Variable Frequency Drives (VFDs)Limi t s and Pot ent ial Consequences
November 13, 2017
J. Clark Maness, EIStaff Professional, WithersRavenel
PRESENTATION
2
T O P I C SBackground
Why use a VFD ?
Typical Problems with VFDs
Examples
3
• VFD: Variable Frequency Drive, also known as: Adjustable Frequency Drive, Variable Speed Drive, AC Drive, etc.
• VFDs are adjustable speed drives used in elect ro-mechanical systems to control AC motor speed and torque
• In the water/wastewater industry, commonly used for controlling pump and blower motor speed, i.e., process control
ht tps:/ /en.wikipedia.org/wiki/Variable-frequency_drive#/media/File:HitachiJ100A.jpg
BACKGROUNDW h at i s a V FD ?
4
BACKGROUNDHow do VFDs w or k?
5
BACKGROUNDHow do VFDs w or k?
6
7
8
9
10
11
12
13
On average, the bursts of DC power create a sinusoidal form of AC current . The imitat ion AC sine wave is called pulse width modulat ion.
14
• To control the speed and torque of the most common motor in industry.
3-Phase Induction Motor
W hy use a V FD?
15
16
• VFDs are good for many applications
• However, VFDs do have a host of issues and can potentially be more harmful than helpful.
Ty p i cal Pr ob l ems
ht tp:/ /www.variablefrequencydrive.org/image/variable-frequency-drive.jpg
17
Bear ing Damage – Induced Shaf t Vol t age • Less than perfect sinusoidal waves produce eddy currents that• Damage can be prevented with insulated bearings or shaft brush bearings
POTENTIAL VFD PROBLEMS
18
I ncr eased M ot or Cool i ng Requi r ed • Below 25hz motor fan speed will not cool motor• Supplementary fan required• Added cost of drive, cable, SCA, controls, access and maintenance• Reduced reliability
http:/ /www.machinedesign.com/sites/machinedesign.com/files/uploads/2014/02/FIG02-Leeson-3-phase.t iff_.jpg
POTENTIAL VFD PROBLEMS
19
Har monics• All VFDs draw harmonic currents which distort voltage supply.
• Harmonic distort ions cause excessive heating of supply equipment and/or malfunction of motor.
• Also reduces overall efficiency of motor.
• Typical Correct ive Measures (increased drive cost):
• Series Reactors • Phase shift ing transformers and six-phase rect ificat ion• Shunt Filters• Active Filters
POTENTIAL VFD PROBLEMS
20
I ncr eased Noise • Due to the harmonics, the motor noise level will increase when it is operated using a VFD• Experience shows that the sound pressure level at A scale at motor rated speed is increased by
anything between 2 and 15dBA with a VFD • This “ extra ” noise level depends mainly on the inverter switching frequency and harmonic
content .• Noise mit igat ion costs increase
POTENTIAL VFD PROBLEMS
21
Ot her• Need for HVAC condit ioned building or panel to house VFDs (higher capital costs)
• Larger control cabinet required for applicat ion
• Increased overall operat ions complexity
POTENTIAL VFD PROBLEMS
22
• Flow Control Valve
• Bypass valves
• Holding tank
• Pump for longer periods
• Change pump impeller diameter
• Alternate pump type
• Newly sized pumps
ALTERNATIVE SOLUTIONS
23
Wetwell
Forcemain
Flow = 200 gpmTDH = 58 feet Motor Speed = 1800 rpm
Ex a m p l e 1Change in Pump Purpose
24
Wetwell
Headworks System (Screenings, Grit , and FOG
Removal)
Flow = 200 gpmTDH = 32 feet Motor Speed = turned down to 1,200 rpm
VFD
Change in Pump Purpose
Ex a m p l e 1
25
Well Pump Stat ion and Storage Tank
Ex a m p l e 2
Well pump 20,000 gal tank
• Well pump stat ion and storage tank provided adequate storage for site
• However, needed to provide enough water at 300 gpm 60 psi to feed sprinkler systems in camp cabins
26
Ex a m p l e 2
Well pump 20,000 gal tank
Booster pumps
4,000 gal hydropneumatic
tank
66 to 86 psi
Cabin sprinklers
VFD • VFDs allowed booster pumps to feed pressurized tank at varying head demands
Well Pump Stat ion and Storage Tank
27
Exist ing Duplex Pump Stat ion
Exist ing 16” FM
Ex a m p l e 3
Exist ing WWTP
• Exist ing Pump Stat ion pumped 162,000 gpd on average, but sized for 725,760 gpd.
• To allow development in Town and not increase capacity of exist ing WWTP needed to redirect flow to a different WWTP
28
Exist ing Duplex Pump Stat ion
New 8” FM
Ex a m p l e 3
Other WWTP
• Cost effect ive solut ion: Install a new wetwell and divert in new forcemain. • Added VFDs to keep constant level (but not a necessary component).• However, VFD created overheating of other components in building and loss of
efficiency with harmonics.• Had to install a harmonic filter to limit voltage fluctuat ion (increased cost).
Exist ing 12” GMNew 12”
GM
New Simplex Pump Stat ion
VFD
VFDs have some drawbacks. Therefore, all scenarios should be considered on a case by case basis, and all reasonable options should be considered.
29
30
Special thanks to Charles R. Underwood
Inc. for their insight and help
VFDs
31
32
VFDs
33
Pump Curve 1: VFD use is viable
34
Pump Curve 3: Pump Oversize
35
Pump Curve 2: VFD use is not viable