Vision® Air Handling Unit Page 1 of 4 www.DaikinApplied.com Job Information Technical Data Sheet Job Name outagamie county ahu repl Date March 10 2021 Submitted By SW Software Version 12.44 Unit Tag ahu-1-matt-revised Unit Overview Model Number Supply Air Volume cfm Static Pressure External Dimensions External inWc Total inWc Height in Width in Length in CAH019GDAM 8400 2.70 3.88 60* 66* 102 *Not including base rails, coil connectors, drain connectors and control boxes. Unit Model Number: CAH019GDAM Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label) Outer Panel: 24 gauge G90 Galvanized Steel (unpainted) Liner: 24 gauge Galvanized Steel (unless noted per section) Insulation: R-13 Injected Foam Unit Configuration: Inline horizontal Drive (Handling) Location: Left Base: 6" formed channel Wall Thickness: 2 in Altitude: 0 ft Parts Warranty: Standard One Year Panel Filter Component: 1 Length: 14 in Shipping Section: 1 Type Efficiency Face Velocity Face Area Air Volume Filter Loading Pleated MERV 8 430 ft/min 19.5 ft² 8400 cfm Side Air Pressure Drop Number of Filters Height Width Depth Clean Air Mean Air Dirty Air 0.19 inWc 0.59 inWc 1.00 inWc 6 20 in 20 in 2 in 2 12 in 24 in 2 in Door Location Width Opening Drive side 10 in Outward

Upload: others

Post on 14-Apr-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vision® Air Handling Unit - Outagamie

Vision® Air Handling Unit

Page 1 of 4 www.DaikinApplied.com

Job Information Technical Data Sheet

Job Name outagamie county ahu repl

Date March 10 2021

Submitted By SW

Software Version 12.44

Unit Tag ahu-1-matt-revised

Unit Overview

Model Number

Supply

Air Volume cfm

Static Pressure External Dimensions

External inWc

Total inWc

Height in

Width in

Length in

CAH019GDAM 8400 2.70 3.88 60* 66* 102

*Not including base rails, coil connectors, drain connectors and control boxes.

Unit

Model Number: CAH019GDAM

Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)

Outer Panel: 24 gauge G90 Galvanized Steel (unpainted)

Liner: 24 gauge Galvanized Steel (unless noted per section)

Insulation: R-13 Injected Foam

Unit Configuration: Inline horizontal Drive (Handling) Location: Left

Base: 6" formed channel Wall Thickness: 2 in

Altitude: 0 ft Parts Warranty: Standard One Year

Panel Filter Component: 1 Length: 14 in Shipping Section: 1

Type Efficiency Face Velocity Face Area Air Volume Filter Loading

Pleated MERV 8 430 ft/min 19.5 ft² 8400 cfm Side

Air Pressure Drop Number of Filters Height Width Depth

Clean Air Mean Air Dirty Air

0.19 inWc 0.59 inWc 1.00 inWc 6 20 in 20 in 2 in

2 12 in 24 in 2 in

Door

Location Width Opening

Drive side 10 in Outward

Page 2: Vision® Air Handling Unit - Outagamie

Vision® Air Handling Unit

Page 2 of 4 www.DaikinApplied.com

Chilled Water Coil Component: 2 Length: 28 in Shipping Section: 2

Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing

(Face x Row)

5WH0706B 294065 Btu/hr 229136 Btu/hr 2 6 7 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air

Pressure

Drop

Finned

Height

Finned

Length

Face Area Face

Velocity Entering Leaving

Dry Bulb Wet Bulb Dry Bulb Wet Bulb

8400 cfm 81.0 °F 65.9 °F 56.1 °F 54.4 °F 0.52 inWc 24 in 53 in 17.67 ft² 475 ft/min

Water Flow Rate Pressure Drop Velocity Volume Weight

Entering Leaving

44.0 °F 54.2 °F 57.70 gpm 12.10 ftHd 3.90 ft/s 15.0 gal 126.00 lb

Connection [Data Per Coil] Min. Fin Surface

Temp.

Min. Tube Wall

Surface Temp.

Fouling Factor

Type Size Location Material

Threaded 1.50 in Drive side Carbon steel 44.0 °F 44.0 °F 0.000

Material Drain Pan Drain Side

Fin Tube Header Case

Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Drive side

AHRI 410 Certification

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program

which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the

Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Hot Water Coil Component: 3 Length: 14 in Shipping Section: 3

Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing

(Face x Row)

5WQ0601B 151897 Btu/hr 2 1 6 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure

Drop

Finned Height Finned Length Face Area Face Velocity

Entering Leaving

Dry Bulb Dry Bulb

8400 cfm 48.0 °F 64.5 °F 0.07 inWc 24 in 50 in 16.67 ft² 504 ft/min

Water Flow Rate Pressure Drop Velocity Volume Weight

Entering Leaving

180.0 °F 124.9 °F 5.50 gpm 0.20 ftHd 0.70 ft/s 4.0 gal 39.00 lb

Connection [Data Per Coil] Min. Fin Surface

Temp.

Min. Tube Wall

Surface Temp.

Fouling Factor

Type Size Location Material

Threaded 1.50 in Drive side Carbon steel 124.9 °F 124.9 °F 0.000

Material

Fin Tube Header Case

Aluminum .0075 in Copper .020 in Copper Galv. steel

AHRI 410 Certification

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program

which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the

Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Page 3: Vision® Air Handling Unit - Outagamie

Vision® Air Handling Unit

Page 3 of 4 www.DaikinApplied.com

Supply Fan Component: 4 Length: 46 in Shipping Section: 4

Fan Performance

Air Volume Static Pressure Fan Energy

Index(FEI)

Total Input

Power

Fan Shaft

Power

Speed Outlet Velocity

External Total Cabinet

Operating Maximum

8400 cfm 2.70 inWc 3.88 inWc 0.00 inWc 1.31 8.5 kW 9.50 BHP 3154 rpm 3457 rpm 2366 ft/min

Fan Data

Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location

Centrifugal DWDI Airfoil / 2 1 16.19 in N/A Up blast CW To Side of Fan

Motor Data

Power Electrical

Supply

Speed Efficiency Enclosure Frame Size Supplier Number of

Poles

Lock Rotor

Current

Full Load

Current

10.0 HP 460/60/3

V/Hz/Phase

1750 rpm Premium TEFC 215 T frame Generic 4 106.70 A 12.00 A

Fan Options

Shaft Grounding Kit: Provided Isolator Type: Spring

Drive Package Data*

Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type

2TB40 2BK80H BX43 2 1.61 Standard - L50 (200K)

*Daikin Applied reserves the right to provide a different but equivalent drive package

VFD/Starter/Disconnect Data

Selection Type: External J-Box Vendor: Factory Standard

Voltage: 460 V Height x Width x Depth: 6.00 in x 6.00 in x 4.00 in

Mounting: Door Side Enclosure: NEMA 1

Door

Location Width Opening

Drive side 30 in Outward

Unit Sound Power (dB)

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Radiated: 91 90 77 75 68 59 46 51

Unit Discharge: 101 100 95 96 90 87 82 80

Unit Return: 95 93 87 88 81 78 71 67

Page 4: Vision® Air Handling Unit - Outagamie

Vision® Air Handling Unit

Page 4 of 4 www.DaikinApplied.com

Shipping Section Details

Section Length

in

Weight

lb

Corner Weights (lb) Center of Gravity (in)

P1 P2 P3 P4 XX YY ZZ

1 14 284 64 64 78 78 8 33 28

2 28 881 258 278 183 163 11 35 30

3 14 432 112 116 104 100 7 34 28

4 46 995 288 240 210 258 22 30 27

Entire Unit

102

2592

708

684

588

612

47

32

28

NOTE: Special components aren't included in the corner weights and center of gravity data.

Supply Static Pressure Drop

Component Option Static Pressure Drop

Panel Filter Panel Filter 0.59 insWg

Chilled Water coil Chilled Water coil 0.52 insWg

Hot Water Coil Hot Water Coil 0.07 insWg

Supply Fan Cabinet -

External Static External Static 2.70 insWg

Total Supply Static 3.88 insWg

AHRI Certification

Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on

AHRI Standards 430/431. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Notes

Standard

1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2007. The approving authority is responsible

for compliance of multi - component building systems.

PFILT

14

1

60

14

CWC

28

2

28

HWC

14

3

14

FAN

46

4

60

46

Elevation View

XZ

Page 5: Vision® Air Handling Unit - Outagamie

400 rpm600 rpm

800 rpm1000 rpm1200 rpm1400 rpm1600 rpm

1800 rpm

2000 rpm

2200 rpm

2400 rpm

2600 rpm

2800 rpm

3000 rpm

3200 rpm

3400 rpm

3600 rpm1 bhp

1.5 bhp2 bhp

3 bhp 5 bhp

7.5 bhp

10 bhp

15 bhp

20 bhp25 bhp

30 bhp

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

8.5

9.0

ST

AT

IC P

RE

SS

UR

E (IN

. OF

WA

TE

R)

0.0

2.0

4.0

6.0

8.0

10

.0

12

.0

CFM (IN 1,000's)

16.19" Airfoil Supply Fan at Standard Conditions

Daikin AHU Fan Curve

Air volume 8400 cfm

Total static 3.88 insWg

Fan Shaft Power 9.5 bhp

Fan speed 3154 rpm

Max speed 3457 rpm

Efficiency 54.1 %

Fan Energy Index(FEI) 1.31

Unit tagging ahu-1-matt-revised

Job name outagamie county ahu repl

Date March-10-2021

Time 11:33

Supply fan performance is certified in accordance with the Central Station

Air-Handling Unit Certification Program, which is based on AHRI Standard 430.

Page 6: Vision® Air Handling Unit - Outagamie
Page 7: Vision® Air Handling Unit - Outagamie
Page 8: Vision® Air Handling Unit - Outagamie
Page 9: Vision® Air Handling Unit - Outagamie
Page 10: Vision® Air Handling Unit - Outagamie
Page 11: Vision® Air Handling Unit - Outagamie