WB7-3 Observations Regarding Window Testing and Failures Roger G. Morse Morse Zehnter Associates Rensselaer Technology Park 165 Jordan Road Troy, NY 12180 [email protected]

Upload: others

Post on 23-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

WB7-3 Observations Regarding

Window Testing and Failures

Roger G. MorseMorse Zehnter Associates

Rensselaer Technology Park

165 Jordan Road

Troy, NY 12180

[email protected]

Page 2: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Window Testing

• Architect identifies a sampling of windows to be tested. – Representative sampling of each window type on the job

• Windows Leak Tested– Independent testing agency

– ASTM E1105 or AAMA 502

• Windows Leak

• Window sub-contractor tunes up windows

• Windows retested and pass

• Windows and their installation are accepted once the sample windows meet requirements of the test.

Page 3: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Leak Test

• ASTM E1105 or AAMA 502

• Pressure differential across window

– Interior negative or

– Exterior positive

• Spray water to form a continuous film of

water on surface

– Does not attempt to mimic kinetic energy of

wind blown rain

Page 4: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

From ASTM

E1105

Page 5: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Installer Tune-up

• Sealants at butt (mitered) joints in gaskets in corners,

• Cam locks, shimmed or adjusted to apply more pressure to gaskets

– “dollar bill” test

• Sealant at fixed joints between aluminum extrusions

– Corners of frames and sashes

– Fasteners

Page 6: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

End Result

• All windows are adjusted during “Tune Up”

• Testing of exemplar windows is a proper

test of the window system

• Windows don’t leak when tester and

contractor leave site

Page 7: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Problems with Testing

• May not include doors

• Testing normally performed after interior

finishes in place

– Hides wall leaks

– May hide leaks within frame perimeter

Page 8: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Problems with End Result

• Great that windows are tested – how

about the rest of the wall

• Windows may not leak at time of test but

how about several years later

• Windstorms

Page 9: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Then Time Happens

• Sealants harden, shrink and crack

• Gaskets shrink and harden

– End joints open up

– Gaskets relax so air and water pass through gasketed joints at an increasing rate over time

• Buildings settle differentially twisting assemblies

• Users damage windows

• Fixed joints aren’t really fixed

Page 10: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 11: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 12: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 13: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 14: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 15: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Then Wind Happens

• Wind pressures during wind driven rain

exceed those in leak test

• Pressures during a hurricane event

drastically exceed test pressures

• Window must have some sort of pressure

relieve feature to prevent water passage

– Pressure balanced seals

– Drainage subsills

Page 16: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Wind Creates Pressure Differentials

Page 17: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Wind Speed Increases with Height

Page 18: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Stack Effect – Warm Climate

Page 19: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Stack Effect – Cold Climate

Page 20: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Combined Effect –

HVAC, Stack and Wind

Page 21: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 22: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Pressure Differentials

Pressure Differential

PSF Inches Water

Test Pressure 9 1.73

Wind Pressure - High 86 17

Wind Pressure - Low 56 11

Page 23: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 24: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Paradigm Shift

• Good Old Days – Stupid & Simple

– Huge water storage, inorganic materials, simple materials and assemblies

• Now – Smart & Sophisticated

– High tech materials

– Complex assemblies

– High performing

– Sustainable

– Water sensitive

Page 25: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Good Old Day

Page 26: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Now

Page 27: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Current State of the Construction

Industry

• Sophisticated High tech materials and systems

• Rapid product development

• Increasing specialization

– Manufacturers

– Contractors

• Increase in magnitude of natural forces affecting

materials and assemblies

– Insulation

– Membranes

Page 28: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Case Study - Florida

• Windows in Florida

• Hurricanes

• General Guidance

– ASTM E2112 – Standard Practice for Installation of Exterior Windows Doors and Skylights

• Specific Regional Guidance

– Fenestration Manufacturers Association Standards

Page 29: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor
Page 30: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

CSI Sections

• Division 03

– Concrete,

• Division 04

– Brick

– Stone

– Concrete Block

• Division 06

– Wood framing

• Division 07

– Flashing

– Sealants

• Division 08

– Windows

• Division 09

– Painting

Page 31: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Manufacturers

• Window

• Flashing

• Sealants

• Brick

• Precast sill

• Concrete block

• Mortar

• Wood blocking

• Fasteners

• Metal furring

• Gypsum drywall

• Paint

Page 32: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Contractors

• Window

• Masonry

• Carpentry

• Drywall

• Painting

• Caulking

Page 33: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

FMA Installation CommitteeFMA/AAMA 100 Flanged Wood Frame

FMA/AAMA 200 Frontal Flanged Surface Barrier

CMU

FMA/AAMA 250 Non-Frontal

Flange (wood)

Surface Barrier

CMU

FMA/AAMA 300 Sliding Glass

Door

Wood Frame

FMA/AAMA 400 Sliding Glass

Door

Surface Barrier

CMU

Page 34: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Fenestration Manufacturer’s

Association

• Drainable sill pan

• Recommended section for a precast sill

that provides drainage

• Use of liquid applied sealants to form

perimeter flashing continuous with sill pan

Page 35: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Strength of Approach

• Establishes draining subsill as a standard

part of window assembly

• Attempts to consolidate critical tasks with

one entity

• Written set of instructions

Page 36: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Starting to Appear in Guide

Specifications

• Palm Beach County Schools

– In window section

• Broward County Schools

– Not yet

• Regional – not in national guide specs

Page 37: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Contractors Involved in Window

Installation

• Mason sub-contractor

– Install precast sill

– prepare the masonry

opening

• Waterproofing sub-

contractor

– Install the sill pan and

perimeter coatings

• Carpentry sub-contractor

– install wood bucks

• Window sub-contractor

– install the window

• Stucco sub-contractor

– stucco over the sill and on

jambs and head

• Painter

– sealant between stucco

and window

– paint

• Drywall sub-contractor

– interior finishes

Page 38: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Specification Sections Involved

• Masonry

• Waterproofing

• Window

• Stucco

• Painting

Page 39: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Next Step

• New window specification section

– consolidates all of the work required by the

standard in a single specification section.

• Include in major guide specifications

providers

– NIBS Construction Criteria Base

– Arcom (AIA) MasterSpec®,

– CSI Spectext®.

Page 40: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Proposed ASTM E 1105 Changes

• Add Low Pressure Water Test (LPWT)

• Intended to jibe better with end user

expectations of the test

Page 41: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

Proposed ASTM E 1105 Changes

• Low Pressure Water Test (LPWT)

– less than 75 pascals (1.57 lbf/ft2)

– No visible water through window

• High Pressure Water Test (HPWT)

– Current definition

– Water may be visible inside window (except

collector sills) - but not past it

• Water penetration through perimeter frame

Page 42: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor

WB7-3 Observations Regarding

Window Testing and Failures

Roger G. MorseMorse Zehnter Associates

Rensselaer Technology Park

165 Jordan Road

Troy, NY 12180

[email protected]