Advantages of Adjustable Speed Drives in Process Control
•Motor Driven Pump Systems account for about 20% of Worldwide Energy Use
•Some Plants have usage approaching 50%
•Adjustable Speed Drives can Improve Process Control and Greatly Reduce Energy Costs
![Page 3: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/3.jpg)
Methods of Variable Flow ControlFans Pumps
Damper Control Throttling Valve Control
Inlet Vane Control
Variable Frequency Drive
Variable Frequency Drive
![Page 4: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/4.jpg)
High Percentage of Plant Connected Horsepower is for Fans and Pumps•Opportunity to save energy when you can
reduce CFM or process flow rate using a variable speed drive rather than using dampers or a control valve
![Page 5: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/5.jpg)
AC MOTOR
BASICS
![Page 6: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/6.jpg)
Purpose of an “AC Motor”
ElectricalEnergy
MechanicalEnergy
The purpose of an AC Motor is to Convert Electrical Energy into Mechanical Energy
![Page 7: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/7.jpg)
AC MOTOR CONSTRUCTION
Stator Winding Assembly
Stator Winding Assembly
RotorAssembly
RotorAssembly
Motor Frame Assembly
Motor Frame Assembly
![Page 8: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/8.jpg)
AC Motor Basics
Rotating Magnetic Field of a 2 Pole AC Induction Motor
Motor RPM is equal to:
120 * Frequency
# Motor Poles
2 Pole Motor2 Pole Motor
Note that Frequency is the only variable to
affect motor speed
Note that Frequency is the only variable to
affect motor speed
![Page 9: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/9.jpg)
Types of Variable Speed ControlBefore AC Variable Speed Drives• Control Valves, Dampers and Vanes
• Fossil Fuel Engines
• Eddy Current Clutches
• Hydraulic Couplings
• Variable Pitch Sheaves
• Motor Generator Sets
![Page 10: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/10.jpg)
AC DriveDC Bus
• Rectifier
- Converts AC line voltage to Pulsating DC voltage
• Inverter
- Changes fixed DC to adjustable AC
- Alters the Frequency of PWM waveform
• Intermediate Circuit (DC BUS)
- Filters the pulsating DC to fixed DC voltage
V
TT
V V V
T
AC Power Supply
Rectifier Inverter
M
![Page 11: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/11.jpg)
Adjustable Speed Drive Availability•110V Single Phase Fractional HP
•Medium Voltage (4160V) Thousands of HP
•Most are 460Volt 1-500 HP
![Page 12: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/12.jpg)
Does my load profile vary sufficiently to justify a AFD?•If the Speed of the Application is constant
DO NOT USE
•If the load is not running at full speed for a large portion of the time then Evaluate the Use
•Sweet Spot is a Variable Torque Load
![Page 13: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/13.jpg)
Variable Torque Loads(Fans & Pumps)
![Page 14: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/14.jpg)
Variable Torque Loads
•In these applications:
• Torque varies directly with speed squared
• Power varies directly with speed cubed•This means that at half speed, the
horsepower required is approximately one eighth of rated maximum
![Page 15: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/15.jpg)
Variable Speed Horsepower Requirements
Flow proportional to speed Q1/Q2= n1/n2
Then: HP2/HP1= (n2/n1)3
Therefore: HP2=HP1(n2/n1)3
At 80% Speed, HP=(.80)3 = .512
![Page 16: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/16.jpg)
Advantages of a Adjustable Speed Drive
•1. Energy savings on fan and pump applications
•2. Better process control and regulation•3. Speeding up or slowing down a
machine or process•4. Inherent power-factor correction•5. Elimination of Other Mechanical
Control Devices
•
![Page 17: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/17.jpg)
Some Considerations WhenApplying ASD to AC Motors
Thermal considerations of motor operation with a VFDshould be one of the first areas of attention for successfulapplication.• The ability of a motor to cool itself effectively is
reduced as the motor is slowed down. Over-sizing the motor or providing external forced air ventilation may be required with extended operation at low speeds and high loads.
• Operation at different speeds can cause mechanical resonances in driven equipment. These speeds should be identified and programmed out of the motor’s operating range.
![Page 18: WISA Meeting Help](https://reader035.vdocuments.us/reader035/viewer/2022062408/56813aba550346895da2c1d9/html5/thumbnails/18.jpg)
ASD Considerations •ASD’s generate harmonic voltages and
currents which can, in some cases, cause undesirable effects on the electrical distribution system and affect equipment operation.
•Longer Cable Lengths can cause a voltage reflection of up to two times the applied voltage due to standing waves or a ‘‘ringing effect’’, and becomes more problematic with longer cable runs (typically greater than 15 m or 50 feet).