smart relay zelio logic sr2 sr3 sr2pack sr3pack module extension zelio
TRANSCRIPT
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
1/72
Smart relays
Zelio Logic
06CatalogueNovember
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
2/72
This international site allows you to access all theTelemecanique products in just 2 clicks viacomprehensive range data-sheets, with direct
links to:1 Complete library: technical documents, catalogs,certificates, FAQs, brochures...
1 Selection guides from the e-catalog.1
Product discovery sites and their Flashanimations.
You will also find illustrated overviews, news to
which you can subscribe, a discussion forum, thelist of country contacts...To live automation solutions every day!
123456525781 Interchangeable
modular functions,
to better meet therequirements for
extensions
1
Software andaccessories common to
multiple product families
9731
High functionality in a
minimum of space1 Freedom in
implementation
35781
Auto-adapts to itsenvironment, "plug &
play"
1 Application functions,control, communication
and diagnostics
embedded in theproducts
1 User-friendly
operation either directlyon the product orremotely
331 Compliance with fieldbus, connection, and
software standards1 Enablingdecentralised or remote
surveillance via the webwith Transparent Readyproducts
5255781 Cost effective
optimum offers that
make selection easy formost typical applications
1 Products that areeasy to understand forusers, electricians and
automation specialists
1 User-friendly intuitiveprogramming
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
3/721
Contents 0 Zelio Logic smart relays1
Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 2 to 5
Compact and modular smart relays1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6 to 9
1
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 10 to 12
1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 14 to 19
1 Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 20 and 21
1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 22 to 27
1
Dimensions, mounting, schemes. . . . . . . . . . . . . . . . . . . . . . . . . . pages 28 to 31
Communication1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Programming protocol1 Description, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 33
Modbus slave communication protocol1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 34
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 35
1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36
Ethernet server communication protocol1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 37
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Communication1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
1 Dimensions, mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 41
Analogue I/O extension modules1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 42
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
1
References, dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . pages 44 and 45
Modem communication interface1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 46 and 47
1 Functions, setting-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 48 and 49
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 50 and 51
1
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 521 Dimensions, connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 53 to 55
Analogue interfacesSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 56 and 57
1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 58 and 59
1
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 60 and 61
1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 62
1 Dimensions, mounting, schemes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63
Powers supplies and transformers1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 64
1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 65 to 68
1 References, dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 69
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
4/722
Selection guide 1 Zelio Logic smart relays 1Compact smart relays
Product type Compact smart relays
Supply voltage1111
24 V1111
100240 V
Number of I/O 12 20 10 12 20
Number of discrete inputs(of which analogue inputs)
8 (0) 12 (0) 6 (0) 8 (0) 12 (0)
Number of relay/transistor outputs 4/0 8/0 4/0 4/0 8/0
With display, with clockProgramming language
SR2 B2 2
2 22 2
2 2
1BFBD or LADDER
SR2 B2 2
2 22 2
2 2
1FUFBD or LADDER
With display, without clockProgramming language
SR2 A2 22 22 22 2
1FULADDER only
Without display, with clockProgramming language
SR2 E2 2
2 22 2
2 2
1BFBD or LADDER
SR2 E2 2
2 22 2
2 2
1FUFBD or LADDER
Without display, without clockProgramming language
SR2 D2 22 22 22 2
1FULADDER only
Programming software (see page 26) Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01
Connectionaccessories(see page 26)
Serial link connecting cable SR2 CBL01 SR2 CBL01
USB connecting cable SR2 USB01 SR2 USB01
Bluetooth interface SR2 BTC01 SR2 BTC01
Memory cartridge (see page 26) SR2 MEM02(1incompatible with SR2 COM01)
SR2 MEM02(1incompatible with SR2 COM01)
Discovery packs (see page 22) SR2 PACK2222
FU
Modem communication interface (see page 52) SR2 COM01 SR2 COM01 (for SR2B and SR2E)
Alarm management software (see page 52) Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02
Converters (thermocouple types J and K, Pt100 probesand voltage/current) (see page 62)
Power supplies for d.c. control circuit(see page 69)
References SR2 1 1 11 1 11 1 1
1 1 1 1B SR2 1 1 11 1 11 1 1
1 1 1 1FU
Pages 22 and 23 22 and 23
(1) FBD: Function Block Diagram.
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
5/723
11
3333
12 V3333
24 V
12 20 10 12 20
8 (4) 12 (6) 6 (0) 8 (4) 12 (2), 12 (6)
4/0 8/0 4/0 4/0, 0/4 8/0, 0/8
SR2 B2 2
2 22 2
2 2
1JDFBD or LADDER
SR2 B2 2 2
2 2 22 2 2
2 2 2
BDFBD or LADDER
SR2 A2 2 22 2 22 2 22 2 2
BDLADDER only
SR2 E2 2 2
2 2 22 2 2
2 2 2
BDFBD or LADDER
SR2 D2 2 22 2 22 2 22 2 2
BDLADDER only
Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01
SR2 CBL01 SR2 CBL01
SR2 USB01 SR2 USB01
SR2 BTC01 SR2 BTC01
SR2 MEM02(1incompatible with SR2 COM01)
SR2 MEM02(1incompatible with SR2 COM01)
SR2 PACK2222
BD
SR2 COM01 SR2 COM01 (for SR2 B and SR2 E)
Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02
RM2
22
2 2 2 2
2 2 22 2 2
2 2 2
BD RM2
22
2 2 2 2
2 2 22 2 2
2 2 2
BD
ABL 7RM1202 ABL 7RM2401 1
SR2 B 1 11 11 1
1 1 1JD SR2 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 BD
22 22 and 23
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
6/724
Selection guide 1 Zelio Logic smart relays 1Modular smart relays and I/O extension andcommunication modules
Product types Modular smart relays
Supply voltage1111
24 V1111
100...240 V
Number of I/O 10 26 10 26
Number of discrete inputs(of which analogue inputs)
6 (0) 16 (0) 6 (0) 16 (0)
Number of relay/transistor outputs 4/0 10/0 4/0 10/0
With display, with clock Yes Yes
Programming language FBD or LADDER FBD or LADDER
Programming software (see page 26) Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01
Connectionaccessories(see page 26)
Serial link connecting cable SR2 CBL01 SR2 CBL01
USB connecting cable SR2 USB01 SR2 USB01
Bluetooth interface SR2 BTC01 SR2 BTC01
Memory cartridge (see page 26) SR2 MEM02(1 incompatible with SR2 COM01)
SR2 MEM02(1 incompatible with SR2 COM01)
Discovery packs (see page 24) SR3 PACK1 BD
Modem communication interface (see page 52) SR2 COM01 SR2 COM01
Alarm management software (see page 52) Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02
Converters (thermocouple types J and K, Pt100 probesand voltage/current) (see page 62)
Power supplies for d.c. control circuit(see page 69)
References (see page 24) SR3 B1 1
1 11 1
1 1
1B SR3 B 2 22 22 22 2 1FU
Associated I/O extension andcommunication module types
Discrete I/O extension modules Discrete I/O extension modules
Number of I/O 6 10 14 6 10 14
Type and number of discrete inputs(or analogue inputs)
4 (0) 6 (0) 8 (0) 4 (0) 6 (0) 8 (0)
Type and number of relay outputs(or analogue outputs)
2 (0) 4 (0) 6 (0) 2 (0) 4 (0) 6 (0)
References SR3 XT1 1 11 1 11 1 11 1 1
B SR3 XT1 1 11 1 11 1 11 1 1
FU
Pages 25 25
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
7/725
11
3333
12 V3333
24 V
26 10 26
16 (6) 6 (4) 16 (6)
10/0 4/0, 0/4 10/0, 0/10
Yes Yes
FBD or LADDER FBD or LADDER
Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01
SR2 CBL01 SR2 CBL01
SR2 USB01 SR2 USB01
SR2 BTC01 SR2 BTC01
SR2 MEM02(12incompatible with SR2 COM01)
SR2 MEM02(12incompatible with SR2 COM01)
SR3 PACK1
BD
SR2 COM01 SR2 COM01
Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02
RM 2 4 2 2 2 2 4 2 2 2 2 4 2 2 2
2 4 2 2 2 BD RM2 4 2 2 2 2 4 2 2 2 2 4 2 2 2
2 4 2 2 2 BD
ABL 7RM1202 ABL 7RM2402 2
2 22 2
2 2
SR3 B261JD SR3 B1 1 1
1 1 11 1 1
1 1 1
BD
Discrete I/O extension modules Network communication modules I/O extension modules
Modbus slave Ethernet server Analogue Discrete
6 10 14 2 Number of words:3 4 (inputs)3 4 (outputs)3 4 (clock)3
1 (status)
2 Number of words:3 4 (inputs)3 4 (outputs)3 4 (clock)3
1 (status)
4 6 10 14
4 (0) 6 (0) 8 (0) 0 (2) 4 (0) 6 (0) 8 (0)
2 (0) 4 (0) 6 (0) 0 (2) 2 (0) 4 (0) 6 (0)
SR3 XT1 1 11 1 11 1 11 1 1
JD SR3 MBU01BD SR3 NET01BD SR3 XT43BD SR3 XT1 1 11 1 11 1 11 1 1
BD
25 40 44 25
andor or
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
8/726
Presentation 1 Zelio Logic smart relays 1Compact and modular smart relays
PresentationZelio Logic smart relays are designed for use in small automated systems. They areused in both the industrial and commercial sectors.
2
22
2
For industry:
2
automation of small finishing, production, assembly or packaging machines.2 decentralised automation of ancillary equipment of large and medium-sizedmachines (textile, plastics, materials processing sectors etc.),2 automation systems for agricultural machinery (irrigation, pumping, greenhousesetc.).
2
22
2 For the commercial/building sectors:
2 automation of barriers, roller shutters, access control,2 automation of lighting systems,2
automation of compressors and air conditioning systems.
Their compact size and ease of setting-up make them a competitive alternative tosolutions based on cabled logic or specific cards.
2
22
2 ProgrammingSimple programming, ensured by the universal nature of the languages, meets all therequirements of automation specialists and also the needs of the electric ian.Programming can be performed:2 independently, using the buttons on the Zelio Logic smart relay (ladder language),2 on a PC using Zelio Soft 2 software.When using a PC, programming can be performed either in LADDER language or infunction block diagram (FBD) language, see pages 8 to 12.
Backlighting of the LCD display (1) is obtained by activating one of the 6 programmingbuttons on the Zelio Logic smart relay or by programming with Zelio Soft 2 software(example: flashing in the event of a malfunction).
The autonomous operating time of the clock, assured by a l ithium battery, is 10years.
Data backup (preset values and current values) is provided by an EEPROM Flashmemory (10 years).
Compact smart relays
Compact smart relays meet requirements for simple automation systems.The number of inputs/outputs can be:1 12 or 20 I/O, supplied with 4 24 V or 5 12 V,1 10, 12 or 20 I/O, supplied with 4 100240 V or 5 24 V.
Modular smart relays and extensions
The number of inputs/outputs for modular smart relays can be:1 26 I/O, supplied with 5 12 V,1 10 or 26 I/O, supplied with 4 24 V, 4 100240 V or 5 24 V
To improve performance and flexibility, Zelio Logic modular smart relays can be fitted
with communication modules and I/O extension modules to obtain a maximum of40 I/O:1
Modbus or Ethernet communication modules, supplied with5
24 V via theZelio Logic smart relay at the same voltage.1 analogue I/O extension modules with 4 I/O, supplied with 5 24 V via theZelio Logic smart relay at the same voltage,1 discrete I/O extension modules with 6, 10 or 14 I/O, supplied via the Zelio Logicsmart relay at the same voltage.
(1) LCD: Liquid Crystal Display.
109446
Zelio Logic compact smart relay
109458
1 2
1 Zelio Logic modular smart relay(10 or 26 I/O)
2 I/O extension module: discrete (6, 10 or 14I/O) or analogue (4 I/O)
000003-2
6
1 2
1 Zelio Logic modular smart relay(10 or 26 I/O)
2 Modbus or Ethernet communicationmodules
3 I/O extension module: discrete (6, 10 or 14I/O) or analogue (4 I/O)
3
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
Combination of modular smart relays with I/O
extension and communication modules
1
11
1
The order shown above must be observed when usinga Modbus slave or Ethernet server communicationmodule and a discrete or analogue I/O extension module.An I/O extension module cannot be fitted before theModbus slave communication module.
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
9/727
Presentation(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
(1) Public Switched Telephone Network.(2) Global System Mobile.
CommunicationCabled and wireless programming tools
1
These programming tools allow the Zelio Logic smart relay to be connected to aPC running Zelio Soft 2 software:2
Link by cables:- Cable SR2 CBL01 to 9-pin serial portor- Cable SR2 USB01 to USB port
2 Wireless link:- Bluetooth interface SR2 BTC01
1 Memory cartridgeThe Zelio Logic smart relay can be fitted with a backup memory cartridge whichenables the application program to be copied into another Zelio Logic smart relay.However, loading and updating of the firmware (software embedded in the product)is only possible with memory cartridge SR2 MEM02.
The memory cartridge also enables a backup copy of the program to be saved priorto replacing the product.
When used with a smart relay without display or buttons, the copy of the programcontained in the cartridge is automatically transferred into the Zelio Logic smart relayon power-up.
Modbus slave and Ethernet server communication modulesModbus and Ethernet communication modules allow connection to automationsystem equipment such as display units or programmable controllers (see pages 32to 41).
Modem communication interface
The Modem communication interface products in the Zelio Logic range include:1 a Modem communication interface SR2 COM01 connected between a Zelio Logicsmart relay and a Modem,1 analogue (PSTN) Modems (1) SR2 MOD01 or GSM Modem (2) SR2 MOD02,1
Zelio Logic Alarm software SR2 SFT02.
They are designed for monitoring or remote control of machines or installations which
operate without personnel.The Modem communication interface supplied with5
12...24 V, enables messages,telephone numbers and calling conditions to be stored, see pages 46 to 55.
523409
Connecting cable
536
135
Bluetooth interface
534944
Memory cartridge
540454
Modbuscommunication module
536136
Ethernetcommunication module
534941
Modemcommunication interface
534943
AnaloguePSTN Modem
534942
GSM Modem
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
10/72
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
11/729
Presentation(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software
Version 4.1 of "Zelio Soft 2" software improves, amongst other things, the ease of
use of user interfaces for the following functions:
The wiring sheet can be split into 2. Splitting allows two separate parts of the wiringsheet to be displayed on the same screen.
This makes it possible to:1
Display the required function blocks in the top and bottom parts.1 Move the split bar as required.1 Connect the function blocks between the 2 parts of the wiring sheet.The split wiring sheet is structured as follows:1 View of top part2 Top window vertical scroll bar
3 Top window horizontal scroll bar4 Split bar5 View of bottom part6 Bottom window vertical scroll bar7 Bottom window horizontal scroll bar
A function allows a block to be replaced without losing the input and outputconnections.E.g.: Replacement of an "OR" block by a "NOR" block.
Waiting
zzzz
LADDER or FBD program simulation mode allows the program to be debugged bysimulating it on the software workshop host computer.A function allows the time on the simulator clock to be modified by setting to 3seconds before the start of the next event.
The Next event button 1 allows modification of the simulator clock 2.
User interfaces
"Split wiring sheet" function (FBD language)
1
2
3
4
5
6
7
Structure of a split wiring sheet
"Replacement of a function block" (FBD language)
1 "OR" block to be replaced
1
2 Move all links to the new "NOR" block
Acceleration and simulation terminals" window"12
2
"Time Prog Simulation" function (LADDER and FBD languages)
3 Delete the "OR" block and positionthe "NOR" block in its place
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
3
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
12/7210
Functions 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software
LADDER languageDefinition
Text function block
Up/down counter
Analogue comparator
Control relay
LCD backlighting
Output coil
Timer
Fast counter
Clock
Counter comparator
Summer/Winter time switching
Message
LADDER language enables a LADDER program to be written with elementaryfunctions, elementary function blocks and derived function blocks, as well as withcontacts, coils and variables.The contacts, coils and variables can be annotated. Text can be placed freely withinthe graphic.
2
22
2
Control scheme input modes
Zelio input mode enables users who have directly programmed the Zelio Logicsmart relay to find the same user interface, even when using the software for the firsttime.Free input mode, which is more intuitive, is very user-friendly and incorporatesmany additional features.With LADDER programming language, two alternative types of symbol can be used:2 LADDER symbols,2 electrical symbols.Free input mode also allows the creation of mnemonics and notes associated witheach line of the program.
Instant switching from one input mode to the other is possible at any time, by simplyclicking the mouse.Up to 120 control scheme lines can be programmed, with 5 contacts and 1 coil perprogram line
2
22
2 Functions:
2 16 Text function blocks,2 16 time delay function blocks; parameters of 11 different types can be set for eachof these (1/10th second to 9999 hours),2 16 up/down counter function blocks from 0 to 32767,2 1 fast counter (1 kHz),2 16 analogue comparator function blocks,2 8 clock function blocks, each with 4 channels,2 28 control relays,2 8 counter comparators,2 LCD screen with programmable backlighting,
2
automatic Summer/Winter time switching,2
variety of functions: coil, latching (Set/Reset), impulse relay, contactor,2 28 message blocks (with communication interface, see page 46).
Functions
Function Electrical scheme LADDER language Notes
Contact I corresponds to the real state of the contact connected to theinput of the smart relay.i corresponds to the inverse state of the contact connected to theinput of the smart relay.
Standard coil The coil is energised when the contacts to which it is connectedare closed.
Latch coil (Set) The coil is energised (set) when the contacts to which it isconnected are closed.It remains set even if the contacts are no longer closed.
Unlatch coil(Reset)
The coil is de-energised (reset) when the contacts to which it isconnected are closed.It remains disabled even if the contacts are no longer closed.
13
14
22
21
or or
I
i
A1
A2
A1
A2
S
A1
A2
R
Presentation:pages 6 to 9
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
13/7211
Functions(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software
Function block diagram language (FBD / Grafcet SFC / Logic functions) (1)Definition
FBD language allows graphical programming based on the use of predefined function blocks; it provides the use of:1 32 functions for counting, time delay, timing, definition of switching threshold, (for example: temperature regulation), generation of impulses,time programming, multiplexing, display,1 7 SFC functions,1 6 logic functions.
Pre-programmed functions
Zelio Logic smart relays provide a high processing capacity, up to 200 function blocks, including 32 pre-programmed functions:
TIMER AC TIMER BH TIMER Li TIMER BW
Timer. Function A/C(ON-delay and OFF-delay)
Timer. Function BH.(adjustable pulsed signal)
Pulse generator(ON-delay, OFF-delay)
Timer. Function BW(pulse on rising/falling edge)
Timer. Function A/C with
external preset adjustment(ON-delay and OFF-delay)
Timer. Function BH with
external preset adjustment(adjustable pulsed signal)
Pulse generator
with external preset adjustment(ON-delay, OFF-delay)
BISTABLE SET- RESET BOOLEAN CAM PRESET COUNT
Impulse relay funct ion Bistable latching - Pr ior ityassigned either to SET orRESET function
Allows logic equations to becreated between connectedinputs
Cam programmer Up/down counter
UP DOWN COUNT PRESET H-METER TIME PROG GAIN TRIGGER
Up/down counter with externalpreset
Hour counter(hour, minute preset)
Time programmer, weeklyand annual.
Allows conversion of ananalogue value by change ofscale and offset.
Defines an activation zonewith hysteresis
MUX COMP IN ZONE ADD/SUB MUL/DIV TEXT
Multiplexing functions on2 analogue values
Zone comparison(Min. 5
55
5 Value 55 5
5 Max.)Add and/or subtract function Multiply and/or divide function Display of 4 pieces of data:
digital, analogue, date, time,messages for Human-Machine interface.
DISPLAY COM COMPARE STATUS ARCHIVE
Display of digital and analoguedata, date, time, messages forHuman-Machine interface.
Sending of messages withcommunication interface(see page 46)
Comparison of 2 analoguevalues using the operands=, >,
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
14/7212
Functions(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software
A Macro is a grouping of function blocks. It is characterised by its number, its name,its links, its internal function blocks (255 max.) and by its I/O connections.
Seen from the outside, a Macro behaves like a function block with inputs and/oroutputs that can be connected to links.Once created, a Macro can be manipulated like a function block.
1 Macro characteristics:2 The maximum number of Macros is 64.2
A password dedicated to Macros can be used to protect their content,2 A Macro can be edited / duplicated,2 A Macro's comments can be edited.1 Macro properties:A "Macro properties" dialogue box allows the properties of a Macro to be entered oredited.
The properties of a Macro are:2 Macro name (optional)2
The block Symbol, which may be:- an identifier,- an image.
2 Name of inputs.2
Name of outputs.
Function block diagram language (FBD / Grafcet SFC / Logic functions) (continued)Macro Function
Creation of a Macro
Inside of a Macro
1 Macro selection2 Edit properties3 Allows return to external view of a Macro4 Internal function block within the Macro
5 Non connected inputs6 Non connected outputs
1 5 2 3 4 6
Outside of a Macro
1 Input connections2 Output connection
21
Presentation:pages 6 to 9
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
15/7213
Description 1 Zelio Logic smart relays 1Compact and modular smart relays
Compact smart relaysWith display - 10, 12 and 20 I/O Without display - 10, 12 and 20 I/O
Zelio Logic compact smart relays have thefollowing on their front panel:
1 Two retractable fixing lugs.2 Two power supply terminals.3 Terminals for connection of the inputs.4 Backlit LCD display with 4 lines of 18
characters.
5 Slot for memory cartridge or connectionto a PC or Modem communicationinterface.
6 6 buttons for programming andparameter entry.
7 Terminals for connection of the outputs.
Modular smart relaysWith display - 10 and 26 I/O
Zelio Logic modular smart relays have thefollowing on their front panel:
1 Two retractable fixing lugs.2 Two power supply terminals.3 Terminals for connection of the inputs.4 Backlit LCD display with 4 lines of 18
characters.5 Slot for memory cartridge or connection
to a PC or Modem communicationinterface.
6 6 buttons for programming andparameter entry.
7 Terminals for connection of the outputs.
Discrete I/O extension modules6 discrete I/O 10 and 14 discrete I/O
Discrete I/O extension modules have the
following on their front panel:1 Two retractable fixing lugs.2 Terminals for connection of the inputs.3 Terminals for connection of the outputs.4 A connector for connection to the Zelio
Logic smart relay (powered via the ZelioLogic smart relay).
5 Locating pegs.
1 2 3
5
17
4
6
1 2 3
5
17
1 2 3
5
17
4
6
1 2
5
13
5
4
1 2
5
13
55
4
Presentation, functions:pages 6 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
16/7214
Characteristics 1 Zelio Logic smart relays 1Compact and modular smart relays
(1) Except for configuration SR3 B1 1 1 BD + SR3 MBU01BD + SR3 XT43BD orSR3 B1 1 1 BD + SR3 NET01BD + SR3 XT43BD class A (class B: work in progress).
General environment characteristicsType SR2 A / SR2 B / SR2 D / SR2 E / SR3 B / SR3 XT
Product certifications UL, CSA, GL, C-Tick
Conformity with thelow voltage directive
Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)
Conformity with theEMC directive
Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4
Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block), IP 40 (front panel)
Overvoltage category Conforming to IEC/EN 60664-1 3
Degree of pollution Conforming to IEC/EN 61131-2 2
Ambient air temperaturearound the deviceconforming to IEC 60028-2-1and IEC 60068-2-2
Operation C - 20...+ 55 (+ 40 in non-ventilated enclosure)
Storage C - 40...+ 70
Maximum relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water
Maximum operating altitude Operation m 2000
Transport m 3048
Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc
Immunity to mechanical shock IEC/EN 60068-2-27, test EaResistance toelectrostatic discharge
Immunity toelectrostatic discharge
IEC/EN 61000-4-2, level 3
Resistance to HF interference(immunity)
Immunity to electromagneticradiated fields
IEC/EN 61000-4-3
Immunity to fast transientsin bursts
IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequencyin common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (6
) IEC/EN 61000-4-11
Immunity to dampedoscillation waves
IEC/EN 61000-4-12
Conducted andradiated emissions
Conforming to EN 55022/11(Group 1)
Class B (1)
Screw terminals connectioncapacity
Flexible cable with cable end mm2 1 conductor: 0.25...2.5, cable: AWG 24...AWG 142 conductors: 0.25...0.75, cable: AWG 24...AWG 18
Semi-solid cable mm2 1 conductor: 0.25...2.5, cable: AWG 25...AWG 14
Solid cable mm2 1 conductor: 0.25...2.5, cable: AWG 25...AWG 142 conductors: 0.2...1.5, cable: AWG 24...AWG 16
Tightening torque N.m 0.5 (tightened using 3.5 mm screwdriver)
Processing characteristicsNumber of controlscheme lines
With LADDER programming 120
Number of function blocks With FBD programming Up to 200
Cycle time ms 6...90
Response time ms Input acquisition time + 1 to 2 cycle times
Back-up time(in the event of power failure)
Day/time 10 years (lithium battery) at 25 C
Program and adjustments inthe Zelio Logic smart relay andin EEPROM memory cartridge
SR2 MEM01
10 years
Program memory checking On each power-up
Clock drift 12 min/year (0 to 55 C)6 sec/month (at 25 C and calibration)
Timer block accuracy 1% 2 of the cycle time
Presentation:pages 6 to 9
Functions :pages 10 to 12
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
17/72
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
18/7216
Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Supply characteristics, 3 100...240 V productsType SR2
2222
101FUSR2
2222
121FUSR2
2222
201FU SR3 B101FU SR3 B261FU
Nominal voltage V6 100240
Voltage limits V6
85264
Nominal frequency Hz 50-60
Nominal input current Without extensions mA 80/30 100/50 80/30 100/50
With extensions mA 80/40 80/60
Power dissipated Without extensions VA 7 11 7 12
With extensions VA 12 17
Micro-breaks Permissible duration ms 10
rms insulation voltage V6
1780
Discrete input characteristics, 3 100...240 V productsType SR 2
22
2 2 2 2 2
2 2 2 2 2 2 2 2
2 2 2 2 FU
Nominal value of inputs Voltage V6
100... 240
Current mA 0.6
Frequencies Hz 47...53 and 57...63
Input switching limit values At state 1 Voltage V 5 6 79
Current mA > 0.17
At state 0 Voltage V 4 6 40
Current mA < 0.5
Input impedance at state 1 k 350
Responsetime
LADDERlanguage
State 0 to 1 (50/60 Hz) ms 50
State 1 to 0 (50/60 Hz) ms 50
FBDlanguage
State 0 to 1 (50/60 Hz) ms 50 min... 255 max. (in increments of 10)
State 1 to 0 (50/60 Hz) ms 50 min...255 max. (in increments of 10)
Isolation Between supply and inputs None
Between inputs None
Protection Against inversion of terminals Yes (control instructions not executed)
Relay output characteristics, 3 100...240 V products
Type SR22
22
2
101FUSR2
2
22
2
121FUSR3 B101FUSR3 XT101FU
SR22
22
2
201FU SR3 B 261FU SR3 XT61FU SR3 XT141FU
Operating limit values V8
5...30.6
24...250
Contact type N/O
Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A
2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A
Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1
Utilisationcategory
DC-12 V8
24
A 1.5
DC-13 V8
24 (L/R = 10 ms)
A 0.6
AC-12 V6
230
A 1.5
AC-15 V6
230
A 0.9
Minimum switching capacity At minimum voltage of 8 12 V mA 10
Low power switchingreliability of contact
8 12 V - 10 mA
Maximum operating rate No-load Hz 10
At Ie (operational current) Hz 0.1
Mechanical life In millions of operating cycles 10
Rated impulse withstandvoltage (Uimp)
Conforming to IEC/EN 60947-1and IEC/EN 60664-1
kV 4
Response time Set ms 10
Reset ms 5
Built-in protection Against short-circuits None
Against overvoltageand overload
None
Presentation:pages 6 to 9
Functions :pages 10 to 12
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
19/7217
Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Supply characteristics, 5 12 V productsType SR2 B121JD SR2 B201JD SR3 B261JD
Nominal voltage V8 12
Voltage limits Including ripple V8
10.414.4
Nominal input current Without extensions mA 120 200 250
With extensions mA 400
Power dissipated Without extensions W 1.5 2.5 3
With extensions W 5
Micro-breaks Permissible duration ms4
1 (repeated 20 times)
Protection Against reversed polarity Yes
Discrete input characteristics, 5 12 V productsType SR
2
22
2 2 2 2 2
2 2 2 2 2 2 2 2
2 2 2 2
JD(inputs I1IA, IHIR)
SR2
22
2 2 2 2 2
2 2 2 2 2 2 2 2
2 2 2 2
JD(inputs IBIG used as discrete inputs)
Nominal value of inputs Voltage V8
128
12
Current mA 4 4
Input switchinglimit values
At state 1 Voltage V 5 8 5.6 5 8 7
Current mA5
25
0.5
At state 0 Voltage V4
8
2.44
8
3Current mA < 0.9 < 0.2
Input impedance at state 1 k 2.7 14
Conforming to IEC/EN 61131-2 Type 1 Type 1
Sensor compatibility 3-wire Yes PNP Yes PNP
2-wire No No
Input type Resistive Resistive
Isolation Between supply and inputs None None
Between inputs None None
Maximum counting frequency kHz 1 1
Protection Against reversed polarity Yes (control instructions not executed) Yes (control instructions not executed)
Analogue input characteristics, 5 12 V productsType SR
2222 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
JD (inputs IBIG used as analogue inputs)
Input range V8 0...10 or 8 0...12
Input impedance k 14
Maximum non destructive voltage V 8 14.4
Value of LSB 39 mV
Input type Common mode
Conversion Resolution 8 bits at maximum voltage
Conversion time Smart relay cycle time
Precision 5 % at 25 C and 6.2 % at 55 C
Repeat accuracy 2 % at 55 C
Isolation Between analogue channel and supply None
Cabling distance m 10 max., with screened cable (sensor not isolated)
Protection Against reversed polarity Yes
Relay output characteristics, 5 12 V productsType SR2 B121JD
SR3 XT101JDSR2 B201JD SR3 B 261JD SR3 X T61JD SR3 X T141JD
Operating limit values V8 5...30, 6 24...250
Contact type N/O
Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A
2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A
Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1
Utilisation category DC-12 V8
24
A 1.5
DC-13 V8
24 (L/R = 10 ms)
A 0.6
AC-12 V6
230
A 1.5
AC-15 V 6 230
A 0.9
Minimum switchingcapacity
At minimum voltage of 8 12 V mA 10
Low power switching reliability of contact8
12 V - 10 mA
Maximum operating rate No-load Hz 10
At Ie (operational current) Hz 0.1
Mechanical life In millions of operating cycles 10
Rated impulse withstandvoltage (Uimp)
Conforming to IEC/EN 60947-1and IEC/EN 60664-1
kV 4
Response time Set ms 10
Reset ms 5
Built-in protection Against short-circuits None
Against overvoltage and overload None
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
20/7218
Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Supply characteristics, 5 24 V productsType SR2
2222
12222
1BDSR2B122BD
SR22222
201BDSR2B202BD
SR3B101BD
SR3B102BD
SR3B261BD
SR3B262BD
Nominal voltage V8 24
Voltage limits Including ripple V 19.230
Nominal input current Without extensions mA 100 50 190 70
With extensions mA 100 160 300 180
Power dissipated Without extensions W 3 6 3 4 6 5
With extensions W 8 10
Micro-breaks Permissible duration ms4
1 (repeated 20 times)
Protection Against reversed polarity Yes
Discrete input characteristics, 5 24 V productsType SR
2
22
2 2 2 2 2
2 2 2 2 2 2 2 2
2 2 2 2
BD(input I1IA, IHIR)
SR2
22
2 2 2 2 2
2 2 2 2 2 2 2 2
2 2 2 2
BD(input IBIG used as discrete input)
Nominal value of inputs Voltage V 8 24 8 24
Current mA 4 4
Input switchinglimit values
At state 1 Voltage V 5 8 15 5 8 15
Current mA5
2.25
1.2
At state 0 Voltage V 4 8 5 4 8 5
Current mA < 0.75 < 0.5
Input impedance at state 1 k 7.4 12
Conforming to IEC/EN 61131-2 Type 1 Type 1
Sensor compatibility 3-wire Yes PNP Yes PNP
2-wire No No
Input type Resistive Resistive
Isolation Between supply and inputs None None
Between inputs None None
Maximum counting frequency kHz 1 1
Protection Against reversed polarity Yes (control instructions not executed) Yes (control inst ructions not executed)
Analogue input characteristics, 5 24 V productsType SR
2222 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
BD (input IBIG used as analogue inputs)
Input range V8 0...10 or 8 0...24
Input impedance k 12Maximum non destructive voltage V
8 30
Value of LSB 39 mV
Input type Common mode
Conversion Resolution 8 bits at maximum voltage
Conversion time Smart relay cycle time
Precision 5 % at 25 C and 6.2 % at 55 C
Repeat accuracy 2 % at 55 C
Isolation Between analogue channel andsupply
None
Cabling distance m 10 maximum, with screened cable (sensor not isolated)
Protection Against reversed polarity Yes
Presentation:pages 6 to 9
Functions :pages 10 to 12
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
21/7219
Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
(1) If there is no volt-free contact between the Zelio Logic smart relay output and the load.
Relay output characteristics, 5 24 V productsType SR2
2222
101BDSR2
2222
121BD
SR3 B101BDSR3 XT101BD
SR22222
201BD SR3 B 261BD SR3 X T61BD SR3 X T141BD
Operating limit values V8 5...30. 6 24...250
Contact type N/O
Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A
2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A
Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1
Utilisationcategory
DC-12 V 8 24
A 1.5
DC-13 V 8 24 (L/R = 10 ms)
A 0.6
AC-12 V 6 230
A 1.5
AC-15 V 6 230
A 0.9
Minimum switching capacity At minimum voltage of 8 12 V mA 10
Low power switchingreliability of contact
8
12 V - 10 mA
Maximum operating rate No-load Hz 10
At Ie (operational current) Hz 0.1
Mechanical life In millions of operating cycles 10
Rated impulse withstandvoltage (Uimp)
Conforming to IEC/EN 60947-1and IEC/EN 60664-1
kV 4
Response time Set ms 10
Reset ms 5
Built-in protection Against short-circuits None
Against overvoltageand overload
None
Transistor output characteristics, 5 24 V productsType SR
2
22
2
B2 2
2 22 2
2 2
2BD
Operating limit values V 8 19.2..0.30
Load Nominal voltage V8
24Nominal current A 0.5
Maximum current A 0.625 at 30 V
Residual voltage At state 1 V 4 8 2 for I = 0.5 A
Response time Set ms4
1
Reset ms 4 1
Built-in protection Against overload andshort-circuits
Yes
Against overvoltage (1) Yes
Against inversions ofpower supply
Yes
Presentation:pages 6 to 9
Functions :pages 10 to 12
Curves :pages 20 and 21
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
22/7220
Curves 1 Zelio Logic smart relays 1Compact and modular smart relays
Electrical durability of relay outputs(in millions of operating cycles, conforming to IEC/EN 60947-5-1)
d.c. loads
DC-12 (1)
DC-13 (2)
(1) DC-12: switching resistive loads and photo-coupler isolated solid-state loads, L/R4
1 ms.(2) DC-13: switching electromagnets, L/R
4
2 x (Ue x Ie) in ms, Ue: rated operational voltage,Ie: rated operational current (with a protection diode on the load, DC-12 curves must be usedwith a coefficient of 0.9 applied to the number in millions of operating cycles).
0 1,51 20,5
0,0
0,5
1,0
1,5
2,0
2,5
3,0
24 V
48 V
onsoo
peratngcyces
Current (A)
0,1 0,3 0,5 0,7 0,9 10,2 0,4 0,6 0,8
0,0
1,4
1,2
1,0
0,8
0,6
0,4
0,2
L/R = 10 ms 24 V
L/R = 10 ms 48 V
L/R = 60 ms 48 V
L/R = 60 ms 24 V
onsoo
peratngcyces
Current (A)
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
23/7221
Curves(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Electrical durability of relay outputs (continued)(in millions of operating cycles, conforming to IEC/EN 60947-5-1)
a.c. loads
AC-12 (1)
AC-14 (2)
AC-15 (3)
(1) AC-12: switching resistive loads and photo-coupler isolated solid-state loads, cos5
0.9.(2) AC-14: switching small electromagnetic loads
4
72 VA, make: cos = 0.3, break: cos = 0.3.(3) AC-15: switching electromagnetic loads > 72 VA, make: cos = 0.7, break: cos = 0.4.
0 0,5 1,5 2,5 3,5 4,51,0 2,0 3,0 4,0 50,0
0,5
1,0
1,5
2,0
2,5
3,0
24 V
48 V
110 V
230 V
Millionsofoperatingcycles
Current (A)
0 0,2 0,6 1,0 1,4 1,80,4 0,8 1,2 1,6 20,0
0,5
1,0
1,5
2,0
2,5
24 V48 V
110 V
230 V
Millionsofoperatingcycles
Current (A)
0,5 0,90,7 1,31,1 1,71,5 1,90,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
230 V 48 V
110 V
Millionsofoperatingcycles
Current (A)
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
References:pages 22 to 27
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
24/72
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
25/7223
References(continued) 1 Zelio Logic smart relays 1Compact smart relays
Compact smart relays without displayNumberof
I/O
Discreteinputs
Including4
4 4
4
0-10 V
analogueinputs
Relayoutputs
Transistoroutputs
Clock Reference Weight
kg
Supply3
33
3
24 V
12 8 0 4 0 Yes SR2 E121B 0.220
20 12 0 8 0 Yes SR2 E201B 0.350
Supply 333
3 100...240 V
10 6 0 4 0 No SR2 D101FU (1) 0.220
12 8 0 4 0 Yes SR2 E121FU 0.220
20 12 0 8 0 No SR2 D201FU (1) 0.350
Yes SR2 E201FU 0.350
Supply 4444 24 V10 6 0 4 0 No SR2 D101BD (1) 0.220
12 8 4 4 0 Yes SR2 E121BD 0.220
20 12 2 8 0 No SR2 D201BD (1) 0.350
6 8 0 Yes SR2 E201BD 0.350
Zelio Soft 2 software for PCDescription Application Reference Weight
kg
Programming softwareZelio Soft 2 software,multi-language
For PC, supplied onCD-Rom (2), compatible withWindows 98, NT, 2000, XP
SR2 SFT01 0.200
AccessoriesConnection accessories
Description Application Length Reference Weightkg
Connecting cable Between the PC(USB connector)and the Zelio Logicsmart relay
3 m SR2 USB01 0.100
Other accessories: see pages 26 and 27
Modem communication interfaceSupply
4444
12...24 V
Description Application Reference Weightkg
Modem communicationinterface
For SR2 E See page 52 0.200
(1) Programming on Zelio Logic smart relay in LADDER language only.(2) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,
installation instructions and a users manual.
109442
SR2 E121BD
SR2 SFT01
536307
SR2 USB01
523109
536306
Modem communication interface
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
26/7224
References 1 Zelio Logic smart relays 1Modular smart relays
Modular smart relays with displayNumberof
I/O
Discreteinputs
Including4
44
4
0-10 V
analogueinputs
Relayoutputs
Transistoroutputs
Clock Reference Weight
kg
Supply3
33
3
24 V
10 6 0 4 0 Yes SR3 B101B 0.250
26 16 0 10 (1) 0 Yes SR3 B261B 0.400
Supply 333
3 100...240 V
10 6 0 4 0 Yes SR3 B101FU 0.250
26 16 0 10 (1) 0 Yes SR3 B261FU 0.400
Supply4
44
4
12 V
26 16 6 10 (1) 0 Yes SR3 B261JD (2) 0.400
Supply 444
4 24 V
10 6 4 4 0 Yes SR3 B101BD 0.250
0 4 Yes SR3 B102BD 0.220
26 16 6 10 (1) 0 Yes SR3 B261BD 0.400
0 10 Yes SR3 B262BD 0.300
Zelio Soft 2 software for PCDescription Application Reference Weight
kg
Programming softwareZelio Soft 2 software,multi-language
For PC, supplied onCD-ROM (3),compatible withWindows 98, NT, 2000, XP
SR2 SFT01 0.200
AccessoriesConnection accessoriesDescription Application Length Reference Weight
kg
Connecting cable Between the PC(USB connector)and the Zelio Logicsmart relay
3 m SR2 USB01 0.100
Other accessories: see pages 26 and 27
Modular discovery packsNumberofI/O
Pack contents:- Compact smart relay with display- Zelio Soft 2 programming software supplied onCD-Rom- Cable PC SR2 USB01 for connection to PC(4)
Reference Weight
Description of compact smart relay with display kg
Supply3
33
3
100...240 V10 SR3 B101FU SR3 PACKFU 0.700
26 SR3 B261FU SR3 PACK2FU 0.850
Supply 444
4 24 V
10 SR3 B101BD SR3 PACKBD 0.700
26 SR3 B261BD SR3 PACK2BD 0.850
(1) Including 8 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A.(2) Can only be used with "Zelio Soft 2" software version
5
V 3.1.(3) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,
installation instructions and a users manual.(4) Replaces cable SR2 CBL01 which is still available separately, as an accessory (see page 26).
Note:The Zelio Logic smart relay and its associated extensions must have an identical voltage.
109444
SR3 B101BD
SR2 SFT01
536307
SR2 USB01
523109
SR2 PACK1 1 1
536308
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
27/7225
References(continued) 1 Zelio Logic smart relays 1Modular smart relays
Modbus and Ethernet communication module (1)4
44
4 24 V supply (via smart relays SR3B...BD)
For use with Network Reference Weightkg
Zelio Logic modular smart relaysSR3 B
2 22 22 22 2
1BD and SR3 B2 22 22 22 2
2BDModbus See page 40
0.110
Ethernet See page 40 0.110
SR3NET
Ethernetcommunication module
524132
Modbuscommunication module
Analogue I/O extension module (2)Supply 4
44
4 24 V (via Zelio Logic smart relay SR3 B...BD)
NumberofI/O
Inputs Including4444
Inclu-dingPt100
Output4444
0-10 VReference Weight
kg
0 - 10 V 0 - 20 mA
4 2 (3) 2 max 2 max 1 max 2 See page 44 0.110
Discrete I/O extension modules
Numberof I/O
Discrete inputs Relay outputs Reference Weightkg
Supply 333
3 24 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1
1 1 1 B)
6 4 2 SR3 XT61B 0.125
10 6 4 SR3 XT101B 0.200
14 8 6 (4) SR3 XT141B 0.220
Supply 333
3 100-240 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1
1 1 1 FU)
6 4 2 SR3 XT61FU 0.125
10 6 4 SR3 XT101FU 0.200
14 8 6 (4) SR3 XT141FU 0.220
Supply 4444 12 V (via Zelio Logic smart relay SR3 B261JD)6 4 2 SR3 XT61JD 0.125
10 6 4 SR3 XT101JD 0.200
14 8 6 (4) SR3 XT141JD 0.220
Supply 444
4 24 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1
1 1 1 BD)
6 4 2 SR3 XT61BD 0.125
10 6 4 SR3 XT101BD 0.200
14 8 6 (4) SR3 XT141BD 0.220
Modem communication interface (5)Supply 4
44
4 12...24 V
Description Reference Weightkg
Modem communication interface See page 52 0.200
(1) See pages 32 to 41.(2) See pages 42 to 45.(3) See page 45.(4) Including 4 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A.(5) See pages 46 to 55.
Note:The Zelio Logic smart relay and its associated extensions must have an identical voltage.
109363
SR3 XT61BD
109369
SR3 XT141BD
Modem communication interface
536306
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
28/7226
References 1 Zelio Logic smart relays 1Compact and modular smart relays
ProgrammingZelio Soft 2 software for PC
Description Application Reference Weightkg
Programming softwareZelio Soft 2 software,multi-language
For PC, supplied onCD-ROM (1), compatible withWindows 98, NT, 2000, XP
SR2 SFT01 0.200
Connection accessories
Description Application Reference Weightkg
Connecting cables Between the PC (SUB-D, 9-pinconnector) and the Zelio Logicsmart relay. Length: 3 m
SR2 CBL01 0.150
Between the PC (USB connector)and the Zelio Logic smart relay.PC compatible withWindows 2000, XPLength: 3 m
SR2 USB01 0.100
Bluetooth interfacefor Zelio Logic smart relays Between the PC (wireless link)and the Zelio Logic smart relay.Range 10 m (class 2)
SR2 BTC01 (2) 0.015
Bluetooth adapterfor non-equipped PC
To be used in conjunction withSR2 BTC01 when the PC is notequipped with Bluetoothtechnology.Connection to the USB porton the PC.PC compatible withWindows 98SE, 2000, XPRange of 10 m (class 2)
VW3 A8115 0.290
Memory cartridges(3)
Description Application Reference Weightkg
EEPROMmemory cartridges
For firmware (software embeddedin the smart relay) version
4
2.4SR2 MEM01 0.010
For firmware (software embeddedin the smart relay) version 5 3.0
SR2 MEM02 0.010
DocumentationDescription/application Language Reference
Weightkg
Users manualfor direct programming onthe Zelio Logic smart relay
English SR2 MAN01EN 0.100
French SR2 MAN01FR 0.100
German SR2 MAN01DE 0.100
Spanish SR2 MAN01ES 0.100
Italian SR2 MAN01IT 0.100
Portuguese SR2 MAN01P0 0.100
(1) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,installation instructions and a users manual.
(2) Can only be used with "Zelio Soft 2" software version2
V 4.1.(3) Program loading using memory cartridge SR2 MEM02 is incompatible with Modem
communication interface SR2 COM01.
SR2 SFT01
536307
SR2 USB01
523109
SR2 BTC01
536135
SR2 MEM02
534944
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
29/7227
References(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Regulated switch mode power supplies (1)Inputvoltage
Nominaloutput voltage
Reference Weightkg
6 100...240 V (50/60 Hz) 8 5 V, 8 12 V or 8 24 V See page 69
Converters (2)Description Reference Weight
kg
Converters for J and K type thermocouples,for Pt100 probes and voltage/current
See page 62
Mounting accessories (3)Description/application Mounting capacity Reference Weight
kg
Dust and damp-proofenclosurewith split blanking platearrangement, fitted with anIP 55 dust and damp-proofwindow with hinged flap, formounting through a door
- 1 or 2 SR2 smart relays with10 or 12 I/O or- 1 SR2 smart relay with 20 I/O or- 1 SR3 smart relay with 10 I/O+ 1 I/O extension module(6, 10 or 14 I/O) or- 1 SR3 smart relay with 26 I/O+ 1 I/O extension module (6 I/O).
14210 0.350
Fixing bracket andsymmetrical mounting rail
For mounting enclosure 14210through a door panel
14211 0.210
(1) See pages 64 to 69.(2) See pages 58 to 63.(3) Products marketed under the Merlin Gerin brand.
Regulated switch modepower supplie
540472
Converters forthermocouples
10900
14210
14211
DF563990
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
Dimensions, schemes:pages 28 to 31
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
30/72
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
31/7229
Schemes 1 Zelio Logic smart relays 1Compact and modular smart relays
Connection of smart relays on 5 supplySR 1 5 1 1 1
1 5 1 1 1 1 5 1 1 1
1 5 1 1 1 1BD, SR 1 5 1 1 1 1 5 1 1 1 1 5 1 1 1
1 5 1 1 1 1JD SR2 B 1 11 11 1
1 1 2BD and SR3 B 1 11 11 1
1 1 2BD
SR3 B2611
D
(1) 1 A quick-blow fuse or circuit-breaker.(2) Fuse or circuit-breaker.(3) Inductive load.(4) Q9 and QA: 5 A (max. current in terminal C: 10 A).
Discrete input used for 3-wire sensors
(1) 1 A quick-blow fuse or circuit-breaker.
+
SRpppppJDc 12 V
SRpppppBDc 24 V
(1)
+
Q1 Q2 Q3 Q4
z 12240 V
50/60 Hz
c 1224 V
L /+
N / z 24240 V50/60 Hz
c 1224 V
(2)(3)
U
(3)
U
or
Q7 C Q8 Q9 QA
5 A(4)
+
+
c 24 V
c 24 V
+
(1)
+Q1 Q2 Q3 Q4
(2)
+
z 12240 V
50/60 Hz
c 1224 V
(3)
U
(3)
U
BN
BK
BLBN
BK
BL
+
(1)
+
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
32/7230
Schemes(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Connection of smart relays on 5 supply (continued)Analogue inputs
(1) 1 A quick-blow fuse or circuit-breaker.(2) Ca: Analogue sensor / Ta: Analogue transmitter.(3) Recommended values: 2.2 k/ 0.5 W (10 kmax.).(4) Screened cables, maximum length 10 m.(5) Analogue inputs according to Zelio Logic to smart relay, see table below:
Smart relays Analogue inputs
SR22
22
2
122 2
2 22 2
2 2
D IBIE
SR2 A201BD IB and IC
SR2 D201BD IB and IC
SR2 B202 22 22 22 2
D IBIG
SR2 E201BD IBIG
SR3 B102222
BD IBIE
SR3 B262 2
2 22 2
2 2
D IBIG
Connection of smart relays on 5 supply, with discrete I/O extension modulesSR3 B
1 1 1
1 1 11 1 1
1 1 1
JD + SR3 XT1 1 1
1 1 11 1 1
1 1 1
JD, SR3 B1 1 1
1 1 11 1 1
1 1 1
BD + SR3 XT1 1 1
1 1 11 1 1
1 1 1
BD
(1) 1 A quick-blow fuse or circuit-breaker.(2) Ca: Analogue sensor / Ta: Analogue transmitter.(3) Recommended values: 2.2 k/ 0.5 W (10 kmax.).(4) Screened cables, maximum length 10 m.
+
+
(1)
(3)
(5)
+
+
(1)
Ca / Ta (2)
(5)
(4)
1 0-10 VANALOG.
+
(1)
(3)
Ca / Ta (2)
QF QG
+
BN
BK
BL
BN
BK
BL
(4)
Warning: QF and QG: 5 A for SR3 XT1411 11 11 11 1
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
33/7231
Schemes(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays
Connection of smart relays on 3 supplySR 1 5 1 1 1
1 5 1 1 1 1 5 1 1 1
1 5 1 1 1 1B, SR 1 5 1 1 1 1 5 1 1 1 1 5 1 1 1
1 5 1 1 1 1FU
SR3 B261B and SR3 B261FU
(1) 1 A quick-blow fuse or circuit-breaker.(2) Fuse or circuit-breaker.(3) Inductive load.(4) Q9 and QA: 5 A (max. current in terminal C: 10 A).
With discrete I/O extension module
SR3 B2 2 2
2 2 22 2 2
2 2 2
B + SR3 XT2 2 2
2 2 22 2 2
2 2 2
B, SR3 B2 2 2
2 2 22 2 2
2 2 2
FU + SR3 XT2 2 2
2 2 22 2 2
2 2 2
FU
(1) 1 A quick-blow fuse or circuit-breaker.
L
L N
SRp ppppFU
a 100240 V
50/60 Hz
SRp ppppB
a 24 V
N
(1)
Q1 Q2 Q3 Q4
z 12240 V
50/60 Hz
c 1224 V
L /+
N / z 12240 V50/60 Hz
c 1224 V
(2)(3)
U
(3)
U
or
Q7 C Q8 Q9 QA
5 A(4)
QF QG
+
L
N
(1)
Module Extension
Warning: QF and QG: 5 A for SR3 XT141 1 11 11 11 1
Presentation:pages 6 to 9
Functions :pages 10 to 12
Characteristics:pages 14 to 19
Curves :pages 20 and 21
References:pages 22 to 27
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
34/7232
Presentation 1 Zelio Logic smart relays 1Communication
In order to communicate with an intelligent environment, Zelio Logic smart relays andtheir I/O extension and communication modules are equipped with various types ofcommunication port.
1 Compact and modular smart relays offer:2 1 RS 232 serial port for connection of the PC, the Modem communication interfaceor a memory cartridge slot.1 Zelio Logic modular smart relay I/O extension and communication modules offer:2 1 Modbus RS 485 port on communication module SR3 MBU01BD,2 1 Ethernet 10/100 base T port supporting the Modbus TCP protocol oncommunication module SR3 NET01BD.
These three ports allow Zelio Logic compact or modular smart relays to use 3communication protocols:1 Programming,1 Modbus,1 Ethernet.
Presentation109449
Smart relay
6
7
Communication ports on Zelio Logic smart relays and their I/O extension and
communication modules
Communicationport
Serial port Modbus port oncommunicationmoduleSR3 MBU01BD
Ethernet port oncommunicationmoduleSR3 NET01BD
Modemcommunicationinterface port
Physical layer RS 232 RS 485 10/100 base T RS 232
Connector Specific to Zelio RJ45 RJ45 Specific to Zelio
Compactsmart relays
All types(connection and
isolation via cableSR2 CBL01 orSR2 USB01)
All modules withclock
SR2 B1 1 1 1 1
SR2 E1 1 1 1 1 (see page52)
Modularsmart relays
All types(connection andisolation via cableSR2 CBL01 orSR2 USB01)
All modules with8
24 V supplySR3 B
1 1 1
BD
All modules with8
24 V supplySR3 B
1 1 1
BD
All types(see page52)
000003-2
6
1 3
1
11
1
The order shown above must be observed when usinga Modbus slave or Ethernet server communicationmodule and a discrete or analogue I/O extension module.An I/O extension module cannot be fitted before theModbus slave or Ethernet server communication module.
2
4
5
1 Modular smart relay(10 or 26 I/O).
2 RS 232 serial port, Zelio Logic typeconnector.
3 Modbus slave or Ethernet servercommunication module.
4 RJ45 connector for Modbus or Ethernetnetwork connection.
5 I/O extension module: discrete(6,10 or 14 I/O) or analogue (4 I/O).
6 Modem communication interface.7 GSM (or analogue PSTN) Modem.
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
35/7233
Description,characteristics 1
Zelio Logic smart relays 1CommunicationProgramming protocol
Description Link by cable
1 Programming PC.2 RS 232 serial link cable (SR2 CBL01) or USB cable (SR2 USB01) (1).3 Zelio Logic compact or modular smart relay.
Wireless link
4 Programming PC with integrated Bluetooth technology (or Bluetooth adapterVW3 A8115 for PC not equipped with Bluetooth technology) (1).
5 Bluetooth interface (SR2 BTC01) for Zelio Logic smart relay (1).
6 Zelio Logic compact or modular smart relay.
Link by Modem
7 Programming PC.8 Modem interface connecting cable supplied with SR2 COM01 (2).9 Modem for transmitting/receiving data SR2 MOD01 or SR2 MOD02 (2).10 Telephone or radio link.11 Communication interface SR2 COM01.12 Zelio Logic compact or modular smart relay.
(1) See page 26.(2) See page 52.
Serial link characteristicsProduct type All Zelio Logic smart relays
Flow rate Kbit/s 115.2
Data bits 7
Stop bits 1
Parity Pair
Physical layer RS 232
Type of connector Specific to Zelio Logic
1
3
2
4
5
6
7
9
10
9 128
11
524107
524106
524108
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
36/7234
Presentation,description 1
Zelio Logic smart relays 1CommunicationModbus slave communication protocol
Presentation
The Modbus communication protocol is of the master/slave type.Two exchange methods are possible:1 Request/reply:2
The request from the master is addressed to a specific slave.2 The master waits for the reply to be returned by the slave polled.1 Distribution:2 The master distributes a request to all the slave stations on the bus.These stations execute the instruction without sending a reply.
Zelio Logic modular smart relays are connected to the Modbus network via theModbus slave communication module. This module is a slave that is not electricallyisolated.The Modbus slave communication module must be connected to an SR3 B
6 6 6
BDmodular smart relay, with a 5 24 V supply.
Configuration
The Modbus slave communication module can be configured:1 independently, using the buttons on the smart relay (1).1 on a PC, using Zelio Soft 2 software, see page 9.
When using a PC, programming can be performed either in LADDER language or infunction block diagram (FBD) language, see pages 10 to 13.
Connection example
Modbus communication module
5
4
4
7
6
1
5bis
2
2
2
3
4
3
3 1 XBT N401 display unit.
2 Modular smart relay SR3 B 1 1 1 BD.
3 Modbus communication module SR3 MBU01BD.
4 Modbus network (cables VW3 A8 306R6 6
).
5 Junction box TWD XCA T3RJ (polarisation and line end adapter activated).
5bis Junction box TWD XCA T3RJ (line end adapter activated).
6 T-junction 170 XTS 04100.
7 T-junction VW3 A8 306TF6 6 .
Function description
1 The Modbus slave communication module is connected to a 2-wire or 4-wireModbus network (2).1
The maximum length of the network is 1000 m (9600 bauds max., AWG 26).1 A maximum of 32 slaves can be connected to the Modbus network, or a maximumof 247 slaves with repeaters.1 Line end adaptors must be fitted to both ends of the line(1 nF/10 V, 120 /0.25 W in series).1 The line must be polarised (470 /0.25 W resistors) (3).1 The connection cable and its RJ45 male connectors must be screened.1 The 7 terminal on the module must be connected directly to the protective earthat one point on the bus.
(1) Programming from the front panel and buttons on the smart relay is only possible in LADDER
language.(2) Please refer to installation instructions supplied with the product.(3) The polarisation resistors must be managed by the master.
DescriptionModbus slave communication module SR3 MBU01BD comprises:
1 Two retractable fixing lugs.2 A Modbus network connection (RJ45 screened female connector).3 A communication LED (COM).4 A Power on LED (PWR).5 A screw terminal block for the protective earth connection.6 A spring for clip-on mounting on a 35 mm mounting rail.7 Two locating pegs.8 Two locating pegs for clip-on fixing.
COM
SR3 MBU01BD
MB485-V1
PWR
6 1
8
8
2
5
3
4
1
7
7
Characteristics:page 35
Functions :page 36
References :page 40
Dimensions, mounting :page 41
532522
524121
524131
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
37/7235
Characteristics 1 Zelio Logic smart relays 1CommunicationModbus slave communication protocol
(1) Except for the configuration SR3 B1 1 1
BD + SR3 MBU01BD + SR3 XT43BD class A (class B:work in progress).
Environment characteristicsType SR3 MBU01BD
Product certifications UL, CSA, GL, C-TICK
Conformity with thelow voltage directive
Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)
Conformity with theEMC directive
Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4
Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block)IP 40 (front panel)
Overvoltage category Conforming to IEC/EN 60664-1 3
Degree of pollution Conforming to IEC/EN 61131-2 2
Ambient air temperaturearound the deviceConforming toIEC/EN 60068-2-1 andIEC/EN 60068-2-2
Operation C - 20... + 55 (+ 40 in non-ventilated enclosure)
Storage C - 40... + 70
Max. relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water
Maximum operating altitude Operation m 2000
Transport m 3048
Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc
Immunity to mechanical shock IEC/EN 60068-2-27, tes t Ea
Resistance toelectrostatic discharge
Immunity toelectrostatic discharge
IEC/EN 61000-4-2, level 3
Resistance to HF interference(immunity)
Immunity toelectromagnetic radiated fields
IEC/EN 61000-4-3
Immunity to fast transientsin bursts
IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequencyin common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (6
) IEC/EN 61000-4-11
Immunity to dampedoscillation waves
IEC/EN 61000-4-12
Conducted and radiatedemissions
Conforming to EN 55022/11(Group 1)
Class B (1)
Earthing Yes (please refer to installation instructions supplied with the product).
Presentation, description :page 34
Functions :page 36
References :page 40
Dimensions, mounting :page 41
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
38/7236
Functions 1 Zelio Logic smart relays 1CommunicationModbus slave communication protocol
(1) Programming from the front panel and buttons on the smart relay is only possible in LADDERlanguage.
Parameter entryParameters can be entered either using Zelio Soft 2 software or directly using thebuttons on the Zelio Logic smart relay (1).When the RUN instruction is given, the Zelio Logic smart relay initialises theModbus slave communication module in a configuration previously defined in thebasic program.
The Modbus slave communication module has 4 parameters:1 number of UART wires and format of the frames on the Modbus network,1 transmission speed,1 parity,1 network address of the Modbus module.
The default parameter settings are as follows: 2-wire, RTU, 19 200 bauds, evenparity, address n1.
Parameter entry Options
Number of wires 2 or 4
Frame format RTU or ASCII
Transmission speedin bauds
1200, 2400, 4800, 9600, 19 200, 28 800, 38 400, 57 600
Parity None, even, odd
Network address 1 to 247
Software workshopparameter entry window
Addressing of Modbus exchangesLADDER programming
In LADDER mode, the 4 data words (16 bits) to be exchanged cannot be accessedby the application. Transfers with the master are implicit and are effected in a waythat is totally transparent.
Modbus exchanges Code Number of words
Image of smart relay I/O Read03
4
Clock words Read/Write16, 06 or 03
4
Status words Read03
1
Function block diagram (FBD) programming
In FBD mode, the 4 input data words (16 bits) (J1XT1 to J4XT1) and the 4 outputdata words (O1XT1 to O4XT1) can be accessed by the application. Dedicatedfunction blocks make it possible to:1 break down a complete type input (16 bits) into 16 separate bit type outputs.2 example: break down a J1XT1 to J4XT1 type input and copy these status valuesto discrete outputs.1 make up a complete type output (16 bits) from 16 separate bit type inputs.2 example: transfer the status value of the discrete inputs or the status of a function
to an O1XT1 to O4XT1 type output.
Modbus exchanges Code Number of words
Input words Read/Write16, 06 or 03
4
Output words Read03
4
Clock words Read/Write16, 06 or 03
4
Status words
Read03
1
J1
XT1
J2
XT1
J3
XT1
J4
XT1
3
72
3
72
3
72
3
72
01
XT1
02
XT1
03
XT1
04
XT1
09
34
09
34
09
34
09
34
Presentation, description :page 34
Characteristics:page 35
References :page 40
Dimensions, mounting :page 41
524121
524110
Input words Output words
FDB program Editing window
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
39/7237
Presentation,description 1
Zelio Logic smart relays 1CommunicationEthernet server communication protocol
Presentation
Zelio Logic modular smart relays are connected to the Ethernet network via theEthernet server communication module.Communication module SR3 NET01BD allows communication on the Ethernetnetwork under the Modbus TCP protocol.
The Ethernet server communication module must be connected to an SR3 B6 6 6 BDmodular smart relay, with a 5 24 V supply.
Configuration
The Ethernet server communication module is configured from a PC with "Zelio Soft"software, see page 9.On the PC, programming is effected in function block (FDB) language, see pages 12and 13.
Connection example
1 Twido client, 40 I/O compact base controller TWD LCAE 40DRF.2 Ethernet network (cables 490 NTW 0006 6 ).3 ConneXium 499 NES 251 00 Switch.4 Zelio Logic modular smart relay SR3 B6 6 6 BD.5 Communication interface SR2COM01.6 Connecting cable SR2 CBL07 (supplied with the Modem communication
interface).7 GSM (or analogue PSTN) Modem.8 Ethernet server communication module SR3 NET01BD.9 Analogue I/O extension module SR3 XT43BD.
Function description
1 The Ethernet server communication module is connected to a local LAN typenetwork.1 The maximum cable length between 2 devices is 100 m.1 The connection cable must be at least category 5, and its RJ45 male connectorsmust be screened.1
The7
terminal must be connected directly to the protective earth.
Description
Ethernet server communication module SR3 NET01BD comprises:
1 Two retractable fixing lugs.2 An Ethernet network connection (RJ45 screened female connector).3 A communication LED (LK/ACT 10/100).4 A status LED (STS).5 A screw terminal block for the protective earth connection.6 A spring for clip-on mounting on a 35 mm mounting rail.7 Two locating pegs.8 Two locating pegs for clip-on fixing.
Ethernet servercommunication module
1
24
3
2 2
4
9
8
8
4
8
7
6
5
2
LK/ACT 10/100
SR3 NET01BD
STS
6 1
8
8
2
5
3
4
1
7
7
Characteristics:page 38
Functions :page 39
References :page 40
Dimensions, mounting :page 41
53631
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
40/7238
Characteristics 1 Zelio Logic smart relays 1CommunicationEthernet server communication module
(1) Except for the configuration SR3 B1 1 1
BD + SR3 NET01BD + SR3 XT43BD class A(class B: work in progress).
Environment characteristicsType SR3 NET01BD
Product certifications UL, CSA, GL (pending), C-TICK (pending)
Conformity with thelow voltage directive
Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)
Conformity with theEMC directive
Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4
Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block)IP 40 (front panel)
Overvoltage category Conforming to IEC/EN 60664-1 3
Degree of pollution Conforming to IEC/EN 61131-2 2
Ambient air temperaturearound the deviceConforming toIEC/EN 60068-2-1 andIEC/EN 60068-2-2
Operation C 0... + 55 (+ 40 in non-ventilated enclosure)
Storage C - 40... + 70
Max. relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water
Maximum operating altitude Operation m 2000
Transport m 3048
Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc
Immunity to mechanical shock IEC/EN 60068-2-27, test Ea
Resistance toelectrostatic discharge
Immunity toelectrostatic discharge
IEC/EN 61000-4-2, level 3
Resistance to HF interference(immunity)
Immunity toelectromagnetic radiated fields
IEC/EN 61000-4-3
Immunity to fast transientsin bursts
IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequencyin common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (6
) IEC/EN 61000-4-11
Immunity to dampedoscillation waves
IEC/EN 61000-4-12
Conducted andradiated emissions
Conforming to EN 55022/11(Group 1)
Class B(1)
Earthing Yes (please refer to installation instructions supplied with the product).
Presentation, description :page 37
Functions :page 39
References :page 40
Dimensions, mounting :page 41
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
41/7239
Functions 1 Zelio Logic smart relays 1CommunicationEthernet server communication module
Parameter entryParameter entry must be carried out using Zelio Soft 2 software.When the RUN instruction is given, the Zelio Logic smart relay initialises theEthernet server communication module in a configuration previously defined in thebasic program.
The Ethernet server communication module has 6 parameters:1 type of addressing (dynamic or static).1 IP address,1 sub-network mask,1 gateway address,1 reserved address,1 time out.
Addressing of Ethernet exchanges
Function block diagram (FBD) programming In FBD mode, the 4 input data words (16 bits) (J1XT1 to J4XT1) and the 4 output
data words (O1XT1 to O4XT1) can be accessed by the application. Dedicatedfunction blocks make it possible to:1 break down a complete type input (16 bits) into 16 separate bit type outputs.2 example: break down a J1XT1 to J4XT1 type input and copy these status valuesto discrete outputs.1 make up a complete type output (16 bits) from 16 separate bit type inputs.2 example: transfer the status value of the discrete inputs or the status of a functionto an O1XT1 to O4XT1 type output.
Ethernet exchanges Code Number of words
Input words Read/Write16, 06 or 03
4
Output words Read03
4
Clock words Read/Write16, 06 or 03
4
Statuswords Read03
1
Ethernet communication module configuration window
J1
XT1
J2
XT1
J3
XT1
J4
XT1
3
72
3
72
3
72
3
72
01
XT1
02
XT1
03
XT1
04
XT1
09
34
09
34
09
34
09
34
Presentation, description :page 37
Characteristics:page 38
References :page 40
Dimensions, mounting :page 41
Input words Output words
FDB program Editing window
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
42/7240
References 1 Zelio Logic smart relays 1Communication
8 Available: 1st quarter 2007
Modbus slave and Ethernet server communication modulesFor use with Network Reference Weight
kg
Modular smart relaysSR3 B
2 2
2 22 2
2 2
1BD and SR3 B2 2
2 22 2
2 2
2BD (1)Modbus SR3 MBU01BD 0.110
Ethernet SR3 NET01BD(2), (3)
0.110
Connection accessoriesAccessory Description Network Length Reference Weight
m kg
T-junctions3 2 x RJ45 connectors3 1 cable with integratedRJ45 connector
Modbus 0.3 VW3 A8 306TF03 0.190
1 VW3 A8 306TF10 0.210
3
2 x RJ45 femaleconnectors3
1 x RJ45 male connector
Modbus Withoutcable
170 XTS 04100 0.020
Junction
boxes
3 Screw terminal block
for main cable3 1 x RJ45 connectorfor tap link3 Isolation of RS 485serial link
2
Polarisation and
line end adapter2 Supply 5 24 V2
Mounting on 35 mm
9
rail
Modbus TWD XCA ISO8
0.100
3
3 x RJ45 connectors3
Polarisation and lineend adapter
2
Mounting on 35 mm
9 rail
Modbus TWD XCA T3RJ8
0.080
Line endadapter
For RJ45 connectorR = 120 , C = 1 nf
Modbus VW3 A8306RC 0.200
RS 485cables
2 x RJ45 connectors Modbus 0.3 VW3 A8306R03 0.030
1 VW3 A8306R10 0.050
3 VW3 A8306R30 0.150
Straightshieldedtwisted paircable
2 x RJ45 connectors Ethernet 2 490 NTW 000 02 (4)
5 490 NTW 000 05 (4)
12 490 NTW 000 12 (4)
40 490 NTW 000 40 (4)
80 490 NTW 000 80 (4)
conneXiumswitch
Ethernet 499 NES 251 00 0.190
(1) Compatible withSR3 B1 11 11 11 1
2BDfeaturing hardware version H1.0.01, available since June2005.
(2) Can only be used in FBD language.(3) Can only be used with "Zelio Soft 2" software version
2
V 4.1.(4) Cable conforming to EIA/TIA-568 standard category 5 and IEC 1180/EN 50 173, class D.
For UL and CSA 22.1 approved cables, add the letter Uat the end of the reference.
499 NES 251 00
SR3 MBU01BD
SR3 NET01BD
TWD XCA ISO
TWD XCA T3RJ
Presentation, description :pages 34 to 37
Characteristics:pages 35 to 38
Functions :pages 36 to 39
Dimensions, mounting :page 41
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
43/7241
Dimensions,mounting 1
Zelio Logic smart relays 1Communication
Communication modules SR3 66601BDCommon side view Rail mounting Screw mounting (retractable lugs)
57
52,5
70
44 15
90
35
27.
5
27.
5
108
35
25
35
100
2 x 4
Presentation, description :pages 34 to 37
Characteristics:pages 35 to 38
Functions :pages 36 to 39
References:page 40
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
44/7242
Presentation,description 1
Zelio Logic smart relays 1Analogue I/O extension modules
PresentationModular smart relays and analogue I/O extension modules
To improve performance and flexibility, Zelio Logic modular smart relays can be fittedwith analogue I/O extension modules with 10-bit resolution.The inputs accept 0-10 V, 0-20 mA and Pt 100 type signals.
Using a Zelio Logic modular smart relay with 5 24 V supply in conjunction with ananalogue 4 I/O extension module makes it possible to obtain up to 30 I/O, including8 analogue inputs and 2 analogue outputs.
The analogue I/O extension module must be connected to an SR3 6 6 6 BD modularsmart relay with a 5 24 V supply.
Description
The analogue I/O extension module has thefollowing on its front panel:1 Two retractable fixing lugs.2 Terminals for connection of the inputs.3 Terminals for connection of the outputs.4 A connector for connection to the smart
relay (powered via the smart relay).5 Locating pegs.
536279
Analogue I/Oextension modules
524127
1 2
1 Modular smart relay(10 or 26 I/O)
2 Analogue I/O extension module(4 I/O)
524128
1 2
1 Modular smart relay(10 or 26 I/O)
2 Modbus or Ethernet communication modules3 Analogue I/O extension module (4 I/O)
3
1 2
5
13
5
4
Characteristics:page 43
References, dimensions :page 44
Schemes:page 45
Combination of modular smart relays with
communication and I/O extension modules
1
11
1
The order shown above must be observed when usinga network communication module and an analogue I/Oextension module.An I/O extension module cannot be fitted before thenetwork communication module.
-
8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio
45/7243
Characteristics 1 Zelio Logic smart relays 1Analogue I/O extension modules
(1) Except for configuration SR3 B1 1 1
BD + SR3 MBU01BD + SR3 XT43BDor SR3 B
1 1 1
BD + SR3 NET01BD + SR3 XT4