voltage tip mitigation in distribution system

Upload: dorababu2007

Post on 02-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 voltage tip mitigation in distribution system

    1/34

    Title of the Project :

    VOLTAGE DIP MITIGATION IN

    DISTRIBUTION SYSTEM WITH

    D-STATCOM

    Under the guidance of

    Sri S.S.Tulasiram Das Garu

    Professor in EEE Dept

    byM.Dorababu

    Roll No. 11012D4302

  • 8/10/2019 voltage tip mitigation in distribution system

    2/34

    The most common power quality problems are voltage sags ,

    harmonic distortion and low power factor

    Voltage sags is caused by fault in the Distribution system

    Harmonic currents in the distribution system will cause harmonic

    distortion , low power factor & additional losses as well as

    heating of electrical equipment.

    Different ways to enhance power quality problems in transmission

    and distribution systems.

    D-Statcom is the most effective device used for enhancement of

    power quality in transmission & Distribution systems

    PWM based control scheme is used for control of electronic

    valves in the D-STATCOM

    The D-Statcom injects a current in to the system to mitigate thevoltage sag.

    LCL Passive Filter is added to D-STATCOM to improve harmonic

    distortion and low power factor

  • 8/10/2019 voltage tip mitigation in distribution system

    3/34

    The objective is

    Voltage sags are mitigated by inserting D- STATCOM in the

    Distribution System

    By adding LCL passive filter to D-STATCOM the harmonicdistortion is reduced & power factor increase close to unity.

    Statcom requires some amount of energy storage to accommodateharmonic power and AC system unbalances

    Statcom equivalent circuit

  • 8/10/2019 voltage tip mitigation in distribution system

    4/34

    D-Statcom :

    IL = Load current

    Is = Source currentVth = Thevenin Voltage

    VL = Load voltage

    Zth = impedance

    Iout= IL- IS= IL- (Vth-VL) / Zth

  • 8/10/2019 voltage tip mitigation in distribution system

    5/34

    The output current ( I out) from the D-STATACOM will correctthe voltage sags by adjusting the voltage drop across the systemimpedance ( Zth= R+ j X)

    Voltage sag correction with D- Statcom depends on:

    The value of impedance : ( Zth = R+ j X )

    The fault level of load bus

    The shunt injected current Ish corrects the voltage sag by adjustingthe voltage drop across the system impedance Zth.

    The value of Ish

    can be controlled by adjusting the output voltage ofthe converter

    The switching frequency is set at 475 Hz

  • 8/10/2019 voltage tip mitigation in distribution system

    6/34

    D STATACOM( Distribution Static Compensator):

    The D-STATCOM is the voltage-sourced inverter that converts aninput dc voltage into a three-phase output voltage at fundamentalfrequency.

    It consist of

    i) Voltage source converter (VSC)

    ii)DC energy storage device

    iii) Controller

    iv) Coupling Transformer

    Voltage source converter (VSC):a) It is a power electronic device which can generate a

    sinusoidal voltage with any required magnitude, frequency &phase angle.

    b) The VSC is used to either completely replace the voltage or toinject the missing voltage.

    c) The missing voltage is the difference between the nominalvoltage and the actual.

  • 8/10/2019 voltage tip mitigation in distribution system

    7/34

    d) It converts the DC voltage across the storage device in to a setof

    three phase ac out put voltages.

    e) These voltages are in phase and coupled with the ac system

    through the reactance of the coupling transformer.

    f) Suitable adjustment of the phase and magnitude of the D-

    STATCOM output voltages allows effective control of active and

    reactive power exchanges between the D-STATCOM and the ac

    system

    g) This configuration allows the device to absorb or generate

    controllable active and reactive power.

    The VSC connected in shunt with the ac system which can beused for up to three quite distinct purposes:

    1. Voltage regulation and compensation of reactive power;

    2. Correction of power factor; and

    3. Elimination of current harmonics.

  • 8/10/2019 voltage tip mitigation in distribution system

    8/34

    Operation principle of the voltage source rectifier:

    The voltage source rectifier operates by keeping the dc linkvoltage at a desired reference value, using a feedback control loop

    To accomplish this task, the dc link voltage is measured andcompared with a reference VREF

    The error signal generated from this comparison is used to switchthe six valves of the rectifier ON and OFF

    In this way, power can come or return to the ac source accordingto dc link voltage requirements

    Voltage VDis measured at capacitor CD

  • 8/10/2019 voltage tip mitigation in distribution system

    9/34

    When the current IDis positive (rectifier operation), the capacitor CDis

    discharged, and the error signal ask the Control Block for more

    power from the ac supply.

    The Control Block takes the power from the supply by generating theappropriate PWM signals for the six valves.

    In this way, more current flows from the ac to the dc side, and the

    capacitor voltage is recovered.

    Inversely, when ID becomes negative (inverter operation), the

    capacitor CDis overcharged, and the error signal asks the control to

    discharge the capacitor and return power to the ac mains.

    The PWM control not only can manage the active power, but also

    reactive power, allowing this type of rectifier to correct power factor.

    The ac current waveforms can be maintained as almost sinusoidal,

    which reduces harmonic contamination to the mains supply.

  • 8/10/2019 voltage tip mitigation in distribution system

    10/34

    Vi: effective output voltage of the D-STATCOM & :power angle &Vs: System voltage.

    The D-STACOM employs an inverter to convert the DC link

    voltage Vdc on the capacitor to a voltage source of adjustable

    magnitude and phase.

    The inductance(L) and resistance(R)represents the equivalent

    circuit elements of the step-down transformer and the inverter is

    the main component of the D-STATCOM

  • 8/10/2019 voltage tip mitigation in distribution system

    11/34

    The controller of the D STATCOM is used to operate the inverter in the

    phase angle between the inverter voltage and the line voltage is dynamically

    adjusted so that the D-STATCOM generates or absorbs the desired VAR at

    the point of connection.

    If Vi is equal to Vs, the reactive power is zero and the D-STATCOM does not

    generate or absorb reactive power

    No-load mode (Vs = Vi)

    When Vi is greater than Vs, the DSTATCOM shows an inductive reactance

    connected at its terminal. The current, I, flows through the transformer

    reactance from the D-STATCOM to the ac system, and the device generates

    capacitive reactive power

  • 8/10/2019 voltage tip mitigation in distribution system

    12/34

    If Vs is greater than Vi, the D-STATCOM shows the system as a

    capacitive reactance. Then the current flows from the ac system to

    the D-STATCOM, resulting in the device absorbing inductivereactive power

  • 8/10/2019 voltage tip mitigation in distribution system

    13/34

  • 8/10/2019 voltage tip mitigation in distribution system

    14/34

    Phase-Modulation of the control signal

    The sinusoidal signal Vcontrol is phase-modulated by means of the angle

    VA = Sin (t+)VB= Sin(t+-2/3)VC = Sin (t++2/3)

  • 8/10/2019 voltage tip mitigation in distribution system

    15/34

    Proportional-integral controller (PI Controller) is a feedback controllerwhich drives the system to be controlled with a weighted sum of theerror signal (difference between the output and desired set point) andthe integral of that value

    PI controller will process the error signal to zero

    The load r.m.s voltage is brought back to the reference voltage bycomparing the reference voltage with the r.m.s voltages that had beenmeasured at the load point

    PWM generator will generates the Sinusoidal PWM waveform orsignal.

    It produces the desired synchronizing signal that required The modulated signal is compared against a triangle signal in order to

    generate the switching signals for VSC valves

    Energy Storage Circuit:

    DC source is connected in parallel with the DC capacitor

    It carries the input ripple current of the converter and it is the mainreactive energy storage element

    DC capacitor could be charged by a battery source or could berecharged by the converter itself.

  • 8/10/2019 voltage tip mitigation in distribution system

    16/34

    Start

  • 8/10/2019 voltage tip mitigation in distribution system

    17/34

    Start

    Design distribution system using MATLAB SIMULINK

    Create distortion by inserting different types of faults

    Analyze the result from scope

    Vary the value of fault resistance

    Is the voltage

    sag>0.9p.u

    PF>0.9

    Is the THD

    below 5%

    Run the simulation between 0-1s

    end

    Inject D-STATCOM

    into distribution

    system

    Add LCL passive

    filter

    Flow Chart

    Yes

    Yes

    No

    No

  • 8/10/2019 voltage tip mitigation in distribution system

    18/34

  • 8/10/2019 voltage tip mitigation in distribution system

    19/34

    SIMULINK DIAGRAM WITHOUT D-STATCOM

    Different Types of faults :

    i)Three phase to ground fault (TPG)

    ii) Double line to ground fault (DLG)

    iii) Line to line fault (LL)

    iv) Single line to ground fault (SLG)

  • 8/10/2019 voltage tip mitigation in distribution system

    20/34

    Fault resistance(Rf) :0.66 Three phase to ground fault

    (TPG)

    Fault resistance(Rf) :0.66 Double line to ground fault

    (DLG)

    Time in

    sec

    Vpu

    Vpu

    Time in

    sec

  • 8/10/2019 voltage tip mitigation in distribution system

    21/34

    Fault resistance(Rf) :0.66 Line to line fault (LL)

    Fault resistance(Rf) :0.66 Single Line to Ground fault

    (SLG)

    Vpu

    Vpu

    Time in

    sec

    Time in

    sec

  • 8/10/2019 voltage tip mitigation in distribution system

    22/34

    Results of voltage sags for different types of fault without D-

    Statcom

    FaultResistance

    (Rf)

    Voltage sagfor TPG

    fault (p.u)

    Voltage sagfor DLG

    fault (p.u)

    Voltage sagfor LL fault

    (p.u)

    Voltage sagfor SLG

    fault (p.u)

    0.66 0.6600 0.7070 0.7587 0.8259

    0.76 0.7107 0.7487 0.7918 0.8486

    0.86 0.7515 0.7833 0.8210 0.8679

  • 8/10/2019 voltage tip mitigation in distribution system

    23/34

    SIMULINK DIAGRAM WITH D-STATCOM

    Fault resistance(Rf) :0 66 Three phase to ground fault (TPG)

  • 8/10/2019 voltage tip mitigation in distribution system

    24/34

    Fault resistance(Rf) :0.66 Three phase to ground fault (TPG)

    Fault resistance(Rf) :0.66 Double line to ground fault (DLG)

    Vpu

    Vpu

    Time in

    sec

    Time in

  • 8/10/2019 voltage tip mitigation in distribution system

    25/34

  • 8/10/2019 voltage tip mitigation in distribution system

    26/34

  • 8/10/2019 voltage tip mitigation in distribution system

    27/34

    HARMONIC SPECTRUM OF OUTPUT CURRENT WITH OUT LCL PASSIVE FILTER

    OUTPUT CURRENT WITHOUT LCL FILTER

    ave orm o spec rum s or on ou pu curren w ou pass ve er or ree ase o rounf lt

  • 8/10/2019 voltage tip mitigation in distribution system

    28/34

    fault

    The above table shows the current harmonic for different types of faults

  • 8/10/2019 voltage tip mitigation in distribution system

    29/34

    Number ofharmonic

    spectrum

    Harmonicdistortion of

    TPG fault%

    Harmonicdistortion of

    DPG

    fault%

    Harmonicdistortion of

    LL fault%

    Harmonicdistortion of

    SLG fault%

    1st 100.00 100.00 100.00 100.00

    3rd 61.57 86.09 42.52 47.225th 1.98 1.84 1.55 1.73

    7th 13.43 17.38 10.27 8.28

    9th 5.98 8.53 5.00 3.56

    11th 1.21 2.95 2.10 0.95

    13th 5.29 6.92 3.55 3.36

    15th 0.84 0.74 0.62 0.61

    17th 1.75 2.84 1.71 1.14

    19th 1.90 2.54 1.33 1.24

    THD 63.63 88.68 44.52 48.27

    Power factor 0.84 0.75 0.91 0.90

    The above table shows the current harmonic for different types of faults

    without filter The percentage of THD shows that , it is not within the IEEE STD

    519-1992. The percentage of power factor is low in the range of 0.75 to 0.91

    lagging.

    Results of current harmonic for different types of faults without LCLassive filter

  • 8/10/2019 voltage tip mitigation in distribution system

    30/34

    HARMONIC SPECTRUM WITH LCL FILTER

    OUTPUT CURRENT WITH LCL FILTER

  • 8/10/2019 voltage tip mitigation in distribution system

    31/34

    The below table shows that with LCL passive filter the percentage of

  • 8/10/2019 voltage tip mitigation in distribution system

    32/34

    Number of

    harmonic

    spectrum

    Harmonic

    distortion of

    TPG fault%

    Harmonic

    distortion of

    DLG fault%

    Harmonic

    distortion of

    LL fault%

    Harmonic

    distortion of

    SLG fault%

    1st 100.00 100.00 100.00 100.00

    3rd 0.80 0.81 0.43 0.83

    5th 0.41 0.42 0.16 0.42

    7th

    0.29 0.30 0.13 0.329th 0.23 0.24 0.13 0.28

    11th 0.19 0.19 0.08 0.20

    13th 0.16 0.16 0.07 0.17

    15th 0.14 0.14 0.05 0.14

    17

    th

    0.12 0.12 0.05 0.1219th 0.11 0.11 0.04 0.11

    THD 1.11 1.12 0.65 1.15

    Power factor 0.99 0.99 0.99 0.99

    The below table shows that with LCL passive filter the percentage of

    THD has reduced . Now the THD is within IEEE STD 519-1992. The

    percentage of power factor increases close to unity.

    Results of current harmonic for different types of faults with LCL

    passive filter

  • 8/10/2019 voltage tip mitigation in distribution system

    33/34

    From the above results it is concluded that the voltage sags are

    mitigated by inserting D-STATCOM in to the distribution system. Byadding LCL passive filter to D-STATCOM, the total harmonic distortion

    (THD) is reduced within the IEEE STD 519-512. The power factor also

    increases close to unity. Hence it is concluded that by adding D-

    STATCOM with LCL filter the power quality is improved.

  • 8/10/2019 voltage tip mitigation in distribution system

    34/34