Project Documentation Document SPEC-0180
Revision A
Wavefront Correction Context Viewer
Critical Design Definition
Luke Johnson, Keith Cummings, Mark Drobilek, Scott Gregory, Erik Johansson, Kit Richards, Friedrich
Wöger
WFC Group
December 2017
CV CDD
SPEC-0180, Rev A Page i
REVISION SUMMARY:
1. Date: August 2013 Revision: Draft Changes: Initial document
2. Date: December 2017 Revision: A Changes: Initial formal release prior to CDR.
CV CDD
SPEC-0180, Rev A Page ii
Table of Contents
1 OVERVIEW ........................................................................................................... 1
1.1 SCOPE OF THE DOCUMENT ...................................................................................... 1
1.2 DELIVERABLES ....................................................................................................... 1
1.3 RELATED DOCUMENTS ............................................................................................ 1
1.4 RELATED DKIST PROJECT DOCUMENTS .................................................................. 2
1.5 INTERFACE CONTROL DOCUMENTS AND DRAWINGS .................................................. 2
1.6 SPECIFIC DEFINITIONS AND TERMINOLOGY ............................................................... 2
1.7 COMPLIANCE MATRIX .............................................................................................. 3
2 INTRODUCTION TO THE CV DESIGN ................................................................ 4
3 CV ALGORITHMS ................................................................................................ 5
3.1 CV CENTROIDING ................................................................................................... 5
3.2 CV LIMB FINDING ................................................................................................... 9
3.3 CV STREHL CALCULATION .................................................................................... 11
3.4 CV PLATE SCALE CALCULATION ........................................................................... 12
3.5 CV FOCUS CALIBRATION ...................................................................................... 14
4 CV OPTICAL DESIGN ........................................................................................ 16
4.1 CV OPTICAL DESIGN REQUIREMENTS .................................................................... 16
4.2 CV OPTICAL PERFORMANCE ................................................................................. 17
4.3 OPTICAL TOLERANCE ANALYSIS ............................................................................ 20
4.3.1 ZEMAX Tolerance Model .............................................................................................20
4.3.2 Monte Carlo Results ....................................................................................................22
4.4 OPTICAL ALIGNMENT ............................................................................................ 22
5 CV HARDWARE DESIGN .................................................................................. 23
5.1 OVERVIEW OF COUDÉ WFS LAYOUT ...................................................................... 23
5.2 OVERVIEW OF WFS OPTO-MECHANICAL LAYOUT ................................................... 25
5.3 CV OPTO-MECHANICAL DESIGN ............................................................................ 27
5.3.1 30-Arcsecond Objective Lens Assembly ...................................................................29
5.3.2 30-Arcsecond Objective Lens Analysis .....................................................................31
5.3.3 60-Arcsecond Objective Lens Assembly ...................................................................36
5.3.4 60-Arcsecond Objective Lens Analysis .....................................................................38
5.3.5 CV Filter Assembly ......................................................................................................42
5.3.6 CV Camera Assembly .................................................................................................44
5.4 CV CAMERA ......................................................................................................... 45
6 THERMAL SYSTEMS ......................................................................................... 47
6.1 CV CAMERA THERMAL CONTROL .......................................................................... 47
7 CV CONTROL SOFTWARE DESIGN................................................................. 49
7.1 OVERVIEW ............................................................................................................ 49
CV CDD
SPEC-0180, Rev A Page iii
7.2 USE CASES .......................................................................................................... 51
7.2.1 Startup ..........................................................................................................................53
7.2.2 Observing Related Modes ...........................................................................................53
7.2.3 Calibrations..................................................................................................................54
7.2.4 Shutdown .....................................................................................................................58
7.3 DETAILED DESIGN................................................................................................. 58
7.3.1 CV Controller ...............................................................................................................58
7.3.2 Camera Controller .......................................................................................................60
7.3.3 Mechanism Controller .................................................................................................66
7.3.4 Motion Controllers .......................................................................................................68
7.3.5 Calibration Sequencer ................................................................................................70
7.3.6 Events Published by the CV and its components .....................................................74
7.3.7 Events subscribed to by the CV and its components ...............................................78
7.3.8 Headers ........................................................................................................................78
7.3.9 Interlocks .....................................................................................................................78
7.3.10 Logging ........................................................................................................................78
7.3.11 Health and Alarms .......................................................................................................79
7.3.12 GUI Screens .................................................................................................................80
7.3.13 Use Case Details .........................................................................................................84
7.4 HARDWARE REQUIREMENTS .................................................................................. 89
CV CDD
SPEC-0180, Rev A Page 1 of 90
1 OVERVIEW
1.1 SCOPE OF THE DOCUMENT
The Context Viewer (CV) Critical Design Definition (CDD) describes the design of the DKIST CV as
conceived and developed by the Wavefront Correction (WFC) team. The design is based on requirements
in the CV Design Requirements Document (DRD) which flow from SPEC-0058, Wavefront Correction
Specifications. SPEC-0058 captures the necessary wavefront correction performance requirements that
will enable DKIST to meet top-level science requirements set forth in SPEC-0001, DKIST Science
Requirements.
1.2 DELIVERABLES
The deliverables for the CV final design are primarily contained in two documents: SPEC-0179, the
DRD, and SPEC-0180, the CDD. In addition, the Interface Control Documents (ICD) describe interfaces
between the CV and other telescope systems.
The DRD contains all CV design requirements. Requirements are captured and summarized in the CV
compliance matrix, CMX-0019.
The CDD, this document, contains detailed descriptions of the CV design, including the following
deliverables,
CV optical design
o Optical tolerance analysis
o Optical alignment plan
o ZEMAX optical design and analysis
CV hardware design
o Motion stages
o Optical mounts
o CV camera
Software design
o Use cases
o Interfaces
o Algorithms
o Detailed design
1.3 RELATED DOCUMENTS
[1] Roberts, L. C., Perrin, M. D., Marchis, F., Sivaramakrishnan, A., Makidon, R. B., Christou, J. C.,
Macintosh, B. A., Poyneer, L. A., van Dam, M. A., and Troy, M., “Is that really your Strehl ratio?”,
Proc SPIE 5490, p. 504-515 (2004)
[2] Cox, “Allen’s Astrophysical Quantities”, 2000
[3] Canny, J., “A Computational Approach To Edge Detection”, IEEE Trans. Pattern Analysis and
Machine Intelligence, 8(6):679–698, 1986.
[4] Duda, R. O. and P. E. Hart, "Use of the Hough Transformation to Detect Lines and Curves in
Pictures," Comm. ACM, Vol. 15, pp. 11–15
[5] http://scikit-image.org/docs/dev/api/api.html
[6] Otsu, N., "A threshold selection method from gray-level histograms", IEEE Trans. Sys., Man., Cyber.
9: 62-66, 1979.
CV CDD
SPEC-0180, Rev A Page 2 of 90
[7] Mir, Hashim, Peter Xu, and Peter Van Beek. "An extensive empirical evaluation of focus measures
for digital photography." IS&T/SPIE Electronic Imaging. International Society for Optics and
Photonics, 2014.
1.4 RELATED DKIST PROJECT DOCUMENTS
SPEC-0001, Science Requirements Document
SPEC-0005, Software and Controls Requirement
SPEC-0012, DKIST Acronym List and Glossary
SPEC-0013, Software Concepts Definitions
SPEC-0014, Software Design
SPEC-0022, Common Services Framework Reference Design
SPEC-0036, Operational Concepts Definitions
SPEC-0037, Risk Management Plan
SPEC-0045, Contingency Management Plan
SPEC-0058, Wavefront Corrections Systems Specifications Document
SPEC-0063, Interconnects and Services
SPEC-0061, Hazard Analysis Plan
SPEC-0068, M5 Tip Tilt Module Specification
SPEC-0070, DKIST Standard Environmental Conditions
SPEC-0109, M5 Tip Tilt Mirror Specification
SPEC-0111, M10 Deformable Mirror Specification
SPEC-0125, High Order Adaptive Optics Real Time FPGA Firmware Specification
SPEC-0129, Wavefront Correction Operational Concepts Model
SPEC-0179, WFC CV DRD
SPEC-0202, Wavefront Correction System Telemetry Specification
TN-0185, WFC CV Camera Trade Study
TN-0188, WFC Context Viewer Software Issues
TN-0193, WFC Context Viewer Camera Test Report
TN-0289, WFC System Power Sequencing
PROC-0261, WFC Alignment Plan
1.5 INTERFACE CONTROL DOCUMENTS AND DRAWINGS
ICD 2.3 – 4.4 WCCS to TCS
1.6 SPECIFIC DEFINITIONS AND TERMINOLOGY
Acronym Meaning
CDD
CSF
CV
DKIST
Critical Design Document
Common Services Framework
Context Viewer
Daniel K. Inouye Solar Telescope
DRD Design Requirements Document
CV CDD
SPEC-0180, Rev A Page 3 of 90
FOV
GOS
HOAO
HOWFS
ICD
LOWFS
Field-of-view
Gregorian Optical Station (at Gregorian focus of telescope)
High-Order Adaptive Optics
High-Order Wavefront Sensor
Interface Control Document
Low Order Wavefront Sensor
OCD
QE
Operational Concepts Definition
Quantum Efficiency
SRD
WCCS
WFC
Science Requirements Document
Wavefront Correction Control System
Wavefront Correction System
1.7 COMPLIANCE MATRIX
The requirements in this document all trace back to the CV DRD, SPEC-0179, through the CV
compliance matrix, CMX-0019, which exists as a separate document.
The CV compliance matrix traces top-down requirements to the original source documents. Direct
requirements are only found in the CV compliance matrix (not in the body of the DRD) and serve as a
mechanism to flow requirements through the DRD into the CDD. Other top-down requirements appear in
the body of the DRD and reference the higher requirements that generate them. Each top-down
requirement in the CV compliance matrix references the CDD implementation which satisfies the
requirement.
The DRD also develops bottom-up requirements, found in the various body sections of the DRD. The
compliance matrix traces all design requirements developed in the DRD to the body of the CDD. Bottom-
up requirements contain references to the CDD section which justify them, the DRD section that they
flow to, and any necessary higher-level requirements. In this way all requirement flows, both top-down
and bottom-up, are traceable through the CV compliance matrix.
CV CDD
SPEC-0180, Rev A Page 4 of 90
2 INTRODUCTION TO THE CV DESIGN
The CV is a first-light subsystem of the DKIST WFC. The CV delivers visible-light images of the center
of the DKIST field of view to a display screen where they can be viewed. The CV also defines the
telescope boresight position, so it is essential to DKIST operation, especially with regards to
determination of the telescope coordinate system. The CV will also assist in WFC calibration activities,
telescope pointing corrections, and image quality evaluation.
The CV is designed to image the central 30 arcseconds of the DKIST field of view, sampled at the
diffraction limit. An alternative objective lens can be inserted to increase the field of view to 60
arcseconds, however, this decreases the pixel sampling by a factor of two so diffraction-limited sampling
is not possible with a 60 arcsecond field of view. Images from the CV camera are sent to the operator
display screen at a rate of 10 frames per second or greater, allowing the operator to visually determine the
pointing and performance of DKIST in close to real-time.
The CV also serves as the telescope pointing reference. The center of the CV field of view is defined to
be the center of the telescope field of view, providing a reference point for boresight alignment and
telescope pointing maps. Due to its position in the DKIST coudé room, the CV will experience little
gravitational flexure or thermal expansion, making it a stable reference from which to measure telescope
flexure.
The CV will also be used for image quality evaluation during engineering time to ensure that the WFC
system is well calibrated and operating within requirements. This ability to determine image quality will
also be used for validation during assembly, testing, and integration of the WFC system. When observing
point sources, the CV is sampled at just above the Rayleigh criterion. This means that we expect its Strehl
estimation to contain 5-10% error relative to the true Strehl[1].
The CV design follows all manufacturing, design, fabrication, drawing, documentation, electrical,
structural, environmental, and materials requirements as defined in DKIST project documents. These
requirements are enumerated in the CV compliance matrix and will be verified by internal design review,
inspection, and test where necessary.
In addition to the design presented in this document, manuals for proper maintenance will be presented
along with the final product. Manuals will follow all project documentation requirements and clearly
explain all information related to normal operations and procedures, emergency operations and
procedures, normal maintenance and procedures, emergency maintenance and procedures, spare parts,
warranties, wiring diagrams, inspection procedures, performance curves, shop drawings, product data,
and similar applicable information.
CV CDD
SPEC-0180, Rev A Page 5 of 90
3 CV ALGORITHMS
This section discusses selected algorithms that will be used as part of CV calibration and operation.
Wherever it is useful for clarification, a step by step procedure will be outlined. Additionally,
mathematical expressions will be used to define quantities that must be calculated as part of each
procedure. Where possible, matrix algebra representations will be used for the sake of clarity.
Please note that the procedures and mathematics that appear in this section are meant more as a
conceptual explanation of the algorithms and are optimized for readability, not for computational
efficiency. Actual implementation in software will only rely on matrix operations where necessary and
will precompute any fixed quantities.
3.1 CV CENTROIDING
The CV will be able to locate the brightest point source in the CV image and find the location of its
optical center relative to the center pixel of the CV camera. CV centroiding will be most commonly used
at night as a way to locate bright stars as part of refining the telescope pointing map. However, other
WFC activities, such as boresight alignment and HOWFS/LOWFS plate scale calibration will also make
use of the same centroiding algorithm.
When using the CV centroiding algorithm, the CV assumes the object of interest is the brightest point
source in the image. To locate the brightest point source, the CV uses a matched filter approach by
convolving the CV image with the expected point source image, which will be retrieved from a database
that is accessible on the DKIST internal network.
For different applications, different point source images will be used. For example, night pointing
calibrations will use a Gaussian or Lorentzian point source references of varying width, boresight
alignment will use a simulated image of the GOS inverted pinhole, and HOWFS and LOWFS platescale
images will use a simulated image of the GOS pinhole. As such, the CV centroiding calculation will
require a reference point source image to be provided as input. The size of the reference image may
change between applications so the CV centroiding algorithm must be able to take reference images of
varying size. The maximum size of the reference image will be 256 x 256 pixels.
The first step in the source location algorithm is hot pixel removal. Hot pixels are detected by applying a
hot pixel filter to the CV image,
𝐼𝑎𝑑𝑗 = 𝐼𝑝𝑟𝑜𝑐 ∗1
8[1 1 11 0 11 1 1
]
𝐼ℎ𝑜𝑡 = 𝐼𝑝𝑟𝑜𝑐 − 𝐼𝑎𝑑𝑗
where 𝐼𝑝𝑟𝑜𝑐 is the dark and gain-corrected CV image, 𝐼ℎ𝑜𝑡 is the filtered CV image, 𝐼𝑎𝑑𝑗 is an image
where the pixel values of 𝐼𝑝𝑟𝑜𝑐 have been replaced with the average of their adjacent pixels, and ∗ is the
convolution operator.
All pixels in 𝐼𝑝𝑟𝑜𝑐 which correspond to pixels in 𝐼ℎ𝑜𝑡 that are above the hot pixel threshold (default value:
750) are replaced by their corresponding values in 𝐼𝑎𝑑𝑗.
𝐼𝑝𝑟𝑜𝑐,ℎ𝑜𝑡 = {𝐼𝑝𝑟𝑜𝑐, 𝐼ℎ𝑜𝑡 < 750
𝐼𝑎𝑑𝑗, 𝐼ℎ𝑜𝑡 ≥ 750
where 𝐼𝑝𝑟𝑜𝑐,ℎ𝑜𝑡 is the CV image with all hot pixels removed.
The next step in source location is matched filtering,
𝐼𝑓 = 𝐼𝑝𝑟𝑜𝑐,ℎ𝑜𝑡 ∗ ℎ𝑝𝑠𝑓
CV CDD
SPEC-0180, Rev A Page 6 of 90
where 𝐼𝑓 is the source identification image, ℎ𝑝𝑠𝑓 is the reference psf image, and * is the convolution
operator. The location of the maximum pixel in 𝐼𝑓 is the location of the brightest point source in the CV
image.
The final step is to apply quadratic interpolation to 𝐼𝑓 to locate the center of the point source to subpixel
accuracy.
𝑥𝑓𝑖𝑛𝑎𝑙 = 𝑥𝑚 +2𝑎2𝑎5 − 𝑎4𝑎6
𝑎62 − 4𝑎3𝑎5
𝑦𝑓𝑖𝑛𝑎𝑙 = 𝑦𝑚 +2𝑎3𝑎4 − 𝑎2𝑎6
𝑎62 − 4𝑎3𝑎5
where [𝑥𝑚, 𝑦𝑚] is the location of maximum pixel in 𝐼𝑓 and,
𝑎2 =1
2(𝐼𝑓[𝑥𝑚 + 1, 𝑦𝑚] − 𝐼𝑓[𝑥𝑚 − 1, 𝑦𝑚])
𝑎3 =1
2(𝐼𝑓[𝑥𝑚 + 1, 𝑦𝑚] − 2𝐼𝑓[𝑥𝑚, 𝑦𝑚] + 𝐼𝑓[𝑥𝑚 − 1, 𝑦𝑚])
𝑎4 =1
2(𝐼𝑓[𝑥𝑚, 𝑦𝑚 + 1] − 𝐼𝑓[𝑥𝑚, 𝑦𝑚 − 1])
𝑎5 =1
2(𝐼𝑓[𝑥𝑚, 𝑦𝑚 + 1] − 2𝐼𝑓[𝑥𝑚, 𝑦𝑚] + 𝐼𝑓[𝑥𝑚, 𝑦𝑚 − 1])
𝑎6 =1
4(𝐼𝑓[𝑥𝑚 + 1, 𝑦𝑚 + 1] − 𝐼𝑓[𝑥𝑚 − 1, 𝑦𝑚 + 1] − 𝐼𝑓[𝑥𝑚 + 1, 𝑦𝑚 − 1] + 𝐼𝑓[𝑥𝑚 − 1, 𝑦𝑚 − 1])
The centroiding algorithm will be implemented via Python script. The hot pixel threshold is set within the
script. The number of frames to average is set by the attribute
“atst.tcs.wccs.cv.calibCtrl.centroidNumImages”, and the ID of the reference image is set by the attribute
“atst.tcs.wccs.cv.calibCtrl.refPsfId”.
We have simulated this algorithm to demonstrate its effectiveness in detecting and centroiding point
sources on simulated night images. The simulation begins by creating a synthetic image consisting of one
bright point source and multiple background point sources placed randomly throughout the image.
The photon flux arriving at the top of Earth’s atmosphere is calculated using standard flux models for a
given apparent magnitude, assuming 5500 K star temperature. Atmospheric transmission in the visible is
estimated from “Allen’s Astrophysical Quantities”[2] and transmission through DKIST to the CV camera
is estimated using theoretical or as-built (where available) coating response curves.
The final CV image is calculated by convolving the perfect point source image with a long-exposure
atmospheric PSF modeled as a Lorentzian with full-width-half-max equal to 𝜆 𝑟0⁄ . Shot noise and read
noise are added to the image based on measured CV camera parameter and hot pixels are added by
randomly setting a user-adjustable number of pixels to their max value, 1023.
The above algorithm is then applied to the noisy image and the error between the measured centroid and
the actual star position is calculated over 100 iterations.
Simulation results are shown in Figure 1. The top two images show a simulated magnitude 4.0 star with
five randomly-positioned background stars that are each half its apparent magnitude. For these
simulations, we assume that the CV filter has been removed. Using the 60-arcsecond field of view, a one
second CV exposure time, and no binning, the stars are all easily visible to the eye and the centroiding
algorithm is able to locate the brightest star to within 5 milli-arcseconds.
CV CDD
SPEC-0180, Rev A Page 7 of 90
The bottom two images show a different image generated with an 8.0 magnitude star. In this case, the
brightest star is very difficult to identify by eye but the centroiding algorithm is able to locate the center
of the bright star to within 0.04 arcseconds. This result demonstrates the power of a matched filter
approach. As seen in Figure 2, the matched filter clearly identifies the stars in the image, even with a
reference PSF that is a different shape and width of the actual PSF. For these simulations, we use a
Lorentzian PSF for the true telescope PSF and our reference PSF is a Gaussian with half the width of the
actual telescope PSF.
Figure 1: Simulated images: [top left] mag 4.0 star [top right] mag 4.0 star with noise [bottom left] mag 8.0 star [bottom
right] mag 8.0 star with noise
CV CDD
SPEC-0180, Rev A Page 8 of 90
Figure 2: Output of the matched filter on the noisy image from the bottom of Figure 1
Figure 3: Estimated CV centroiding error both with and without the CV filter in place
Figure 3 shows the estimated performance of the CV centroiding algorithm as a function of star
brightness. The plot was made using the same estimation methods described in TN-0185. Results of the
full centroiding simulation described earlier agree closely with the results shown in Figure 3.
For night-time imaging with the filter in place, the limiting magnitude is approximately 5.0 for a
centroiding accuracy of 0.1 arcseconds. With the filter removed, the limiting magnitude is increased to
approximately 8.5. These results suggest that it may be possible to do night-time pointing maps with the
CV filter in place, however, removing the filter will provide much better performance.
CV CDD
SPEC-0180, Rev A Page 9 of 90
The CV filter is designed to be easily removable by hand and will not shift the beam when replaced so we
recommend removing the CV filter for night-time pointing map calculations.
3.2 CV LIMB FINDING
The CV will be able to locate the solar limb position as part of the procedure for establishing the
heliocentric coordinate system. The limb finding algorithm works by identifying the most prominent line
in the CV image using a combination of the Canny edge detection algorithm and Hough line transform.
Before running the solar limb image through the Canny and Hough algorithms, the dark and gain-
corrected CV image will be downsampled to reduce the computational complexity of the problem and
average out noise. Based on simulations, the default downsampling will be by a factor of 8. The
downsampling factor may be adjusted during IT&C based on on-sky results.
The Canny edge detection algorithm [3] is a non-linear image processing method that uses gradients to
identify edge features in images. Its output is a binary image with ones representing edge pixels. We will
use the “canny” function in the scikit-image package for Python[5] to implement the Canny edge detection
step of this algorithm. The Canny filter parameters are set within the Python script and can be easily
adjusted by the WFC specialist.
After processing with the Canny edge filter, the resulting binary image is run through a Hough line
transform. The Hough line transform maps points in image space to sinusoids in Hough space, a space
parameterized by the polar coordinates of a vector normal to lines in image space. If a strong line feature
exists in the image, the sinusoids produced in Hough space by the line pixels will all intersect at a
common point, which defines the vector normal to the line feature. The Hough transform will identify the
most prominent line in the CV image, which should be the solar limb.
For this algorithm, we will use the “hough_line” and “hough_line_peaks” functions in the scikit-image
package[5] to implement the Hough transform.
When using the CV limb finding calibration, the accuracy will be improved if the CV is set to the 30
arcsecond field of view so that the solar limb is better fit by a line.
We have simulated this algorithm using a synthetic image of the solar limb. The synthetic image was
generated using the solar limb darkening function at 550 nm from “Allen’s Astrophysical Quantities”[2],
𝐼(𝜓)
𝐼(0)= 1 − 0.47(1 − cos 𝜓) − 0.23(1 − cos 𝜓)2
where 𝐼 is the intensity, 𝜓 is the angle of incidence from the emitting surface to the observer. Using the
small angle approximation,
cos 𝜓 ≈ √1 − (𝜃
sin Ω)
2
where 𝜃 is the angle from the center of the sun to the observed point on the sun and Ω is the angle from
the center of the sun to the limb of the sun.
CV CDD
SPEC-0180, Rev A Page 10 of 90
Figure 4: Simulated limb images [left] noiseless image [right] with detector noise and atmospheric blurring. Heat map
stretch shows intensity values at 550 nm.
Figure 5: [left] Canny edge detector output [right] Hough transform results
A simulated 30-arcsecond image of the solar limb with no noise and no diffraction effects is shown in
Figure 4. After the limb image is generated, it is convolved with an atmospheric PSF, created using the
same process as in the previous section, and random photon noise and read noise are added. For noise
purposes, we assume that the CV exposure time has been adjusted so the maximum non-saturated pixel is
approximately 80% of the detector’s full well depth.
Figure 5 shows the result of applying the Canny edge detector and then a Hough line transform to the
limb image. The global maximum in the Hough transform results identifies the position of the solar limb.
Using this method, we are able to detect the solar limb position to an accuracy better than 0.1 arcseconds
and a repeatability better than 0.05 arcseconds. There is some bias in the measurement because the solar
limb is actually an arc rather than a line. As a result of this, using the smallest field of view possible will
give the best accuracy when finding the solar limb.
CV CDD
SPEC-0180, Rev A Page 11 of 90
If the CV is required to identify the solar limb to better than 0.1 arcseconds accuracy then we may need to
alter this algorithm. One way to improve its accuracy would be to apply a correction factor to find the
difference between the solar limb position and the linear approximation to the limb.
It’s also possible that the accuracy could be improved by using the Hough circle transform instead of the
Hough line transform. The Hough circle transform is generally applied to circles that fit fully within the
image. However, since we are able to tightly constrain the circle’s radius, we should be able to accurately
identify the solar center point based on a limb image.
3.3 CV STREHL CALCULATION
The CV will need to estimate the Strehl ratio of a point source for use during fabrication and laboratory
integration before being shipped to the telescope.
When Strehl ratio measurement is enabled, the CV will grab the most recent image from the CV camera,
perform a Strehl measurement, and report the measured Strehl value. The Strehl measurement routine will
perform a user-defined number of measurements and return the mean Strehl and the standard deviation of
the Strehl measurements.
The Strehl ratio measurement procedure will estimate the Strehl ratio of the brightest point source in the
CV image using the following procedure, which is very similar to method 2b from Roberts, et al[1].
1. The centroiding algorithm from section 3.1 will be used to estimate the position of the brightest
point source in the image. The reference PSF used for the centroiding algorithm and the reference
PSF used later in the Strehl calculation will be the same array. Reference PSF arrays will be
calculated offline and loaded from a database when the Strehl calculation is requested. The
reference PSF to use will be loaded based on both the current CV field of view and the current
calibration target in use.
2. The CV image is translated, using Shannon interpolation, by the negative of the error vector
measured in the previous step. The center pixel of the detected point source should now be
aligned with the center pixel of the CV detector.
3. The CV image will be cropped to a square image encompassing the central 171 by 171 pixels of
the full CV image.
4. The median value of all pixels outside a 68 pixel radius from the center of the cropped image will
be calculated and subtracted from all pixels of the cropped image.
5. All pixels in the cropped image within a 68 pixel radius of the center will be summed together
and all pixels in the cropped image will be divided by this summed value.
6. The same procedures in steps 4 and 5 will be applied to the reference PSF. If the reference PSF is
larger than the cropped PSF, the central 171 by 171 pixel region of the reference PSF will be
cropped before applying these procedures.
7. The Strehl ratio will be estimated by dividing the maximum value of the processed image from
step 5 by the maximum value of the processed reference image from step 6.
When generating reference PSF images, we will account for pixel size by generating a PSF from
analytical methods at a resolution at least 4x the final resolution, then downsampling to the resolution of
the CV.
The Strehl calculation is performed by a Python script. The script can be easily modified to change the
values of the window size (step 3), the radii of the background subtraction region (step 4), and the PSF
normalization radius (step 5).
CV CDD
SPEC-0180, Rev A Page 12 of 90
Reference PSFs will be generated offline and loaded into the bulk database. An attribute in the CV
controller (atst.tcs.wccs.cv.calibCtrl.refPsfId) indicates which reference PSF is to be used in the
calibration script.
3.4 CV PLATE SCALE CALCULATION
The CV will need to estimate its plate scale as part of the routine WFC calibration process. The CV
platescale is used for calibrating the telescope pointing and the HOWFS and LOWFS offpointing
positions.
The CV platescale will be calibrated using a line grid target at the GOS focal plane of the telescope. The
line grid target will contain horizontal and vertical lines with a known constant spacing between them.
When the CV is configured to perform a plate scale calibration, it will image the line grid target, calculate
the distance between the grid lines in pixels, and use knowledge of the line grid spacing to estimate the
CV platescale.
The key calculation to this algorithm is the determination of the line spacing in the CV image. For this
step we rely on the Hough line transform. Similar to section 3.2, we will use the scikit-image function
“hough_line” in this algorithm as well. In Hough space, the grid of lines corresponds to two columns of
points, with the space between points in one column representing the pixel distance between grid lines in
the horizontal direction, and the space between points in the other column representing the pixel distance
between grid lines in the vertical direction.
We calculate the spacing between points by extracting the column of points, finding its autocorrelation,
and determining the distance from the center of the autocorrelation to its first maximum.
One note on this procedure is that the GOS targets will rotate relative to the CV based on the telescope
altitude, azimuth, and coudé angles. Therefore, it is unlikely that the horizontal and vertical grid lines will
be aligned with the x and y axes of the CV unless the coudé platform is specifically rotated for this
purpose. Additionally, the GOS grid target may have an alignment target obscuring the grid lines in the
central 20 arcseconds
In order to perform this calibration with a centrally-obscured, non-aligned grid, we first do a rough
calculation of the grid angle, then mask out the center of the image with a square of the appropriate size
and rotation. We then perform the plate scale calculation, and finally we rotate the calculated plate scales
from the target grid horizontal-vertical coordinates into the CV x-y coordinates.
The full procedure is as follows,
1. Identify which field-of-view is currently selected for the CV
2. Acquire a CV image that has been dark and gain-corrected.
3. Calculate the Otsu threshold of the image[6] using the scikit-image function “threshold_otsu[5]”.
Set all pixels with intensity value above the Otsu threshold to zero and all pixels with intensity
value equal to or below the Otsu threshold to one.
4. Perform a low-resolution (angular resolution ~0.5 degrees) Hough transform on the thresholded
image using the scikit-image “hough_line” function over angles -45 to +45 degrees.
5. Sum along the radial values (columns) of the resulting Hough accumulator and find the maximum
value, corresponding to the rotation angle of the target grid.
6. Create a square mask the size of the known obscuration in the center of the grid target, at a
rotation angle equal to the rotation angle calculated in step 5. The size of the mask will depend on
the selected CV field of view. Set all pixel values of the image obtained in step 2 within the
masked area equal to the mode of the intensity values in that same image.
CV CDD
SPEC-0180, Rev A Page 13 of 90
7. Calculate the Otsu threshold of the masked image[6] using the scikit-image function
“threshold_otsu[5]”. Set all pixels with intensity value above the Otsu threshold to zero and all
pixels with intensity value equal to or below the Otsu threshold to one.
8. Calculate a high-resolution Hough line transform (angular resolution < 0.05 degrees) to the
thresholded image from step 7 using the scikit-image function “hough_lineError! Reference source not f
ound.” for angles between -90 and +90 degrees.
9. Search the columns of the Hough space image that correspond to angles between -45 and +45
degrees for the column that has the largest summed value. Extract that column and all columns to
the left and right of it corresponding to angles ±5 degrees of the maximum column. The exact
number of columns to extract may change during IT&C based on the width of the grid lines on
the target.
10. Average across rows of the extracted columns from the previous step to form a 1-D array.
Calculate the autocorrelation of this array. Find the gradient of the autocorrelation.
11. Ignoring the peak near zero, calculate the first zero-crossing where the gradient of the
autocorrelation goes from positive to negative. Use quadratic interpolation to find the zero-
crossing value to subpixel precision.
12. The zero-crossing value is the number of pixels between grid lines in the horizontal direction.
13. Set the values in all columns extracted in step 9 to zero and search all columns in the Hough
image for the column with the largest summed value. Check that this new maximum column is
approximately 90 degrees from the maximum column found in step 9. Extract the new maximum
column and all columns to the left and right of it corresponding to angles ±5 degrees of the
maximum column. The exact number of columns to extract may change during IT&C based on
the width of the grid lines on the target.
14. Repeat steps 10-12, with the columns extracted in step 13. The zero-crossing value from this
second set of columns is the pixel spacing between grid lines in the horizontal direction.
15. Using the known spacing of the target grid lines, project the measured horizontal and vertical grid
spacings into the CV x and y coordinate plane and calculate the CV plate scale in x and y
directions.
We have simulated this algorithm to verify that it meets accuracy requirements. Note that there are
additional steps in the algorithm that are not detailed in the above steps. The additional steps deal with
how to handle maxima near the edge of the Hough accumulator, smoothing to improve detection of the
zero-crossing in steps 11 and 14, and a fix to prevent the projection of grid spacing to CV x and y
coordinates from blowing up when the grid is rotated at 45 degrees.
The test image of the line grid was simulated based on line grid images from the DST that were
dynamically rescaled to match the line grid spacing at the DKIST. The 30-arcsecond CV field of view
was simulated, since the obscuration from the central Air Force target is more pronounced in that
configuration.
CV CDD
SPEC-0180, Rev A Page 14 of 90
Figure 6: [clockwise from top left]: Grid image, thresholded image, Hough transform, Extracted column average.
Figure 6 shows the DST image used in our simulations, rescaled to the 30 arcsecond CV platescale. The
center 21 arcseconds of the image has been cut out to approximate the proposed GOS target. The
proposed GOS target has an Air Force resolution target obscuring the center 21 arcseconds of the grid, so
that area of the image is unusable for platescale calculations. In our simulations, we were able to identify
the CV platescale to an accuracy of 0.0002 arcseconds per pixel.
Further testing was run with the CV camera in the lab, using a printed grid target. The printed grid target
was used to test that the algorithm was robust for variable grid spacing, thickness, and rotation.
3.5 CV FOCUS CALIBRATION
The CV will need to optimize its focus as part of the routine WFC calibration process.
The CV Focus Calibration uses an iterative search to maximize the squared image gradient, a criteria
shown to repeatably find the best focus position for a variety of image structures[7].
The full procedure is as follows,
1. Identify the objective lens currently in use by the CV
2. Move the z-axis motor of the active CV objective lens to its “default” named position.
CV CDD
SPEC-0180, Rev A Page 15 of 90
3. Read the current “default” named position from the current motor position and set it as the center
of the current focus-finding iteration. Set the step size of the current focus-finding iterations as
the default step size. The default step size is set through an attribute of the CV camera controller.
4. Move the z-axis motor of the active CV objective lens to the position, ‘center – step size’.
5. Acquire a CV image that has been dark and gain-corrected and calculate the squared sum of the
image gradients in x and y directions,
𝑔𝑡𝑜𝑡 = 𝑔𝑥 + 𝑔𝑦
where,
𝑔𝑥 = ∑ ∑(𝐼(𝑥 + 1, 𝑦) − 𝐼(𝑥, 𝑦))2
𝑁−2
𝑦=0
𝑀−1
𝑥=0
𝑔𝑦 = ∑ ∑(𝐼(𝑥, 𝑦 + 1) − 𝐼(𝑥, 𝑦))2
𝑁−2
𝑦=0
𝑀−1
𝑥=0
6. Repeat steps 4 and 5 for the positions ‘center’ and ‘center + step size’.
7. Fit a polynomial to the squared gradients calculated for the three z positions and find the z-
position that corresponds to the maximum squared gradient.
8. If the z-position corresponding to the maximum squared gradient is bracketed by ‘center – step
size’ and ‘center + step size’ then define the center of the next iteration as the z-position
corresponding to the maximum squared gradient and divide the step size by two.
9. If the z-position corresponding to the maximum squared gradient is outside the range searched by
the previous steps, then define the center of the next iteration as ‘center – step size’ if the best z-
position is less than ‘center – step size’. Otherwise define the center of the next iteration as
‘center + step size’. Do not change the step size.
10. Check convergence criteria. If the maximum number of iterations has been reached or the
difference between the center of the next iteration and the center of the current iteration is less
than the minimum step size, proceed to the next step. The maximum number of iterations is set
through an attribute of the CV controller. The minimum step size is set in the CV Focus
calibration script.
If the convergence criteria has not been met, continue to the next focus-finding iteration by
repeating steps 4-10 with the new center position and step size.
11. Move the z-motor of the active objective lens to the position corresponding to the maximum
squared gradient.
12. Enable position saves on the current z-axis motor and save the current position as the “default”
named position.
We have tested this algorithm in the lab on a variety of test targets to verify that it meets accuracy and
repeatability requirements.
CV CDD
SPEC-0180, Rev A Page 16 of 90
4 CV OPTICAL DESIGN
This section presents the CV optical design and analysis supporting its ability to meet all design
requirements. The optical layout of the CV elements is shown in Figure 7. The optical interface to the CV
is defined by the transmissive surface of the LOWFS beam splitter.
The two CV objective lenses are mounted on motorized translating stages so that they can be moved
perpendicular to the optical path. Using these motorized stages, either of the objective lenses can be
moved into or out of the beam path, providing either a 30 arcsecond field of view or a 60 arcsecond field
of view.
A flat-top filter with 530 nm central wavelength and 10 nm bandpass will be placed in the converging
beam between the objective lens and the final image.
When DKIST is observing in diffraction-limited mode, the CV will receive diffraction-limited images.
Consequently, the final image must be sampled finely enough to resolve fine structures in the observed
objects and the CV optics must not significantly degrade the image quality. These aspects of the CV
design are captured in the CV design requirements.
Figure 7: CV optical layout
4.1 CV OPTICAL DESIGN REQUIREMENTS
The following are the requirements used to create and tolerance the CV optical design.
1. Central wavelength: 530 nm
CV CDD
SPEC-0180, Rev A Page 17 of 90
2. Bandpass: 10 nm
3. Field of View switchable between 30 arcseconds and 60 arcseconds (square)
4. Strehl performance (30 arcsecond FoV): minimum 0.7 over full field
5. Strehl performance (60 arcsecond FoV): minimum 0.4 over central 45 arcseconds,
minimum 0.3 over remainder of FoV
6. Final image plate scale (30 arcsecond FoV): 1.980 arcseconds/mm
7. Final image plate scale (60 arcsecond FoV):3.960 arcseconds/mm
8. Maximum track length: 3.2 meters measured from LOWFS beam splitter
Optical design requirements 1-3 flow down directly from SPEC-0058. Optical design requirement 4
derives from engineering requirements to use the CV for validating WFC Strehl performance.
Requirement 5 derives from the operational need to display images of the telescope FoV without
significantly degrading the image quality.
Requirements 6 and 7 are driven by requirement 3 in combination with SPEC-0058, which sets
requirements on the pixel sampling of the CV. The chosen CV camera has 7.4 micron pixels and an active
area that is 2048 x 2048 pixels square. As a result, we desire the final pixel scale to be,
30 𝑎𝑟𝑐𝑠𝑒𝑐𝑜𝑛𝑑𝑠
2048∗0.0074 𝑚𝑚= 1.980 𝑎𝑟𝑐𝑠𝑒𝑐𝑜𝑛𝑑𝑠/𝑚𝑚,
for the 30 arcsecond field of view and, similarly, 3.959 arcseconds/mm for the 60 arcsecond field of view.
Final plate scale is a function of system focal length:
𝑃 =206265
𝑓
where P is the platescale in arcseconds/mm and f is the effective focal length in mm. In order to achieve
the desired platescales, we require a focal length of 104.20 meters for the 30-arcsecond CV and 208.40
meters for the 60-arcsecond CV. Given the system’s numerical aperture of 4 meters, these focal lengths
correspond to an effective F/# of 26.050 for the 30-arcsecond CV and 13.025 for the 60-arcsecond CV.
The expected plate scales yield a final resolution of 1.87 pixels per resel for the 30-arcsecond FoV and
0.93 pixels per resel for the 60-arcsecond FoV, with a resel defined as the CV central wavelength divided
by the telescope aperture. This sampling meets the top-level resolution requirements in SPEC-0058.
Requirement 8 is an engineering requirement to ensure all the optics fit on the table space allocated.
4.2 CV OPTICAL PERFORMANCE
Figure 8 and Figure 10 show spot diagrams from the baseline optical design of the 30-arcsecond and 60-
arcsecond CV configurations. Spots are shown at the center and at each edge of the field of view.
CV CDD
SPEC-0180, Rev A Page 18 of 90
Figure 8: Spot diagram of center and corners of the 30-arcsecond CV.
Figure 9: Strehl map for as-designed 30-arcsecond CV
CV CDD
SPEC-0180, Rev A Page 19 of 90
Figure 10: Spot diagram of center and corners of the 60-arcsecond CV.
Figure 11: Strehl map for as-designed 60-arcsecond CV
CV CDD
SPEC-0180, Rev A Page 20 of 90
4.3 OPTICAL TOLERANCE ANALYSIS
ASE Optics performed the tolerance analysis for the WFC relay optics, including the CV. Requirements
for performing this analysis are given in section 4.1. Results from the full WFC Relay Optics tolerance
analysis are discussed in DKIST project document TN-0189.
4.3.1 ZEMAX Tolerance Model
Table 1 contains the parameters used by ASE Optics to run the tolerance analysis for the CV with the 30
arcsecond objective selected. The parameters used for the 60 arcsecond CV are identical to those for the
30 arcsecond CV except for the change in position of the objective lens, which causes the airspace
compensator for the 60 arcsecond CV to be reduced by about half.
Table 1: ZEMAX model tolerance inputs for WFC relay optics with 30 arcsecond CV
# Type Surf Nominal Min Max Comment
1 TOFF - - - - ** Compensator
2 COMP 101 -1905.1 -20.0 20.0 Airspace, triplet to image plane
3 CPAR 102 -1.3039 -2.00 20.0 Image Plane, Theta-X Tilt
4 CPAR 102 0.0000 -2.00 20.0 Image Plane, Theta-Y Tilt
5 TOFF - - - -
6 TWAV - - 0.6328 - Default test wavelength.
8 TOFF - - - - ** Homogeneity Tolerances:
9 TEZI 84 0.0000 -2.54E-5 2.54E-5 HOAO Splitter
10 TEZI 91 0.0000 -2.54E-5 2.54E-5 LOAO Splitter
11 TEZI 97 0.0000 -2.00E-5 2.00E-5 Triplet, L1
12 TEZI 98 0.0000 -3.00E-5 3.00E-5 Triplet, L2
13 TEZI 99 0.0000 -2.00E-5 2.00E-5 Triplet, L3
14 TOFF - - - - ** Power Tolerances:
15 TFRN 84 0.0000 -0.100 0.100 HOAO Splitter Front
16 TFRN 85 0.0000 -0.100 0.100 HOAO Splitter Back
17 TFRN 91 0.0000 -0.100 0.100 LOAO Splitter Front
18 TFRN 92 0.0000 -0.100 0.100 LOAO Splitter Back
19 TFRN 97 0.0000 -0.500 0.500 Triplet
20 TFRN 98 0.0000 -0.500 0.500
21 TFRN 99 0.0000 -0.500 0.500
22 TFRN 100 0.0000 -0.500 0.500
23 TOFF - - - - ** Thickness tolerances:
24 TOFF - - - - ** Airspaces
25 TTHI 87 -174.60 -0.500 0.500 HOAO Splitter to LOAO Splitter
CV CDD
SPEC-0180, Rev A Page 21 of 90
26 TTHI 94 -175.40 -0.500 0.500 LOAO Splitter to Triplet
27 TOFF - - - - ** Glass Thickness
28 TTHI 84 -25.400 -0.150 0.150 HOAO Splitter
29 TTHI 91 -25.400 -0.150 0.150 LOAO Splitter
30 TTHI 97 -10.000 -0.150 0.150 Triplet, L1
31 TTHI 98 -15.000 -0.150 0.150 Triplet, L2
32 TTHI 99 -10.000 -0.150 0.150 Triplet, L3
33 TOFF - - - - ** Surface Tilt Tolerances:
34 TSTX 84 0.0000 -1.39E-3 1.39E-3 HOAO Splitter
35 TSTY 84 0.0000 -1.39E-3 1.39E-3
36 TSTX 91 0.0000 -1.39E-3 1.39E-3 LOAO Splitter
37 TSTY 91 0.0000 -1.39E-3 1.39E-3
38 TSTX 97 0.0000 -1.67E-3 1.67E-3 Triplet L1 Front
39 TSTY 97 0.0000 -1.67E-3 1.67E-3
40 TSTX 98 0.0000 -1.67E-3 1.67E-3
41 TSTY 98 0.0000 -1.67E-3 1.67E-3
42 TSTX 99 0.0000 -1.67E-3 1.67E-3
43 TSTY 99 0.0000 -1.67E-3 1.67E-3
44 TSTX 100 0.000 -1.67E-3 1.67E-3 Triplet L3 Back
45 TSTY 100 0.0000 -1.67E-3 1.67E-3
46 TOFF - - - - ** Element decenter & tilt tolerances:
47 TEDX 97 0.0000 -0.025 0.025 Triplet
48 TEDY 97 0.0000 -0.025 0.025
49 TETX 97 0.0000 -8.33E-3 8.33E-3
50 TETY 97 0.0000 -8.33E-3 8.33E-3
51 TOFF - - - - ** Element Tilt within triplet
52 TETX 97 0.0000 -1.67E-3 1.67E-3 Triplet L1
53 TETY 97 0.0000 -1.67E-3 1.67E-3
54 TETX 99 0.0000 -1.67E-3 1.67E-3 Triplet L3
55 TETY 99 0.0000 -1.67E-3 1.67E-3
56 TOFF - - - - ** Irregularity tolerances:
57 TIRR 84 0.0000 -0.100 0.100 HOAO Splitter Front
58 TIRR 85 0.0000 -0.100 0.100 HOAO Splitter Back
CV CDD
SPEC-0180, Rev A Page 22 of 90
59 TIRR 91 0.0000 -0.100 0.100 LOAO Splitter Front
60 TIRR 92 0.0000 -0.100 0.100 LOAO Splitter Back
61 TIRR 97 0.0000 -0.500 0.500 Triplet
62 TIRR 98 0.0000 -0.500 0.500
63 TIRR 99 0.0000 -0.500 0.500
64 TIRR 100 0.0000 -0.500 0.500
65 TOFF - - - - ** Index tolerances:
66 TIND 84 1.4585 -5.00E-4 5.00E-4 HOAO Splitter
67 TIND 91 1.4585 -5.00E-4 5.00E-4 LOAO Splitter
68 TIND 97 1.5225 -2.00E-4 2.00E-4 Triplet L1
69 TIND 98 1.4388 -2.00E-4 2.00E-4 Triplet L2
70 TIND 99 1.5225 -2.00E-4 2.00E-4 Triplet L3
71 TOFF - - - - ** Abbe number tolerances:
72 TABB 84 67.821 -0.339 0.339 HOAO Splitter
73 TABB 91 67.821 -0.339 0.339 LOAO Splitter
74 TABB 97 59.835 -0.120 0.120 Triplet L1
75 TABB 98 94.946 -0.190 0.190 Triplet L2
76 TABB 99 59.835 -0.120 0.120 Triplet L3
4.3.2 Monte Carlo Results
A Monte Carlo analysis was used to evaluate the likelihood of the manufactured CV design to meet Strehl
requirements based on the defined manufacturing and alignment tolerances. 1000 simulations were run
for each CV setup. For the 30 arcsecond CV, 92% if the Monte Carlo results met requirements, and for
the 60 arcsecond CV, 99% of the Monte Carlo results met requirements.
4.4 OPTICAL ALIGNMENT
Installation and alignment of the CV will be done after the WFC relay optics, up to and including the
LOWFS beamsplitter, have been installed and aligned. The 30 arcsecond objective lens will be installed
first and the facility CMM will be used to position it. Next, the filter assembly will be installed. A facility
wavefront sensor (4D PhaseCam) will be used to fine-tune the decenter and tilt of the 30 arcsecond
objective lens. The 30 arcsecond objective will then be moved out of the beam and the 60 arcsecond
objective will be installed, aligned with the CMM, and then fine-tuned using the wavefront sensor.
Finally, the camera will be installed and aligned using the CMM and fine-tuned using the GOS pinhole to
center and focus the camera. An extended source at the GOS, such as an air force target or grid, will be
used to fine-tune the camera tilt. Additional alignment details will be documented in PROC-0261, WFC
Alignment Plan, and will be included with the documentation delivered with the system.
CV CDD
SPEC-0180, Rev A Page 23 of 90
5 CV HARDWARE DESIGN
5.1 OVERVIEW OF COUDÉ WFS LAYOUT
The following few images give a perspective of the overall CV design in the coudé room and relative
position to the other associated coudé instrumentation.
A top down view of the overall coudé instrumentation optical layout is shown in Figure 12. The location
of the wavefront correction optical system is shown in brown in the upper left quadrant.
Figure 12: Overhead view of coudé instrumentation
Figure 13 shows an overhead view of the wavefront correction system and how it is fed by the main
telescope light feed. Figure 13 also shows a closer overhead view of the wavefront correction system as it
is laid out on optical tables in the coudé instrument lab.
CV CDD
SPEC-0180, Rev A Page 24 of 90
Figure 13: Light feed to WFC optics (left), WFC bench closeup (right)
Figure 14 shows the wavefront correction system and telescope feed optics with the major components
labeled, along with the High Order WFS, Context Viewer and Low Order WFS channels.
Figure 14: WFC system with optical paths labeled
CV CDD
SPEC-0180, Rev A Page 25 of 90
5.2 OVERVIEW OF WFS OPTO-MECHANICAL LAYOUT
Figure 15 shows an overview of the WFC opto-mechanical system layout. The WFC feed optics and
Context Viewer are depicted in the yellow light path, while the HOWFS is shown in the red light path and
the LOWFS is shown in the green light path.
Figure 15: Opto-mechanical layout of WFC, CV path shown in yellow.
A detailed drawing of the wavefront correction system components is shown in Figure 16 along with an
identification of each major subsystem item in Table 2.
CV CDD
SPEC-0180, Rev A Page 26 of 90
Figure 16: WFC detail with all components labeled.
Table 2: WFC component list
Item # Description
1 M10 - Deformable Mirror
2 BS1 - WFS Beam Splitter
3 OAA1 - Off Axis Asphere #1
4 FM1 - Fold Mirror
5 FM2 - Fold Mirror
6 OAA2 - Off Axis Asphere #2
7 HOWFS BS - High Order Beam Splitter
8 LOWFS BS - Low Order Beam Splitter
9 CV 30 OL - Context Viewer 30 arcsecond Objective Lens
10 CV 60 OL - Context Viewer 60 arcsecond Objective Lens
11 CV Filter
12 CV Camera
CV CDD
SPEC-0180, Rev A Page 27 of 90
Item # Description
13 HO FSM – High Order Field Steering Mirror
14 HO OL – High Order WFS Objective Lens
15 HO FS – High Order WFS Field Stop
16 HO PL – High Order WFS Pupil Lens
17 HO LA – High Order WFS Lenslet Array
18 HO RL1 – High Order WFS Relay Lens #1
19 HO F – High Order WFS Filter
20 HO RL2 – High Order WFS Relay Lens #2
21 HO Camera
22 LO FSM – Low Order WFS Field Steering Mirror
23 LO OL – Low Order WFS Objective Lens
24 LO FS – Low Order WFS Field Stop
25 LO PL – Low Order WFS Pupil Lens
26 LO LA – Low Order WFS Lenslet Array
27 LO RL1 – Low Order WFS Relay Lens #1
28 LO F – Low Order Filter
29 LO RL2 – Low Order WFS Relay Lens #2
30 LO Camera
5.3 CV OPTO-MECHANICAL DESIGN
A summary of the CV opto-mechanical layout is shown in Figure 17. The following subsections provide
detailed design descriptions of each of the CV assemblies.
CV CDD
SPEC-0180, Rev A Page 28 of 90
Figure 17: CV opto-mechanical overview
Table 3: CV motions and part numbers
The required CV motions and associated mechanism part numbers are listed above in Table 3.
Motorized Micrometer Manual Stage MFR Stage Model Motor MFR Motor Model Micrometer MFR Micrometer Model
WFC CV
HR Objective Lens
X Parker 404200XRMS__D2H7L7C1M12E1B1P1R1 Parker SM232BE-NPSN
Y NSO Newport SM-50
Z Parker 40450XRMS__D2H7L7C5M3E1B1P1R1 Parker SM232BE-NPSN
α NSO
β NSO
LR Objective Lens
X Parker 404200XRMS__D2H7L7C1M12E1B1P1R1 Parker SM232BE-NPSN
Y NSO Newport SM-50
Z Parker 40450XRMS__D2H7L7C5M3E1B1P1R1 Parker SM232BE-NPSN
α NSO
β NSO
Filter
Z Newport
Camera Mount
X Newport M-426 Newport SM-25
Y Newport M-426 Newport SM-25
Z Newport M-426 Newport SM-25
β NSO Newport AJS100-1
Common to Filter & Camera
Dovetail Rail Newport PRL-12
Dovetail Carrier Newport M-PRC-3
Dovetail Carrier Newport M-PRC-3
Filter Holder Newport FH-2R
CV CDD
SPEC-0180, Rev A Page 29 of 90
5.3.1 30-Arcsecond Objective Lens Assembly
Figure 18: CV 30 arcsec objective lens assembly
CV CDD
SPEC-0180, Rev A Page 30 of 90
The 30-arcsecond objective lens assembly is a mount consisting of motorized stages for translation in the
x and z axes, a manual micrometer for translation in the y axis, and a tip/tilt adjustable lens cell. The
assembly is shown in Figure 18.
The motorized x-axis stage is used for placing the lens into or out of the optical path. The motorized z-
axis stage is used for positioning the lens along the optical path for focus. These stages are 404XR series
manufactured by Parker and the motors are Parker SM23 series brushless servo motors with closed loop
encoder feedback.
The y-axis adjustment is a manual micrometer used for positioning the height of the lens in the optical
path above the bench. The adjustment is accomplished by means of a micrometer driven wedge and
locked in place with a clamping dovetail slide. This adjustment is for alignment purposes and would
remain locked in place at all other times. The micrometer is a Newport SM-50 with 1µm Vernier scale
resolution.
The lens cell is tip/tilt adjustable. The pivot point is a spherical bearing and the tip/tilt is performed by
turning two spring loaded adjusting screws that can be locked with opposing setscrews. This adjustment
is used for alignment purposes and would be locked in place during normal operations.
Table 4: 30 arcsec objective lens requirements & actual performance specs
Requirement Actual
X-axis Automated Motorized
Resolution: x-axis 5 µm 5 µm
Repeatability: x-axis 5 µm 3 µm
Accuracy: x-axis 25 µm 20 µm
Range: x-axis 100 mm 200 mm
Velocity: x-axis 25 mm/s 300 mm/s max
Z-axis Automated Motorized
Resolution: z-axis 5 µm 5 µm
Repeatability: z-axis 5 µm 3 µm
Accuracy: z-axis 25 µm 12 µm
Range: z-axis ±10 mm 50 mm
Velocity: z-axis 1 mm/s 300 mm/s max
Y-axis Manual Adjust Micrometer
Resolution: y-axis 5 µm 4.7 µm/10 µm micrometer div
Range: y-axis ±10 mm ±11.6 mm
Lockable: y-axis
Tip/Tilt Resolution 1 arcminute 3.9 arcsec/° adj screw
Tip/Tilt Range ±5 arcmin 23.3 arcmin/turn adj screw
Lockable: Tip/Tilt
CV CDD
SPEC-0180, Rev A Page 31 of 90
Table 5: 30 arcsec objective lens COTS datasheets
COTS Datasheets for 30 arcsec Objective Assy
Parker 404XR series stages 34001-Parker-XR_SeriesStages.pdf
Parker SM series motors 34002-Parker-SM_SeriesMotor.pdf
Newport SM series micrometers 34003-Newport-SM_Series Micrometers.pdf
The requirement to motorize the 30-arcsecond objective lens assembly in x flows from the SPEC-0058
requirement that the CV provide a selectable field of view between 30 arcseconds and 60 arcseconds.
Tolerance analysis results show that this objective lens must be centered to an accuracy of 25 microns in
x, y, and z translation. This drives the minimum increment as well as the repeatability of the x and z
motors, and the manual adjust increment in the y-axis micrometer. The necessary ranges for these three
mechanisms are 10 mm in order to accommodate all the alignment cases generated by Monte Carlo
analysis with a safety factor of 3.
The objective lens also must be aligned to within 60 arcseconds accuracy tip and tilt, which sets a
requirement on the lens mounting stability. The tip and tilt range must be 5 arcminutes in order to
accommodate all the alignment cases generated by Monte Carlo analysis with a safety factor of 3.
Finally, the objective lens assembly must be able to be removed from the optical beam completely
without causing any vignetting. This imposes an additional requirement that the x-translation motor be
capable of, at minimum, 100 mm of translation.
5.3.2 30-Arcsecond Objective Lens Analysis
The analysis requirements for the 30-Arcsecond Objective Lens optical flexure was determined by
looking at multiple material and design constraints regarding the following: 1) the allowable optical
surface error as determined by the system engineering optical tolerance analysis, 2) stress limits of the
optic, 3) stress limits of the flexure, 4) predetermined lateral stability requirements up to 0.5 G while
preventing optic-to-cell gapping, and 5) maximizing flexure deformation tolerances.
Actual results of the optical surface errors have been calculated using nodal displacements from finite-
element analysis by Hofstadter Analytical Services. Dan Hofstadter’s analysis report details the unit
optical surface errors, the optical/flexure interface, as well as survivability of specific subassemblies. The
unit optical surface errors were used to determine the maximum allowable RMS surface deformation per
total applied load which defines the maximum preload.
By comparison, stresses calculated by the finite-element software were not used in the immediate area of
line contact between flexure and optical element. The nature of the finite-element model resulted in
unrealistically high stresses in the optic along the line contact. Instead, Hertzian stresses were calculated
manually by means of a linear loading analysis using a guideline of 4.4kN/m as the maximum allowable
contact line load. In all cases, the calculated line load is an order of magnitude or more under this limit.
Refer to Hofstadter’s analysis report, more specifically reference #3 - Strength of Glass from Hertzian
Line Contact, for more details.
All cases involving larger optics, such as the 30-Arcsecond Objective Lens, are deformation limited
instead of stress limited; therefore maximum preloads were determined by the wavefront error
requirements of the optic. Minimum preloads were determined by maximizing the loading conditions to
abate gapping, yet allow for manageable flexure tolerances during fabrication and assembly. The optical
flexure was analyzed via ANSYS finite element analysis (FEA) at the minimum and maximum preloads
to determine flexure displacements at both extremes and verify stresses were below allowable limits.
CV CDD
SPEC-0180, Rev A Page 32 of 90
The flexure for the 30-Arcsecond Objective Lens is identical to the High Order and Low Order Objective
Lens flexure. The flexure is sized to accommodate a minimum loading of 0.70G without axially gapping
the optic/cell interface while lateral stability up to 1.2G is maintained with annealed brass pins located
+/50 degrees from nadir. The overall shape of the flexure has been optimized for imparting minimal
optical wavefront errors to meet the 24.8nm RMS requirement, from the thicker continuous inner ring
helping to distribute the load more effectively, to the long flexure fingers helping to maximize the
allowable axial tolerances for ease of manufacturing the flexure and cell. This particular flexure has been
designed and analyzed for an allowable axial deflection of 0.490 – 1.225 mm which corresponds to the
following specific design constraints: 1) minimum deflection of 0.490mm at a preload of 8N restrains the
optic axially a minimum of 0.7G, while 2) the maximum deflection of 1.225mm at a preload of 20N is
well below the acceptable stress limits of the glass and just below acceptable optical wavefront errors
using a safety factor of 2. The optic thickness and diameter has been measured to match machine the cell
to get as close as possible to nominal preload. In addition, shims at various thicknesses are used to
improve the position of the flexure as needed. Monitoring fastener torque during assembly as well as
interferometer testing will guarantee acceptable preloads and wavefront errors.
The analysis methodology to determine the appropriate flexure design is as follows. Per Hofstadter
Analytical Services, unit optical surface errors were used to determine the maximum allowable RMS
surface deformation per total applied load for each size optic. Size class of the optics is listed in Table 6
below, 30” Objective Lens Preliminary Preload Estimates. Additionally, the table below highlights the
flexure design preloads at the MIN and MAX requirements. Due to the surface error requirement of
24.8nm RMS focus removed, the maximum design preload derived from this requirement is 20N, which
corresponds to the optical surface deformation limit as shown in the table below. The minimum preload
was reduced to 8N which prevents gapping of the optic up to an axial load of 0.7G.
MIN Preload Requirement (No Axial Gapping @ .7G) = 8N
MAX Preload Requirement (Design Load) = 20N
CV CDD
SPEC-0180, Rev A Page 33 of 90
Table 6: 30” Objective Lens Preliminary Preload Estimates
FEA ANSYS results shown in Figure 19 below verify flexure stresses and deformations to be at
acceptable levels at the MAX preload listed above. Margin of safety calculated below.
CV CDD
SPEC-0180, Rev A Page 34 of 90
Figure 19: FEA analysis of 30” Objective Lens mounting flexure
Calculate the Margin of Safety (MOS) of the stress in the flexure based on material properties and safety
factors listed below as well as the design parameters and load/deflection of the ANSYS analysis output
listed above:
Flexure Material: Phosphor Bronze C51000 H08 Spring Temper, Flexure Thickness = 2.03mm
Material Strength: Yield = 551 MPa, Tensile = 690 MPa
Safety Factors: 1.5 Ultimate (Tensile Strength), 1.25 Yield
Predicted Stress @ Design Load of 20N = 171 MPa
MOS = (551 MPa / (171 MPa * 1.25)) - 1 = 1.6 (MOS ≥0 is acceptable)
Calculate the MOS (Margin of Safety) of the optical wavefront errors based on maximum allowable
errors as determined by the system engineering optical tolerance analysis and actual wavefront errors as
documented in Dan Hofstadter’s analysis report and scaled to this particular optic (size class 1 as shown
in the table below with the column titled “Surf nm/N”).
MAX Allowable Surface Error, Focus Removed = 24.8nm RMS
Safety Factor = 2.0
Predicted Surface Error @ MAX Flexure Preload, Focus Removed = 12nm RMS
MOS = (24.8nm RMS / (12nm RMS * 2.0)) - 1 = .03 (MOS ≥0 is acceptable)
Axial gapping of the optic is analyzed as follows to determine if the impact loads at 2G is within
acceptable limits. Using FEA, a representative optical mount was analyzed for stiffness to quantify the
optic displacement during a seismic event to calculate an effective spring rate. Impact velocity is
calculated using fundamental equations of dynamics which in turn gives you the kinetic energy at impact
which is converted into a maximum displacement. Maximum acceleration is derived from the stiffness of
the assembly, its maximum displacement, and the mass of the system, which ultimately calculates the
force on the optic in terms of a linear line load. The maximum allowable linear line load at impact is
4.4kN/m. This analysis assumes any load half the maximum, 2.2kN/m or less, is acceptable. All optics
pass in this regard; the 30-Arcsecond Objective Lens is no exception. Results are shown in Table 7
below.
CV CDD
SPEC-0180, Rev A Page 35 of 90
Table 7: 30” Objective Lens mount axial gapping analysis
CV CDD
SPEC-0180, Rev A Page 36 of 90
5.3.3 60-Arcsecond Objective Lens Assembly
Figure 20: CV 60 arcsec objective lens assembly
CV CDD
SPEC-0180, Rev A Page 37 of 90
The 60-arcsecond lens assembly is essentially the same as the 30-arcsecond lens assembly, except that the
two lenses themselves are different thicknesses.
The 60-arcsecond objective lens assembly is a mount consisting of motorized stages for translation in the
x and z axes, a manual micrometer for translation in the y axis, and a tip/tilt adjustable lens cell. The
assembly is shown in Figure 20.
The motorized x-axis stage is used for placing the lens into or out of the optical path. The motorized z-
axis stage is used for positioning the lens along the optical path for focus. These stages are 404XR series
manufactured by Parker and the motors are Parker SM23 series brushless servo motors with closed loop
encoder feedback.
The y-axis adjustment is a manual micrometer used for positioning the height of the lens in the optical
path above the bench. The adjustment is accomplished by means of a micrometer driven wedge and
locked in place with a clamping dovetail slide. This adjustment is for alignment purposes and would
remain locked in place at all other times. The micrometer is a Newport SM-50 with 1µm Vernier scale
resolution.
The lens cell is tip/tilt adjustable. The pivot point is a spherical bearing and the tip/tilt is performed by
turning two spring loaded adjusting screws that can be locked with opposing setscrews. This adjustment
is used for alignment purposes and would be locked in place during normal operations.
Table 8: 60 arcsec objective lens requirements & actual performance specs
Requirement Actual
X-axis Automated Motorized
Resolution: x-axis 5 µm 5 µm
Repeatability: x-axis 5 µm 3 µm
Accuracy: x-axis 25 µm 20 µm
Range: x-axis 100 mm 200 mm
Velocity: x-axis 25 mm/s 300 mm/s max
Z-axis Automated Motorized
Resolution: z-axis 5 µm 5 µm
Repeatability: z-axis 5 µm 3 µm
Accuracy: z-axis 25 µm 12 µm
Range: z-axis ±10 mm 50 mm
Velocity: z-axis 1 mm/s 300 mm/s max
Y-axis Manual Adjust Micrometer
Resolution: y-axis 5 µm 4.7 µm/10 µm micrometer div
Range: y-axis ±10 mm ±11.6 mm
Lockable: y-axis
Tip/Tilt Resolution 1 arcminute 3.9 arcsec/° adj screw
Tip/Tilt Range ±5 arcmin 23.3 arcmin/turn adj screw
CV CDD
SPEC-0180, Rev A Page 38 of 90
Lockable: Tip/Tilt
Table 9: 60 arcsec objective lens COTS datasheets
COTS Datasheets for 60 arcsec Objective Assy
Parker 404XR series stages 34001-Parker-XR_SeriesStages.pdf
Parker SM series motors 34002-Parker-SM_SeriesMotor.pdf
Newport SM series micrometers 34003-Newport-SM_Series Micrometers.pdf
The requirement to motorize the 60-arcsecond objective lens assembly in x flows from the SPEC-0058
requirement that the CV provide a selectable field of view between 30 arcseconds and 60 arcseconds.
Tolerance analysis results show that this objective lens must be centered to an accuracy of 25 microns in
x, y, and z translation. This drives the minimum increment as well as the repeatability of the x and z
motors, and the manual adjust increment in the y-axis micrometer. The necessary ranges for these three
mechanisms are 10 mm in order to accommodate all the alignment cases generated by Monte Carlo
analysis with a safety factor of 3.
The objective lens also must be aligned to within 60 arcseconds accuracy tip and tilt, which sets a
requirement on the lens mounting stability. The tip and tilt range must be 5 arcminutes in order to
accommodate all the alignment cases generated by Monte Carlo analysis with a safety factor of 3.
Finally, the objective lens assembly must be able to be removed from the optical beam completely
without causing any vignetting. This imposes an additional requirement that the x-translation range be
capable of up to 100 mm of translation.
5.3.4 60-Arcsecond Objective Lens Analysis
The 60-Arcsecond Objective lens is similar to the 30-Arcsecond Objective lens, but it is slightly thicker
and heavier, however the optic is located in the cell with the same custom designed flexure. The analysis
requirements for the 60-Arcsecond Objective Lens flexure still look at the same material and design
constraints. Optical wavefront errors are identical which results in slightly lower axial gapping loads for
the same preload. Lateral stability is still achieved in the form of two annealed brass pins at +/-50
degrees from nadir.
The 60-Arcsecond Objective Lens flexure is designed to accommodate a minimum loading of 0.65G
without axially gapping the optic/cell interface versus 0.7G with the 30-Arcsecond Objective Lens. Both
are optimized to meet optical wavefront errors of 24.8nm RMS maximum. The 60-Arcsecond flexure has
the same allowable axial deflection of 0.490 – 1.225mm which corresponds to the following specific
design constraints: 1) minimum deflection of 0.490mm at a preload of 8N restrains the optic axially a
minimum of 0.65G while 2) maximum deflection of 1.225mm at a preload of 20N is well below the
acceptable stress limits of the glass and just below acceptable optical wavefront errors using a safety
factor of 2. Shims at various thicknesses are used to improve the position of the flexure as needed to
optimize the preload.
The minimum and maximum preloads corresponding to minimum and maximum requirements are
highlighted in Table 10 below. These preloads correspond to known displacements which will be verified
during assembly and test.
MIN Preload Requirement (No Axial Gapping @ .65G) = 8N
MAX Preload Requirement = 20N
CV CDD
SPEC-0180, Rev A Page 39 of 90
Table 10: 60” Objective Lens Preliminary Preload Estimates
FEA ANSYS results shown in Figure 21 below verify flexure stresses and deformations to be at
acceptable levels at the MAX preload listed above. Margin of safety calculated below.
CV CDD
SPEC-0180, Rev A Page 40 of 90
Figure 21: FEA results for the 60” Objective Lens mount flexure
Calculate the MOS (Margin of Safety) of the stress in the flexure based on material properties and safety
factors listed below as well as the design parameters and loads/deflections of the ANSYS analysis output
listed above:
Flexure Material: Phosphor Bronze C51000 H08 Spring Temper, Flexure Thickness = 2.03mm
Material Strength: Yield = 551 MPa, Tensile = 690 MPa
Safety Factors: 1.5 Ultimate (Tensile Strength), 1.25 Yield
Predicted Stress @ Design Load of 20N = 171 MPa
MOS = (551 MPa / (171 MPa * 1.25)) - 1 = 1.6 (MOS ≥0 is acceptable)
Calculate the MOS (Margin of Safety) of the optical wavefront errors based on maximum allowable
errors as determined by the system engineering optical tolerance analysis and actual wavefront errors as
documented in Dan Hofstadter’s analysis report and scaled to this particular optic (size class 1 as shown
in the table below with the column titled “Surf nm/N”):
MAX Allowable Surface Error, Focus Removed = 24.8 nm RMS
Safety Factor = 2.0
Predicted Surface Error @ MAX Flexure Preload, Focus Removed = 12nm RMS
MOS = (24.8nm RMS / (12nm RMS * 2.0)) - 1 = .03 (MOS ≥0 is acceptable)
Axial gapping of the 60-Arcsecond Objective Lens optic is analyzed the same as the 30-Arcsecond
Objective Lens to determine if the impact load at 2G is within acceptable limits. The linear line loading is
slightly greater for the 60-Arcsecond Lens due to its greater mass. See 5.3.2 for a description of the
analysis. It is shown in Table 11 below that loads on this optic are less than half the maximum allowable
linear line loading guideline of 4.4kN/m, therefore impact loads due to axial gapping is deemed
acceptable.
CV CDD
SPEC-0180, Rev A Page 41 of 90
Table 11: 60” Objective Lens axial gapping analysis
CV CDD
SPEC-0180, Rev A Page 42 of 90
5.3.5 CV Filter Assembly
Figure 22: CV filter assembly
The filter holder assembly and camera stage assembly are mounted on a common Newport dovetail rail
and riser block. See Figure 24. The dovetail rail allows manual positioning of the filter holder assembly
along the z-axis. The filter holder is a standard Newport FH-2R filter holder mounted to a stand, which is
in turn mounted to a Newport dovetail carrier, as shown in Figure 22. The filter can easily be placed into
or out of the beam using the dovetail carrier clamp.
Table 12: Filter assembly requirements & actual performance specs
Requirement Actual
Resolution: x-axis 1 mm Located by CMM arm as required
Lockable: x-axis Clamped to optical bench
Resolution: y-axis 1 mm Shim as required
Lockable: y-axis Bolted to dovetail carrier
Resolution: z-axis 1 mm Located by CMM arm as required
Lockable: z-axis
Table 13: Filter assy COTS datasheets
COTS Datasheets for Filter Assy
Newport dovetail rail components 34004-Newport-Dovetail Rail Components.pdf
CV CDD
SPEC-0180, Rev A Page 43 of 90
Newport filter holders 34005-Newport-Filter Holders.pdf
The CV is required to have a central wavelength of 530 nm with a bandpass of 10 nm. This will be
accomplished by inserting a bandpass filter into the beam after the objective lens. The filter will be in a
converging beam and its surface quality must be /2 P-V total surface irregularity and /4 P-V surface
irregularity with focus removed.
A COTS solution for the CV filter has been found, the Chroma ZET532/10x has a central wavelength of
532 nm and a bandwidth of 10 nm. The filter response, shown in Figure 23, does contain significant
transparency at wavelengths longer than 1000 nm. However, the camera quantum efficiency at 1000+ nm
is below 4%, as shown in Figure 25, so we do not expect a significant performance impact from the red
excess of the filter. In case the red excess does prove to be problematic, an additional filter can be added
to block the red light.
Figure 23: Chroma ZET532/10x transmission curve
CV CDD
SPEC-0180, Rev A Page 44 of 90
5.3.6 CV Camera Assembly
Figure 24: CV camera and filter assembly
The camera stage assembly and filter holder assembly are mounted on a common Newport dovetail rail
and riser block. See Figure 24. The dovetail rail allows manual positioning of the camera stage assembly
along the z-axis. The camera is mounted to a series of stacked Newport M-426 crossed roller bearing
linear translation stages that give micrometer adjustment for the x-y-z translations. The micrometers are
Newport SM-50 models. The datasheets for the COTS components are found in 34007-Newport-Crossed
Roller Linear Stages.pdf, 34004-Newport-Dovetail Rail Components.pdf and 34003-Newport-SM_Series
Micrometer.pdf.
Table 14: Camera mount requirements & actual performance specs
Requirement Actual
Resolution: x-axis 7.4 µm 1 µm
Range: z-axis 10 mm ±12.5 mm
Lockable: z-axis
CV CDD
SPEC-0180, Rev A Page 45 of 90
Resolution: y-axis 7.4 µm 1 µm
Range: z-axis 10 mm ±12.5 mm
Lockable: z-axis
Resolution: z-axis 25 µm 1 µm
Range: z-axis 10 mm ±12.5 mm
Lockable: z-axis
Resolution: β rotation 1 arcminute 1 arcsec/° adjusting screw
Range: β rotation ±5° ±6°
Lockable: β rotation
Table 15: Camera mount COTS datasheets
COTS Datasheets for Camera Mount Assy
Newport SM series micrometers 34003-Newport-SM_Series Micrometers.pdf
Newport dovetail rail components 34004-Newport-Dovetail Rail Components.pdf
Newport crossed roller linear stages 34007-Newport-Crossed Roller Linear Stages.pdf
The CV camera is required to image the full 30 or 60 arcsecond image formed by the CV optical system.
In order to properly align the camera to within one pixel accuracy, the x and y micrometer adjustment
must have a minimum increment of 7.4 microns in each axis and lock into place so that it remains stable
at the desired position. The camera stage must also be adjustable in horizontal tilt (tilt about the y-axis) to
allow adjustment of the image plane tilt. The horizontal tilt manual adjustment must have a minimum
increment of 60 arcseconds and a range of at least 5 degrees. The default horizontal tilt angle is -1.30
degrees. Default tilt in the vertical direction is zero but some vertical tilt may be necessary to correct for
optical manufacturing defects, in which case shims will be used for compensation. The z-axis manual
adjustment of the camera stage must have a minimum increment of 25 microns.
A square aperture mask is located just in front of the camera and cooling enclosure. The aperture opening
measures 18.0mm on each side. It can be translated ±1mm in the x and y axes. Slight rotation about the
z-axis is accommodated by adjusting the four opposing set screws accordingly.
5.4 CV CAMERA
We have selected a COTS camera, based on the Truesense Imaging KAI-04070 CCD sensor, as the
camera for the CV. The KAI-04070 provides performance sufficient to meet or exceed all daytime and
nighttime requirements on the CV and cameras based around this sensor cost much less than other
cameras with similar performance.
A complete discussion of the trade study that selected this sensor can be found in DKIST project
document TN-0185 – AO CV Camera Study. We explored two COTS cameras based around this sensor,
the Illunis RMV-4070 and the Imperx Bobcat B2021. We procured a loaner version of the Bobcat B2021
to be tested in-house and confirmed that it meets performance and usability requirements for the WFC
CV. The full acceptance test report can be found in DKIST project document TN-0193 AOCV Camera
Test Report. Due to difficulties with procuring a test model from Illunis, the RMV-4070 was not
evaluated and the Bobcat B2021 has been chosen as the CV camera.
CV CDD
SPEC-0180, Rev A Page 46 of 90
The Bobcat B2021 operates over a gigabit ethernet interface so no frame grabber is needed.
Table 16: Summary of Imperx B2021 camera test report
Test Requirement Test result Pass/Fail Comments
Frame rate
(full frame)
10 fps 12 fps Pass Camera capable of 10-12 fps full
frame over GigE interface
Gain N/A 10.65 e- per DN N/A
Read noise <30 e- rms 17 e- rms Pass
Dark current <10 e-/sec/pix 1.16 e-/sec/pix Pass
Linearity < 2.0% error 0.93% error Pass
Defective pixels 0 dead pixels
<0.1% defective
pixels
0 dead pixels,
0.026% defective
pixels
Pass defective pixels do not affect
imaging performance
Sensor well
depth
>40,000 e- 44,000 e- Pass
Figure 25: B2021 sensor quantum efficiency
CV CDD
SPEC-0180, Rev A Page 47 of 90
6 THERMAL SYSTEMS
6.1 CV CAMERA THERMAL CONTROL
The CV camera, as delivered from the supplier, does not meet the SPEC-0063 requirement for surface
temperature in the coudé room. The camera itself generates approximately 5 W of heat energy while
operating, which will be vented by enclosing the camera in an airtight box and using a facility-provided
vacuum line to draw out the heated air.
This method of thermal management will also be used for the LOWFS and HOAO cameras. A full
discussion of the WFC approach to controlling camera surface temperature as well as test results
demonstrating its efficacy is presented in the HOAO CDD, SPEC-0147.
Figure 26: CV camera mount and thermal enclosure
CV CDD
SPEC-0180, Rev A Page 48 of 90
Figure 27: Detail of CV camera thermal enclosure
CV CDD
SPEC-0180, Rev A Page 49 of 90
7 CV CONTROL SOFTWARE DESIGN
7.1 OVERVIEW
The AO CV software consists of three basic functions: control of the AO CV camera, publishing of the
real time image data to the Bulk Data Transport (BDT) and control of the motorized stages in the CV
optics. The AO CV software will be implemented using the DKIST Common Services Framework as
specified in SPEC-0022, Common Services Framework: Users’ Manual, and will be written according to
DKIST software concepts and requirements as outlined in SPEC-0005, Software and Controls
Requirements, and SPEC-0013, Software Concepts Definition.
Figure 28: AO CV System Context
The AO CV is one of the five subsystems of the Wavefront Correction Control System (WCCS), which is
illustrated above in Figure 28. A context diagram of the AO CV software is illustrated below in Figure
29.
Observatory Control System
(OCS)
Telescope Control System (TCS)
Wavefront Correction Control
System (WCCS)
Limb Tracker (LT)Context Viewer
(CV)
Low-Order Wavefront Sensor
(LOWFS)aO Engine
High Order Adaptive Optics
(HOAO)
CV CDD
SPEC-0180, Rev A Page 50 of 90
Figure 29: AO CV high-level control software context diagram.
The high-level control software is implemented in a hierarchical fashion with a CSF Management
Controller at the top (named after the subsystem it controls, which is common usage in CSF) and two
main branches: one for the control of the Motion Control Subsystem, which includes control of all the
motorized stages, and the other for the control of AO CV camera. The controller in the middle, the
Calibration Sequencer, is responsible for sequencing the AO CV system through its calibration routines.
A block diagram of the Motion Control Subsystem is shown below in Figure 30.
Figure 30: A context diagram for the Motion Control Subsystem of the AO CV control software.
The control of the motorized stages is accomplished using a CSF Management Controller, named the
Mechanism Controller (MC), along with CSF/Base Motion Controllers for each stage where automated
control is required. The use of the MC relieves the top-level AO CV controller from the task of managing
these devices and also allows for the encapsulation of various common mechanical configurations and
CV CDD
SPEC-0180, Rev A Page 51 of 90
any particular sequencing required through a single common interface. The stages control the positioning
of the 30 arc-sec and 60 arc-sec objective lenses with in/out linear stages in x and focus adjustment linear
stages in z. The low-level motion control is implemented using a Delta Tau Power PMAC motion control
system. The CSF/Base software provides the necessary driver support and Motion Controller class to
easily integrate the above devices into the AO CV control system software. It should be noted that each
device controller outputs a status report to the CSF Event Network that is subscribed to by the MC, which
is the reason it shows an Event Network input. It was too crowded to show these event outputs in the
block diagram, so they have been left out. The MC uses these status reports to ascertain the status of each
device in the creation of its summary status event.
The camera will be controlled either using the DKIST Camera Systems Software (CSS) or custom camera
control software that leverages the software to be developed for the HOAO and LOWFS cameras. This is
discussed in more detail in the section on camera control below.
7.2 USE CASES
In describing the use cases for the CV, it is important to understand that the CV is just one component of
the larger WCCS system. It receives commands from the WCCS originated by operator action at the OCS
level or from the WCCS GUI. Technically this makes the operator the “actor” for these use cases, but it is
conceptually simpler to illustrate and discuss these use cases from the perspective that the WCCS is the
actor. During normal operation the CV responds only to commands and configurations sent by the WCCS
(for engineering purposes it can also be controlled from its engineering GUI). Its operational mode is
based on the overall WFC mode of the WCCS, as defined in SPEC-0129, WCCS Operational Concepts
Definition. . The mode is passed down to each WCCS subsystem using the attribute
atst.tcs.wccs.<subsystem>.mode, where <subsystem> represents one of the 5 WCCS subsystems shown
above in Figure 28 (in the case of the Context Viewer, this attribute is atst.tcs.wccs.cv.mode). The seven
WFC modes are: off, idle, calibrate, diffractionLimited, seeingLimitedOnDisk, seeingLimitedCoronal, and
limbTracking. How the CV behaves in these WFC modes is shown in the table below.
WFC Mode Meaning for the AO CV
off The CV subsystem is initialized but is not active.
idle The CV system is initialized and set to its default configuration. The CV
display is updated. CV images may be saved to the DHS upon command.
calibrate The CV system may perform its focus calibration and support the telescope
boresight calibration and other AO system calibrations. The CV display is
updated. CV images may be saved to the DHS upon command.
diffractionLimited The CV camera is running and the CV display is updated. CV images may be
saved to the DHS upon command.
seeingLimitedOnDisk The CV camera is running and the CV display is updated. CV images may be
saved to the DHS upon command.
seeingLimitedCoronal The CV camera is running and the CV display is updated. CV images may be
saved to the DHS upon command.
limbTracking If there is sufficient light, the CV may be used in Limb Tracking mode. As
with the other operational modes, the CV camera is running and the CV
display is updated. CV images may be saved to the DHS upon command.
Table 17: The meaning of the various WFC modes for the AO CV.
CV CDD
SPEC-0180, Rev A Page 52 of 90
The main purpose of the CV is to provide a real-time image of the telescope boresight. It is used for both
visual and automated performance analysis of the AO system. The CV images are also used by the OCS
for the selection of AO Lock Points (this may be done from the WFC Engineering display as well). CV
images may be saved to the DHS on command for engineering purposes. The CV may be used for
alignment and calibration purposes as well, including the support of night time pointing map
measurements and as a pointing reference for the establishment of the heliocentric coordinate system. The
CV is running in almost all of the WFC modes and supports basic startup and shutdown activities. These
use cases are discussed in further detail in this section.
A UML Use-Case diagram for the AO CV is shown below.
Figure 31: AO CV Use case diagram
CV CDD
SPEC-0180, Rev A Page 53 of 90
7.2.1 Startup
The power state of the CV computer is managed through its Intelligent Platform Management Interface
(IPMI) port and sequenced from a script running on the parent WCCS system. The initial power on
command is initiated by the OCS, TCS or from the WFC Engineering GUI by remotely executing a
power sequencing script on the WCCS. The details of this power sequencing process are TBD and will be
documented in TN-0289 WFC System Power Sequencing. Upon power-up, the CV computer will
automatically boot and start any necessary system services. No CSF containers or components have been
deployed yet.
The lifecycle of the WFC system is normally managed by the TCS, but for laboratory and engineering
purposes may also be managed from the WFC Engineering GUIs. The top-level WCCS controller is
managed directly by the TCS or Engineering GUI and the WCCS in turn manages the lifecycles of its
subsystem top-level controllers.
The following basic steps are accomplished to bring up the CV system:
The CV system is powered up as described above
The TCS loads and starts all of the containers used by the WCCS and its subsystems using the
WCCS Deployed Logical Units that have been defined for this purpose. This includes the
container for the CV.
The TCS issues a lifecycle init command to the WCCS which forwards it to the CV subsystem as
well. The CV then loads its components and initializes them. At this point the CSF components
are loaded but are not yet running.
Next, the TCS issues a lifecycle startup command to the WCCS which it forwards to the CV
subsystem. The CV components and controllers execute their startup sequences and transition to
the running state. At this point the CV is running and ready to accept commands and
configurations on its public interface.
During the startup command processing the CV configures the camera to its default settings and
starts publication of image data to the BDT. This allows for image data to be viewed on the GUI
screens as the system is coming up. Note: the camera is configured to free-run and does not
require software or hardware triggers for normal operation.
Finally, the TCS sends a configuration to the WCCS commanding it to the “idle” state. The
WCCS forwards this to the CV as well. The CV commands all of its motors to go through their
indexing/homing sequences and then commands them to their default operating positions.
The CV is now operating normally.
The host computer that runs the Context Viewer software will be specified such that the system will be
operational and ready to receive and act upon commands within 5 minutes of a cold power-off start (the
computer specifications for the WFC System are listed in Section 4.5.5 of SPEC-0178, WFC Common
Items CDD).
7.2.2 Observing Related Modes
The CV is active for all the WFC modes associated with observing (diffraction-limited, seeing-limited on-
disk, seeing-limited coronal, and limb tracking). The WCCS instructs the CV to transition to one of these
modes by sending a CSF configuration containing the WFC mode attribute set to the desired mode. The
objective lenses are moved to their appropriate default positions for particular mode selected. In all of
these modes, the CV camera runs at the default or requested frame rate and exposure time and publishes
image data to the BDT for display at the operator’s console and/or the WFC Engineering GUI. Image data
CV CDD
SPEC-0180, Rev A Page 54 of 90
may be saved to the BDT by sending the appropriate commands to the CV Camera Controller (CC).
Image data will continue to be saved indefinitely until manually stopped by the operator.
7.2.3 Calibrations
The CV supports several types of calibrations: dark, gain, focus, boresight alignment, Strehl calculation,
plate scale, non-automated alignments, night time pointing map updates, and limb finding. Overviews of
each calibration are presented in this section. Detailed discussions of some of the calibrations are
presented later in the section on Use Cases. In general, calibrations are implemented using Python scripts
executed by the Calibration Sequencer. Some calibrations (e.g., boresight) require the use of multiple
WFC subsystems and must be sequenced at the WCCS level. Moreover, some calibrations require the
PA&C to be in a particular configuration. This is accomplished by the OCS commanding the TCS to
configure the PA&C or by the OCS putting the TCS in aoCalibrate mode, which allows the WCCS to
command the PA&C directly. For the purposes of the discussions in the section it does not matter which
method is used and we simply note how the GOS must be configured and assume that it is configured
properly for the particular calibration to be executed. There is also one calibration (gain) that requires the
TCS to perform random steering of the telescope. This is initiated from the OCS. In general, to perform
calibrations the CV must be sent a configuration from the OCS/TCS or from the WCCS or CV
Engineering GUIs with the WFC mode attribute set to “calibrate”. Other parameters supporting the
particular calibration task to be accomplished are also included in the configuration. Additional details are
presented in the section on the Calibration Sequencer.
7.2.3.1 Dark Calibration
The beam must be blocked at the GOS in order to accomplish this calibration. Once the beam is blocked,
the CV performs the following steps:
Sets the CV camera parameters appropriate for recording a dark field
Sets the number of frames to be summed
Turns off dark and gain correction
Sums the raw uncorrected images.
Divides the resulting image sum by the number of frames.
Analyzes the new dark correction array to ensure it valid and has not been modified by offset
level compensation in the camera. An error is returned if the dark distribution is invalid.
Loads the new dark correction array as the current dark correction array.
Saves the new dark correction array in the calibration database.
All the steps of this procedure can be performed within the CV except for blocking the beam.
7.2.3.2 Gain Calibration
Random telescope steering is required in order to accomplish this calibration. Once the random steering is
in progress, the CV performs the following steps:
Sets the number of frames to be summed.
Turns off dark and gain correction
Computes the gain correction array as follows:
o Sums the raw uncorrected images.
o Computes an average from the sum
o Corrects it by the current dark correction array
CV CDD
SPEC-0180, Rev A Page 55 of 90
o Calculates the minimum value of the corrected array to ensure there is no division by
zero. If zero pixels are present, the corrected array is set to all ones and a warning is
logged.
o Computes the reciprocal of the result
o Normalizes the result by the mean of the corrected average.
o The resulting gain distribution is analyzed to ensure there are no outliers beyond a user
defined threshold. An error is returned if the gain distribution is invalid.
Loads the new gain correction array as the current gain correction array.
Saves the new gain correction array in the calibration database.
All the steps of this procedure can be performed within the CV except for the random telescope motion.
7.2.3.3 Focus Adjustment
The focus of the CV is checked and adjusted as needed. A line target (USAF, grid, etc.) must be inserted
at the GOS in order to accomplish this calibration. The CV Focus Calibration uses an iterative search to
maximize the squared image gradient, a criteria shown to repeatably find the best focus position for a
variety of image structures. The CV performs the following steps (see Section 3.5 for more details):
The current objective lens is moved to its default z-axis position, which we call “center”
The step size is set to the default step size
The following steps are iterated:
o The objective lens is moved to position center – step size.
o A dark and gain corrected image is recorded and the squared sum of the image gradients
is computed
o The previous two steps are repeated for lens positions center, and center + step size.
A polynomial fit to the three points is performed and the z position corresponding to the
maximum squared gradient is computed.
If the position of maximum gradient is bracketed by the three points, the new position is used for
center, and step size is divided by two.
If the maximum gradient position is not bracketed, then the end point that is closest to the
computed position is chosen as the new center and the step size is unchanged.
The convergence criteria are checked along with the maximum number of iterations allowed. If
the algorithm has converged or the max iterations have been reached, then go to the next step.
Otherwise, continue iterating the steps above starting from the new position, moving there if
needed.
If the maximum iterations have been reached and the convergence criteria have not been satisfied,
then return an error and log a warning.
If the algorithm converged then set the new position as the default position for the z-axis (updates
the property database).
All the steps of this procedure can be performed within the CV except for inserting the line target at the
GOS.
7.2.3.4 Boresight Alignment
The Boresight Alignment procedure is used to align the boresight of the telescope and uses both the CV
and the pupil sensing capability of the HOAO. A point source is required at the GOS for this calibration.
CV CDD
SPEC-0180, Rev A Page 56 of 90
Because the alignment requires inputs from multiple AO subsystems, the procedure is scripted from the
WCCS level. As part of the procedure, the WCCS requests a centroid measurement from the CV. At the
CV level, the following steps are accomplished:
An average CV image is calculated.
The centroid of the spot is computed using the match filter algorithm described in Section 3.1.
The offset error in arc-sec from the boresight (center of the CV detector) is published in a CSF
event.
The aO Engine subscribes to the event, receives the result, and computes how to adjust M3 and M6 to
center the spot on the CV and the center the pupil in the HOAO (this requires input from the HOAO as
well). The process is repeated until both the spot and the pupil are centered to an acceptable level. These
steps require coordination with other AO subsystems and the TCS subsystems and must be scripted from
the WCCS.
7.2.3.5 Strehl Calculation
The Strehl calculation will be used in the laboratory to verify the proper alignment of the optics and to
compare to the Strehl estimates based on telemetry data from the HOAO. There are no point sources that
are small enough spatially to perform this calculation at the summit, so it is used only in the laboratory.
The following steps are taken:
A point source of sufficient brightness is placed in the beam and the CV camera parameters are
adjusted until the desired spot intensity is achieved.
CV images are recorded and the calculation is performed as described in Section 3.3.
A matplotlib plot showing the results will be generated and saved, as well as the results of the
calculation will be written to the log database.
Once the source has been set up, the remainder of the procedure can be scripted form the CV.
7.2.3.6 Plate Scale Calibration
The plate scale calibration will be run as part of the routine calibration set. A line grid target must be
placed in the beam at the GOS for this calibration. The procedure outlined in Section 3.3 is executed in a
Python script. The procedure is quite complicated, so the steps are not listed here. With the exception of
placing the line grid target into the beam, the entire procedure can be scripted within the CV.
7.2.3.7 Non-Automated Calibrations
A number of the alignments for the AO system may not easily be automated, or may be performed so
infrequently that it is not worth automating them. These are most likely adjustments initiated by an
operator at the WCCS or CV Engineering GUIs, although they may require configuration of the PA&C as
well. The CV will likely be used to support these calibrations. The following steps are typically
performed:
The PA&C is configured for the calibration source or target as required.
The AO system is placed in calibrate mode.
The various AO optical devices are configured as desired for the calibration to be performed.
These actions are performed from the WCCS Engineering GUI.
Various measurements are performed and data are taken and analyzed (including CV images).
CV CDD
SPEC-0180, Rev A Page 57 of 90
The appropriate optical devices are adjusted as required. These actions are performed from the
WCCS Engineering GUI.
These steps are repeated until the desired level of alignment is achieved.
At operator request, the new positions of the affected devices are saved as new default or named
positions.
The new positions of the affected devices are saved as the new default and/or named position values for
each device.
7.2.3.8 Night Time Pointing Map Updates
The CV will be used to assist in the computation of night time pointing map updates. For this application,
the CV camera must be configured with the appropriate exposure time and frame rate for night time
operation to achieve a good SNR on bright stars. Dark and gain corrections must be applied as well. The
centroid capability used in the boresight calibration will be reused to support this feature. The steps to be
taken are expected to be something like this, sequenced from the TCS:
The TCS configures the WCCS to be in idle mode
The TCS instructs the AO Engine to perform an aoZero to clear all the AO offsets used by M1,
M2, M3 and M6
The TCS instructs the CV to configure the camera for night time operation
The TCS moves the telescope to a bright star
The TCS requests the CV to perform a centroid calculation averaging over a specified number of
image frames
The CV performs the centroid calculation and publishes the offset from the boresight in a CSF
event
The TCS subscribes to the event and receives the offset information
This process is repeated until the desired set of stars has been processed
The array of offsets are used to compute new pointing kernel parameters
At the CV level, the following steps are taken:
The camera is configured for night time operation (this is only done once)
An average CV image is calculated using the requested number of frames
The centroid of the spot is computed and the offset error in arc-sec from the boresight is
published in a CSF event
7.2.3.9 Limb Finding
The CV will be used to support updates to the TCS pointing when bringing the telescope up each
morning. This involves moving the telescope to several different limb positions around the sun (e.g., N, S,
E, W) and calculating the position of the limb in a CV image for each case. The position of the limb is
calculated by performing a Canny edge detection followed by a Hough line transform to obtain a
parametric description of the line representing the edge of the limb relative to the boresight. The x and y
position of the orthogonal vector from the boresight to the line is returned to the TCS in a CSF event. The
procedure is described in detail in Section 3.2. The steps to be taken are expected to be something like
this, sequenced from the TCS:
The TCS configures the WCCS to be in idle mode
CV CDD
SPEC-0180, Rev A Page 58 of 90
The TCS instructs the AO Engine to perform an aoZero to clear all the AO offsets used by M1,
M2, M3 and M6
The TCS points the telescope at a desired limb position
The TCS requests the CV to perform limb finding on a CV image
The CV performs the limb finding algorithm and publishes the result in a CSF event
The TCS subscribes to the event and receives the limb position information
This process is repeated until all the desired limb positions have been processed
The limb positions calculated by the CV are used by the TCS to update its pointing reference
7.2.4 Shutdown
The shutdown of the CV is accomplished using the following steps:
A configuration with WFC mode attribute set to “off” is sent from the OCS, TCS or WCCS
Engineering GUI. As part of the transition to off the CV motors are all moved to their “stow”
positions
The TCS sends the lifecycle commands shutdown, uninit, and unload to the WCCS, which
forwards them to the CV (this may also be initiated from the WCCS engineering GUIs). During
these lifecycle transitions the following steps are taken:
o The image acquisition from the CV camera and all publications to the BDT are halted
o All events published by the CV are halted.
o All CV event subscriptions are cancelled
o All software resources in use are freed
The TCS executes the remote power shutdown script on the WCCS, which in response executes
the appropriate power shutdown sequence for the CV.
At this point the CV is powered down and inoperative.
7.3 DETAILED DESIGN
7.3.1 CV Controller
The CV Controller is the top-level controller for the CV sub-system and is responsible for managing the
overall operation of the CV subsystem. It is an extension of the CSF/Base Java Management Controller
class. The CSF device name for the CV controller is atst.tcs.wccs.cv and the controller itself is referred to
as the CV Manager Controller.
The typical use case for the CV is any of the normal observing modes, with the possible exception of limb
tracking, where its use is dependent on how much light is available. In these modes the CV is designed to
be used with a minimum of operator interaction. The operator typically specifies only the WFC mode and
any particular calibrations to be performed. The remainder of the parameters required to operate the CV
are downloaded from the CSF Property Database during startup. However, all parameters required to
operate the CV are accessible through its public interface via the CV Engineering GUI.
7.3.1.1 Attributes
The following attributes are received and acted upon by the CV controller.
CV CDD
SPEC-0180, Rev A Page 59 of 90
Name Type Comment
atst.tcs.wccs.cv
.mode String The current WFC mode
.calibrate String The specific calibration task to be performed
.calibCtrl.<attribute name> Varies Attributes for the Calibration Sequencer
.mc.<attribute name> Varies Attributes for the Mechanism Controller subsystem of the
CV
.cc.<attribute name> Varies Attributes for CV Camera Controller
7.3.1.1.1 .mode
Data Type: String
Units: N/A
Valid Values: off | idle | calibrate | diffractionLimited | seeingLimitedOnDisk | seeingLimitedCoronal
| limbTracking
Default Value: None
The .mode attribute represents the current operational mode of the WCCS and is used to control the
behavior of the CV.
7.3.1.1.2 .calibrate
Data Type: String
Units: N/A
Valid Values: dark | gain | boresight | focus | manual | nightTime | limbFinding | none
Default Value: None
The .calibrate attribute is used to indicate what particular type of calibration is to be performed. If this
attribute is present, the entire configuration is submitted to the Calibration Sequencer for processing if a)
the WFC mode is set to calibrate (normal WFC calibrations) or b) the WFC mode is set to idle and the
.calibrate attribute is set to “nightTime” or “limbFinding” (for TCS applications).
7.3.1.1.3 .calibCtrl.<attribute name>
These are attributes for the Calibration Sequencer for the CV system. These attributes are forwarded by
the CV controller directly to the Calibration Sequencer.
7.3.1.1.4 .mc.<attribute name>
These are attributes for the Mechanism Controller subsystem of the CV and are intended for the MC itself
or for one of the devices managed by the MC. These attributes are forwarded by the CV controller
directly to the MC.
CV CDD
SPEC-0180, Rev A Page 60 of 90
7.3.1.1.5 .cc.<attribute name>
These are attributes are for the CV Camera Controller and are used to configure the CV camera. These
attributes are forwarded by the CV controller directly to the CC.
7.3.1.2 Properties
All of the attributes used in the public interface for the CV will be backed by properties in the property
database. In addition there are many other properties that are not public that are used by the system. All of
the properties will be documented as part of the final user documentation for the system.
7.3.1.3 Sequencing
In general, all the run-time specific parameters for the CV will be sent from the Observatory Control
System (OCS) to the Telescope Control System (TCS) and then on to the WCCS and CV. Moreover,
these parameters are all sent at once in a single CSF configuration. Because of this, the CV must know
how to properly sequence these parameters to its components. In general, the following rules will apply:
If the WCCS .mode attribute is set to calibrate and the CV .calibrate attribute is present, the
entire configuration is sent to the Calibration Sequencer for processing. The particular calibration
script to be executed is responsible for sequencing the various actions in the proper order.
In addition, to support night time pointing map calibrations and daytime limb finding for
coordinate system initialization, the entire configuration is sent to the Calibration Sequencer for
processing if the WCCS .mode attribute is set to idle and the CV .calibrate attribute is present
and set to nightTime or limbFinding.
If no specific calibration is to be processed, parameters for configuring the motorized stages and
the CV camera are sent to the MC and the camera controller, respectively.
7.3.2 Camera Controller
The Camera Controller (CC) implements the functionality required to configure the CV camera, retrieve
dark and gain images from the Bulk Data Store (BDS), perform dark and gain corrections on the real-time
image stream from the camera and publish image data to the BDT. The control of the camera is
implemented using a low level C++ interface and the Pleora camera driver supplied by the manufacturer.
The low level interface is wrapped with JNI and exposes a Java interface that is used by the CC. The CC
implements a separate thread that performs the dark and gain corrections. Because the correction thread is
part of the Camera Controller, it receives the camera images directly from camera interface. After
performing the dark and gain corrections it passes the resulting images on to both the Calibration
Sequencer and the BDT network. The correction thread is also responsible for turning on/off the flag
indicating that the data should be saved to the BDT. Moreover, the CC implements a dedicated thread to
perform automatic exposure time adjustment to ensure we are using an appropriate percentage of the
CCD well depth. The auto exposure control is user selectable and has several parameters to control its
operation (see SPEC-0179, Section 5.8 for details on the algorithm used). The passing of image data to
the calibration sequencer is done using a pass box, which is a synchronized queue of size one whose
contents may be overwritten by the source if the subscriber has not yet used the data. The BDS interface
to the CC is used for the downloading of dark and gain images. The CC is implemented using an
extension of the CSF/Base Java Hardware Controller class.
CV CDD
SPEC-0180, Rev A Page 61 of 90
Figure 32: A block diagram illustrating the CV Camera Controller design. The box with the dashed outline indicates that
the dark and gain corrections thread and the auto exposure adjustment thread are part of the Camera Controller.
7.3.2.1.1 Attributes
The following attributes are received and acted upon by the CC controller for the design based on a
custom CSF controller.
Name Type Comment
atst.tcs.wccs.cv.cc
.ldDarkName String The name of the dark image to be used
.ldDarkVersion String The version ID of the dark image to be used
.ldGainName String The name of the gain image to be used
.ldGainVersion String The version ID of the gain image to be used
CV CDD
SPEC-0180, Rev A Page 62 of 90
.darkCorrect Boolean Turns dark correction on/off
.gainCorrect Boolean Turns gain correction on/off
.publishData Boolean Turns the publishing of data to the BDT on/off
.saveData Boolean Turns the saving of data to the BDT on/off
.configSetup String Instructs the CC to setup the camera with its default
parameters for either daytime or night time use
.frameRate Float Sets the frame rate in Hz
.expTime Int Sets the exposure time in µsec
.expControl String The camera exposure control method
.expUpdate Real The time between exposure updates
.expMin Int The minimum count threshold
.expMax Int The maximum count threshold
7.3.2.1.1.1 .ldDarkName
Data Type: String
Units: N/A
Valid Values: N/A
Default Value: N/A
The .ldDarkName attribute is used to specify the name of the existing dark image to be downloaded from
the calibration store for use in the dark correction.
7.3.2.1.1.2 .ldDarkVersion
Data Type: String
Units: N/A
Valid Values: N/A
Default Value: N/A
The .ldDarkVersion attribute is used to specify the unique version ID of the existing dark image to be
downloaded from the calibration store for use in the dark correction.
7.3.2.1.1.3 .ldGainName
Data Type: String
Units: N/A
Valid Values: N/A
Default Value: N/A
CV CDD
SPEC-0180, Rev A Page 63 of 90
The .ldGainName attribute is used to specify the name of the existing gain image to be downloaded from
the calibration store for use in the gain correction.
7.3.2.1.1.4 .ldGainVersion
Data Type: String
Units: N/A
Valid Values: N/A
Default Value: N/A
The .ldGainVersion attribute is used to specify the unique version ID of the existing gain image to be
downloaded from the calibration store for use in the gain correction.
7.3.2.1.1.5 .darkCorrect
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: True
The .darkCorrect attribute is used to indicate whether dark corrections are to be performed or not.
7.3.2.1.1.6 .gainCorrect
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: True
The .gainCorrect attribute is used to indicate whether gain corrections are to be performed or not.
7.3.2.1.1.7 .publishData
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: False
The .publishData attribute is used to indicate whether image data should be published to the BDT or not.
The WFC system shares a camera line with the CryoNIRSP instrument (which also blocks the light beam
to the WFC) and should not publish to the BDT when the CryoNIRSP is in use. This attribute takes
CV CDD
SPEC-0180, Rev A Page 64 of 90
precedent over the .saveData attribute. Even if the saving of data is turned on, if this attribute is set to
false, no data will be published, and therefore, no data will be saved.
7.3.2.1.1.8 .saveData
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: False
The .saveData attribute is used to indicate whether image data published to the BDT should be saved or
not. The saving of data occurs in the correction thread. Once the saving of data has been started it will
continue until a configuration is received by the CC containing the .saveData attribute set to false.
7.3.2.1.1.9 .configSetup
Data Type: String
Units: N/A
Valid Values: day | night
Default Value: false
The .configSetup attribute is used to indicate that the CC should load the default camera parameters
required for day or night time operation, as specified by the value of the attribute, from the property
database and use them to configure the camera.
7.3.2.1.1.10 .frameRate
Data Type: Real
Units: Frames/sec
Valid Values: 1 – 16.65
Default Value: 10
The .frameRate attribute is used to get or set the frame rate of the CV camera. Note that the frame rate
and exposure time are inter-dependent and must be set to mutually compatible settings. When a frame rate
change is requested, the Camera Controller checks to see if the new frame rate is compatible with the
current exposure time. If necessary, the exposure time will be truncated to the maximum allowed for the
new frame rate.
7.3.2.1.1.11 .expTime
Data Type: Int
Units: µsec
Valid Values: 1 – 1.6e7 µsec
CV CDD
SPEC-0180, Rev A Page 65 of 90
Default Value: TBD
The .expTime attribute is used to set the exposure time of the camera. Note that the frame rate and
exposure time are inter-dependent and must be set to mutually compatible settings. This attribute will be
checked to ensure it does not exceed the maximum allowable exposure time for the current frame rate and
will be clipped to the maximum value if necessary.
7.3.2.1.1.12 .expControl
Data Type: String
Units: Choice
Valid Values: auto | manual
Default Value: manual
The .expControl attribute is used to turn the automatic exposure control on and off.
7.3.2.1.1.13 .expUpdate
Data Type: Real
Units: Seconds
Valid Values: 1 - 300
Default Value: TBD
The .expUpdate attribute determines the time in seconds between exposure updates.
7.3.2.1.1.14 .expMin
Data Type: Int
Units: DN
Valid Values: 0 – 4094, expMin < expMax
Default Value: 800 (~20% of well depth)
The .expMin attribute is the lower bound on the acceptable level of maximum average intensity in the
reference subaperture. When the maximum average intensity drops below this level, the exposure time
will be increased.
7.3.2.1.1.15 .expMax
Data Type: Int
Units: DN
Valid Values: 1 – 4095, expMax > expMin
Default Value: 3300 (~80% of well depth)
CV CDD
SPEC-0180, Rev A Page 66 of 90
The .expMax attribute is the upper bound on the acceptable level of maximum average intensity in the
reference subaperture. When the maximum average intensity rises above this level, the exposure time will
be decreased.
7.3.2.2 Properties
All of the attributes used in the public interface for the Camera Controller will be backed by properties in
the property database. In addition there are many other properties that are not public that are used by the
system. All of the properties will be documented as part of the final user documentation for the system.
The CC will be implemented with a maximum of at least two CSF action threads to allow ample
resources for both configuring camera parameters and loading or saving files to the calibration store. Note
that these CSF threads are in addition to the special thread used to perform the dark and gain corrections
(which is not a CSF thread).
7.3.3 Mechanism Controller
The Mechanism Controller (MC) is responsible for managing all the motion control devices in the CV. It
relieves the burden of the top-level CV controller of managing these resources. The Mechanism
Controller is implemented as an extension of the CSF/Base Java ManagementController class, which is
designed to automatically manage the control functions and lifecycles of a number of subordinate
controllers. It also allows for the implementation of custom motion sequencing or encapsulation of
custom configurations managed through a single interface. For example, by commanding the MC to go to
a hypothetical configuration called “Configuration_A”, only a single CSF attribute need be sent to the
MC. The MC then translates the name “Configuration_A” into the appropriate set of commands to its
subordinate motion controllers to move them to the desired positions, allowing a single attribute to be
used to indicate the desired configuration of all the motorized stages.
All values used to communicate with the MC are maintained in the same data format as those used in the
motors so that type conversion errors do not reduce the native accuracy of the motors.
As of this writing, there are two special functions that have been identified: automatically moving the
objective lenses in response to the selection of a desired field of view, and the ability to save the current
position of a device as either the default position or as a named position. Custom methods will be added
to the MC to implement these capabilities. These functions are described in further detail below.
The CSF device name for the MC is atst.tcs.wccs.cv.mc. The table below describes the naming scheme
for the MC and its subordinate controllers. Each subordinate controller is discussed in detail below.
Name Description
atst.tcs.wccs.cv.mc
.fov The field of view selection
.savePosition Update the Property DB using the current position of a
device
.objLens30X 30” Objective lens horizontal position
.objLens30Z 30” Objective lens axial (focus) position
.objLens60X 60” Objective lens horizontal position
.objLens60Z 60” Objective lens axial (focus) position
CV CDD
SPEC-0180, Rev A Page 67 of 90
7.3.3.1 Objective lens positioning based on FOV selection
While the ability to command each objective lens separately is needed as a lower level control capability,
during operations only one lens is used at a time while the other lens is out of the beam. This is how the
two separate FOVs are achieved. When the 30” FOV is selected, the 30” objective lens is positioned in
the beam and the 60” objective lens is moved out of the beam. When the 60” FOV is selected, the
opposite takes place. We automate this functionality using an MC attribute for the FOV. When the MC
receives this attribute it knows to move each of the objective lenses to its proper position based on the
particular FOV selected. The attribute for this functionality is atst.tcs.wccs.cv.mc.fov.
7.3.3.1.1 .fov
Data Type: Int
Units: Size of the FOV in arc-sec
Valid Values: 30 | 60
Default Value: 30
7.3.3.2 Saving the current position of a device
The MC implements the capability to update the Property DB information for a selected device and
named position. This functionality will be used during alignments and calibrations to update the defined
positions as needed. The functionality is invoked using the .savePosition attribute, which is a unique
string indicating the device name and the particular named position to be updated (“default” is a named
position) . A special method will be added to the MC to implement this capability.
7.3.3.2.1 .savePosition
Data Type: String[]
Units: N/A
Valid Values: objLens30XIn | objLens30XOut | objLens30ZDefault | objLens60XIn objLens60XOut
| objLens60ZDefault
Default Value: None
7.3.3.3 Properties
All of the attributes used in the public interface for the Mechanism Controller will be backed by
properties in the property database. In addition there are many other properties that are not public that are
used by the system. All of the properties will be documented as part of the final user documentation for
the system.
Two of the attributes used in the mechanism controller are .objLens30PlateScale and
.objLens60PlateScale. These attributes are used to store the values of the 30-arcsecond plate scale and the
60-arcsecond plate scale. They can be modified manually through the CV Property Editor or by a Python
script, such as the plate scale calibration script.
The MC will be implemented using at least 2 CSF action threads so that each motor may be commanded
independently.
CV CDD
SPEC-0180, Rev A Page 68 of 90
7.3.4 Motion Controllers
All motion controllers will be implemented using the Java MotionController class provided by the
CSF/Base software. The MotionController class provides a standard interface for motion control and has
driver support for the Delta Tau PPMAC system. It provides support for absolute moves, relative moves,
named positions, and automatic conversion between user units and the underlying raw units of each stage.
At the time of this writing, the raw units have not been defined for these stages; they will be determined
during the implementation of the motion control system. The descriptions below discuss the absolute
position and named position attribute details for each device. The absolute position attribute allows for
positioning of the device anywhere in its range, while the named position attribute allows for positioning
the device to one or more pre-defined positions with a user-assigned name. The named positions represent
the default or typical calibrated user positions for these devices.
The DeltaTau support uses the DeltaTauConnection and DeltaTauChannel classes in CSF/Base to connect
to the underlying PPMAC hardware and control the various motorized stages. If special indexing is
required for any of the stages, the DeltaTauConnection class will be extended to override the index()
method as needed. Moreover, special PPMAC motion programs may be required to implement custom
sequencing to implement the indexing. The need for this will be determined on a case by case basis as we
integrate the motion control system for the CV.
WFC motion control design is detailed in the WFC Common Items CDD, SPEC-0178. As discussed in
the Common Items CDD, the CV will share the use of a single Delta Tau PPMAC chassis with the other
WCCS subsystems. A single CPU will be used to support the motion control software for all the movable
devices in the entire AO system. Standard CSF/Base Motion Controllers are used to support each device.
The remainder of this section describes the devices controlled by the MC. The full attribute names for
these devices are found by combining the fully qualified device name as given in the paragraph with
either a .pos or .namedPos suffix. For example, to set the absolute position of the 30” objective lens
along the x axis, the full attribute name is: atst.tcs.wccs.cv.mc.objLens30X.pos.
7.3.4.1 30” Objective Lens
Each objective lens has two separate axes of motion combined on a single mount. The x motor axis
represents the lateral position of the lens with respect to the beam path, while the z axis represents the
position of the lens along the beam path. The CSF device names for these stages for the 30” objective lens
are atst.tcs.wccs.cv.mc.objLens30X and atst.tcs.wccs.cv.mc.objLens30Z, respectively. The attributes
defined for these stages are shown below.
7.3.4.1.1 objLens30X.pos
Data Type: Real
Units: mm
Valid Values: 0 – TBD
Default Value: None
7.3.4.1.2 objLens30X.namedPos
Data Type: String
Units: N/A
Valid Values: Default | In | Out
CV CDD
SPEC-0180, Rev A Page 69 of 90
Default Value: Default
7.3.4.1.3 objLens30Z.pos
Data Type: Real
Units: mm
Valid Values: 0 – TBD
Default Value: None
7.3.4.1.4 objLens30Z.namedPos
Data Type: String
Units: N/A
Valid Values: Default
Default Value: Default
7.3.4.2 60” Objective Lens
The 60” objective lens has attribute definitions that are identical to the attributes used for the 30”
objective lens. The CSF device names for these stages for the 60” objective lens are
atst.tcs.wccs.cv.mc.objLens60.x and atst.tcs.wccs.cv.mc.objLens60.z, respectively. The attributes
defined for these stages are shown below.
7.3.4.2.1 objLens60X.pos
Data Type: Real
Units: mm
Valid Values: 0 – TBD
Default Value: None
7.3.4.2.2 objLens60X.namedPos
Data Type: String
Units: N/A
Valid Values: Default | In | Out
Default Value: Default
7.3.4.2.3 objLens60Z.pos
Data Type: Real
Units: mm
CV CDD
SPEC-0180, Rev A Page 70 of 90
Valid Values: 0 – TBD
Default Value: None
7.3.4.2.4 objLens60Z.namedPos
Data Type: String
Units: N/A
Valid Values: Default
Default Value: Default
7.3.4.3 Motion Controller Properties
The CSF properties associated with the CV Motion Controllers will be identified and documented during
implementation. They will include the following:
Default and named position properties for each stage.
Any properties required to configure the motion controller for normal operation: units, range,
limits, etc.
7.3.5 Calibration Sequencer
The Calibration Sequencer is responsible for sequencing the CV through the various steps required to
perform calibrations. Calibrations are performed when the top-level CV controller receives a CSF
configuration containing both the atst.tcs.wccs.cv.mode attribute set to “calibrate” and the
atst.tcs.wccs.cv.calibrate attribute indicating the particular calibration to be performed. The CV
controller will immediately forward the configuration to the Calibration Sequencer for execution. The
Calibration Sequencer will execute the proper procedures based on the particular calibration task
identified in the calibrate attribute. The controller may submit various commands through CSF
configurations to the MC and the CC to cause them to achieve a desired state at any point in the
procedure. The Calibration Sequencer also uses the Image Pass Box described earlier to receive dark and
gain corrected images for any processing required by a particular calibration.
The Calibration Sequencer must also support the specialized TCS applications for night time pointing
map calibrations and daytime coordinate system initialization. However, the WCCS and all its subsystems
will be in idle mode for these applications. In order to send configurations for these two applications
directly to the Calibration Sequencer, the following rule is observed: when the incoming configuration
contains the atst.tcs.wccs.cv.mode attribute set to “idle” and the atst.tcs.wccs.cv.calibrate attribute set to
either “nightTime” or “limbFinding”, the CV Controller will send the configuration directly to the
Calibration Sequencer for processing.
The Calibration Sequencer will be implemented using an extension of the CSF Java
ScriptInterpretingController which will automatically download Python scripts from the script database to
sequence the calibrations.
7.3.5.1 Attributes
The following attributes are received and acted upon by the Calibration Sequencer. During development
we may add additional attributes for some of the commonly used parameters used in the various
calibration routines, as needed.
CV CDD
SPEC-0180, Rev A Page 71 of 90
Name Type Comment
atst.tcs.wccs.cv
.calibrate String The name of the particular calibration task to be
accomplished
atst.tcs.wccs.cv.calibCtrl
.mode String The current WFC mode
.scriptName String The name of the script to be downloaded from the script
database
.scriptId String The id of the script to be downloaded from the script
database
.refPsfId String The ID of the reference image to download from the
Bulk Data Store
.centroidNumImages Int The number of CV images to accumulate when
computing the centroid.
.numImages Int The number of CV images to accumulate when
computing dark and gain calibration images
.focusNumSteps Int The maximum number of steps to be used in the focus
calibration
.focusStepSize Float The size of the focus change used in the focus calibration
.logEvents Boolean Used to indicate whether the .centroid and .limbPosn
events are to be logged
.saveDark Boolean Triggers saving the new dark as the default dark.
.saveGain Boolean Triggers saving the new gain as the default gain.
7.3.5.1.1 .calibrate
Data Type: String
Units: N/A
Valid Values: dark | gain | boresight | focus | manual | nightTime | limbFinding
Default Value: None
The .calibrate attribute is used to indicate the particular type of calibration is to be performed. The value
of the attribute may also be used to load the default script to be run for the specified calibration task if the
.scriptName and .scriptVersion attributes are not specified.
7.3.5.1.2 .mode
Data Type: String
Units: N/A
CV CDD
SPEC-0180, Rev A Page 72 of 90
Valid Values: off | idle | calibrate | diffractionLimited | seeingLimitedOnDisk | seeingLimitedCoronal
| limbTracking
Default Value: None
The .mode attribute represents the current operational mode of the WCCS and is used to control the
behavior of the CV.
7.3.5.1.3 .scriptName
Data Type: String
Units: N/A
Valid Values:
Default Value: None
The .scriptName attribute contains the name of the Python script to be downloaded from the script
database and run to execute the desired calibration procedure. A combination of the script category (the
controller name), script name and script ID form a primary key that is used to identify and download the
script from the script database for execution.
7.3.5.1.4 .scriptVersion
Data Type: String
Units: N/A
Valid Values:
Default Value: None
The .scriptVersion attribute contains the unique ID of the Python script to be downloaded from the script
database and run to execute the desired calibration procedure. A combination of the script category (the
controller name), script name and script ID form a primary key that is used to identify and download the
script from the script database for execution.
7.3.5.1.5 .refPsfId
Data Type: String
Units: N/A
Valid Values: seeLimit | diffLimit | seeLimit | pinhole | invPinhole | pinhole
Default Value: None
The .refPsfId attribute contains the ID of the reference PSF to be downloaded from the Bulk Data Store
for use in the centroid calculations performed by the calibration scripts.
7.3.5.1.6 .centroidNumImages
Data Type: Integer
CV CDD
SPEC-0180, Rev A Page 73 of 90
Units: N/A
Valid Values: 1-1000
Default Value: 1
The .centroidNumImages attribute specifies the number of raw images to be accumulated when
computing the centroid.
7.3.5.1.7 .numImages
Data Type: Integer
Units: N/A
Valid Values: 1-1000
Default Value: 100
The .numImages attribute specifies the number of raw images to be accumulated when computing dark
or gain calibration images.
7.3.5.1.8 .focusNumSteps
Data Type: Integer
Units: N/A
Valid Values: 1-10
Default Value: 5
The .focusNumSteps attribute specifies the maximum number of steps to be taken in the automated focus
calibration algorithm.
7.3.5.1.9 .focusStepSize
Data Type: Float
Units: mm
Valid Values: TBD
Default Value: TBD
The .focusStepSize attribute specifies the size in mm of an adjustment step in focus (z) to be used in the
automated focus calibration algorithm.
7.3.5.1.10 .saveDark
Data Type: Boolean
Units: N/A
Valid Values: True | False
CV CDD
SPEC-0180, Rev A Page 74 of 90
Default Value: False
The .saveDark attribute triggers the Calibration Sequencer to save the newest captured dark image as the
default dark image. The default dark image will be used for dark corrections.
7.3.5.1.11 .saveGain
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: False
The .saveGain attribute triggers the Calibration Sequencer to save the newest captured gain image as the
default gain image. The default gain image will be used for gain corrections.
7.3.5.1.12 .logEvents
Data Type: Boolean
Units: N/A
Valid Values: True | False
Default Value: False
The .logEvents attribute is used to indicate whether the atst.tcs.wccs.cv.centroid and
atst.tcs.wccs.cv.limbPosn are to be logged. CSF does not provide automatic logging of events, so the
logging is accomplished by the Calibration Sequencer by using the CSF Archive Service to record the
attributes posted to an event. The archive service is called immediately after the posting of an event.
7.3.5.2 Properties
All of the attributes used in the public interface for the Calibration Sequencer will be backed by properties
in the property database. In addition there are many other properties that are not public that are used by
the system. All of the properties will be documented as part of the final user documentation for the
system.
7.3.6 Events Published by the CV and its components
7.3.6.1 CV Controller Events
The top-level CV controller will publish the following general status event.
Name Rate Comment
atst.tcs.wccs.cv
.cStatus 1 Hz A general CV status event
CV CDD
SPEC-0180, Rev A Page 75 of 90
7.3.6.1.1 .cStatus
This event reports the general status of the Context Viewer. The attributes are listed in the table below.
Attribute Name Type Units Range Comment
cMode String N/A
off | idle | calibrate |
diffractionLimited |
seeingLimitedOnDisk |
seeingLimitedCoronal |
limbTracking
The current mode of the CV
Status String N/A The CV camera status
Inpos Boolean N/A True | False The CV in-position status
framerate Int Hz 1-17 The camera frame rate
expTime Int µsec 2 – 106 The camera exposure time
avgCounts Float DN The average count value
darkCorrect Boolean N/A True | False Whether dark correction is enabled or
not
gainCorrect Boolean N/A True | False Whether gain correction is enabled or
not
saveData Boolean N/A True | False Whether data is being saved to the
BDT or not
publishData Boolean N/A True | False Whether data is being published to
the BDT or not
configSetup String N/A Day | Night What basic configuration the system
is using, day or night
7.3.6.2 Camera Controller Events
The following events and data are sent from the CV CC.
Name Rate( Hz) Comment
atst.tcs.wccs.cv.cc
.cStatus 1.0 The general status of the CV camara in a single status event
7.3.6.2.1 .cStatus
Attribute Name Type Units Range Comment
cMode String N/A
off | idle | calibrate |
diffractionLimited |
seeingLimitedOnDisk |
seeingLimitedCoronal |
The current mode of the CV
CV CDD
SPEC-0180, Rev A Page 76 of 90
limbTracking
Status String N/A The camera status
Inpos Boolean N/A True | False The camera in-position status
framerate Int Hz 1-17 The camera frame rate
expTime Int µsec 2 – 106 The camera exposure time
currentTemperature Float ºC The internal camera temperature
avgCounts Float DN The average count value
darkCorrect Boolean N/A True | False Whether dark correction is enabled
or not
gainCorrect Boolean N/A True | False Whether gain correction is enabled
or not
saveData Boolean N/A True | False Whether data is being saved to the
BDT or not
publishData Boolean N/A True | False Whether data is being published to
the BDT or not
configSetup String N/A Day | Night What basic configuration the
system is using, day or night
7.3.6.3 Mechanism Controller Events
The following events and data are sent from the CV MC.
Name Rate( Hz) Comment
atst.tcs.wccs.cv.mc
.cStatus 1.0 The general status of the CV mechanisms in a single status
event
7.3.6.3.1 .cStatus
Attribute Name Type Units Range Comment
cMode String N/A
off | idle | calibrate |
diffractionLimited |
seeingLimitedOnDisk |
seeingLimitedCoronal |
limbTracking
The current mode of the CV
inpos Boolean N/A True | False The camera in-position status
fov Int arcsec 30 | 60 The current field of view
objLens30Pos Float[] mm TBD The absolute position of the 30
arcsec objective lens in X, Z
CV CDD
SPEC-0180, Rev A Page 77 of 90
objLens60Pos Float[] mm TBD The absolute position of the 60
arcsec objective lens in X, Z
plateScale Float arcsec/pixel The current CV plate scale
7.3.6.4 CV Calibration Sequencer Events
The Calibration Sequencer will publish the following events.
Name Rate Comment
atst.tcs.wccs.cv
.centroid On request The centroid position of the spot off of the boresight
.limbPosn On request The orthogonal distance to the limb from the boresight
7.3.6.4.1 atst.tcs.wccs.cv.centroid
Attribute Name Type Units Range Comment
centroid Real[2] Arc-sec N/A A 2-element vector containing the results of
a centroid computation
wci:timestamp String The timestamp for the wciWatch data
wci:tcsDmdPos Real[3] The current TCS demand position
wci:coudeDmdAngle Real Degrees The current coudé demand angle
wci:tcsInPosition Boolean The TCS in position status
wci:tcsCurPos Real[3] The TCS current position
wci:coudeCurAngle Real Degrees The coudé current position
wci:offsets Real[3] Arc-sec The current TCS offsets
This event reports the centroid position of a single spot in the CV image in arc-seconds off the telescope
boresight in x and y in the WFC coordinate system. It also includes a success Boolean and an
errorMessage string, which is only set if success is false. This event may be used to support both
boresight calibration and night time pointing. The current TCS position information from the CSF utility
WciWatch is appended to the centroid data for use in any required coordinate transformations. These
attributes are defined in TN-0088, Base Software for Control Systems.
7.3.6.4.2 atst.tcs.wccs.cv.limbPosn
Attribute Name Type Units Range Comment
limbPos Real[2] Arc-sec N/A A 2-element vector containing the results of
a limb finding computation
success Boolean Indicates if the limb finding calculation was
successful or not
CV CDD
SPEC-0180, Rev A Page 78 of 90
errorMessage String An error message with details on any failure
wci:timestamp String The timestamp of the wciWatch data
wci:tcsDmdPos Real[3] The current TCS demand position
wci:coudeDmdAngle Real Degrees The current coudé demand angle
wci:tcsInPosition Boolean The TCS in position status
wci:tcsCurPos Real[3] The TCS current position
wci:coudeCurAngle Real Degrees The coudé current position
wci:offsets Real[3] Arc-sec The current TCS offsets
This event reports the orthogonal distance from the boresight to the limb in arc-sec in the WFC coordinate
system. This event is only used to support the daytime initialization of the telescope coordinate system. It
also includes a success Boolean and an errorMessage string, which is only set if success is false. The
current TCS position information from the CSF utility WciWatch is appended to the centroid data for use
in any required coordinate transformations. These attributes are defined in TN-0088, Base Software for
Control Systems.
7.3.7 Events subscribed to by the CV and its components
The CV does not subscribe to any events outside of its own sub-system. The MC will subscribe to its own
motion controllers’ status events.
7.3.8 Headers
The CV is not required to respond to any header requests.
7.3.9 Interlocks
The CV does not respond to any Global Interlock System interlock events. The main WCCS controller
will respond to GIS interlock events, if required, and direct the WCSS subsystems to respond as needed.
7.3.10 Logging
General status logging to the log database is accomplished automatically by CSF for the following
categories of events:
lifecycle changes
health changes
connection changes
commands and responses
alarms
In addition we will incorporate logging of debug messages using varying debug levels as outlined in
SPEC-0022, Section 6.3, Debug Messages:
Level 1: at the entry/exit of major code sections (code modules),
Level 2: at the entry/exit of methods and procedures (unless these are expected to be called within
tight loops) and in object constructors (with the same caveat),
Level 3: at key points within methods and procedures (again, outside of tight loops), and
CV CDD
SPEC-0180, Rev A Page 79 of 90
Level 4: within tight loops (should be small messages with critical information only).
These debug messages are intended for diagnostic and engineering.
Logging of events is accomplished by using the CSF archive service and a .logEvents attribute to turn
logging on and off, as described earlier.
7.3.11 Health and Alarms
7.3.11.1 Health
CV components will set their health according to the guidelines outlined in SPEC-0022. Health is only
reported when a component’s health status changes state. If a component is operating normally, its health
is GOOD. All CV components will set their health to GOOD upon startup and initialization. If a
component detects a failure within itself or in a hardware component under its direct control and it is still
able to operate, but at a reduced capability, it will set its health to ILL. If a component detects a failure
within itself or in a hardware component under its direct control and it is no longer able to operate, the
component will set its health to BAD. If a component is able to recover from a failure and operate
normally, whether by internal means or by external intervention from the operator, it will return its health
to GOOD.
7.3.11.2 Alarms
Alarms are to be used when operator notification and possible action are required to report equipment
danger or failure, or when continued operation in a malfunctioning state will result in bad data being
recorded either by the system in question or by other systems or instruments impacted by the
malfunctioning system.
We have analyzed the possible failure scenarios for the CV, resulting in the following table of failures and
CV alarm responses. Note: the responses of the motion controllers are the default behavior of the
MotionController class and are not programmed or configured directly by the CV.
Failure Alarm Response
A motion control device
fails
An incorrectly placed optic in the CV
may cause the CV image data to be
bad. The motion controller raises an
alarm.
The CV Camera Controller
is unable to control the
camera
The CV camera may be operating at
incorrect settings, possibly leading to
bad CV image data. The CV Camera
Controller raises an alarm.
The CV Camera Controller
is unable to acquire image
data from the camera
Proper functioning of the CV image
data stream is required. The CV
Camera Controller raises an alarm.
A call to a CSF service by
a CV component fails
If the service is critical to the proper
functioning of the CV and to the
viability of the CV image data, the
component in question will raise an
alarm.
A component detects an If the resource failure can result in
CV CDD
SPEC-0180, Rev A Page 80 of 90
internal SW resource
problem
bad CV image data being produced,
the component will raise an alarm.
7.3.12 GUI Screens
The CV will provide an Engineering GUI screen with multiple tabs to provide the following basic
functionality:
The current state and status of the CV
A summary of the positions of the motorized devices
A reduced size version of the current CV image
Setting any CV parameter
Moving any CV motorized device
Updating the default or named position of any CV device
Sequencing the CV through any internal calibrations
Startup/shutdown of the CV
A minimal control and status screen for the OCS Operator’s AO GUI tab
In addition, the CV will provide a separate display with a full size rendering of the current CV image
along with target and AO lock point location information.
We have mocked up some concept screens, shown in the figures below. Initial screens will be developed
based on these mock-ups during implementation and their design will be iterated and updated during lab
integration and testing. All Engineering GUI screens will be implemented using the JES tools that are part
of the CSF.
The high-resolution CV image and status display will be implemented using technologies other than JES
to provide advanced graphics capabilities such as interactive zoom, pan and contrast enhancement that are
not easily implemented in JES (Qt or PyQt are possibilities).
CV CDD
SPEC-0180, Rev A Page 81 of 90
Figure 33: Screen 1 of 2 of CV Engineering GUI mock-up.
CV CDD
SPEC-0180, Rev A Page 82 of 90
Figure 34: Screen 2 of 2 of CV Engineering GUI mock-up.
CV CDD
SPEC-0180, Rev A Page 83 of 90
Figure 35: A mockup of the full-size CV Display.
CV CDD
SPEC-0180, Rev A Page 84 of 90
7.3.12.1 Full-Size CV Display
The full-size CV display will be implemented using the new 4k Ultra HD standard, which supports 3840
x 2160 pixels. Although 4k displays are currently available, we plan to postpone the purchase of a display
for as long as possible to allow the technology to mature and the prices to drop. Currently 32” 4k
monitors are available for under $1000. We are working with the DKIST Operations Group to specify the
appropriate size monitor to be hung on a wall in the Operations Room. A mockup of the CV display using
the 4k format is shown above in Figure 35. The 2048 x 2048 image display is centered in the left 2160 x
2160 pixel portion of the screen. The remaining space on the right is used for basic CV status
information: the current time stamp, the current field of view and plate scale, and the current lock point
position as an offset from the boresight in arc-seconds in the WFC coordinate system. The boresight of
the telescope is the center of the image display. The lock point location is shown by a dashed blue reticle
(both the HOWFS and LOWFS lock points can be shown).
7.3.13 Use Case Details
In this section we present detailed discussions of the following uses cases: normal observing, dark
calibration, and boresight calibration. These use cases cover the important operational modes of the CV
and the typical interaction required between the CV controller, MC and motion controllers, and the
Camera Controller and camera. This section describes these interactions in detail. Note: the gain
calibration is nearly identical to the dark calibration and is not detailed here.
7.3.13.1 Normal Observing
The primary use of the CV is to display real-time image data during the diffractionLimited,
seeingLimitedOnDisk, seeingLimitedCoronal, and, possibly, limbTracking modes. We refer to this usage
as “normal observing”. We assume that the CV has been initialized and calibrated and that it is currently
in the idle mode. The sequence diagram shown below in Figure 36 illustrates in detail the interaction
between the CV controller, the MC and the motion controllers, and the CC and the camera during this
mode of operation. The following actions take place (the numbers in the list refer to the sequence
numbers in the diagram):
1. The WCCS sends a configuration to the CV containing the mode attribute set to one of the
normal observing modes mentioned above.
2. The CV now sends configurations simultaneously to the MC and the CC instructing them to
configure their devices according to the attributes contained in the configuration. For all intents
and purposes, these commands occur simultaneously, but this cannot be shown in the diagram.
Instead we show the command to the MC occurring first.
3. The CV commands the CC to configure the camera.
4. The CC sends a configuration command to the camera.
5. The MC sends a command to the objective lenses to move the 30” lens into the beam and the 60”
lens out of the beam (the MC does not send the command if the lenses are already in their proper
positions).
6. The objective lenses move into their requested positions (normally this would be illustrated using
one thread for each lens, but for brevity we show a single thread representing both devices).
7. The camera configures itself and begins streaming images. Note that we use the free-run
capability of the camera which does not require any software or hardware triggers.
8. The motion controllers for the lenses signal to the MC that they are done.
9. The MC signals to the CV that it is done.
10. The Camera signals the CC that it is done.
CV CDD
SPEC-0180, Rev A Page 85 of 90
11. The CC signals to the CV that it is done. The entire CV subsystem is configured at this point.
Note that the publishing of image data to the BDT occurs automatically in the CC and is not
shown in the sequence diagram.
12. After some time the WCCS sends a configuration to the CV requesting it to store data to the
DHS.
13. The CV forwards the request to the CC.
14. The CC responds by changing the meta-data that is sent to the DHS to indicate that the image
data shall now be saved.
15. The CC responds to the CV that it is done.
16. After some time the WCCS sends a configuration to the CV requesting it to stop storing data to
the DHS.
17. The CV forwards the request to the CC.
18. The CC responds by changing the meta-data that is sent to the DHS to indicate that the image
data shall not be saved.
19. The CC responds to the CV that is done.
Figure 36: A sequence diagram illustrating CV normal observing operation..
7.3.13.2 Dark Calibration
The dark calibration is a typical calibration procedure for the CV. It requires that the beam be blocked at
the GOS, which must be initiated at the WCCS level. The remainder of the procedure can be sequenced
either from the WCCS or in the CV. The description below assumes the procedure is implemented within
the CV and that the beam is already blocked at the GOS. The following actions take place (refer to Figure
37):
CV CDD
SPEC-0180, Rev A Page 86 of 90
1. The WCCS sends a configuration to the CV containing the mode attribute set to “calibrate” and
the calibrate attribute set to “dark”.
2. The CV controller forwards the configuration to the Calibration Sequencer for processing.
3. The Calibration Sequencer forwards the appropriate camera settings to the Camera Controller and
commands it to configure the camera.
4. The Camera Controller sends the commands to the camera.
5. The camera configures itself.
6. The camera signals the CC that it is done.
7. The CC signals the Calibration Sequencer that it is done.
8. The calibration sequencer begins the image summing loop by requesting an image from the
Correction Thread (this is actually a blocking read to the pass box mentioned earlier).
9. The camera performs an exposure. Note: the camera free-runs, so this step occurs asynchronously
with respect to the other steps in the loop.
10. The camera notifies the Correction Thread that an image is ready.
11. The Correction Thread applies the dark and gain corrections.
12. The Correction Thread notifies the Calibration Sequencer that the requested image is ready (this
is actually a return from the blocking read on the pass box).
13. The new image is added to the running sum. Steps 9-13 are repeated for the requested number of
frames.
14. The Calibration Sequencer computes an average from the sum.
15. The Calibration Sequencer validates the average dark frame to make sure it is OK.
16. The Calibration Sequencer saves the dark frame to the Calibration Store.
17. The Calibration Sequencer signals the CV that it is done.
CV CDD
SPEC-0180, Rev A Page 87 of 90
Figure 37: A sequence diagram illustrating the CV dark calibration.
7.3.13.3 Boresight Calibration
This procedure is used to align the boresight of the telescope. It must be sequenced from the WCCS
because it uses data from both the CV and the HOAO in the computations. A point source is required at
the GOS as well. The description below assumes the GOS pinhole is already in position. The WCCS
sends a configuration to the CV containing the mode attribute set to “calibrate” and the calibrate attribute
set to “boresight”. As part of the procedure, the WCCS requests a centroid measurement from the CV. At
the CV level, the following actions take place (refer to Figure 38):
1. The WCCS sends a configuration to the CV containing the mode attribute set to “calibrate” and
the calibrate attribute set to “boresight”.
2. The CV controller forwards the configuration to the Calibration Sequencer for processing.
3. The Calibration Sequencer sends a configuration to the MC to move the objective lenses to select
the desired field of view.
4. The Calibration Sequencer sends a configuration to the Camera Controller to configure the
camera.
5. The Camera Controller sends the configuration parameters to the camera.
6. The MC sends a command to the objective lenses to move to the appropriate positions for the
desired FOV (the MC does not send the command if the lenses are already in their proper
positions).
CV CDD
SPEC-0180, Rev A Page 88 of 90
7. The camera configures itself.
8. The objective lenses move to the proper positions. Note: this is shown in the sequence diagram
using a single thread for brevity.
9. The objective lens controllers respond to the MC that they are in position (done).
10. The in position message for the lenses is passed up to the Calibration Sequencer.
11. The camera signals the Camera Controller that it is finished configuring itself.
12. The Camera Controller signals the Calibration Sequencer that it is done.
13. The calibration sequencer begins the image summing loop by requesting an image from the
Correction Thread (this is actually a blocking read to the pass box mentioned earlier).
14. The camera performs an exposure. Note: the camera free-runs, so this step occurs asynchronously
with respect to the other steps in the loop.
15. The camera notifies the Correction Thread that an image is ready.
16. The Correction Thread applies the dark and gain corrections.
17. The Correction Thread notifies the Calibration Sequencer that the requested image is ready (this
is actually a return from the blocking read on the pass box).
18. The new image is added to the running sum. Steps 13-18 are repeated for the requested number of
frames.
19. The Calibration Sequencer computes an average from the sum.
20. The Calibration Sequencer computes the centroid of the image.
21. The Calibration Sequencer publishes the centroid results in a CSF event.
22. The Calibration Sequencer signals the CV that it is done.
If multiple centroid calculations are required, the process is repeated by the WCCS without the
preliminary configuration of the camera and lenses (steps 3-12).
CV CDD
SPEC-0180, Rev A Page 89 of 90
Figure 38: A sequence diagram illustrating the CV portion of the boresight calibration.
7.4 HARDWARE REQUIREMENTS
The CV control software will all run on a single multi-core CPU. One or two cores may be dedicated to
the camera control, dark and gain corrections, and image publication to the BDT, as needed. The
remaining CSF controllers are not a significant load for the CPU. The motion controllers are all deployed
in a separate CPU dedicated to control of all the AO system motion control devices. All the CSF
controllers are Java-based and are deployed in a single Java CSF Container on the CPU. A deployment
diagram for the CV high level software is shown below in Figure 39.
CV CDD
SPEC-0180, Rev A Page 90 of 90
Figure 39: Deployment diagram for the HOAO high-level software.