % in the range 3 x � 220 V and - 20…- 2 % in the ranges 3 x� 380…480 V)(+ 2…+ 20 % in the ranges 3 x � 220…440 V and + 2…+ 10 % in the range 3 x� 480 V)

Fixed hysteresis 2 % of UnAdjustment of asymmetry threshold 5…15 % of Un selected Setting accuracy ± 10 % of the threshold setting (of the full scale value)

Repeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole rangeMeasurement error with temperature variation 0.05 % / °C

Presentation, description :page 3/18

Operation:page 3/19

References, dimensions :page 3/21

3/21

3

Characteristics (continued)

reference,dimensions,scheme 3

Zelio Control - modular measurement and control relays 3

Multifunction 3-phase supply control relays RM35 TF

Time delay characteristicsTime delay on crossing the threshold s 0.1…10. 0 + 10 %Repeat accuracy (with constant parameters) ± 0.3 %Reset time ms 1500 max at 480 V

Response time in the event of a fault ms < 200Delay on pick-up ms 500

Output characteristicsType of output 2 C/O contacts

Contact type Cadmium-freeMaximum switching voltage V �/� 250Rated breaking capacity VA 1250

Maximum breaking current A �/� 5Minimum breaking current mA 10 /� 5 VMechanical durability 30 x 106 operating cycles

Electrical durability 1 x 105 operating cyclesMaximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

ReferenceFunction Rated 3-phase

supply voltage Output Reference Weight

V kg� Phase sequence� Phase failure� Asymmetry� Undervoltage and

overvoltage in window mode

� 220…480 2 C/O 5 A RM35 TF30 0.130

Dimensions SchemeRM35 TF30 RM35 TF30

mm/In.

RM35 TF30

1056

70

2,8

0.11

76/2.99

72,5/2.85

72/2.83

90/3

.54

35/1.38

L1 L2 L3

L1 L2

R

L3

24221412

2111

11 21 2412 2214

Presentation, description :page 3/18

Operation :page 3/19

Characteristics:page 3/20

3/22

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

Presentation Motor temperature measurement and control relays RM35 TM50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and L3, phase failure and motor temperature via PTC probes (with or without memory). The "phase" and "temperature" control functions are independent of each other.These control relays accept different nominal 3-phase voltage values: ��208… 480 V.They also detect line breaks or short-circuiting of the probes.A version with fault memory and Test/Reset function is available.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail

Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

DescriptionRM35 TM50MW RM35 TM250MW

1 Spring for clip-on mounting on 35 mm � rail.

2 Temperature contact (11-14).3 Phase contact (21-24).4 Configuration: selection of temperature

control operating mode (with or without memory). Memory - No Memory

5 Pushbutton (activation of temperature control) Test/Reset

R1 Yellow LED: temperature relay state indicator.Un Green LED: power ON indicator.R2 Yellow LED: phase relay state indicator.

RM35 TM���MW

1064

39

T1 L1 L2 L3

A1 1411 21 24A2

T2

1 2 3

Un

R2

R1

T1 L1 L2 L3

A1 1411 21 24A2

T2 Y1

4

5

1 2 3

Un

R2

R1

Operation:pages 3/23 and 3/24

Characteristics:pages 3/25 and 3/26

References, dimensions :page 3/27

3/23

3

Operation 3 Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

Operating principleRelays RM35 TM50MW and RM35 TM250MW monitor:� The status of the 3-phase supply,� The temperature of motors with embedded PTC probes. The "phase" and "temperature" control functions are independent of each other.

The 3-phase supply control function (208…480 V) monitors:� The correct sequence of phases L1, L2, L3: � Total failure of a phase, including in the case of regeneration (asymmetry greater than 30 % of the average of the three phases).

Phase and temperature control relays: RM35 TM50MW and RM35 TM250MW� 3-phase supply controlAs soon as phase sequence (L1, L2, L3) and phase presence (symmetry of their amplitude < 30 %) are considered to be correct, the output relay contact closes and LED R2 is lit.In the event of total failure or drop in amplitude of a phase (phase failure with regeneration) or inversion of phase sequence, the output relay contact opens and LED R2 goes out.

The result of the control is indicated by the status of output relay R2, N/O contact 21-24 open in the event of a fault.

���� Temperature controlThe temperature control relay can take up to 6 PTC (positive temperature coefficient) probes wired in series between terminals T1 and T2.A fault is declared when the resistance of the temperature sensing circuit exceeds 3100 Ω. Return to normal status is detected when the resistance is once again below 1650 Ω.

The result of the control is indicated by the status of the "temperature" output relay, N/O contact 11-14 open in the event of a fault.Opening of the thermal sensing circuit, which has the same effect as a high temperature (resistance exceeds 3100 Ω) is therefore interpreted as a fault.Total short-circuiting of the temperature probe(s), detected when resistance is less than 15 Ω ± 5 Ω, is treated as a fault.LED R1 is lit when the temperature is correct.

Function diagrams

� Function: ��Sequence of phases L1, L2, L3.��Total phase failure.

21-24

30 % Un 30 % Un30 % Un

L3

L2

Phase L3

Phase L2

Phase L1

Phase relay R2

��Motor temperature control via PTC probe

1650 Ω

3100 Ω

15 Ω

11-14θ° relay R1

Resistance T1-T2

Supply Un

Presentation, description :page 3/22

Characteristics:pages 3/25 and 3/26

References, dimensions :page 3/27

3/24

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

Phase and temperature control relay (with or without memory): RM35 TM250MWConfiguration

The configuration is taken into account when relay RM35 TM250MW is energised.Selection of operating mode: Set the switch to the required operating mode: � Temperature control without memory,� Temperature control with memory.

On energisation, placing the switch in one of the five intermediate positions holds the relay in the open contact state and the error is signalled by simultaneous flashing of the LEDs.The position of the mode selector switch is taken into account on energisation. Any modification of its position during operation has no effect: the active configuration may therefore be different from that indicated by the switch; the RM35 TM250MW operates normally but the fact that the configuration has been changed is signalled by simultaneous flashing of the three LEDs.

� Memory Relay version RM35 TM250MW has a selector switch which allows the temperature control operating mode to be configured with or without memory.In "memory" mode, when a fault is detected, the "temperature" relay locks in the open position. As soon as the temperature returns to the correct value, the relay can be unlocked (reset), either by pressing the "Test/Reset" button (for at least 50 ms), or by closing a volt-free contact (for at least 50 ms) between terminal Y1 and T1 (without a parallel load).Relay RM35 TM250MW can also be reset by switching the power off then on (see reset time).

� Use of the “Test/Reset” buttonRelay version RM35 TM250MW has a "Test/Reset" button which can be used to check that the temperature control function is working correctly and to reset this function after locking in "memory" mode.

The press and release times are 50 ms for both functions.When the temperature is normal, pressing the "Test/Reset" button simulates overheating, the "temperature" output relay contact is open and the "no fault" LED is off.If "memory" mode is not active, the "fault" indication is maintained for as long as the button is pressed.

If "memory" mode is active, "fault" indication is locked and the button must be released then pressed again to reset the function.In "memory" mode, when a fault has been detected and the temperature has returned to normal, the "temperature" control relay can be unlocked (reset) by pressing the "Test/Reset" button.

Function diagrams

� Function: ��Motor temperature control via PTC probe (with memory) Memory.

11-14

S2 T1/Y1

1650 Ω3100 Ω

15 Ω

Test/Reset

Test/Reset

θ° relay R1

Resistance T1-T2

Supply Un

��Use of the “Test/Reset” button(without memory) No Memory.

(with memory) Memory.

11-14

15 Ω

1650 Ω3100 Ω

Test/Reset

Test/Reset

θ° relay R1

Supply Un

Resistance T1-T2

Reset Reset Reset

11-14

15 Ω

1650 Ω3100 Ω

Test/Reset

θ° relay R1

Supply Un

Resistance T1-T2

Presentation, description :page 3/22

Characteristics:pages 3/25 and 3/26

References, dimensions :page 3/27

3/25

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

Environment characteristicsConforming to standards NF EN 60255-6, IEC 60255-6 and IEC 60034-11-2Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4 (1.2/50 µs)Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicators R1 (temperature) Yellow LED (flashes during the time delay on crossing the threshold)

R2 (phase) Yellow LED

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4…264

Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement No (current limitation)Maximum power consumption VA � 4 VA / � 0.5 W

Immunity to microbreaks 20 ms at 20.4 V

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3IEC 61000-6-4IEC 61000-6-3

Input and 3-phase measurement circuit characteristicsMeasurement range V � 208…480Operating range V � 176…528

Frequency of the measured signal 50…60 Hz ± 10 %Input resistance kΩ 602/line

Presentation, description :page 3/22

Operation:pages 3/23 and 3/24

References, dimensions :page 3/27

3/26

3

Characteristics (continued) 3 Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

Output characteristicsType of output 2 N/O contacts

Contact type Cadmium-free

Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250

Minimum breaking current mA 10/ � 5 V

Maximum breaking current A �/� 5

Electrical durability 1 x 104 operating cycles

Mechanical durability 30 x 106 operating cycles

Maximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

Time delay on crossing the threshold

Phases ms 300

Temperature ms 300

Response time input Y1 (contact Y1-T1) and pushbutton ms 50 min.Reset time ms 10 000

Delay on pick-up ms 500

Temperature control characteristicsMaximum voltage of temperature control circuit V 3.6 (T1-T2 open)

Temperature sensing circuit short-circuit current mA 7 (T1-T2 short-circuited)

Maximum resistance of temperature sensor at 20°C Ω 1500

Tripping threshold Ω 3100 ± 10 %

Reset threshold Ω 1650 ± 10 %

Circuit short-circuit detection range Ω 0…15 ± 5

Presentation, description :page 3/22

Operation:pages 3/23 and 3/24

References, dimensions :page 3/27

3/27

3

References,dimensions,scheme 3

Zelio Control - modular measurement and control relays 3

3-phase supply and motor temperature control relays RM35 TM

ReferencesFunction Supply

voltageRated3-phase supply voltage

Output Reference Weight

V V kg� Phase sequence� Phase failure� Motor temperature

via PTC probe

�/� 24…240 � 208…480 2 N/O5 A

RM35 TM50MW 0.120

� Phase sequence� Phase failure� Motor temperature

via PTC probe� Selection (with or

without memory)� “Test/Reset” button

�/� 24…240 � 208…480 2 N/O5 A

RM35 TM250MW 0.120

Dimensions SchemeRM35 TM��������MW RM35 TM��������MW

mm/In.

RM35 TM50MW

1064

39

RM35 TM250MW

1056

72

90/3

.54

2,8

0.11

76/2.99

72,5/2.85

35/1.3872/2.83

A1 A2

T1 T2 L1 L2 L3

11 21 2414

14 24

11 21

R1 R2

Presentation, description :page 3/22

Operation:pages 3/23 and 3/24

Characteristics:pages 3/25 and 3/26

3/28

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Presentation Voltage measurement and control relays RM35 UB330, RM17 UB310 and RM35 UB3N30 monitor the following, on 3-phase supplies:

RM35 UB330 RM17 UB310 RM35 UB3N30

Failure of one or more phases,Absence of neutralOvervoltage and undervoltageVoltage between phases 220…480 V 208…480 VVoltage between phases and neutral. 120…277 V

Function performedFunction not performed

They monitor their own supply voltage, measured as a true rms value.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail

Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

DescriptionRM35 UB330 RM35 UB3N30

1a Voltage range selector switch (220, 380, 400, 415, 440 and 480 V).

1b Voltage range selector switch (120, 127, 220, 230, 240, 260 and 277 V).

2 Overvoltage setting potentiometer. >U3 Undervoltage setting potentiometer. <U4 Undervoltage threshold delay setting

potentiometer. Tt25 Overvoltage threshold delay setting

potentiometer. Tt16 Spring for clip-on mounting on 35 mm �

rail.

Un Green LED: indicates that supply to the relay is on.R1 Yellow LED: indicates relay output state. High voltage threshold.R2 Yellow LED: indicates relay output state. Low voltage threshold.

RM17 UB3101 Voltage range selector switch (208, 220,

380, 400, 415, 440 and 480 V).2 Time delay adjustment potentiometer. Tt3 Overvoltage setting potentiometer. >U4 Undervoltage setting potentiometer. <U5 Spring for clip-on mounting on 35 mm �

rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM17 UB310RM35 UB3���

1064

38

1056

64

L1

12 22 21 2411 14

L3L2

R1

Un

R2

1a2345

6

L1

12 22 21 2411 14

L3 NL2

R1

Un

R2

1b2345

6

5

L1 L2 L3

12 11 14

1234

Operation:pages 3/29 to 3/31

Characteristics:page 3/32

References, dimensions :page 3/33

3/29

3

Operation 3 Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Operating principle3-phase voltage control relays monitor: � Undervoltage and overvoltage:Un Phase/phase 208 V 220 V 380, 400, 415,

440 V480 V

RM17 UB310 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 10

< U (%) - 12…- 2 - 17…- 2 - 20…- 2 - 20…- 2RM35 UB30 > U (%) – + 2…+ 20 + 2…+ 20 + 2…+ 10

< U (%) – - 12…- 2 - 20…- 2 - 20…- 2

Un Phase/neutral 120 V 127 V 220, 230, 240, 260 V

277 V

RM35 UB3N30 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 20

< U (%) - 20…- 2 - 20…- 2 - 20…- 2 - 20…- 2

� Failure of one or more phases,� The presence of neutral (RM35 UB3N30 only).Measurements are made between Phases/Phases for the RM35 UB330 and the RM17 UB310 and between Phases/Neutral for the RM35 UB3N30.Fault signalling is by LED. RM35 UB relays allow differentiation on the source of the fault (one LED for high threshold, one LED for low threshold).

���� Voltage selector switch:� Set the switch to the 3-phase supply voltage Un.� The position of this switch is only taken into account on energisation of the device.� If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the voltage selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

Overvoltage/undervoltage control relays: RM35 UB330The relay monitors its own supply voltage Un:� The relay monitors:

- failure of at least one of the three phases (U measured < 0.7 x Un),- the undervoltage,- the overvoltage.

� Each threshold has its own independently adjustable time delay from 0.3 to 30 s.� In the event of a voltage fault, the corresponding relay (one undervoltage output / one overvoltage output) opens at the end of the time delay set by the user.� In the event of phase failure, both relays open instantly without waiting for the end of the time delay set by the user.� On energisation of the device with a fault measured, the relays stay open.

Function diagrams

� Functions: � Phase failure.

� Overvoltage and undervoltage.

Tt 1: overvoltage threshold delay (adjustable on front panel).Tt 2: undervoltage threshold delay (adjustable on front panel).

30 % Un 30 % Un30 % Un

Phase L3

Phase L2

Phase L1

Relays R1/R2

<U

>U

11-1211-14

21-2221-24

L1L2

L3

Tt1 Tt2

Phases L1/L2/L3

Relay R1

Relay R2

Hysteresis

Hysteresis

Presentation, description :page 3/28

Characteristics:page 3/32

References, dimensions :page 3/33

3/30

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Overvoltage/undervoltage + absence of neutral control relay: RM35 UB3N30The relay monitors its own supply voltage Un:� The relay monitors:

- the presence of neutral,- the undervoltage,- the overvoltage,- phase failure.

� Each threshold has its own independently adjustable time delay from 0.3 to 30 s.� In the event of a voltage fault, the corresponding relay (one undervoltage output / one overvoltage output) opens at the end of the time delay set by the user.� In the event of absence of neutral or phase, both relays open instantly without waiting for the end of the time delay set by the user.� On energisation of the device with a fault measured, the relays stay open.

Function diagrams

� Functions: � Phase failure.

� Overvoltage and undervoltage.

Tt 1: overvoltage threshold delay (adjustable on front panel).Tt 2: undervoltage threshold delay (adjustable on front panel).

30 % Un 30 % Un30 % Un

Phase L3

Phase L2

Phase L1

Relays R1/R2

<U

>U

11-1211-14

21-2221-24

L1L2

L3

Tt1 Tt2

Phases L1/L2/L3

Relay R1

Relay R2

Hysteresis

Hysteresis

Presentation, description :page 3/28

Characteristics:page 3/32

References, dimensions :page 3/33

3/31

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Overvoltage/undervoltage control relay: RM17 UB310The relay monitors its own supply voltage Un:� The relay monitors:

- the undervoltage,- the overvoltage,- phase failure.

� An adjustable time delay from 0.3 to 30 s allows inhibition of the output relay if a transient fault occurs.� In the event of a voltage fault, the relay opens at the end of the time delay set by the user.� On energisation of the device with a fault measured, the relay stays open.� In the event of phase failure, the relay opens instantly.

Function diagrams

� Functions: � Phase failure.

� Overvoltage and undervoltage.

Tt: overvoltage and undervoltage threshold delay (adjustable on front panel).

30 % Un 30 % Un30 % Un

Phase L3

Phase L2

Phase L1

Relays

11-12/11-14

<U

>U

L1L2

L3

Tt Tt

Phases L1/L2/L3

Relays

Hysteresis

Hysteresis

Presentation, description :page 3/28

Characteristics:page 3/32

References, dimensions :page 3/33

3/32

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 3/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-27 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to IEC 60664-1, 60255-5

> 500 MΩ, � 500 V

Rated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plasticPower ON indicator Green LED

Relay state indicator Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRelay type RM35 UB330 RM35 UB3N30 RM17 UB310

Rated supply voltage Un V � 3 x 220… 3 x 480 � 3 x 120… 3 x 277 � 3 x 208… 3 x 480Operating range V � 194…528 � 114…329 � 183…528 Frequency Of the power supply circuit 50/60 Hz ± 10 %

Galvanic isolation, supply/measurement NoMaximum power consumption VA ��2.9 ��3.9 ��1.8Immunity to microbreaks ms 50 5 80

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN61000-6-3IEC 61000-6-4IEC 61000-6-3

Input and measurement circuit characteristicsMeasurement range V � 194…528 � 114…329 � 183…528 Phase failure detection threshold V 194 114 183Frequency of the measured signal Hz 50…60 ± 15 % 50…60 ± 15 % 50…60 ± 10 %

Maximum measuring cycle ms 150/measurement as true rms valueFixed hysteresis 2 % UnSetting accuracy ± 10 % of the full scale value

Repeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole rangeMeasurement error with temperature variation 0.05 % / °C

Time delay characteristicsDelay on crossing the threshold s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 1 %Reset time ms 1500

Response time in the event of a fault ms < 200Delay on pick-up ms 500

Presentation, description :page 3/28

Operation:pages 3/29 to 3/31

References, dimensions :page 3/33

3/33

3

Characteristics (continued),

references,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

3-phase voltage control relays RM17 UB3 and RM35 UB3

Output characteristicsRelay type RM35 UB330 RM35 UB3N30 RM17 UB310

Output type 1 C/O + 1 C/O contacts 1 C/O contactContact type Cadmium-free

Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Maximum breaking current A �/� 5

Minimum breaking current mA 10/� 5 VMechanical durability 30 x 106 operating cyclesElectrical durability 1 x 104 operating cycles 1 x 105 operating cycles

Maximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferencesFunction Rated 3-phase

supply voltage Output Reference Weight

V kg� Overvoltage and

undervoltage between phases

� 220…480 (Phase-phase)

1 C/O+1 C/O1 per threshold5 A

RM35 UB330 0.130

� 208…480(Phase-phase)

1 C/O5 A

RM17 UB310 0.080

� Overvoltage and undervoltage between phases and neutral

� Absence of neutral

� 120…277 (Phase-neutral)

1 C/O+1 C/O1 per threshold5 A

RM35 UB3N30 0.130

DimensionsRM35 UB330, RM35 UB3N30 RM17 UB310

mm/In.

SchemesRM35 UB330 RM17 UB310 RM35 UB3N30

RM17 UB310RM35 UB330

1064

38

1056

64

RM35 UB3N30

1056

69

2,8

0.11

76/2.99

72,5/2.85

72/2.83

90/3

.54

35/1.38

2,8

0.11

76/2.99

72,5/2.85

72/2.83 17,50.69

90/3.54

L1 L2 L3

L1 L2

R1 R2

L3

1112 14 22 21 24

2111

12 14 2422

L1 L2 L3

L1 L2

R

L3

1112 14

11

12 14

L1 L2 L3 (N)

(N)L1 L2 L3

1112 14 22 21 24

2111

12 14 2422

R1 R2

Presentation, description :page 3/28

Operation:pages 3/29 to 3/31

Characteristics:page 3/32

3/34

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

Presentation Single-phase and d.c. voltage measurement and control relays RM17 UAS�� and RM17 UBE�� monitor:

RM17 UAS14 UAS15 UAS16 UBE15 UBE16

OvervoltageUndervoltageOvervoltage and undervoltage (window mode)Nominal voltages (V) � 12 �/�

110…240�/� 24…48

�/� 110…240

�/� 24…48

They allow selection of operating mode.They monitor their own supply voltage, measured as a true rms value.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail

Applications� Protection of electronic or electromechanical devices against overvoltage and undervoltage.� Normal/emergency power supply switching.

DescriptionRM17 UAS��������

1 Configuration: selection of operating mode <U / >U, (with or without memory). Memory - No Memory

2 Setting potentiometer3 Hysteresis adjustment potentiometer H4 Time delay setting potentiometer, Tt5 Spring for clip-on mounting on 35 mm� rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM17 UBE1����

1 Maximum voltage range selection and setting potentiometer.

2 Minimum voltage range selection and setting potentiometer.

3 Time delay setting potentiometer. Tt4 Spring for clip-on mounting on 35 mm � rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM17 UAS�� RM17 UBE��

1064

42

1064

44

Function performed

Function not performed

A1 A2

12 11 14

R

<U >U

Un

1234

5

12 11 14

R

Un

123

4

A1 A2

Operation:pages 3/35 and 3/36

Characteristics:pages 3/37 and 3/38

References:page 3/38

Dimensions, schemes :page 3/39

3/35

3

Operation 3 Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

Operating principleVoltage control relays RM17 UAS and RM17 UBE monitor: � The voltages of single-phase and d.c. supplies.

These products monitor their own supply voltage.

RM17 UAS�� relays give the user a choice of two operating modes: � Overvoltage or undervoltage,� Fault memory selected or not.

An adjustable time delay, on crossing the thresholds, provides immunity to transients, so preventing spurious triggering of the output relay.

Fault signalling is by LED.

Overvoltage or undervoltage control relays: RM17 UAS14, UAS15 and UAS16The operating mode is fixed by the user: A switch allows selection between the following modes:� Undervoltage with or without memory� Overvoltage with or without memory.

The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

The undervoltage or overvoltage threshold value is set by means of a graduated potentiometer clearly indicating the Un to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…20 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.If the voltage controlled exceeds the threshold setting for a time greater than that set on the front panel (0.1…10 s), the output relay opens and LED R goes out. As soon as the voltage returns to a value above (or below) the threshold setting minus (or respectively plus) the hysteresis, the relay instantly closes.

"Memory" modeIf "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position. The power must be switched off to reset the product.

Function diagrams

� Function: Undervoltage control. <U� without memory. No Memory

� with memory. Memory

11-12/11-14

U

U

Tt

<

Relays

Hysteresis

Supply Un

Threshold

Tt11-12/11-14

UU <

Relays

Hysteresis

Supply Un

Threshold

� Function: Overvoltage control. >U� without memory. No Memory

� with memory. Memory

Tt: time delay after crossing of threshold

11-12/11-14

U >

Tt

URelays

Threshold

Supply Un

Hysteresis

11-12/11-14

U >

U

TtRelays

Threshold

Supply Un

Hysteresis

Presentation, description :page 3/34

Characteristics:pages 3/37 and 3/38

References:page 3/38

Dimensions, schemes :page 3/39

3/36

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

Overvoltage and undervoltage control relays: RM17 UBE15 and UBE16Relays RM17 UBE operate in window mode: they check that the voltage controlled stays between a minimum threshold and a maximum threshold.

The undervoltage or overvoltage threshold values are set by means of two graduated potentiometers clearly indicating the Un to be monitored.

The hysteresis is fixed at: 3 % of the threshold setting.

If the voltage controlled exceeds the high threshold setting, or falls below the low threshold setting for a time greater than that set on the front panel (0.1…10 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage falls below the high threshold setting value minus the hysteresis, or rises above the low threshold setting value plus the hysteresis, the relay instantly closes.

On energisation of the device with a fault measured, the relay stays open.

Function diagrams

� Function: Control of overvoltage and undervoltage in window mode. <U<

Tt: time delay after crossing of threshold

11-12/11-14

Tt Tt

U

U >

U <

Relays

Hysteresis

Supply Un

ThresholdHysteresis

Threshold

Presentation, description :page 3/34

Characteristics:pages 3/37 and 3/38

References:page 3/38

Dimensions, schemes :page 3/39

3/37

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz

Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250 or 400

Insulation test voltageConforming to IEC 60664-1/60255-5

Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LED (flashes during the time delay on crossing the threshold)Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRelay type RM17 UAS14 RM17 UAS16

RM17 UBE16RM17 UAS15RM17 UBE15

Rated supply voltage Un V � 12 �/� 24…48 �/� 110…240Operating range V � 7…20 �/� 15…100 �/� 50… 270Setting range V � 9…15 �/� 20…80 �/� 65…260

Polarity on d.c. supply YesFrequency Of the power supply circuit Hz 50/60 Hz ± 10 %Galvanic isolation, supply/measurement No

Maximum power consumption at Un � 1 W � 1.6 W, � 3.9 VA � 1 W, � 3 VAImmunity to microbreaks ms 20 at 12 V 20

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Input and measurement circuit characteristicsFrequency of the measured signal Hz 50…60 ± 10 %

Maximum measuring cycle ms 250/measurement as true rms valueAdjustable hysteresis or fixed hysteresis RM17 UAS�� 5…20 % of the threshold setting

RM17 UBE�� 3 % of the fixed threshold setting

Setting accuracy 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole range

Measurement error with temperature variation 0.2 %/ °C

Time delay characteristicsTime delay on crossing the threshold s 0.1…10, 0 + 10 %Repeat accuracy (with constant parameters) ± 1 %

Reset time s 1.5Delay on pick-up ms � 500 / � 1000

Presentation, description :page 3/34

Operation:pages 3/35 and 3/36

References:page 3/38

Dimensions, schemes :page 3/39

3/38

3

Characteristics (continued),references 3

Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

Output characteristicsType of output 1 C/O contact

Contact type Cadmium-free

Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250

Minimum breaking current mA 10/ � 5 V

Maximum breaking current A �/� 5

Electrical durability 1 x 105 operating cycles

Mechanical durability 30 x 106 operating cycles

Maximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferencesFunction Ranges

controlledNominal voltage

Out-put

Reference Weight

V V kg

� Overvoltage or undervoltage

� 9…15 � 12 1 C/O5 A

RM17 UAS14 0.080

�/� 20…80 �/� 24…48 1 C/O5 A

RM17 UAS16 0.080

�/� 65…260 �/� 110…240 1 C/O5 A

RM17 UAS15 0.080

� Overvoltage and undervoltagein window mode

�/� 20…80 �/� 24…48 1 C/O5 A

RM17 UBE16 0.080

�/� 65…260 �/� 110…240 1 C/O5 A

RM17 UBE15 0.080

RM17 UAS14 RM17 UAS16 RM17 UAS15

1064

42

1064

41

1064

42

RM17 UBE16 RM17 UBE15

1064

44

1064

43

Presentation, description :page 3/34

Operation:pages 3/35 and 3/36

Characteristics:pages 3/37 and 3/38

Dimensions, schemes :page 3/39

3/39

3

Dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE

DimensionsRM17 UAS�������� RM17 UBE��������

mm/In.

SchemesRM17 UAS14 RM17 UAS16, RM17 UAS15, RM17 UBE��������

Application scheme

17,50.69

90/3.54

A1 A2

12 11 14

R

Un

72/2.83

2,8

0.11

76/2.99

72,5/2.85

72/2.83

2,8

0.11

76/2.99

72,5/2.8517,5

0.69

90

/3.5

4

A1 A2

12 11 14

A1 – A2 +

1112 14

A1

A2

11

12 14

R

1112 14

A1

A2

11

12 14

R

A1 + A2 –

111412

Q2

12

Q2

12

Q11/L1 2

3/L2 4

5/L3 6

Q4

RM17 U

A2

A1

To sensitive loads

Presentation, description :page 3/34

Operation:pages 3/35 and 3/36

Characteristics:pages 3/37 and 3/38

References:page 3/38

3/40

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Multifunction voltage control relays RM35 UA

Presentation Multifunction voltage control relays RM35 UA1�MW monitor both a.c. and d.c. voltages.� Automatic � or � recognition,� Measurement ranges from 0.05 V to 600 V,� Selection between overvoltage and undervoltage,� Measurement as true rms value,� Selectable memory function.

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relays are designed for clip-on mounting on � rail

Applications� d.c. motor overspeed control,� Battery monitoring,� Monitoring of a.c. or d.c. supplies,� Speed monitoring (with tacho-generator).

DescriptionRM35 UA11MW, UA12MW, UA13MW

1 Configuration: selection of operating mode <U / >U, (with or without memory) Memory - No Memory

2 Voltage threshold setting potentiometer. U Value

3 Hysteresis adjustment potentiometer. H4 Time delay setting potentiometer. Tt5 Spring for clip-on mounting on 35 mm � rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 UA1�MW

1056

78

5

A1

12 22 21 241411

A2 E3 E2 E1 M

Un

R

< U > U

1234

Operation:page 3/41

Characteristics:page 3/42

References, dimensions :page 3/43

3/41

3

Operation 3 Zelio Control - modular measurement and control relays 3

Multifunction voltage control relays RM35 UA

Operating principleControl relays RM35 UA1�MW are designed for the monitoring of a.c. or d.c. voltages.

They automatically recognise the form of the � or � (50 or 60 Hz) signal.

Fault signalling is by LED.

Overvoltage and undervoltage control relays: RM35 UA11MW, UA12MW and UA13MW � The operating mode is fixed by the user : A switch allows selection between the following modes: � Undervoltage with or without memory,� Overvoltage with or without memory.

The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

The undervoltage or overvoltage threshold value is set by means of a potentiometer graduated as a percentage of the scale value of Un to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.In overvoltage mode, if the voltage controlled exceeds the threshold setting for a time greater than that set on the front panel (0.3…30 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage drops below the value of the threshold setting, minus the hysteresis, the relay instantly closes. In undervoltage mode, if the voltage controlled falls below the threshold setting for a time greater than that set on the front panel (0.3…30 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage rises above the value of the threshold setting, plus the hysteresis, the relay instantly closes.

� "Memory" mode : If "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position.The power must be switched off to reset the product.

Function diagrams

� Function: Undervoltage control. < U� without memory. No Memory

� with memory. Memory

11-12/11-1421-22/21-24

U

U

Tt

<

Relays

Hysteresis

Supply Un

Threshold

11-12/11-1421-22/21-24

U

Tt

U <

Relays

Hysteresis

Supply Un

Threshold

� Function: Overvoltage control. > U� without memory. No Memory

� with memory. Memory

Tt: time delay after crossing of threshold (adjustable on front panel)

11-12/11-1421-22/21-24

U >

Tt

URelays

Hysteresis

Supply Un

Threshold

11-12/11-1421-22/21-24

U >

U

Tt

Relays

Hysteresis

Supply Un

Threshold

Presentation, description :page 3/40

Characteristics:page 3/42

References, dimensions :page 3/43

3/42

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Multifunction voltage control relays RM35 UA

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz

Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250 or greater (measured at 600 V)

Insulation test voltageConforming to IEC 60664-1/60255-5

Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LEDMounting positionwithout derating

In relation to normal vertical mounting plane

Any position

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4… 264Polarity on d.c. supply No

Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes

Maximum power consumption ��3.5 VA, ��0.6 WImmunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Input and measurement circuit characteristicsRelay type RM35 UA11MW RM35 UA12MW RM35 UA13MW

Measurement range V 0.05…5 1…100 15…600Sub-measurement range E1-M V 0.05…0.5 1…10 15…150

E2-M V 0.3…3 5…50 30…300E3-M V 0.5…5 10…100 60…600

Input resistance E1-M kΩ 5 22 150E2-M kΩ 30 110 300

E3-M kΩ 50 220 600

Frequency of the measured signal Hz 40…70 ± 10 %Maximum measuring cycle ms 30/measurement as true rms valueThreshold setting 10…100 % of the range

Adjustable hysteresis or fixed hysteresis 5…50 % of the threshold settingSetting accuracy 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %

Measurement error with voltage variation < 1 % / V over the whole rangeMeasurement error with temperature variation ± 0.05 % / °C

Presentation, description :page 3/40

Operation:page 3/41

References, dimensions :page 3/43

3/43

3

Characteristics (continued)

references,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Multifunction voltage control relays RM35 UA

Time delay characteristicsTime delay on crossing the threshold Tt s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 2 %Reset time s 1.5

Delay on pick-up ms 600

Output characteristicsType of output 2 C/O contactsContact type Cadmium-free

Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 V

Maximum breaking current A �/� 5Electrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cycles

Maximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferencesFunction Range

controlledSupply voltage

Output Reference Weight

V V kg

� Over-voltage or undervoltage

0.05…5 �/� 24…240 2 C/O5 A

RM35 UA11MW 0.130

1…100 �/� 24…240 2 C/O5 A

RM35 UA12MW 0.130

15…600 �/� 24…240 2 C/O5 A

RM35 UA13MW 0.130

Dimensions Application schemeRM35 UA1����MW Example: overspeed monitoring (undervoltage function)

mm/In.

SchemeRM35 UA1����MW

RM35 UA11MW

1056

78

RM35 UA12MW

1056

79

RM35 UA13MW

1056

80

90/3

.54

72/2.83

2,8

0.11

76/2.99

72,5/2.85

35/1.38

A1

12 22 21 241411

A2 E3 E2 E1 M

111412

212422

KM1

KM1

KM1

12

3

1 1

1

2

2

4

56

U1

W1

V1

M1 3

A1

A2

E2

M

RM35 UA12MW

N

Q1

1/L1

2

3/L2

4

5/L3

6

Q2

Q3 Q42

U

V

Overspeed StartOverspeed

Tacho-generator

Stop

A1 A2 E3 E2 E1 M

12 11 14 22 21 24

A1

A2

11

12 14

21

22 24

R

Presentation, description :page 3/40

Operation:page 3/41

Characteristics:page 3/42

3/44

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Current control relays RM17 JC

Presentation The control relay RM17 JC00MW is designed to monitor a.c. currents.

� Integrated current transformer,� Measurement range 2…20 A,� Choice of action on the output relay.

Control status is indicated by a LED.

The relay is designed for clip-on mounting on � rail

Applications� Monitoring of load state of motors and generators,� Monitoring of current drawn by a 3-phase motor,� Monitoring of heating or lighting circuits,� Monitoring of pump draining (undercurrent),� Monitoring of overtorque (crushers),� Monitoring of electromagnetic brakes or clutches.

DescriptionRM17 JC00MW

1 Overcurrent setting potentiometer.2 Spring for clip-on mounting on 35 mm � rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM17 JC00MW

1064

45

A1 Y1 A2

12 11 14

Un

R1

2

Operation:page 3/45

Characteristics:page 3/46

References, dimensions :page 3/47

3/45

3

Operation 3 Zelio Control - modular measurement and control relays 3

Current control relays RM17 JC

Operating principle� Control relay RM17 JC00MW is designed to monitor overcurrent.� It is equipped with an integrated current transformer

Fault signalling is by LED.

Current control relayRelay RM17 JC00MW controls overcurrent. The relay closes when the current exceeds the threshold setting on the front panel and opens when it drops below the threshold minus the hysteresis.When terminal Y1 is linked to A1 (+), the output is reversed. The relay opens when the current exceeds the threshold setting on the front panel and closes again when it drops below the hystereris value.

Function diagram

I>

I

Y1 A1

Y1 A1 11-1211-14

11-1211-14

Relays

Relays

Hysteresis

Supply Un

Presentation, description :page 3/44

Characteristics:page 3/46

References, dimensions :page 3/47

3/46

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Current control relays RM17 JC

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4Mounting positionwithout derating

In relation to normalvertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4…264

Polarity on d.c. supply YesVoltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit Hz 50/60 Hz ± 10 %

Galvanic isolation, supply/measurement YesMaximum power consumption VA 3 VA, 1 WImmunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3

Input and measurement circuit characteristicsMeasurement range A 2…20

Continuous overload at 25 °C A 100Non repetitive overload < 3 s at 25 °C A 300Frequency of the measured signal Hz 40…70 sinusoidal

Maximum measuring cycle ms 30, measured as true rms valueAdjustment of current threshold % 10…100 % of the rangeFixed hysteresis % 15 % of the threshold setting, fixed

Setting accuracy ± 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0,5 %Measurement error with voltage variation < 1 % / V over the whole range

Measurement error with temperature variation ± 0,05 % / °C

Time delay characteristicsTime delay in the event of a fault ms < 200

Delay on pick-up ms 500

Output characteristicsOutput type 1 C/O contact

Contact type Cadmium-freeNominal current A 5Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250Minimum breaking current mA 10 / � 5 VElectrical durability 1 x 105 operating cycles

Mechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

Presentation, description :page 3/44

Operation:page 3/45

References, dimensions :page 3/47

3/47

3

Reference,dimensions,scheme 3

Zelio Control - modular measurement and control relays 3

Current control relays RM17 JC

ReferenceFunction Supply Measure-

ment range

Output Reference Weight

V A kg� Overcurrent �/� 24…240 2…20 1 C/O

5 ARM17 JC00MW 0,110

DimensionsRM17 JC00MW

mm/In.

SchemeRM17 JC00MW

RM17 JC00MW

1064

45

97/3.82 17,50.69

90/3

.54

2,8

0.11

101/3.98

97,5/3.84

10/0.39

12 1411

11

12 14

A1 A2Y1

RI>

Presentation, description :page 3/44

Operation:page 3/45

Characteristics:page 3/46

3/48

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Current control relays RM35 JA

Presentation Multifunction current control relays RM35 JA3�MW monitor both a.c. and d.c. currents.� Automatic � or � recognition,� Measurement ranges from 2 mA to 15 A, � Selection between overcurrent and undercurrent,� Measurement as true rms value,� Selectable memory function.

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relays are designed for clip-on mounting on � rail

Applications� Excitation control of d.c. machines,� Control of load state of motors and generators,� Control of current drawn by a 3-phase motor,� Monitoring of heating or lighting circuits,� Control of pump draining (undercurrent),� Control of overtorque (crushers),� Monitoring of electromagnetic brakes or clutches.

DescriptionRM35 JA31MW, RM35 JA32MW

1 Configuration: selection of operating mode <I / >I, (with or without memory) Memory - No Memory.

2 Current threshold setting potentiometer. I %

3 Hysteresis adjustment potentiometer. Hysteresis

4 Time delay adjustment potentiometer. Tt5 Starting inhibit time delay adjustment

potentiometer. Ti6 Spring for clip-on mounting on 35 mm �

rail.

Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 JA3�MW

1056

82

A1

12 22 21 241411

A2 E3 E2 E1 M

< I > I

UnR

6

12345

Operation:page 3/49

Characteristics:page 3/50

References, dimensions :page 3/51

3/49

3

Operation 3 Zelio Control - modular measurement and control relays 3

Current control relays RM35 JA

Operating principleControl relays RM35 JA3�MW are designed for the monitor of a.c. or d.c. currents.

They automatically recognise the form of the � or � (50 or 60 Hz) signal and can provide direct monitor up to 15 A. Above this value, a current transformer can be connected.

Fault signalling is by LED.

a.c. or d.c. current control relays: RM35 JA31MW and JA32MWThe operating mode is fixed by the user: A switch allows selection between the following modes: � Undercurrent, with or without memory,� Overcurrent, with or without memory.The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

The undercurrent or overcurrent threshold value is set by means of a potentiometer graduated as a percentage of the scale value of I to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.In overcurrent (undercurrent) mode, if the current exceeds (falls below) the threshold setting for a time greater than that set on the front panel (0.3…30 s), the relays open and the LED goes out.As soon as the current returns to below (above) the threshold minus (plus) hysteresis, the relay instantly closes again.

"Memory" mode: If "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position.The power must be switched off to reset the product.

On energisation, an inhibit time delay (1…20 s) makes it possible to inhibit current peaks (or troughs) on start-up of equipment.

Function diagrams

� Function: Undercurrent detection. < I� without memory. No Memory

� with memory. Memory

11-12/11-1421-22/21-24

TiTt Tt Ti

II <

Relays

Hysteresis

Supply Un

Threshold

11-12/11-1421-22/21-24

Ti Ti

II <

Tt Tt

Relays

Hysteresis

Supply Un

Threshold

� Function: Overcurrent detection. > I� without memory. No Memory

� with memory. Memory

Ti: starting inhibit time (adjustable on front panel)Tt: time delay after crossing of threshold (adjustable on front panel)

11-12/11-1421-22/21-24

Tt Tt TiTi

I

I >

Relays

Hysteresis

Supply Un

Threshold

11-12/11-1421-22/21-24

Ti Tt Ti

II >

Tt

Relays

Hysteresis

Supply Un

Threshold

Presentation, description :page 3/48

Characteristics:page 3/50

References, dimensions :page 3/51

3/50

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Current control relays RM35 JA

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250Insulation test voltageTo IEC 60664-1/60255-5

Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4 (1.2/50 µs)ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LEDMounting positionwithout derating

In relation to normal vertical mounting plane

Any position

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4… 264Polarity on d.c. supply No

Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes

Maximum power consumption ��3.5 VA, ��0.6 WImmunity to microbreaks ms 50

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3

Measurement circuit and input characteristicsRelay type RM35 JA31MW RM35 JA32MW

Measurement range 2…500 mA 0.15…15 ASub-measurement range E1-M 2…20 mA 0.15…1.5 A

E2-M 10…100 mA 0.5…5 A

E3-M 50…500 mA 1.5…15 AInput resistance E1-M Ω 5 0.05

E2-M Ω 1 0.015

E3-M Ω 0.2 0.005Frequency of the measured signal Hz 40…70 ± 10 %Maximum measuring cycle ms 30/measurement as true rms value

Threshold setting 10…100 % of the rangeAdjustable hysteresis 5…50 % of the threshold settingSetting accuracy ± 10 % of the full scale value

Repeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation 1 % / V over the whole rangeMeasurement error with temperature variation 0.05 % / °C

Time delay characteristicsTime delay on energisation Ti s 1…20, 0 + 10 %Time delay on crossing the threshold Tt s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 2 %

Reset time s 1.5Delay on pick-up ms 300

Presentation, description :page 3/48

Operation:page 3/49

References, dimensions :page 3/51

3/51

3

Characteristics (continued),

references,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Current control relays RM35 JA

Output characteristicsType of output 2 C/O contactsContact type Cadmium-freeMaximum switching voltage V �/� 250

Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 VMaximum breaking current A �/� 5

Electrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferencesFunction Range

controlledSupply Output Reference Weight

V kg� Overcurrent or

undercurrent2 …500 mA �/� 24…240 2 C/O

5 ARM35 JA31MW 0.130

0.15…15 A �/� 24…240 2 C/O5 A

RM35 JA32MW 0.130

Dimensions SchemeRM35 JA3����MW RM35 JA3����MW

mm/In.

Application schemesExample: detection of jamming on a crusher (overcurrent function)

Current measured ���� 15 A Current measured > 15 A

RM35 JA31MW

1056

82

RM35 JA32MW

1056

83

72/2.83

2,8

0.11

76/2.9972,5/2.85

90/3

.54

35/1.38

A1

12 22 21 241411

A2 E3 E2 E1 M A1 A2 E3 E2 E1 M

12 11 14 22 21 24

A1

A2

11

12 14

21

22 24

R

111412

212422

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

E3

M

A1

A2

RM35 JA3

N

StartOK

Stop

111412

212422

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

E3

M

A1

A2

RM35 JA3

N

StartOK

Stop

Presentation, description :page 3/48

Operation:page 3/49

Characteristics:page 3/50

3/52

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Presentation Level control relays RM35 LM33MW and RM35 LV14MW control one or two levels, with fill or empty function:� RM35 LM33MW: control by resistive level probe,� RM35 LV14MW: control by discrete sensor.

Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail

ApplicationsThese devices monitor the levels of conductive liquid or non-conductive material.They control the actuation of pumps or valves to regulate levels. They are also suitable for protecting submersible pumps against dry running, or protecting tanks from "overflow". They can also be used to control dosing of liquids in mixing processes and to protect heating elements in the event of non immersion.They have a transparent, hinged cover on their front panel to avoid any accidental alteration of the settings. This cover can be directly sealed.

� Application examples for RM35 LM33MW:� spring, town, industrial and sea water,� metallic salt, acid or base solutions,� liquid fertilizers,� non concentrated alcohol (< 40 %),� liquids in the food-processing industry: milk, beer, coffee, etc.

� Application examples for RM35 LV14MW:� chemically pure water,� fuels, liquid gasses (inflammable),� oil, concentrated alcohol (> 40 %),� ethylene, glycol, paraffin, varnish and paints.

DescriptionRM35 LM33MW

1 Configuration: selection of operating mode: / and of sensitivity range. LS, St, HS.

2 Sensitivity adjustment potentiometer. %3 Switch for selecting the number of levels. 4 Time delay adjustment potentiometer. Tt5 Spring for clip-on mounting on 35 mm � rail.

RM35 LV14MW1 Configuration: selection of operating

mode: / and of sensor type PNP, NPN.

2 Time delay adjustment potentiometer. Tt 3 Switch for selecting the number of levels.4 Spring for clip-on mounting on 35 mm � rail.

Tt Yellow LED: indicates timing status.Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 L���MW

1056

85

A1

12 22 21 2411 14

A2 Min Max C

Tt

Un

R

5

1234

12V

A1 12 11 14A2

12V Min Max 0V

TtUn

R

4

123

Operation:pages 3/53 to 3/55

Characteristics:pages 3/56 and 3/57

References, dimensions :page 3/57

3/53

3

Operation 3 Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Operating principleControl relays RM35 LM and RM35 LV are designed to control levels of: � Conductive liquid for RM35 LM,� Any other material for RM35 LV.

Relay RM35 LM measures the levels by means of resistive probes.Relay RM35 LM controls the levels of conductive liquids.The operating principle is based on measurement of the apparent resistance of the liquid between two submerged probes. When this value is less than the threshold setting on the front panel of the device, the relay changes state. To avoid electrolytic phenomena, an a.c. current runs across the probes. A selector switch on the front panel allows selection of the required function and sensitivity range. Control of one single level can be achieved by using the 2nd selector switch.In this case, the Max level probe stays up in the air and an adjustable time delay avoids any wave effect.

Relay RM35 LV measures the levels by means of discrete sensors.

These two products activate their output relay when a tank is either emptying or filling.

A green LED indicates that the supply is ON.A yellow LED indicates the state of the output relay.A yellow LED indicates that timing is in progress.The green and yellow LEDs flash to indicate an unacceptable setting position.

Level control relay: RM35 LM33MWConfiguration

A selector switch on the front panel allows selection of the required sensitivity range and of the empty or fill function.A second switch allows selection of the number of levels (1 or 2) and the type of time delay in the case of 1 level mode.The configuration of these switches is taken into account on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

Function diagram ���� Control of two levels� Fill/Empty function

� empty functionlevel: 2, function:

- LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

The output relay stays open until the liquid reaches the Max. level probe. As soon as the Max. level is reached, the contact closes and then allows emptying of the tank (valve opens, pump starts, ...). When the level drops below the Min. level, the contact opens to stop the emptying process.

Note: When two levels are controlled, the anti-wave time delay function is not active.

� fill functionlevel: 2, function:

- LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

The output relay stays energised until the liquid reaches the Max. level probe. As soon as the Max. level is reached, the contact opens and the pump stops. When the level drops below the Min. level, the contact closes again and pumping re-starts to raise the level.

Note: When two levels are controlled, the anti-wave time delay function is not active.

11-12/11-1421-22/21-24

11-12/11-1421-22/21-24

Supply Un

Relays

Relays

Max. level

Min. level

Presentation, description :page 3/52

Characteristics:pages 3/56 and 3/57

References, dimensions :page 3/57

3/54

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Level control relay: RM35 LM33MW (continued)Configuration (continued)

Function diagrams ���� Control of one level, empty function� Empty function T on � level: 1 - on delay functions:

- LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

When the liquid level rises above the probe for a time greater than the time delay value Tt set on the front panel, the relay is energised and stays energised until the liquid level drops back down to the probe. If the liquid drops back down to below the set level before the end of the time delay, the relay does not energise.

� Empty function T off � level: 1 - off delay functions: - LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

When the liquid level rises above the probe, the relay instantly energises and stays energised until the liquid again reaches the probe level for a time Tt set on the front panel. If the liquid drops back down to below the set level before the end of the time delay period, the relay stays energised.

���� Control of one level, fill function� Fill function T on � level: 1 - on delay functions:

- LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

When the liquid level drops below the probe for a time greater than the time delay value Tt set on the front panel, the relay is energised and stays energised until the liquid level rises back up to the probe. If the liquid rises back up to above the set level before the end of the time delay period, the relay does not energise.

� Fill function T off � level: 1 - off delay functions: - LS (Low Sensitivity: 250 Ω…5 kΩ), - St (Standard Sensitivity: 5 kΩ…100 kΩ), - HS (High Sensitivity: 50 kΩ…1 MΩ).

When the liquid level drops below the probe, the relay instantly energises and stays energised until the liquid level again reaches the probe level and stays above it for a time greater than the time delay period Tt set on the front panel. If the liquid drops back down to below the set level before the end of the time delay period, the relay stays energised.

11-12/11-1421-22/21-24

Tt Tt Tt

Supply Un

Relays

Level

11-12/11-1421-22/21-24

Tt Tt Tt Tt

Supply Un

Relays

Level

11-12/11-1421-22/21-24

Tt Tt Tt

Supply Un

Relays

Level

11-12/11-1421-22/21-24

Tt Tt Tt

Supply Un

Relays

Level

Presentation, description :page 3/52

Characteristics:pages 3/56 and 3/57

References, dimensions :page 3/57

3/55

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Level control relay: RM35 LV14MWConfiguration

A selector switch on the front panel allows selection of the function (empty or fill) and the type of sensor.A second switch allows selection of the number of levels (1 or 2) and the type of time delay in the case of 1 level mode.

The configuration of these switches is taken into account on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

Function diagram ���� Control of two levels��Fill/Empty function

� empty function. Level: 2The output relay stays open until the material level reaches the Max. probe. As soon as the Max. level is reached, the contact closes and then allows emptying of the tank (valve opens, pump starts, ...). When the level drops below the Min. probe, the contact opens to stop the emptying process.

� fill function. Level: 2The output relay stays energised until the material level reaches the Max. probe. As soon as the Max. level is reached, the contact opens and the pump stops. When the level drops below the Min. probe, the contact closes again and pumping re-starts to raise the level.

Note: When two levels are controlled, the anti-wave time delay function is not active.

Function diagrams ���� Control of one level, empty function��Empty function T on � level: 1 - on delay

When the material level rises above the probe for a time greater than the time delay value Tt set on the front panel, the relay is energised and stays energised until the material level drops back down to the probe. If the level rises above the probe before the end of the time delay period, the relay does not energise.

��Empty function T off � level: 1 - off delay When the material level rises above the probe, the relay instantly energises and stays energised until the material level again reaches the probe and stays below it for a time greater than the time delay value Tt set on the front panel. If the level drops back down to below the probe before the end of the time delay period, the relay stays energised.

��Fill function T on ���� Control of one level, fill function� level: 1 - on delayWhen the material level drops below the probe for a time greater than the time delay value Tt set on the front panel, the relay is energised and stays energised until the material level again reaches the probe. If the level rises above the probe before the end of the time delay period, the relay does not energise.

� Fill function T off � level: 1 - off delay When the material level drops below the probe, the relay instantly energises and stays energised until the material level again reaches the probe and stays above it for a time greater than the time delay period Tt set on the front panel. If the level drops back down to below the probe before the end of the time delay period, the relay stays energised.

11-12/11-14

11-12/11-14

Supply Un

Relays

Relays

Max. level

Min. level

11-12/11-14

Tt Tt Tt

Supply Un

Relays

Level

11-12/11-14

Tt Tt Tt Tt

Supply Un

Relays

Level

11-12/11-14

Tt Tt Tt

Supply Un

Relays

Level

11-12/11-14

Tt Tt Tt

Supply Un

Relays

Level

Presentation, description :page 3/52

Characteristics:pages 3/56 and 3/57

References, dimensions :page 3/57

3/56

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz

Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250

Insulation test voltageConforming to IEC 60664-1/60255-5

Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LEDTiming indicator Yellow LED

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

Mounting Conforming to IEC/EN 60715 On � rail

Supply characteristicsSupply voltage Un V �/� 24…240Operating range V �/� 20.4…264

Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes

Maximum power consumption at Un VA ��5W � 1.5

Immunity to microbreaks ms � 90, � 100

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 2002 / IEC 61000-6-2

Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3

Measurement circuit and input characteristicsRelay type RM35 LM33MW RM35 LV14MW

Measurement range 250 Ω…1 MΩ –Sub-measurement range LS 250 Ω…5 kΩ –

St 5 kΩ…100 kΩ –HS 50 kΩ…1 MΩ –

Sensitivity adjustment 5…100 % of the range –

Setting accuracy ± 10 % of the full scale / ± 20 % for the HS rangeMeasurement error with temperature variation 0.5 % / °CMaximum voltage at the probe terminals V 12

Maximum current across the probes mA < 1 40Maximum probe cable length m 100 100Maximum capacity of probe cable nF 1 for LS, 2.2 for St and 4.7 pour HS 10

Delay on pick-up ms 600 500

Presentation, description :page 3/52

Operation:pages 3/53 to 3/55

References, dimensions :page 3/57

3/57

3

Characteristics (continued)

references,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Level control relays RM35 L

Time delay characteristicsRelay type RM35 LM33MW RM35 LV14MW

Time delay on crossing the threshold s 0.1…5, 0 + 10 %Repeat accuracy (with constant parameters) ± 2 %

Reset time s 1.75 4 if 1 line broken / 1 if 2 lines broken

Output characteristicsType of output 2 C/O contacts 1 C/O contactContact type Cadmium-free

Nominal current A 5Maximum switching voltage V �/� 250Rated breaking capacity VA 1250

Minimum breaking current mA 10/ � 5 VMaximum breaking current A �/� 5Electrical durability 1 x 105 operating cycles

Mechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

ReferencesFunction Supply

voltageOutput Reference Weight

V kgDetection by resistive probes(see page 3/58)

�/� 24…240 2 C/O5 A

RM35 LM33MW 0.130

Detection by discrete sensors(see page 3/60, references XX5 12A������������)

�/� 24…240 1 C/O5 A

RM35 LV14MW 0.130

Dimensions SchemesRM35 LM33MW, RM35 LV14MW RM35 LM33MW RM35 LV14MW

mm/In.

RM35 LM33MW RM35 LV14MW

1056

85

1056

86

/0954.3

35/1.38

2,8

0.11

76/2.99

72,5/2.85

72/2.83

1112 14 22 21 24

2111

12 14 2422

A1 A2 CMin Max

A1

A2

1112 14

11

12 14

A1 A2

0VMin Max12VNC 12V

A1

A2

Presentation, description :page 3/52

Operation:pages 3/53 to 3/55

Characteristics:pages 3/56 and 3/57

3/58

3

References 3 Zelio Control - modular measurement and control relays 3

Electrode holders and probes

ProbesApplication No.

of probes

Length Opera-ting temper-ature

Maximum pressure

Reference Weight

mm °C kg/cm2 kgRecommendedfor drinks vending machines and where installation space is limited(Stainless steel)

3 1000 80 2 RM 79 696 044 0.800

Suitable for boilers, pressure vessels and under high temperature conditions (1)(304 stainless steel)

1 1000 200 25 RM 79 696 014 0.360

Description Material Reference Weightkg

Protected probefor mounting by suspension

Protective shellPUC (S7)Electrode : stainless steel

RM 79 696 043 0.150

Description Type ofinstallation

Maximum operating temperature

Reference Weight

°C kgLiquid levelcontrol probe

Suspended by cable

100 LA9 RM201 0.100

Electrode holdersDescription Material Reference Weight

kgElectrode for use up to 350 °Cand 15 kg/cm2 (2)

Stainless steel isolated by ceramic

RM 79 696 006 0.150

(1) 3/8" BSP mounting thread with hexagonal head. Use a 24 mm spanner for tightening.(2) 3/8" BSP mounting thread.

RM 79 696 043

5610

34

LA9 RM201

RM 79 696 006

5610

35

5610

36

Dimensions :page 3/59

3/59

3

Dimensions 3 Zelio Control - modular measurement and control relays 3

Electrode holders and probes

ProbesRM 79 696 044

38,5

32

7

3

14

26

Ø 27,5

Ø 1112

11

100

PF 1/2

RM 79 696 014

60

Ø6

1000 60

G 3/8A

RM 79 696 043

Ø 2

5

80

LA9 RM201

150

16

Electrode holderRM 79 696 006

46 29

84

6,5

49

20,7

13

9,5

Acr

oss

flats

1/4

whi

t

5/32

whi

t

3/8 tapered NPT

References :page 3/58

3/60

3

References 3 Ultrasonic sensors 3

Osisonic®, Optimum and Universal (1)Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output

Optimum sensorsSensors Sensing

distance (Sn)m

Function Output Reference Weight

kgØ 12 0.05 NO PNP/NPN XX5 12A1KAM8 (1) 0.011

0.10 NO NPN XX5 12A2NAM8 (1) 0.011

PNP XX5 12A2PAM8 (1) 0.011Ø 18 0.15 NO PNP/NPN XX5 18A1KAM12 0.033

Universal sensorsØ 18 0.50 (adjustable) NO NPN XX5 18A3NAM12 0.033

PNP XX5 18A3PAM12 0.033Ø 30 1 (adjustable) NO PNP/NPN XX6 30A1KAM12 0.091

NO + NC NPN XX6 30A1NCM12 (2) 0.091PNP XX6 30A1PCM12 (2) 0.091

8 (adjustable) NO + NC NPN XX6 30A3NCM12 0.110

PNP XX6 30A3PCM12 0.110

AccessoriesTeach mode pushbuttonTeach mode pushbutton For use with

sensorsReference Weight

kgSelection of detection windowInput: M12 female connectorOutput: M12 male connector

XX5 18A3�AM12and XX7 V1A1�AM12

XXZ PB100 0.035

Cabling accessories (4-wire output) (3)Connectors

For use withsensor

Type Reference Weightkg

M8 Ø 12 Connection by in-line IDC

Straight XZ CC8FDM40V 0.010

Elbowed XZ CC8FCM40V 0.010Connection to solder terminals

Straight XZ CC8FDM40S 0.010Elbowed XZ CC8FCM40S 0.010

M12 Ø 18, Ø 30 Metalclamping ring

Straight XZ CC12FDM40B 0.020Elbowed XZ CC12FCM40B 0.020

Plasticclamping ring

Straight XZ CC12FDP40B 0.020

Elbowed XZ CC12FCP40B 0.020Pre-wired connectors

For use withsensor

Type Lengthm

Reference Weightkg

M8 Ø 12 Straight 2 XZ CP0166L2 0.0805 XZ CP0166L5 0.180

10 XZ CP0166L10 0.360Elbowed 2 XZ CP0266L2 0.080

5 XZ CP0266L5 0.180

10 XZ CP0266L10 0.360M12 Ø 18, Ø 30 Straight 2 XZ CP1141L2 0.090

5 XZ CP1141L5 0.190

10 XZ CP1141L10 0.370Elbowed 2 XZ CP1241L2 0.090

5 XZ CP1241L5 0.190

10 XZ CP1241L10 0.370

Fixing accessoriesDescription For use with

sensorReference Weight

kgFixing clamps Ø 12 XSZ B112 0.006

Ø 18 XSZ B118 0.01090° fixing bracket Ø 12 XXZ 12 0.025

Ø 18 XUZ A118 0.038Ø 30 XXZ 30 0.115

3D fixing kit(4)

M12 rod Ø 12, Ø 18 and Ø 30 XUZ 2001 0.050Support for M12 rod

Ø 12, Ø 18 and Ø 30 XUZ 2003 0.160

Ball-joint mounted fixing bracket

Ø 12 XUZ B2012 0.175Ø 18 XUZ B2003 0.175

Ø 30 XUZ B2030 0.160(1) Accessories recommended for RM35 LV14MW control relays.(2) Sensor available with stainless steel 303 case. To order, replace the 1st letter A by the letter S.(3) For 3-wire cabling accessories, refer to the Global Detection catalogue.(4) To obtain a 3D fixing kit, order:

rod support XUZ 2003, M12 rod XUZ 2001 and ball-joint mounted fixing bracket XUZ B20��������.

XX5�18A1KAM12

5664

547

5645

31

XX6�30A1KAM12XX6�30A3�CM12

XX5�18A3�AM12

5327

13

5645

33

XXZ PB100

5645

30

5645

3456

4535

XSZ B11�

5645

32

XUZ A118

XUZ 2003

XUZ 2001 B20XUZ

5325

17

3D fixing kit example

Characteristics:page 3/61

Dimensions:page 3/62

Schemes:page 3/63

XX5�12A1KAM8

XZ�CC12FD�40B

XZ�CP1041L�

5645

4653

2243

3/61

3

Characteristics, setting-up

3

Ultrasonic sensors 3

Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output

Sensor type XX5 12A1����������������

XX5 12A2����������������

XX5 18A1����������������

XX5 18A3����������������

XX6 30A1����������������

XX6 30A3����������������

CharacteristicsProduct certifications �

Conformity to standards IEC 60947-5-2, UL508 pending and CSA C22-2 n° 14 pendingConnection Connector M8 - 4-pin M8 - 3-pin M12 - 4-pin

Sensing range mm 6.4…51 6.4…102 19…152 51…508 51…991 203…8000Nominal sensing distance (Sn) m 0.05 0.1 0.15 0.50 1 8Operating distance mm 6.4…51

Fixed6.4…102 Fixed

25…152 Fixed

Adjustable using teach mode

Differential travel mm < 0.7 < 0.7 < 0.35 < 2.5 < 2.5 < 12.7

Blind zone (no object must pass through this zone whilst the sensor is operating)

mm 0…6.4 0…6.4 0…19 0…51 0…51 0…203

Transmission frequency kHz 500 300 200 75Repeat accuracy mm ± 0.7 ± 1.27 ± 0.9 ± 2.54Overall beam angle (see detection lobe) 11° 10° 8° 6° 10° 16°

Minimum size of object to be detected Cylinder Ø 2.5 mm or flat bar 1 mm wide

Cylinder Ø 1.6 mm

Cylinder Ø 2.5 mm up to a sensing distance of 150 mm

Cylinder Ø 1.6 mm up to a sensing distance of 635 mm

Cylinder Ø 50.8 mm up to a sensing distance of 4732 mm

Degree of protection Conforming to IEC 60529and IEC 60947-5-2

IP 67 IP 65

Storage temperature °C - 40…+ 80

Operating temperature °C - 20…+ 65 0…+ 50 - 20…+ 65 0…+ 60 - 20…+ 60Materials Case ULTEM® Valox® ULTEM®

Sensing face Epoxy Silicone Epoxy Silicone Epoxy

Vibration resistance To IEC 60068-2-6 Amplitude ± 1 mm (f = 10…55 Hz)Mechanical shock resistance To IEC 60068-2-27 30 gn, duration 11 ms, in all 3 axesResistance to electromagnetic interferenceElectrostatic discharges To IEC 61000-4-2 kV 8, level 4Radiated electromagnetic fields To IEC 61000-4-3 V/m 10, level 3Fast transients To IEC 61000-4-4 kV 1, level 3

LED indicators Output state Yellow LED, rear

Yellow LED – Yellow LED Yellow LED, rear

Yellow LED, rear

Power on Green LED, rear

Green LED – Green LED

– –

Setting-up assistance – – – Dual colour Multicolour LED, rearRated supply voltage V � 12…24 V with protection against reverse polarityVoltage limits (including ripple) V � 10…28 V

Current consumption, no-load mA 25 60 40 50Switching capacity mA < 100 (PNP and NPN) with overload and short-circuit protectionVoltage drop V < 1 (PNP and NPN)

Maximum switching frequency Hz 125 125 80 40 10 2Delays First-up ms 20 20 350 100 720 800

Response ms 2 3 3 10 20 200

Recovery ms 2 3 3 10 20 200Deviation angle from 90° of the object to be detected

± 10° ± 10° ± 10° ± 7° ± 7° ± 5°

Setting-up precautionsMinimum mounting distancesSide by side Face to face

e: respect the distances indicated on the detection curves shown on page 3/63.

e = 4 x Sn max.

ee

Reference:page 3/60

Dimensions:page 3/62

Schemes:page 3/63

3/62

3

Dimensions 3 Ultrasonic sensors 3

Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output

DimensionsXX5 12A��������AM8 XX5 18A1KAM12 XX5 18A3�AM12

XXZ PB100 XX6 30A1KAM12 XX6 30A3����CM12

(1) Cable, length: 152.4 mm.

AccessoriesXUZ A118 XXZ 12, XXZ 30

90° fixing bracket (Ø 18) 90° fixing bracket (Ø 12 and Ø 30)

XXZ a b c c1 e H G G1 Ø Ø112 35 40 33 18 2 31 18 18 25 1330 67 65 52 25 3 51 35 33 50 31

XSZ B112, XSZ B118 XUZ 2001 XUZ 2003Fixing clamps (Ø 12 and Ø 18) M12 rod Support for M12 rod

XSZ a a1 b b1 b2 ØB112 21.9 14.5 16 15.5 8.5 12

B118 26 15.7 22.3 20.1 11.5 18(1) 2 elongated holes Ø 4 x 8.XUZ B2012 XUZ B2003 XUZ 2030

Ball-joint mounted fixing bracket (Ø 12) Ball-joint mounted fixing bracket (Ø 18) Ball-joint mounted fixing bracket (Ø 30)

M12x1

50

38

65

51

M18x1 M18x1

77,7

43 4,7

63

1614,5

(1) M12x1

20

85

45 20

M30x1,5

117,35

42,164,3

M30x1,5

Ø43

,2

2,5 Ø18,2

35

28

1

15

206,5

6,5

=

10

=

16,5

= =

50

a

10Ø5Ø1

G1 Ø

G

H

c1

c

e

b

4 822,3

(1)

38,3

b

b2

a

3,5

b1

a1

126

5055

132

40 23

40

M12

1,9

12

19

53

36

1919

5,7

22,9

40

33

36

76,5

M4

Ø12,4

67

5,7

22,9

40

33

36

76,5

M4

Ø18,5

67

6

22,9

46,324

,1

42,2

90,5

M3

81,7

13

Ø30,5

3/63

3

Curves, schemes 3

Ultrasonic sensors 3

Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output

Detection curvesXX5 12A1KAM8 XX5 12A2����NAM8 XX5 18A1KAM12 XX5 18A3����AM12

XX6 30A1����CM12 XX6 30A3����CM12

Blind zone

Wiring schemesM8 connectorXX5 12A1KAM8 XX5 12A2����

4-wire type NO outputs, PNP and NPN 3-wire type NO outputs, NPN NO outputs, PNP

1 (+) 2 PNP output3 (-) 4 NPN output

(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)

1 (+) 3 (-)4 NPN or PNP output

(-) BU (Blue) (+) BN (Brown)BK (Black)

M12 connectorXX5 18A1KAM12 XX5 18A3����

4-wire type NO outputs, PNP and NPN 3-wire type NO outputs, NPN NO outputs, PNP

1 (+) 2 PNP output3 (-) 4 NPN output

(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)

1 (+) 3 (-)4 NPN or PNP output

(-) BU (Blue) (+) BN (Brown)BK (Black)

XX6 30A1KAM12 XX6 30A��������CM124-wire type NO outputs, PNP and NPN NO + NC outputs, NPN NO + NC outputs, PNP

1 (+) 2 PNP output3 (-) 4 NPN output

(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)

(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)

XXZ PB100 (teach mode pushbutton for XX5 18A3�AM12)

1 (+) BN (Brown) 2 WH (White)3 (-) BU (Blue) 4 BK (Black)

0 10 20 30 40 50 60

-20

-30

-10

10

20

30mm

mm cm2 4 6 8 100

10

-10

20

30

-20

-30

mm

100 150 200500mm

40

-40

80

120

-80

-120

mm

65 190 320 445 570mm

0

mm

100

-100

200

300

-200

-300

20 40 60 80 100cm

0

100

-100

200

300

400

-200

-300

-400

mm

2 4 6 8 m0

100

-100

200

300

400

-200

-300

-400

cm

4

3

2

12/WH

3/BU

4/BK

1/BN

NPNPNP

4

1 3 3/BU

4/BK

1/BN

NPN4/BK

3/BU

1/BN

PNP

3

2

4

12/WH

3/BU

4/BK

1/BN

NPNPNP

3

2

4

13/BU

4/BK

1/BN

NPN4/BK

3/BU

1/BN

PNP

3

2

4

12/WH

3/BU

4/BK

1/BN

NPNPNP

3/BU

2/WH 4/BK

1/BN

NPN NC

NO3/BU

2/WH

4/BK

1/BN

NPN NC

NO

4

41

13

3

4

1

32

24

1

3

Sensor side

M12 male connector

M12 female connector

OutputXXZ PB100

3/BU

1/BN 1/BN

NO2/WH

4/BK

3/BU

4/BK

XX5 18A3 XXZ PB100

3/64

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

PresentationMeasurement and control relay RM35 BA10 is used for control and monitoring of 3-phase and single-phase pumps.It monitors:� The sequence of phases L1, L2 and L3.� The absence of one or more phases,� Undercurrent for protection against running empty,� Overcurrent for protection against overload.

This control relay accepts different nominal voltage values:� � 208… 480 V in 3-phase mode,� � 230 V in single-phase mode.

It is self-powered and measurements are true rms values.

Settings are protected by a sealable cover.Control status is indicated by a LED.

The relay is designed for clip-on mounting on � rail

Applications� Management of pumps.

DescriptionRM35 BA

1 Configuration: selection of active function and operating mode. 3ph/1ph (Double - Single).

2 Overcurrent setting potentiometer. > I3 Undercurrent setting potentiometer. < I4 Time delay adjustment potentiometer. Tt5 Starting inhibition time delay adjustment

potentiometer. Ti6 Spring for clip-on mounting on 35 mm � rail.

Def. Yellow LED: indicates fault present status.Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 BA10

1056

91

E1

Y1 12 11 14Y2

L2 L3L1

Def.

Un

R

> I

< I

12345

6

Operation:pages 3/65 and 3/66

Characteristics:pages 3/66 and 3/67

References, dimensions :page 3/68

Schemes:page 3/69

3/65

3

Operation 3 Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

Operating principlePump control relay RM35 BA10 can operate on a single-phase or 3-phase supply. It incorporates 3 functions in a single unit: � Current control,� Phase presence control (in 3-phase mode),� Phase sequence control (in 3-phase mode).

It has two operating modes which are designed to control a pump via two external signal inputs (Y1 Y2).

These two signals are controlled by volt-free contacts.

Control inputs Y1 and Y2 can be connected to:� A level sensor,� A level relay,� A pressure sensor,� A pushbutton, etc...

Fault signalling is by LED with differentiation of the cause of the fault.

3-phase and single-phase pump control relayThe operating mode is fixed by the user: A switch allows selection between the following modes:� Single control,� Double control,� Single-phase or 3-phase supply.The position of the switch, and therefore the operating mode, is read by the product on energisation.

If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

Function diagrams Single control mode � Functions : � Single control mode (3ph/1ph).

This mode is designed to control a pump via an external signal.The relay output is closed when the signal is present at Y1 (contact closed).Y2 can be used to reset the relay after a current fault.

� Double control mode (3ph/1ph). Double control mode

This mode is designed to control a pump via two external control signals (Y1 and Y2).The output relay closes when both input signals are present (Y1 and Y2 closed).It will open as soon as one of these signals disappears.

Ti: time delay to inhibit fault monitoring on starting of pump (overcurrent and undercurrent, setting on front panel).Tt: time delay in the event of a fault (overcurrent or undercurrent, setting on front panel).I. Def.: presence of a current fault (overcurrent or undercurrent)

Tt TtTtTi Ti Ti

Y1

Y2

II.Def.

11-1211-14Relays

Supply Un

TiTiTiTtTi Tt

Y1

Y2

I.Def.

11-1211-14Relays

Supply Un

Presentation, description :page 3/64

Characteristics:pages 3/66 and 3/67

References, dimensions :page 3/68

Schemes:page 3/69

3/66

3

Operation (continued),

characteristics 3

Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

3-phase and single-phase pump control relay (continued)Function diagrams � Control

If the control relay is configured for a single-phase supply, it monitors the current consumed by the pump.If the control relay is configured for a 3-phase supply, it monitors the current, phase sequence and phase failure.

If a phase fault is detected, the output relay opens immediately.On energisation, if there is a phase sequence or phase failure fault, the output is unable to energise.

The overcurrent and undercurrent values are set by two separate potentiometers, graduated from 1 to 10 A.In the event of a setting error (low threshold greater than high threshold) the output relay is open and all the LEDs flash to signal the error.If a current fault occurs (overcurrent or undercurrent) the relay opens when the fault persists for longer than the threshold time delay setting. When the current returns to a correct value, the output relay stays open. It can only be re-energised by a RESET: either by switching off the power,or by closing of external contact Y2 (in single control mode). An inhibition time delay on energisation (Ti) allows detection of current peaks on starting of the motor.

� Functions : � Overcurrent detection. > I

� Undercurrent detection. < I.

Ti : time delay to inhibit fault monitoring on starting of pump (overcurrent and undercurrent, setting on front panel).Tt: time delay in the event of a fault (overcurrent or undercurrent, setting on front panel).

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-27 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indicator Yellow LEDFault indication Yellow LED

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un 3-phase V � 208…480

Single-phase V ��230

Operating range V � 183…528 Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %

Galvanic isolation, supply/measurement NoMaximum power consumption VA ��5Immunity to microbreaks ms 500

Ti Tt Ti

II >

11-12/11-14Relays

Supply Un

11-12/11-14

Ti Tt Ti

II <

Relays

Supply Un

Presentation, description :page 3/64

Operation:pages 3/65 and 3/66

References, dimensions :page 3/68

Schemes:page 3/69

3/67

3

Characteristics (continued), 3 Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3

Measurement circuit and input characteristicsMeasurement range A � 1…10

Input resistance Ω E1 - L2 : 0.01

Overload Permanent at 25 °C A 11 (E1-L2)

Non repetitive < 1 s at 25 °C A 50 (E1-L2)Frequency of the measured signal Hz 50…60 ± 10 %

Maximum measuring cycle ms 140/measurement as true rms value

Hysteresis 5 % of the threshold

Setting accuracy ± 10 % of the threshold setting (of the full scale value)

Repeat accuracy (with constant parameters) ± 1 %

Measurement error with voltage variation 1 % / V over the whole range

Measurement error with temperature variation ± 0.05 % / °C

Time delay characteristicsTime delay on energisation Ti s 1…60. 0 + 10 %

Time delay on crossing the threshold Tt s 0.1…10. 0 + 10 %

Repeat accuracy (with constant parameters) ± 1 %

Reset time s 2

Minimum duration Y2 (reset) ms 300

Response time in the event of a fault ms < 300

Delay on pick-up ms 500

Output characteristicsType of output 1 C/O contact

Contact type Cadmium-free

Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250

Maximum breaking current A �/� 5

Minimum breaking current 10 mA/� 5 V

Mechanical durability 30 x 106 operating cycles

Electrical durability 1 x 105 operating cycles

Maximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

Presentation, description :page 3/64

Operation:pages 3/65 and 3/66

References, dimensions :page 3/68

Schemes:page 3/69

3/68

3

Reference,dimensions 3

Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

ReferenceFunction Current

range controlled

Supply voltage

Output Reference Weight

A V kg3-phase:� Phase sequence� Phase failure� Overcurrent and

undercurrent controlSingle-phase :� Overcurrent and

undercurrent control

1…10 � � 208…480, 3-phase� � 230,single-phase

1 C/O5 A

RM35 BA10 0.110

DimensionsRM35 BA10

mm/In.

RM35 BA10

1056

91

2,8

0.11

76/2.99

72,5/2.85

72/2.83

90/3

.54

35/1.38

E1

Y1 12 11 14Y2

L2 L3L1

Def.

Un

R

> I

< I

Presentation, description :page 3/64

Operation:pages 3/65 and 3/66

Characteristics:pages 3/66 and 3/67

Schemes:page 3/69

3/69

3

Schemes 3 Zelio Control - modular measurement and control relays 3

3-phase and single-phase pump control relays RM35 BA

Schemes RM35 BA103-phase < 10 A Single-phase �������� 230 V < 10 A

(1) 100 mA quick-blow fuse or circuit-breaker.

3-phase > 10 A Single-phase �������� 230 V > 10 A

(1) 100 mA quick-blow fuse or circuit-breaker.

M 3

F1 (1)

L1

L2

L3

KM1U1

W1

V1

N

L1 L2 L3E1

Y1 Y2 1112 14

11

12 14

R

M

U

V

KM1

N

L1 L2 L3E1

Y1 Y2 1112 14

11

12 14

Ph

F1 (1)

R

L1

L2

L3

KM1U1

W1

V1 M 3

N

L1 L2 L3E1

Y1 Y2 1112 14

11

12 14

T.I.

F1 (1)

R

M T.I.

U

V

PhKM1

N

L1 L2 L3E1

Y1 Y2 1112 14

11

12 14

F1 (1)

R

Presentation, description :page 3/64

Operation:pages 3/65 and 3/66

Characteristics:pages 3/66 and 3/67

References, dimensions :page 3/68

3/70

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Frequency control relay RM35 HZ

PresentationFrequency control relay RM35 HZ monitors frequency variations on 50 or 60 Hz a.c. supplies:

� Over-frequency and under-frequency with two independent relay outputs. � Selectable memory function.

It monitors its own supply voltage, measured as a true rms value.

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relay is designed for clip-on mounting on � rail

ApplicationsMonitoring of electrical power sources:� Generating sets, wind turbines, micro-power stations...

DescriptionRM35 HZ21FM

1 Configuration: selection of 50/60 Hz frequency range and operating mode (with or without memory). Memory - No Memory

2 Frequency threshold multiplication switch. x1-x23 Low frequency threshold setting switch. F <4 High frequency threshold setting switch. F >5 Time delay adjustment potentiometer.6 Spring for clip-on mounting on 35 mm � rail.

R1 Yellow LED: indicates relay state (high frequency threshold).Un Green LED: indicates that supply to the relay is on.R2 Yellow LED: indicates relay state (low frequency threshold).

RM35 HZ21FM

1056

84

A1

12 2214 21 2411

A2

R1

Un

R2

12345

6

Operation:page 3/71

Characteristics:pages 3/72 and 3/73

References, dimensions :page 3/73

3/71

3

Operation 3 Zelio Control - modular measurement and control relays 3

Frequency control relay RM35 HZ

Operating principleFrequency control relay RM35 HZ monitors:� Frequency variations on 50 or 60 Hz supplies.� It allows monitoring of over-frequency and under-frequency, via adjustment of two independent thresholds. It has two relay outputs: one per threshold.

Fault signalling is by LED.

���� Function selector switch:� Set the switch to frequency of 50 or 60 Hz of the supply monitored, then select Memory or No memory mode. The position of the switch, and therefore the operating mode, is read by the product on energisation.� If the switch is set to an unacceptable position, the product detects a fault, the output relays stay open and the LEDs flash to signal the position error.� If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.� The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.

� The relay monitors its own supply voltage Un:The under-frequency or over-frequency threshold values are set by means of two graduated potentiometers indicating the variation value of the frequency to be monitored.A switch x1 / x2 allows the control scale to be doubled. Hysteresis is fixed at 0.3 Hz.

If the frequency of the voltage controlled exceeds the over-frequency threshold setting for a time greater than that set on the front panel (0.1…10 s), the corresponding output relay opens and its LED goes out. During the time delay, this LED flashes.As soon as the frequency drops below the value of the threshold setting, minus the hysteresis, the relay instantly closes.

If the frequency of the voltage controlled falls below the under-frequency threshold setting for a time greater than that set on the front panel (0.1…10 s), the corresponding output relay opens and its LED goes out. During the time delay, this LED flashes.As soon as the frequency rises above the value of the threshold setting, plus the hysteresis, the relay instantly closes. On energisation of the device with a fault measured, the relay stays open.

� "Memory" mode: If "Memory" mode is selected, the relay opens after the time delay and stays in that position when crossing of the threshold is detected.The power must be switched off to reset the product.

Function diagrams

� Function: Over-frequency and under-frequency control� (without memory) No Memory.

Tt: time delay after crossing of threshold (adjustable on front panel)

���� (with memory) Memory.

Tt: time delay after crossing of threshold (adjustable on front panel)

Tt Tt

F

11-1211-14

21-2221-24

F >

F <

Relay R1

Hysteresis

Supply Un

Relay R2

Hysteresis

Tt Tt

F

11-1211-14

21-2221-24

F >

F <

Relay R1

Hysteresis

Supply Un

Relay R2

Hysteresis

Presentation, description :page 3/70

Characteristics:pages 3/72 and 3/73

References, dimensions :page 3/73

3/72

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Frequency control relay RM35 HZ

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic

Power ON indicator Green LEDRelay state indication (R1-R2) Yellow LEDs. These LEDs flash during the delay on crossing the thresholdMounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V � 120…277Operating range V � 102…308Voltage limits Of the power supply circuit - 15 %, + 10 Hz

Frequency Of the power supply circuit 50/60 Hz ± 10 HzGalvanic isolation, supply/measurement NoMaximum power consumption VA ��6

Immunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3

Measurement circuit and input characteristicsMeasurement range Hz 40…70Frequency of the measured signal Hz 40…70

Maximum measuring cycle ms 200, measured as true rms valueThreshold setting Hz - 10…+ 2 and - 2…+ 10Adjustable or fixed hysteresis Hz 0.3 fixed

Setting accuracy ± 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < ± 1 % over the whole range

Measurement error with temperature variation ± 0.05 % / °CMaximum frequency of input signals Hz 70 max

Time delay characteristicsTime delay on crossing the threshold s 0.1…10, 0 + 10 %

Setting accuracy ± 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 % Reset time ms 2000

Delay on pick-up ms 500

Presentation, description :page 3/70

Operation:page 3/71

References, dimensions :page 3/73

3/73

3

Characteristics (continued),

reference,dimensions,scheme 3

Zelio Control - modular measurement and control relays 3

Frequency control relay RM35 HZ

Output characteristicsOutput type 1 C/O + 1 C/O contactsContact type Cadmium-freeNominal current A 5

Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 V

Electrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full load

Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferenceFunction Range

controlledSupply voltage

Output Reference Weight

V kg� Over-frequency

and under-frequency50 or 60 Hz

40…60 Hz (50 Hz) / 50…70 Hz (60 Hz)

� 120…277 1 C/O + 1 C/O 5 A

RM35 HZ21FM 0.130

DimensionsRM35 HZ21FM

mm/In.

SchemeRM35 HZ21FM

RM35 HZ21FM

1056

84

A1

12 2214 21 2411

A2

90/3

.54

35/1.38

2,8

0.11

76/2.99

72,5/2.85

72/2.83

A1 A2

1112 14 22 21 24

A1

A2 2111

12 14 2422

R1 R2

Presentation, description :page 3/70

Operation:page 3/71

Characteristics:pages 3/72 and 3/73

3/74

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

PresentationSpeed control relay RM35 S0MW monitors: � Underspeed:� without memory,� with memory,� with inhibition by external contact S2.� Overspeed:� without memory,� with memory,� with inhibition by external contact S2.

Speed control relay RM35 S0MW measures via:� A 3-wire PNP or NPN proximity sensor input,� A Namur proximity sensor input,� A 0-30 V voltage input,� A volt-free contact input.

It operates with either N/O or N/C sensors. The adjustable time between impulses is 0.05 s…10 min. The power-on inhibition time is adjustable from 0.6 to 60 s.Inhibition is controlled by an external contact.

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relay is designed for clip-on mounting on � rail

Applications� Monitors speed or rate of rotary or linear movements in the following applications:� conveyors/conveyor belts,� packaging,� mechanical handling.

DescriptionRM35 S00MW

1 Configuration: selection of operating mode: Underspeed or overspeed.Underspeed/Overspeed with or without memory. Memory - No Memory

2 Speed threshold setting potentiometer. Value3 Speed range selector switch4 Starting inhibition time delay adjustment

potentiometer. Ti5 Spring for clip-on mounting on 35 mm � rail.

In Yellow LED: indicates inhibition status (time-delay or S2 input).Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.

RM35 S0MW

1056

87

Y1

A1 12 11 14A2

12V12V E1 E2 0V

RUn

In

1234

5

Operation:pages 3/75 and 3/76

Characteristics:pages 3/77 and 3/78

References, dimensions :page 3/79

3/75

3

Operation 3 Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

Operating principleRelay RM35 S0MW monitors the speed (rate, frequency) of a process (conveyor, conveyor belt, etc.) via discrete sensors: 3-wire PNP or NPN proximity sensor, or 0-30 V voltage input, or NAMUR proximity sensor, or volt-free contact.It can be used for monitoring underspeed or overspeed.

Speed control relay: RM35 S0MW���� MeasurementThe cycle of the process being monitored is the series of impulses characterised by a two-state signal: high and low. The speed measurement is obtained by measuring the period of this signal, from the first change of state detected (either rising or falling edge).Digital processing of the signal allows the disparity between the signals to be calculated.At power up, or after appearance (or reappearance) of the sensor signal, detection (characterisation) of the signal requires processing of one or more periods (maximum of two). During this time, control is inoperative.� Operating modeUsing the switch, select one of the four operating modes: � Underspeed without memory,� Underspeed with memory,� Overspeed without memory,� Overspeed with memory.

Function diagrams ���� Underspeed control� Function: Underspeed control - Underspeed� Without memory - No Memory

At the end of the starting inhibition time delay "Ti", as soon as the speed measured drops below the threshold setting, the output relay changes state from "closed" to "open".It returns to its initial state when the speed is again higher than the threshold plus hysteresis (fixed at 5% of the threshold setting).When power is restored, after a break having lasted at least 1 s, the relay is in the on ("normal") state during the time delay and stays in that state for as long as the speed remains higher than the threshold.

� With memory Memory When relay RM35 S has been configured in "memory" mode, if underspeed is detected, the output relay stays in the off ("alarm") state whatever the further evolution of the process speed. It will not be able to return to the on ("normal") state until contact S2 closes (for at least 50 ms). If, when S2 re-opens, the speed is not high enough, the relay returns to the locked, off ("alarm") state.Relay RM35 S can also be reset by a power break (at least 1 s); the relay then returns to the on ("normal") state for at least the duration of the time delay, whatever the process speed.

� With inhibition by S2 - Inhib./S2 At power up, in order to allow the process being monitored to reach its nominal operating speed, relay RM35 S is inhibited for a time delay adjustable from 0.6…60 s. This time delay can be adjusted (shortened or lengthened) during inhibition.Relay RM35 S can also be inhibited by closing of contact S2: on starting, for example, if the process run up to speed time is greater than 60 s, or at any time during operation.Whether it results from a starting inhibition time delay or closing of S2, inhibition keeps the output relay in the "closed" position and is signalled by illumination of the inhibition LED.If, after lifting of inhibition (end of starting inhibition time delay or opening of contact S2), the signal detection phase has not been completed, the relay drops out after the set wait time between two impulses (measured as from the end of inhibition). Inhibition must last as long as is necessary for the product to detect at least 2 periods.When the signal has not been 'characterised' by the end of the inhibition period, the "inhibition" LED flashes for as long as speed measurement is impossible.It is also possible to inhibit relay RM35 S at any time, during operation, by closing S2.

VVs

Ti Ti

1 sec mini

In

11-12/11-14

Supply Un

Relays

HysteresisThreshold

1 sec mini

50 ms mini

V

S2

Ti Ti

Vs

In

11-12/11-14

Supply Un

Relays

HysteresisThreshold

Ti

V

S2

Vs

In

11-12/11-14

Supply Un

Relays

HysteresisThreshold

Presentation, description :page 3/74

Characteristics:pages 3/77 and 3/78

References, dimensions :page 3/79

3/76

3

Operation (continued) 3 Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

Speed control relay: RM35 S0MW (continued)Function diagrams ���� Overspeed control� Function: overspeed control - Overspeed� Without memory- No Memory At the end of the starting inhibition time delay, "Ti", as soon as the speed measured

is higher than the threshold setting, the output relay changes state from "closed" to "open".It returns to its initial state when the speed is again lower than the threshold minus hysteresis (fixed at 5% of the threshold setting).When power is restored to relay RM35 S, after a break having lasted at least 1 s, the relay is in the on ("normal") state during the time delay and stays in that state for as long as the speed remains lower than the threshold.

� With memory - Memory When relay RM35 S has been configured in "memory" mode, if overspeed is detected, the output relay stays in the off ("alarm") state whatever the further evolution of the process speed. It will not be able to return to the on ("normal") state until contact S2 closes (for at least 50 ms). If, when S2 re-opens, the speed is too high, the relay returns to the locked off ("alarm") state.Relay RM35 S can also be reset by a power break (at least 1 s); the relay then returns to the on ("normal") state for at least the duration of the time delay, whatever the process speed.

� With inhibition by S2. - Inhib./S2 At power up, in order to allow the process being monitored to reach its nominal operating speed, relay RM35 S is inhibited for a time delay adjustable from 0.6…60 s. This time delay can be modified (shortened or lengthened) during inhibition.Relay RM35 S can also be inhibited by closing of contact S2: on starting, for example, if the process run up to speed time is greater than 60 s, or at any time during operation.Whether it results from a starting inhibition time delay or closing of S2, inhibition keeps the output relay in the "closed" position and is signalled by illumination of the inhibition LED.If, after lifting of inhibition (end of starting inhibition time delay or opening of contact S2), the signal detection phase has not been completed, the relay drops out after the set wait time between two impulses (measured as from the end of inhibition).Inhibition must last as long as is necessary for the product to detect at least 2 periods.When the signal has not been 'characterised' by the end of the inhibition period, the "inhibition" LED flashes for as long as speed measurement is impossible.It is also possible to inhibit relay RM35 S at any time, during operation, by closing S2.

V

Ti Ti

1 sec mini

In

11-12/11-14

Vs

Supply Un

Relays

HysteresisThreshold

V

1 sec mini

50 ms mini

Ti Ti

S2

Vs

In

11-12/11-14

Supply Un

Relays

HysteresisThreshold

Ti

V

S2Vs

In

11-12/11-14

Supply Un

Relays

HysteresisThreshold

Presentation, description :page 3/74

Characteristics:pages 3/77 and 3/78

References, dimensions :page 3/79

3/77

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC

Ambient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)

Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529

Casing IP 30

Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III

Insulation resistance Conforming to IEC 60664-1, 60255-5

> 500 MΩ, � 500 V

Rated insulation voltage Conforming to IEC 60664-1 V 250Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.

Shock wave kV 4

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC3 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plasticPower ON indicator Green LED

Relay state indicator (R) Yellow LEDInhibit status indication Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4…264Polarity on d.c. supply No

Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes

Maximum power consumption � 5 VA and � 3 WImmunity to microbreaks ms 50

Sensor supply characteristicsNominal voltage V 12 ± 0,5

Available current mA 50 for �/��24 V � Un � �/��240 V40 for Un < �/��24 V at 25 °C

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4,NF EN 61000-6-3,IEC 61000-6-4,IEC 61000-6-3

Presentation, description :page 3/74

Operation:pages 3/75 and 3/76

References, dimensions :page 3/79

3/78

3

Characteristics (continued) 3 Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

Measurement circuit and input characteristicsInput circuit 3-wire sensor (E1) PNP or NPN, 12 V, 50 mA max

NAMUR sensor (E2) 12 V, 1.5 kΩVolt-free contact input (E1) 12 V, 9.5 kΩVoltage input (E1) Voltage range: 0 V min, 30 V max

Input resistance: 9.5 kΩHigh state: 4.5 V minLow state: 1 V max

Minimum impulse time At high state ms 5At low state ms 5

Measurement range 0.05…0.5 s0.1…1 s0.5…5 s1…10 s0.1…1 min0.5…5 min1…10 min

Threshold setting 10…100 % of the rangeFixed hysteresis 5 % of the threshold setting

Setting accuracy ± 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole range

Measurement error with temperature variation ± 0,1 % / °C maxFrequency of input signals Hz 1.7 mHz min, 20 Hz max

Time delay characteristicsResponse time on crossing the threshold ms 15 max

Repeat accuracy (with constant parameters) ± 0.5 % Reset time in memory mode Contact S2 ms 50 minimum

Supply Un s 1

Inhibition time delay On energisation 0.6…60 s +10 % of the full scale valueDelay on pick-up ms 50

Output characteristicsOutput type 1 C/O contact

Contact type Cadmium-freeNominal current A 5Maximum switching voltage V �/� 250

Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 VElectrical durability 1 x 105 operating cycles

Mechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

Presentation, description :page 3/74

Operation:pages 3/75 and 3/76

References, dimensions :page 3/79

3/79

3

Reference,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Speed control relays RM35 S

ReferenceFunction Supply

VMeasurementInput

Output Reference Weightkg

� Underspeed,� Overspeed

�/� 24…240 � 3-wire PNP or NPN proximity sensor (1),

� Namur proximity sensor,

� 0-30 V voltage,� Volt-free contact.

1 C/O5 A

RM35 S0MW 0.130

(1) See page 3/80.

DimensionsRM35 S0MW

mm/In.

SchemesRM35 S0MW

Contact input Namur proximity sensor input

NPN/PNP sensor input 0-30 V voltage input

(2) A quick-blow fuse or circuit-breaker.

RM35 S0MW

1056

87

2,8

0.11

76/2.99

72,5/2.85

72/2.8390

/3.5

435/1.38

1112 14

11

12 14

A1 A2

Y1 12 V

S2Inhib. - Reset

R

S1

12 V E1 E2 0 V

+/–

–/+

z 24...240 V50/60 Hz

F1 (2)

S2Inhib. - Reset

1112 14

11

12 14

A1 A2

Y1 12 V

R

S1

12 V E1 E2 0 V

+/–

+ –

–/+

z 24...240 V50/60 Hz

F1 (2)

S2Inhib. - Reset

1112 14

11

12 14

A1 A2

Y1 12 V

R

S1

12 V E1 E2 0 V

+/–

–/+

z 24...240 V50/60 Hz

B BUBK

F1 (2)

S2Inhib. - Reset

1112 14

11

12 14

A1 A2

Y1 12 V

R

S1

12 V E1 E2 0 V

+/–

–+

–/+

z 24...240 V50/60 Hz

e

F1 (2)

Presentation, description :page 3/74

Operation:pages 3/75 and 3/76

Characteristics:pages 3/77 and 3/78

3/80

3

References 3 Inductive proximity sensors 3

Osiprox® Optimum (1)Cylindrical, flush mountable, increased rangeThree-wire, d.c. supply, solid-state output

Sensing distance Sn(mm)

Function Output Connection Reference Weightkg

Ø 6 plain 2.5 NO PNP Pre-cabled (L = 2 m) XS1 L06PA349 0.025

M8 connector XS1 L06PA349S 0.010M12 connector XS1 L06PA349D 0.015

NPN Pre-cabled (L = 2 m) XS1 L06NA349 0.025

M8 connector XS1 L06NA349S 0.010M12 connector XS1 L06NA349D 0.015

NC PNP Pre-cabled (L = 2 m) XS1 L06PB349 0.025

M8 connector XS1 L06PB349S 0.010NPN Pre-cabled (L = 2 m) XS1 L06NB349 0.025

M8 connector XS1 L06NB349S 0.010

Ø 8, threaded M8 x 12.5 NO PNP Pre-cabled (L = 2 m) XS1 N08PA349 0.035

M8 connector XS1 N08PA349S 0.015M12 connector XS1 N08PA349D 0.020

NPN Pre-cabled (L = 2 m) XS1 N08NA349 0.035M8 connector XS1 N08NA349S 0.015M12 connector XS1 N08NA349D 0.020

NC PNP Pre-cabled (L = 2 m) XS1 N08PB349 0.035M8 connector XS1 N08PB349S 0.015M12 connector XS1 N08PB349D 0.020

NPN Pre-cabled (L = 2 m) XS1 N08NB349 0.035M8 connector XS1 N08NB349S 0.015M12 connector XS1 N08NB349D 0.020

Ø 12, threaded M12 x 14 NO PNP Pre-cabled (L = 2 m) XS1 N12PA349 0.070

M12 connector XS1 N12PA349D 0.020NPN Pre-cabled (L = 2 m) XS1 N12NA349 0.070

M12 connector XS1 N12NA349D 0.020NC PNP Pre-cabled (L = 2 m) XS1 N12PB349 0.070

M12 connector XS1 N12PB349D 0.020

NPN Pre-cabled (L = 2 m) XS1 N12NB349 0.070M12 connector XS1 N12NB349D 0.020

Ø 18, threaded M18 x 110 NO PNP Pre-cabled (L = 2 m) XS1 N18PA349 0.100

M12 connector XS1 N18PA349D 0.040NPN Pre-cabled (L = 2 m) XS1 N18NA349 0.100

M12 connector XS1 N18NA349D 0.040

NC PNP Pre-cabled (L = 2 m) XS1 N18PB349 0.100M12 connector XS1 N18PB349D 0.040

NPN Pre-cabled (L = 2 m) XS1 N18NB349 0.100

M12 connector XS1 N18NB349D 0.040

Ø 30, threaded M30 x 1.520 NO PNP Pre-cabled (L = 2 m) XS1 N30PA349 0.160

M12 connector XS1 N30PA349D 0.100

NPN Pre-cabled (L = 2 m) XS1 N30NA349 0.160M12 connector XS1 N30NA349D 0.100

NC PNP Pre-cabled (L = 2 m) XS1 N30PB349 0.160

M12 connector XS1 N30PB349D 0.100NPN Pre-cabled (L = 2 m) XS1 N30NB349 0.160

M12 connector XS1 N30NB349D 0.100

AccessoriesDescriptionmm

Reference Weightkg

Fixing clamps Ø 8 XSZ B108 0.006Ø 12 XSZ B112 0.006Ø 18 XSZ B118 0.010

Ø 30 XSZ B130 0.020(1) Accessories recommended for RM35 S0MW control relays

8011

20

XS1 L06�A349

8012

31

XS1 N����349

8011

67

XS1 N08��349S

8012

32

XS1 N����349D

XSZ B1��

3/81

3

Characteristics, schemes, setting-up, dimensions 3

Inductive proximity sensors 3

Osiprox® OptimumCylindrical, flush mountable, increased rangeThree-wire, d.c. supply, solid-state output

CharacteristicsSensor type XS1 ��������������������349D XS1 ��������������������349S XS1 ��������������������349

Product certifications UL, CSA, �Connection M12 connector M8 connector Pre-cabled, length: 2 m

Operating zone Ø 6.5 and Ø 8 mm 0…2 Ø 12 mm 0…3.2 Ø 18 mm 0…8 Ø 30 mm 0…16

Differential travel % 1...15 of real sensing distance (Sr)Degree of protection Conforming to IEC 60529 IP 67 IP 68, double insulation

(except Ø 6.5 and Ø 8: IP 67)Storage temperature °C - 40…+ 85

Operating temperature °C - 25…+ 50 Materials Case Nickel plated brass

Cable – PvR 3 x 0.34 mm2 except Ø 6.5 and Ø 8: 3 x 0.11 mm2

Vibration resistance Conforming to IEC 60068-2-6

25 gn, amplitude ± 2 mm (f = 10 to 55 Hz)

Shock resistance Conforming to IEC 60068-2-27

50 gn, duration 11 ms

Output state indication Yellow LED, 4 viewing ports at 90° Yellow LED, annular

Rated supply voltage V � 12…24 with protection against reverse polarityVoltage limits (including ripple) V � 10…36Switching capacity mA � 200 with overload and short-circuit protection

Voltage drop, closed state V � 2 Current consumption, no-load mA � 10Maximum switching frequency Ø 6.5, Ø 8 and Ø 12 Hz 2500

Ø 18 Hz 1000Ø 30 Hz 500

Delays First-up ms � 5

Response ms � 0.2 for Ø 8 and Ø 12, � 0.3 for Ø 18, � 0.6 for Ø 30Recovery ms � 0.2 for Ø 8 and Ø 12, � 0.7 for Ø 18, � 1.4 for Ø 30

Wiring schemesConnector Pre-cabled PNP 3-wire NPN 3-wire

M8 M12 BU: BlueBN: BrownBK: Black

Setting-upMinimum mounting distances (mm)

Sensor Side by side Face to face Facing a metal object Mounted in a metal supportØ 6.5 e � 5 e � 30 e � 7.5 d � 10 h � 1.6

Ø 8 e � 5 e � 30 e � 7.5 d � 10 h � 1.6Ø 12 e � 8 e � 48 e � 12 d � 14 h � 2.4Ø 18 e � 20 e � 96 e � 30 d � 28 h � 3.6

Ø 30 e � 40 e � 240 e � 60 d � 50 h � 6

DimensionsFlush mountable in metal

Sensor Pre-cabled M8 connector M12 connectora b a b a b

Ø 6.5 33 30 42 34 45 24Ø 8 33 25 42 26 45 23

Ø 12 33 25 – – 48 29Ø 18 36.5 28 – – 48.6 28

Ø 30 40.6 32 – – 52.7 32

1 3

4

1 2

4 3

BN/1

BU/3

+PNP BK/4 (NO)

BK/2 (NC)

BN/1

BU/3

+

BK/4 (NO)BK/2 (NC)

NPN

e

e e h

d

a

b

3/82

3

Presentation,description 3

Zelio Control - modular measurement and control relays 3

Temperature control relays RM35 AT� for elevator machine rooms and 3-phase supplies

PresentationMeasurement and control relays RM35 ATL0MW, RM35 ATR5MW and RM35 ATW5MW are designed for monitoring the temperature in elevator machine rooms, in compliance with directive EN81. � PT 100 input, � Adjustable control around 5 °C and 40 °C, � Independent adjustment of high and low thresholds,� Possibility of integrated phase control,

Settings are protected by a sealable cover.

Control status is indicated by a LED.

The relays are designed for clip-on mounting on � rail.

Applications� Temperature control for elevator machine rooms.

DescriptionRM35 ATL0MW RM35 ATR5MW

1 High temperature threshold setting potentiometer. θ>

2 Potentiometer for adjustment of time delay on crossing of temperature threshold. Tt

3 Low temperature threshold setting potentiometer. θ<

4 Spring for clip-on mounting on 35 mm � rail.

5 High temperature threshold contact (11-14).

6 Low temperature threshold contact (21-24).

7 High and low temperature threshold contacts.

> Yellow LED: indicates relay output state (high temperature threshold).Un Green LED: indicates that supply to the relay is on.< Yellow LED: indicates relay output state (low temperature threshold).

RM35 ATW5MW

1 High temperature threshold setting potentiometer. θ>

2 Potentiometer for adjustment of time delay on crossing of temperature threshold. Tt

3 Low temperature threshold setting potentiometer. θ<

4 Spring for clip-on mounting on 35 mm � rail.

5 Temperature relay contact (11-14).6 Phase relay contact (21-44).

<θ°< Yellow LED: indicates temperature relay output state. R1Un Green LED: indicates that supply to the relay is on.

Yellow LED: indicates phase relay output state. R2

RM35 AT�0MW

1056

88

4

A

A1 12 11 14A2

B B

>

<Un

123

7

A

A1 1411 21 24A2

B B

>

<Un

123

456

A L1 L2 L3

A1 1411 21 24A2

B B

UnL1

L2L3

<<

123

456

L1

L2L3

Operation:page 3/83

Characteristics:pages 3/84 and 3/85

References, dimensions :page 3/85

3/83

3

Operation 3 Zelio Control - modular measurement and control relays 3

Temperature control relays RM35 AT� for elevator machine rooms and 3-phase supplies

Operating principleTemperature control relays for elevator machine rooms are designed to monitor the said temperature between 5°C and 40°C in compliance with directive EN81.

Temperature control relay: RM35 ATL0MWAfter a delay on pick-up after energisation, and for as long as the temperature monitored by the PT100 probe remains between the two thresholds set on the front panel, the output relay is closed and the yellow LEDs are on.When the temperature crosses one of the threshold settings on the front panel (high or low threshold), the time delay set on the front panel (Tt) is activated. The yellow LED corresponding to the threshold crossed (low or high), flashes.At the end of the time delay, if the temperature is still outside the threshold setting, the output relay opens and the yellow LED corresponding to the threshold crossed goes out.The output relay closes instantly (within the response time on disappearance of a fault) when the temperature returns within the window of the two threshold settings on the front panel, plus the fixed hysteresis.

If the PT 100 probe is incorrectly wired (missing or short-circuited) the relay is open and the 3 LEDs flash.

Temperature control relay: RM35 ATR5MWAfter a delay on pick-up after energisation, and for as long as the temperature monitored by the PT100 probe remains between the two threshold settings on the front panel, the output relays are closed and their yellow LEDs are on.When the temperature crosses one of the threshold settings on the front panel (high or low threshold), the time delay set on the front panel (Tt) is activated. The yellow LED corresponding to the threshold crossed (low or high), flashes.At the end of the time delay, if the temperature is still outside one of the threshold settings, the corresponding output relay opens and the yellow LED corresponding to the threshold crossed goes out.The output relay closes instantly (response time on disappearance of a fault) when the temperature returns within the window of the two threshold settings on the front panel, plus (or minus) the fixed hysteresis.

If the PT 100 probe is incorrectly wired (missing or short-circuited) the relays are open and the 3 LEDs flash.

Temperature and phase control relay: RM35 ATW5MWAfter a delay on pick-up after energisation, and for as long as the temperature monitored by the PT100 probe remains between the two threshold settings on the front panel, the temperature relay R1 is closed.When the temperature crosses one of the threshold settings on the front panel (high or low threshold), the time delay set on the front panel (Tt) is activated. The yellow temperature LED flashes. At the end of the time delay, if the temperature is still outside the threshold setting, the output relay R1 opens and the yellow LED goes out.The output relay R1 closes instantly when the temperature returns to within the window of the two threshold settings on the front panel, plus or minus the fixed hysteresis.

The device also monitors the correct sequence of phases L1, L2 and L3 of the 3-phase supply and total phase failure, even in the case of phase regeneration (< 70 %).After a delay on pick-up after energisation, and for as long as phase presence and phase sequence are correct, relay R2 and the "phase" LED are On. When a fault appears, the "phase" relay opens and the "phase" LED instantly goes out (response time on appearance of a fault). When the fault disappears, the phase control relay and LED are activated (response time on disappearance of a fault).

If the PT 100 probe is incorrectly wired (missing or short-circuited) relay R1 is open and LED R1 flashes.

Function diagram

� Function:� Temperature control by PT 100 probe.

Tt: Time delay after crossing of the temperature threshold (adjustable on front panel).

11-12

>

<

Tt Tt

θ°

θ°θ°

11-14Relays

Hysteresis

Supply Un

Hysteresis

Function diagram

� Function� Temperature control by PT 100 probe.

Tt: Time delay after crossing of the temperature threshold (adjustable on front panel).

11-14

21-24

Tt Tt

>

<

θ°

θ°θ°

Relay R1

Hysteresis

Supply Un

Hysteresis

Relay R2

Function diagram

� Function� Temperature control by PT 100 probe� Sequence of phases L1, L2, L3.� Phase failure.

Tt: Time delay after crossing of the temperature threshold (adjustable on front panel).

11-14

Tt Tt

>

<

θ°

θ°θ°

Relay R1

Hysteresis

Supply Un

Hysteresis

Presentation, description :page 3/82

Characteristics:pages 3/84 and 3/85

References, dimensions :page 3/85

3/84

3

Characteristics 3 Zelio Control - modular measurement and control relays 3

Temperature control relays RM35 AT� for elevator machine rooms and 3-phase supplies

Environment characteristicsRelay type RM35 ATL0MW RM35 ATR5MW RM35 ATW5MW

Conforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOST

Marking ����: 73/23/EEC and EMC 89/336/EECAmbient air temperature around the device

Storage °C - 40…+ 70Operation °C - 20…+ 50

Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gn

Degree of protectionConforming to IEC 60529

Casing IP 30Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 100 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250 250 400

Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

ConnectionMaximum c.s.a.Conforming to IEC 60947-1

Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)

Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)

Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.In

Housing material Self-extinguishing plasticPower ON indicator Green LED Green LED Green LEDRelay state indicator High threshold Yellow LED Yellow LED –

Low threshold Yellow LED Yellow LED –High threshold/low threshold – – Yellow LEDPhases – – Yellow LED

Mounting Conforming to IEC/EN 60715 On 35 mm � rail

Supply characteristicsRelay type RM35 ATL0MW RM35 ATR5MW RM35 ATW5MW

Rated supply voltage Un V �/� 24…240

Operating range V � 20.4…264 � 21.6…264

Voltage limits Of the power supply circuit � - 15 %, + 10 %� - 10 %, + 10 %

Frequency Of the power supply circuit Hz 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes NoMaximum power consumption at Un VA ��3.5

W � 0.6Immunity to microbreaks ms 10

Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2

Emission NF EN 61000-6-4 NF EN61000-6-3 , IEC 61000-6-4, IEC 61000-6-3

Measurement circuit and input characteristicsMeasurement range Low temperature °C - 1, 1, 3, 5, 7, 9, 11

High temperature °C 34, 36, 38, 40, 42, 44, 46

Temperature sensor PT 100 - 3-wirePhase measurement range V – – 208…480, - 15 %/+ 10 %Frequency of the measured signal Hz – – 50…60 ± 1

Detection of phase failure with regeneration – – > 30 % of the average of the 3 phases

Input resistance Temperature Ω 13303-phase kΩ – – 600

Setting accuracy °C ± 2

Maximum length of PT100 probe cables m 10

Presentation, description :page 3/82

Operation:page 3/83

References, dimensions :page 3/85

3/85

3

Characteristics (continued),

references,dimensions,schemes 3

Zelio Control - modular measurement and control relays 3

Temperature control relays RM35 AT� for elevator machine rooms and 3-phase supplies

Time delay characteristicsRelay type RM35 ATL0MW RM35 ATR5MW RM35 ATW5MW

Time delay on crossing the threshold s 0.1…10, 0 + 10 %Reset time s 8

Maximum response time In case of 3-phase fault ms – – 500In case of temperature fault s 3.5 + Tt 3.5 + Tt 3.5 + TtOn disappearance of fault s 3.5 3.5 0.5

Delay on pick-up ms 200 200 200

Output characteristicsOutput type 1 C/O contact 2 N/O contacts 2 N/O contacts

Contact type Cadmium-free

Nominal current A 5Maximum switching voltage V �/� 250Rated breaking capacity VA 1250

Minimum breaking current mA 10/ � 5 VElectrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cycles

Maximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14

ReferencesFunction Supply 3-phase

controlOutput Reference Weight

V V kg� Overtemperature :

34…46 °C� Under-temperature

- 1…11 °C

�/� 24…240 – 1 C/O5 A

RM35 ATL0MW 0.130

– 2 N/O5 A

RM35 ATR5MW 0.130

� Overtemperature : 34…46 °C

� Under-temperature- 1…11 °C

� Phase sequence� Phase failure

�/� 24…240 � 208…480 2 N/O5 A

RM35 ATW5MW 0.130

Dimensions SchemesRM35 AT��������MW RM35 ATL0MW RM35 ATR5MW RM35 ATW5MW

mm/In.

RM35 ATL0MW

1056

88

RM35 ATR5MW

1056

89

RM35 ATW5MW

2,8

0.11

76/2.99

72,5/2.85

72/2.83

90/3

.54

35/1.38

1112 14

A1

A2

11

12 14

A1 A2

A B

R

B

21 2411 14

A1

A2

A1 A2

A B B

1411

2421

R1 R2

A1 A2

A1

A2

A B L1 L2 L3B

11 21 2414

14 24

11 21L1 L2 L3R1 R2

Presentation, description :page 3/82

Operation:page 3/83

Characteristics:pages 3/84 and 3/85

3/86

3

General characteristics 3 Zelio Control - industrial measurement and control relays 3

RM4 relays

(1) Value not communicated(2) Except RM4-T, see page 3/91.

EnvironmentConforming to standards IEC 60255-6, EN 60255-6

Product certifications CSA, GL, UL, pending

��������marking LVD 73/23/EEC and EMC 89/336/EEC

Zelio Control measurement relays conform to European regulations relating to � marking

Ambient air temperaturearound the device

Storage °C - 40…+ 85

Operation °C - 20…+ 65

Permissible relative humidity range

Conforming to IEC 60721-3-3 15…85 % Environmental class 3K3

Vibration resistance Conforming to IEC 60068-2-6, 10 to 55 Hz

a = 0.35 ms

Shock resistance Conforming to IEC 60068-2-27 15 gn - 11 ms

Degree of protectionConforming to IEC 60529

Casing IP 50Terminals IP 20

Degree of pollution Conforming to IEC 60664-1 3

Overvoltage category Conforming to IEC 60664-1 III

Rated insulation voltage Conforming to IEC V 500Conforming to CSA V (1)

Test voltage for insulation tests

Dielectric test kV 2,5

Shock wave kV 4,8

Voltage limits Power supply circuit 0.85…1.1 Uc (2)

Frequency limits Power supply circuit 50/60 ± 5 %

Disconnection value Power supply circuit > 0.1 Uc (2)

Mounting positionwithout derating

In relation to normal vertical mounting plane

Any position

CablingMaximum c.s.a.Conforming to IEC 60947-1

Flexible cable without cable end mm2 2 x 2.5

Flexible cable with cable end mm2 2 x 1.5

Tightening torque Conforming to IEC 60947-1 N.m 0.6…1.1

Immunity to electromagnetic interference (EMC) (Application class 2 conforming to EN 61812-1)Electrostatic discharge Conforming to IEC 61000-4-2 Level 3 (6 kV contact, 8 kV air)

Electromagnetic fields Conforming to IEC 61000-4-3 Level 3 (10 V/m)

Fast transients Conforming to IEC 61000-4-4 Level 3 (2 kV)

Shock waves Conforming to IEC 61000-4-5 Level 3 (2 kV)

Radiated and conducted emissions

CISPR11 Group 1 class A

CISPR22 Class A

3/87

3

General characteristics (continued) 3

Zelio Control - industrial measurement and control relays 3

RM4 relays

Output circuit characteristicsMechanical durability In millions of operating cycles 30

Current limit Ith A 8

Rated operational limits at 70 °CConforming to IEC 60947-5-1/1991and VDE 0660

V 24 115 250AC-15 A 3 3 3DC-13 A 2 0.3 0.1

Minimum switching capacity 12 V/10 mA

Switching voltage Rated V � 250

Max. V � 440

Contact material 90/10 nickel silver

a.c. load d.c. loadCurve 1 Curve 2 Load limit curveElectrical durability of contacts on resistive loadin millions of operating cycles

Reduction factor k for inductive loads (applies to values taken from durability Curve 1)

Example: 1 L/R = 20 ms2 L/R with load protection diode

An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.5 A and cos ϕ = 0.3.For 0.5 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2.

For cos ϕ = 0.3: k = 0.6The electrical durability therefore becomes:1.5 106

operating cycles x 0.6 = 900 000 operating cycles.

3 Resistive load

10

1

0,1

0,010 1 2 3 4 5 6 7 8

Current broken in A

M

illio

ns o

f ope

ratin

g cy

cles 1

0,6

0,5

0,9

0,8

0,7

0,4

0,31 0,8 0,6 0,5 0,4 0,3 0,2

Power factor on breaking (cos ϕ)

Red

uctio

n fa

ctor

k 300

40

30

200

100

50

20

100,1 0,2 0,5 1 2 5 2010

1

2

3

Current in A

Vol

tage

in V

RM4

K

+

3/88

3

Presentation 3 Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

These devices are designed to monitor 3-phase supplies and to protect motors and other loads against the faults listed in the table below.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.

� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).

� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).

� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.

Functions

RM4 TG RM4 TU RM4 TR RM4 TAMonitoring of rotational direction of phasesDetection of complete failure of one or more of the phases

Undervoltage detectionOvervoltage and undervoltage detection (2 thresholds)Detection of phase asymmetry (imbalance)

Function performedFunction not performed

RM4 T

5610

11

Applications

References :page 3/92

Characteristics :page 3/91

Dimensions, schemes :page 3/93

PresentationRM4 TG RM4 TU

R Yellow LED: indicates relay output state.

<U Red LED: undervoltage fault.1 Undervoltage setting potentiometer.

RM4 TR31, RM4 TR33, RM4 TR32 RM4 TR34

1 Time delay function selector:

Fault detection delayedFault detection extended

2 Potentiometer for setting time delay in seconds.3 Potentiometer for setting overvoltage as a direct

value.

4 Potentiometer for setting undervoltage as a direct value.

R Yellow LED: indicates relay output state.

U Green LED: indicates that supply to the RM4 is on.>U Red LED: overvoltage fault.<U Red LED: undervoltage fault.

P Red LED: phase failure or incorrectrotational direction of phases.

RM4 TA3 RM4 TA0 1 Asymmetry threshold setting potentiometer,

from 5 to 15 %.

2 Potentiometer for setting time delay, 0.1 to 10 s.

R Yellow LED: indicates relay output state.

U Green LED: indicates that supply to the RM4 is on.A Red LED: phase asymmetry.P Red LED: phase failure or incorrect rotational

direction of phases.

R

1R

<U

34

1

2

RU

<UP

>U

1

2

RU

<UP

>U

1

2

RU

P

A 1

R

3/89

3

Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

The supply voltage to be monitored is connected to terminals L1, L2, L3 of the product.

There is no need to provide a separate power supply for RM4 T relays, they are self-powered by terminals L1, L2, L3.

���� Monitoring rotational direction of phases and detection of complete failure of one or more phases (RM4 T all models):��When terminals L1, L2, L3 are energised, the relay is energised and the yellow LED comes on if the rotational direction of phases is correct and if all 3 phases are present.��If one or more of the phases have failed or if the rotational direction is incorrect, the relay is not energised at switch-on.��In normal operation (no fault) the relay is energised; it de-energises instantaneously in the event of failure of one or more of the phases (any time delay set is not active on these faults).��In the event of failure or absence of a single phase, a voltage greater than the detection threshold (≈ 130 V on RM4 TG, undervoltage threshold setting on RM4 TU and RM4 TR) can be generated back through the control circuit, thus preventing detection of the phase failure. In this case, we recommend the use of RM4 TA relays.��The absence of a phase is signalled, on RM4 TR and RM4 TA, by illumination of LED “P”.

���� Overvoltage and undervoltage detection (RM4 TR):��In normal operation, the relay is energised and LEDs "U" and "R" are illuminated.��If the average of the 3 voltages between phases goes outside the range to be monitored, the output relay is de-energised:

- overvoltage: the red LED “> U” illuminates,- undervoltage: the red LED “< U” illuminates.

��When the supply returns towards its rated value, the relay is re-energised according to the hysteresis value (5 %) and the corresponding red LED goes out.��A selector switch allows selection of an adjustable time delay from 0.1 s to 10 s. With function transient "over" or "under" voltages are not taken into account. With function all variations above or below are taken into account and re-energisation of the relay is delayed.��In all cases, in order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms).

Operating principle

Function diagram (RM4 TR31, RM4 TR32)

t t

< t

t t t t t

< t

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

RM4 TR31RM4 TR32

UL1 L2 L3 0 Volt

Setting > U0.95 x Setting > U

1.05 x Setting < USetting < U

Function

Function

t: time delay

Function diagram (RM4 TR33, RM4 TR34)

t t

< t

t t t

< t

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

242 V 440 V230 V 418 V

208 V 378 V198 V 360 V

RM4 TR33RM4 TR34

TR33 TR34

UL1 L2 L3

t t

0 Volt

t: time delay

Function

Function

References :page 3/92

Characteristics :page 3/91

Dimensions, schemes :page 3/93

3/90

3

Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

���� Undervoltage detection only (RM4 TU)��In normal operation, the output relay is energised and the yellow LED is illuminated.��If the average of the 3 voltages between phases is less than the undervoltage threshold setting, the relay is de-energised after 550 ms and the red LED “< U” illuminates.

t : fixed time delay = 550 ms

���� Detection of phase asymmetry (RM4 TA)��In normal operation, the output relay is energised and the yellow and green LEDs are illuminated. ��In the event of an asymmetry fault, after a time delay set between 0.1 s and 10 s (on RM4 TA3 only), the output relay is de-energised, the yellow LED goes out and red LED “A” illuminates (RM4 TA3� only).��The relay re-energises when the asymmetry value measured is less than half of the asymmetry value setting (hysteresis).

t : time delay

Example: asymmetry set at 10 %, mains supply voltage 400 V

- relay de-energisation threshold: 400 V – 10 % = 360 V, 10 %,- relay re-energisation threshold: 400 V – 10% = 380 V.

2

Note : If there is distortion of the 3-phase supply sine wave, malfunctioning of the RM4 T 3-phase supply control relay is possible.

Operating principle (continued)

Function diagram

t

< t 0 volt

15/18 25/2815/16 25/26

UL1 L2 L3

1.05 x Setting < USetting < U

Function diagram

15-1815-16

25-2825-26

t t

L1

L3 L2

L2

L1 L3

L3

L2 L1

Relay

Asymmetry >set threshold Asymmetry >

set threshold

References :page 3/92

Characteristics :page 3/91

Dimensions, schemes :page 3/93

3/91

3

Characteristics 3 Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

Output relay and operating characteristicsRelay type RM4 TG RM4 TU RM4 TR RM4 TA

Number of C/O contacts 2 2 2 RM4 TA3�: 2RM4 TA0�: 1

Output relay state Energised during fault free operation.De-energised or unable to energise on detection of rotational direction fault or failure of one or more phases.

Energised during fault free operation.De-energised on detection of undervoltage or rotational direction fault or failure of one or more phases.

Energised during fault free operation.De-energised on detection of overvoltage, undervoltage or rotational direction fault or phase failure.

Energised during fault free operation.De-energised on detection of asymmetry fault, phase failure or rotational direction fault.

Accuracy of the switching threshold setting

As % of the set value – ± 3 % ± 3 % ± 3 %

Switching threshold drift Depending on the permissible ambient temperature

– ≤ 0.06 % per degree centigrade

≤ 0.06 % per degree centigrade

≤ 0.06 % per degree centigrade

Within the measuring range – ≤ 0.5 % ≤ 0.5 % ≤ 0.5 %

Accuracy of the time delay setting

As % of the full-scale value – ± 10 % ± 10 % ± 10 %

Time delay drift Within the measuring range – ≤ 0.5 % ≤ 0.5 % ≤ 0.5 %

Depending on the rated operational temperature

– ≤ 0.07 % per degree centigrade

≤ 0.07 % per degree centigrade

≤ 0.07 % per degree centigrade

Hysteresis Fixed – About 5 % of the de-energisation threshold

About 5 % of the de-energisation threshold

About 50 % of the asymmetry percentage

Delay on pick-up ms < 650 < 650 < 650 < 650

Measuring cycle ms ≤ 80 ≤ 80 ≤ 80 ≤ 80

Measuring input characteristicsRelay type RM4 TG RM4 T��1

RM4 TR33RM4 T��2RM4 TR34

Nominal voltage V 220…440 RM4 T��1: 220…240RM4 TR33: 220

RM4 T��2: 380…440RM4 TR34: 400

Maximum operating range V 198…484 160…300 290…484

(1) Minimum voltage required for operation of indicators and of the time delay.

Presentation :pages 3/88 to 3/90

References :page 3/92

Dimensions, schemes :page 3/93

3/92

3

References 3 Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

Control relays: rotational direction and presence of phasesTime delay Rated mains

supply voltage (1)Width Output

relayReference Weight

s V mm kgWithout 220...440

50/60 Hz22.5 2 C/O RM4 TG20 0.110

Control relays: rotational direction and presence of phases + undervoltageTime delay Rated mains

supply voltage (1)Control threshold

Width Output relay

Reference Weight

s V V mm kgWithout 220…240

50/60 HzUndervoltage160…220

22.5 2 C/O RM4 TU01 0.110

380…44050/60 Hz

Undervoltage300…430

22.5 2 C/O RM4 TU02 0.110

Control relays: rotational direction and presence of phases + overvoltage & undervoltageRelays with fixed voltage thresholdsAdjustable time delay Rated mains

supply voltage (1)Control threshold

Width Output relay

Reference Weight

s V V mm kg0.1...10 220

50/60 HzUndervoltage198Overvoltage242

22.5 2 C/O RM4 TR33 0.110

40050/60 Hz

Undervoltage360Overvoltage440

22.5 2 C/O RM4 TR34 0.110

Relays with adjustable voltage thresholdsAdjustable time delay Rated mains

supply voltage (1)Control threshold

Width Output relay

Reference Weight

s V V mm kg0.1…10 220…240

50/60 HzUndervoltage160…220Overvoltage220…300

22.5 2 C/O RM4 TR31 0.110

380…44050/60 Hz

Undervoltage300…430Overvoltage420…480

22.5 2 C/O RM4 TR32 0.110

Control relays: rotational direction and presence of phases + asymmetryTime delay on de-energisation

Rated mains supply voltage (1)

Control threshold

Width Outputrelay

Reference Weight

s V % mm kgFixed0.5

220...24050/60 Hz

Asymmetry5…15

22.5 1 C/O RM4 TA01 0.110

380…44050/60 Hz

Asymmetry5…15

22.5 1 C/O RM4 TA02 0.110

Adjustable0.1…10

220...24050/60 Hz

Asymmetry5…15

22.5 2 C/O RM4 TA31 0.110

380...44050/60 Hz

Asymmetry5…15

22.5 2 C/O RM4 TA32 0.110

(1) Can be used on other supply voltages provided that the minimum operational voltages, maximum voltage between phases and compatibility with the control threshold ranges are complied with, see page 3/91.

RM4 TG20

5610

24

RM4 TR33

5610

25

RM4 TA01

5610

26

Presentation :pages 3/88 to 3/90

Characteristics :page 3/91

Dimensions, schemes :page 3/93

3/93

3

Dimensions,schemes 3

Zelio Control - industrial measurement and control relays 3

3-phase supply control relays RM4 T

DimensionsRM4 T

Rail mounting Screw fixing

SchemesRM4 TG20, TU0���� RM4 TR3����, TA3���� RM4 TA0����

L1, L2, L3 Supply to be monitored L1, L2, L3 Supply to be monitored L1, L2, L3 Supply to be monitored

15(11)-18(14) 1st C/O contact of the output relay

15-18 1st C/O contact of the output relay

15-18 1st C/O contact of the output relay15(11)-16(12) 15-16 15-16

25(21)-28(24) 2nd C/O contact of the output relay

25-28 2nd C/O contact of the output relay25(21)-26(22) 25-26

Application schemeExample

80 22,5

78

89,5

82

66

78

L1 L2 L3

28 (24) 26 (22)18 (14)

25 (21)15 (11) 16 (12)

L1 L2 L3

2825 (2

1)

2616

(24)

(22)18

15 (11)

(14)

(12)

L1 L2 L3

18 15 1628 25 26

1815

16 2825

26

L1 L2 L3

L1 L2 L3

18 15 16

1815

16

L1 L2 L3

151816

252826

RM4 T

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

L3L2L1

N

Fault Start

Stop

Presentation :pages 3/88 to 3/90

References :page 3/92

Characteristics :page 3/91

3/94

3

Presentation 3 Zelio Control - industrial measurement and control relays 3

Voltage control relays RM4 U

1 Overvoltage setting potentiometer.2 Undervoltage setting potentiometer.3 Time delay function selector:

4 Potentiometer for setting time delay in seconds.

The voltage to be monitored is connected to terminals L1, L3 of the product.

There is no need to provide a separate power supply for RM4 UB relays, they are self-powered by terminals L1, L3.

If the voltage goes outside the range to be monitored, the output relay is de-energised:- overvoltage: the red LED “> U” illuminates,- undervoltage: the red LED “< U” illuminates.When the voltage returns towards its rated value, the relay is re-energised according to the hysteresis value (5 %) and the corresponding red LED goes out.A selector switch allows selection of an adjustable time delay from 0.1 s to 10 s. With function transient "over" or "under" voltages are not taken into account. With function all variations above or below are taken into account and re-energisation of the relay is delayed.In all cases, in order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms).

t : time delay

FunctionsThese devices are designed for monitoring single-phase voltages.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.

Applications� Protection of electronic or electromechanical devices against overvoltage and undervoltage.� Normal/emergency power supply switching.

PresentationRM4 UB

RM4 UB

12

3

4

RU

<U>U

Fault detection delayed.

Fault detection extended.

R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.> U Red LED: overvoltage fault.< U Red LED: undervoltage fault.

Operating principle

Function diagram

t t

< t

t t t t t

< t

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

RM4 UB34RM4 UB35

UL1 L3 0 Volt

Setting > U0.95 x Setting > U

1.05 x Setting < USetting < U

Function

Function

References :page 3/95

Characteristics :page 3/96

Dimensions, schemes : page 3/97

5610

37

3/95

3

References 3 Zelio Control - industrial measurement and control relays 3

Voltage control relays RM4 U

Relays with adjustable voltage thresholdsAdjustabletime delay

Control threshold

Width Output relay

Reference Weight

s V mm kg0.1…10 Undervoltage

80…12050/60 HzOvervoltage160…220

22.5 2 C/O RM4 UB34 0.110

Undervoltage160…22050/60 HzOvervoltage220…300

22.5 2 C/O RM4 UB35 0.110

RM4 UB

Presentation :page 3/94

Characteristics :page 3/96

Dimensions, schemes : page 3/97

5610

38

3/96

3

Characteristics 3 Zelio Control - industrial measurement and control relays 3

Voltage control relays RM4 U

Output relay and operating characteristicsNumber of C/O contacts 2

Output relay state Energised during fault free operation.De-energised on detection of an overvoltage or undervoltage fault

Accuracy of the switching threshold setting

As % of the set value ± 3 %

Switching threshold drift Depending on the permissible ambient temperature

≤ 0.06 % per degree centigrade

Within the measuring range ≤ 0.5 %

Accuracy of thetime delay setting

As % of the full scale value ± 10 %

Time delay drift Within the measuring range ≤ 0.5 %

Depending on the rated operational temperature

≤ 0.07 % per degree centigrade

Hysteresis Fixed About 5 % of the de-energisation threshold

Measuring cycle ms ≤ 80

Measuring input characteristicsMinimum operational voltage V RM4: 60

RM4 UB35: 160

Maximum permissible voltage between L1 and L3

V RM4 UB34: 300

RM4 UB35: 300

Presentation :page 3/94

References :page 3/95

Dimensions, schemes : page 3/97

3/97

3

Dimensions,schemes 3

Zelio Control - industrial measurement and control relays 3

Voltage control relays RM4 U

DimensionsRM4 UB

Rail mounting Screw fixing

Connection schemesRM4 UB

L1, L3 Voltage to be monitored

15-18 1st C/O contact 15-16 of the output relay

25-28 2nd C/O contact25-26 of the output relay

Application schemeExample

80 22,5

78

89,5

82

66

78

L1 L3

18 15 1628 25 26

1815

16 2825

26

L1 L3

151816

Q2

12

Q2

12

Q11/L1 2

3/L2 4

5/L3 6

Q4

RM4 UB

L3L1

Tosensitiveloads

Presentation :page 3/94

References :page 3/95

Characteristics :page 3/96

3/98

3

Presentation 3 Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

1 Adjustment of voltage threshold as % of setting range max. value.2 Hysteresis adjustment from 5 to 30 % (2).3 Fine adjustment of time delay as % of setting range max. value.4 Switch combining: - selection of the timing range: 1s, 3s, 10s, 30s, no time delay,- selection of overvoltage (>) or undervoltage (<) detection.

See table below.

(1) Selection by switch on front face.(2) Value of voltage difference between energisation and de-energisation of the output relay

(% of the voltage threshold to be measured).

FunctionsThese devices are designed to detect when voltage rises above or drops below a preset threshold, on an a.c. or a d.c. supply.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.

Relay type Voltage control Overvoltage or undervoltage detection (1)

Measuring range

RM4 UA0�� Yes No 50 mV…500 VRM4 UA3� Yes Yes 50 mV…500 V

Applications :- d.c. motor overspeed control,- battery monitoring,- monitoring of a.c. or d.c. supplies,- speed monitoring (with tacho-generator).

PresentationRM4 UA0�������� RM4 UA3����

Width 22.5 mm Width 22.5 mm

RM4 UA01

12

RU

1234

RU

R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.

Table showing details for switch 4Switch position Function Time delay (t)< 0 Undervoltage control No time delay< 1 Undervoltage control 0.05 to 1 s

< 3 Undervoltage control 0.15 to 3 s< 10 Undervoltage control 0.5 to 10 s< 30 Undervoltage control 1.5 to 30 s

> 0 Overvoltage control No time delay> 1 Overvoltage control 0.05 to 1 s> 3 Overvoltage control 0.15 to 3 s

> 10 Overvoltage control 0.5 to 10 s> 30 Overvoltage control 1.5 to 30 s

References :page 3/100

Characteristics :page 3/101

Dimensions, schemes :page 3/102

Setting-up :page 3/103

5610

46

3/99

3

Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

The supply voltage is connected to terminals A1-A2. The voltage to be monitored is connected to terminals B1, B2 or B3 and C.

Hysteresis is adjustable between 5 and 30%: for overvoltage h = (US1 - US2) / US1, for undervoltage h = (US2 - US1) / US1. A measuring cycle lasts only 80 ms, which allows rapid detection of changes in voltage.

Relay set for overvoltage detection (RM4 UA0� or selector on “>” for model RM4 UA3�) :If the voltage is > the setting threshold US1, the output relay is energised with or without a time delay. When the voltage returns to a value US2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.

Relay set for undervoltage detection (selector on “<”, model RM4 UA3� only):If the voltage is < the setting threshold US1, the output relay is energised with or without a time delay. When the voltage returns to a value US2 above the threshold, depending on the hysteresis setting, the relay is de-energised.

���� Functions� Overvoltage control

� Undervoltage control

Note: the measurement ranges can be extended above 500 V by adding a resistor, see page 3/103.The measurement range on � supply can be extended by means of a voltage transformer, the secondary of which is connected to the measuring terminals of the corresponding RM4.

Operating principle

Function diagrams

Voltagemeasured

Relay

Function “>”

t : time delay

t < t

US1US2

15-1815-16

25-2825-26

U supply A1-A2

Relay

Function “<”

t < t

US1US2

15-1815-16

25-2825-26

Voltagemeasured

U supply A1-A2

t : time delay

References :page 3/100

Characteristics :page 3/101

Dimensions, schemes :page 3/102

Setting-up :page 3/103

3/100

3

References 3 Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

Voltage measurement relays: overvoltage detectionTime delay Voltage to be

measured depending on connection���� or ��������

Width Output relay

Basic reference,to be completed by adding the voltage code (1)

Weight

V mm kgWithout 0.05...0.5 22.5 1 C/O RM4 UA01���� 0.168

0.3…3

0.5…5

1...10 22.5 1 C/O RM4 UA02���� 0.1685…5010…100

30...300 22.5 1 C/O RM4 UA03���� 0.168

50…500

Voltage measurement relays: overvoltage or undervoltage detectionAdjustabletime delay

Voltage to be measured depending on connection ���� or ����

Width Output relay

Basic reference, to be completed by adding the voltage code (1)

Weight

s V mm kg0.05...30 0.05...0.5 22.5 2 C/O RM4 UA31�������� 0.168

0.3…30.5…5

1...10 22.5 2 C/O RM4 UA32�������� 0.168

5…5010…100

30...300 22.5 2 C/O RM4 UA33�������� 0.16850…500

(1) Standard supply voltages

RM4 UA0��������

Volts 24 110...130 220...240� 50/60 Hz B F M

RM4 UA3���� Volts 24...240 110...130 220...240 380...415� 50/60 Hz MW F M Q� MW – – –

RM4 UA01

Presentation :pages 3/98 and 3/99

Characteristics :page 3/101

Dimensions, schemes :page 3/102

Setting-up :page 3/103

5610

46

3/101

3

Characteristics 3 Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

Power supply circuit characteristicsRelay type RM4 UA0�� RM4 UA3�

Rated supply voltage (Un) � 50/60 Hz V 24 110...130 220...240 24...240 110…130 220...240 380...415� V – – – 24...240 – – –

Average consumption at Un � VA 2 1.9…3.3 2.7…3.5 1.5…3.3 1.9…3.3 2.7…3.4 2.7…3

� W – – – 1.2 – – –

Output relay and operating characteristicsRelay type RM4 UA0�� RM4 UA3�

Number of C/O contacts 1 2

Output relay state Energised when:voltage measured > threshold setting

Energised when:voltage measured > threshold setting (“>” function)voltage measured < threshold setting (“<” function)

Setting accuracy of the switching threshold As % of the full-scale value: ± 5 %

Switching threshold drift % ≤ 0.06 per degree centigrade, depending on the permissible ambient temperature

% ≤ 0.5, within the supply voltage range (0.85…1.1 Un)

Hysteresis (adjustable) % 5…30 of the voltage threshold setting

Setting accuracy of the time delay As % of the full-scale value: ± 10 %

Time delay drift % – ≤ 0.5, within the supply voltage range (0.85…1.1 Un)

≤ 0.07 per degree centigrade, depending on rated operating temperature

Measuring cycle ms ≤ 80

Measuring input characteristicsInternal input resistance and permissible overload depending on the voltage measurement rangesRelay type RM4 UA�1 RM4 UA�2 RM4 UA����3

Measurement range� 50-60 Hz and �

V 0.05…0.5 0.3…3 0.5…5 1…10 5…50 10…100 30…300 50…500

Internal input resistance Ri kΩ 6.6 43 71 23 112 225 668 1111

Permissible continuous overload V 20 60 80 90 150 300 400 550

Permissible non repetitive overloadfor t ≤ 1 s

V 25 80 100 100 200 400 500 550

Presentation :pages 3/98 and 3/99

References :page 3/100

Dimensions, schemes :page 3/102

Setting-up :page 3/103

3/102

3

Dimensions,schemes 3

Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

DimensionsRM4 UA

� Rail mounting Screw fixing

SchemesRM4 UA01, UA02 RM4 UA03 RM4 UA31, UA32 RM4 UA33

A1-A2 Supply voltage Connection and current values to be measured, depending on type of RM4 UAB1, B2, Voltages to be measured RM4 UA�1 B1-C 0.05…0.5 V RM4 UA�2 B1-C 1…10 V RM4 UA�3 B2-C 30…300 V

B3, C (see table opposite) B2-C 0.3…3 V B2-C 5…50 V B3-C 50…500 VB3-C 0.5…5 V B3-C 10…100 V

Application schemeExample: overspeed monitoring (undervoltage function)

80 22,5

78

89,5

82 4

66

78

A1 A2 CB1 B3B2

18 16 15

1815

16

B3

B2

B1

A2

A1

C

A1 A2 CB3B2

18 16 15

1815

16

B3

B2

A2

A1

C

A1 A2 CB1 B3B2

2628 2518 16 15

1815

16

B3

2825

26

B2

B1

A2

A1

C

A1 A2 CB3B2

2628 2518 16 15

1815

16

B3

2825

26

B2

A2

A1

C

Q1

1/L1

2

3/L2

4

5/L3

6 Q41 2Q32 1

Q22 1

151816

252826

RM4 UA

KM1

KM1

A1

A2

B1

C

U

v

KM1

12

34

56

U1

W1

V1

M1 3

Tacho-generator

Overspeed

Stop

Start

Presentation :pages 3/98 and 3/99

References :page 3/100

Characteristics :page 3/101

Setting-up :page 3/103

3/103

3

Setting-up 3 Zelio Control - industrial measurement and control relays 3

Voltage measurement relays RM4 U

Undervoltage threshold to be measured: 12 V �.Output relay time delay: 20 s.Reset voltage threshold: 13.2 VSupply voltage: 230 V at � 60 Hz.

� Adjustments:� Adjustment of function and timing range, switch 4:- determine the timing range, immediately greater than the time required; in the above example 30 s,- determine whether overvoltage or undervoltage detection is required; in this example, undervoltage,- position switch 4 according to the above 2 criteria; in this example, switch 4 on < 30.� Fine adjustment of time delay:Depending on the max. range setting displayed at 4 (in the above example: 30 s) use potentiometer 3 to set the required time delay as a % of value 4.In the above example, the required time = 20 s therefore :

� Set the voltage threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring.In the above example: wiring B2-C, max. value of measuring range = 50 V, therefore:

� Set the hysteresis 2 as a % of the threshold value; in this example:

Setting-upExample of undervoltage to be measured

Product selected RM4 UA32MConnection of voltage to be measured B2-C (5 to 50 V)

Set the time delay potentiometer 3 to 66.

Setting 1 = = 24 % Set the voltage threshold setting potentiometer 1 to 24.

Setting 2 = = 10 % Set the hysteresis 2 to 10.

1234

RU

t x 1004

20 x 10030

= 66 %=

12 x 10050

13.2 - 1212

Extension of the measuring range

���� or ���� supply

Simply connect an additional resistor (Rs) in series with the measuring input B3 or C.If the value of Rs is in the region of: Rs = Ri where:

Ri Internal resistance of input B3-C.Um Maximum value of threshold setting range.U Voltage threshold to be measured.

The tripping threshold of the relay will be towards the maximum graduation on the threshold setting potentiometer.In general, the power consumed by the resistor does not exceed 0.5 W.For a.c. voltages, it is also possible to use a voltage transformer.

Supply by the measured voltage For monitoring mains and power supplies, the

RM4 UA can be supplied by the voltage to be controlled, provided that:- the measurement threshold is within the operating range of the product's power supply (0.85…1.1 Uc), - variations of the voltage to be measured are compatible with the supply and measurement voltage ranges.

RsC

B3

Ri U > 500 V

RM4 UA33U

Um -1

A1

A2

B2/B3

C

RM4 UA

Presentation :pages 3/98 and 3/99

References :page 3/100

Characteristics :page 3/101

Dimensions, schemes :page 3/102

3/104

3

Presentation 3 Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

1 Adjustment of current threshold as % of setting range max. value.2 Hysteresis adjustment from 5 to 30 % (2).3 Fine adjustment of time delay as % of setting range max. value.4 10-position switch combining: - selection of the timing range: 1 s, 3 s, 10 s, 30 s, no time delay,- selection of overcurrent (>) or undercurrent (<) detection.

See table below.

(1) Selection by switch on front face.(2) Value of current difference between energisation and de-energisation of the output relay

(% of the current threshold to be measured).

FunctionsThese devices are designed to detect when current rises above or drops below a preset threshold, on an a.c. or a d.c. supply.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.

Relay type Overcurrent detection

Overcurrent or undercurrent detection (1)

Measuring range

RM4 JA01 Yes No 3 mA…1 ARM4 JA31 Yes Yes 3 mA…1 ARM4 JA32 Yes Yes 0.3 A…15 A

Applications :- excitation control of d.c. machines,- control of load state of motors and generators,- control of current drawn by a 3-phase motor,- monitoring of heating or lighting circuits,- control of pump draining (undercurrent),- control of overtorque (crushers),- monitoring of electromagnetic brakes or clutches.

DescriptionRM4 JA01 RM4 JA31 RM4 JA32

Width 22.5 mm Width 22.5 mm Width 45 mm

RM4 JA01

RM4 JA32

12

RU

1234

RU

1234

RU

R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.

Table showing details for switch 4Switch position Function Time delay (t)< 0 Undercurrent detection No time delay

< 1 Undercurrent detection 0.05 to 1 s< 3 Undercurrent detection 0.15 to 3 s< 10 Undercurrent detection 0.5 to 10 s

< 30 Undercurrent detection 1.5 to 30 s> 0 Overcurrent detection No time delay> 1 Overcurrent detection 0.05 to 1 s

> 3 Overcurrent detection 0.15 to 3 s> 10 Overcurrent detection 0.5 to 10 s> 30 Overcurrent detection 1.5 to 30 s

References :page 3/106

Characteristics :page 3/107

Dimensions, schemes :page 3/108

Setting-up :page 3/109

5610

6156

1062

3/105

3

Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

The supply voltage is connected to terminals A1-A2.The current to be monitored is connected to terminals B1, B2, B3 and C. See diagram below.

Hysteresis is adjustable between 5 and 30 %: for overcurrent h = (IS1 - IS2) / IS1, for undercurrent h = (IS2 - IS1) / IS1.A measuring cycle lasts only 80 ms, which allows rapid detection of changes in current.

Relay set for overcurrent detection (RM4 JA01 or selector on “>” for model RM4 JA3�).If the current is > the setting threshold IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.

Relay set for undercurrent detection (selector on “<”, model RM4 JA3� only).If the current is <, the setting threshold IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 above the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.

� Functions� Undercurrent detection

� Overcurrent detection

Note: The measurement ranges can be extended by means of a current transformer, the secondary of which is connected to the measuring terminals of the RM4 relay, or by means of a resistor connected in parallel with the measuring input (see example page 3/109 “Setting-up”).

Operating principle

Function diagrams

t < t

IS1IS2

15-1815-16

25-2825-26

A1-A2

Current measured

Relay

U supplyFunction “<”

t : time delay

B1, B2, B3RM4 JA

C

LoadU drop < 1 V

Mea

sure

men

t

t < t

IS1IS2

15-1815-16

25-2825-26

A1-A2

Currentmeasured

Relay

U supplyFunction “>”

t : time delay

References :page 3/106

Characteristics :page 3/107

Dimensions, schemes :page 3/108

Setting-up :page 3/109

3/106

3

References 3 Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

Overcurrent detectionTime delay Current to

be measured depending on connection���� or ��������

Width Output relay

Basic reference,to be completed by adding the voltage code (1)

Weight

s mm kgWithout 3...30 mA 22.5 1 C/O RM4 JA01���� 0.172

10...100 mA

0.1...1 A

Overcurrent or undercurrent detectionAdjustabletime delay

Current to be measured depending on connection���� or ��������

Width Output relay

Basic reference, to be completed by adding the voltage code (1)

Weight

s mm kg0.05...30 3...30 mA 22.5 2 C/O RM4 JA31�������� 0.172

10...100 mA

0.1...1 A

0.3...1.5 A 45 2 C/O RM4 JA32������������ 0.204

1...5 A3...15 A

(1) Standard supply voltages

RM4 JA01 Volts 24 110...130 220...240� 50/60 Hz B F M

RM4 JA31 Volts 24...240 110...130 220...240 380...415and RM4 JA32 � 50/60 Hz MW F M Q

� MW – – –

RM4 JA01

RM4 JA32

Presentation :pages 3/104 and 3/105

Characteristics :page 3/107

Dimensions, schemes :page 3/108

Setting-up :page 3/109

5610

6856

1069

3/107

3

Characteristics 3 Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

Power supply circuit characteristicsRelay type RM4 JA01 RM4 JA31 and RM4 JA32

Rated supply voltage (Un) � 50/60 Hz V 24 110...130 220...240 24...240 110…130 220...240 380...415� V – – – 24...240 – – –

Average consumption at Un � VA 2 1.9…3.3 2.7…3.5 1.5…3.3 1.9…3.3 2.7…3.4 2.7…3

� W – – – 1.2 – – –

Output relay and operating characteristicsRelay type RM4 JA01 RM4 JA31 and RM4 JA32

Number of C/O contacts 1 2

Output relay state Energised when: current measured > threshold setting

Energised when:current measured > threshold setting (“>” function)current measured < threshold setting (“<” function)

Setting accuracy of the switching threshold As % of the full-scale value: ± 5 %

Switching threshold drift % ≤ 0.06 per degree centigrade, depending on the permissible ambient temperature

% ≤ 0.5, within the supply voltage range (0.85…1.1 Un)

Hysteresis (adjustable) % 5…30 of the current threshold setting

Setting accuracy of the time delay As % of the full-scale value: ± 10 %

Time delay drift % – ≤ 0.07 per degree centigrade, depending on temperature

≤ 0.5, within the supply voltage range(0.85… 1.1 Un)

Measuring cycle ms ≤ 80

Measuring input characteristicsInternal input resistance and permissible overload depending on the current measurement rangesRelay type RM4 JA01 and RM4 JA31 RM4 JA32

Measurement range��50-60 Hz and ����

3…30 mA 10…100 mA 0.1…1 A 0.3…1.5 A 1… 5 A 3… 15 A

Internal input resistance Ri Ω 33 10 1 0.06 0.02 0.006

Permissible continuous overload A 0.05 0.15 1.5 2 7 20

Permissible non repetitive overloadfor t ≤ 3 s

A 0.2 0.5 5 10 15 100

Presentation :pages 3/104 and 3/105

References :page 3/106

Dimensions, schemes :page 3/108

Setting-up :page 3/109

3/108

3

Dimensions,schemes 3

Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

DimensionsRM4 JA (common side view) RM4 JA���� RM4 JA32

Rail mounting Screw fixing �

Connection schemesRM4 JA01 RM4 JA31 RM4 JA32

A1-A2 Supply voltage Connection and current values to be measured, depending on type of RM4 JA

B1, B2, Currents to be measured RM4 JA01 B1-C 3…30 mA RM4 JA32 B1-C 0.3…1.5 AB3, C (see table opposite) & RM4 JA31 B2-C 10…100 mA B2-C 1…5 A

B3-C 0.1…1 A B3-C 3…15 A

Application schemesExample: detection of blockage on a crusher (overcurrent function)

Current measured ≤ 15 A Current measured > 15 A

80 22,5

78

45

78

89,5

82 66

78

A1 A2 CB1 B3B2

18 16 15

1815

16

B3

B2

B1

A2

A1

C

A1 A2 CB1 B3B2

2628 2518 16 15

1815

16

B3

2825

26

B2

B1

A2

A1

C

A1 A2 C B1 B2 B3

18 16 15 28 26 25

1815

16

B3

2825

26

B2

B1

A2

A1

C

151816

252826

RM4 JA3

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

B3

C

A1

A2

N

Overtorque Start

Stop

151816

252826

RM4 JA3

KM1

KM1

1/L1

2

3/L2

4

5/L3

6

Q1

2/T

1

4/T

2

6/T

3

1

Q2

3 5

KM1

12

34

56

U1

W1

V1

M1 3

B3

C

A1

A2

N

Overtorque Start

Stop

Presentation :pages 3/104 and 3/105

References :page 3/106

Characteristics :page 3/107

Setting-up :page 3/109

3/109

3

Setting-up 3 Zelio Control - industrial measurement and control relays 3

Current measurement relays RM4 J

Overcurrent threshold at: 13 A.Output relay time delay: 5 s.Reset current threshold: 11 ASupply voltage: 127 V ����

� Adjustments:� Adjustment of function and timing range, switch 4:- determine whether overcurrent or undercurrent detection is required; in this example, overcurrent,- determine the timing range, immediately greater than the time required; in this example 10 s,- position switch 4 according to the above 2 criteria; in this example, switch 4 on > 10.� Fine adjustment of time delay:Depending on the max. range setting displayed at 4 (in the above example: 10 s) use potentiometer 3 to set the required time delay as a % of value 4.In the above example, the required time = 5 s therefore:

� Set the current threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring.In the above example: wiring B3-C, max. value of measuring range = 15 A, therefore:

� Set the hysteresis 2 as a % of the threshold value; in this example:

� d.c. or a.c. supplySimply connect a resistor “Rs” to terminals B1-C (or B2, B3-C) on the measuring input.The relay energisation threshold will be towards the middle of the setting potentiometer range if the value of Rs is in the region of:

� Application: Use of relay RM4 JA31�� (10 to 100 mA).Connection B2-C to measure a threshold of 1 A, knowing that Ri = 10 Ω for this rating and that Im = 100 mA.The value of Rs will be: = 0.526 Ω

P = (1 - ) 2 x 0.526 i.e. 0.47 W

Select a resistor Rs capable of dissipating at least twice the calculated value, i.e. 1 W for this example, in order to limit temperature rise.On an a.c. supply, it is also possible to use a current transformer.

Setting-UPExample of overcurrent to be measured

Product selected RM4 JA32MWConnection of current to be measured B3-C (3 to 15 A)

Set the time delay potentiometer 3 to 50.

Setting 1 = = 87 % Set the current threshold setting potentiometer 1 to 87.

Setting 2 = = 15.4 % Set the hysteresis 2 to 15(13 - 11 = 2 i.e. 15.4 % of the current to be measured).

1234

RU

t x 1004

5 x 10010

= 50 %=

13 x 10015

13 - 1113

Extension of the measuring range

Rs = where:

Ri Internal resistance of input B1-C,Im Maximum value of threshold setting range, I Current threshold to be measured.

Power dissipated by Rs: P = Rs (I -Im/2)2

Rs

B1

C

RM4 JA

Ri

Ii = Im/2 I

Ri(2I/Im) - 1

10(2 x 1/0.1) - 1

0.12

Presentation :pages 3/104 and 3/105

References :page 3/106

Characteristics :page 3/107

Dimensions, schemes :page 3/108

3/110

3

Presentation 3 Zelio Control - industrial measurement and control relays 3

Liquid level control relays RM4 L

FunctionsThese devices monitor the levels of conductive liquids.They control the actuation of pumps or valves to regulate levels and are also suitable for protecting submersible pumps against running empty, or protecting tanks from "overflow". They can also be used to control dosing of liquids in mixing processes and to protect heating elements in the event of non immersion.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.

� Compatible liquids:� spring, town, industrial and sea water,� metallic salt, acid or base solutions,� liquid fertilizers,� non concentrated alcohol (< 40 %),� liquids in the food-processing industry: milk, beer, coffee, etc.

� Non-compatible liquids:� chemically pure water,� fuels, liquid gasses (inflammable),� oil, concentrated alcohol (> 40 %),� ethylene, glycol, paraffin, varnish and paints.

DescriptionRM4 LG01 RM4 LA32

Width 22.5 mm Width 22.5 mm

1 Fine adjustment of time delay (as % of setting range max. value).2 Fine adjustment of response sensitivity (as % of setting range max. value).3 Function selector switch:

- empty or fill .4 Switch combining:

- selection of the response sensitivity range,- selection of time delay on energisation or on de-energisation of the relay.

RM4 LG01

RM4 LA32

23R

U

12

4RU

3

R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.

Table showing details for switch 4Switch position Time delay Sensitivity500 On-delay High = 500 kΩ range

500 Off-delay High = 500 kΩ range50 On-delay Medium = 50 kΩ range50 Off-delay Medium = 50 kΩ range

5 On-delay Low = 5 kΩ range5 Off-delay Low = 5 kΩ range

References :page 3/112

Characteristics :page 3/113

Dimensions, schemes :page 3/114

Setting-up :page 3/115

5610

7856

1079

3/111

3

Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3

Liquid level control relays RM4 L

The operating principle is based on a change in the resistance measured between immersed or non-immersed electrodes. Low resistance between electrodes: liquid present. High resistance between electrodes: no liquid present. The electrodes may be replaced by other sensors or probes which transmit values representing variations in resistance.The a.c. measuring voltage which is < 30 V and galvanically insulated from the supply and contact circuits, ensures safe use and the absence of any electrolysis phenomena.RM4 relays may be used:� For detection of a liquid level, operating with 2 electrodes, one reference electrode and one high level electrode, or an LA9 RM201 probe. Example: prevention of tank overflow.� For regulating a liquid level between a minimum and a maximum level, operating with 3 electrodes, one reference electrode, one low level electrode and one high level electrode, or two LA9 RM201 probes. Example: water tower.The state of the output relay can be configured:� Empty function : the output relay is energised when high level electrode B2 is immersed and is de-energised when low level electrode B3 is "dry" (1).� Fill function : the output relay is energised when the low level electrode is "dry" and is de-energised when high level electrode is immersed (1).On model RM4 LA32 a time delay can be set on energisation or de-energisation of the output relay in order to raise the maximum level function or to lower the minimum level function .This function also makes it possible to avoid pulsing of the output relay (wave effect) when operating with 2 electrodes .

Operating principle

Function diagrams

���� Empty function��Maximum level detection (2 electrodes or 1 probe LA9 RM201)

��Regulation between a maximum and a minimum level (3 electrodes or 2 probes LA9 RM201)

���� Full function��Maximum level detection (2 electrodes or 1 probe LA9 RM201)

��Regulation between a maximum and a minimum level (3 electrodes or 2 probes LA9 RM201)

B1 : reference electrode B2 : high level electrode B3 : low level electrode

(1) When operating with 2 electrodes, the high level electrode performs both high and low level functions.

tt

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

15/18

LA32

LA32

LG01 Ð 15/16

B1 B2B1 B2B1 B2TypeRM4-

Function switch 3

Time delay switch 4

U supplyA1/A2

t t

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

15/1815/16

B1 B3 B2B1 B3 B2B1 B3 B2B1 B3 B2

LA32

LA32

LG01 Ð

TypeRM4-

Function switch 3

Time delay switch 4

U supplyA1/A2

LA32

LA32

LG01 Ðtt

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

15/1815/16

B1 B2B1 B2B1 B2TypeRM4-

Function switch 3

Time delay switch 4

U supplyA1/A2

tt

15/18 25/2815/16 25/26

15/18 25/2815/16 25/26

15/1815/16

B1 B3 B2B1 B3 B2B1 B3 B2B1 B3 B2

LA32

LA32

LG01 Ð

TypeRM4-

Function switch 3

Time delay switch 4

U supplyA1/A2

References :page 3/112

Characteristics :page 3/113

Dimensions, schemes :page 3/114

Setting-up :page 3/115

3/112

3

References 3 Zelio Control - industrial measurement and control relays 3

Liquid level control relays RM4 L

Liquid level control relaysTime delay Sensitivity

scaleWidth Output

relayBasic reference, to be completed by adding the voltage code (1)

Weight

kΩ mm kgWithout 5…100 22.5 1 C/O RM4 LG01���� 0.165

Adjustable 0.1...10 s

0.25 ...5 22.5 2 C/O RM4 LA32�������� 0.1652.5 ...5025 ...500

Level control probe for liquid Type of installation Maximum operating

temperatureReference Weight

°C kgSuspended by cable 100 LA9 RM201 0.100

(1) Standard supply voltages

RM4 LG01 Volts 24 110...130 220...240 380...415� 50/60 Hz B F M Q

RM4 LA32 Volts 24...240 24 110...130 220...240 380...415� 50/60 Hz MW B F M Q� MW – – – –

RM4 LG01

RM4 LA32

LA9 RM201

Presentation :pages 3/110 and 3/111

Characteristics :page 3/113

Dimensions, schemes :page 3/114

Setting-up :page 3/115

5610

8756

1089

5610

88

3/113

3

Characteristics 3 Zelio Control - industrial measurement and control relays 3

Liquid level control relays RM4 L

Power supply circuit characteristicsRelay type RM4 LG01 RM4 LA32

Rated supply voltage (Un) � 50/60 Hz V 24 110...130 220...240 380...415 24...240 24 110...130 220...240 380...415

� V – – – – 24...240 – – – –

Average consumptionat Un

� VA 1.9 2.6 2.4 2.9 2.7 3.1 2.7 2.6 3.4

� W – – – – 2.4 – – – –

Output relay and operating characteristicsNumber of C/O contacts 1 2

Output relay state Can be configured by switch: empty / fill

Electrode circuit characteristics (1)

Sensitivity scale kΩ 5…100 (adjustable) 0.25…5 2.5…50 25…500

Maximum a.c. electrode voltage(peak to peak)

V 24 24

Maximum current in the electrodes mA 1

Maximum cable capacity nF 10 200 25 4

Maximum cable length m 100 1000 100 20

(1) The electrodes may also be incorporated in the probes. The probes are normally designed for fixing to a tank by means of a bracket with a seal (closed tanks) or suspended by their own electrical connecting cable (boreholes, etc.). See page 3/115 “Setting-up” Probe LA9-RM201.

Presentation :pages 3/110 and 3/111

References :page 3/112

Dimensions, schemes :page 3/114

Setting-up :page 3/115

3/114

3

Dimensions,schemes 3

Zelio Control - industrial measurement and control relays 3

Liquid level control relays RM4 L

DimensionsRM4 LG01, LA32

Rail mounting Screw fixing

Probe LA9 RM201

Connection schemesRM4 LG01 RM4 LA32

A1-A2 B1, B2, B3

Supply voltageElectrodes(see table opposite)

Electrodes and level controlled

B1 Reference or tank earth electrode15-18 1st C/O contact

of the output relay15-16 B2 High level

25-28 2nd C/O contactof the output relay25-26 B3 Low level

22,5

78

80 89,5

82 Ø4

66

78

150

16

B1 B2A1 15

B3

18 16 A2

1815

16

B3

B2

B1

A2

A1

B1 B2A1 15

B325

18 16 A228 26

1815

16

B3

26 2825B

2

B1

A2

A1

Presentation :pages 3/110 and 3/111

References :page 3/112

Characteristics :page 3/113

Setting-up :page 3/115

3/115

3

Setting-up 3 Zelio Control - industrial measurement and control relays 3

Liquide level control relays RM4 L

� Select the empty /fill function according to the sequence to be performed.� If necessary, set potentiometer 1 to minimum (time delay).� Set potentiometer 2 to minimum; on RM4-LA, select the lowest sensitivity range using potentiometer 4 (5 or 5 ).� With all the electrodes immersed, turn the sensitivity potentiometer towards maximum until the relay is energised ( function) or de-energised ( function), then exceed the threshold by about 10 % to compensate for variation in the supply voltage.If the relay is not able to energise, a higher sensitivity scale must be used (selector 4 on RM4 LA32) or relay RM4 LG must be replaced by an RM4 LA32 relay and the adjustment procedure must be started again.� Then check that the relay de-energises ( function) or energises ( function) as soon as electrodes B3 and B2 are out of the liquid. If the relay does not de-energise, select a lower sensitivity scale.

This probe is of the "suspension" type. It is coaxial, i.e. in addition to the normal (central) electrode, the stainless steel skirt can also act as earth (reference electrode), which means that there is no need to install a separate reference probe. In this way, for controlling one level, only one probe is required instead of 2; for controlling 2 levels, only 2 probes are required instead of 3.

Setting-up

� The electrode connection point must be protected against corrosion by sticking or sealing. In areas where thunderstorms are likely to occur, measures must also be taken to protect the electrode lines.Note: the high level can be raised by means of the adjustable time delay from 0.1 to 10 seconds with function .The low level can be lowered by means of this same time delay with function .

RM4 LG01 RM4 LA32

23R

U

12

4RU

3

Probe LA9 RM201

The connecting cable must be of the "2-conductor" type, with common cylindrical PVC sheath, having a maximum diameter of 6.3 mm. The skirt also acts as a "calming chamber", so avoiding inaccuracy due to an agitated surface of the liquid (waves).Maximum operating temperature: 100 °C.Probe LA9 RM201 can also be fixed on various containers (cisterns, tanks, ...) by means of a bracket or other suitable fixing device.

LA9 RM201

2-conductor cable in cylindrical sheath(max Ø 6.3 mm)

Level electrode

Reference electrode(skirt)

Connection examples

���� Control by electrodes

���� Control by probes

B3

B2

B1

A1 B2 B3B1

A2

High level

Low level

Sup

ply

volta

ge

B1B2

B3B2

B1

RM4 LG01

2 levels 1 level

Presentation :pages 3/110 and 3/111

References :page 3/112

Characteristics :page 3/113

Dimensions, schemes :page 3/114

3/116

3

Functions,schemes 3

Zelio Control - industrial measurement and control relays 3

Plug-in liquid level control relays RM 84 870

The output relay changes state when the level of the liquid reaches the maximum level probe, with the minimum level probe submerged. It returns to its initial state when the minimum level probe is no longer in contact with the liquid.

� Controlling the levels of conductive liquids� Regulation of two thresholds:� minimum,� maximum.� Emptying function.� Plug-in, 8 or 11-pin.� Sensitivity adjustable from 5 kΩ to 100 kΩ.

Operating principleControl of maximum and/or minimum levels of conductive liquids (tap water, sea water, waste water, chemical solutions, coffee ...).

The operating principle is based on measurement of the apparent resistance of the liquid between two submerged probes. When this value is less than the threshold setting on the front panel of the device, the output relay changes state. To avoid electrolytic phenomena, an a.c. current runs across the probes.

Applications in the food-processing, chemical industries, etc.

Regulation of two levels, minimum/maximum

Emptying control

Connection scheme

For RM 84 870 807 (special 11-pin base fitting), pin 5 must be connected to “a” (maximum) and pin 7 must be connected to “c” (common).

Un

T

Energisation of the device

Level being controlled

Emptying function

Max. level

Min. level

Output relay Down

R S T

M P

12

3

45 6

7

8

10

9

11 1

2

3

4 5

67

8

a

bc

c b a

a - Maximumb - Minimumc - Common

8-pin11-pin

Input

References :page 3/117

Characteristics :page 3/117

Dimensions :page 3/117

3/117

3

References, characteristics,dimensions 3

Zelio Control - industrial measurement and control relays 3

Plug-in liquid level control relays RM 84 870

ReferencesLiquid level control relays

Number of pins Voltage Reference Weightkg

8-pin ��24 V RM 84 870 301 0.140

��120 V RM 84 870 303 0.140

��230 V RM 84 870 304 0.140

11-pin ��24 V RM 84 870 306 0.140

��120 V RM 84 870 308 0.140

��230 V RM 84 870 309 0.140

Special 11-pin base fitting ��230 V RM 84 870 807 0.190

Accessories

Description Sold in lots of Unit reference Weightkg

11-pin socket 10 RUZ 1A 0.067

Note: The probe cable, with a maximum length of 100 metres (recommended probes, see page 3/58) need not be screened, but it is inadvisable to fit it in parallel with the power supply cables.Screened cable may be used, with the screening connected to the common.

CharacteristicsSupply voltage Un V � 24, 120, 230 (50/60 Hz)

Operating range 0.85…1.15 x Un

Maximum power consumption VA 3

Sensitivity adjustment kΩ 5…100

Measurement accuracy(at maximum sensitivity)

0…+ 30 %

Maximum electrode voltage V � 24 (50/60 Hz)

Maximum electrode current mA 1 (50/60 Hz)

Maximum cable capacity nF 10

Response time High level ms 300

Low level ms 500

Output relay (to meet AC-1 requirements, resistive load) 1 C/O contact, AgCdO � 8 A max.

Galvanic isolation via transformer(4 kV, 8 mm creepage distance)

Class II VDE 0551

Isolation of contacts and electrodes from the supply kV � 2.5

Temperature limits Operation °C - 20…+ 60 Storage °C - 30…+ 70

Product certifications c UL us, CSA

Dimensions

RM 84 870 303

5610

08

70 39

50

163,5

Functions :page 3/116

Scheme :page 3/116

3/118

3

Functions,scheme 3

Zelio Control - industrial measurement and control relays 3

Plug-in liquid level control relays RM 84 870, combined fill/empty functions

For RM 84 870 808 (special 11-pin base fitting), pin 5 must be connected to “a” (maximum) and pin 7 must be connected to “c” (common).

� Controlling the levels of conductive liquids.� Combined fill/empty function.� Combined regulation of emptying a well and filling a tank.� Plug-in, 11-pin.� Output relay state indication LED.� Sensitivity adjustable from 5 kΩ to 100 kΩ

Operating principleCombined fill/empty function

The output relay changes state when the level of the liquid in the tank reaches the maximum level probe, with the minimum level probe submerged. It returns to its initial state when the minimum level probe is no longer in contact with the liquid.

When the level of the liquid in the well reaches the minimum level probe, the pump stops.

If, on energisation or after a power cut, the maximum level probe in the tank is above the liquid level, reset the device by pressing button BP.

Emptying control

(1) Pushbutton

Connection scheme

Un

(1)(1)(1)Max. levelWellMin. level

Output relay

Max. levelTankMin. level

R S T

M P

12

34

a

bc

5 67

8

109

11

TankWell

Pushbutton

Output

Input

a : maximumb : minimumc : common

References :page 3/119

Characteristics :page 3/119

Dimensions :page 3/119

3/119

3

References, characteristics,dimensions 3

Zelio Control - industrial measurement and control relays 3

Plug-in liquid level control relays RM 84 870, combined empty/fill functions

ReferencesLiquid level control relays

Number of pins Voltage Reference Weightkg

11-pin ��24 V RM 84 870 401 0.140

��120 V RM 84 870 403 0.140

��230 V RM 84 870 404 0.140

Special 11-pin base fitting ��230 V RM 84 870 808 0.190

Accessories

Description Sold in lots of Unit reference Weightkg

11-pin socket 10 RUZ 1A 0.067

Note: The probe cable, with a maximum length of 100 metres (recommended probes, see page 3/58) need not be screened, but it is inadvisable to fit it in parallel with the power supply cables.Screened cable may be used, with the screening connected to the common.

CharacteristicsSupply voltage Un V � 24, 120, 230 (50/60 Hz)

Operating range 0.85…1.15 x Un

Maximum power consumption VA 3

Sensitivity adjustment kΩ 5…100

Measurement accuracy(at maximum sensitivity)

0…+ 30 %

Maximum electrode voltage V � 24 (50/60 Hz)

Maximum electrode current mA 1 (50/60 Hz)

Maximum cable capacity nF 10

Response time High level ms 300Low level ms 500

Output relay (to meet AC-1 requirements, resistive load) 1 C/O contact, AgCdO � 8 A max.

Galvanic isolation via transformer(4 kV, 8 mm creepage distance)

Class II VDE 0551

Isolation of contacts and electrodes from the supply kV � 2.5

Ambient air temperature Operation °C - 20…+ 60 Storage °C - 30…+ 70

Product certifications c UL us, CSA

Dimensions

RM 84 870 40�

5610

09

70 39

50

163,5

Functions :page 3/118

Scheme :page 3/118