welcome to fire eater introduction to fire eater control inert inergen system
TRANSCRIPT
Welcome to Fire Eater
Introduction to Fire Eater Control Inert INERGEN system
Control Inert
The Control Inert (Ci) INERGEN system consists of the components necessary to make a complete stand alone INERGEN system.The components in the Control Inert system are approved in accordance with the current valid European Directives.Among others:
89/106/EEC Construction Products97/23/EEC Pressure Equipment99/36/EC Transportable Pressure Equipment73/23/EEC Low voltage89/336/EEC Electromagnetic compatibility
Control Inert
The main components of the system isCylinders: 2 – 80 liter, 200 & 300 barHand Wheel Valve: W24.32 – M25x1.5 200-400 barDischarge valve: Ci IV8Manoswitch: Ci ManoswActivation system: Ci IS8, Ci IM8, Ci PA8 (Ci IW8)Hoses: DN10 500 – 4000mmManifold system: Ci MTx (1-10), OrificePipe system: Galvanized 75 barNozzles: Mono-orifice
Cylinders
Pressure: Filling @ 15C 200 & 300Work max 400 bar
Colors: Ral 3000 RedRal 6018 Light Green (EN 1089
Construction: EN1964-2Approval: TPED, marked
Hand Wheel Valve
INERGENEN 849100Kg 25EM25x1.5
Fire-Eater 1116
mm-yy DK630B####Test xxxBurst yyy Bar
MüLLER 0034
Double approval TPED, marked & CE
mark
More information
Discharge Valve
Ci IV8 EN12094-4 (CPD) Approved
PAIn/out
DischargeBackpressure
Out/In
Mech. Act.
SupplypressureMore information
Manoswicth
Ci Manoswitch EN12094-10 (CPD) Approved
Features dual End Of Line resistor (fully monitored circuit)
EN120940
xxx
xxx
xxx
xxx
bar
Kl. 1.6
INERGEN
IG541
4Brown
Black
1 3Blue
413
BrownBlack
BlueNo Pressure
More information
Activationsystem
Ci IS8 Electrician actuatorCi IM8Manual actuatorCi PA8 Pneumatic actuator
More information
More informationMore information
Hoses
Hoses now have ø7.8 Flow diameter
More information
Manifolds
FeaturesIntegrated Check Valves which opens by hose
connectionSingle Orifice up to ø22mm
Pipe system
PED compatibleup to DN 32 No CE marking requiredDN 32- 100 CE by installation companyDN 100 up CE by Notified Body
Ci-MT Next kit
For systems with more manifolds
01
11
12
03
02
21 31 41 42 51 61 2322
Nozzles
Mono-Orifice Nozzle 2 Designing criteria:
Single room applicationMultiple room applications
BrassBSPT or NPT tread
More information
Tools
1. Power MeterTo verify that there are sufficient energy for
activation2. Ci IV8 Reset tools
To reset IV83. Ci Actuator Reset
To reset actuators for Control Inert
More information