valid from manual type updated€¦ · heat recovery cell 3 bypass flap 4 supply air filter g4 6...
TRANSCRIPT
Manual
MA
NU
AL
Ventilation unit
DocumentD4686
Valid from02.10.2017
Updated12.2.2018
Model Vallox 101 MC RVallox 101 MC L
Type3740
2
MA
IN PA
RTS
Extract air fan1
Supply air fan2
Supply air filter F7 5
Heat recovery cell
3
Bypass flap
4
Supply air filter G46
Extract air filter G47
8
Post-heating radiator (in the supply air duct)
9
Safety switch
10
Supply air heating adjustment
11
Supply/extract air flow adjustment
R model in the figure.
In the L model, the parts are mirrored
WARNING!The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit. Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety.
7
5
6
11
10
8
9
12
13
14
Vallox Simple Control control panel (ordered separately)
Vallox ProControl control panel (ordered separately)
Vallox Capto PTC EC control hood, Vallox X-Line PTXP MC control hood, or Vallox X-Line PTXPA MC control hood (ordered separately)
12
14
13
Vallox X-Line PTXP MC Vallox X-Line PTXPA MC (optional)
Vallox Capto PTC EC (optional)
(optional) (optional)
2
3
4
1
3 © Vallox Oy - All rights reserved
USIN
G TH
E UN
IT
The fan speed of the Vallox ventilation unit is adjusted using a four-step control.
The available speed options of the control switch are 1, 2, 3, and 4:
1. Away mode. The ventilation efficiency can be temporarily reduced when the apartment is unoccupied.
2-3. Standard mode. In standard mode, the air inside the apartment is replaced once every two hours.
4. Boost mode. Cooking, sauna, bathing, drying of clothes, guests, and other similar situations can require that ventilation be increased from the standard setting.
The fan speed can also be controlled through a separate Vallox control hood, the Vallox ProControl control panel, or directly through voltage messages (0-10 V).
Vallox Simple Control control panel
The temperature of the air blown into the apartment can be adjusted approximately between +10 °C and +30 °C. The unit has an automatic summer/winter function (a bypass flap).
• When the adjusted temperature is between +10 °C and +30 °C, the heat recovery cell is not bypassed, i.e. the unit is in winter mode.
• In the OFF position, the unit is in the summer mode, i.e. post-heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above +14 °C. The heat recovery will be turned on when the outdoor temperature falls below +12 °C.
• In the AUTO position, the unit will operate as follows around the year: The default post-heating setting is +17 °C. The unit will bypass the heat recovery cell when the temperature of the outdoor air exceeds +14 °C. The heat recovery will be turned on when the outdoor temperature falls below +12 °C. During the bypass, post-heating is turned off.
Adjusting supply air temperature
FAN SPEED ADJUSTMENT
ADJUSTING THE SUPPLY AIR TEMPERATURE AND SUMMER/WINTER FUNCTION
The winter function of the ventilation unitThe limit value has been set in the factory for freezing of the heat recovery cell. When this limit value is exceeded, the ventilation unit starts to defrost the heat recovery cell by directing the outdoor air past the heat recovery cell.
The duration of the defrost cycle is 15-45 min depending on the amount of ice accumulated in the heat recovery cell and on the extract air flow. The factory settings ensure optimal operation in standard living and detached house conditions. Even though the winter operation parameters can be adjusted for certain extreme conditions, such as swimming pool facilities, it is always advisable to contact Vallox maintenance services.
4
USIN
G TH
E UN
IT
FIREPLACE SWITCHA switch with timer functions can be connected to the unit. The switch stops the extract air fan when the fireplace is being used. NOTE! Starting up the extract air fan can reduce the draw of the fireplace! In winter, this can disturb the winter mode of the ventilation unit. The situation will return to normal soon after the fireplace mode is turned off.
ADJUSTING THE SUPPLY AND EXTRACT AIR RATIO This function might be needed when the air flows are adjusted at the valves during installation. The user does not need to adjust this function once the valves have been adjusted, and indeed should not adjust it at all. A potentiometer can be used to reduce the supply or extract air flow as required.
When the potentiometer is set roughly in the centre position, neither the supply nor the extract air flow has been reduced. When the potentiometer is turned anti-clockwise, the supply air flow is reduced, and when the potentiometer is turned clockwise, the extract air flow is reduced.
The potentiometer for adjusting the supply and extract air flows
TROUBLESHOOTINGFlashing LED
Problem Correction
1 NTC sensor of the supply air from the cell is faulty
Check the sensor and the wires, replace as required
2 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
3 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
4 NTC sensor of the exhaust air is faulty Check the sensor and the wires, replace as required
5 NTC sensor of the outdoor air is faulty Check the sensor and the wires, replace as required
6 The supply air fan has stopped. Check the wiring of the fan, re¸place the fan as required
7 The extract air fan has stopped. Check the wiring of the fan, replace the fan as required
8 EEPROM is faulty Replace the circuit board
Concealed installation of the fireplace switch (optional)
TROUBLESHOOTING TABLEIf the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error relay, signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring. NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.
MAINTENANCE REMINDERIf a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from inside the unit. The maintenance reminder will be set off automatically when the door of the ventilation unit is opened or the power is turned off. The maintenance reminder can also be set off manually.
The Vallox Simple Control control panel, and the Vallox X-Line PTXP MC and PTXPA MC control hoods, VAK 0-10 VDC:
• The low speed is turned on, then higher-lower-higher
- Low speed under 4 V
- High speed over 6 V
- The selected speed will always be turned on for 1-5 seconds
Vallox Capto PTC EC control hood:• The damper is closed, then open-closed-open
• Press at a 1-5 second interval.
The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary maintenance measures.
5 © Vallox Oy - All rights reserved
MA
INTEN
AN
CE
The R model is shown in the figures. In the L model, the parts are mirrored.
BEFORE BEGINNING MAINTENANCE WORKWhen you open the door of Vallox 101 MC, the safety switch (S) cuts the power. Despite this, disconnect the power supply plug anyway. Always disconnect the power plug before starting maintenance on the Vallox 101 MC.
FILTERSWhen the maintenance reminder becomes activated, check the cleanliness of the filters and replace them if required. The Vallox ventilation unit has three air filters:
• Class G4 coarse filter (A) filters insects, heavy pollen and other relatively large foreign objects out of the outdoor air.
• Class F7 fine filter (B) filters microscopic pollen and dust particles out of the supply air.
• Class G4 coarse filter (C) filters the extract air and keeps the heat recovery cell clean.
Using original Vallox filters ensures the best operation of the ventilation unit and the best filtering results. The filter replacement interval depends on the ambient dust concentration. It is recommended that the filters be replaced every spring and autumn, or at the very least once a year.
HEAT RECOVERY CELLCheck that the heat recovery cell (D) is clean roughly once a year when the filters are being replaced. Clean by washing as required.
• Remove the sealing strip (E) above the heat recovery cell in the direction of the arrow. Also remove the extract air filter (C).
• Lift the heat recovery cell and pull it out of the unit.
IMPORTANT! Handle the cell carefully! For example, do not lift the cell by the layers. The cell layers are very thin and easily damaged.
If the heat recovery cell is dirty, clean it by immersing it in water containing a small amount of a mild detergent. Rinse the heat recovery cell clean with a water spray. When all the water has drained from between the layers, the heat recovery cell can be installed.
• Ensure that the lower support (F) is in place between the knobs at the bottom of the unit before the heat recovery cell is installed.
• Push the heat recovery cell in place. Also push the sealing strip (E) in place so that the strip is supported by the corner bracket (G) at the rear. Lastly, install the extract air filter (C) in place.
S
A
B
C
E G
C
D
F
6
MA
INTEN
AN
CE FANS
Check the cleanliness of the fans when servicing the filters and the heat recovery cell. Clean the fans as required. The fans are very sensitive to external impacts, and it is recommended that they be cleaned in place rather than removing them.
You can clean the fan blades with compressed air or by brushing them gently. Do not remove or move the fan blade balancing weights.
Cleaning the fans• Remove the extract air filter (C), the sealing strip (E),
and the heat recovery cell (D) from the unit following the instructions provided earlier. The fans can now be cleaned. The control grille in the suction outlet of the supply air fan (T) can be removed if it is in the way during cleaning. To remove the grille, the supply air fan must first be removed from the unit.
• To remove the fan, disconnect the quick connector (H) of the supply air fan (T) and/or the extract air fan (P) cables.
• Push the fan cables and the rubber feed through (I) into the fan chamber.
• Remove the wing screws used to fasten the fans (J) (3 screws per fan).
• Remove the fan from the unit by pulling it forward and by tilting it slightly backwards at the same time.
Removing and mounting the supply air fan attenuation grid
• Remove the mounting screws (4) of the air flow control grille of the supply air fan and remove the grille. You can now clean the fan. Put the control grille back in place after cleaning.
Mounting the fans• Ensure that the rubber feed throughs set in place
when reinstalling the fan. Fasten the fan in place with wing screws (3 screws/fan).
E
C
P
D
S
H
S
K
S
P
H
J JI I
The R model is shown in the figures. In the L model, the parts are mirrored.
7 © Vallox Oy - All rights reserved
MAINTENANCE
MA
INTEN
AN
CECONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new buildings, condensation runoff can form rapidly. Condensed water must be able to freely leave the unit. At some time before the heating season begins (e.g. during autumn maintenance), check that the condensing water outlets in the bottom pool are not clogged. To check this, pour some water into the pool. Clean as required. Water must at all times be kept out of the electrical system.
See the condensing water connections on page 15. 2
91
291
147,5 147,5
R modelL model
Installation of the Vallox Silent Klick water seal on the bottom pool
Installation of the Vallox Silent Klick water seal on the wall.
447
598
53
8
TECH
NIC
AL SPEC
IFICATIO
NS
Volume flow rate (dm3/s)
Volume flow rate (dm3/s)
Pres
sure
loss
in d
ucts
. Tot
al p
ress
ure
(Pa)
Pow
er, W
Supply/extract air volumes
Power table
Combined input power of the fans (kW)Airflow specified in the ventilation plan (m3/s) SFP =SFP rate (Specific Fan Power)
recommended value <1,8kW (m3/s)T = supply airP = extract air
Air flow measurement pointsMeasurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.
TECHNICAL SPECIFICATIONS Product title Vallox 101 MC R Vallox 101 MC L
Product number41026384102629
HVAC code79121177912118
Air volumes Supply air Extract air
90 dm³/s, 100 Pa98 dm³/s, 100 Pa
Electrical connection 230V, 50Hz 8.3A power plug
Enclosure protection class IP34
Post-heating radiator Power, 1500 W
Preheating radiator –
Additional heating radiator –
Fans Supply air Extract air
0.115 kW, 0.9 A EC0.115 kW, 0.9 A EC
Specific energy consumption (SEC) in a cold climate in a temperate climate
A+ B
Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power (SFP)
70 % A82 %1,0 (38 dm3/s)
Filters Supply air Extract air
G4 + F7G4
Heat recovery bypass Automatic
Weight 50 kg
Extract air
Supply air
0
50
100
150
200
250
300
0,0 10,0 20,0 30,0 40,0 50,0 60,0 70,0 80,0 90,0 100,0 110,0
2,7 V 3,8 V 4,7 V5,7 V
6,5 V
7,5 V8,0 V
9,0 V
10,0 V
11,4 V
0255075
100125150175
200225250275300325350
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
2,7 V
6,5 V
7,5 V
T9,0 V
8,0 V
10,0 V11,4 V
5,7 V
4,7 V
3,8 V
SFP 1,0
SFP 1,5
SFP 1,8
9 © Vallox Oy - All rights reserved
TECH
NIC
AL SPEC
IFICATIO
NS
SOUND VALUESSound power level in the supply air duct
by octave band Lw, dBSound power level in the extract air duct
by octave band Lw, dB
Adjustment position V / Air flow dm3/s Adjustment position V / Air flow dm3/s
Adjustment position 2.7 V 3.8 V 4.7 V 5.7 V 6.5 V 4.5 V 8.0 V 9.0 V 10.0 V 11.4 V 2.7 V 3.8 V 4.7 V 5.7 V 6.5 V 4.5 V 8.0 V 9.0 V 10.0 V 11.4 V
Air flow dm3/s 8.6 15 16.9 37.7 45.1 53.5 57.3 67.4 73.3 82.3 11.3 24.4 34.3 45.6 55.6 65.9 72.6 83 91.5 99.2
Air flow m³/h 30.96 54 60.84 135.72 162.36 192.6 206.28 242.64 263.88 296.28 40.68 87.84 123.48 164.16 200.16 237.24 261.36 298.8 329.4 357.12
Medium frequency of the octave band Hz
63 *56 *58 *63 67 70 72 75 77 79 80 62 *53 *56 *58 *61 64 67 68 70 71
125 52 62 63 65 67 69 71 74 76 78 52 58 58 61 64 67 69 70 73 74
250 44 52 57 64 70 66 70 71 72 74 35 45 50 57 60 60 62 62 62 63
500 40 49 53 58 61 64 65 69 71 74 *27 *34 40 44 48 51 53 55 57 62
1000 32 41 46 51 55 58 60 63 67 68 *16 *23 28 33 36 39 42 44 46 48
2000 *24 34 40 47 51 55 57 61 63 65 *14 *17 *23 29 32 36 38 41 43 44
4000 *23 *25 31 38 43 48 50 55 57 60 *16 *16 *17 *21 *24 *28 31 34 36 39
8000 *21 *21 *23 30 35 41 44 51 53 56 *20 *20 *20 *20 *20 *21 *22 *24 26 29
LW,dB LWA, dB(A)
*58 *64 67 71 74 75 78 80 82 84 62 *59 61 64 67 69 72 73 75 77
41 50 54 60 64 65 67 70 73 75 39 43 45 50 54 55 57 58 59 62
Sound pressure le Vel, in decibels (A) coming through the en Velope from the room in which the unit is installed (10m2 sound absorption) Adjustment position / air flows (supply/extract)
Adjustment position 2.7 V 3.8 V 4.7 V 5.7 V 5.9 V 7.5 V 8.0 V 9.0 V 10.0 V 11.4 V
Air flow dm3/s 13/15 21/24 29/32 39/41 43/46 55/58 60/62 69/72 76/78 84/85
Air flow m³/h 46.8/54 75.6/86.4 104.4/115.2 140.4/147.6 154.8/165.6 198/208.8 216/223.2 248.4/259.2 273.6/280.8 302.4/306
LpA, dB (A) *21 *26 30 36 38 42 43 46 48 50
Dimensions and duct outlets
Duct outlets
L modelInner diameter of the female collar: ø 125 mm1. Exhaust air out2. Outdoor air to the unit3. Supply air to the apartment4. Exhaust air from the apartment to the unit
R modelInner diameter of the female collar: ø 125 mm1. Supply air to the apartment2. Exhaust air from the apartment to the unit3. Exhaust air out4. Outdoor air to the unit
485
38
447
The installation space required by the Vallox elbow is 47 mm. See Condensing water connections, p. 15
598
53
500
447
The installation space required by the Vallox Silent Click water seal is 73 mm. See Condensing water connections, p. 15
136,50
461,50
598
104
322
~ 5
96
154,50
443,50
125
1 3
2 4
10
ELECTR
ICA
L CO
NN
ECTIO
NS
INTERNAL ELECTRICAL CONNECTIONLIN
E: Phase
NEU
TRA
L: Neutral
SLI: S
afety switch phase feed
SN
I: Safety sw
itch neutral feedS
LO: S
afety switch phase to the circuit board
SN
O: S
afety switch neutral to the circuit board
SFL: P
hase to supply air fanS
FN: N
eutral to supply air fanEFL: P
hase to extract air fanEFN
: Neutral to extract air fan
FSO
: Fireplace switch feed
FSI: Fireplace sw
itch outputA
HL: P
ost-heating phaseA
HN
: Post-heating neutral
PH
L: Additional heater phase
PH
N: A
dditional heater neutralB
L: Dam
per motor phase A
BL1: D
amper m
otor phase BB
N: D
amper m
otor neutralE/I: Error relay feedE/O
: Error relay output
Freezing level adjustment
Fireplace switch
M
1 2 3 Program
ming connector
Safety / door sw
itch
Belim
o damper
motor 2
30 V
AC
VA
Krem
ote m
onitoring
E/IE/O
When rem
ote monitoring is used
Leave the signal LED of the external
control panel or cooker hood disconnected.A
lso disconnect the short circuit link betw
een connectors 3 and 5
from the fem
ale side of the control panel connector.
Post-heating control
PW
M level adjustm
ent
4 5 6
Protective earth to a separate block
7 8 9
1
Supply
air fan
23
Extract air fan
45
LINE
NEU
TRA
LS
LIS
NI
SLO
SN
OS
FL
Extract air NTC
Outdoor air N
TC
Supply air to the apartm
ent NTC
Exhaust air NTC
Supply air from
the cell NTC
SFN
EFLEFNFS
OFS
IA
HL
AH
NP
HL
PH
N
230
V 5
0 H
z
BL1
BL
BN
E/IE/O
9. G
ND
/ -8. S
upply fan PW
M7. S
upply fan tacho6
. GN
D / -
5. Extract fan P
WM
4. Extract fan tacho3. G
ND
/ -2
. 11,4 VD
C / +
1. Control signal S
1
DIP
Sw
itchU
pD
own
1. Post-heating
ElectricV
KL
2. A
dditional heatingElectric
MLV
3. Type of the unitB
ypassS
upply fan stop4. Extra
An external 0
-10V
DC
voltage supply can be connected to the S
and GN
D signals
of the control signal for fan control.
23
4
DIP
switch
ERR
OR
RELA
Y
(potential-free)
*Fan neutral to FSI w
hen the fireplace sw
itch is used
LED
*Without the fireplace sw
itch, the fan neutral is connected to EFNW
ith the fireplace switch, the fan neutral is m
oved to FSI
12
34
LED-
+S
1 2 3 4 5
1 2 3 4 5
Error relay
90 °C130 °C
R1
T1T2
Electric post-heating radiator 15
00
W
7034800A
11 © Vallox Oy - All rights reserved
ELECTR
ICA
L CO
NN
ECTIO
NS
EXTERNAL ELECTRICAL CONNECTION with Vallox Capto PTC EC control hood.
EXTERNAL ELECTRICAL CONNECTION with the Vallox Simple Control control panel / Vallox PTXP MC, Vallox PTXPA MC cooker hood
S + - LED
Simple Control
SS
++
--
Control signal S
11.2 VDC / +
GND / -
Error relay / LED
LED LED
Internal connection of the ventilation unit
S+- LED
PTXP MC, PTXPA MC
7034500A
ALARMTAC
HO
GN
D
0-11
VPIEZO+ -
DAMPIN OUT
MODEIN OUT
F A
LARM
RS 485A B GND
NL
DA
MPE
R1
2
3LI
GH
TN
L
FAN
N
L
EC roof fan
Tacho-S
MC VENTILATION UNITFive terminal connector**
GNDS
GNDS
MC VENTILATION UNITFour terminal connector
MV VENTILATION UNIT
GNDAN/I
RM/IRM/O
E/ILED / E/O
PRO
GRA
MM
ING
C
ON
NEC
TORS
OF
THE
MO
THER
BO
ARD
CONTACT DATA:GUARD FUNCTION:NORMAL SITUATION = OPENACTIVATED = CLOSED
HOUSE AUTOMATION:NORMAL SITUATION = OPENERROR SITUATION (HOOD OR VENTILATION UNIT) = CLOSEDACTIVATED GUARD FUNCTION = FLASHING
POSITION OF THE DAMPER:DAMPER CLOSED = CONTACT OPENDAMPER OPEN = CONTACT CLOSED
* External error data is connected in the place of the short circuit link of the mother board
** Disconnect the short circuit link between connectors 3 and 5 from the MC unit’s control panel connector
IN OUT
PE
EXTR
A
DA
MPE
R PO
SITI
ON
CO
NTA
CT
DA
TA
GU
ARD
FU
NC
TIO
NC
ON
TAC
T D
ATA
HO
USE
AU
TOM
ATI
ON
CO
NTA
CT
DA
TA
3 POTENTIAL FREE CONTACT DATA 24VDC/5A
*NOTE!
12
ELECTR
ICA
L CO
NN
ECTIO
NS
EXTERNAL ELECTRICAL CONNECTION with Vallox ProControl control panel
EXTERNAL ELECTRICAL CONNECTION With an external control panel
Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5Ventilation unit cable Control panel connector
S Y1+ leave disconnected- G0
LED S/DI2
CONTROL PANELG 24 VAC feed S/DI2 Error relayG0 0 VAC G0 0 VACY1 10 V, control voltage
of the ventilation unitY2DI1 Boost at the cooker hoodA1 24 VAC 1 A, intermediate
relay control
Y3A2Y4U1 0...10 V, humidity boostA+ RS-485B- RS-485C RS-485 Common
RH%
optional 946147
Nomak2x2x0,5+0,5
0...1
0V
LED
GG0Y1Y2DI1A1Y3A2Y4U1A+B-C
S/DI2G0
Vallox Procontrol949034
S
LED
S
++
--
B termCONFIG
Control signal S Cooker hood or boost switch
11.2 VDC / +
GND / -
DISTRIBUTION BOARD
L N24V
Error relay / LED
Nomak 2x2x0,5+0,5 ModbusRS-485Nomak 2x2x0,5+0,5
Cable types specified in the drawing are indicative
2x0.5
2x0.5
Internal connection of the ventilation unit
The phase of 24 VAC feed is connected to the control panel connector G and the neutral to the connector G0
Control signal S
GND / - An external 0-10 VDC voltage can be connected to the S and GND connectors for fan control.
External control panel
SS
++
--
GND / -
LED LED
Internal connection of the ventilation unit
Control signal S
11.2 VDC / +
Error relay / LED
13 © Vallox Oy - All rights reserved
INSTA
LLATION
INSTALLATION SITEVallox 101 MC must be installed in a location where the temperature remains above +10 °C. When the unit is installed without a protective enclosure, the location must be chosen so that its noise does not cause any disturbance. Such locations include storage premises and technical spaces.
NOTE! Remember to make a service door in the finished ceiling so that the connection cables can be accessed. The service door should be located roughly 500 mm from the unit door.
162
12 21
20 60
2030 30
2060 11
203030
11
84 84
35 30 35
ø7 14 kpl550
30
25 25
30°
Wall mounting plate
283
16
4
6 604
Bottom edge of the wall mounting plate
The top surface of the side panel of the unit can be installed against the finished ceiling surface.When the wall mounting plate is used, it must be observed that the ventilation unit will rise roughly 10 mm above the final installation height!
The outer diameter of the duct is 12 mm
Wall mountingMount the Vallox 101 MC on the wall with a mounting plate, as shown in the adjacent figure. Make sure that the unit is horizontally level after mounting.
Wall structureThe wall structure must be observed in the mounting. Avoid mounting the unit on hollow, echoing intermediate walls and on bedroom walls, or take measures to prevent conduction of noise.
14
INSTA
LLATION
Ceiling mounting by using a ceiling mounting plate (optional)The unit can be equipped with an optional ceiling mounting plate. The ceiling mounting plate must be fastened on rafter frames or other frame structure with M8 thread bars. The bars must be fastened so that they withstand the weight of the unit.
The ceiling mounting plate must be fastened horizontally to make sure that the unit is level. The ceiling mounting plate must be fastened so that there is a 10 mm gap between its rear edge and the finished wall. This way the ventilation unit will be installed as close to the wall as possible. The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively, a concealed mounting method can be used, in which case the finished ceiling can be 30 mm or less from the top edge of the white covering strip.
The ceiling mounting plate is fastened to the M8 thread bars with the mounting supplies delivered with the mounting plate. NOTE! The end of the thread bars must be 5mm or less below the fastening nut (more detailed instructions are provided with the ceiling mounting plate).
Installing the ventilation unit to the ceiling mounting plateRemove the unit door. Lift the unit and take the wires through the opening in the ceiling mounting plate. Lift the ventilation unit against the ceiling mounting plate so that it locks in place. The unit has become locked on the ceiling mounting plate when the two operating levers on the mounting plate have been restored to the same level with the white covering strip of the ceiling mounting plate (more detailed instructions are provided with the ceiling mounting plate).
Ceiling mounting plate (optional)The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively, a concealed mounting method can be used, in which case the finished ceiling can be 30 mm or less from the top edge of the white covering strip.
The minimum distance from the finished rear wall is 10 mm
The recommended distance from the finished side wall is 10 mm
598 10 10
598
Finished wall Finished wall
Concealed installation of the ceiling mounting plate on the ceiling, max. 30 mm.
483
453
53
53
Finished ceiling
Water seal Silent Klick
Installation space of the water seal 73 mm
Installation space of the elbow 47 mm
Concealed installation of the ceiling mounting plate on the ceiling, max. 30 mm
483
453
38
38
Finished ceiling
Elbow
10
Finished wall
15 © Vallox Oy - All rights reserved
INSTA
LLATION
The delivery includes the Vallox Silent Klick water seal. A pipe will be connected to the water seal that leads the water that is condensed from the extract air to the floor drain (not directly into the sewer). The pipe must not rise after the water seal. The ventilation unit must be installed straight to ensure that condensing water can exit the unit unobstructed.
Installation of the Vallox Silent Klick water seal on the bottom pool
Installation of the Vallox Silent Klick water seal on the wall. The elbow underneath the unit takes less space than the water seal.
47
3873
53
ElbowInstallation height 38 mm, installation space 47 mm, outer diameter of the duct 12 mm
Vallox Silent Klick water seal Installation height 53 mm, installation space 73 mm, outer diameter of the duct 12 mm
Location of the condensing water outlets, R and L models
If the Vallox Silent Klick water seal does not fit into the unit directly, the elbow can be installed at the bottom, and the water seal can be installed on the wall. This installation method requires that there is a 47 mm space underneath the unit. The elbow requires a 38 mm space when installed.
291
291
147,5 147,5
R modelL model
Installation of the Vallox Silent Klick water seal on the wall
CONDENSING WATER CONNECTIONSInstallation of the Vallox Silent Klick water seal on the bottom pool
Attic floor penetration plate (optional)When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.
The attic floor penetration plate can be fastened on the finished rear wall.
Finished wall
15 15
The minimum distance from the side walls is 15 mm.
© Vallox - All rights reserved
www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
Customer Service +358 10 7732 200 | Aftersales +358 10 7732 270 D46
86 |
12.2
.20
18 |
EXPLODED VIEW AND PARTS LIST (Type 3740)
NO. Part Product number1 Supply / extract air fan ....................................................................................935450
2 Supply air fan attenuation grid......................................................................935451.
3 Wall mounting plate ......................................................................................3080700
4 Water seal Vallox Silent Klick .....................................................................3292500
5 Filter (F7 + G4, supply) .....................................................................................978225
6 HR cell .................................................................................................................933260
7 Lower support for the HR cell ..................................................................... 4102504
8 Upper support for HR cell ........................................................................... 3467200
9 Filter frame (extraction) ...................................................................................978226
10 Filter (G4, extract) ............................................................................................. 978227
NO. Part Product number11 Bypass flap assembly .................................................................................... 4102523
12 Damper motor ....................................................................................................930621
13 Post-heating resistor........................................................................................942220
14 Door ................................................................................................................... 4102334
15 Mounting screw of the door ...........................................................................990712
16 Motherboard ......................................................................................................949035
17 Safety switch ......................................................................................................948370
18 Glass tube fuse 320 mA slow 5x20 mm ....................................................952486
19 NTC sensor (specify the sensor reference number in the order) .........946140
R model in the figure. In the L model, the parts are mirrored
EXPLO
DED
VIEW
1
15
6 7
2
8
10
9
11
12
13
1415
17
161819