versatec compact horizontal specification catalog · as a leader in the industry, waterfurnace is...

16
WaterFurnace SP1408 02/06 Design Features Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications Compact Horizontal Water Source/Geothermal Heat Pumps ¾ - 1½ Tons Versatec Compact Horizontal Specification Catalog

Upload: others

Post on 30-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

Wat

erFu

rnac

e

SP1408 02/06

Design Features

Factory Options

Accessories

Dimensional Data

Physical Data

Performance Data

Engineering Guide Specifications

Compact Horizontal Water Source/Geothermal Heat Pumps¾ - 1½ Tons•

Vers

atec

Com

pact

Hor

izon

tal S

peci

ficat

ion

Cat

alog

Page 2: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

WaterFurnace Versatec Compact Horizontal units are an excellent choice for commercial or institutional applica-tions with multiple small zones in boiler/cooling tower or geothermal applications. Units are available in 3 sizes (¾, 1 and 1½ tons). Versatec Compact Horizontal units provide the user with a great combination of performance, flexibility, options and value. The physical dimensions of the units are similar to older vintage water source heat pumps made by other manufacturers to facilitate retro-fits.

All Versatec units utilize R-22 refrigerant and PSC blower motors. Standard electromechanical controls with compressor control modules are included to facilitate easy installation and quick service. Airflow options are either left side or end dis-charge, all with right side return air. Heat exchangers can be copper (standard) or cupro-nickel (when used on open loop systems). Heavy gauge metal cabinets add durability to the system.

As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built is exposed to a wide range of quality control procedures throughout the assembly process and is then subjected to a rigorous battery of computerized run tests to certify that it meets or exceeds performance standards for efficiency and safety, and will perform flawlessly at startup. As further affirmation of our quality standards, each unit carries our exclusive Quality Assurance emblem, signed by the final test technician.

WaterFurnace International's corporate headquarters and manufacturing facility is located in Fort Wayne, Indiana. A sce-nic three-acre pond located in front of the building serves as our geothermal heating and cooling source to comfort-condi-tion our 110,000 square feet of manufacturing and office space. As a pioneer, and now a leader in the industry, the team of WaterFurnace engineers, customer support staff and skilled assembly technicians is dedicated to providing the finest comfort systems available.

By choosing or specifying WaterFurnace Versatec Series products, you can be assured of many years of reliable service and performance at a value-oriented price.

Page 3: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Table of ContentsPerformance Summary at ARI Conditions 4

Model Nomenclature 4

Design Features 5-6

Accessories and Other Options 7

Dimensional Data 8

Physical Data 9

Electrical Data 9

Blower Performance Data 9

Correction Factors 10

Reference Calculations 10

Legend and Notes 10

Capacity Data 11-1�

Wiring Schematic 14

Control Operation 15

Engineering Guide Specifications 15

Page 4: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

4

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Model Nomenclature

Performance Summary at ARI13256-1 WLHP Conditions

Cooling Heating

ModelAirflow

Flow86° F EWT 68° F EWT

CFMRate

Capacity EER Capacity COPGPMBTUH BTUH

VLC09 350 2.5 8,400 10.0 13,100 4.2VLC12 375 3.5 11,000 9.3 16,300 3.4VLC18 600 5.0 16,900 11.0 24,500 3.9

R C0 A1 S

FamilyVersatec Compact (Low Temperature)

Unit Capacity9,000 BTU @ 86°F12,000 BTU @ 86°F18,000 BTU @ 86° F

Return AirR = Right

Discharge OptionsE = EndS = Side

Voltage0 = 208-230/60/12 = 265/60/1

SVLC 18 S

VintageA = Current

Non-Standard OptionsSS = Standard

Sound KitA = NoneB = Blanket

Coax OptionsC = CopperN = Cupronickel

Cabinet Options1 = Unpainted

B

Notes: Rated in accordance with ARI/ISO standard 13245-1: 1998.Cooling capacities based on 80.6°F D.B. and 66.2°F W.B.Heating capacities based on 68°F D.B.

Page 5: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

5

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Versatec water source heat pumps are designed to meet the heating/air conditioning requirements of condo-miniums, hotels/motels, apartments, offices, schools and hospitals. The Versatec Compact Horizontal heat pump line from 9,000 to 18,000 BTUH consists of 3 unit sizes. Each unit size can be provided for operation at various supply voltages. Versatec Compact horizontal units are safety listed through ETL. All Versatec VLC units are de-signed to operate with liquid temperatures between 25°F and 110° F.

Quality and FlexibilityQuality, flexibility, efficiency and performance are major

requirements for all WaterFurnace products, and our Versatec product line is no exception. Each water source heat pump is factory assembled and computer run-tested to ensure reliability. All refrigerant brazing is performed in a nitrogen atmosphere and units are deep evacuated to less than 200 microns prior to refrigerant charging.

For maximum flexibility, each unit is available in right-hand air return and have end or side air discharge options.

The CabinetThe cabinet is constructed of enviromentally respon-

sible galvanized steel for maxmum corrosion resistance. Servicing to all internal components is done easily through

Design Featuresremovable access panels. The interiors of the top and side panels and the bottom of the unit are covered with 1/2” thick, 1-1/2 lb density coated glass fiber. Units are supplied with hanger brackets and grommets to facilitate instal-lation. The standard size filters (1") are held in place by factory mounted brackets. Cabinet design allows for side or end discharge in right return units as shown in Figure 1.

The flush mounted water connections (1/2" FPT) and copper condensate connections (3/4" FPT) are internally secured requiring no backup wrenches. Threaded copper adaptors are low-temperature soldered to prevent mis-shaping or weakening of the fitting, eliminating potential start up leaks.

The electrical components are located in the compres-sor section of the unit. Two knockouts are provided on the side and front of the cabinet to facilitate main power and low voltage control wiring through separate holes. All wir-ing connections are made inside the cabinet for maximum safety. Power wiring is conveniently applied to box lugs directly on the compressor contactor. Each unit is rated to accept time delay breakers (USA only) for overcurrent protection of the branch circuit.

The control box is accessible through a panel and houses the major operating electrical controls including the transformer, compressor relay and fan relay. The corner-located control box allows field wiring from two sides. Each component is readily accessible for service or replacement.

VLC09/VLC1� VLC18

Figure 1: Side or End Discharge

Page 6: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

6

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Design Features (cont.)Compressor Section

Each refrigeration system includes a hermetic com-pressor, reversing valve, water-to-refrigerant coaxial heat exchanger, high stability thermostatic expansion valve, airside coil and safety controls. Three panels allow for ac-cess to the compressor, coaxial heat exchanger, reversing valve and safety controls. High and low pressure ports are provided for easy servicing, and the coaxial heat exchang-er and all refrigerant suction lines are insulated to prevent condensation at low entering water temperatures.

Efficient compressors provide super quiet operation with high reliability. All compressors are isolated from the bottom panel with rubber isolators. The compressor junc-tion box is always located toward the front access panel.

The high stability bi-directional thermostatic expansion valve delivers optimum refrigerant flow over a wide range of conditions and provides bi-directional operation without troublesome check valves. External pressure regulating flow control valves are not recommended, as they tend to compete with the TX valve.

The reversing valve is “cool-brazed” at the factory to prevent damage from excess heat and is energized in the cooling mode.

The two heat exchanger components incorporate the most recent heat transfer technologies. The oversized

coaxial heat exchanger has a convoluted copper (optional cupronickel) inner tube and a steel outer tube and is designed for a maximum heat transfer at normal and low water flow rates (down to 1.5 gpm per ton on well water systems). This minimizes pressure drop and also enhanc-es freeze protection.

Safety controls include a low pressure switch for loss of charge protection and a high pressure switch which is designed to lock out compressor operation at extreme conditions.

Fan SectionThe one or two fan section access panels provide ser-

vice access to the fan motor.The fan motor is a three speed (four speed on VLC09

and VLC12) long life PSC type with internal thermal over-load protection. Large low rpm blowers result in decreased noise and also provide high static capability. The motor is isolated from the fan housing for minimum vibration trans-mission. All multi-speed motors have a terminal strip (on the motor) for simple motor speed change without going back to the control box. The discharge panel has 1” duct flange allowing adequate material for connecting the duct-work.

Page 7: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

7

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Accessories and Other OptionsSolenoid Valve (Field Installed)

A 24 VAC solenoid valve (24 VA maximum current draw) can be furnished and field wired so as to be ener-gized whenever there is a call for compressor operation. The solenoid valve will be quick opening and spring re-turned closed. Slow opening valves will be acceptable only if equipped with an end switch to permit compressor op-eration only after full opening. The body size of the valve shall match the water connection size of the heat pump.Cupronickel Heat Exchanger

Cupronickel (90/10) coaxial heat exchangers offer bet-ter corrosion protection and are recommended when more corrosive loop fluids are expected such as brackish well water, etc.Supply/Return Hose Kits

This kit contains a complete set of supply and return hoses, consisting of 24'' stainless braided fire resistant hoses with MPT x FPT swivel with MPT adaptor, two (2) bronze ball valves (one with P/T plug), Y-strainer with blow-down valve, and Hays Mesurflo automatic flow control valve with P/T plugs. The kit is shipped factory assembled and tagged. Specify gpm (in half gpm incre-ments) and tagging for each hose kit.Closed Loop Flow Center

The flow center is an insulated pump assembly which includes all pumping and valving for small closed loop ground source systems to 20 gpm.Hydronic Loop Controller

The hydronic loop controller is a microprocessor-based control panel for control of water loop heat rejector (tower), heat supplier (boiler), and/or water well pumps and circula-tion pumps. Includes audible and visual alarms, tempera-ture indication and add-on options of low flow switches, remote alarm sensor wells and pump alternator.

Compressor Sound PackageThis package provides an acoustical wrap for the

compressor.Hanger Kit (Field Installed)The hanger kit accessory consists of galvanized steel brackets, bolts, lock washers and isolators and shall be designed to fasten to the unit corner posts for suspension from 3/8" threaded rods. Digital Wall-Mounted Thermostats

A digital 24 VAC wall-mounted thermostat can be furnished. The sub-base includes Off-Heat-Cool-Auto, On-Auto fan switch and a fault light.

A digital seven-day programmable wall mounted thermostat is available to control the heat pump. The sub-base includes Off-Heat-Cool-Auto, an On-Auto fan switch, and a fault light.Mechanical Wall-Mounted Thermostats

A mechanical manual changeover 24 VAC wall-mount-ed thermostat can be supplied. The sub-base includes Off-Heat-Cool and an On-Auto fan switch. Setback shall be manual or automatic if a time clock is used.

A mechanical manual changeover 24 VAC wall-mount-ed thermostat with fault light is available. The sub-base includes Off-Heat-Cool, an On-Auto fan switch and a fault light.Thermostat Guard

A thermostat guard can be furnished to prevent tam-pering with the wall mount thermostat.

Page 8: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

8

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Dimensional Data

Model A B C D E F G H I J K

VLC09, VLC1�

20.25 26.38 10.88 17.06 9.51 7.48 12.79 8.00 18.48 27.82 0.89[51.44] [67.01] [27.64] [43.33] [24.16] [19.00] [32.49] [20.32] [46.94] [70.66] [2.26]

K M N O P Q R S T U V0.75 1.21 1.94 1.47 2.00 1.00 1.50 4.38 9.51 7.48 1.21[1.91] [3.07] [4.93] [3.73] [5.08] [2.54] [3.81] [11.13] [24.16] [19.00] [3.07]

Model A B C D E F G H I J

VLC18

21.52 25.5 10.44 19.00 9.35 10.44 13.29 4.54 18.63 27.6[54.66] [64.77] [26.52] [48.26] [23.75] [26.52] [33.76] [11.53] [47.32] [70.10]

K L M N O P Q R S1.05 0.65 16.16 2.90 1.49 1.01 2.25 4.54 14.04[2.67] [1.65] [41.05] [7.37] [3.78] [2.57] [5.72] [11.53] [35.66]

END DISCHARGE

FRONT

B

D

E

F

H

N

O

PQ

R

S

C

V

SIDE DISCHARGE

FRONTA

C

G

I

J

K

L

M

U

T

SIDE DISCHARGE

FRONT

AG

I

J

K

L

M

E

C

END DISCHARGE

FRONT

B

D

E

F

H

N

OP

Q

RS

VLC09 and VLC12 VLC18

Note: Dimensions in Inches [cm]. Rev. 2/1/06

Page 9: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

9

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Model VLC09 VLC1� VLC18

Fan Wheel 6 x 9 6 x 9 9 x 7[15.2 x 22.9] [15.2 x 22.9] [22.9 x 17.8]

PSC Fan Motor HP 1/10 1/10 1/6PSC Fan Motor Speeds 4 4 3Compressor Recip. Recip. Recip.

Refrigerant Charge (R-22) 25 24 31[0.709] [0.680] [0.879]

Air Coil Dimensions 10 x 16 10 x 16 14 x 16[25.4 x 40.6] [25.4 x 40.6] [35.6 x 40.6]

Air Coil Face Area 1.1 1.1 1.56[0.102] [0.102] [0.145]

Return Air Connection (WxD) 10.8 x 17.1 10.8 x 17.1 18.8 x 13.5[27.4 x 43.4] [27.4 x 43.4] [47.7 x 34.3]

Supply Air Connection (WxD) 9.5 x 7.5 9.5 x 7.5 10.4 x 9.4[24.1 x 19.1] [24.1 x 19.1] [26.4 x 23.9]

Water Inlet/Outlet Size (FPT) 0.5 0.5 0.5[1.27] [1.27] [1.27]

Filter (Disposable) 10 x 17 10 x 17 14 x 18[25.4 x 43.2] [25.4 x 43.2] [35.6 x 45.7]

Shipping Weight 100 104 171[45.4] [47.2] [77.6]

Electrical Data

Blower Performance Data

Physical Data

Model Fan Airflow (cfm) @ E.S.P. (in. wg)VLC09, 12 Speed 0.0 0.1 0.2 0.3 0.4 0.5

H 420 400 385 370 335 290

265V MH 400 390 375 350 325 280ML 380 360 330 310 280 265L 330 310 290 270 240 250H 400 380 360 240 300 260

230V MH 350 330 310 290 250 230ML 330 310 290 260 230 200L 290 270 250 225 210 -H 380 360 340 330 290 250

208V MH 320 300 280 265 225 220ML 300 280 260 230 220 -L 260 240 220 205 - -

VLC18H 670 650 640 590 530 460

265V M 610 600 580 540 490 420L 540 530 510 480 440 380H 750 700 660 610 560 490

230V M 680 660 620 580 525 460L 590 580 550 520 470 395H 680 650 620 575 520 450

208V M 600 580 560 520 470 415L 510 494 475 450 420 375

Fan Total MinRated Voltage Compressor

Motor Unit CircMax

ModelVoltage Min/Max MCC RLA LRA FLA FLA Amp

Fuse

VLC09 208-230/60/1 197 /253 5.5 3.5 20.0 0.6 4.1 5.0 1 02 6 5 / 6 0 / 1 239 /292 4.8 3.1 16.0 0.6 3.7 4.5 1 0

VLC12 208-230/60/1 197 /253 9.1 5.8 31.0 0.6 6.4 7.9 1 02 6 5 / 6 0 / 1 239 /292 5.5 3.5 22.0 0.6 4.1 5.0 1 0

VLC18 208-230/60/1 197 /254 14.0 9.0 48.0 1.1 10.1 12.3 2 02 6 5 / 6 0 / 1 239 /292 12.0 7.7 44.0 1.0 8.7 10.6 1 5

Notes: HACR circuit breaker in USA only. All fuses Class RK-5.

Notes: Dimensions in: Inches [cm], Ounces [kg], Square Feet [sq. meters], Pounds [kg]. Rev. 2/1/06

Page 10: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

10

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Correction Factors

Notes: Capacity data on pages 8-10 does not include water pumping watts and is based upon 15% methanol anti-freeze solution. For nonstandard airflow conditions, apply the appropriate correction factors found above. Interpolation between EWT, GPM and CFM data is permissible. LAT published is approximate only. Extrapolation for heating data down to 25° F is permissible. Catalog illustrations cover the general appearance of WaterFurnace products at time of publication. We reserve the right to make changes in design and construction at any time without notice.

CFM = airflow, cubic feet/minuteEWT = entering water temperature, FahrenheitGPM = water flow in gallons/minuteWPD = water pressure drop, PSI and feet of waterEAT = entering air temperature, °F (dry bulb/wet bulb)HC = air heating capacity, MBTUHTC = total cooling capacity, MBTUHSC = sensible cooling capacity, MBTUHKW = total power unit input, kilowattsHR = total heat of rejection, MBTUH

HE = total heat of extraction, MBTUHEER = Energy Efficient Ratio = BTU output/Watt inputCOP = Coefficient of Performance = BTU output/BTU inputLWT = leaving water temperature, °FLAT = leaving air temperature, °FTH = total heating capacity, MBTUHLC = latent cooling capacity, MBTUHS/T = sensible to total cooling ratio

Abbreviations and Definitions

Legend and Notes

Reference Calculations

Airflow Percent of Nominal CFM Correction 85% 90% 95% 100% 105% 110% 115%

Total Cooling Capacity 0.972 0.982 0.993 1.000 1.007 1.010 1.013Sensible Cooling Capacity 0.926 0.948 0.974 1.000 1.027 1.055 1.066

kW - Cooling 0.977 0.984 0.993 1.000 1.011 1.018 1.028Total Heat of Rejection 0.975 0.983 0.991 1.000 1.008 1.015 1.018Total Heating Capacity 0.967 0.978 0.990 1.000 1.990 1.017 1.024

kW - Heating 1.009 1.006 1.003 1.000 .997 .995 .993Total Heat of Absorption .967 .976 .989 1.000 1.010 1.019 1.025

LWT = EWT +

LAT (DB) = EAT (DB) -

LC = TC - SC

S/T =

Cooling Calculations:Heating Calculations:HR

GPM x 500

SCCFM x 1.08

SCTC

LAT = EAT +

HEGPM x 500

LWT = EWT -

HCCFM x 1.08

Page 11: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

11

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Capacity DataVLC09 at 350 CFM

W PD COOLING W PD HEATINGEWT GPMPSI FT EA TC SC KW HR EER

EWT GPMPSI FT EA HC KW HE LAT COP

75/63 9.8 7.2 0.64 12.0 15.3 60.0 6.1 0.65 3.9 76.3 2.771.5 2.7 6.3 80/67 10.6 7.5 0.65 12.9 16.3 1.5 3.0 6.9 70.0 6.0 0.68 3.6 85.8 2.56

85/71 11.5 7.8 0.67 13.8 17.2 80.0 5.8 0.72 3.3 95.3 2.3675/63 10.0 7.2 0.61 12.1 16.3 60.0 6.4 0.67 4.1 77.0 2.80

50 2.0 4.1 9.4 80/67 10.9 7.5 0.63 13.0 17.3 30 2.0 4.5 10.4 70.0 6.2 0.71 3.8 86.5 2.5985/71 11.7 7.8 0.64 13.9 18.3 80.0 6.0 0.74 3.5 96.0 2.3975/63 10.2 7.3 0.60 12.2 17.1 60.0 6.7 0.68 4.3 77.6 2.86

2.5 5.4 12.4 80/67 11.1 7.6 0.61 13.2 18.2 2.5 5.9 13.6 70.0 6.5 0.72 4.0 87.1 2.6485/71 12.0 7.9 0.62 14.1 19.3 80.0 6.3 0.75 3.7 96.6 2.4475/63 9.2 6.9 0.68 11.5 13.4 60.0 8.0 0.69 5.6 81.1 3.37

1.5 2.7 6.2 80/67 9.9 7.2 0.70 12.3 14.3 1.5 2.9 6.6 70.0 7.7 0.73 5.2 90.4 3.0985/71 10.7 7.5 0.71 13.2 15.1 80.0 7.4 0.77 4.8 99.7 2.8475/63 9.3 6.9 0.65 11.6 14.3 60.0 8.3 0.71 5.9 82.0 3.42

60 2.0 4.0 9.3 80/67 10.2 7.2 0.67 12.4 15.2 40 2.0 4.3 9.9 70.0 8.0 0.75 5.5 91.3 3.1485/71 11.0 7.5 0.68 13.3 16.1 80.0 7.8 0.79 5.1 100.5 2.8875/63 9.5 7.0 0.63 11.7 15.0 60.0 8.6 0.73 6.1 82.7 3.44

2.5 5.3 12.2 80/67 10.4 7.3 0.65 12.6 16.0 2.5 5.6 13.0 70.0 8.3 0.77 5.7 92.0 3.1785/71 11.2 7.6 0.66 13.5 16.9 80.0 8.0 0.81 5.3 101.2 2.9175/63 8.5 6.6 0.73 11.0 11.7 60.0 9.8 0.74 7.3 85.9 3.89

1.5 2.8 6.5 80/67 9.3 6.9 0.74 11.8 12.5 1.5 2.7 6.3 70.0 9.4 0.77 6.8 94.9 3.5785/71 10.0 7.2 0.76 12.6 13.2 80.0 9.1 0.81 6.3 104.0 3.2875/63 8.7 6.6 0.69 11.1 12.6 60.0 10.2 0.76 7.6 87.0 3.96

70 2.0 4.2 9.7 80/67 9.5 6.9 0.71 11.9 13.4 50 2.0 4.1 9.4 70.0 9.8 0.79 7.1 96.0 3.6385/71 10.2 7.2 0.72 12.7 14.2 80.0 9.5 0.83 6.6 105.1 3.3375/63 8.9 6.7 0.67 11.2 13.2 60.0 10.5 0.78 7.9 87.9 3.96

2.5 5.5 12.7 80/67 9.7 7.0 0.69 12.0 14.1 2.5 5.4 12.4 70.0 10.2 0.82 7.4 96.9 3.6285/71 10.4 7.3 0.70 12.8 14.9 80.0 9.8 0.86 6.8 105.9 3.3275/63 8.3 6.5 0.75 10.8 11.0 60.0 11.3 0.79 8.6 90.0 4.21

1.5 2.8 6.4 80/67 9.0 6.7 0.77 11.6 11.7 1.5 2.7 6.2 70.0 10.9 0.83 8.1 99.0 3.8685/71 9.7 7.0 0.78 12.4 12.4 80.0 10.6 0.87 7.6 107.9 3.5575/63 8.3 6.5 0.75 10.9 11.0 60.0 11.8 0.81 9.1 91.3 4.29

80 2.0 4.1 9.6 80/67 9.0 6.8 0.77 11.6 11.8 60 2.0 4.0 9.3 70.0 11.4 0.85 8.5 100.2 3.9485/71 9.7 7.0 0.78 12.4 12.5 80.0 11.0 0.89 8.0 109.2 3.6175/63 8.6 6.6 0.70 11.0 12.3 60.0 12.2 0.83 9.4 92.4 4.31

2.5 5.4 12.5 80/67 9.4 6.8 0.71 11.8 13.1 2.5 5.3 12.2 70.0 11.8 0.87 8.8 101.2 3.9585/71 10.1 7.1 0.73 12.6 13.9 80.0 11.4 0.92 8.3 110.1 3.6375/63 8.0 6.3 0.78 10.7 10.3 60.0 12.9 0.84 10.0 94.1 4.48

1.5 2.8 6.4 80/67 8.7 6.6 0.80 11.4 10.9 1.5 2.8 6.5 70.0 12.5 0.89 9.4 103.0 4.1285/71 9.4 6.8 0.81 12.2 11.6 80.0 12.0 0.93 8.9 111.9 3.7975/63 7.9 6.3 0.81 10.6 9.7 60.0 13.5 0.86 10.5 95.6 4.58

85 2.3 4.7 10.9 80/67 8.6 6.6 0.83 11.4 10.4 70 2.0 4.2 9.7 70.0 13.0 0.91 9.9 104.4 4.2085/71 9.3 6.9 0.84 12.1 11.0 80.0 12.6 0.95 9.3 113.3 3.8775/63 8.3 6.4 0.72 10.8 11.5 60.0 13.9 0.88 10.9 96.8 4.62

2.5 5.4 12.5 80/67 9.0 6.7 0.74 11.6 12.3 2.5 5.5 12.7 70.0 13.5 0.93 10.3 105.6 4.2585/71 9.8 6.9 0.75 12.3 13.0 80.0 13.0 0.97 9.7 114.4 3.9175/63 7.8 6.1 0.81 10.5 9.6 60.0 14.4 0.89 11.4 98.1 4.73

1.5 2.7 6.3 80/67 8.4 6.4 0.82 11.2 10.2 1.5 2.8 6.4 70.0 14.0 0.94 10.8 107.0 4.3685/71 9.1 6.7 0.84 12.0 10.8 80.0 13.5 0.99 10.2 115.8 4.0375/63 7.8 6.1 0.76 10.5 10.3 60.0 14.8 0.87 11.9 99.2 5.02

90 2.0 4.1 9.4 80/67 8.5 6.4 0.78 11.2 11.0 80 2.0 4.1 9.6 70.0 14.4 0.91 11.3 108.0 4.6285/71 9.2 6.7 0.79 11.9 11.6 80.0 13.9 0.96 10.6 116.8 4.2675/63 8.0 6.2 0.75 10.6 10.8 60.0 15.2 0.88 12.2 100.2 5.04

2.5 5.3 12.4 80/67 8.7 6.5 0.76 11.3 11.5 2.5 5.4 12.5 70.0 14.7 0.93 11.6 109.0 4.6485/71 9.4 6.8 0.78 12.1 12.2 80.0 14.3 0.98 10.9 117.7 4.2775/63 7.3 5.8 0.84 10.2 8.6 60.0 15.9 0.94 12.7 102.1 4.96

1.5 2.7 6.2 80/67 7.9 6.1 0.86 10.9 9.2 1.5 2.7 6.3 70.0 15.5 0.99 12.1 111.0 4.5885/71 8.5 6.3 0.88 11.5 9.7 80.0 15.0 1.04 11.5 119.8 4.2475/63 7.4 5.8 0.80 10.2 9.2 60.0 16.2 0.87 13.2 102.8 5.46

100 2.0 4.0 9.3 80/67 8.1 6.1 0.82 10.9 9.8 90 2.0 4.1 9.4 70.0 15.7 0.91 12.6 111.5 5.0385/71 8.7 6.3 0.84 11.6 10.4 80.0 15.2 0.96 12.0 120.3 4.6575/63 7.6 5.9 0.78 10.2 9.7 60.0 16.5 0.89 13.5 103.6 5.45

2.5 5.3 12.2 80/67 8.2 6.2 0.80 10.9 10.3 2.5 5.3 12.4 70.0 16.0 0.93 12.8 112.4 5.0385/71 8.9 6.4 0.81 11.7 10.9 80.0 15.5 0.98 12.2 121.1 4.6475/63 6.8 5.5 0.88 9.8 7.7

1.5 2.6 6.1 80/67 7.4 5.7 0.90 10.5 8.285/71 8.0 5.9 0.92 11.1 8.775/63 7.0 5.5 0.84 9.9 8.3

110 2.0 4.0 9.1 80/67 7.6 5.7 0.86 10.5 8.885/71 8.2 5.9 0.88 11.2 9.475/63 7.1 5.6 0.82 9.9 8.7

2.5 5.2 12.0 80/67 7.7 5.8 0.83 10.6 9.285/71 8.3 6.0 0.85 11.2 9.8

Notes: Multiple Flow Rates (for EWT) are shown in tables. The lowest flow rate shown is used for geothermal open loop/ well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for boiler tower applications.

Page 12: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

1�

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Capacity Data (cont.)VLC12 at 375 CFM

W PD COOLING W PD HEATINGEWT GPMPSI FT EA TC SC KW HR EER

EWT GPMPSI FT EA HC KW HE LAT COP

50 30

60 40

70 50

80 60

85 70

90 80

100 90

110

75/63 12.0 8.1 1.00 15.4 11.91.5 2.7 6.3 80/67 13.0 8.5 1.03 16.5 12.7

85/71 14.0 8.8 1.05 17.6 13.475/63 11.3 8.2 0.97 14.6 11.6

2.5 55.0 127.1 80/67 12.3 8.6 0.99 15.7 12.485/71 13.3 8.9 1.01 16.7 13.175/63 11.5 8.3 0.94 14.8 12.2

3.5 8.8 20.4 80/67 12.5 8.6 0.96 15.8 13.085/71 13.5 9.0 0.98 16.9 13.875/63 11.3 7.8 1.08 15.0 10.5

1.5 2.7 6.2 80/67 12.3 8.2 1.10 16.0 11.285/71 13.3 8.5 1.12 17.1 11.975/63 11.1 7.9 1.03 14.6 10.7

2.5 5.3 12.2 80/67 12.0 8.3 1.05 15.6 11.485/71 13.0 8.6 1.07 16.6 12.175/63 11.3 8.0 1.00 14.7 11.3

3.5 8.7 20.1 80/67 12.3 8.3 1.02 15.8 12.085/71 13.3 8.7 1.04 16.8 12.775/63 10.7 7.6 1.15 14.6 9.3

1.5 2.8 6.5 80/67 11.6 7.9 1.17 15.6 9.985/71 12.5 8.2 1.19 16.6 10.575/63 10.8 7.6 1.09 14.5 9.9

2.5 5.5 12.7 80/67 11.8 8.0 1.11 15.6 10.685/71 12.7 8.3 1.13 16.6 11.275/63 11.1 7.7 1.06 14.7 10.5

3.5 9.0 20.8 80/67 12.0 8.0 1.08 15.7 11.185/71 13.0 8.4 1.10 16.8 11.875/63 10.3 7.4 1.20 14.4 8.6

1.5 2.8 6.4 80/67 11.2 7.7 1.23 15.4 9.285/71 12.1 8.0 1.25 16.4 9.775/63 10.6 7.4 1.13 14.5 9.4

2.5 5.4 12.5 80/67 11.5 7.7 1.15 15.5 10.085/71 12.4 8.0 1.18 16.5 10.675/63 10.7 7.6 1.11 14.5 9.7

3.5 8.9 20.5 80/67 11.7 7.9 1.13 15.5 10.485/71 12.6 8.2 1.15 16.5 11.075/63 10.0 7.3 1.26 14.3 8.0

1.5 2.8 6.4 80/67 10.9 7.6 1.28 15.2 8.585/71 11.7 7.9 1.31 16.2 9.075/63 10.4 7.2 1.17 14.4 8.9

3.2 7.5 17.3 80/67 11.3 7.5 1.19 15.4 9.485/71 12.2 7.8 1.22 16.3 10.075/63 10.4 7.4 1.15 14.3 9.0

3.5 8.9 20.5 80/67 11.3 7.8 1.17 15.3 9.685/71 12.2 8.1 1.20 16.3 10.275/63 9.7 7.1 1.31 14.1 7.4

1.5 2.7 6.3 80/67 10.5 7.4 1.34 15.1 7.885/71 11.3 7.7 1.37 16.0 8.375/63 9.9 7.2 1.25 14.2 7.9

2.5 5.3 12.4 80/67 10.8 7.5 1.28 15.1 8.485/71 11.6 7.8 1.30 16.1 8.975/63 10.1 7.3 1.20 14.2 8.4

3.5 8.7 20.2 80/67 11.0 7.6 1.22 15.1 9.085/71 11.8 7.9 1.25 16.1 9.575/63 9.1 6.8 1.39 13.8 6.5

1.5 2.7 6.2 80/67 9.9 7.1 1.42 14.7 6.985/71 10.7 7.4 1.45 15.6 7.375/63 9.3 6.9 1.33 13.8 7.0

2.5 5.3 12.2 80/67 10.1 7.2 1.36 14.7 7.485/71 10.9 7.5 1.39 15.6 7.975/63 9.5 7.0 1.27 13.8 7.4

3.5 8.6 19.9 80/67 10.3 7.3 1.30 14.7 7.985/71 11.1 7.6 1.33 15.6 8.475/63 8.5 6.5 1.48 13.5 5.8

1.5 2.6 6.1 80/67 9.2 6.7 1.51 14.4 6.185/71 10.0 7.0 1.54 15.2 6.575/63 8.7 6.6 1.41 13.5 6.1

2.5 5.2 12.0 80/67 9.4 6.8 1.44 14.3 6.585/71 10.2 7.1 1.47 15.2 6.975/63 8.8 6.6 1.35 13.4 6.5

3.5 8.5 19.6 80/67 9.6 6.9 1.38 14.3 7.085/71 10.4 7.2 1.41 15.2 7.4

60.0 9.6 0.93 6.4 83.7 3.031.5 3.0 6.9 70.0 9.3 0.98 6.0 93.0 2.79

80.0 9.0 1.03 5.5 102.2 2.5760.0 10.1 0.96 6.9 85.0 3.10

2.5 5.9 13.6 70.0 9.8 1.01 6.3 94.2 2.8580.0 9.5 1.06 5.8 103.3 2.6260.0 10.5 0.98 7.2 85.9 3.15

3.5 9.7 22.4 70.0 10.1 1.03 6.6 95.0 2.8980.0 9.8 1.08 6.1 104.2 2.6660.0 11.3 1.02 7.8 87.9 3.24

1.5 2.9 6.6 70.0 10.9 1.08 7.3 97.0 2.9880.0 10.6 1.13 6.7 106.1 2.7460.0 11.9 1.06 8.3 89.3 3.29

2.5 5.6 13.0 70.0 11.5 1.11 7.7 98.4 3.0380.0 11.1 1.17 7.1 107.4 2.7960.0 12.2 1.08 8.5 90.2 3.33

3.5 9.3 21.4 70.0 11.8 1.13 8.0 99.3 3.0680.0 11.4 1.19 7.4 108.3 2.8260.0 13.0 1.12 9.2 92.1 3.41

1.5 2.7 6.3 70.0 12.6 1.18 8.6 101.1 3.1480.0 12.2 1.24 8.0 110.1 2.8960.0 13.6 1.16 9.7 93.7 3.45

2.5 5.4 12.4 70.0 13.2 1.22 9.0 102.6 3.1880.0 12.8 1.28 8.4 111.6 2.9360.0 14.0 1.18 10.0 94.6 3.49

3.5 8.8 20.4 70.0 13.6 1.24 9.3 103.5 3.2180.0 13.1 1.30 8.7 112.4 2.9660.0 14.6 1.22 10.4 96.1 3.51

1.5 2.7 6.2 70.0 14.2 1.28 9.8 105.0 3.2480.0 13.8 1.35 9.2 114.0 2.9960.0 15.3 1.26 11.0 97.8 3.56

2.5 5.3 12.2 70.0 14.8 1.33 10.3 106.7 3.2880.0 14.4 1.39 9.7 115.6 3.0360.0 15.6 1.28 11.3 98.6 3.59

3.5 8.7 20.1 70.0 15.2 1.35 10.6 107.5 3.3180.0 14.7 1.41 9.9 116.4 3.0660.0 16.2 1.32 11.7 100.0 3.59

1.5 2.8 6.5 70.0 15.8 1.39 11.0 108.9 3.3280.0 15.3 1.46 10.4 117.9 3.0860.0 16.9 1.36 12.3 101.8 3.64

2.5 5.5 12.7 70.0 16.5 1.43 11.6 110.7 3.3780.0 16.0 1.51 10.9 119.6 3.1260.0 17.3 1.38 12.6 102.7 3.67

3.5 9.0 20.8 70.0 16.8 1.45 11.9 111.5 3.3980.0 16.4 1.53 11.2 120.4 3.1460.0 17.7 1.41 12.9 103.7 3.67

1.5 2.8 6.4 70.0 17.3 1.49 12.2 112.7 3.4180.0 16.9 1.56 11.5 121.7 3.1760.0 18.5 1.46 13.5 105.6 3.71

2.5 5.4 12.5 70.0 18.0 1.54 12.8 114.5 3.4480.0 17.6 1.61 12.1 123.4 3.2060.0 18.9 1.48 13.8 106.6 3.72

3.5 8.9 20.5 70.0 18.4 1.56 13.1 115.4 3.4580.0 17.9 1.64 12.4 124.3 3.2160.0 19.2 1.50 14.1 107.5 3.74

1.5 2.7 6.3 70.0 18.8 1.58 13.4 116.5 3.4880.0 18.4 1.66 12.7 125.5 3.2560.0 20.0 1.56 14.7 109.4 3.77

2.5 5.3 12.4 70.0 19.6 1.64 14.0 118.3 3.5080.0 19.2 1.72 13.3 127.3 3.2760.0 20.4 1.59 15.0 110.4 3.77

3.5 8.7 20.2 70.0 20.0 1.67 14.3 119.3 3.5180.0 19.5 1.75 13.6 128.3 3.27

Notes: Multiple Flow Rates (for EWT) are shown in tables. The lowest flow rate shown is used for geothermal open loop/ well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for boiler tower applications.

Page 13: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

1�

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Capacity Data (cont.)VLC18 at 600 CFM

W PD COOLING W PD HEATINGEWT GPMPSI FT EA TC SC KW HR EER

EWT GPMPSI FT EA HC KW HE LAT COP

50 30

60 40

70 50

80 60

90 70

100 80

110 90

75/63 20.5 13.6 1.33 25.1 15.43.0 3.4 7.9 80/67 22.3 14.1 1.36 27.0 16.5

85/71 24.1 14.7 1.38 28.8 17.475/63 20.5 13.6 1.26 24.8 16.3

4.0 5.4 12.6 80/67 22.3 14.1 1.29 26.7 17.385/71 24.1 14.7 1.31 28.6 18.475/63 20.6 13.7 1.22 24.8 16.9

5.0 8.6 19.9 80/67 22.4 14.2 1.25 26.7 18.085/71 24.2 14.8 1.27 28.6 19.175/63 19.5 13.2 1.42 24.3 13.7

3.0 3.4 7.8 80/67 21.2 13.7 1.45 26.1 14.685/71 22.9 14.3 1.48 27.9 15.475/63 19.5 13.2 1.36 24.2 14.4

4.0 5.4 12.4 80/67 21.2 13.7 1.39 26.0 15.385/71 22.9 14.3 1.42 27.8 16.275/63 19.7 13.3 1.32 24.2 14.9

5.0 8.5 19.6 80/67 21.4 13.8 1.35 26.0 15.885/71 23.1 14.4 1.38 27.8 16.875/63 18.4 12.8 1.52 23.6 12.1

3.0 3.1 7.2 80/67 20.0 13.3 1.55 25.3 12.985/71 21.6 13.8 1.58 27.0 13.775/63 18.5 12.8 1.46 23.5 12.7

4.0 5.1 11.8 80/67 20.1 13.3 1.49 25.2 13.585/71 21.7 13.8 1.52 26.9 14.375/63 18.7 12.9 1.42 23.6 13.1

5.0 8.0 18.4 80/67 20.3 13.4 1.45 25.3 14.085/71 21.9 14.0 1.48 27.0 14.875/63 17.1 12.3 1.62 22.6 10.6

3.0 3.1 7.1 80/67 18.6 12.8 1.65 24.2 11.385/71 20.1 13.3 1.68 25.8 12.075/63 17.3 12.3 1.55 22.6 11.1

4.0 5.0 11.6 80/67 18.8 12.8 1.58 24.2 11.985/71 20.3 13.3 1.62 25.8 12.675/63 17.5 12.5 1.52 22.7 11.5

5.0 7.8 18.1 80/67 19.0 13.0 1.56 24.3 12.285/71 20.5 13.5 1.59 25.9 12.975/63 15.8 11.9 1.71 21.7 9.3

3.0 3.0 7.0 80/67 17.2 12.4 1.75 23.2 9.985/71 18.6 12.9 1.78 24.7 10.475/63 16.1 11.9 1.65 21.7 9.8

4.0 4.9 11.4 80/67 17.5 12.4 1.68 23.2 10.485/71 18.9 12.9 1.71 24.7 11.075/63 16.2 12.0 1.62 21.8 10.0

5.0 7.5 17.3 80/67 17.7 12.5 1.66 23.3 10.785/71 19.1 13.0 1.69 24.8 11.375/63 14.3 11.2 1.80 20.5 8.0

3.0 3.0 6.9 80/67 15.6 11.7 1.83 21.8 8.585/71 16.8 12.2 1.87 23.2 9.075/63 14.6 11.2 1.74 20.5 8.4

4.0 4.9 11.3 80/67 15.9 11.7 1.77 21.9 9.085/71 17.2 12.2 1.81 23.3 9.575/63 14.8 11.4 1.72 20.7 8.6

5.0 7.6 17.6 80/67 16.1 11.9 1.75 22.1 9.285/71 17.4 12.3 1.79 23.5 9.775/63 12.8 10.6 1.88 19.3 6.8

3.0 2.9 6.8 80/67 14.0 11.0 1.92 20.5 7.385/71 15.1 11.5 1.96 21.8 7.775/63 13.2 10.6 1.83 19.4 7.2

4.0 4.8 11.1 80/67 14.3 11.0 1.87 20.7 7.785/71 15.4 11.5 1.90 21.9 8.175/63 13.4 10.8 1.81 19.6 7.4

5.0 6.5 15.0 80/67 14.5 11.2 1.85 20.8 7.985/71 15.7 11.7 1.88 22.1 8.3

60.0 14.0 1.30 9.6 77.3 3.163.0 3.7 8.7 70.0 13.6 1.37 8.9 86.7 2.90

80.0 13.1 1.44 8.2 96.2 2.6760.0 14.4 1.30 9.9 77.7 3.24

4.0 5.7 13.1 70.0 13.9 1.37 9.2 87.1 2.9780.0 13.4 1.44 8.5 96.5 2.7360.0 14.8 1.32 10.3 78.2 3.28

5.0 9.2 21.3 70.0 14.2 1.39 9.5 87.6 3.0180.0 13.7 1.46 8.8 96.9 2.7660.0 16.9 1.41 12.1 80.9 3.52

3.0 3.6 8.3 70.0 16.3 1.48 11.2 90.1 3.2280.0 15.7 1.56 10.4 99.4 2.9660.0 17.3 1.41 12.5 81.4 3.60

4.0 5.4 12.5 70.0 16.7 1.48 11.6 90.6 3.3080.0 16.1 1.56 10.8 99.8 3.0360.0 17.7 1.43 12.9 81.9 3.64

5.0 8.8 20.3 70.0 17.2 1.50 12.0 91.2 3.3580.0 16.5 1.58 11.1 100.4 3.0760.0 19.7 1.52 14.5 84.4 3.81

3.0 3.4 7.9 70.0 19.0 1.60 13.6 93.5 3.5080.0 18.4 1.68 12.6 102.7 3.2160.0 20.2 1.52 15.1 85.0 3.91

4.0 5.4 12.6 70.0 19.5 1.60 14.1 94.1 3.5880.0 18.8 1.68 13.1 103.2 3.2960.0 20.8 1.54 15.6 85.7 3.97

5.0 8.6 19.9 70.0 20.1 1.62 14.5 94.8 3.6380.0 19.3 1.70 13.5 103.9 3.3360.0 22.4 1.61 16.8 87.6 4.06

3.0 3.4 7.8 70.0 21.6 1.70 15.8 96.7 3.7380.0 20.9 1.78 14.8 105.8 3.4360.0 23.0 1.62 17.4 88.4 4.15

4.0 5.4 12.4 70.0 22.2 1.71 16.4 97.4 3.8180.0 21.4 1.79 15.3 106.4 3.5060.0 23.6 1.64 18.0 89.2 4.21

5.0 8.5 19.6 70.0 22.8 1.73 16.9 98.2 3.8780.0 22.0 1.82 15.8 107.2 3.5560.0 25.0 1.71 19.1 90.8 4.28

3.0 3.1 7.2 70.0 24.2 1.80 18.0 99.9 3.9480.0 23.4 1.89 17.0 108.9 3.6360.0 25.7 1.73 19.8 91.7 4.36

4.0 5.1 11.8 70.0 24.9 1.82 18.7 100.7 4.0180.0 24.1 1.91 17.6 109.7 3.7060.0 26.4 1.75 20.5 92.6 4.43

5.0 8.0 18.4 70.0 25.6 1.84 19.3 101.6 4.0780.0 24.7 1.93 18.1 110.5 3.7560.0 27.2 1.81 21.1 93.6 4.41

3.0 3.1 7.1 70.0 26.5 1.91 20.0 102.7 4.0780.0 25.7 2.00 18.9 111.7 3.7660.0 28.1 1.83 21.8 94.7 4.49

4.0 5.0 11.6 70.0 27.3 1.93 20.7 103.7 4.1480.0 26.5 2.03 19.6 112.7 3.8360.0 28.8 1.85 22.5 95.5 4.55

5.0 7.8 18.1 70.0 28.0 1.95 21.3 104.5 4.2080.0 27.1 2.05 20.1 113.5 3.8860.0 29.5 1.91 23.0 96.4 4.52

3.0 3.0 7.0 70.0 28.8 2.01 21.9 105.5 4.1980.0 28.0 2.11 20.8 114.6 3.8860.0 30.5 1.94 23.8 97.6 4.60

4.0 4.9 11.4 70.0 29.7 2.04 22.7 106.6 4.2680.0 28.9 2.14 21.6 115.7 3.9560.0 31.1 1.96 24.5 98.4 4.66

5.0 7.5 17.3 70.0 30.3 2.06 23.3 107.4 4.3180.0 29.5 2.17 22.1 116.4 3.99

Notes: Multiple Flow Rates (for EWT) are shown in tables. The lowest flow rate shown is used for geothermal open loop/ well water systems with a minimum 50° F. The second flow rate shown is the minimum geothermal closed loop flow rate. The third flow rate shown is optimum for geothermal closed loop and the suggested flow rate for boiler tower applications.

Page 14: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

14

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Wiring SchematicVersatec Compact Horizontal 208-230, 265/60/197P643-02 11/6/03

Factory low voltage wiring

LegendSwitch - High pressure

Switch - Low pressure

Relay coil

Field wire lug

Ground

Relay Contacts -N.O., N.C.

Polarized connector

Notes:1 - Switch blue and red wires for 208 V operation.Factory line voltage wiring

Field low voltage wiringField line voltage wiringOptional blockQuick connect terminal

Wire nut

Screw terminal -field connection

CC -HP -LP -RB -RV -TB -

Compressor contactorHigh pressure switchLow pressure switchBlower relayReversing valve coilTerminal board

Blue230 V

TransformerNOTE 1

Red208 V

BlackCom

Compressor

UnitPower Supply

208-230-265/60/1

Capacitor

CC

T1

L1

T2

Tan

L2G

C

R

S

BlackRed

Blue

L1

132

P

CCM - Compressor Control Module

PS - Power strip

265 V

2 - Refer to installation manual for fan speed settings.

Capacitor

RB

Black

Brown

Cap

BrownWhite

PSCFan Motor

Green

MH L

3 Air flowSettings

COM

NO

White

Common

Reversing Valve

Run Signal

Compressor

Fault Signal

24V

Yellow24 VAC

TB

O

C

Y1

G

S

L

R

COMPRESSORCONTROL MODULE

TESTPIN

HP

HP

CC

CG

LOR

CLP

LPY

HP

HP

CC

CG

LOR

CLP

LPY

CC

HP

LP

Black/White

GreenRed

Green

Red

Brown

Brown

Blk/WhtViolet

BlackBlackBlueBlue

YellowYellow

Orange

Orange

Pink

RBViolet

Violet

Fan

RV

Cap

Brn

Wh

WhBlk

Red

Grn

3 24 1 C

Yel 4 Air FlowSettings

Blu

PSCFan Motor

NOTE 3

White

Black

3 - Motor wiring for 09 and 12 unit sizes.

Green

Page 15: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

15

VERSATEC COMPACT HORIZONTAL SPECIFICATION CATALOG

Engineering Guide SpecificationsGeneral

The water source heating/cooling units shall be a re-verse cycle suspended type with horizontal air inlet and discharge. Units shall be designed to operate with liquid temperatures between 25°F and 110°F and listed by a nationally recognized safety testing laboratory or agency, such as ETL Testing Laboratory. Each unit shall be com-puter run-tested at the factory, and mounted on a pallet, and stretch wrapped for shipping.

An optional additional four-year warranty covering the compressor and major parts shall be available.

Casing & CabinetThe cabinet shall be fabricated from heavy-gauge

galvanized steel. The interior shall be insulated with 1/2" thick, multi-density, coated glass fiber with edges sealed or tucked under flanges. Access panels shall be provided and be removable with supply and return ductwork in place. A 1" duct collar shall be provided on the supply air opening. Standard-size filters (1") shall be provided. Units shall have a filter bracket. Units shall have a right air inlet and side or end air discharge.

Refrigerant CircuitAll units shall contain a sealed refrigerant circuit includ-

ing a hermetic motor-compressor, bidirectional thermal ex-pansion valve, finned tube air-to-refrigerant heat exchang-er, reversing valve, and a coaxial tube water-to-refrigerant heat exchanger.

Compressors shall be high-efficiency, designed for heat pump duty and mounted on vibration isolators. Compres-sor motors shall be single-phase with internal overload protection. The finned tube coil shall be sized for low-face velocity.

The coaxial water-to-refrigerant heat exchanger shall be designed for close approach temperatures, constructed of a convoluted copper (optional cupronickel) inner tube and a steel outer tube, and capable of 450 psi water and

refrigerant working pressures. The thermal expansion valve shall provide proper superheat over the entire liquid temperature range with minimal “hunting.” The valve shall operate bi-directionally without the use of check valves. Externally mounted pressure regulating flow control valves are not acceptable.

The water-to-refrigerant heat exchanger and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures.

Fan Motor and AssemblyThe fan shall be direct drive with a dynamically balanced

wheel. The housing and wheel shall be designed for quiet, low outlet velocity operation. The fan motor shall operate at multiple speeds, be high-efficiency, provide high static capability, include three or four on-motor selectable airflow options, be permanently lubricated, have thermal overload protection and be isolated from the housing by rubber grommets.

ElectricalA terminal block with screw terminals shall be provided for

field low-voltage wiring, and a 75VA low-voltage transformer shall be provided. Line voltage box lugs shall be provided for unit wiring. Units shall have knockouts for entrance of low and line voltage wiring.

PipingSupply and return water connections shall be copper

threaded fittings (1/2" FPT) mechanically fastened to unit cabinet, eliminating the need for backup wrenches when making field piping connections. Threaded copper adap-tors shall be low-temperature soldered to prevent misshap-ing or weakening of the fitting, eliminating potential start up leaks.

All water piping shall be insulated to prevent condensation at low liquid temperatures. The condensate connection shall be flush mounted 3/4" FPT and must be trapped externally.

Control OperationHeating Operation Heat, First Stage (Y)

Fan motor is started, and the compressor is energized.

Cooling OperationCool, First Stage (Y, O)

Fan motor is started, and the reversing valve and com-pressor are energized.

Fan OperationFan Only (G)

The fan is energized and operates continuously.

Lockout ConditionsHigh Pressure

This lockout mode occurs when the normally closed safety switch is opened momentarily (15 psig).Low Pressure

This lockout mode occurs when the normally closed safety switch is opened for 30 continous seconds.

Page 16: Versatec Compact Horizontal Specification Catalog · As a leader in the industry, WaterFurnace is dedicated to innovation, quality and customer satisfaction. In fact, every unit built

WaterFurnace International, Inc.9000 Conservation WayFort Wayne, IN 46809www.waterfurnace.com

Product: VersatecType: Compact Horizontal Water Source Heat PumpsSize: ¾ through 1½ Tons

Document Type: Specification CatalogPart Number: SP1408Release Date: 02/06Supercedes: WF1408 (05/03)

WFI has a policy of continuous product research and development and reserves the right to change design and specifications without notice. ©2006 WFI.