unit 4: refrigeration principle - trent global · unit 4: refrigeration principle 4.1 introduction...
TRANSCRIPT
12/5/2014
1
UNIT 4: REFRIGERATIONPRINCIPLE
4.1 Introductioni. Buildings are essentially enclosed spaces designed for the purpose of
accommodating occupants and their activities.ii. Thermal comfort is incorporated with the building design in terms of
architectural design (e.g Buildings designed with transparent atriums toallow natural light to emanate buildings) as well as M & E services(Sufficient lighting, air conditioning, etc).
– Thermal comfort for humans determined by several factors, e.gclothing of occupants, average temperature of locality, etc.
– Average thermal comfort: 27 Degrees Celsius.– Thermal comfort: Crucial in preventing building sickness in occupants
(Especially important for office/working environment, as it will affectproductivity);
iii. Refrigeration cycle: Designed to remove heat from building’s premisesto external environment, as well as heat up building interior duringperiods of cold weather.
12/5/2014
2
iv. Calculations:a) British Thermal Unit (BTU): Unit of energy to measure power consumption for
air con units;– 1 BTU = amount of heat necessary to raise one pound of water (0.454 kg) y
1 degree Fahrenheit (F) or 0.56 degrees Centigrade;– 1 BTU = 252 calories or 1.055 kilo Joules (kJ);– 1,000 kWh = 3.41 million BTU;– Necessary to design power requirements for cooling;– If BTU is sized too high, humidity of cooled area may be insufficiently
removed. If BTU is too low, insufficient cooling may occur;– Typical methodfor sizing BTU: Area of room (In square feet) x 25;– E.g: If room size is 12 feet by 15 feet, area is 180 square feet x 25 = roughly
4500 BTU;– May include other factors: E.g Temperature and humidity of the locality, no
of occupants (Generally, 1 occupant would represent about 1000 BTU), etc.b) Volumetric Air Flow: Volumetric measurement of airflow per unit time from a
ventilation (Natural or mechanical) device;– Usually in metre cube per hour (CMH) or Liters/Sec;– Used for designing air flow requirements in accordance to Code of Practice
for locality/Country (SS 553: 2009 for Singapore).
Volumetric Flow Rate Conversion Chart
12/5/2014
3
4.2 Understanding the Refrigeration Cycle
i. Refrigerant cycle functions as a heat exchanger.ii. The medium for heat exchange:
a) Chemical refrigerant: Used for split units, VRV systems andother air conditioning systems;
– Usually chosen for their low boiling points;– Very volatile chemicals, hence have huge capacity of heat
absorption and dissipation. Because of their volatility,copper piping needs to be insulated by armaflex to reducethe effects of condensation;
– Usually stored in canisters complete with nozzles for ease oftopping up in air con systems;
– Environmental Issues: Old refrigerant types using CFCs areknown to threaten the ozone layer, and are usually bannedin most countries (E.g Freon refrigerants manufacturedunder DuPont).
4.2.1 How the Refrigeration Cycle Works
TypicalChemicalRefrigerant forStored inCanister form
12/5/2014
4
b) Water: Used in water chillers. Transfers heat from a chemicalrefrigerant to a heat dissipation element (i.e Cooling Tower). Usuallymade of tougher materials, e.g stainless steel.
Chilled water piping (Stainless steel)in water chiller system. Connectionto local water supply helps toreplenish losses in system
Copper tubing for refrigerant inA/C system c/w armaflexinsulation
iii. How the RefrigerationCycle Works:
a) Compressor:• Receives low pressure
refrigerant fromevaporator;
• Compresses and pumpsthe refrigerant throughoutthe refrigeration system;
• Provides sufficient highpressure to drive therefrigerant system;
b) Condenser:• Receives high pressure
refrigerant fromcompressor;
• Transfers heat fromrefrigeration system tooutside environment;
HighTemp
LowTemp
LowTemp
Schematic Diagram of Refrigeration Cycle
12/5/2014
5
c) (Thermal) ExpansionValve:
• Receives highpressure refrigerantfrom Condenser;
• Controls refrigerantflow to evaporator;
• Connected to thesensor bulb, installedat evaporator tomonitor temperature;
• Temperature setting(usually via remotecontrol) will relaymessage to sensor,which will adjustrefrigerant flowaccordingly to meetset temperature.
d) Evaporator:• Receives low pressure refrigerant from
evaporator;• Usually incorporated with a fan coil unit within
the building premises;• Receives heat from building’s premises, which
eventually is sent to the condenser to beexpelled to the external environment.
SensorBulb
Evaporator Unit
Split Unit Air Con FCU
Compressor and Condenser unitincorporated in outdoor condensingunit.
12/5/2014
6
v. Condensation Issues for Air Can Evaporator/Fan Coil Units Condensation occurs in fan coil units when the cold surface of the
evaporator meets the warm air within the building proper; The situation worsens if the fan coil unit is located near sources of air, e.g
near the entrance of the lobby, where the constant opening and closing ofdoor causes constant warm air to come into contact with the evaporator;
Drain pan is usually located beneaththe evaporator coil;
Condensate is collected at the pan,which is connected to PVCcondensate piping (See picture onright);
Condensate piping is usuallyconnected to a drain or waste trapand flows away as waste water in thesanitary system;
Regular maintenance is required toprevent backflow of condensatewater due to chokage from debris,such as dirt particles.
Typical design for condensatepiping.
Condensate piping is usually designed with a downward gradient, i.e thehighest point from the condensate pan must be directed downwards viapiping towards the drainage point. Concept similar to sanitary drainagesystem;
Should the condensation piping follow a irregular travel pattern, i.e thepiping travels upwards and downwards before reaching the drainagepoint, the water may not be able to flow to the drainage point. This willcause water to floor backwards to the pan, causing leakage at the FCU;
In this case, a condensate pump needs to be installed to pump away thecondensate.
Typical drainage pump installed topump away condensate to highergradient
Typical condensate pump
12/5/2014
7
vi. Compressors
• Compressors: Device which increases pressure and decreases volume of afluid (Hence compressing the fluid) to drive it through a piping system;
• Electrically driven: Needs a constant power source to drive it;• Difference from pumps: Pumps do not compress fluids as their main
function is to transport fluids via pressurization (e.g condensate pumpused to transport a/c condensate to drainage).
Compressor Categories
Single Stage CentrifugalCompressor
• Types of A/C Compressors:a) Reciprocating Compressors Range: Up to 180kW; Typical for small localized systems, e.g
window sill A/C units; Positive displacement type;How it Works– Piston moves downwards, creating
vacuum in cylinder space above thepiston. This draws refrigerant into thespace from the intake valve (Outletvalve is in closed position during thisprocess);
– When piston reaches bottom, it springsup and compresses the refrigerant.Compressed refrigerant is forced intothe exhaust valve. At this point, theintake valve is closed;
– Cycle is repeated.
12/5/2014
8
b) Rotary Screw Compressors Mid-Range: Up to 2MW; Suitable for mid-range chiller
systems; Compact, smooth running,
limited vibration; Spring suspensions not
required; Consists of Dry Type and Oil
Flooded Type.Dry Type:– Two rotors (1 is driver, the
other is driven) or helicalscrews used to compress gas;
– Timing gears are used toensure rotors maintain precisealignment;
– Oil-free, suitable for sensitiveenvironments, e.g Hospitals.
Dry Type Rotary Compressor
Helical Screws for compressing Fluids
Oil-flooded type:– Similar design,– Oil is injected into
compression cavities for: Sealing purposes to prevent
backflow of refrigerant; Cooling sink for refrigerant
discharge; Transferring mechanical
energy between driver anddriven rotors;
– Refrigerant gas enterscompressor, mixes with oil andexits compressor;
– Oil is mixed with refrigerantand separated in gas-oilseparator before compressedgas is discharged.
– Separated oil is returned tomicro oil filter for filtering andthen to oil cooler to be cooled.
Oil-flooded Rotary CompressorSystem
12/5/2014
9
c) Rotary Vane Compressors Rotary Motion: Utilizing a
series of vanes and slots in therotor;
Rotor is actually offset fromcenter of the housing;
How it Works:– Rotating shaft rotates and
shifts, turning the rotor as well;– Vanes move in and out of the
slots, causing refrigerant fromsuction port to be compressedbefore it leaves thecompressor.
Cross Section of Rotary VaneCompressor
Schematic of Rotary VaneCompressor
d) Centrifugal Compressors High Range: 3.5MW; Incorporated with large,
centralized chiller systems;How it Works:– Rotating disk/impeller
rotates in housing, drivingrefrigerant to force it to theimpeller rim;
– Velocity increases, convertsto high pressure and isdiverted to condenser.
Centrifugal Compressorincorporated in Centralized AirConditioning System
12/5/2014
10
4.3 Air Conditioning & Mechanical VentilationTypes• Various types of air conditioning and mechanical ventilation systems are
available in the market;• While functions may differ in accordance to their allocated functions (e.g Type
of refrigeration, Centralized and localized cooling, etc), the basic design issimilar to the vapor compression system: Heat absorption (Evaporator),temperature control apparatus (Expansion Valve), heat dissipation(Condenser), propulsion of heat transfer medium (Compressor).
4.3.1 Localized Cooling Systems
• Designed for localized cooling in small rooms or areas, e.g rooms, offices,etc;
• Cooling element (Evaporator) is usually incorporated with mechanicalfan/blower;
• Types of localized cooling systems include:a) Window sill air conditionersb) Split systemsc) Multi split systemsd) Variable refrigerant flow split systems.
Window Sill Air Con Installationat Residential Unit
12/5/2014
11
i. Window Sill A/C:• As the name suggests, the
apparatus is mounted onwindow sill;
• Follows the vaporcompression/refrigerant cyclemethod;
• All components inside cabinetunit;
• Evaporator facing unit interior,condenser facing outsideenvironment;
• Evaporator: Warm air is drawnfrom room into filter, thenpasses back to room as cold air;
• Condenser: Expels heat frombuilding via blower.
ii. Single Split Unit A/Cs• Similar to Window Sill A/C;• Evaporator and Expansion Valve
(Fan Coil Unit, or FCU) housedseparately from Condenser Unit(CU: Combination of compressorand Condenser);
• Comes with Ducting andDuctless units.
Ductless Split UnitA/C
Ducted Split UnitA/C
12/5/2014
12
iii. Multi-Split Unit Air Conditioning
• Similar to single split unit A/Cs;• One CU unit is linked to more than 1
no of FCU units;• Advantages:
– Saves space, without the need tofree up floor space to install moreCU units;
– Energy Saving Features.
Comparison between single splitunits and multiple split units
iv. Variable refrigerant flow (VRF)Split Unit Systems
• Also known as VRV(VariableRefrigerant Volume)for Daikinprototypes;
• Similar to split units,with up to 40 FCUsconnected toexternal modular CUunit;
• Each FCU iscontrolled by itsown solenoid valvekit, able to regulaterefrigerant flow (andtemp)individuallyfor each FCU;
12/5/2014
13
• Prototypes may includeheating and coolingelements;
• Advantages:a) Does not need huge
floor space forinstallation, unlikechiller systems;
b) Flexibility of use, astemperature forvarious FCUs can beadjusted individualunlike centralizedsystems;
c) Energy savingproperties;
d) Can be used for avariety of settings, e.gIndustrial premises,retail, offices, etc.
4.3.2 Reverse Cycle Heat Pump (HVAC)i. In countries where the 4 seasons are
prevalent, HVAC (Heating Ventilationand Air Conditioning) systems arerequired to provide both cooling andheating functions within buildings.
ii. Reverse Cycle Heat Pumps can beemployed to serve a HVAC function:– System is similar to vapor
compression cycle;– Uses refrigerant similar to standard
split unit A/C;– Can be used for cooling and heating
purposes by reversing refrigerantcycle flow;
– Requires a heat sink to transfer heat(Similar to CU unit of Vaporcompression cycle):
• Outside environment;• Ground.
Outdoor Units for HeatPumps
12/5/2014
14
iii. How it works:a) For cooling purposes:• Outdoor unit serves as condenser, expelling heat via fan (Similar to split
unit a/c);• Internal unit serves as a evaporator, receiving heat and directing it to the
outdoor unit;
b) For heating purposes:• Outdoor unit serves as evaporator, as heat is received by the outdoor unit
and directed to the indoor unit via the heated refrigerant;• Internal unit serves as a condenser, receiving heat and directing it to the
indoor unit to heat the building interior.
12/5/2014
15
iv. Geothermal Heat Pump
• Similar to normal heat pumps, but usesground as heat sink;
• During winter, heat is pumped from theground and used to heat building;
• During summer, the reverse happens, andthe building is cooled.
• Advantages: Cheap: Electricity is required only to
drive the compressor; Environmentally friendly: Significantly
low CO2 emissions; Highly efficient, as it utilizes the
ground as the heat sink (Especially sofor heating purposes).
4.3.3 Absorption Cooling
i. Using heat (Derived from a heatingelement, e.g gasoline, solar power, etc)to drive heat exchange medium (insteadof compressor in typical vaporcompression cycle) as a driving force;
ii. Can be localized or centralized A/Csystems;
iii. Preferable to vapor compression typesin terms of:
• Lower operating costs (Because nocompressor is used);
• Unreliable electricity supply in locality;• Where there is a supply of surplus heat
source (e.g economizer from a nearbyboiler can use recycled heat to be used forabsorption cooling);
• Can utilize solar power and other forms of“clean energy” to provide the heatingelement.
A localized domesticAbsorption CoolingRefrigerator
12/5/2014
16
iv. Basic Absorption Cooling Cyclea) Heat is the driving force for the absorption
cooling cycle;b) Evaporation Process:• Liquid refrigerant enters evaporator;• Absorbs heat from evaporator’s
surroundings, becomes gaseous form;c) Absorption Process:• Gaseous refrigerant enters absorber;• Low pressure gaseous refrigerant dissolved
in another fluid;• This allows for more refrigerant to
evaporate in evaporator due to reducedpartial pressure;
d) Regeneration Process:• Dissolved refrigerant in absorber heated,
allowing refrigerant to evaporate (Similar tocompressor function);
• Evaporated refrigerant condenses via heatexchanger, replenishes refrigerant inevaporator (Similar to condenser function).
v. Single Pressure Absorption Cycle
• Capacity range: 5kW up to12MW;
• Utilizes absorbent (Lithium-bromide) and refrigerant(Water).
• Heat source: Steam, hot water;• Coefficient of Performance
(COP): <1;How it Works:a) Generator:• Heat source heats up the
lithium-bromide solution;• Water evaporates and enters
condenser;• Concentrated lithium-bromide
solution flows into absorber, tobe pumped back to generatorafter being cooled by coolingwater;
12/5/2014
17
b) Condenser:• Receives vaporized water
(Refrigerant) from generator;• Cooling water system: Transfers
heat from vaporized water tocooling tower for externalcooling;
• Vaporized water condenses,pressure increases, temperaturedecreases and flows toevaporator;
c) Evaporator:• Specialized nozzles spray the low
temperature refrigerant onchilled water piping systemcirculating between the indoorcooling unit (Usually an airhandling unit) and theevaporator;
• Cooled chilled water circulatedback to indoor unit;
• Heated refrigerant is absorbedinto solution in absorber.
d) Absorber• Continuous water-lithium bromide
solution constantly receives heatedwater vapor from evaporator, as wellas lithium bromide solution fromgenerator;
• Solution is pumped back to generatorto complete cycle via solution pump.
vi. Two-Stage/Double Effect Absorption Chillers
• More efficient than single stage/single absorption cycles/units;• Requires higher temperature from heat source at generator (>140
degrees Centigrade);• Uses 2 generators:a) Main generator (steam fed or direct gas fired burners): Generates heat
for the system;b) Low temperature generator: Recovers heat which would otherwise be
lost to cooling tower to drive the refrigerant.c) Triple effect absorption chillers also available as well, similar principle as
two stage absorption chillers.
12/5/2014
18
vii. Water Spray Absorption Refrigeration
• Inclusive of de-humidifying function;
• How it works:1) Warm, moist air
enters ducting systemfan air inlet;
• Salt solution sprayed;• Humidity reduced;• Temperature relatively
unaffected;2) Warm, dry air enters
evaporative cooler;• Pure water sprayed;• Temperature reduced;• Humidity increases;
1
2
3
4
3) Cool, moist air enters fan air outlet;• Cool moist air is sprayed with salt solution at fan
air outlet to reduce humidity;4) Cool dry air is exits the system.• Refrigeration system (In Blue): Salt solution tank
collects spray from both pure water and saltsolution, where it is heated, condensed and purewater is collected to complete refrigerant cycle.
12/5/2014
19
4.3.4 Chilled Water Air Conditioning Systemsi. Designed for centralized cooling
over large properties, e.gshopping malls;
ii. How it works:a) Condensing Water System:• Uses water as refrigerant;• Transfers heat from compressor
to cooling tower;• Heat is dissipated from cooling
tower;• Condensing pump: Provides
energy for water to transversesystem;
b) Chiller: Acts as a heat exchangerbetween chilled water systemand condenser water system;
• Vapor compression cycle;• Chemical refrigerant used;
Typical Chilled Water A/C Systemincorporating Air Handling Unit Systemand Exhaust System
c) Chilled water system:• Uses water as refrigerant;• Transfers heat from air handling unit to
chiller;• Chilled water pump: Provides energy for
water to transverse system;d) Air handling unit: Acts as a evaporator
for centralized cooling;• Ducting air vents split to various
locations throughout designatedlocations for cooling purposes;
• Cooling fans installed to provemechanical ventilation;
• Filters installed to filter out dust fromoutlets;
• Dehumidifier installed to reducehumidity;
e) Exhaust system: Mechanicalventilation system designed to expelstale air from building proper.
Typical Air Handling Unit
12/5/2014
20
Tutorial Questions1) Explain in detail, with the aid of illustration, how the Refrigeration Cycle (Vapor
Compression Cycle) works (20 marks).2) Condensation issues in Fan Coil Units (FCUs) are a common problem in many air
con installations, causing FCU units to leak, or “sweat” .i. Briefly describe how condensation occurs (2 points).ii. Explain, with the aid of a simple sketch, how condensation piping should be
installed so as to prevent leakage in air cons (10 points).iii. Explain, with the aid of a simple sketch, the condition(s) whereby air con
condensation pumps should be installed in condensation piping system (8 points).3) Illustrate with the aid of a simple sketch, on how the Absorption Cooling Cycle
works (20 marks).4) Heat Ventilation Air Conditioning (HVAC) systems are common in some
countries.i. Identify the type of environmental conditions which will necessitate the use of
HVACs (2 points);ii. Identify the basic functions of the HVAC systems (2 points);iii. Describe in detail how Reverse Cycle Heat Pump works(9 points).iv. Briefly describe how the Geothermal Heat Pump works, and list down the
advantages of using the geothermal heat pump (7 points).