7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 1/157
SEMINAR and
WORKSHOP on DUsCompliance with the PDC
November 12 – 13, 2012
Grand Men Seng Hotel, Davao City
Ronaldo T. Garcia
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 2/157
OUTLINEDMC Resolution 46, Series 2010
ERC Resolution 13, Series 2011
Rules to Govern the Monitoring ofCompliance of DUs with the PDC
Regulatory Compliance Officer
Distribution Code Enforcement Fines and Penalties
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 3/157
DMC Resolution No. 46,
Series 2010RATIFICATION OF THE ENDORSEMENT TO
THE ERC OF THE DRAFT "RULES TO GOVERN
THE MONITORING OF COMPLIANCE OF DISTRIBUTION UTILITIES WITH THE PHILIPPINE DISTRIBUTION CODE ”
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 4/157
Background
As mandated, the DMC, in coordination with the ERC,drafted rules governing the monitoring of compliance ofthe DUs with the PDC;
Expository presentations on the draft rules wasconducted on Sept. 22, 2010 (for Visayas & Mindanao)and Sept. 24, 2010 (for Luzon) at Mandaue, Cebu &ERC Hearing Room, respectively to gather inputs andcomments from DUs;
Public consultation was also conducted on Oct. 21, 2010at ERC Hearing Room before finalization of the same
Rules;
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 5/157
Background
The Distribution Technical StandardSubcommittee (DTSSC) gathered the commentsfrom various DUs and requested that the final
draft of the rules be forwarded to the ERC;
On December 6, 2010, the DMC has ratify andendorsed the draft rules to the ERC the draft
"Rules to Govern the Monitoring of Complianceof the Distribution Utilities (DUs) with thePhilippine Distribution Code" for its approval.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 6/157
DMC Res. 46, Series 2010
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 7/157
ERC Resolution No.
13, Series 2011Resolution Adopting the DMC
Rules to Govern the Monitoring ofCompliance of DUs with the PDC
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 8/157
Legal Basis
Section 43 (b) of RA 9136
Mandates the ERC to promulgate andenforce a National Grid Code and a
Distribution Code;Section 43 (t) of RA 9136
Mandates the ERC to perform such otherregulatory functions that are appropriate andnecessary in order to ensure the successfulrestructuring and modernization of theelectric power industry.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 9/157
Legal Basis
Section 2.2.5.1 of the PDC
DMC shall establish and publish its ownrules and procedures relating to the
conduct of its business, which include,among others, the monitoring ofdistribution code enforcement;
Section 2.2.5.2 of the PDCThe Rules and procedures of the DMCshall be approved by the ERC
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 10/157
Background
June 21, 2011 - Approval of the Rules
August 8, 2011 - Publication in The DailyTribune, pages 4-5
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 11/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 12/157
Salient FeaturesArticle I - General Provisions
Article II - Standards and Measurements
Article III - Prioritization of Compliance withthe Standards
Article IV - Requirements and Procedures
Article V - Final Provisions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 13/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 14/157
General ProvisionsPurpose
Scope of Application
Definition of Terms
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 15/157
PurposeEstablish a monitoring system
Ensure DU compliance
Promote accountability
Protect public interest
Set order of priority
Set a timeline for the compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 16/157
Scope of Application
Privately-owned DUs
Electric Cooperatives
LGU Owned-and–Operated DUs
Consortium of DUs
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 17/157
Scope of Application (Cont…)
Entities duly authorized to own, operateand maintain distribution facilities withineconomic zones
Other duly authorized entities engaged inthe distribution of electricity
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 18/157
DISTRIBUTOR’S COMPLIANCEMONITORING REPORT
The DCMR shall include the currentinformation on compliance with the PDCand Summary of Compliance Plans.
Proofs, justifications and explanation of itsself-assessment on the degree ofcompliance.
ERC through the DMC, shall assess anddetermine the degree or level ofcompliance of the DU.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 19/157
DISTRIBUTOR’S COMPLIANCEMONITORING REPORT (Cont…)
If the DU’s system does not comply withany of the requirements, the DU shallprepare a reliable and attainable
Compliance Plan.
The Compliance Plan shall indicate
The definite activities or projects to beimplemented by the DU.
The schedule of implementation andcosts associated with the said activities.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 20/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 21/157
Standards and Measurements
45 Standards
DSC-PDC # - Title of the Standard
Reference
References to the PDC Section
Description of the Standard
Measurements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 22/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 23/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-001
(3.2.3.4;
5.2.3)
Long Duration Voltage VariationsThe DU shall ensure that no undervoltage orovervoltage is present at the connection point ofany user in the Distribution System during normaloperating conditions.
Measurement:
Committed five (5) years statement of DistributionDevelopment Plan (DDP) shall be prepared inaccordance with the required technical analysesspecified in the PDC.
3rd R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 24/157
Long Duration Voltage Variations
PDC IEEE 1159-1995
Duration Voltage
Magnitude Duration
VoltageMagnitude
1. Undervoltage > 1 min < 90%< 0.9 > 1 min 0.8 to 0.9pu
2. Overvoltage > 1 min> 110%> 1.1
> 1 min1.1 to 1.2
pu
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 25/157
Long Duration Voltage Variations
Undervoltage plot
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 26/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-002
(3.2.3.5;
5.2.3.3)
Voltage Sags in the DistributionSystemThe DU shall ensure that the Distribution Systemhas sufficient capacity so that Voltage Sags whenstarting large induction motors will not adverselyaffect any User facilities or Equipment.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine Voltage Sags at the Connection Pointsof Users with large induction motors.
3rd R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 27/157
Voltage Sags in the Distribution System
PDC IEEE 1159-1995
DurationVoltage
MagnitudeDuration
VoltageMagnitude
1. Sag
0.5 cycleto 1.0min
10% to 90%0.1 to 0.9
Instantaneous
0.5 to 30
cycles
0.1 to 0.9 pu
Momentary 30 cycles to 3s
0.1 to 0.9 pu
Temporary 3 s to 1 min 0.1 to 0.9 pu
2. Swell
0.5 cycleto 1.0min
110% to180%
1.1 to 1.8
Instantaneous0.5 to 30cycles
1.1 to 1.8 pu
Momentary 30 cycles to 3s
1.1 to 1.4 pu
Temporary 3 s to 1 min 1.1 to 1.2 pu
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 28/157
Instantaneous Voltage Sag Caused by a Single-Line-To-Ground Fault
Voltage Sags in the Distribution System
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 29/157
Temporary Voltage Sag Caused by Motor Starting
Voltage Sags in the Distribution System
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 30/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-003
(3.2.4.4)
Total Harmonic Distortion (THD)At any User System, the THD of the voltage at
the Connection Points of the Distribution Systemshall not exceed five percent (5%) during normaloperating conditions.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine the THD of the voltage at theConnection Points of the Distribution System.
3rd NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 31/157
Total Harmonic Distortion (THD)
Harmonics - Sinusoidal voltages and currents
having frequencies that are integral multiples ofthe fundamental frequency. (PDC)
Total Harmonic Distortion (THD) – The ratioof the root-mean-square of the harmonics contentto the root-mean-square value of the fundamentalquantity, expressed as a percent of thefundamental. (Proposed PDC)
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 32/157
Total Harmonic Distortion (THD)
The total harmonic distortion (THD) is used to define theeffect of harmonics on the power system voltage. It isused in low-voltage, medium-voltage, and high-voltagesystems. It is expressed as a percent of the fundamental
and is defined as
%100×=
voltagel fundamentatheof amplitudetheof square
voltagesharmonicallof amplitudeof squaresallof sumTHD
%100
1
50
2
2
×=
∑=
V
V
THDh
h
Where V h = harmonic component of voltage of the order indicated by the subscript.h = order of harmonic
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 33/157
Total Harmonic Distortion (THD)
Composite harmonic waveform
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 34/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-004
(3.2.4.5)
Total Demand Distortion (TDD)At any User System, the TDD of the current at the
Connection Points of the Distribution Systemshall not exceed five percent (5%) during normaloperating conditions.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine the TDD at the Connection Points ofthe Distribution System.
3rd NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 35/157
Total Demand Distortion (TDD)
Total Demand Distortion (TDD) – The totalroot-mean-square of the harmonicscurrent distortion, in percent of the
maximum demand load current (15 or 30min demand).
( )
L
h
h
h
I
I
TDD
∑∞=
==
1
2
where I L = rms value of maximum demand load current h = harmonic order (1, 2, 3, 4, etc.)I h = rms load current at the harmonic order h
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 36/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-005
(3.2.5.2)
Voltage Unbalance in theDistribution SystemThe maximum Voltage Unbalance at theConnection Point of any User of the DistributionSystem, excluding the Voltage Unbalance passedon from the Grid shall not exceed 2.5 percentduring normal operating conditions.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine the Voltage Unbalance at theConnection Point.
3rd R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 37/157
Voltage Unbalance
Voltage Unbalance – Themaximum deviation from the
average of the three phasevoltages divided by the averageof the three phase voltages,
expressed in percent. (PDC)
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 38/157
Voltage Unbalance
Imbalance trend for a residential feeder
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 39/157
Voltage Unbalance
%100max
×=voltageaverage
voltageaverage fromdeviationUnbalanceVoltage
Sample:The phase-to-phase voltage reading
Va = 230 V Vb = 232 V Vc = 225 V
Average voltage = (230 + 232 + 225)÷3 = 229 V.
The max deviation = 4 (for the value of 225,i.e. 230=1; 232=3; 225=4)
Voltage Unbalance = 4÷229 × 100%= 1.7467 %= 1.7 %
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 40/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-006
(3.2.6.4)
Flicker Severity in the DistributionSystemThe Flicker Severity at the Connection Point ofany User of the Distribution System shall notexceed 1.0 unit for short term and 0.8 unit for longterm.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine the Flicker Severity at the ConnectionPoints of the Distribution System.
3rd R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 41/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R
or N R
DSC-PDC-007
(3.2.7.2)
Short Duration Peaks in theDistribution SystemInfrequent short-duration peaks may be permitted toexceed the levels specified in Section 3.2.4 of the PDCfor TDD and THD provided that such increases do notcompromise the service to other End-Users or causedamage to any Equipment at the Connection Points of
the Distribution System.Measurements:Procedures for connection of Users that may imposeshort-duration peaks should show that short-durationpeaks are being measured, monitored, and controlled.
3rd R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 42/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-008
(3.3.4.1;
3.3.2;
3.3.3)
Submission of DistributionInterruption ReportsThe Distribution Utility shall submit on a quarterlybasis the monthly Interruption Reports for itsDistribution System using the standard formatprescribed by the ERC, as adopted by the DMC.
Measurements:Records of events involving outage of Equipmentand power interruption of Users of the DistributionSystem for the last five (5) years shall bemaintained.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 43/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 44/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-009
(3.4.2.1;
3.4.1.2;
3.4.1.3)
Distribution System Loss ReportThe DU shall identify and report separately the
Technical and Non-Technical Losses in itsDistribution System to the ERC, through theDMC. The report shall include the AdministrativeLoss or Company Use.
Measurements:Records of actual System Losses segregated intoTechnical and Non-Technical, includingAdministrative Loss or Company Use for the lastfive (5) years shall be maintained.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 45/157
ERC Issuances on System Loss
Sept. 29, 2004 – ERC issued the Guidelines for the approval ofCaps on the Recoverable Rate of DistributionSystem Loss.
June 7, 2007 – ERC issued Res. No. 19, S.2007, “A Resolution
Embodying the ERC’s Policy for Replacing Existing
System Loss Caps of Distribution Utilities.”Dec. 8, 2008 – ERC promulgated Res. No.17, S.2008, “A Resolution
Adopting a New System Loss Cap for DUs.”
May 6, 2010 – ERC issued Res. No. 11, S.2010 “ A Resolution
Clarifying the Policy on the Treatment of KWHCompany Use by DU’s.”
May 9, 2011 – ERC issued Res. No.11, S.2011 “ A Resolution
Clarifying Resolution No. 17, S.2008 and SuspendingIndefinitely the Filing of the DU’s RespectiveApplication.”
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 46/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-010
(3.4.3.3;
5.2.4.2)
Technical Loss Reduction throughReactive Power CompensationThe DU shall correct feeder and substationfeeder bus Reactive Power Demand to a levelwhich will economically reduce feeder loss.
Measurements:Actual measurements, computer simulations,and/or calculations shall be conducted todetermine feeder losses.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 47/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-011
(3.5.3.1;
3.5)
Customer Service Program ReportThe DU shall prepare and submit a report to the
ERC, through the DMC, on the Customer ServiceStandards provided in the PDC. The DistributionUtility shall justify the basis for the target levels ofperformance.
Measurements:
Records of Customer Service Program for thelast five (5) years shall be maintained. CustomerService Program shall include target levels andcorresponding justifications.
2nd NR
Table 3 1
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 48/157
Table 3-1
Customer Service Standards for Distribution UtilitiesCustomer Service Measure of Performance
Processing of application including
estimates of charges
Number of days upon submission of complete requirements
Service connection Number of days upon compliance with all government and Distribution Utility
requirements
Restoration of service after a fault
Interruption on the secondary side,
including service drop/lateral
Numbers of hours for 100% restoration
Power Quality complaints a) Visit within x number of working days after receipt of complaint or substantive
answer within y number of days; and
b) Correction of Power Quality problems within z number of months
Informing Customers on schedule of
power Interruptions
Announcements x number of days prior to the scheduled Interruptions
Responding to emergency calls Response within x number of hours after receipt of call
Billing queries and complaints a) Answer to queries within x number of hours; and
b) Correction of errors in billing statement within y number of hours (or days)
Payment queries and complaints a) Answer to queries within x number of hours; and
b) Correction of errors in payments within y number of hours (or days)
Meter complaints a) Visit within x number of working days after receipt of complaint or substantive
answer within y number of days; and
b) Correction of meter problems within z number of weeks
Reconnection of service Reconnect within x hours after payment of all dues, provided payment is made before a
specified cut-off time
Making and Keeping of appointments a) Specific time is given to the Customer; and
b) Seeing the Customer at the appointed time
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 49/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-012
(3.6.1.1;
3.6.1.2;
3.6.1.3)
Distribution System Development,Operation and Maintenance according to
PEC and OSHSThe Distribution Utility shall develop, operate, andmaintain its Distribution System in a safe manner andshall always ensure a safe work environment for its
employees.
Measurements:Review of safety requirements and procedures forDistribution System design, installation, operation andmaintenance shall be conducted to determineconsistency to the provisions of the latest editions ofPEC 1 & 2 and OSHS.
1st NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 50/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-013
(3.6.3;
3.6.2;
3.6.3)
Submission of Personnel SafetyRecords and ReportsThe DU shall submit to the ERC, through theDMC, copies of records and reports required byOSHS as amended. These shall include themeasurement of performance specified in Section3.6.2 of the PDC.
Measurements:Records of accidents and illnesses of employeesshall be maintained.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 51/157
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 52/157
OutlineI. Rule 1000 – General Provision
II. Rule 1020 - Registration
III. Rule 1033 – Training and Personnel
Complement
IV. Rule 1040 – Health and Safety Committee
V. Rule 1050 – Notification and Keeping of
Records of Accidents and/or
Occupational Illnesses
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 53/157
General ProvisionRULE 1000 - GENERAL PROVISION
Rule 1001: Purpose and Scope:(1) To protect every workingman against the dangers of injury,
sickness or death through safe and healthful workingconditions, thereby assuring the conservation of valuablemanpower resources and the prevention of loss or damage tolives and properties, consistent with national developmentgoals and with the State’s commitment for the totaldevelopment of every worker as a complete human being.
(2) This Standards shall apply to all places of employmentexcept as otherwise provided in this Standard.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 54/157
RegistrationRULE 1020 - REGISTRATION• 1021: General Provisions:
Every employer shall register his business with the
Regional Labor Office or authorized representativehaving jurisdiction thereof to form part of a databank ofall covered establishments.
• 1022: Registrable Unit:
The establishment regardless of size of economicactivity, whether small, medium or large scale in onesingle location, shall be one registrable unit.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 55/157
RegistrationRULE 1020 – REGISTRATION (Cont…)
• 1023: Period of Registration:
(1) Existing establishments shall be registered within
sixty (60) days after the effectivity of this Standards.(2) New establishments shall register within thirty (30)
days before operation.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 56/157
RegistrationRULE 1020 – REGISTRATION (Cont…)
• 1024: Registration:
(1) Registration shall be made in form DOLE-BWC-IP-3
in 3 copies & to be submitted to the Regional LaborOffice or authorized representatives.
(2) Registration shall be free of charge & valid for thelifetime of the establishment except when any of thefollowing conditions exists:
a. change in business name,
b. change in location,
c. change in ownership, or
d. re-opening after previous closing.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 57/157
RegistrationRULE 1020 – REGISTRATION (Cont…)
• 1024: Registration: (Cont…)
(3) Registration shall include a layout plan of the place of
work floor by floor, in a scale of 1:100 meters white orblue print showing all the physical features of theworkplace including storage, exits, aisles, machinery,clinic, emergency devices and location.
(4) The registration form may be reprinted or reproducedand the back page may be used for other information.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 58/157
Training & Personnel Complement
RULE 1030 - TRAINING OF PERSONNEL INOCCUPATIONAL SAFETY AND HEALTH
• 1033: Training and Personnel Complement:
(1) The training course prescribed by the Bureau underthis rule shall be a requisite for the appointment ofthe safetyman in place of employment.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 59/157
Training & Personnel Complement
• 1033: Training and Personnel Complement: (Cont..)
(2) At least the ff. no. of supervisors or technical personnelshall take the required training & shall be appointedsafety man, full time or part-time depending on thenumber of workers employed, & the type of workplace.
Number of Workers No. of Safety Man
Hazardous Workplace
200 and below 1 part-time safety man
Over 200 to 1000 1 full-time safety man
For every 1000 workers 1 full-time safety man
Non-hazardous Workplace
Less than 1000 1 part-time safety man
For every 1000 1 full-time safety man
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 60/157
Training & Personnel Complement
RULE 1030 - TRAINING OF PERSONNEL INOCCUPATIONAL SAFETY AND HEALTH
• 1033: Training and Personnel Complement:
(Cont…)(3) Duties of the Safety Man:
A part-time safetyman shall be allotted at least 4hours per week to perform the duties as safetyman.
(4) The employment of a full-time safety man may not berequired if the employer enters into a written contractwith a qualified consultant or consulting organization.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 61/157
Health and Safety Committee
RULE 1040 - HEALTH & SAFETYCOMMITTEE
• 1041: General Requirements:
In every place of employment, a health and safetycommittee shall be organized within sixty (60) days afterthis Standards takes effect and for new establishmentswithin one (1) month from the date the business starts
operating. In both cases the Committee shall reorganizeevery January of the following year.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 62/157
Health and Safety Committee
RULE 1040 - HEALTH & SAFETY COMMITTEE
1042: Types & Composition of Health & SafetyCommittee:
TYPE No. of Workers Team Composition
A > 400 Chairman, Members (2 DH, 4W), Physician &Sec.
B >200 - 400 Chairman, Members (1 S, 3W), Physician orNurse & Sec.
C 100 - 200 Chairman, Members (1 F, 3W), Nurse & Sec.
D <100 Chairman, Members (3W), Nurse & Sec.
E 2> under 1Bldg. Chairman, Members (2S, 2W) & Sec.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 63/157
Health and Safety Committee
RULE 1040 - HEALTH & SAFETY COMMITTEE
• 1043: Duties of the Health and Safety Committee:
1043.01: Health and Safety Committee:
The Committee is the planning & policymaking group in all matters
pertaining to safety and health. The principal duties of theCommittee are:
(1) Plans & develops accident prevention programs.
(2) Directs the accident prevention efforts in accordance with thesafety programs, safety performance and government regulationsin order to prevent accidents.
(3) Conducts safety meetings at least once a month.
(4) Reviews reports of inspection, accident investigations &implementation of program.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 64/157
Health and Safety Committee
RULE 1040 - HEALTH & SAFETY COMMITTEE
• 1043: Duties of the Health and Safety Committee:
1043.01: Health and Safety Committee:
(5) Submits reports to the manager on its meetings & activities.
(6) Provides necessary assistance to gov’t. inspecting authorities inthe proper conduct of their activities.
(7) Initiates & supervises safety training for employees.
(8) Develops and maintains a disaster contingency plan and
organizes such emergency service units as may be necessary tohandle disaster situations pursuant to the emergencypreparedness manual for establishments of the Office of CivilDefense.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 65/157
Health and Safety Committee
RULE 1040 - HEALTH & SAFETY COMMITTEE
• 1044: Term of Office of Members:
1044.01: Health and Safety Committee:
The term of office of the department head in the committee may
be one (1) year.
The term of office of the worker members in Type A and Type Bmay be for two (2) years each; in Type C, D and E Committees,may all be one (1) year.
The chairman, physician or nurse and the safety man shall bepermanent members of the committee.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 66/157
Records of Accidents
• 1054: Keeping of Records:(1) The employer shall maintain & keep an accident or
illness record which shall be open at all times for
inspection to authorized personnel containing thefollowing min. data:
a. Date of accident or illness;
b. Name of injured or ill employee, sex and age;
c. Occupation of injured or ill employee at the time ofaccident or illness;
d. Assigned causes of accident or illness;
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 67/157
Records of Accidents
• 1054: Keeping of Records: (Cont…)
e. Extent and nature of disability;
f. Period of disability (actual and/or charged);
g. Whether accident involved damaged to materials,equipment or machinery, kind and extent of damage,including estimated or actual cost; and
h. Record of initial notice and/or report to the Regional
Labor Office or authorized representative.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 68/157
Records of Accidents
• 1054: Keeping of Records: (Cont…)
(2) The employer shall accomplish an Annual WorkAccident/Illness Exposure Data Report in duplicate
using the prescribed form DOLE/BWC/HSD-IP-6b,which shall be submitted to the Bureau copyfurnished the Regional Labor Office or dulyauthorized representative having jurisdiction on orbefore the 30th day of the month following the end of
each calendar year.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 69/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-014
(5.2.3.2)
Selection of Voltage Ratings ofDistribution EquipmentThe Distribution Utility shall consider themaximum estimated Voltage Swell in theselection of the voltage ratings of DistributionEquipment.
Measurements:Procedures and criteria for selection of voltageratings of Distribution Equipment.
3rd NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 70/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-015
(5.2.8.1;
5.2.8.2;
6.5.2.2)
Transient Overvoltage SuppressionDevices in the Distribution SystemThe Distribution System and the User Systemshall be designed and operated to includedevices that will mitigate the effects of transientovervoltage on the Distribution System and theUser System.
Measurements:Design procedures and criteria for selection andcoordination of insulation Equipment (e.g.,transformers, CB, fuses, DS, CT/PT, couplingdevices, etc.)
1st NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 71/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-016
(5.2.9.1;
5.2.9;
7.2.1.4)
Protection of the Distribution SystemThe Distribution System shall be designed and
operated with sufficient protection to ensuresafety and to limit the frequency and duration ofinterruptions to End-Users.
Measurements:Protection policy, requirements, and procedures
shall include but not limited to fault clearance timeand auto reclosing.All Distribution Equipment and devices shall beproperly coordinated and adequately protected.
1st NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 72/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-017
(5.2.10.1;
5.2.10.2;
6.3.3.3)
Fault Levels Information in theDistribution SystemThe Distribution Utility shall inform the User of thedesigned and the existing fault levels of theDistribution System at the Connection Point.
Measurements:Short circuit reports shall contain the designedand existing fault levels at each Connection Pointto be considered by the User in the design of theUser System.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 73/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-018
(5.2.11.1;
5.2.11)
Grounding Method Used in theDistribution SystemThe DU shall inform the User of the grounding methodused in the Distribution System. The specification ofDistribution Equipment shall consider the maximumVoltage Swell that will be imposed on the Equipmentduring faults involving ground.
Measurements:Grounding method used in the DistributionSystem and standards and specifications forcompliance of Users shall be readily available toUsers.
1st NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 74/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-019
(5.2.12.2;
5.2.12)
Monitoring and Control ofEquipment for User SystemThe DU shall provide, install, and maintain thetelemetry outstation and all associated Equipmentneeded to monitor the User System.
Measurements:Telemetry outstation and all associatedEquipment needed to monitor the User Systemshall be provided, installed, and maintained. ThisStandard is applicable only to DU with anagreement with at least one (1) User regardingtelemetry.
3rd NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 75/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-020
(5.2.13.1;
5.2.13)
Standards for Equipment in theDistribution SystemAll Equipment at the Connection Point shallcomply with the requirements of the IECStandards or their equivalent national standards.
Measurements:All Equipment at the Connection Point of theDistribution System shall be designed,manufactured and tested in accordance with therequirements of the IEC Standards or theirequivalent national standards.
1st NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 76/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-021
(5.2.14.2)
Maintenance Logbook for the Equipmentin the Distribution System
The DU shall maintain a logbook containing the testresults and maintenance records relating to itsequipment at the Connection Point and shall make this
logbook available when requested by the User.
Measurements:
Test results & maintenance records of equipment in allConnection Points of the Dist. Sys. shall readily beavailable to determine completeness of records.Records of testing and maintenance of equipment at all
Connection Points of the Dist. Sys. shall be listed.
1st R
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 77/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-022
(5.3.5.1;
5.3;
5.9.3)
Application for New Connection orModification of Existing Connection to the
Distribution SystemThe DU shall establish the procedure for theprocessing of applications for connection ormodification of an existing connection to theDistribution System.
Measurements:Procedures and requirements for application ofnew connection or modification of existingconnection to the Distribution System shall beconsistent with Article 5.3 of the PDC.
1st NR
S f C
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 78/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-023
(5.6.3.1;
5.6)
Fixed Asset Boundary Document forEquipment in the Distribution System
The Distribution Utility shall establish theprocedure and forms required for the preparationof the Fixed Asset Boundary Documents.
Measurements:Procedures and forms for preparation of Fixed
Asset Boundary Documents for Equipment at theConnection Point of the Distribution System shallbe in accordance with Article 5.6 of the PDC.
1st NR
Di ib ’ S f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 79/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R
or N R
DSC-PDC-024
(5.7.1.1;
5.7)
Electrical Diagrams for the Equipment inthe Distribution System
The DU shall specify the procedure and format tobe followed in the preparation of the ElectricalDiagrams for any Connection Point.
Measurements:Procedures and forms for preparation of Electrical
Diagrams at the Connection Point of theDistribution System shall be in accordance w/ Art.5.7 of the PDC.Electrical Diagrams for all the Connection Pointsof the Distribution System shall be completed.
1st NR
Di ib ’ S f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 80/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-025
(5.8.1.1;
5.8)
Connection Point Drawing in theDistribution SystemThe DU shall specify the procedures and formatsto be followed in the preparation of theConnection Point Drawings for any ConnectionPoint.
Measurements:Procedures and forms for preparation ofConnection Point Drawings at the ConnectionPoint of the Distribution System shall be inaccordance with Article 5.8 of the PDC.
1st NR
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 81/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-026
(5.9.3;
5.9)
User Data RegistrationThe DU shall develop the forms for all data to be
submitted in accordance with an application for aConnection Agreement or an AmendedConnection Agreement.
Measurements:Procedures and forms for submission of
Distribution System Data to be registered shall bein accordance with Article 5.9 of the PDC.Data relating to Connection Point and UserSystem for all the Connection Points of theDistribution System shall be completed.
1st NR
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 82/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-027
(6.2.1.2;
6.2.5.1;
6.4;
6.5)
Maintenance of DistributionPlanning Data BankThe DU shall consolidate and maintain the Dist.Planning Data according to the ff. categories:
(a) Forecast Data;(b) Estimated Equipment Data; and(c) Registered Equipment Data.
Measurements:Procedures for collection and updating ofDistribution Planning Data shall be in accordancewith Articles 6.4 and 6.5 of the PDC.
1st R
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 83/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-028
(6.2.5.2;
6.2.5;
6.3)
Submission of DDPThe Distribution Utility shall develop and submit
its DDP annually to the Department of Energy(DOE). In the case of an Electric Cooperative,such plan shall also be submitted through theNational Electrification Administration (NEA). Acopy of the DDP shall also be submitted to theDMC.
Measurements:Distribution Development Plan (DDP) preparedduring the preceding year shall be submitted tothe DOE, NEA, and DMC.
1st R
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 84/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-029
(6.3.1.1;
6.3)
Distribution Planning StudiesThe DU shall conduct distribution planning
studies to ensure the safety and reliability of theDistribution System.
Measurements:Procedures for conducting Distribution Planningstudies.
Analytical tools shall include, but are not limited tovoltage drop analysis, short circuit analysis,system loss analysis, reliability analysis andeconomic/ financial analysis, for conductingDistribution Planning and impact studies
1st R
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 85/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-030 (7.2.1.5;
7.4)
Distribution Operating ProceduresThe DU is responsible for ensuring that safe and
economic distribution operating procedures arealways followed.
Measurements:Distribution operating procedures, includingcommunications channels
1st NR
Di t ib t ’ St t t f C li
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 86/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-031
(7.4.3.1)
Submission of Monthly ReportsThe DU shall prepare and submit to the DMC
monthly reports on distribution operation.Measurements:Records of Distribution operations (MonthlyOperations Reports) shall be submitted to theDMC using the prescribed format by the ERC as
adopted by the DMC on a quarterly basispursuant to DMC Resolution No. 32, series of2009.
1st R
Distrib tor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 87/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-032
(7.4.3.2)
Submission of SIRThe DU shall submit to the DMC the Significant
Incident Reports prepared pursuant to theprovisions of Section 7.7.2 of the PDC.
Measurements:Records of Significant Incidents in the DistributionSystem (all Significant Incident Reports) shall be
submitted to the DMC using the prescribed formatunder the DMC SIR Procedures approved byERC through Resolution No. 5 series of 2010“Resolution Adopting the DistributionManagement Committee Significant Incident
Reporting Procedures”
1st R
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 88/157
Distributor’s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-033
(7.4.3.3)
Submission of Annual OperationsReportThe DU shall prepare and submit to the DMC anAnnual Operations Report. This report shall include theSignificant Incidents on the Distribution System thathad a material effect on the Distribution System or theSystem of any User.
Measurements:Records of Distribution operations (AnnualOperations Report) shall be submitted to theDMC using the ERC DU-MO2 prescribedtemplate.
1st R
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 89/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-034
(7.5.1.1;
7.2.1.2;
7.5)
Distribution Maintenance ProgramThe DU shall prepare the ff. Dist. Maint. Prog’s.
based on forecasted demand, User’s provisionalMaint. Prog. & requests for maintenanceschedule:Records of procedures for preparing the Dist. Maint.
Prog. shall be in accordance w/ Sect. 7.5.1 of the PDC.
Measurements:Records of Maint. Prog’s. shall include the ff:Three (3)-year Maintenance Program;
Annual Maintenance Program; andMonthly Maintenance Program
1st R
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 90/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-035
(7.6.1.1;
7.2.1.6;
7.6)
Distribution Demand and VoltageControl ProgramThe Distribution Utility shall implement DemandControl when the System Operator has issued aRed Alert Notice due to a generation deficiency inthe Grid or when a Multiple Outage Contingencyresulted in island grid operation.
Measurements:Records of procedures for Demand Control.Records shall include responses to theinstructions of the System Operator.
1st NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 91/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-036
(7.7.1.3;
7.7)
Distribution Emergency ProceduresThe DU shall develop and maintain a Manual of
Distribution Emergency Procedures, which listsall parties to be notified, including their businessand home phone numbers, in case of anemergency.
Measurements:
Manual of Distribution Emergency Proceduresshall be developed, maintained and distributed,and shall include procedures to be observedduring emergency drills.
2nd NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 92/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-037
(7.7.1.4;
7.7)
Distribution Emergency DrillsEmergency drills shall be conducted at least once
a year to familiarize all personnel responsible foremergencies.
Measurements:Emergency drills conducted during the precedingyear.
If an emergency drill has not been conducted yet,schedules and detailed instructions for theemergency drill shall be provided.
2nd R
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 93/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-038
(7.8.1.5;
7.8)
Safety Coordination Procedures forSafety PrecautionsSafety Coordination Procedures shall beestablished for the coordination, establishment,maintenance and cancellation of safetyprecautions on MV and HV Equipment when workor testing is to be carried out on the Distribution
System or the User System.Measurements:Records of procedures for implementing SafetyPrecautions shall be in accordance with Article7.8 of the PDC
2nd NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 94/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-039
(7.9.1.1;
3.2;
7.9.1)
Power Quality Testing & Monitoringin the Distribution SystemThe DU shall, from time to time, determine theneed to test and/or monitor the Power Quality atvarious points on its Distribution System.
Measurements:Procedures and schedule of monitoring of Power
Quality of selected nodes of the DistributionSystem.
3rd NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 95/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-040 (7.9.2.1;
7.9.2)
Monitoring of Effect of User Systemon the Distribution SystemThe DU shall, from time to time, monitor the effectof the User System on the Distribution System.
Measurements:Procedures and schedule of monitoring the effectof the User System on the Distribution System.
3rd R
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 96/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P
r i o’ t y.
R or N R
DSC-PDC-041
(7.10.1.1;
7.10)
System Tests on the Distribution Systemor the User System
System Tests w/c involve the simulation of conditionsor the controlled application of unusual or extremeconditions that may have an impact to the Dist. Sys. orthe User Sys. shall be carried out in a manner thatshall not endanger any personnel or the general public.
Measurements:
Records of procedures for implementing Sys. Testsshall be in accordance with Article 7.10 of the PDC.Procedures shall describe the details of therequirements for the Sys. Test Request, Sys. TestGroup, Sys. Test Program and Sys. Test Report.
1st NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 97/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R or N R
DSC-PDC-042
(7.11.1.1;
7.11)
Capability Tests Procedures forEmbedded Gen. Units
Tests shall be conducted, in accordance with theagreed procedures and standards to confirm thecompliance.
Measurements:Records of procedures to confirm the capability of
Embedded Generating Units shall be inaccordance w/ Article 7.10 of the PGC & Article7.11 of the PDC.Capability Tests shall be conducted for all EmbeddedGenerating Units w/in the Distribution System.
1st NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 98/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R or N R
DSC-PDC-043
(7.12.1.1;
7.12.1)
Std. Sys. for Site & Equip’t. IDThe DU shall develop and establish a Standard Systemfor Site and Equipment Identification to be used inidentifying any site or equipment in all electricaldiagrams, Connection Point drawings, distributionoperation instructions, notices and other documents
Measurements:Procedures for Standard System for Site and
Equipment Identification shall be in accordancewith Section 7.12.1 of the PDC.Records of all Site and Equipment shall be withassigned identification according to the StandardSystem for Site and Equipment Identification.
3rd NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 99/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R or N R
DSC-PDC-044
(7.12.2.1;
7.12.2)
Std. labeling Sys. for Site & Equip’t. IDThe Distribution Utility shall develop and establisha Standard Labeling System, which specifies thedimension, sizes of character, and colors of labelsto identify the Sites and Equipment.
Measurements:Procedures for labeling the Sites and Equipment
in the Distribution System shall be in accordancewith Section 7.12.2 of the PDC.
3rd NR
Distributor’s Statement of Compliance
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 100/157
Distributor s Statement of Compliance
Ref. No.(PDC Sect .)
StandardMeasurements
P r i o’ t y.
R or N R
DSC-PDC-045
(7.12.2.2)
Installation of Site & Equip’t. ID.The Distribution Utility or the User shall be
responsible for the provision and installation of aclear and unambiguous label showing the Siteand Equipment Identification at their respectiveSystem.
Measurements:
All Sites and Equipment in the DistributionSystem shall be certified and labeled indicatingthe dates and persons in-charge of labeling inaccordance with the Standard System for Siteand Equipment Identification and Labeling.
3rd NR
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 101/157
PRIORITIZATION
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 102/157
PRIORITIZATION
• First Priority - Compliance within 1 year
• Second Priority - Compliance within 3 years
• Third Priority - Compliance within 5 years
Note: DUs under PBR, compliance within 5 years after its current regulatory reset
ECs under the RSEC-WR, ERC decision on their performance standard would prevail
First Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 103/157
First Priority
Reference StandardDSC-PDC-008 Interruption Report
DSC-PDC-009 System Loss Report
DSC-PDC-010 Technical Loss ReductionDSC-PDC-012 Safety Procedures
DSC-PDC-013 Safety Reports
DSC-PDC-015 Transient Overvoltage
DSC-PDC-016 Protection of the Dist. System
DSC-PDC-017 Fault Levels
DSC-PDC-018 Grounding Method
First Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 104/157
First Priority
Reference StandardDSC-PDC-020 Standards for Equipment
DSC-PDC-021 Maintenance Logbook
DSC-PDC-022 Application for New ConnectionDSC-PDC-023 Fixed Asset Boundary
DSC-PDC-024 Electrical Diagram
DSC-PDC-025 Connection Point Drawing
DSC-PDC-026 User Data Registration
DSC-PDC-027 Planning Data Bank
DSC-PDC-028 DDP
First Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 105/157
First Priority
Reference StandardDSC-PDC-029 Distribution Planning Studies
DSC-PDC-030 Operating procedure
DSC-PDC-031 Submission of Monthly ReportsDSC-PDC-032 Submission of SIR
DSC-PDC-033 Annual Operations Report
DSC-PDC-034 Maintenance Program
DSC-PDC-035 Demand & Voltage Control
DSC-PDC-041 System Tests
DSC-PDC-042 Capability Tests
Total 27
Second Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 106/157
Second Priority
Reference Standard
DSC-PDC-011 Customer Service Program
DSC-PDC-036 Emergency Procedures
DSC-PDC-037 Emergency Drills
DSC-PDC-038 Safety Coordination
Total 4
Third Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 107/157
Third Priority
Reference StandardDSC-PDC-001 Long Duration Voltage Variation
DSC-PDC-002 Voltage Sags
DSC-PDC-003 THDDSC-PDC-004 TDD
DSC-PDC-005 Voltage Unbalance
DSC-PDC-006 Flicker Severity
DSC-PDC-007 Short Duration Peak
Third Priority
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 108/157
Third Priority
Reference Standard
DSC-PDC-014 Voltage Ratings
DSC-PDC-019 Equipment Monitoring & Control
DSC-PDC-039 Power Quality Testing
DSC-PDC-040 Monitoring of the Effect of User SystemDSC-PDC-043 Equipment Identification
DSC-PDC-044Labeling System for Site andEquipment
DSC-PDC-045Installation of Site and EquipmentIdentification
Total 14
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 109/157
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 110/157
Reportorial Requirements
DUs shall submit its Distributor’sCompliance Monitoring Report using theprescribed template (Annex “A”).
Distributor’s Compliance Monitoring Report
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 111/157
Distributor s Compliance Monitoring Report
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 112/157
Reportorial Requirements
• The Report shall specify, but not limited to,the following:
a) Standard or the prescribed technical
specifications, performancestandards, financial standards orother requirements of the PDC;
b) Measurements by which thecompliance of the reporting entitywith the Standard will be assessed;
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 113/157
Reportorial Requirements
• The Report shall specify, but not limited to,the following: (Cont…)
c) Self-assessment and certification of the
reporting entity concerning its degree orlevel of compliance with the Standard;and
d) Definite activities or projects to beimplemented by the DU to fully complywith the requirements of the PDC.
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 114/157
Reportorial Requirements
The DU shall assess the applicability of theStandard to its Distribution System(s). If theStandard is applicable, the self-assessed degreeor level of compliance shall be indicated in the
Report. The degree of compliance with theStandard can be:
Full Compliance - Complies with all the requirements of the
Standard; and
Non-Compliance - Not in compliance with one or more of the
requirements of this Standard but has definite plan and schedule tocorrect all violations or complete all requirements;
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 115/157
Reportorial Requirements
Where the DU is in full compliance with the non-recurringStandard, the DU shall submit any proof of compliance inlieu of the required supporting information and/ordocuments. However, should there be any amendments
to the required supporting information and/or documents,these shall submitted as part of the Report.
The non-recurring Standard is a Standard that requiresestablishment of policies, procedures and systems tocomply with technical standards. Table 2 indicates therecurring & the non-recurring Standard.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 116/157
RECURRING
DSC-PDC-001 Voltage Variations
DSC-PDC-002 Voltage Sags
DSC-PDC-005 Voltage Unbalance
DSC-PDC-006 Flicker Severity
DSC-PDC-007 Short Duration PeaksDSC-PDC-008 Interruption Reports
DSC-PDC-009 System Loss Report
DSC-PDC-010 Loss Reduction - KVAR
DSC-PDC-013 Safety Records & Rpts.
DSC-PDC-017 Fault Levels
DSC-PDC-021 Maintenance Logbook
DSC-PDC-027 Planning Data
DSC-PDC-028 DDP
NON-RECURRING
DSC-PDC-003 THD
DSC-PDC-004 TDD
DSC-PDC-011 Cust. Service Program
DSC-PDC-012 PEC & OSHS
DSC-PDC-014 Voltage RatingsDSC-PDC-015 Transient Overvoltage
DSC-PDC-016 Protection
DSC-PDC-018 Grounding Method
DSC-PDC-019 Monitoring & Control
DSC-PDC-020 Standards for Equip’t.
DSC-PDC-022 App’tn. for New Con’tn.
DSC-PDC-023 Fixed Asset Boundary
DSC-PDC-024 Electrical Diagrams
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 117/157
RECURRING
DSC-PDC-029 Planning Studies
DSC-PDC-031 Monthly Reports
DSC-PDC-032 SIR
DSC-PDC-033 Annual Operations Rpt.
DSC-PDC-034 Maintenance ProgramDSC-PDC-037 Emergency Drills
DSC-PDC-040 Effect of User
DSC-PDC-041 System Tests
NON-RECURRING
DSC-PDC-025 Connection Pt. Draw’g.
DSC-PDC-026 User Data Registration
DSC-PDC-030 Operating Procedures
DSC-PDC-035 Demand & Volt. Cont’l.
DSC-PDC-036 Emergency ProceduresDSC-PDC-038 Emergency Drills
DSC-PDC-039 Power Quality
DSC-PDC-042 Tests Procedures
DSC-PDC-043 Site & Equipment I.D.
DSC-PDC-044 Labeling System
DSC-PDC-045 Installation of I.D.
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 118/157
Reportorial Requirements
Where the Standard is not applicable tothe reporting entity or the reporting entityis not in full compliance with the Standard,
the reporting entity shall explain thereasons for such conditions.
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 119/157
Reportorial Requirements
The DU entity shall ensure that supportinginformation and/or documents to justify its self-assessment of compliance w/ the Standard arereadily available for verification & inspection by
the ERC, through the DMC. These shall includedocumentations containing procedures, records,reports, programs, plans, actions taken or to be
taken & other information that demonstrate thecompliance of the reporting entity with theStandard.
Reportorial Requirements
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 120/157
Reportorial Requirements
The Distributor’s Compliance MonitoringReport shall be certified by the authorizedperson of the reporting entity and shall be
submitted under oath to the ERC, throughthe DMC.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 121/157
Procedures for Reporting
4.2.1 ReportingA reporting entity shall submit to the ERC
not later than May 31 of each year, the
Distributor’s Compliance MonitoringReport (in hard and electronic copies),indicating its performance for the
preceding calendar year against theminimum Standards provided in the PDC.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 122/157
Procedures for Reporting
4.2.2 Self-AssessmentA reporting entity shall conduct self-
assessment through periodic monitoring of
its compliance with the Standards of thePDC and provide in a form and mannerand at such times as may be requested by
the ERC, Distributor’s ComplianceMonitoring Report under oath as set out inSection 4.2.3 of these Rules.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 123/157
Procedures for Reporting
4.2.3 Record KeepingA DU shall maintain records of compliance
and shall be available anytime for
inspection.
A DU shall maintain detailed records of all
technical and economic evaluationconducted to comply w/ the requirementsset out in Chapter 6 the PDC.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 124/157
Procedures for Reporting
4.2.3 Record Keeping (Cont…)
All submitted reports shall be kept by
the DMC and made available to theERC upon request for a period of five
(5) years.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 125/157
ocedu es o epo t g
4.2.4 Compliance AuditThe ERC, through the DMC, shall conduct
annual Compliance Audit in random
manner, including spot inspections, tomonitor compliance of the reporting entitywith the Standards of the PDC.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 126/157
p g
4.2.4 Compliance Audit (Cont…)The DU will be provided with a 60-day
notification and all the necessary
documents required by the Audit Team.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 127/157
p g
4.2.4 Compliance Audit (Cont…) The Audit Team will review the DU’s evidence of
compliance with all the applicable Standards of
the PDC with the technical personnel of thereporting entity and as required, provideadditional information to clarify data previouslysupplied to the Audit Team.
Interviews supplied to the Audit Team, inconjunction with evidence provided, will be thebasis in validating compliance with the PDC.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 128/157
p g
4.2.4 Compliance Audit (Cont…)At the end of the Compliance Audit, the
Audit Team shall conduct exit briefing with
the reporting entity to discuss thepreliminary audit findings and feedbackfrom the reporting entity.
The Audit Team - composed of DMCBoard Members with DMC technicalsupport staff.
Procedures for Reporting
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 129/157
p g
4.2.5 BudgetBudget for the conduct of the monitoring
and Compliance Audit by the ERC,
through DMC, shall be included in theannual budget of the DMC.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 130/157
Final Provisions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 131/157
• 5.1 Administrative Sanctions
Violation of these Rules shall be subjectto the imposition of fines and penalties inaccordance with the “Guidelines toGovern the Imposition of AdministrativeSanctions in the form of Fines and
Penalties Pursuant to Section 46 ofEPIRA”, as amended.
Final Provisions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 132/157
• 5.2 Separability
If for any reason, any provision of theseRules is declared unconstitutional orinvalid by final judgment of a competentcourt, the other parts or provisionshereof which were not affected thereby
shall continue to be in full force andeffect.
Final Provisions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 133/157
• 5.3 Repealing ClauseAny rule or regulation inconsistent with the provisions of theseRules is hereby repealed and modified accordingly.
• 5.4 Effectivity
These Rules shall take effect immediately upon publication in anewspaper of general circulation in the country and upon postingelectronically.
Let copies of these Rules be furnished the University of thePhilippines Law Center-Office of the National AdministrativeRegister (UPLC-ONAR) and all concerned Distribution Utilities.
Pasig City, June 21, 2011.
ERC Res. No. 19, Series 2006
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 134/157
A Resolution Clarifying Issues on theAppointment of a RCO and Prescribing theDuties and Responsibilities (Cont…) I. No specific requirement as long as he could function as an Internal
Coordinator within the regulated entity for purposes of complyingwith ERC issuances;
II. No need of creation of a new position, as what was required ismerely to designate one of its senior officers to function as such;and
III. Replacement of RCO should not be more frequent than once every2 years & such replacement would only bind the ERC after 7 days
from its receipt of the notice of replacement.
ERC Res. No. 19, Series 2006
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 135/157
A Resolution Clarifying Issues on theAppointment of a RCO and Prescribing theDuties and Responsibilities (Cont…)
The duties and responsibilities of the RCO are;1. Monitoring of ERC issuances;
2. Assuring the timely compliance of the regulated entityto pertinent ERC issuances;
3. Participation in the Mandatory Regulatory EducationProgram (MREP) courses;
ERC Res. No. 19, Series 2006
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 136/157
A Resolution Clarifying Issues on theAppointment of a RCO and Prescribing theDuties and Responsibilities (Cont…)
The duties and responsibilities of the RCO are;4. Attending RCO meetings/ seminars/ conferences
scheduled by the ERC;
5. Recipient of all general guidelines/issuances of the
ERC, wherein the receipt of RCO is receipt of theregulated entity rule applies; and
6. Such other duties and responsibilities that the ERCmay, from time to time prescribe.
DISTRIBUTION CODE ENFORCEMENT
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 137/157
2.5 DISTRIBUTION CODE ENFORCEMENT ANDREVISION PROCESS
2.5.1 Enforcement Process2.5.1.1 Any party that has evidence that any other
party has violated or is violating any provision ofthe Distribution Code may file a complaint to theDMC who shall initiate an enforcement process.The DMC may initiate the enforcement processeven if no complaint has been filed but it has
information on possible Distribution Codeviolations. The ERC may also direct the DMC tobegin the enforcement process.
DISTRIBUTION CODE ENFORCEMENT
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 138/157
• 2.5.1 Enforcement Process (Cont…)
2.5.1.2 The steps of the enforcement process are asfollows:
(a) The DMC shall send a written notice to the offending party with thespecifics of the alleged violation and the recommended course of actionneeded to correct the alleged violation;
(b) The offending party shall respond in writing, within 30 days from receipt ofthe notice from the DMC, its reaction to the alleged violation and to statewhether or not it shall comply with the course of action recommended bythe DMC;
(c) If the DMC is satisfied with the response, it shall make a report, including
the recommended course of action, to the ERC who shall render the finaldecision on the matter; and
(d) If the DMC is not satisfied with the response, it shall document thecharges against the offending party and submit a report, including therecommended course of action, fines, and penalties to the ERC.
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 139/157
Fines andPenalties
Outline
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 140/157
ERC Guidelines of 2002ERC Resolution No. 13, Series of 2005
ERC Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 141/157
GUIDELINES TO GOVERN THEIMPOSITION OF ADMINISTRATIVE
SANCTIONS IN THE FORM OFFINES AND PENALTIES
PURSUANT TO
SECTION 46 OF REPUBLIC ACTNO. 9136
Salient Features
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 142/157
ARTICLE I - KEY FUNCTIONS OF THE ERCARTICLE II - SCOPE & DEFINITION OF TERMS
ARTICLE III - ADMINISTRATIVE SANCTIONS
ARTICLE IV – CONTEMPTARTICLE V - COMPROMISE SETTLEMENT
ARTICLE VI - EFFECTIVITY
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 143/157
SECTION 4. NON-SUBMISSION OFDOCUMENTS
A penalty P50,000 plus P100 a day for every
day of violation shall be imposed upon anyperson who fails, without any justifiable reason,to submit documents and other documentsrequired and deemed material and pertinent by
the ERC.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 144/157
SECTION 5. Non-Compliance w/ the Provisions of the Act and its IRR,Grid & Distribution Codes & Rules, Regulations, Orders, Resolutions &Other Laws of the ERC.
A fine of P100,000 plus P100 a day for every day of violation shallbe imposed upon any person who has been found to have
committed a violation of any of the provisions of the Act and itsIRR, the Philippine Grid and Distribution Codes and rules,regulations, orders, resolutions and other laws the implementationand enforcement of which are assigned to the ERC, including butnot limited to the following:
a) Operating as a Generation Company/Facility without a valid Certificateof Compliance (COC) and appropriate clearances.
b) Failure to provide open and non-discriminatory access to theTransmission and Distribution System, as and whenprescribed/required.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 145/157
SECTION 5. Non-Compliance w/ the Provisions of the Act and its IRR,Grid & Distribution Codes & Rules, Regulations, Orders, Resolutions &Other Laws of the ERC. (Cont…)
c) Non-compliance with the prescribed technical specificationsand performance standards.
d) Non-submission of a plan to comply with technicalspecifications prescribed by the Grid or Distribution Codesand/or failure to implement said plan within three (3) years fromthe effectivity of the said Codes.
e) Operating as an Electricity Supplier without a valid license orpermit.
f) Failure to file an application for unbundling of rates.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 146/157
SECTION 5. Non-Compliance w/ the Provisions of the Act and its IRR,Grid & Distribution Codes & Rules, Regulations, Orders, Resolutions &Other Laws of the ERC. (Cont…)
g) Operating as a Transmission or Distribution Utility without avalid Certificate of Public Convenience and Necessity (CPCN).
h) Failure to file duly negotiated Transition Supply Contracts withinthe time prescribed by law.
i) Failure to implement the mandated rate reduction.
j) Failure of the Distribution Utility to adopt and implement a lifelinerate.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 147/157
SECTION 6. ISSUANCE OF NOTICE ANDWARNING
The penalty shall be imposed only after the
offender has been duly informed in writing of saidviolation, has been given an opportunity to presentan explanation and has been duly warned of theconsequences of said violation. The imposition of
any administrative sanction is without prejudice toany criminal action that may be filed, if warranted,under existing laws, rules and regulations.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 148/157
SECTION 7. ANTI-COMPETITIVE ACTS. A penalty not lower than P50,000 but not exceeding
P50,000,000 shall be imposed upon any person who hasbeen found, after due notice and hearing, to have engaged
in any anti-competitive act including but not limited tocross-ownership, cross-subsidization, price or marketmanipulation or other unfair trade practices.
This monetary sanction shall be without prejudice to the
imposition of price controls, issuance of injunctions,requirement of divestment or disgorgement of excessprofits and any criminal action that may be filed, ifwarranted, under existing laws, rules and regulations.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 149/157
SECTION 8. FRAUD OR MISREPRESENTATION• A penalty not lower than P50,000 but not exceeding
P50,000,000 shall be imposed upon any DU w/c has beenfound to have committed fraud or misrepresentation in
connection w/ its failure to comply with its obligation tomitigate potential stranded contract costs as providedunder Section 33 of the Act and Rule 17 of its IRR.
This monetary sanction shall be w/o prejudice to the
requirement of divestment or disgorgement of excessprofits and any criminal action that may be filed, ifwarranted, under existing laws, rules and regulations.
Article III – Administrative Sanctions
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 150/157
SECTION 9. REVOCATION OF FRANCHISE ORPRIVILEGE
• The repeated commission of violations
provided under Sections 5, 7 and 8 hereofshall be a ground for ERC to recommend toCongress the revocation of the franchise orprivilege granted to the offender.
Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 151/157
No. ofViolation
Basic Amount ofPenalty
Additional Penalty to be Imposed for the Delay in theCompliance from Notification
1st violation PhP50,000.00a)More than 1 (one) month but less than three(3) months - 10% of the basic amount of penaltyb)Three (3) months to six (6) months – 50% ofthe basic amount of penalty.c)More than six (6) months - 50% of the basicamount of penalty for every month of delay
2nd and 3rdviolations
PhP100,000.00
4th andsubsequentviolations
PhP200,000.00
“RESOLUTION AMENDING THE GUIDELINES TO GOVERN THE
IMPOSITION OF ADMINISTRATIVE SANCTIONS IN THE FORM OFFINES AND PENALTIES PURSUANT TO SECTION 46 OFREPUBLIC ACT NO. 9136”
• Amends Sections 4 and 5, Article III of the GUIDELINES TO GOVERN THEIMPOSITION OF ADMINISTRATIVE SANCTIONS IN THE FORM OF
FINES AND PENALTIES PURSUANT TO SECTION 46 OF REPUBLICACT NO. 9136 ("Guidelines") approved on May 17, 2002.
Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 152/157
No. of Violation
Basic Amount of
Penalty Additional Penalty1st violation PhP200,000.00
a) 50% of the basic amount of penalty if
there were Financial benefits that may
be derived as a result of the violation
b) 75% of the basic amount of penalty ifthe violation is intended to conceal
illegal acts
c) 100% of the basic amount of penalty if
the violation directly affects the
consumers
2nd violation PhP300,000.00
3rd violation and
subsequent
violations
PhP500,000.00 and
Cancellation of the
Certificate of Public
Convenience and
Necessity (CPCN),
License and the Franchise
for Consortium
• If the reports/documents submitted contain
fraudulent information/data, the same shall betreated as non-compliance with the precedingparagraph and shall be subject to the followingsanctions:
Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 153/157
No. of Violation Amount of Penalty
1st violation PhP100,000.002nd violation PhP200,000.00
3rd and subsequent violations PhP400,000.00
• The official or personnel of the juridical entity
solely responsible for the submission of thefraudulent reports shall be subject to the followingsanctions:
The responsible officer being referred to, are those who have
directly participated in, or have authorized the preparation ofsuch reports/documents.
No compromise agreement shall be allowed in cases where thesame violation was committed more than once.
Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 154/157
SECTION 5. NON COMPLIANCE WITH THEPROVISIONS OF THE ACT AND ITS IRR, GRID ANDDISTRIBUTION CODES, RULES, REGULATIONS,ORDERS, RESOLUTIONS AND OTHER LAWS OF THEERC.
• Any person who has been found to have committed a violation ofany provisions of the Act and its IRR, the Philippine Grid andDistribution Codes (PGDC), rules, regulations, orders, resolutionsand other laws the implementation and enforcement of which aredelegated to the ERC, including but not limited to the following, shall
be subject to the following sanctions:
Resolution No. 03, Series of 2009
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 155/157
No. of violation Basic Amount of Penalty
Additional Penalty Shall be
Imposed for Any Willful Delayin the Implementation
1st and 2nd violation PhP100,000.00 a) 10% of the basic amount
of penalty if the compliance
was made after one (1)
month from notice
b) 50% of the basic amount of
penalty if the compliance
was made after two (2)
months from notice
b) 100% of the basic amounto f penalty if the
compliance was made after
three (3) months from
notice.
3rd and 4th violation PhP300,000.00
5th and subsequent
violationsPhP500,000.00and
Cancellation of the
Certificate of PublicConvenience and
Necessity (CPCN),
License and the
Franchise for
Consortium
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 156/157
Thank You
7/30/2019 Workshop on DUs Compliance with the PDC
http://slidepdf.com/reader/full/workshop-on-dus-compliance-with-the-pdc 157/157
Distribution Management Committee20th Floor Pacific Center Bldg., San Miguel Avenue, Ortigas
Center
www.gmcdmc.phNorth Luzon [email protected]
South Luzon [email protected]
Visayas [email protected]
Mindanao [email protected]