VLADEM CONTEMPORARY
ADDENDUM #3
Date: May 11, 2020
This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated April 15, 2020 noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification.
In addition to this 2-page document, this Addendum consists of 32 pages: 6 pages of Specifications, 3 pages of MEP addendum description, and 23 pages of Revised Drawings.
ADDENDUM TO THE SPECIFICATIONS
Item No. Spec. Section
1. Specification Section 00 01 10 Table of Contents: Add Section 08 51 30, Steel Frame Windows.
2. Add Specification Section 08 51 30 Steel Frame Windows
3. Specification Section 08 80 00 Glazing, add paragraph H to section 2.7 Glass type:
H. Glass Type G7 - Exterior: Obscured spandrel glass.1.Thickness of Glass: 1/2 inch.2.'Opaque White' by Pilkington or approved equal.
ADDENDUM TO THE DRAWINGS
Item No.
4. (Re: Architectural drawings) Windows G, E1, E2, E3, E4, and H are to be new steel frame Jamestown125 Series windows by Hope’s. Openings for G, E1, E2, E3, and E4 2’-4 1/2”x3’-0”, windows are to be awnings. The opening for H is 3’-0”x7’-0”, and is to be fixed glazing. Refer to Specification Section 08 51 30 Steel Frame Windows.
5. Add Bridgers & Paxton’s ‘Vladem Contemporary - Addendum 03” document, dated 5/11/2020.
6. Replace Sheet #187, MH100 HVAC Plan Level 0 Basement, in its entirety with sheet of the same name with revision date of 5/8/2020.
7. Replace Sheet #188, MH101 HVAC Plan Level 01 Ground, in its entirety with sheet of the same name with revision date of 5/8/2020.
8. Replace Sheet #189, MH102 HVAC Plan Level 02 Upper, in its entirety with sheet of the same name with revision date of 5/8/2020.
9. Replace Sheet #191, MP100 Mechanical Piping Plan Level 0 Basement, in its entirety with sheet of the same name with revision date of 5/8/2020.
10. Replace Sheet #194, M-401 Enlarged Mechanical Plans, in its entirety with sheet of the same name with revision date of 5/8/2020.
11. Replace Sheet #195, M-402 Enlarged Mechanical Plans, in its entirety with sheet of the same name with revision date of 5/8/2020.
1 2 5 J e f f e r s o n N . E . , A l b u q u e r q u e , N e w M e x i c o 8 7 1 0 8 p h 5 0 5 - 2 5 5 - 4 0 3 3 p o f 1 2
-
d n c a + S t u d i o G P 12. Replace Sheet #199, M-504 Mechanical Details, in its entirety with sheet of the same name with revision date
of 5/8/2020.
13. Replace Sheet #201, M-601 Heating Water Piping Schematic, in its entirety with sheet of the same name with revision date of 5/8/2020.
14. Replace Sheet #202, M-602 Chilled Water Piping Schematic, in its entirety with sheet of the same name with revision date of 5/8/2020.
15. Replace Sheet #203, M-701 Mechanical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
16. Replace Sheet #204, M-702 Mechanical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
17. Replace Sheet #205, M-703 Mechanical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
18. Replace Sheet #206, M-704 Mechanical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
19. Replace Sheet #209, MI602 Mechanical Controls Diagrams, in its entirety with sheet of the same name with revision date of 5/8/2020.
20. Replace Sheet #213, MI606 Controls Sequence of Operations, in its entirety with sheet of the same name with revision date of 5/8/2020.
21. Replace Sheet #216, ED101 Electrical Demolition Plan, in its entirety with sheet of the same name with revision date of 5/8/2020.
22. Replace Sheet #217, ES101 Electrical Site Plan, in its entirety with sheet of the same name with revision date of 5/8/2020.
23. Replace Sheet #221, EP100 Power Plan Level 0 Basement, in its entirety with sheet of the same name with revision date of 5/8/2020.
24. Replace Sheet #225, ET100 Special Systems Plan Level 0 Basement, in its entirety with sheet of the same name with revision date of 5/8/2020.
25. Replace Sheet #231, E-401 Enlarged Power Plans, in its entirety with sheet of the same name with revision date of 5/8/2020.
26. Replace Sheet #239, E-702 Electrical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
27. Replace Sheet #240, E-703 Electrical Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
28. Replace Sheet #242, E-705 Electrical Panel Schedules, in its entirety with sheet of the same name with revision date of 5/8/2020.
ATTACHMENTS Attachments as listed above and also: - none
By: dnca/StudioGP cc: File
All other provisions and conditions of the Drawings and Specifications remain unchanged.
END OF ADDENDUM #3
1 2 5 J e f f e r s o n N . E . , A l b u q u e r q u e , N e w M e x i c o 8 7 1 0 8 p h 5 0 5 - 2 5 5 - 4 0 3 3 p o f 2 2
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
1
SECTION 08 51 30 STEEL FRAME WINDOWS
PART 1 - GENERAL
1.1 DESCRIPTION
A. Work included:
1. Hot-rolled steel triple weatherstripped windows to replace existing fixed windows at locations described and as scheduled.
2. All window anchors, mullions, covers and trim.
3. Stainless steel insect screens for all operating ventilators. (optional)
4. Factory applied Hope’s Power of 5 Finishing System.
B. Related work specified elsewhere:
1. Glass, glazing and glazing materials, Section 08810.
2. Perimeter caulking, Section 07915.
3. Miscellaneous structural items, Section 05100.
1.2 QUALITY ASSURANCE
A. Manufacturer shall have not less than 10 years experience in the fabrication of heavy custom steel windows and be a member of The Steel Window Institute (SWI).
B. Installation of windows shall be done by experienced window installers.
C. Allowable tolerances: Size dimensions + 1/16 inch.
D. Source quality control:
1. Air infiltration test:
a. Meets or exceeds ASTM E283.
b. Maximum air infiltration 0.50 CFM/Ft. of crack length with differential pressure across window unit of 1.57 PSF.
2. Water penetration test:
a. Meets or exceeds ASTM E331.
b. No water penetration for 15 minutes when window is subjected to a rate of flow of 5 gal./hr./sq. ft. with differential pressure across window unit of 2.86 PSF.
3. Field test:
a. Field testing criteria (when applicable) shall be in accordance with AAMA 502-12.
4. Quality of Power of 5 non-coastal finishing process shall meet or exceed the following designations (non-coastal application – greater than (1) mile from salt water and/or similar corrosive environments):
a. Paint Blistering: ASTM D714.
b. Humidity: ASTM D4585.
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
2
c. Salt Spray (Fog): ASTM B117.
d. Painted Products in Corrosive Environments: ASTM D1654.
e. Cyclic Fog/Dry (Prohesion): ASTM G85.
f. Slat Fog/UV Painted Metal: ASTM D5894.
g. Pull off Strength of Coating: ASTM D4541.
5. Upon request, the window manufacturer shall provide a test report from a qualified independent U.S. testing laboratory regularly engaged in testing windows to verify that products conform to test requirement as outlined.
1.3 SUBMITTALS
A. Samples (as requested by architect):
1. Typical 6" long window profile with glazing beads.
2. Sample of specified muntin, showing welded intersections and glazing beads.
3. Color sample of finish.
4. Hardware.
B. Shop drawings and manufacturer's literature:
1. Submit for approval shop drawings showing window and installation details, including anchorage, fastening and recommended sealing methods.
2. Dimensioned elevations showing window opening and window sizes.
3. The manufacturer shall not commence any work until shop drawings have been approved.
4. Color charts for finishes.
1.4 PRODUCT, STORAGE AND HANDLING
A. The General Contractor shall be responsible for the protection and storage of the windows after delivery to the site.
B. Store in designated areas in an upright position on wood slats or on a dry floor in a manner that will prevent damage. Ventilate canvas or plastic coverings to prevent humidity buildup.
1.5 WARRANTY
A. Provide Hope’s standard 10 year Limited Warranty.
PART 2 - PRODUCT AND FABRICATION
2.1 Manufacturers:
A. Furnish all labor and materials to complete the fabrication of windows as shown on architect's drawings and as specified herein. All windows covered by this specification shall be domestically manufactured in the U.S.A.
B. Manufacturers: Subject to compliance with requirements covered in this specification, provide products by Hope’s Windows, Inc. – Jamestown, NY (phone: 716-665-5124, e-mail: [email protected]) whose name and products are used to establish the standard of workmanship.
C. Substitutions: Written approval necessary 10 days prior to bid through submission of the following:
1. Full-size window/door samples matching required scope.
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
3
2. Applicable test reports as outlined in Quality Assurance Section 1.2
3. List of (5) recently completed projects of similar size and scope.
2.2 MATERIALS
A. Heavy custom triple weatherstripped windows shall be manufactured from solid hot-rolled steel profiles.
1. Profiles made from steel with flanges rolled integrally at the mill.
2. Perimeter frames and ventilator profiles shall have glazing rebates providing an unobstructed glazing surface of at least 3/4".
3. Glazing rebate surfaces must be perpendicular to the web or stem of the profile. Applied glazing rebate extensions and rebate surfaces that are tapered will not be acceptable.
4. Combined weight of frame and ventilator profiles shall be a minimum of 4.20 pounds per lineal foot. Frame profile alone shall not weigh less than 1.80 pounds per lineal foot.
5. All steel profiles must be a minimum of 1-3/4″ in depth.
6. The frame and ventilator profiles shall have integral grooves located in the exterior and interior bedding contacts for the reception of triple weatherstripping.
B. Muntins:
1. True Divided Lite muntins:
a. Muntins shall be manufactured from solid hot-rolled steel, size to be determined by design.
b. Glazing rebate surfaces must be perpendicular to the stem of this profile. Rebate surfaces that are tapered will not be acceptable.
c. 1-3/4” tee shall weigh 1.62 pounds per lineal foot, the 1-3/8” tee shall weigh 1.44 pounds per lineal foot and the 7/8” tee shall weigh 1.19 pounds per lineal foot (specify).
d. All steel muntin profiles must be a minimum of 1-3/4″ in depth.
C. Glazing beads shall be extruded aluminum Alloy 6063-T5 with a minimum thickness of .062 inches.
D. Weatherstripping shall be extruded EPDM closed cell sponge, flexible silicone or polyethylene clad urethane foam.
E. Operable Hardware:
1. Pivots: Bronze cup pivots.
2. Fasteners: Brass or Bronze cam fasteners.
3. Friction and limit device: Stainless steel with sliding brass shoe and screw adjusted friction.
F. All screws that are furnished by Hope’s, for hardware, trim, covers, anchoring, weatherbars, water dams, screens, etc. shall be non-ferrous brass or stainless steel. Glazing bead retainer screws are plated steel.
G. Power of 5 Finishing
1. Non-Coastal – greater than (1) mile from salt water and/or similar corrosive environments.
a. Cleaning.
b. Pretreatment.
c. Epoxy E-Coat primer.
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
4
d. Epoxy powder primer.
e. Ultrathane polyurethane top coat.
2.3 FABRICATION
A. Fabricate steel windows in accordance with approved shop drawings.
B. Corners of frame and ventilator shall be mitered or coped then solidly welded. Exposed and contact surfaces shall be finished smooth flush with the adjacent surfaces. All interior and exterior rail bar and muntin joints shall be face welded and ground smooth.
C. Muntins
1. True Divided Lite muntins shall be coped and welded to the perimeter frame. Muntin intersections shall be slotted, cross notched and welded. All interior and exterior muntin joints shall be face welded and ground smooth.
D. Glazing:
1. All windows shall be designed for inside glazing.
2. Provide replaceable continuous glazing beads to suit the glass as specified.
3. Glazing beads shall be cut and shop fitted to each glass lite prior to shipment.
4. Manufacturer to provide correct glazing wedge and tape in accordance with the tested assembly.
E. Weatherstrip:
1. All ventilators shall receive continuous weatherstripping that shall be applied to the integral weatherstrip grooves in the interior and exterior contact surfaces of the frame and ventilator profiles. Weatherstripping that is surface applied or requires additional retainer or requires screws for application shall not be acceptable.
F. Operable Hardware:
1. Ventilators shall be hung on bronze cup pivots located at the head and sill.
2. Provide one cam fastener at each jamb. Provide double grip fasteners for ventilators over 5'6" in height.
3. Friction device shall be applied to the swing-out portion at the head.
2.4 FACTORY FINISHING
A. Power of 5
1. Cleaning:
a. All hot-rolled steel profiles must be acid pickled as defined by SSPC – SP8 to ensure a pristine, white metal substrate prior to fabrication.
2. Pretreatment:
a. Following welding and all machining operations, hot-rolled products and accessories are subjected to the following pretreatments geared specific to projects proximity to corrosive environment. Cold-rolled, formed sheet steel components are manufactured from A60 galvannealed sheet and subjected to applicable processes outlined below.
b. Inland locations (12-stage process) – Greater than one (1) mile from salt water and/or similar corrosive environments.
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
5
i. Alkaline cleaning spray.
ii. Alkaline cleaning submersion.
iii. Water immersion rinse combo.
iv. Water immersion rinse clean.
v. Acid immersion.
vi. Neutralizing rinse.
vii. Water immersion rinse clean.
viii. Conditioner immersion.
ix. Zinc phosphate immersion.
x. Rinse immersion.
xi. Sealer immersion.
xii. Water reverse osmosis rinse immersion.
3. Epoxy E-coat Primer:
All pickled and pretreated frames and accessories are immersed into an electrostatic (E-coat) bath of PPG epoxy primer to ensure all substrates are encapsulated evenly and completely. Use of spray primers only will not be an acceptable alternative to this process due to benefits from additional cleaning and frame submersion.
a. Permeate spray.
b. Permeate rinse.
c. Epoxy primer immersion and electrostatic encapsulation
d. Water reverse osmosis rinse
e. Oven-cure, 45 minutes @ 350° F
4. Epoxy Powder Primer:
Following pre-treatments and E-coat system, all frames and accessories shall receive an abrasion resistant powder coating prior to final top-coat.
a. Powder is applied electrostatically over cured E-coat to a dry film thickness (DFT) of 2.0 – 3.0 mils.
b. Parts oven baked at 325° F to completely cure prior to final top coat.
c. Powder coat is intended as an intermediate finish applied prior to the final finish top coat.
5. Polyester Powder Top Coat.
Following all pre-treatments, e-coat and powder abrasion layer, all products shall receive Hope’s ultrathane polyurethane finish with touch-up capability, low chalking and fading characteristics, unlimited color matching, and 70,000+ standard colors, including metallics.
6. Power of 5 Overview (non-coastal):
a. Combined overall dry film thickness (DFT) shall be a minimum of 4.6 mils (inland locations)
b. Overall process shall provide full documented compliance with the following criteria:
-
VLADEM CONTEMPORARY 404 MONTEZUMA AVE, SANTA FE, NM 87501
08 51 30- Steel Frame Windows -
6
i. Acid Pickling: SSPC-SP8.
ii. Paint Blistering: ASTM D714.
iii. Humidity: ASTM D4585.
iv. Painted Products in Corrosive Environment: ASTM D1654.
v. Salt Spray (Fog): ASTM B117.
vi. Cyclic Fog/Dry (Prohesion): ASTM G85.
vii. Salt Fog/UV Painted Metal: ASTM D5894.
viii. Pull Off Strength of Coating: ASTM D4541.
PART 3 - EXECUTION
3.1 INSPECTION
A. Window openings shall conform with details, dimensions and tolerances shown on the window manufacturer's approved shop drawings.
B. Conditions which may adversely affect the window installation must be corrected before installation commences.
C. The wash down of the adjacent masonry or surrounding substrate must be completed before erection commences to prevent damage to the finish by the cleaning materials.
3.2 INSTALLATION
A. Windows specified under this section shall be installed by experienced personnel.
B. Install windows in openings in strict accordance with approved shop drawings.
1. Set units plumb, level and true to line, without warp or rack of frames.
2. Anchor units securely to surrounding construction with approved fasteners.
3. The exterior joints between the windows, trim and mullions shall be properly sealed watertight with an approved sealant and neatly pointed.
C. Attach ventilator hardware, as required, and adjust ventilators to operate smoothly free from twist and to be weathertight when closed.
D. Attach loose muntin grids per approved shop drawings, if applicable.
E. Repair any abraded areas of the factory finish.
3.3 CLEANING
A. Window installer shall leave window surfaces clean after installation and ready to receive glass and glazing. The window installer will not be responsible for final cleaning.
END OF SECTION 08 51 30
-
4600 C Montgomery Blvd. NE Albuquerque, NM 87109 main 505.883.4111 www.bpce.com
May 11th 2020 Devendra Contractor 125 Jefferson NE, Albuquerque, NM 87108 SUBJECT: VLADEM CONTEMPORARY – ADDENDUM 03 Dear Mr. Contractor: Please include the following information in your addendum to the bidders. We have prepared this addendum on a separate sheet such that your office need not retype this addendum information. Sincerely, BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
-
TO: Devendra Contractor RE: Vladem Contemporary – addendum 03 5/11/2020 Page 2
4600 C Montgomery Blvd. NE, Albuquerque, NM 87109 main 505.883.4111 www.bpce.com
PRIOR APPROVALS The following manufacturers have properly submitted their request to be allowed to bid substitute equipment and services for the referenced project. Based on information submitted, and our knowledge of and previous experience with the companies and products represented, we feel that the following are capable of providing products and services equivalent to those specified. EQUIPMENT SUBSTITUTE SPECIFICATIONS 1. Section [ ]:
a. Comments if any DRAWINGS 1. MH100 – HVAC PLAN LEVEL 0 BASEMENT (Re-issued sheet attached):
a. ADD keyed notes 16 and 17. 2. MH101 – HVAC PLAN LEVEL 01 GROUND (Re-issued sheet attached):
a. ADD keyed notes 24 through 34. b. ADD manual balancing dampers. c. REVISE return air path through 111-STAFF OFFICES.
3. MH102 – HVAC PLAN LEVEL 02 UPPER (Re-issued sheet attached): a. ADD keyed notes 22 through 31. b. ADD manual balancing dampers.
4. MP100 – MECHANICAL PIPING PLAN LEVEL 0 BASEMENT (Re-issued sheet attached): a. REVISE keyed notes 2, 3 and 4. b. REVISE HWS/R and CHS/R piping.
5. M-401 – ENLARGED MECHANICAL PLANS (Re-issued sheet attached): a. REVISE keyed note 3. b. ADD keyed notes 6 through 10. c. REVISE piping/equipment layout in 002-PUMP ROOM. d. REVISE piping/equipment layout in 004-MECHANICAL.
6. M-402 – ENLARGED MECHANICAL PLANS (Re-issued sheet attached): a. REVISE AHU-1 unit section label.
7. M-504 – MECHANICAL DETAILS (Re-issued sheet attached): a. REVISE details A3, C1 and C3.
8. M-601 – HEATING WATER PIPING SCHEMATIC (Re-issued sheet attached): a. REVISE heating water piping schematic.
9. M-602 – CHILLED WATER PIPING SCHEMATIC (Re-issued sheet attached): a. REVISE chilled water piping schematic.
10. M-701 – MECHANICAL SCHEDULES (Re-issued sheet attached): a. REVISE hot water heating coil section of DEDICATED OUTSIDE AIR SYSTEM (DOAS)
schedule. b. REVISE air washer section of GALLERY VAV AIR HANDLING UNIT schedule. c. REVISE hot water heating coil section of VAV AIR HANDLING UNIT schedule. d. REVISE boxed sheet note.
11. M-702 – MECHANICAL SCHEDULES (Re-issued sheet attached): a. REVISE PUMPS schedule.
-
TO: Devendra Contractor RE: Vladem Contemporary – addendum 03 5/11/2020 Page 3
4600 C Montgomery Blvd. NE, Albuquerque, NM 87109 main 505.883.4111 www.bpce.com
b. ADD IP-3 to PUMPS schedule. c. REVISE VARIABLE FREQUENCY DRIVES schedule. d. REVISE boxed sheet note.
12. M-703 – MECHANICAL SCHEDULES (Re-issued sheet attached): a. REVISE boxed sheet note.
13. M-704 – MECHANICAL SCHEDULES (Re-issued sheet attached): a. REVISE GLYCOL FILL SYSTEM schedule. b. ADD BRAZED PLATE HEAT EXCHANGERS schedule. c. REVISE GRILLES AND DIFFUSERS schedule. d. REVISE boxed sheet note.
14. MI602 – MECHANICAL CONTROLS DIAGRAMS (Re-issued sheet attached): a. ADD SNOW MELT SYSTEM CONTROL DIAGRAM. b. ADD keyed note 4.
15. MI606 – CONTROLS SEQUENCE OF OPERATIONS (Re-issued sheet attached): a. ADD snow melt system sequence of operation.
16. ED101 – ELECTRICAL DEMOLITION PLAN (Re-issued sheet attached): a. REVISE scale. b. REVISE routing of underground utilities due to separate site utility package. c. ADD keynote 6 for protection of existing underground Century Link at location of new
building construction. 17. ES101 – ELECTRICAL SITE PLAN (Re-issued sheet attached):
a. REVISE scale and remove bar scale. b. REVISE routing of underground utilities due to separate site utility package. c. ADD routing of Century Link fiber and copper to MDF.
18. EP100 – POWER PLAN LEVEL 0 BASEMENT (Re-issued sheet attached): a. ADD power for P-1/VFD-1, P-2/VFD-2, IP-1/VFD-3, IP-2/VFD-4, and IP-3 in Mechanical
004. b. REVISE thermal overload switch to receptacle for GF-1.
19. ET100 – SPECIAL SYSTEMS PLAN LEVEL 0 BASEMENT (Re-issued sheet attached): a. REMOVE routing of conduit to MDF. This is shown on ES101.
20. E-401 – ENLARGED POWER PLANS (Re-issued sheet attached): a. REMOVE power IP-1/VFD-3 and IP-2/VFD-4 in Pump Room 002.
21. E-702 – ELECTRICAL SCHEDULES (Re-issued sheet attached): a. REVISE Manufacturer/Model for luminaire types TR04, TR06, TR08, TR12, TS, TS04,
TS06, TS08, TS10, and TS12 in Electrical Luminaire Schedule. 22. E-703 – ELECTRICAL SCHEDULES (Re-issued sheet attached):
a. ADD IP-3 to Electrical Connections For Mechanical Equipment Schedule. 23. E-705 – ELECTRICAL PANEL SCHEDULES (Re-issued sheet attached):
a. REVISE circuits 7-12 in panel M0A. b. REVISE circuits 32, 34, and 36-42 in panel M0B.
-
SE
LE
CT
.
S
MO
DELNUMBERTRADENAM
EPRO
DUCTM
ATERIAL
UP
TU1-1
TU1-2
TU1-3
TU1-4
TU2-2
8"ø
14"ø
M-4011
M-4013
10"x8"
10"x8"
18"x
10"
20"x
12"
6"ø
1
2
3 4 6
EA
EB
EC
ED
EE
EF
E1 E2 E3 E4 E5 E6
5
16"ø
6A5A
8x6150
SR-18x6150
SR-18x6150
SR-1
8x6150
SR-18x6150
SR-18x6150
SR-1
8x6150
SR-1
8x6150
SR-1
8x6170
SR-1
8x6170
SR-1
10"x8" 14"x8"14"x10"
ACU-2
ACU-1
CH-1
020
Mechanical Yard
Stair S4
005
Janitorial /
Housekeeping
002
Pump Room001
Electrical Room
007
Workshop
Stair 2
000
Hall 1
015
Study Room
003
MDF Room /
SecurityEquipment
004
Mechanical
010
Layout / Exhibit
Staging Elevator 1Elevator 2
008
Loading
Photography
014
Transit Storage
013
Clean Room /
Framing
012
Cold Storage
011
Collections
006
Elevator Machine
009
W/C
Stair 4
10"ø
12"ø 10"ø
8"ø6"ø
8x680
ER-38x680
ER-3
8x660
SR-1
8x660
SR-1
8x8120
SR-1
8x8150
SR-18x8140
SR-1
LSD-2
255
LSD-2
255
LSD-2250
LSD-2200
LSD-2200
LSD-2290
10"ø
ILF-1
LSD-2250
FCU-4
16x12970
SR-1
18x12RG-3
18"x12"
16"x12"
16"x6"
CSE-1
DD-1
6"ø
8x6TG-1
10x8TG-1
14x12TG-1
16x14TG-1
12"ø
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:18
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
HVAC PLAN LEVEL 0BASEMENT
MH100SCALE: 1/8" = 1'-0"MH100
1 HVAC LEVEL 0 BASEMENT PLAN
GENERAL SHEET NOTES
KEYNOTES1. SEE SHEET M-401 FOR CONTINUATION OF DUCTWORK.2. 8"Ø EXHAUST DUCT UP TO LEVEL ABOVE.3. WATER HEATER 4"Ø GALVANIZED STEEL COMBUSTION AIR INTAKE. INSTALL PER
MANUFACTURER'S INSTALLATION MANUAL.4. BOILER 6"Ø GALVANIZED STEEL COMBUSTION AIR INTAKE. INSTALL PER
MANUFACTUER'S INSTALLATION MANUAL.5. AIR-COOLED CHILLER. REFER TO EQUIPMENT SCHEDULE.6. COLD STORAGE DESICCANT DEHUMIDIFER, INSTALLED ON FINISHED FLOOR.
REFER TO EQUIPMENT SCHEDULE.7. 8"Ø PROCESS AIR INLET. TRIM DUCT FLUSH WITH INSIDE SURFACE OF COLD
STORAGE PANEL AND PROTECT WITH SCREEN.8. 8"Ø PROCESS AIR OUTLET. TRIM DUCT FLUSH WITH INSIDE SURFACE OF COLD
STORAGE PANEL AND PROTECT WITH SCREEN.9. 6"Ø REACTIVATION AIR INLET. PENETRATE WALL 6" BELOW DECK. PROVIDE TRIM
RING AND CUT DUCT FLUSH.10. 6"Ø REACTIVATION AIR OUTLET, DISCHARGE TO 004-MECHANICAL. PENETRATE
WALL 6" BELOW DECK. PROVIDE TRIM RING AND CUT DUCT FLUSH.11. COLD STORAGE EVAPORATOR, INSTALLED INSIDE COLD STORAGE ENCLOSURE.
MOUNT FLUSH WITH CEILING PANEL. REFER TO EQUIPMENT SCHEDULE.12. COLD STORAGE TEMPERATURE/HUMIDITY CONTROLLER. REFER TO
SPECIFICATION 2X XXXX.13. DOUBLE-WALL INSULATED COLD STORAGE ENCLOSURE. REFER TO
SPECIFICATION XX XXXX.14. INTERLOCK MOTORIZED DAMPER WITH FIRE ALARM SYSTEM.15. RECIRCULATING FILTERED FAN UNIT, BAILEIGH INDUSTRIAL AFS-1000 OR
EQUIVALENT. UNIT SHALL HAVE 1/3 HP MOTOR, 4 AMP FLA, WITH 3-PRONG CORD AND PLUG. UNIT SHALL BE PROVIDED WITH RF REMOTE CONTROL. SUSPEND UNIT FROM STRUCTURE.
16. LINEAR SLOT DIFFUSER. 4' LENGTH, (2) 1" SLOTS.17. PROVIDE FACTORY FACE-OPERATED CABLE BALANCING DAMPER WITH LINEAR
SLOT DIFFUSER.
A. COORDINATE DUCT ROUTING AND EQUIPMENT INSTALLATION WITH STRUCTURE, ARCHITECTURAL AND ELECTRICAL PLANS. GIVE SPECIAL ATTENTION TO STRUCTURAL BEAM ELEVATIONS, CEILING HEIGHTS, CABLE TRAYS AND ANY ROOF DRAIN LEADERS.
B. PROVIDE WALL MOUNTED TEMPERATURE ZONE SENSORS. REFER TO CONTROLS SPECIFICATIONS FOR MOUNTING HEIGHTS.
C. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN FOREXACT LOCATION OF GRILLES AND DIFFUSERS.
D. SEE DETAIL A2/M-502 FOR DIFFUSER AND REGISTER CONNECTIONS.PROVIDE MANUAL BALANCING DAMPERS FOR EACH CONNECTION.
E. SEE DETAIL D1/M-503 FOR EXHAUST GRILLE CONNECTION.F. SEE DETAIL C5/M-501 FOR MEDIUM VELOCITY FITTING DETAILS.G. SEE DETAIL A1/M-501 FOR LOW VELOCITY FITTING DETAILS.H. TEMPERATURE SENSORS LOCATED IN COMMON AREAS SHALL BE PROVIDED
WITH CLEAR PLASTIC COVER AND LOCK.I. ALL EXPOSED DUCTWORK TO BE PAINTED PER ARCHITECTURAL SPECIFICATIONS.J. PROVIDE SOUND ELBOWS FOR ALL CEILING RETURN AIR GRILLES PER DETAIL
A5/M-501.K. SEE TERMINAL UNIT DETAILS A5/M-502 & C5/M-502. REFER TO TERMINAL UNIT
SCHEDULE FOR VAV BOX INLET DUCT DIAMETER.L. REFER TO SHEETS M-501 THROUGH M-505 FOR MECHANICAL DETAILS.M. REFER TO MECHANICAL LEGEND SHEET M-001 FOR ADDITIONAL GENERAL
NOTES.
1
1
1
2
34
5
0' 4' 8' 16'
N
6
7
8
11
9
10
12
13
14
14
14
15
1616
1616
16
16
16
1
1
1
1
1
1
1
1 5/8/2020 Addendum #3
Digitally signed by Abbas ShirianDate: 2020.05.08 14:36:31-06'00'
187
Deirdre Harris244
-
UP
SE
LE
CT
.
S
MODELNUMBER
TRADENAME
PRODUCT
MATERIAL
{B8523F9B-3463-40AD-B1A5-A671FF52A739}
95590{
50EC46A0-B368-49B0-BE74-F3BB46658F2B}95590
30"x20"
TU1-5A
TU1-5B
48"x36"
30"x
20"
36"x24"
TU2-6
TU2-5
44"x22"
40"x
20"
TU2-4A
TU2-4B
LSD-1260
LSD-1260
LSD-1260
LSD-1260
LSD-1260
LSD-1260
LSD-1220LSD-1
220LSD-1220LSD-1
220LSD-1
220LSD-1220LSD-1
220LSD-1
220
84x20RG-3
LSD-1135
LSD-1135
LSD-1130
LSD-1135
LSD-1130LSD-1
130
TU2-7
TU2-8
TU2-3
22"x16"
16"ø
36"x
24"
16"ø
12"ø16"ø
30"x20"
20"x
14"
24"x
12"
LSD-1135LSD-1
135LSD-1135LSD-1
135
LSD-1
14"ø
12"ø
22"x
14"
16"x
12"
12"x8"
14"x12"
12"x8"
18"x12"
22"x12"
18"x8"
LSD-1
135
24"x
18"
24"x18"
18"x10"
16"x10"
LSD-1210
LSD-1210
LSD-1210
16"x14"
14"x10"
TU1-5C
14"x12"
LSD-1135
14"x8"
ER-1100
ER-2300
ER-2250
ER-280
ER-1
120
CEF-1
L-1
CH-1
SD-1240
LSD-2195
LSD-2195
LSD-2195
LSD-2195
1
2
3 4 6
7
A
B
C
D
E
EA
EB
EC
ED
EE
EF
E1 E2 E3 E4 E5
E6
5
8
9
22"x14"
6A5A
8"x20"
RG-2
FSD FSD
FSD
60x48RG-4
26"x26"
SD-2300
SD-2300
40"x
20"
LSD-1150LSD-1
150LSD-1150
LSD-1
150
LSD-1150
LSD-1150
LSD-1150
LSD-1
150
LSD-1150
LSD-1150
LSD-1
150
LSD-1150LSD-1
150LSD-1
150
LSD-1
170
LSD-1170
16"x12"
22"x16"
LSD-1200
SD-190
26"x
22"
SD-1
80
SD-1
50
RG-2
12"ø
10"ø
24"x18"
10"x12"
10"ø
SD-2
220
SD-2120
10"x10"
SD-280
8"x10"
6x650
SR-1
ACU-3
LSD-1450
60"x
28"
LSD-1LSD-1
LRG-2
LSD-1
108
Classroom
100
Vestibule 1
102
Lobby
109
Event Storage
110
W/C 2 Family
115
W/C 3 Staff
113
Breakroom
112
Conference
111
Staff Offices
Stair 1Elevator 1
Elevator 2
118
W/C 4 Women
119
W/C 5 Men 123
Elec. Cl.
120
Receiving
101
Vestibule 2
Covered Terrace
103
Gallery 1
125
Gift Shop
127
W/C
129
Vestibule 3
105
Alcove 1
Stair 2
Stair 3
121
Janitor122
IDF
Loading Dock
114
Guard Changing
Copy / Supply
107
Classroom
Hall
Mechanical Yard
Stair S5
Existing
concrete laodingdock
LSD-1
16"ø
RG-1
6"ø
12"ø
80x32RG-3
6"ø
8"ø
16"ø
14"ø
LSD-2300
LSD-2300
LSD-2300
LSD-2300
10"ø
FCU-5
L-3
LSD-1320
LSD-1320
LSD-1
320
LSD-1320
LSD-1320
16"x
14"
BCU-1
8"ø
42"x12"
RG-2
12"ø
12"x10"
117
Coat Hall
116
Elevator Hall
128
Elec
LSD-2160
LSD-1200
RG-1
RG-1
24"x18"
24"x18"
32"x24"
36x24RG-3
LRG-1120
30x36RG-3
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:21
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
HVAC PLAN LEVEL 01GROUND
MH101SCALE: 1/8" = 1'-0"MH101
1 HVAC LEVEL 1 GROUND PLAN
GENERAL SHEET NOTES
KEYNOTES1. 14"x20" SUPPLY AIR DUCT FOR FUTURE. CAP DUCTWORK IN GIFT SHOP SHELL. SEE
SHEET MH102 FOR CONTINUATION.2. 14"x20" MAKE-UP AIR DUCT FOR FUTURE KITCHEN HOOD. CAP DUCTWORK IN GIFT
SHOP SHELL. SEE SHEET MH102 FOR CONTINUATION.3. NOT USED.4. 8"Ø EXHAUST DUCT UP IN CHASE TO LEVEL ABOVE. SEE SHEET MH102 FOR
CONTINUATION.5. ELECTRIC UNIT HEATER FOR GIFT SHOP SHELL SPACE.6. INSTALL RETURN GRILLE WITH BOTTOM EDGE 4" A.F.F..7. ACOUSTICALLY LINED SOUND BOOT ON BACK OF GALLERY RETURN GRILLE.8. 28"x56" RETURN DUCT DOWN TO BASEMENT MECHANICAL ROOM. SEE SHEET
M-401 FOR CONTINUATION.9. OUTSIDE AIR LOUVER. REFER TO EQUIPMENT SCHEDULE.10. 30"x22" AHU-1 SUPPLY DUCT IN CHASE. SEE SHEET M-401 FOR CONTINUATION.11. 48"x36" AHU-2 RETURN DUCT IN CHASE. SEE SHEET M-401 FOR CONTINUATION.12. 44"x24" AHU-2 SUPPLY DUCT IN CHASE. SEE SHEET M-401 FOR CONTINUATION.13. 26"x24" AHU-2 SUPPLY DUCT UP TO SECOND LEVEL. SEE SHEET MH102 FOR
CONTINUATION.14. 40"x20" RETURN DUCT UP TO SECOND FLOOR GALLERY. SEE SHEET MH102 FOR
CONTINUATION.15. 14"x12" EXHAUST DUCT UP THRU ROOF TO EF-1.16. 8"Ø EXHAUST DUCT UP FROM THE BASEMENT. SEE SHEET MH100 FOR
CONTINUATION.17. 24"Ø AHU-1 SUPPLY DUCT UP IN CHASE TO SECOND LEVEL. SEE SHEET MH102 FOR
CONTINUATION.18. 18. 42"x42" RELIEF DUCT UP THRU ROOF TO RF-1.19. 6"Ø STAINLESS STEEL DOUBLE-WALLED CATEGORY IV VENT. ALL JOINTS AND
SEAMS MUST BE SEALED GAS TIGHT AND SHALL NOT BE COMMON VENTED. INSTALL PER MANUFACTURER'S INSTALLATION MANUAL.
A. COORDINATE DUCT ROUTING AND EQUIPMENT INSTALLATION WITH STRUCTURE, ARCHITECTURAL AND ELECTRICAL PLANS. GIVE SPECIAL ATTTENTION TO STRUCTURAL BEAM ELEVATIONS, CEILING HEIGHTS, CABLE TRAYS AND ANY ROOF DRAIN LEADERS.
B. PROVIDE WALL MOUNTED TEMPERATURE ZONE SENSORS. REFER TO CONTROLS SPECIFICATIONS FOR MOUNTING HEIGHTS.
C. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN FOREXACT LOCATION OF GRILLES AND DIFFUSERS.
D. SEE DETAIL A2/M-502 FOR DIFFUSER AND REGISTER CONNECTIONS.PROVIDE MANUAL BALANCING DAMPERS FOR EACH CONNECTION.
E. SEE DETAIL D1/M-503 FOR EXHAUST GRILLE CONNECTION.F. SEE DETAIL C5/M-501 FOR MEDIUM VELOCITY FITTING DETAILS.G. SEE DETAIL A1/M-501 FOR LOW VELOCITY FITTING DETAILS.H. TEMPERATURE SENSORS LOCATED IN COMMON AREAS SHALL BE PROVIDED
WITH CLEAR PLASTIC COVER AND LOCK.I. ALL EXPOSED DUCTWORK TO BE PAINTED PER ARCHITECTURAL
SPECIFICATIONS.J. PROVIDE SOUND ELBOWS FOR ALL CEILING RETURN AIR GRILLES PER DETAIL
C1/M-502.K. SEE TERMINAL UNIT DETAILS A5/M-502 & C5/M-502. REFER TO TERMINAL UNIT
SCHEDULE FOR VAV BOX INLET DUCT DIAMETER.L. REFER TO SHEETS M-501 THROUGH M-505 FOR MECHANICAL DETAILS.M. REFER TO MECHANICAL LEGEND SHEET M-001 FOR ADDITIONAL GENERAL
NOTES.
4
6
7
8
9
10
11
12
13
14
15
16
KEYNOTES (CONT.)20. 4"Ø STAINLESS STEEL DOUBLE-WALLED CATEGORY IV VENT. ALL JOINTS AND
SEAMS MUST BE SEALED GAS TIGHT AND SHALL NOT BE COMMON VENTED. INSTALL PER MANUFACTURER'S INSTALLATION MANUAL.
21. 6"Ø SUPPLY DUCT UP IN CHASE TO SECOND LEVEL. SEE SHEET MH102 FOR CONTINUATION.
22. 36"x24" RETURN AIR DUCT FROM LEVEL ABOVE. SEE SHEET MH102 FOR CONTINUATION.
23. HUMIDISTAT FOR MONITORING/TRENDING ONLY.24. PROVIDE FACTORY FACE-OPERATED CABLE BALANCING DAMPER WITH LINEAR
SLOT DIFFUSER.25. PROVIDE FACTORY FABRICATED MITERED CORNER MODULE. CONTRACTOR SHALL
MEASURE AND COORDINATE LENGTHS OF MITERED CORNER MODULES TO KEEP FIELD CUTTING TO AN ABSOLUTE MINIMUM.
26. INACTIVE SLOT DIFFUSER FOR CONTINUOUS APPEARANCE. BLANK OFF BACK OF LINEAR SLOT DIFFUSER WITH SHEET METAL. PAINT INSIDE OF SHEET METAL BLACK.
17
18
19
20
0' 4' 8' 16'
N
21
22
23
25
25
26
26
26
KEYNOTES (CONT.)27. LINEAR SLOT DIFFUSER. 4' LENGTH, (2) 1" SLOTS.28. LINEAR SLOT DIFFUSER. 4' LENGTH, (3) 1" SLOTS.29. LINEAR SLOT DIFFUSER. 5' LENGTH, (4) 1" SLOTS.30. LINEAR SLOT DIFFUSER. 5' LENGTH, (3) 1" SLOTS.31. LINEAR SLOT DIFFUSER. 4' LENGTH, (1) 1" SLOTS.32. LINEAR SLOT DIFFUSER. 3' LENGTH, (3) 1" SLOTS.33. LINEAR SLOT DIFFUSER. 4' LENGTH, (4) 1" SLOTS.34. BALANCING DAMPER IN VERTICAL DUCT.
28
28
28
24
24
24
28
28
281
24
24
24
29
1
24
30
1
24
30
24
301
24
28
241
28
24 28
241
28
24 28
24128
24 28
24128
24
1
30 1
31
31
31
31
31
31
31
1
3124
3124
3124
3124
1
131
31
24
31
24
31
241
28
1
26
1
27
271
271
27
27
27
27
2727
1
27
27
27
27
27
27
27
1
1
1
1
1
1
1
1
1
1
1
1
32
32
32
321
1
1
1
1
1
1
1
1
1
1
321
31
1
31
1
31
1
31
1
30
33
33
33
33
33
1
1
1
24
24
1
24
1
1
1
1
34
TYP.
24
24
24
24
24
24
1 5/8/2020 Addendum #3
Digitally signed by Abbas ShirianDate: 2020.05.08 14:36:56-06'00'
188
Deirdre Harris244
-
SE
LE
CT
.
S
DN
{6D0A672A-010B-4AB8-AB55-D072C8E400E1}
15240
Open to
Below
Open to
Below
Open to
Below
LSD-1135LSD-1
135LSD-1135LSD-1
135LSD-1
135
TU1-6A
TU1-6B
LSD-1250
LSD-1250
LSD-1250
LSD-1250
LSD-1
250
LSD-1
250
LSD-1250
LSD-1
250
TU2-10
18"x14"
12"ø
26"x22"
16"ø
14"ø
10"ø
TU2-9A
TU2-9B
TU1-7
24"x16"
16"ø
ER-2
60
ER-280
14x6200
ER-310"x10"
TU2-11
1
2
3 4 6
7
A
B
C
D
E
EA
EB
EC
ED
EE
EF
E1 E2 E3 E4 E5 E6
5
8
9
6A5A
RF-1
EF-1
14"ø
36x54RG-3
24"x14"
CU-1CU-2
8"ø
CU-3
LSD-1125
LSD-1125
16x10RG-3
14"ø
LSD-2300
LSD-2
310
LSD-2310
24x16RG-3
16x10RG-3
LSD-1
280LSD-1
280LSD-1
280LSD-1
280LSD-1280LSD-1
280LSD-1
280LSD-1
280LSD-1
280LSD-1
AD
LSD-1
280
202
Light Gallery
200
Hall
201
Gallery 2
Chase
Stair 1
Elevator 1
Elevator 2
206
W/C 7
Family
211
Artist's Studio
207
Catering / Loading
209
Collections
214
Roof Terrace
204
Women's Board
Storage
212
Studio Terrace
Stair 3
203
Hall
208
Janitor
205
Vestibule
Stair 2
Roof below
Loading Dock
Canopy below
Loading Dock
Canopy below
pla
nte
r
planter
pla
nte
r
210
Bridge Hall
14"ø
18"x14"
14"ø
12"ø
14"ø
L-2
SD-1310
SD-1
310
RG-1
14"ø
24"x20"
18x12550
ER-3
10"x10"
10"ø
LSD-2190
LSD-2
190
10"ø
LSD-1130LSD-1
130LSD-1130LSD-1
130LSD-1
130
LSD-1135LSD-1
135LSD-1135LSD-1
135LSD-1135
LSD-1130
LSD-1130
LSD-1
130
LSD-1130
LSD-1130
VFD-14
SD-380
16"x14"
10"x12"
24"x14"
24"x14"
24"x14"
26"x22"
26"x22"
28"x24"
24"ø
6"ø
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:23
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
HVAC PLAN LEVEL 02UPPER
MH102SCALE: 1/8" = 1'-0"MH102
1 HVAC LEVEL 2 UPPER PLAN
GENERAL SHEET NOTES
KEYNOTES1. 14"x20" SUPPLY AIR DUCT FOR FUTURE. CAP DUCTWORK ABOVE CEILING. SEE
SHEET MH101 FOR CONTINUATION.2. 14"x20" MAKE-UP AIR DUCT FOR FUTURE KITCHEN HOOD. CAP DUCTWORK ABOVE
CEILING. SEE SHEET MH101 FOR CONTINUATION.3. NOT USED.4. 8"Ø EXHAUST DUCT UP THRU ROOF. TERMINATE IN CODE COMPLIANT MANNER.
REFER TO SHEET MH103 FOR CONTINUATION.5. 10"x10" EXHAUST DUCT UP THRU ROOF TO EF-2.6. 24"Ø AHU-1 SUPPLY DUCT UP FROM FLOOR BELOW. SEE SHEET MH101 FOR
CONTINUATION.7. 5"Ø STAINLESS STEEL DOUBLE-WALLED CATEGORY IV VENT. ALL JOINTS AND
SEAMS MUST BE SEALED GAS TIGHT AND SHALL NOT BE COMMON VENTED. INSTALL PER MANUFACTURER'S INSTALLATION MANUAL.
8. 4"Ø STAINLESS STEEL DOUBLE-WALLED CATEGORY IV VENT. ALL JOINTS AND SEAMS MUST BE SEALED GAS TIGHT AND SHALL NOT BE COMMON VENTED. INSTALL PER MANUFACTURER'S INSTALLATION MANUAL.
9. EXHAUST FAN ON ROOF CURB, PER EQUIPMENT SCHEDULE.10. RELIEF FAN ON ROOF CURB, PER EQUIPMENT SCHEDULE.11. CONDENSING UNIT INSTALLED ON ROOF CURB. ROUTE REFRIGERANT PIPING TO
ROOF PENETRATION HOUSING PER DETAIL X/M-50X. PROVIDE REFRIGERANT PIPING AND ALL ACCESSORIES FOR A COMPLETE AND FUNCTIONAL SYSTEM PER MANUFACTURER'S INSTALLATION MANUAL.
12. ROOF PENETRATION HOUSING, THE VAULT MODEL NUMBER 201412. INSTALL PER DETAIL D4/M-505 AND MANUFACTURER'S INSTALLATION MANUAL.
13. 20"x40" RETURN DUCT DOWN TO FIRST FLOOR. SEE SHEET MH101 FOR CONTINUATION.
14. 26"x22" AHU-2 SUPPLY DUCT UP FROM FIRST FLOOR. SEE SHEET MH101 FOR CONTINUATION.
A. COORDINATE DUCT ROUTING AND EQUIPMENT INSTALLATION WITH STRUCTURE, ARCHITECTURAL AND ELECTRICAL PLANS. GIVE SPECIAL ATTENTION TO STRUCTURAL BEAM ELEVATIONS, CEILING HEIGHTS, CABLE TRAYS AND ANY ROOF DRAIN LEADERS.
B. PROVIDE WALL MOUNTED TEMPERATURE ZONE SENSORS. REFER TO CONTROLS SPECIFICATIONS FOR MOUNTING HEIGHTS.
C. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN FOREXACT LOCATION OF GRILLES AND DIFFUSERS.
D. SEE DETAIL A2/M-502 FOR DIFFUSER AND REGISTER CONNECTIONS.PROVIDE MANUAL BALANCING DAMPERS FOR EACH CONNECTION.
E. SEE DETAIL D1/M-50X FOR EXHAUST GRILLE CONNECTION.F. SEE DETAIL C5/M-501 FOR MEDIUM VELOCITY FITTING DETAILS.G. SEE DETAIL A1/M-501 FOR LOW VELOCITY FITTING DETAILS.H. TEMPERATURE SENSORS LOCATED IN COMMON AREAS SHALL BE PROVIDED
WITH CLEAR PLASTIC COVER AND LOCK.I. ALL EXPOSED DUCTWORK TO BE PAINTED PER ARCHITECTURAL
SPECIFICATIONS.J. PROVIDE SOUND ELBOWS FOR ALL CEILING RETURN AIR GRILLES PER DETAIL
A5/M-501.K. SEE TERMINAL UNIT DETAILS A5/M-502 & C5/M-502. REFER TO TERMINAL UNIT
SCHEDULE FOR VAV BOX INLET DUCT DIAMETER.L. REFER TO SHEETS M-501 THROUGH M-505 FOR MECHANICAL DETAILS.M. REFER TO MECHANICAL LEGEND SHEET M-001 FOR ADDITIONAL GENERAL
NOTES.
5
6
7
8
9
10
111111
KEYNOTES (CONT.)15. 6" SUPPLY DUCT UP FROM FIRST FLOOR. SEE SHEET MH101 FOR CONTINUATION.16. 36"x24" RETURN AIR DUCT TO LEVEL BELOW. SEE SHEET MH101 FOR
CONTINUATION.17. STRUCTURE, FOR REFERENCE ONLY.18. 28"x24" RETURN DUCT UNDERNEATH 24"x14" SUPPLY DUCT.19. 26"x22" SUPPLY DUCT UNDERNEATH 24"x14" SUPPLY DUCT.20. 6"Ø EXHAUST DUCT UP IN CHASE FROM GIFT SHOP TO ROOF. SEE SHEET MH103
FOR CONTINUATION.21. INACTIVE SLOT DIFFUSER FOR CONTINUOUS APPEARANCE. BLANK OFF BACK OF
LINEAR SLOT DIFFUSER WITH SHEET METAL. PAINT INSIDE OF SHEET METAL BLACK. 22. MOTORIZED DAMPER. CONNECT TO FMS.23. RELIEF AIR LOUVER. REFER TO M-704.24. BACKDRAFT DAMPER. CONNECT TO BACK OF RETURN AIR GRILLE.25. LINEAR SLOT DIFFUSER. 3' LENGTH, (2) 1" SLOTS.26. LINEAR SLOT DIFFUSER. 4' LENGTH, (1) 1" SLOTS.27. LINEAR SLOT DIFFUSER. 4' LENGTH, (3) 1" SLOTS.28. LINEAR SLOT DIFFUSER. 4'-11" LENGTH, (4) 1" SLOTS.29. LINEAR SLOT DIFFUSER. 5' LENGTH, (4) 1" SLOTS.30. BALANCING DAMPER IN VERTICAL DUCT.
12
13
14
0' 4' 8' 16'
N
15
1617
18
19
20
21
KEYNOTES (CONT.)31. CHASE IS TO FUNCTION AS A RELIEF AIR PLENUM. CONSTRUCT AND SEAL IN AN AIR
TIGHT MANNER.
22
23
24
1
1
1
26
26
26
26
261
26
26
26
26
261
29
29
29
29
29
29
29
29
1
1
26
26
26
26
26
1
26
26
26
26
26
1
28
28
28
28
28
28
28
28
28
28
28
1
28 1
27 1
27 1
27 1
1
26
26
1
1
251
25
130
TYP.
30
TYP.
1 5/8/2020 Addendum #3
31
Digitally signed by Abbas ShirianDate: 2020.05.08 14:37:20-06'00'
189
Deirdre Harris244
-
SE
LE
CT
.
S
MO
DELNUMBERTRADENAM
EPRO
DUCTM
ATERIAL
UP
020
Mechanical Yard
Stair 4
003
MDF
Room/SecurityEquipment
002
Pump Room 001
Electrical Room
006
Elevator Machine
007
Workshop
Stair 2000
Hall 1
015
Study Room
009
W/C
004
Mechanical
010
Layout / Exhibit
Staging
Elevator 1
Elevator 2008
Loading
Photography
014
Transit Storage
013
Clean Room /
Framing
012
Cold Storage
011
Collections
005
Janitorial/
Housekeeping
CH-1
M-4012
M-4014
1
2
3 4 6
EA
EB
EC
ED
EE
EF
E1 E2 E3 E4 E5 E6
5 6A5A
ACU-2
ACU-1
TU1-3
TU1-2TU1-1
TU1-4
1"1"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
3/4"
HW
RH
WS
HWRHWS
CHS
CSE-1
1 1/2"
1 1/2"
TU2-2
CHR
1 1/2"1 1/2"
RL RS
FCU-4
3/4"
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:24
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
MECHANICAL PIPINGPLAN LEVEL 0 BASEMENT
MP100SCALE: 1/8" = 1'-0"MP100
1 MECHANICAL PIPING LEVEL 0 BASEMENT PLAN
GENERAL SHEET NOTES
KEYNOTES1. COLD STORAGE REFRIGERANT PIPING TO MECHANICAL ROOM. SEE SHEET M-401
FOR CONTINUATION.2. 4" HWS/R PIPING TO MECHANICAL ROOM. SEE SHEET M-401 FOR CONTINUATION.3. 1-1/2" CHS/R AND HWS/R PIPING TO MECHANICAL ROOM. SEE SHEET M-401 FOR
CONTINUATION.4. 3/4" CHS/R PIPING TO BOILER ROOM. SEE SHEET M-401 FOR CONTINUATION.5. 1-1/2" CHS PIPING TO FIRST FLOOR. SEE SHEET MP101 FOR CONTINUATION.6. 1-1/2" CHR PIPING FROM FIRST FLOOR. SEE SHEET MP101 FOR CONTINUATION.7. 4" CHS/R PIPING TO MECHANICAL ROOM. SEE SHEET M-401 FOR CONTINUATION.8. LINE SIZE ISOLATION VALVES.
A. SEE EQUIPMENT SCHEDULE FOR PIPE SIZES TO EACH TERMINAL UNIT AND FAN COIL UNITS.
B. SEE DETAIL A2/M-501 AND B5/M-503 FOR PIPING PENETRATION DETAIL.C. SEE DETAIL D5/M-503 FOR PIPE HANGING DETAIL.D. VENT ALL HIGH POINTS IN PIPING SYSTEMS PER DETAIL A5/M-503.E. PROVIDE DRAINS AT ALL LOW POINT OF PIPING SYSTEMS PER DETAIL D1/M-505.F. SEE SHEET M-501 THROUGH M-505 FOR MECHANICAL DETAILS.
0' 4' 8' 16'
N
1
3
2
4
6
7
5
8
1 5/8/2020 Addendum #3
1
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:37:39-06'00'
191
Deirdre Harris244
-
AS-2
P-1 P-2
AS-1
ET-2
ET-1
CF-2
CF-1
DOAS-1
AHU-2
VFD-2VFD-1
VFD-3
VFD-4
38"x16"
12"ø
48"x
36"
20"x
24"
L-1
004
Mechanical
EA
EB
EC
ED
EE
EF
E1 E2
40"x12"
30"x22"
38"x16"
28"x
48"
Stair 4
30"x40"
AHU-1
26"x
18"
72"x
22"
44"x
22"
16"ø 16"ø
FCU-1
FCU-2
FCU-1FCU-2
VFD-5
VFD-6
VFD-7
VFD-8
VFD-9
VFD-10
VFD-11
VFD-12
VFD-13
FMS
CSC-1
GF-1
IP-1
IP-2
PHX-1IP-3
004
Mechanical
VFD-1
P-1
VFD-2
P-2
VFD-3
VFD-4
AS-1
ET-2
ET-1
AS-2
CF-1
CF-2
DOAS-1
AHU-2
2 1/2" HWS2 1/2" HWR
2" CHR2" CHS
1 1/2" HWS1 1/2" HWR
3" CHS
3" CHR
3" CHS
3" CHR
2" HWS2" HWR
3"
CH
R
4"
CH
R
EA
EB
EC
ED
EE
EF
E1 E2
CSC-1
FCU-1
FCU-2
RLRS
FMS
VFD-10
VFD-11
VFD-12
VFD-13
VFD-5
VFD-6
VFD-7
VFD-9
VFD-8
AHU-1
IP-2
IP-1
PHX-1
IP-3
GF-1
~~
1 1
/2"
HW
S
4"
CH
R1 1
/2"
HW
R4"
CH
R
4"
HW
S
3"
HW
R
4" HWR
4" HWS3" HWS
3" HWS
2"
HW
R
3"
CH
S2"
HW
S
4" CHS
4" CHR
1 1/2" CHR
4"4"
4"
4"
1"
1"1"
002
Pump Room
EA
E3
B-1 B-2
FCU-3
4" HWR
4" HWS
002
Pump RoomB-1 B-2
FCU-3
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:14
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
ENLARGED MECHANICALPLANS
M-401
3/16" = 1'-0"1
ENLARGED MECHANICAL ROOM DUCTWORK3/16" = 1'-0"
2ENLARGED MECHANICAL ROOM PIPING
1/4" = 1'-0"3
ENLARGED PUMP ROOM VENTING
1/4" = 1'-0"4
ENLARGED PUMP ROOM PIPING
GENERAL SHEET NOTESA. COORDINATE DUCT ROUTING AND EQUIPMENT INSTALLATION WITH STRUCTURE,
ARCHITECTURAL AND ELECTRICAL PLANS. GIVE SPECIAL ATTENTION TO STRUCTURAL BEAM ELEVATIONS, CEILING HEIGHTS, CABLE TRAYS AND ANY ROOF DRAIN LEADERS.
B. PROVIDE WALL MOUNTED TEMPERATURE ZONE SENSORS. REFER TO CONTROLS SPECIFICATIONS FOR MOUNTING HEIGHTS.
C. SEE DETAIL C5/M-501 FOR MEDIUM VELOCITY FITTING DETAILS.D. SEE DETAIL A1/M-501 FOR LOW VELOCITY FITTING DETAILS.E. ALL EXPOSED DUCTWORK TO BE PAINTED PER ARCHITECTURAL
SPECIFICATIONS.F. SEE TERMINAL UNIT DETAILS A5/M-502 & C5/M-502. REFER TO TERMINAL UNIT
SCHEDULE FOR VAV BOX INLET DUCT DIAMETER.G. REFER TO SHEETS M-501 THROUGH M-505 FOR MECHANICAL DETAILS.H. SEE EQUIPMENT SCHEDULE FOR PIPE SIZES TO EACH TERMINAL UNIT AND FAN
COIL UNITS.I. SEE DETAIL A2/M-501 AND B5/M-503 FOR PIPING PENETRATION DETAIL.J. SEE DETAIL D5/M-503 FOR PIPE HANGING DETAIL.K. VENT ALL HIGH POINTS IN PIPING SYSTEMS PER DETAIL A5/M-503.L. PROVIDE DRAINS AT ALL LOW POINT OF PIPING SYSTEMS PER DETAIL D1/M-505.M. REFER TO MECHANICAL LEGEND SHEET M-001 FOR ADDITIONAL GENERAL
NOTES.
KEYNOTES1. BASE MOUNTED PUMP ON HOUSEKEEPING PAD. SEE DETAIL B2/M-505. 2. VERTICAL EXPANSION TANKS ON HOUSEKEEPING PAD.3. 3/4" MAKE-UP WATER CONNECTION. REFER TO PIPING DIAGRAMS ON SHEETS
M-601 AND M-602, AS WELL AS PLUMBING DRAWINGS, FOR ADDITIONAL INFORMATION.
4. 2-1/2" HWS/HWR PIPING UP TO FLOOR ABOVE. SEE SHEET MP101 FOR CONTINUATION.
5. COLD STORAGE CONDENSING UNIT. SUSPEND FROM DECK ABOVE WITH SPRING ISOLATORS. REFER TO EQUIPMENT SCHEDULE.
6. 2-WAY CHW CONTROL VALVE. REFER TO DETAIL C1/M-504.7. 3-WAY CHW CONTROL VALVE. REFER TO DETAIL A1/M-504.8. 2-WAY HW CONTROL VALVE. REFER TO DETAIL A3/M-504.9. 3-WAY HW CONTROL VALVE. REFER TO DETAIL C3/M-504.10. TO/FROM SNOW MELT TUBING MANIFOLDS.
11 11
2
2
2
2
3
3
4
5
5
1 5/8/2020 Addendum #3
1
3
1
9 6
7
7
8
10
1 1
1
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:38:00-06'00'
194
Deirdre Harris244
-
DIS
CH
AR
GE
P
LE
NU
M
ME
RV
14
FIL
TE
R
AC
CE
SS
S
EC
TIO
N
AC
CE
SS
S
EC
TIO
N
SUPPLY FAN SECTION
AC
CE
SS
S
EC
TIO
N
AC
CE
SS
S
EC
TIO
N
CH
ILLE
D
WA
TE
R C
OIL
AC
CE
SS
S
EC
TIO
N
HO
T W
AT
ER
CO
IL
AIR
MIX
ING
S
EC
TIO
N
OUTSIDE AIR
DIS
CH
AR
GE
P
LE
NU
M
ME
RV
14
FIL
TE
R
AC
CE
SS
S
EC
TIO
N
AC
CE
SS
S
EC
TIO
N
SUPPLY FAN SECTION
AC
CE
SS
S
EC
TIO
N
AC
CE
SS
S
EC
TIO
N
CH
ILLE
D
WA
TE
R C
OIL
AC
CE
SS
S
EC
TIO
N
HO
T W
AT
ER
CO
IL
AIR
MIX
ING
S
EC
TIO
N
OUTSIDE AIR
3' -
5 1
/4"
5' -
1 1
/2"
19' - 3 1/32"
PLAN VIEW
ELEVATION VIEW
SUPPLY AIR
SU
PP
LY
FA
N S
EC
TIO
N
AC
CE
SS
SE
CT
ION
CH
ILLE
D W
AT
ER
CO
IL
RE
TU
RN
FA
N S
EC
TIO
N
AIR
MIX
ING
S
EC
TIO
N
AC
CE
SS
SE
CT
ION
AC
CE
SS
SE
CT
ION
ME
RV
14 F
ILT
ER
SE
CT
ION
DIS
CH
AR
GE
PLE
NU
M
AIR
WA
SH
ER
AC
CE
SS
SE
CT
ION
AC
CE
SS
SE
CT
ION
CH
ILLE
D W
AT
ER
CO
IL
AIR
MIX
ING
S
EC
TIO
N
AC
CE
SS
SE
CT
ION
ME
RV
14 F
ILT
ER
SE
CT
ION
DIS
CH
AR
GE
PLE
NU
M
AIR
WA
SH
ER
5' -
5"
7' -
9 1
/2"
RELIEF AIR
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
PLAN VIEW
ELEVATION VIEW
30' - 5 29/32"
AC
CE
SS
SE
CT
ION
AC
CE
SS
SE
CT
ION
SU
PP
LY
FA
N S
EC
TIO
N
RE
TU
RN
FA
N S
EC
TIO
N
DIS
CH
AR
GE
PLE
NU
M
ME
RV
14 F
ILT
ER
SE
CT
ION
SU
PP
LY
FA
N S
EC
TIO
N
AC
CE
SS
SE
CT
ION
CH
ILLE
D W
AT
ER
CO
IL
AC
CE
SS
SE
CT
ION
HO
T W
AT
ER
CO
IL
RE
TU
RN
FA
N S
EC
TIO
N
AIR
MIX
ING
SE
CT
ION
AC
CE
SS
SE
CT
ION
ME
RV
14 F
ILT
ER
SE
CT
ION
AC
CE
SS
SE
CT
ION
CH
ILLE
D W
AT
ER
CO
IL
AC
CE
SS
SE
CT
ION
HO
T W
AT
ER
CO
IL
AIR
MIX
ING
SE
CT
ION
AC
CE
SS
SE
CT
ION
5' -
5"
PLAN VIEW
ELEVATION VIEW
26' - 6 15/16"
7' -
9 1
/2"
DIS
CH
AR
GE
PLE
NU
M
SUPPLY AIR
SU
PP
LY
FA
N S
EC
TIO
N
RE
TU
RN
FA
N S
EC
TIO
N
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:15
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
Author Checker
ENLARGED MECHANICALPLANS
M-402
SCALE: NOT TO SCALE3
DEDICATED OUTSIDE AIR UNIT, DOAS-1
SCALE: NOT TO SCALE1
AIR HANDLING UNIT, AHU-1SCALE: NOT TO SCALE
2AIR HANDLING UNIT, AHU-2
1 5/8/2020 Addendum #3
1
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:38:21-06'00'
195
Deirdre Harris244
-
SCALE = NONE
CHILLED WATER COIL PIPING SCHEMATIC (3-WAY)A1
SUPPLY WATER SHALL BE CONNECTED TO AIR LEAVING SIDE OF COIL
COLLECT ALL DRAINS, INSTALL HOSE CONNECTION AND CAP
TEMPERATURE AND PRESSURE (T&P) FITTING, TYP.
PRESSURE GAUGE, TYP
THERMOMETER , TYP
UNION, TYP.
AUTOMATIC THREE-WAY CONTROL VALVE. COORDINATE PORT CONFIGURATION WITH CONTROLS CONTRACTOR.
ISOLATION VALVE, TYP.
MANUAL AIR VENT
1/2" SHUT-OFF VALVE AND DRAIN
DASHED PIPING AND COILS INDICATE TYPICAL PIPING REQUIREMENTS FOR MULTIPLE COILS
[FLOW BALANCE VALVE] [AUTOMATIC FLOW LIMITING VALVE]. SEE SPECIFICATIONS.
UNION OR FLANGE. INSTALL SO AS TO ALLOW REMOVAL OF COIL WITHOUT MAJOR REMOVAL OF PIPING.
GAUGE COCK, TYP.
1
2
3
4
6
7
8
9
10
11
12
CHS
CHR
COIL
AIR FLOW
COIL
5 4 8
6 12
7
3
5
369
1
3
11
3
10
8
3
2
13
14
5
14
1313
11
NC C
NO
GENERAL NOTES
A. PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN SYSTEM. SEE MANUAL AIR VENT DETAIL
B. SEE PLANS AND/OR PIPING SCHEMATIC FOR PIPE SIZES.
C. T&P FITTINGS INSTALLED IN PIPING 2" AND SMALLER SHALL BE INSTALLED IN ELBOW OR IN THE BRANCH SIDE OF A 2" TEE.
D. DRAIN VALVE AT ALL LOW POINTS OF PIPING. SEE DRAIN VALVE DETAIL
THE OTHERGLYCOL WATERSYSTEMS
FROM OTHERSYSTEMPRESSURESENSOR
PROVIDE ADDITIONAL PUMP(S)FOR OTHER SYSTEMS WHERENOTED
SET REGULATING VALVE TO MAINTAIN MAKE-UP PRESSURE 15 PSIG ABOVE HIGHEST SYSTEM PRV SETTING.
GLYCOL-WATER FEED UNIT
CW FROM BACKFLOW PREVENTER
AIR VENT,TYPICAL.SEE SPECS
RELIEF VALVE
PRESSURESENSOR TO ACTIVATE PUMP
FROM BOILERAND OTHERRELIEF VALVES
LINE TOPUMPSUCTION
3" CONCRETE PAD
AIR PURGE
3/4" 3/4"
NOTE:
AIR CONTROL AND MAKE-UP FOR GLYCOL SYSTEMSCALE = NONEC4
TANK
A
S
D
HB
AUTOMATICAIR VENT
TO F.STO PUMPSUCTION
AIR SEPARATOR- WHENSCHEDULED
HIGH CAPACITYFLOAT TYPE AIRVENT, TYPICAL
TO F.S
RELIEF VALVE
TO F.S
SCHEDULED AIRPURGER-LINE SIZE
TO F.S
RELIEF VALVESET AT 10%ABOVE PRVSETTING
PRESSUREREDUCING VALVE
TYPICAL DRAINVALVE WITH 3/4"HOSE CONNECTION
SCHEDULEDEXPANSIONTANK
VERTICALTANKAPPLICATION
TEE FORPARALLELTANKS IF SCHEDULED
TO F.S
FROM REDUCEDPRESSUREBACKFLOWPREVENTER, SEEPLUMBINGDRAWING
3/4" BYPASS
12" MIN.
TEE FOR PARALLELTANKS IF SCHEDULED
HORIZONTAL TANKAPPLICATION
LINE TO PUMP SUCTION
PROVIDE TANK SADDLESAND HANGER RODS
SCHEDULEDEXPANSION TANK
A
A
A
A
6
3
4
2
5
1
1
3
7
SCALE = NONE
AIR CONTROL AND MAKE-UP WATER DETAILA4
1. PROVIDE ONLY THE DASHED PIPING FOR TYPE OF TANK SCHEDULED
2. CONNECT TO SIDE OF MAIN TO PREVENT AIR OF DEBRIS FROM ENTERING PIPE TO TANK. TOP OR BOTTOM CONNECTION NOT PERMITTED.
3. PROVIDE 1.2" MINIMUM DROP ANTI-THERMOSYPHON LOOP TO PREVENT GRAVITY HEATING OF TANK. (HEATING SYS. ONLY)
4. SEE PIPING SCHEMATIC FOR LINE SIZES.
5. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS SHOWN ON CONVERTOR OR BOILER DETAIL.
6. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED ON EQUIPMENT SCHEDULE.
7. SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGH POINT IN SYSTEM HAS A MINIMUM OF 4 PSIG.
KEYNOTES
1. SUPPLY WATER SHALL BE CONNECTED TO AIR LEAVING SIDE OF COIL
2. COLLECT ALL DRAINS, INSTALL HOSE CONNECTION AND CAP
3. TEMPERATURE AND PRESSURE (T&P) ITTING, TYP.
4. PRESSURE GAUGE, TYP
5. THERMOMETER, TYP
6. UNION, TYP
7. AUTOMATIC TWO-WAY CONTROL VALVE
8. ISOLATION VALVE
9. MANUAL AIR VENT
10. 1/2" SHUT-OFF VALVE AND DRAIN
11. DASHED PIPING AND COILS INDICATE TYPICAL PIPING REQUIREMENTS FOR MULTIPLE COILS
12. [FLOW BALANCE VALVE] [AUTOMATIC FLOW LIMITING VALVE]. SEE SPECIFICATIONS. NOT REQUIRED IF PRESSURE-INDEPENDENT CONTROL VALVE IS SPECIFIED.
13. UNION OR FLANGE. INSTALL SO AS TO ALLOW REMOVAL OF COIL WITHOUT MAJOR REMOVAL OF PIPING.
14. GAUGE COCK, TYP.
NOTE:
• PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN SYSTEM. SEE MANUAL AIR VENT DETAIL
• SEE PLANS AND/OR PIPING SCHEMATIC FOR PIPE SIZES.
• T&P FITTINGS INSTALLED IN PIPING 2" AND SMALLER SHALL BE INSTALLED IN ELBOW OR IN THE BRANCH SIDE OF A 2" TEE.
• DRAIN VALVE AT ALL LOW POINTS OF PIPING. SEE DRAIN VALVE DETAIL
SCALE = NONE
CHILLED WATER COIL PIPING SCHEMATIC (2-WAY)
CHS
CHR
COIL
AIR FLOW
COIL
5 4 8
6 1273
5
369
1
3
11
3
10
8
3
2
C1
14
1313
11
KEYNOTES
SCALE = NONE
HOT WATER COIL PIPING SCHEMATIC (2-WAY)A3
NOTE:
• PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN SYSTEM. SEE MANUAL AIR VENT DETAIL
• SEE PLANS AND/OR PIPING SCHEMATIC FOR PIPE SIZES.
• T&P FITTINGS INSTALLED IN PIPING 2" AND SMALLER SHALL BE INSTALLED IN ELBOW OR IN THE BRANCH SIDE OF A 2" TEE.
• DRAIN VALVE AT ALL LOW POINTS OF PIPING. SEE DRAIN VALVE DETAIL
HWS
HWR
COIL
AIR FLOW
COIL
5 4 8
6 1273
5
369
1
3
11
3
10
8
3
2
14
1313
11
1. SUPPLY WATER SHALL BE CONNECTED TO AIR LEAVING SIDE OF COIL
2. COLLECT ALL DRAINS, INSTALL HOSE CONNECTION AND CAP
3. TEMPERATURE AND PRESSURE (T&P) FITTING, TYP.
4. PRESSURE GAUGE, TYP
5. THERMOMETER, TYP
6. UNION, TYP
7. AUTOMATIC TWO-WAY CONTROL VALVE
8. ISOLATION VALVE
9. MANUAL AIR VENT
10. 1/2" SHUT-OFF VALVE AND DRAIN
11. DASHED PIPING AND COILS INDICATE TYPICAL PIPING REQUIREMENTS FOR MULTIPLE COILS
12. [FLOW BALANCE VALVE] [AUTOMATIC FLOW LIMITING VALVE]. SEE SPECIFICATIONS. NOT REQUIRED IF PRESSURE-INDEPENDENT CONTROL VALVE IS SPECIFIED.
13. UNION OR FLANGE. INSTALL SO AS TO ALLOW REMOVAL OF COIL WITHOUT MAJOR REMOVAL OF PIPING.
14. GAUGE COCK, TYP.
KEYNOTES
SCALE = NONE
HOT WATER COIL PIPING SCHEMATIC (3-WAY)C3
1. SUPPLY WATER SHALL BE CONNECTED TO AIR LEAVING SIDE OF COIL
2. COLLECT ALL DRAINS, INSTALL HOSE CONNECTION AND CAP
3. TEMPERATURE AND PRESSURE (T&P) FITTING, TYP.
4. PRESSURE GAUGE, TYP
5. THERMOMETER , TYP
6. UNION, TYP.
7. AUTOMATIC THREE-WAY CONTROL VALVE. COORDINATE PORT CONFIGURATION WITH CONTROLS CONTRACTOR.
8. ISOLATION VALVE, TYP.
9. MANUAL AIR VENT
10. 1/2" SHUT-OFF VALVE AND DRAIN
11. DASHED PIPING AND COILS INDICATE TYPICAL PIPING REQUIREMENTS FOR MULTIPLE COILS
12. [FLOW BALANCE VALVE] [AUTOMATIC FLOW LIMITING VALVE]. SEE SPECIFICATIONS.
13. UNION OR FLANGE. INSTALL SO AS TO ALLOW REMOVAL OF COIL WITHOUT MAJOR REMOVAL OF PIPING.
14. GAUGE COCK, TYP.
HWS
HWR
COIL
AIR FLOW
COIL
5 4 8
6 12
7
3
5
369
1
3
11
3
10
8
3
2
14
1313
11
NC C
NO
NOTE:
• PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN SYSTEM. SEE MANUAL AIR VENT DETAIL
• SEE PLANS AND/OR PIPING SCHEMATIC FOR PIPE SIZES.
• T&P FITTINGS INSTALLED IN PIPING 2" AND SMALLER SHALL BE INSTALLED IN ELBOW OR IN THE BRANCH SIDE OF A 2" TEE.
• DRAIN VALVE AT ALL LOW POINTS OF PIPING. SEE DRAIN VALVE DETAIL
KEYNOTES
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bri
dge
rs &
Pa
xto
n P
roje
ct N
o: 7
77
3
Sheet of
No.
5/8
/20
20 2
:25
:15
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
MECHANICAL DETAILS
M-504
1 5/8/2020 Addendum #3
1
1
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:38:40-06'00'
199
Deirdre Harris244
-
PLUMBING DRAWING 6/P-401
3/4" NPW MAKE-UP, FORCONTINUATION SEE
TO F.S.
~
4"
4"
3/4"
WITH FILTERBYPASS FEEDER
4"HWS
EXPANSION TANK
HOT WATER
AS-1
AUTOMATIC AIR VENT
A
TO FLOOR SINK
FIRST FLOOR
HWR
HWS
BOILER
IP-1
B-1
VENT TOATMOSPHERE
FOR CONTINUATION
GAS TRAIN
GAS
VENTAIR
TO F.S.~
CONDENSATE NEUTRALIZER
BOILER
IP-2
B-2
VENT TOATMOSPHERE
SEE PLUMBING DRAWING 6/P-401FOR CONTINUATION
GAS TRAIN
GAS
6"∅ 6"∅
VENTAIR
TO F.S.
~
CONDENSATE NEUTRALIZER
4"
4"
4"
4"
3/4"
CF-1
~~
~
~
~
ET-1
~
4"
HWS
HW
S
HWR
BASEMENT
002
FROM BASEMENTTERMINAL UNITS
TO BASEMENT TERMINAL UNITS
~~
SLEEVEPIPE
SEE DETAIL C1/M-505.
SEE DETAIL B1/M-505.
PUMP ROOM
~~
SECOND FLOOR
ROOF
~~
~~
FIRST FLOOR
SECOND FLOOR
ROOF
TO 2ND FLR.TERMINAL UNITS
FROM 2ND FLR. TERMINAL UNITS
TO GIFTSHOPBLOWER COIL UNIT
FROM GIFTSHOPBLOWER COIL UNIT
FROM BASEMENTAHUs
TO BASEMENT AHUs
SEE PLUMBING DRAWING 6/P-401
KEEP THIS VALVE NORMALLY CLOSED. ONCE THESYSTEM IS FILLED AND AIR IS REMOVED, THE MAKEUP WATER CONNECTION SHOULD BE VALVED OFF. WHEN THE SYSTEM HAS SMALL NORMAL WATER LOSSES, E.G., AT AUTOMATIC AIR VENTS AND PUMP SEALS, THE VALVE WILL HAVE TO BE MANUALLY REOPENED OCCASIONALLY TO FILL SYSTEM.
QUICK FILL BYPASS.NORMALLY CLOSED.
6"∅6"∅
PHX-1
BRAZED PLATE HEAT EXCHANGER
004
MECHANICAL~
~
~~
IP-3
SNOW MELT TUBING CIRCUIT (TYP.)
SNOW MELT TUBING MANIFOLD (TYP.)
~~
~~
~~
TO 1ST FLR.TERMINAL UNITS
FROM 1ST FLR. TERMINAL UNITS
M
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:16
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
HEATING WATER PIPINGSCHEMATIC
M-601SCALE: NOT TO SCALE1HEATING WATER PIPING SCHEMATIC
1 5/8/2020 Addendum #3
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:39:09-06'00'
201
Deirdre Harris244
-
CWR
CWS
AUTOMATIC AIR VENT
AIR SEPARATORTANGENTIAL
CW
R CW
R
CH-1
BASEMENT
FIRST FLOOR
CW
R
CW
R
3/4"
WITH FILTERBYPASS FEEDER
CHILLER YARD
4"
CWS
CWR
AS-2
100% STAND-BYLEAD
PADCONCRETE
CWS
CWR
CWR
CWR
CWS
4"
4"
4"4" 4"
4"4"
4"
4"
FLOW METERCONNECT TO FMS
CF-2 P-1 P-2
CWS
CWR
PIPESLEEVE
~~
~~
SEE DETAIL B2/M-505.SEE DETAIL
C1/M-505.
SEE DETAIL B2/M-505.
CHASE
004
MECH ROOM
TO BASEMENT AHUs
FROM BASEMENT AHUsCWR
CWS
4"
~~
SLEEVEPIPE
~~
TO FCUs
FROM FCUs
CWR
CWS
4"
~~
WITH PUMPGLYCOL FEEDER
GF-1
1-1/2"
3/4"
PLUMBING DRAWING 6/P-401
3/4" NPW MAKE-UP, FORCONTINUATION SEE
TO F.S.
~
EXPANSION TANK
HOT WATER
3/4"
ET-2
~
KEEP THIS VALVE NORMALLY CLOSED. ONCE THESYSTEM IS FILLED AND AIR IS REMOVED, THE MAKEUP WATER CONNECTION SHOULD BE VALVED OFF. WHEN
THE SYSTEM HAS SMALL NORMAL WATER LOSSES, E.G., AT AUTOMATIC AIR VENTS AND PUMP SEALS, THE VALVE
WILL HAVE TO BE MANUALLY REOPENED OCCASIONALLY TO FILL SYSTEM.
QUICK FILL BYPASS.NORMALLY CLOSED.
1"
4"
PR
V
PR
V
~TO HWR
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:16
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
CHILLED WATER PIPINGSCHEMATIC
M-602
SCALE: NOT TO SCALE1CHILLED WATER PIPING SCHEMATIC
1 5/8/2020 Addendum #3
1
Digitally signed by Abbas ShirianDate: 2020.05.08 14:39:31-06'00'
202
Deirdre Harris244
-
ABBAS
SH I R I AN
11383
GI N
EE
R
ONL
E
A
N
SROFES
EDP
I
IR
EG
STER
NEW
ME X I CO
404
Mon
tezu
ma
Ave
, S
anta
Fe
, N
M
87
50
1
Sheet Title
Set
Drawn by Checked by
Date
Co
nsulta
nt
File
Date Issue
NE
W M
EX
ICO
MU
SE
UM
OF
AR
T
VL
AD
EM
CO
NT
EM
PO
RA
RY
1 2
5
J e
f f
e r
s o
n
S t
r e
e t
N
E
A
l b
u q
u e
r q
u e
N M
8
7 1
0 8
p h
(
5 0
5 )
2
5 5
-4 0
3 3
Bridgers
& P
axto
n P
roje
ct N
o: 7773
Sheet of
No.
5/8
/20
20 2
:25
:16
PM
D:\R
evit 2
01
8\P
roje
cts
\777
3_
ME
P-N
MM
oA
-RA
ILY
AR
D_p
zp
ha
res@
bpce.c
om
.rvt
April 15, 2020
Bid Set
PZP AS
MECHANICALSCHEDULES
M-701
DEDICATED OUTSIDE AIR SYSTEM (DOAS)
SYMBOLTRANE
MODEL NO. TYPE LOCATION
SUPPLY FAN CHILLED WATER COOLING COIL HOT WATER HEATING COIL
OPER.WEIGHT(LBS.)
MINOUTSIDE
AIR
OVERALL UNITDIMENSIONS (IN.)
AIRFLOW(CFM)
EXT.SP.(IN.WC)
TOTALSP.(IN.WC)
FANBHP
FANRPM
MOTOR DATA
FAN SIZE ANDTYPE
MAX.FACEVEL.(FPM)
TOTALCAPACITY
(MBH)
SENSIBLECAPACITY
(MBH)
EAT (°F) LAT (°F)
GPMCOIL
ROWS
WATERTEMP (°F)
MAX PRESSURELOSS
MAX.FACEVEL.(FPM)
TOTALCAPACITY
(MBH)EAT(°F)
LAT(°F) GPM
WATER TEMP(°F)
MAX PRESSURELOSS
LENGTH WIDTH HEIGHTHP V PH HZ DB WB DB WB ENT. LVG.AIR (IN.
WC)WATER(FT. WC) ENT. LVG.
AIR (IN.WC)
WATER(FT. WC)
DOAS-1 CSAA010UA INDOOR PERFORMANCECLIMATE CHANGER
BASEMENTMECHANICAL
4,500 0.5 4.6 5.26 2697 7.5 460 3 60 18.25 IN.DIRECT DRIVE
463 175 153 90 64 50 49.02 29 6 38 50 0.37 2.44 463 320 5 90 16 180 140 0.105 0.86 2600 4,500 247 62 42
GALLERY VAV AIR HANDLING UNIT
SYMBOLTRANE
MODEL NO. TYPE LOCATION
SUPPLY FAN RETURN/RELIEF FAN
TOTALAIRFLOW
(CFM)
FANARRAY
QTY.
EACH FANAIRFLOW
(CFM)
EACHEXT. SP.(IN. WC)
EACHTOTAL SP.
(IN. WC)
EACHFANBHP
EACHFANRPM
MOTOR DATA(EACH)
FAN SIZE AND TYPE
TOTALAIRFLOW
(CFM)
FANARRAY
QTY.
EACH FANAIRFLOW
(CFM)
EACHEXT. SP.(IN. WC)
EACHTOTAL SP.
(IN. WC)EACH FAN
BHP
EACHFANRPM
MOTORHP (EACH) FAN SIZE AND TYPEHP V PH HZ
AHU-1 CSAA030UA INDOOR PERFORMANCE CLIMATE CHANGER BASEMENT MECHANICAL 12,000 2 6,000 2.0 4.9 7.39 2440 10 460 3 60 20 IN. DIRECT DRIVE 12,000 2 6,000 0.8 1.0 2.38 1,706 5 20 IN. DIRECT DRIVE
VAV AIR HANDLING UNIT
SYMBOLTRANE
MODEL NO. TYPE LOCATION
SUPPLY FAN RETURN/RELIEF FAN
TOTALAIRFLOW
(CFM)
FANARRAY
QTY.
EACH FANAIRFLOW
(CFM)
EACHEXT. SP.(IN. WC)
EACHTOTAL SP.
(IN. WC)
EACHFANBHP
EACH
FANRPM
MOTOR
FAN SIZE AND TYPE
TOTALAIRFLOW
(CFM)
FANARRAY
QTY.
EACH FANAIRFLOW
(CFM)
EACHEXT. SP.(IN. WC)
EACHTOTAL SP.
(IN. WC)
EACHFANBHP
EACHFANRPM
MOTOR
FAN SIZE AND TYPEHP
(EACH)HP
(EACH)
AHU-2 CSAA040UA INDOOR PERFORMANCE CLIMATE CHANGER BASEMENT MECHANICAL 13,500 2 6,750 2.0 4.7 7.5 2175 10 22.25 IN. DIRECT DRIVE 13,500 2 6,750 1.0 1.7 3.4 1716 5 22.25 IN. DIRECT DRIVE
VAV AIR HANDLING UNIT (CONTINUED)
SYMBOL
CHILLED WATER COOLING COIL HOT WATER HEATING COIL
MINOUTSIDE
AIR(CFM)
OPER.WEIGHT(LBS.)
OVERALL UNIT DIMENSIONS (IN.)
NOTES
MAX.FACEVEL.(FPM)
TOTALCAPACITY
(MBH)
SENSIBLECAPACITY
(MBH)
EAT (°F) LAT (°F)
GPMCOIL
ROWS
WATERTEMP (°F)
MAX PRESSURELOSS TOTAL
AIRFLOW(CFM)
MAX.FACEVEL.(FPM)
TOTALCAPACITY
(MBH)EAT(°F)
LAT(°F) GPM
WATER TEMP(°F)
MAX PRESSURELOSS
LENGTH WIDTH HEIGHTDB WB DB WB ENT. LVG.AIR (IN.
WC)WATER(FT. WC) ENT. LVG.
AIR (IN.WC)
WATER (FT.WC)
AHU-2 471 423 323 80 63 52 51.09 71 4 38 50 0.288 2.89 13,500 471 565 45 95 28.2 180 140 0.067 1.84 5,000 6,227 349 94 65
GALLERY VAV AIR HANDLING UNIT (CONTINUED)
SYMBOL
CHILLED WATER COOLING COIL AIR WASHER SECTION
OPER.WEIGHT(LBS.)
MIN OUTSIDEAIR
OVERALL UNIT DIMENSIONS (IN.)
MAX.FACEVEL.(FPM)
TOTALCAPACITY
(MBH)
SENSIBLECAPACITY
(MBH)
EAT (°F) LAT (°F)
GPM
WATERTEMP (°F)
MAX PRESSURELOSS
EAT(°F)
EVAPORATIONRATE (GPH)
LAT(°F)
MEDIATYPE EFFICENCY
PRESSUREDROP
(IN WC) LENGTH WIDTH HEIGHTDB WB DB WB ENT. LVG.AIR (IN.
WC)WATER(FT. WC)
AHU-1 418 377 287 80 63 52 51.05 62.5 38 50 0.23 2.34 80 17.2 64.7 CELDEK 90% 0.15 6,600 SEE DOAS-1 398 94 65
AIR COOLED CHILLER
SYMBOLTRANE
MODEL NO. TYPEREFR.TYPE
EVAPORATOR/ CONDENSOR DATA SINGLE PO