Columbia Concrete Products - Variable Frequency Drive 5/06 Page 1 This manual provides installation and operation information applicable to the Columbia Variable Frequency Drive. TABLE OF CONTENTS Control Pod ................................................................................................ 2 Display Mode ............................................................................................. 5 Edit Mode ................................................................................................... 6 Warning Mode ............................................................................................ 7 Warning Codes ........................................................................................... 7 Trip Mode ................................................................................................... 7 Compression Test ....................................................................................... 8 Fill Test ..................................................................................................... 10 Trip Codes ................................................................................................ 12 Installation Tips ......................................................................................... 15 Maintenance Tips ...................................................................................... 16 Troubleshooting Tips ................................................................................. 17 Variable Frequency Drive For use with Block Machines Columbia Machine, Inc. Vancouver, Washington

Upload: others

Post on 13-Jun-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 1

This manual provides installation and operation information applicableto the Columbia Variable Frequency Drive.

TABLE OF CONTENTS

Control Pod ................................................................................................ 2

Display Mode ............................................................................................. 5

Edit Mode ................................................................................................... 6

Warning Mode ............................................................................................ 7

Warning Codes........................................................................................... 7

Trip Mode ................................................................................................... 7

Compression Test ....................................................................................... 8

Fill Test ..................................................................................................... 10

Trip Codes................................................................................................ 12

Installation Tips ......................................................................................... 15

Maintenance Tips...................................................................................... 16

Troubleshooting Tips ................................................................................. 17

Variable Frequency DriveFor use with Block Machines

Columbia Machine, Inc.Vancouver, Washington

Page 2: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 2 5/06

Control Pod

The Control Pod is a device consisting of a display and keypad used for thefollowing:

• Reading and changing the values of software parameters thatare used to configure, control, and monitor the (VFD) VariableFrequency Drive

• Displaying the operating status of the VFD• Displaying fault and trip codes

A VFD parameter is similar to a PLC address (N10;7 - “Feed Drawer Dwell Time”,etc.). VFD parameters for block machines can be found in the block machineschematics.

The display has three display modes:• Basic Mode - used to indicate the status of the VFD• Display Mode - used for selecting a parameter to edit• Edit Mode - used for editing the selected parameter

The programming keys are used for:• Changing the mode of operation of the display• Selecting a parameter to edit• Editing the selected parameter• Saving new values given to parameters

Always warm-up vibrator shaft before start of shift. Warm-up vibratorshaft by running vibrator at fill speed for a couple of minutes oruntil the vibrator motor amp draw falls well below the motor ratedFull Load Amps shown on the motor nameplate. To monitor vibratormotor amp draw go to paramter 4.01. If the VFD trips when firststarted due to over current condition (AI.AC) with an extremelycold vibrator shaft, slow down fill speed for vibrator warm-up.

WARNING

Page 3: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 3

The five (5) programming keys perform the following functions:

• • changes the VFD mode from display to Edit modeand also acts as a save key after edit has beenmade.

• • selects a parameter• increases the value of a digit

• • selects a parameter• decrease the value of a digit

• • displays a parameter number• selects the next left display digit• selects another menu

• • displays the parameter number• selects the next right display digit• selects another menu

The three (3) Control keys perform the following functions:

• The RUN key activates the Drive. The RUN key isactive only when the Drive is operating in the keypadmode.

• The STOP-RESET button performs three functions:• stop the Drive• reset the Drive after it has tripped• saves new parameters after edits are made

• The FWD/REV key changes the direction of the rotationof the motor. (This is not enabled by default)

FWD/REV

STOP-RESET

RUN

PROGRAMMING

Page 4: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 4 5/06

In order to access various Control Pod modes, use the following steps:

1) Turn the unit on. The unit begins in the “Basic” mode. In theBasic mode, line 1 displays the parameter value (see “A” inthe illustration below). Line 2 displays the status of the VFD(see “B” in the illustration below).

2) Press the key (see “C” in the illustration) to changefrom the Basic mode to the Display mode.

C

B

A

Page 5: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 5

Display Mode

In the Display mode:

1) Line 1 (see “A” in the illustration below) displays the parametervalue.

2) Line 2 (see “B” in the illustration below) displays the menu itemnumber in the first two digits.

3) Line 2 (see “B” in the illustration below) displays theparameter number in the last two digits.

4) The key (see “C” in the illustration below) allows theoperator to change from the Display mode to the Edit mode.The Control Pod returns to the Basic Mode 8 seconds after thelast keystroke.

5) The keys (see “D” in the illustration below)allows the operator to change to the desired menu, whichappears in the first two digit places of line 2 of the digitaldisplay (see “B” in the illustration below).

6) The keys (see “E” in the illustration on thebelow) allows the operator to change to the desired parameternumber in the last two digits of line 2 of the digital display (see“B” in the illustration below).

C

B

A

D

E

Page 6: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 6 5/06

Edit Mode

In the Edit mode:

1) Line 1 (see “A” in the illustration below) displays the parametervalue.

2) Line 2 (see “B” in the illustration below) displays the menu itemnumber in the first two digits.

3) Line 2 (see “B” in the illustration below) displays the parameternumber in the last two digits.

4) The key (see “C” in the illustration below) allows the

operator to change from the Edit mode back to the Displaymode. The Control Pod returns to the Basic Mode 8 secondsafter the last keystroke. To save edits:

1) Enter 1000 in the 00.00 parameter2) Page to the Display mode3) Push the Stop-Reset button

5) The

keys (see “D” in the illustration below)

allow the operator to select and edit the value of the digit online 1. The selected digit will flash.

6) The

keys (see “E” in the illustration below)allow

the operator to increase or decrease the value of the selecteddigit.

C

B

A

D

E

Rdy

Page 7: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 7

Trip Mode

The VFD is disabled in the Trip Mode, resulting in the motor decelerating to a stop.The LED display shows trip code information (see the illustration below). Push thereset button to re-enable the VFD.

See the following page 12 for Trip Codes.

Warning Mode

In the warning mode, the VFD flashes a warning code on line 2 of the LED display(see “B” in the illustration).The VFD remains enabled, but may trip if the faultindicated by the warning code is not corrected. The warning codes are as follows:

Warning Codes

DISPLAY FAULT

br.rs Braking resistor overload

Ovld 1 x t - motor overload

The VFD generates this indication when the output current of theconverter is higher than the rated motor current and the overloadaccumulator value has reached 75%.

This indication is a warning that the motor will trip because of over-load when there is no load reduction.

hot Heatsink over-temperature

This indicates that the heatsink has reached a temperature of 95°Cand that the drive is still overloaded.

Air Ambient over-temperature

RESET

TRIP MESSAGE

TRIP CODE TriP

Trip 0

Page 8: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 8 5/06

COMPRESSION TEST

OBJECTIVE: To determine the optimum vibrator compression speed forshortest compression time on a given product.

THEORY: The proper fill speed and feed drawer dwell time have, fromprevious tests, been determined. This will assure that, withthese variables set as determined, the proper amount ofmaterial has been deposited into the mold. We must nowvary the com-pression speed on the vibrator motor to determine which compression speed results in the shortest compression time.

PROCEDURE: 1) Record product description and date on compressiontest data sheet.

2) Set fill speed and feed drawer dwell at optimumsettings as determined in fill test. Retain these settings for the duration of this test.

3) Set compression speed at 3000 RPM and recordcompression time.

4) Repeat Step 3 for successively lower compressionspeeds (2800, 2600, etc.) as indicated on the datasheet.

5) Plot results on the data sheet graph.

6) Determine optimum compression speed. This speedwill be at the lowest point on the graph. If this point isnot obvious, run additional tests at compressingspeeds between the lowest points on the graph (recording each compression speed and compressingtime) until satisfied that the optimum compressionspeed has been determined. Record this speed onthe data sheet.

Optimum fill and compression speeds are likely to vary withproduct dimensions and between cored and solid productsof the same dimensions. Therefore, these tests should beperformed on each product category. This test procedureassumes that the vibrator continued to run when fill is com-plete, continuing right on into compression (no double start).In the event that double start is being used (for pavers forexample), use the duration of the first vibrator instead of feeddrawer dwell in the fill test.

NOTE

Page 9: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 9

Page 10: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 10 5/06

VARIABLE SPEED DRIVE TEST PROCEDURE

FILL TEST

OBJECTIVE: To determine optimum vibrator motor speed for quickestmold fill on a given product.

THEORY: There are many combinations of vibrator fill speed and feeddrawer dwell which will result in the proper amount of materialbeing deposited into the mold. Proper mold fill is attainedwhen the compression time matches the established standardfor the particular product being produced. Since theestablished standard compression time is based on a variablespeed of 3000 RPM, this fill test should be run at 3000RPM compression speed.

PROCEDURE: 1) Record product description and date on fill test datasheet.

2) Set compression speed at 3000 RPM for the durationof this test.

3) Set fill speed at 3000 RPM and find feed drawer dwelltime which results in desired compression time.Record this feed drawer dwell time on the data sheet.

4) Repeat Step 3 for successily lower fill speeds (2800,2600, etc.) as indicated on the data sheet.

5) Plot results on the data sheet graph.

6) Determine optimum fill speed. This speed will be atthe lowest point on the graph. If this point is not obvious,run additional tests at fill speeds between the lowestpoints on the graph (recording each fill speed and feeddrawer dwell) until satisfied that the optimum fill speedhas been determined. Record this speed on the datasheet.

Page 11: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 11

Page 12: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 12 5/06

Trip Codes

Page 13: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 13

Page 14: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 14 5/06

Page 15: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 15

Installation Tips

During installation make sure all VFD panel conduit entries are dust tight. Cementdust can travel long distances through the inside of conduit so after installationmonitor the VFD panel to make sure cement dust is not entering the VFD panelthrough the various conduits. Cement dust damages a VFD in a couple ways:

1. The keys in the keypad become sticky

2. When enough cement dust accumulates on the electronic componentsoverheating of the components occurs causing damage

THE VFD WARRANTY WILL NOT BE HONORED IF VFD FAILS DUE TOEXCESSIVE CEMENT DUST BUILD UP ON VFD COMPONENTS.

Page 16: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 16 5/06

Maintenance Tips

If cement dust build up inside the VFD panel is observed take corrective action,(see installation tip above) then blow the cement dust out of the panel.

Always keep the VFD panel door shut with door clips tightened to keep out dust.

If cement dust accumulates on the VFD heat sinks on the back of the VFD panelblow off heat sinks. If cement dust build up occurs fairly quickly (within one month)take measures to reduce VFD panel exposure to cement dust if possible.Excessive cement dust exposure may cause the cooling fans in the heat sinks to failprematurely.

Page 17: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

5/06 Page 17

TroubleShooting Tips (USED ON CPM & BLOCK MACHINES)

Most service calls on the VFD problems usually fall under the following categories, thefirst two being the most common:

1. SLOW ACCELERATION AT BEGINNING OF SHIFT - Typically this happens in cold weather. Tosolve the problem reduce vibrator speed to roughly 1,000 RPM and run for one totwo minutes to warm up the vibrator shaft grease or oil.

2. DECELERATION TIME TO SHORT - Sometimes customer wants to extend decelerationtime to help strip product. Add more time to parameter 0.04 as required. Also thestrip delay time in the PLC can be increased to give the vibrator more time tocome to a stop if necessary.

3. SLOW ACCELERATION - This happens when there is a drop in plant voltage.

4. O1.AC FAULT CODE - This an Over Current Fault. This is the VFD giving warningthat an excessive amount of current is being required by the motor and motordamage may result. This is often caused by bad vibrator shaft bearings. Theprocedure to verify it’s the vibrator bearings’ causing the fault is to do thefollowing:

A. Get the motor nameplate full load amps (FLA), then use an amp probe or goto parameter 0-12 to see what vibrator motor running amps are, thencompare. If the running amps are more than nameplate FLA something isputting an excessive load on the VFD.

B. Disconnect the drive belt and check the vibrator motor running amps. Runningamps should be about half of nameplate FLA with belt disconnected.

If the running amps are high with belt disconnected the fault is most likely causedby a vibrator motor problem (see step 8). If the running amps return to normal withthe belt disconnected the fault is most likely caused be bad vibrator bearings. Theproblem may also be improper grease or excessive pallet table air pressure settingsor a new vibrator shaft has been installed and need to be broke in.

5. OU FAULT CODE - This is a DC buss over voltage fault typically caused by anoverheated braking resistor. This could be caused by the braking resistor havingan accumulation of cement dust.

6. AO2 FAULT CODE - This is an heat sink over temperature fault typically caused by abuild up of cement dust in the VFD heat sink or cooling fins.

7. VIBRATOR COG BELT BREAKS - Lengthen S ramp time (parameter 0.19) to .2 seconds,replace cog belt with Kraft belt.

Page 18: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Columbia Concrete Products - Variable Frequency Drive

Page 18 5/06

8. VFD GOES DEAD BUT COMES BACK TO LIFE IF YOU CYCLE POWER - If you encounter this problemand you have verified it’s not a problem with the 3 phase contactor supplying powerto the VFD, order a new VFD because it is about to fail, be sure to include theserial # of the bad drive on the CSA and return to Columbia.

9. ON A DUAL MOTOR, SINGLE VFD PANEL THE MANUAL MOTOR PROTECTOR FOR ONE OF THE

MOTORS TRIPS - A motor coupler has failed so the vibrator motor with the good couplingis doing all the work or one of the motors may be defective.

10.VIBRATOR MOTOR RUNS AT A MUCH LOWER RPM THAN CALLED FOR, TWO OF THE MOTOR LEADS

SHOW VERY HIGH AMP DRAW AND ONE LEAD SHOWS NO AMP DRAW - Bad vibrator motor.

11. VFD DISPLAYS THE “RUN” MESSAGE BUT NO OUTPUT TO MOTOR is given (RPM display staysat 0) there may be a problem with the speed reference wiring which comes fromeither potentiometers on the VFD panel or a PLC analog signal. If the wiring appearsto be OK and a bad VFD is suspected do the following: Change parameter 1.14from 0 to 4 which put the VFD in keypad mode. Now use the keypad on the front ofthe VFD to operate the VFD. With the VFD in the “Rdy” mode push the greenbutton then push the up arrow until the desired speed is reached. If the VFD operatescorrectly the problem is in the speed reference wiring. If the VFD fails to operatefrom the keypad the VFD may be defective.

12.THE PLC GIVES THE COMMAND TO START THE VIBRATOR BUT THE VFD DOESN’T DISPLAY THE “RUN”MESSAGE. Verify the PLC output is on for either Fill or Compression speed. If theoutput is on, check that the Fill or Compression relay is latching. If the relays arelatching check wiring between relays and VFD terminals (push up on VFD signalwire terminals to make sure they are snapped in place).

If the above measures fail to isolate a vibration system problem a more extremetechnique is to bypass the VFD and operate the vibrator motor with an appropriatelysized across the line starter to determine if the fault lies with the VFD or vibratorbearings (or motor). An across the line starter can also be used to operate the blockmachine at a slower cycle rate if a VFD failure is encountered in a location whereshipping a replacement VFD across a border causes delays.

Be sure and give the Columbia Service Department the serial # (found on top, rightcover of the VFD) when requesting a replacement VFD under warranty.

Page 19: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 1 of 8

VFD TROUBLE SHOOTING MANUAL: INITIAL VFD DIAGNOSTICS VFD Status Page 2 VFD Trip Codes Page 2 Common VFD Terminology Page 2 Initial VFD Diagnostics Pages 3

Process of elimination – VFD, Motor, vibrator shaft Pages 3 & 4 VFD Trip Codes (Troubleshooting) Pages 4 & 5 VFD Alarm Warning Codes (Troubleshooting) Page 5 & 6 Common VFD Issues Page 6 & 7 UN-Common VFD Conditions Page 7 Returning a Drive Page 8

Page 20: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 2 of 8

VFD STATUS Display Description inh Inhibit Mode VFD waiting for “Drive Enable” signal (power flow at terminal B4) rdy Ready Mode VFD waiting for “Run Enable” signal (power flow terminals B3 & B5) run Run Mode VFD running if “Speed Reference” received (power flow at terminals B5) VFD TRIP CODES Display Description Possible Solutions O1.AC VFD Over Current Extend Accel ramp or check for bad vibrator shaft bearings. OH2 Heat Sink Over Temp Clean Heat Sinks OA VFD Over Temp Check enclosure temp r.S. Loose Wire Check Wiring It.AC Motor Overload Extend Accel time (parameter 0.03) th Motor Over Temp Check motor temp OU DC Buss Over Voltage Extend decal ramp. COMMON VFD TERMINOLOGY Display Description HOT BRAKING RESISTOR

Braking resistor should only get hot on deceleration of motor. Bleed off from motor decelerating is discharged thru the braking resistor .If Resistor is heating up but motor is not running – VFD has probably failed. If resistor is too hot resistor’s thermistor will trip and cut off power to VFD. DARK DISPLAY - If display is dark – and motor is running, only the display has failed. If motor is not running, and has 480volts at input to drive, then VFD is probably dead. Check incoming voltage – if 480volts not present – determine why voltage is not 480. Tripped brake resistor?? SHELF LIFE: Capacitors run “dry” after a year. You need to hook your spare VFD to 3 phase (380-460) at least once a year. The dryer the capacitor, the greater the chance for the VFD to fail when power is applied. . VFD: Variable frequency drive.

Page 21: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 3 of 8

INITIAL VFD DIAGNOSTICS Try to determine if the problem is really with the VFD or is it the motor or vibrator shaft.

1_ Is the incoming voltage correct? (Check all three legs for equal voltage) 2_ What is the amp output to the vibrator motor under load (during compression)?

Process of elimination – VFD, Motor, vibrator shaft:

A. If vibrator fails to achieve the desired RPM, and the Amp output is above motor nameplate Full Load Amps -

>> Then the VFD is OK and the problem is the motor or vibrator shaft.

• If the vibrator belt is disconnected, and the amps remain high,

>> the motor is the problem. Motor bearings??

• If the vibrator belt is disconnected, and the amps within motor name plate,

>> the motor is okay, so the vibrator shaft is the problem.

B. If the vibrator fails to achieve the desired RPM, and the Amp output is below motor nameplate Full Load Amps – >> The VFD is the problem.

• At this point verify the VFD is getting the speed reference for compression speed.

• This is done by observing the VFD display. It should display the compression speed called for.

If not, check the potentiometer or analog signal. (CPM uses analog signal from the PLC, Block machine uses a set of Potentiometers)

• If the correct speed is being displayed but not achieved,

Reset the VFD parameters back to factory presets load (U.S.A into parameter 29) and reprogram the VFD as shown on parameter sheet of machine wiring schematics.

Listed below are the most common VFD problems encountered: 1_ Slow acceleration at beginning of shift –

• Typically this happens in cold weather. To solve the problem reduce vibrator speed to

roughly 1,000 RPM and run for a minute or two to warm up the vibrator shaft grease or oil at the beginning of the shift.

Page 22: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 4 of 8

2_ Deceleration time too short – Sometimes customers want to extend Deceleration time to help strip product. Add more time to parameter 0.04 as required. Also the strip delay time in the PLC can be increased to give the vibrator more time to come to a stop if necessary.

3_ Slow acceleration at install –

A. lower than expected plant voltage (if present check isolation transformers tap settings). B. less than ideal sheave ratio.

• Because the easiest change to make in the field is changing sheave ratio. This has been the solution at some plants. With a 1 to 1 sheave ratio Motor torque falls off above 1800 RPM making it difficult to achieve 3,000RPM if the plant voltage is lower than expected. The 1 to 1.6 ratio we used on older machines works better at high RPM than the 1 to 1 ratio but has reduced pull up torque. At present new equipment has been designed to 1 to 1.36 sheave ratio. The 1 to 1.36 sheave ratio has been found to be the ideal ratio for this application. Columbia Machine Typically oversize’s our VFD’s enough so any ratio will work.

• Another possible solution is to provide an isolation transformer to boost voltage to 460V.

A higher voltage into the VFD gives a higher VFD voltage output to the motor increasing the vibrator motors ability to develop the power needed at RPM's above 1,800RPM.

VFD TRIP CODES

O1.AC fault code – over current fault. POSSIBLE CAUSES

1. Bad vibrator shaft bearings. 2. Vibrator motor has bad bearings. 3. Improper or excessively thick shaft grease. 4. Excessive pallet table air pressure. 5. Short circuit in motor winding’s.

TROUBLESHOOTING

Step 1: Compare nameplate & actual running amps. Get the motor nameplate FLA from motor nameplate or refer to schematic. Then use an amp probe to see what the vibrator motor running amps are. This can also be done by holding the ‘M” key for two seconds on the Drive’s display. Drive will then display amps in place of RPM’s. Step 2: If the running amps are more than nameplate FLA something is putting an excessive load on the motor, in most cases it is bad bearings either in the motor or vibrator shaft (GO TO STEP 3). If fault code occurs while powering up VFD panel. (GO TO STEP 6).

Step 3: Remove belt from vibrator shaft and run vibrator motor on compression speed simulating an automatic function for several cycles. If amps continue to be higher than motor FLA the motor has probably failed. (GO TO STEP 5) if amps are lower than motor name plate (GO TO STEP 4)

Page 23: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 5 of 8

Step 4: After completing step 3 and the motor amps are not above the motor nameplate you probably have bad vibrator shaft bearings. This can be confirmed by using a temperature gun to measure the temperature of the Vibrator shaft bearing housing. Temperature should not exceed 155 degrees Fahrenheit or 68 degrees Celsius on a forced lube shaft. On a greased shaft the bearing temperatures should not exceed 200 degrees Fahrenheit or 94 degrees Celsius. In either case if the bearing temperatures exceed the listed limits the bearings need replacement. Step 5: Power down the VFD panel lock out and tag out the VFD disconnect. Wait for VFD Capacitors to bleed down (approximately 20 minutes). Disconnect wires leading to VFD motor/motors and safely secure them in such a way that the leads cannot touch output of VFD drive in any way. (step 5 continued) Power the VFD panel up and once again jog the Compression speed simulating the automatic function of the machine. If the Drive fault has stopped then the Motor has failed and needs replacement. If drive fault persists the Drive has failed and needs replacement. Step 6: If the O1.AC fault code is displayed at power up the VFD has detected a direct short, most likely in the motor windings (GO TO STEP 5).

OV fault code – (may appear as OU) dc buss over over voltage fault. POSSIBLE CAUSES

1. Accumulation of cement dust on braking resistor 2. Open circuit in braking resistor wiring

TROUBLESHOOTING

Step 1: Power down VFD lock out and tag out the VFD disconnect. Blow Cement dust off of braking resistor. If problem persists (GO TO STEP 2). Step 2: Power down VFD lock out and tag out the VFD disconnect. Check for open circuit in braking resistor. If problem persists (GO TO STEP 3). Step 3:.Extend time in VFD parameter 04 to continue operating.

OH2 or OHT2 fault code – heat sink over temperature fault

The heat sink over temperature fault is caused by typically caused by a build up of cement dust in the VFD heat sink or cooling fins.

Note: See OV fault code – (may appear as OU) step 1 thru 3. VFD ALARM WARNING CODES

OVL.D warning code – (may appear as OUL.D) motor overload warning. POSSIBLE CAUSES

1. Motor is at 105 percent of rated current. 2. Worn vibrator shaft bearings. 3. Vibrator motor has worn bearings.

Page 24: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 6 of 8

TROUBLESHOOTING

Step 1: See trouble shooting O1.AC steps 1 thru 6. Step 2: Extend time in parameter 03 or 62 to continue operation.

HOT warning code – Heat sink over temp POSSIBLE CAUSES

1. Accumulation of cement dust on VFD heat sinks.

TROUBLESHOOTING Step 1: Blow dust off of heat sinks. Step 2: Remove from direct sunlight.

BR.RS warning code – Braking resistor overload POSSIBLE CAUSES

1. Accumulation of cement dust on braking resistor.

TROUBLESHOOTING Step 1: Blow dust off of resistor.

Ac.lt warning code – Drive is in current limit POSSIBLE CAUSES

1. Worn vibrator shaft bearings. 2. Vibrator motor has worn bearings. 3. Ratios are less than ideal.

TROUBLESHOOTING

Step 1: Extend time in parameter 03 or 62 to continue operation. Step 2: See trouble shooting O1.AC steps 1 thru 6.

COMMON VFD ISSUES The VFD goes dead but comes back to life if you cycle power –

If you encounter this problem and you have verified it’s not a problem with the 3 phase contactor supplying power to the VFD, get a new VFD in the mail. The one you have isn't healthy. Contact Columbia Machine. Be sure and include the serial # of the bad drive.

On a CPM VFD panel the Manual Motor Protector for one of the motors trips, or the vibrator runs at a much lower RPM then is called for

Page 25: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 7 of 8

POSSIBLE CAUSES

1. A motor coupler has failed so the vibrator motor with the good coupling is doing all the work.

TROUBLESHOOTING

Step 1: Power down VFD and lock out any CPM controls. lock out and tag out the VFD disconnect. Raise stripper beam and begin inspecting the couplings in the Vibrator assembly. Replace bad coupler or (GO TO STEP 2).

Step 2: An Amp probe can be placed on all three legs of suspected motor (one leg at a time). One leg will typically indicate no current on one leg. No current on any leg indicates a failed vibrator motor. Replace Motor.

VFD supply fuses blow or trips Drive Motor Starter Protector with no load on VFD – Defective VFD, Contact Columbia Machine. Be sure and include the serial # of the bad drive.

VFD suddenly operates differently.

POSSIBLE CAUSES 1. Someone has altered the drive parameters in advertently. 2. Drive parameter has been change but not recorded since last power cycle.

TROUBLESHOOTING

Step 1: Reenter drive parameters from Schematic. (GO TO STEP 2).

Step 2: Default drive at parameter 29 and reenter parameters. VFD fails to operate and displays “inh”

This indicates a problem with the wiring to the VFD enable input (B3) (B5). This circuit typically contains motor starter overload and auxiliary contacts and may also include a lube pump interlock. These items may be bypassed temporarily in order to isolate a field wiring problem. Also sometimes that VFD control wire terminal strip comes loose and needs to be reseated UNCOMMON VFD CONDITIONS

With VFD problems that don’t fit the above examples, often times the problem is either cement dust builds up in the VFD or someone has accidentally made an unwanted parameter change. If cement dust build up is noted blow off the VFD inside and out. Typically the cement enters the panel through conduit entries in the top of the panel. If a parameter error is suspected, clear the VFD parameters and reprogram as shown on the parameter sheet provided with the block equipment.

Page 26: Variable Frequency Drive For use with Block Machines · Columbia Concrete Products - Variable Frequency Drive Page 2 5/06 Control Pod The Control Pod is a device consisting of a display

Control Techniques - VFD Troubleshooting - Nov 17, 2011 Page 8 of 8

RETURNING A DRIVE Get PO Number. __________________________ Get Serial Number or old drive _______________ Get Model Type __________________________ Contact names ________________________ Swap for new drive model – _ need adaptor plate?? _________ _ Drawings ? part numbers ---- NOTES: