Wireless Measurement System for Building Monitoring and Commissioning

Tom Webster, P.E.George AnwarJames BonnellCliff Federspiel

(and many others)Center for the Built Environment

UC Berkeley

Page 2: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Introduction

� Purpose and significance of this work

� Large cuts in building energy use are needed to support global warming goals - time is of the essence (e.g., CA AB32)

� Major new funding is becoming available for this effort

� New regulations (standards, labeling, certification, etc. ) willrequire unprecedented levels of performance checking and verification

� Comfort needs to be maintained with energy reductions

� Many new system types with asymmetrical environments will be used

� We need better, faster, more efficient means to measure and analyze building performance

Page 3: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Commissioning at the New York Times

� Purpose

� To develop a multi-function mobile cart and associated tools to support underfloor air distribution (UFAD) commissioning

� Provide data to support UFAD commissioning research

Page 4: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

UFAD System overview

Variable plenum

pressureSwirl diffusers Variable-speed fan coil

serving linear bar grilles

Page 5: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

UFAD commissioning toolkit

� Artificial loads

� Thermal plume generators to simulate

occupied conditions for internal load

� Cart

� Mobile sensor platform supporting

wireless temperature sensor network

� Laptop computer for logging, analysis,

and human interface

� Procedures

� Functional testing procedures for UFAD

systems

� Cart operating instructions

Page 6: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

UFAD commissioning cart

Page 7: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

New York Times cart system architecture

WiFi

NYT Cart system diagram

Page 8: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Commissioning at NYT

Mote

Page 9: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Pre-occupancy workflow

� Pre-test

� Prepare mote maps & test setup

� Deploy motes

� Deploy artificial loads

� Steady state tests

� “Live walk thru”

� Commissioning tests

� Multiple single zone tests for entire floor, 6-10 locations per zone

� Save data after each zone test

� Analysis

� Review results offline, comparetests

� Retest modifications plan

200 artificial

loads70 motes

Page 10: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Detailed view

Page 11: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Analysis screens

� Metrics calculations

Page 12: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Analysis screens

� Acceptance checking

Page 13: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Some things we learned

� Cx process

� Few “knobs” to turn:

� Supply temperature is not a tuning parameter for individual zones

� Artificial loads work well, but not practical

� UFAD

� Plenum and zones “decoupled” - Plenum temperatures vary widely by location, yet zone profiles consistent

� Return and ceiling temperatures cool

� Leakage prevention requires constant surveillance

� Cart and software

� Not practical to analyze while testing

� Better filtering for analysis needed

� Smaller, more reliable base station needed

Page 14: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

New Project Objectives:Advanced wireless monitoring system

� Design and demonstrate next generation, all wireless, monitoringand measurement system that can be portable, highly flexible, and easily deployed for all types of new and existing buildings

� Develop functional specifications for prototype system

� Hardware - Motes & sensors

� Software – Data acquisition, display, analysis

� Build two prototype systems

Page 15: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

NEW: Proposed System Architecture

Cell Net

Cell Net

Page 16: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Potential uses

� Commissioning (Cx)

� Retro/Re/continuous commissioning

� Functional testing

� Controls and operations analysissupport

� Post occupancy evaluation (POE)

� Energy performance

� Comfort performance

� “Real-time” comfort modeling

� Desktop monitoring

� Measurement and verification

� Research and case studies

Lighting

39%

Cooling

15%

Ventilation

10%

Refrigeration

8%

Office Equipment

1%

Miscellaneous

23%

Heat/Cook/ DHW

4%

Total ~ 80,000 GWh

Page 17: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Possible applications

� New and existing traditional buildings/systems

� Advanced high performance buildings/systems

� Radiant cooling and heating

� UFAD/DV/chilled beams – stratifiedenvironments

� Mixed Mode/Natural Ventilation

� Personal Environmental Control (PEC)

� Data Centers

� At least 10% energy savings possible (IBM)

� Cool Communities

� Outside sensors

� Camera actuation, image capture

Page 18: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Distinguishing features

� Un-tethered measurement system with known

calibration and flexible deployment

� Easy deployment

� Pre-configured mote setup

� Mote location mapping

� Large sub-system point capacity

� Multiple sub-systems per project

� BMS interface – seamless integration with mote data

� Remote server

� Data archiving – automatic transfers

� Application specific analysis support

Page 19: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Prototype system components

� Motes

� Mesh technology - Dust Networks @ 2.4 GHz

(low power, international standards)

� 250 motes possible per gateway (or manager), multiple managers

possible for a single test series

� Multi-sensor motes – 8 sensors per mote (direct connect)

� Maxim “1-wire” temperature sensors

� Accuracy : +- 0.1C in 10-40C range (9-12 bit resolution)

� Configurable sampling rates (burst rate option or image transfers)

� Automatic I/O configuration

� Location identification

� Near term - Tablet PC geo taggingand mote naming conventions

� Far term – Indoor GPS solutions

Page 20: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Sensors

� Voltage input

� Temperature

� Air temperature

� Water temperature

� Surface temperature

� Globe temperature

� Air velocity

� Relative humidity

� Pressure

� Light/solar

� Power

Page 21: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Prototype system components

� Base station

� Small profile PC (FIT PC 2) running DB software

� 1.1, 1.6 Ghz clock

� 1GB memory, 2.5” SATA HDD

� 6W

� $250-350

� Interface to Dust mesh network

� Interface to cell network for access –building independent cell data modems

� Linux OS, Firebird DB

� BACnet interface

� Two way access between systems

� Command BMS points

Page 22: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Prototype system components

� Application server

� Data archive and applications server

� 5 sub-systems each running 5 tests

� Accessible by 5 users concurrently

� LabView based interface that supports multiple APIs

� User annotation during and post test

� Standard real time displays

� User created data analysis algorithms and metrics calculations

� Comparisons to previous data/information,standards, acceptance criteria

Internet

`

Application Server (AS)

Hosted Archive DB

w/ LabView server

Remote Analysis

Monitoring and

Analysis computers

Broadband Router

Wireless Measurement

System (WMS)

Base StationWireless network

manager

Mote mesh network

UPS

Remote Cx

On-site cart or site laptop

Page 23: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Applications examples

MIXED AIR TEMPERATURE ANALYSIS

(SCHEDULED-ON HOURS ONLY)

40

45

50

55

60

65

70

75

40 45 50 55 60 65 70 75 80

Outside Air Temperature (F)

Mix

ed

Air

Te

mp

era

ture

(F

)

MAT Ideal Economizer Operation

Economizer analysis

SYSTEM AIR TEMPERATURES

(ALL MONITORED HOURS)

40

45

50

55

60

65

70

75

80

4/6/93

12:00

4/7/93

0:00

4/7/93

12:00

4/8/93

0:00

4/8/93

12:00

4/9/93

0:00

4/9/93

12:00

4/10/93

0:00

4/10/93

12:00

4/11/93

0:00

4/11/93

12:00

4/12/93

0:00

4/12/93

12:00

4/13/93

0:00

4/13/93

12:00

4/14/93

0:00

4/14/93

12:00

4/15/93

0:00

4/15/93

12:00

Date and Time

Te

mp

era

ture

(F

)

OAT MAT RAT SAT Schedule

Custom trend logs

Power = 1.013* Flow2 + 0.009

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

No

rma

lize

d F

an

Po

we

r

Normalized Air Flow

Building 225 AHU#3

Fan power analysis

Page 24: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Applications examples

0

10

20

30

40

50

-6 -5 -4 -3 -2 -1 0 1 2 3 4

Pe

rce

nt

of

Re

ad

ing

s

Sept. 2007: Temperature Difference from 74 °F

Perimeter

Perimeter/Interior

Interior

Perimeter H/C Deadband

Room temperature analysis

UFAD stratification performance

Page 25: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Summary

� Wireless is here and coming on strong!

� Wireless system benefits:

� independence from but potential integration with/augmentation ofexisting BMS

� independence from existing LAN

� reduced labor (for data gathering and analysis)

� operations-centric instead of design-centric (many sites could be commissioned all the time from anywhere)

� For the large transformations coming, better tools are

needed…wireless can help

� Business models may be changing; now is the time to

plan on how best to use it to your best advantage

Page 26: Wireless Measurement System for Building Monitoring and ... · UFAD commissioning toolkit Artificial loads Thermal plume generators to simulate occupied conditions for internal load

Questions, comments, contributions

Tom Webster

[email protected]

Private officePerimeter open plan Interior open plan