variable primary flow.ppt

58
Proprietary & Confidential 1 Johnson Control s 1 Continuous Acceleration of Skills for Higher earnings Johnson Controls ® Building Simplified

Upload: alfredo-merizalde-aviles

Post on 28-Jan-2016

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Variable Primary Flow.ppt

Proprietary & Confidential1Johnson Controls

1

Continuous

Acceleration of

Skills for

Higher earnings

Johnson Controls ®

Building Simplified

Page 2: Variable Primary Flow.ppt

Add Photo/Graphic

Presentation Title

Presenters:Andrew Clancy, Business Development Sr Manager - NavyScott Schmittel, Account ExecutiveJason Richwine , Application Engineer

Page 3: Variable Primary Flow.ppt

Proprietary & Confidential

Consulting Engineer’s Office

3

Page 4: Variable Primary Flow.ppt

Proprietary & Confidential

The Project

University Classroom Building

Central Chilled Water Plant

This building cannot be connected

Cooling tower will not work

Variable Primary Flow

4

Page 5: Variable Primary Flow.ppt

Proprietary & Confidential

Discovery

5

Scott Branch Account Manager - Buddy

Page 6: Variable Primary Flow.ppt

Proprietary & Confidential

Discovery

Low Delta T Syndrome

300Tons – Cooling

Two 150 Ton Chillers

Scroll

Screw

6

Page 7: Variable Primary Flow.ppt

Proprietary & Confidential

Johnson Controls Capabilities

7

Dave Jason Richwine

Page 8: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

Constant Speed Primary Pumps

Variable Speed Secondary Pumps

Common Pipe

Typical load with two way valves

Page 9: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System at Design

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

1080 GPM @ 54.0 °F

Secondary Pumps

1080 GPM @ 44.0 °F

Typical Coil

No flow

44.0 °F

54.0 °F

150 ton chillers360 GPM Each54.0-44.0°F

1080 GPM @ 54.0 °F

Page 10: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System at Part Load

51.5 °F

51.5 °F

51.5 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

1080 GPM @ 51.5 °F

Secondary Pumps

810 GPM @ 44.0 °F

Typical Coil

44.0 °F

54.0 °F

270 GPM @ 44.0 °F

810 GPM @ 54.0 °F

75% System Load

Page 11: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

54.0 °F

54.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

720 GPM @ 54.0 °F

Secondary Pumps

720 GPM @ 44.0 °F

Typical Coil

44.0 °F

54.0 °F

No Flow

720 GPM @ 54.0 °F

OFF 67% System LoadClean Coils

Page 12: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

54.0 °F

54.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

720 GPM @ 54.0 °F

Secondary Pumps

792 GPM @ 44.0 °F

Typical Coil

44.0 °F

53.0 °F

72 GPM @ 53.0 °F

792 GPM @ 53.0 °F

OFF 67% System LoadDirty Coils

Page 13: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

53.0 °F

53.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

720 GPM @ 53.0 °F

Secondary Pumps

792 GPM @ 44.8 °F

Typical Coil

44.8 °F

53.0 °F

72 GPM @ 53.0 °F

792 GPM @ 53.0 °F

OFF 67% System LoadDirty Coils

Page 14: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

51.9 °F

51.9 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

720 GPM @ 51.9 °F

Secondary Pumps

900 GPM @ 44.8 °F

Typical Coil

44.8 °F

51.9 °F

180 GPM @ 51.9 °F

900 GPM @ 51.9 °F

OFF 67% System LoadDirty Coils

Page 15: Variable Primary Flow.ppt

Proprietary & Confidential

Primary/Secondary System

Variable Primary System

Secondary Pumps

Primary Pumps

Primary Pumps

Flow Meter

BypassValve

Automatic Isolation Valve

Typical load with 2 way valve

Typical load with 2 way valve

Page 16: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System at Design

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

1080 GPM @ 56.0 °F

1080 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

150 ton chillers360 GPM Each54.0-44.0°F

Typical load with two way valves

Page 17: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Part Load

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

270 GPM Each

810 GPM @ 54.0 °F

810 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve

75% System Load

810 GPM @ 54.0 °F

Page 18: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Part Load

54.0 °F

54.0 °F

44.0 °F

44.0 °F

Primary Pumps

180 GPM Each

540 GPM @ 54.0 °F

540 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve

50% System LoadChiller off

540 GPM @ 54.0 °F

Page 19: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Min Flow (120 gpm each)

51.5 °F

44.0 °F

Primary Pumps

120 GPM (one operating)

120 GPM @ 51.5 °F

90 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Open

Typical load with two way valve

System flow below chiller minimum flow

Chiller off

Chiller off

Closed

Closed

30 GPM @ 44.0

90 GPM @ 54.0 °FFlow meter

Pumps off

Page 20: Variable Primary Flow.ppt

Proprietary & Confidential

Designing a VPF Bypass

Size for minimum flow through one chiller

Bypass valve shall be the normally open type

Valve head ratings must be higher than pump dead head

Linear characteristic - valve position % equals flow %

Fast actuator

Valve control range 100:1

Flow meter controls bypass to maintain chiller minimum flow

Page 21: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Min Flow (120 gpm each)

51.5 °F

44.0 °F

Primary Pumps

120 GPM (one operating)

120 GPM @ 51.5 °F

90 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Open

Typical load with two way valve

Pumps maintain system pressure

Bypass maintains minimum flow

Chiller off

Chiller off

Closed

Closed

30 GPM @ 44.0

90 GPM @ 54.0 °FFlow meter

Pumps off

Page 22: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a VPF Flow Meter for Small Tonnage Systems

Best accuracy job can afford

Minimum +/- 5% at evaporator minimum flow

Set bypass to open when flow equals minimum plus 2 times flow meter accuracy rating

Example: 120 gpm minimum, flow meter +/- 5%, set minimum flow at 120 + 120*10% = 132 gpm

Calibrate flow meter at least as often as manufacturer recommends

Buy the best

Page 23: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting VPF AHU Control Valves

All valve pressure ratings greater than pump dead head

Sized by pressure

% valve position equals % coil capacity

Control range 200:1

Page 24: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting VPF Chiller Isolation Valves

All valve pressure ratings greater than pump dead head

Linear characteristic - valve position % equals flow %

Modulating valve with slow actuator

Page 25: Variable Primary Flow.ppt

Proprietary & Confidential

VPF Design Considerations

Flow rate changes – Staging on additional chillers

Page 26: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (1 chiller running)

54.0 °F

44.0 °F

Primary Pumps

120 GPM Each

360 GPM @ 546.0 °F

360 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve360 GPM

Page 27: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Staging on second chiller)

54.0 °F

45.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 55.0 °F

396 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve396 GPM

Need to add chiller

Page 28: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

55.0 °F

35.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 55.0 °F

396 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve198 GPM

198 GPM55.0 °F

55.0 °F

Page 29: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

55.0 °F

35.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 55.0 °F

396 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve198 GPM

198 GPM55.0 °F

55.0 °F

LCHWT approaches 35F

LWT Cutout at 40F

Off goes chiller 1

Page 30: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

55.0 °F

40.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 55.0 °F

396 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve264 GPM

132 GPM55.0 °F

55.0 °F

Open slowly

Chiller 2 comes on when flow exceeds minimum

Chiller 1 unloads to maintain set point

Page 31: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

54.0 °F

44.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 54.0 °F

396 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve198 GPM

198 GPM44.0 °F

54.0 °F

Both valves fully open

Flow equalizes

Chillers modulate to maintain chilled water set point

Page 32: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

55.0 °F

42.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 55.0 °F

396 GPM @ 45.9 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve276 GPM

120 GPM55.0 °F

55.0 °F

Open to change flow 36gpm/min

Chiller 2 comes on when flow is 120gpm – in 3 min 20 sec

Chiller 1 is still producing 100% capacity

Page 33: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System (Open isolation valve)

54.0 °F

44.0 °F

Primary Pumps

132 GPM Each

396 GPM @ 54.0 °F

396 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve198 GPM

198 GPM44.0 °F

54.0 °F

Both valves fully open

Flow equalizes

Chillers modulate to maintain chilled water set point

Page 34: Variable Primary Flow.ppt

Proprietary & Confidential

Staging on Chiller 2 in VPF Systems

Maintain minimum flow through the operating chiller

Avoid sudden changes in flow anywhere in the system

Prefer schemes that work when bringing on any chiller

Page 35: Variable Primary Flow.ppt

Proprietary & Confidential

Setting Flow Rate of Change

Start with 10% of design flow per minute

YORK small tonnage chillers can handle faster changes

If the project requires rapid flow changes, contact application engineering

If problems occur during operation, adjust the rate

Page 36: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Handling Rapidly Decreasing Loads

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

1080 GPM @ 56.0 °F

1080 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

150 ton chillers360 GPM Each54.0-44.0°F

Typical load with two way valves

Page 37: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Handling Rapidly Decreasing Loads

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

360 GPM Each

1080 GPM @ 44.0 °F

0 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Open

150 ton chillers360 GPM Each54.0-44.0°F

Typical load with two way valves

Page 38: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Handling Rapidly Decreasing Loads

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

324 GPM Each

972 GPM @ 44.0 °F

972 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valves

Close the closest valve first

Page 39: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Handling Rapidly Decreasing Loads

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

288 GPM Each

864 GPM @ 44.0 °F

864 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valves

Close the next closest valve

Page 40: Variable Primary Flow.ppt

Proprietary & Confidential

Variable Primary System – Handling Rapidly Decreasing Loads

54.0 °F

54.0 °F

54.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

252 GPM Each

756 GPM @ 44.0 °F

756 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valves

Close the next closest valve

Page 41: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Look at all applicable selections

Evaluate based on full load performance

Evaluate based on part load performance

Evaluate based on evaporator minimum flow

Evaluate based on required temperature control accuracy

Page 42: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 43: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 44: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 45: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 46: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 47: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 48: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 49: Variable Primary Flow.ppt

Proprietary & Confidential

Selecting a Small Tonnage Chiller for VPF

Page 50: Variable Primary Flow.ppt

Proprietary & Confidential

Optimizing Air-cooled Chiller Operation

Optimize Chiller Efficiency

Optimize Pump Efficiency

Define loading and unloading sequences

Model annual energy use

Page 51: Variable Primary Flow.ppt

Proprietary & Confidential

Optimizing Air-cooled Chiller Operation

Chiller is more efficient at 80% than at 40% for the given ambient temperature.

Page 52: Variable Primary Flow.ppt

Proprietary & Confidential

288 GPM

Optimizing Air-cooled Chiller Operation

9 Ft. Head

288 GPM144 GPM each 2.5 Ft. Head

Page 53: Variable Primary Flow.ppt

Proprietary & Confidential

Optimizing Air-cooled Chiller Operation

Chiller is more efficient at 40% than at 80% for the given ambient temperature.

Page 54: Variable Primary Flow.ppt

Proprietary & Confidential

Optimizing Air-cooled Chiller Operation

Page 55: Variable Primary Flow.ppt

Proprietary & Confidential

STC Special Case – How would you design this system?

The Setup 20 ton VPF cooling system

One chiller, one AHU

44F chilled water with 54F return

Chiller has two scroll compressors (0%, 50%, or 100% capacity)

The Problem Load remains constant at around 55% or 60% for several hours

Chiller can’t meet demand with one compressor on

Chiller severely over-cools with both compressors on

System is unstable

The Hint Start by thinking about how increasing system water volume can add stability

Page 56: Variable Primary Flow.ppt

Proprietary & Confidential

Summary

How VPF systems work

How to select control components for system stability

How to sequence chillers on and off

How to control the chillers, pumps, and valves

How to size the bypass

56

Page 57: Variable Primary Flow.ppt

Proprietary & Confidential57

Quiz

1. Must Open ‘New’ Browser Window by clicking on:

2. Access CASH Website for Quiz

To start the quiz, click on the to the right of the quiz title

3. Please complete the quiz at your leisure.

Page 58: Variable Primary Flow.ppt

Proprietary & Confidential58

Question & Answer Time

Open Forum

To ask a question:

• Raise your WebEx “Hand” to ask a question

• You will be recognized at which point you

may proceed to ask your question