UL Class CF CUBEFuse holders
2011/65/EU
Catalog symbols
• TCFH(amps)N (600 V UL Listed)• TCFH(amps)NW (690 V UL Recognized)
Description
The Bussmann™ series CUBEFuse™ holder is a finger-safe modular system of single-pole 30, 60, 100, 200, 225 and 400 amp holders. All holders dovetailed together to create the desired number of poles for the application, including mixed amp ratings between the 30, 60 and 100 amp holders.
The 200, 225 and 400 amp holders require installing lugs to make conductor connections. These are listed on page 3.
The CUBEFuse holder is available as the 600 V UL® Listed version utilizing the time-delay Low-Peak™ CUBEFuse (TCF up to 400 A) or fast-acting CUBEFuse (FCF up to 100 A), or the 690 V UL Recognized version utilizing the fast-acting wind CUBEFuse (WCF up to 100 A).
Ratings
• Volts• 600 Vac / 300 Vdc (UL Listed)
• 690 Vac (UL Recognized up to 100 A)
• Amps• 30, 60, 100, 200, 225, 400 A
• SCCR• 300 kA RMS Sym. (30, 60, 100 A UL Listed)
• 200 kA RMS Sym. (200, 225, 400 A UL Listed)
• 200 kA RMS Sym. (CSA® Certified 100 A and below)
• 100 kA DC (UL Listed and CSA Certified 100 A and below)
• 50 kA RMS Sym. (UL Recognized)
Agency information
• 600 V UL Listed, Guide IZLT, File E14853• 690 V UL Recognized, Guide IZLT2, File E14853• CSA Certified, Class 6225-01, File 47235, cURus
component Certified (30, 60 and 100 A holders)• CE (100 A and below)• RoHS compliant
Mounting
• 35 mm DIN-Rail/panel (Up to 100 A)• Panel mount (200 to 400 A)
Operating and storage temperature range
• -40°C to 80°C (-40°F to 176°F)
Catalog no.Max holder
ampsFuse amp
range
600 V UL Listed
TCFH30N 30 1-30
TCFH60N 60 1-60
TCFH100N 100 1-100
TCFH200N 200 110-200
TCFH225N 225 110-225
TCFH400N 400 110-400
690 V UL Recognized
TCFH30NW 30 1-30
TCFH60NW 60 1-60
TCFH100NW 100 1-100
Features
• Finger-safe construction for enhanced safety*• Amp rating rejection helps prevent overfusing
by rejecting higher fuse amp ratings• Smallest installed fuse and holder footprint of
any Class J or R installation• All holders dovetail together to create the
required number of poles, mixed 30, 60 and 100 A holders dovetail together
• 30, 60 and 100 A holders have dual wire rated box lug terminals for wiring ease
• 200, 225 and 400 A holders available with a variety of lugs and terminal shrouds for application flexibility
• Up to 300 kA SCCR withstands high fault currents
* 200, 225 and 400 A holders require installed shrouds.
Technical Data 9007Effective March 2019Supersedes February 2019
BUSSMANNSERIES
2
Technical Data 9007Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
30, 60 and 100 A CUBEFuse holder fuse applications
Holder catalog no. Volts
CUBEFuse type and amp range
TCF and TCF_RN FCF_RN WCF_RN
TCFH30N
600
1-30 1-30
—TCFH60N 1-60 1-60
TCFH100N 1-100 1-100
TCFH30NW
690 — —
1-30
TCFH60NW 1-60
TCFH100NW 1-100
Conductor ratings and torque for 30, 60 and 100 A holders
Ratings are for 75°C Cu AWG solid/stranded conductors. Torque is in N•m (lb-in).
Terminal wire rating
Holder catalog no.
TCFH30N / TCFH30NW
TCFH60N / TCFH60NW
TCFH100N / TCFH100NW
Single 8-10; 2.8 (25), 12-18; 2.6 (20)
10-14; 2.6 (20), 4-8; 3.9 (35)
10-18; 2.6 (20)**, 1-8; 4.5 (40)†
Dual 10-18; 2.8 (25)* 10-18; 2.6 (20), 6-8; 3.9 (35) 6; 5.1 (45)†
* 10-18 AWG stranded, 14-18 AWG solid** Solid and stranded† Stranded
Carton quantity and weight
Amp rating Qty. Weight per carton lb (kg)
30 12 2.42 (1.10)
60 12 2.57 (1.17)
100 6 1.38 (0.63)
All 30, 60 and 100 A CUBEFuse holders dovetail together to create the desired number of poles. Each holder accepts CUBEFuse amp ratings up to its rating. E.g., the 60 amp holder will accept a CUBEFuse from 1 to 60 A.
Amps H I J K L M
Max height with fuse
30 2.3 (58) 0.76 (19) 1.36 (34) 0.15 (4) — — 2.36 (60)60 2.6 (66) 1.03 (26) 1.60 (41) 0.17 (4) — — 2.73 (69)
100 2.91 (74) 1.05 (27) 2.01 (51) 0.15 (4) 0.80 (20) 2.51 (64) 3.27 (83)
Dimensions — in (mm)
Recommended Bussmann series fuses
Type Amp range Data sheet
600 volt UL Listed
Time-delay indicating Low-Peak™ 6-100 A9000
Time-delay non-indicating Low-Peak 1-100 A
Fast-acting non-indicating 1-100 A 2147
690 volt UL Recognized
Fast-acting wind power 1-100 A 9009
3
Technical Data 9007Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
200, 225 and 400 A CUBEFuse holder fuse applications
Holder catalog no. Volts CUBEFuse amp range
TCFH200N
600 Vac/300 Vdc
110-200
TCFH225N 110-225
TCFH400N 110-400*
* Achieving 400 A continuous current requires three ganged holders and installed lug catalog number CCP2-L4B-3 to permit the necessary copper conductor size.
Available lug kits
For complete installation, the 200, 225 and 400 A CUBEFuse holders require lugs. The table below contains the information necessary for ordering the desired lug kit for the application.
Accessories
Catalog no.Holder amps Description
CCP2-TS2-3
200/225
3-pole terminal shroudCCP2-PB2 Phase barriers (pack of 2)
CCP2-CWK2 1/4” QC terminals. Use with CCP2-L2-1A, CCP2-MW2-3 and CCP2-MW2-6 lugs (pack of 12)
CCP2-TS6-3400
3-pole terminal shroudCCP2-PB6 Phase barriers (pack of 2)
Recommended Bussmann series fuses
Type Amp range Data sheet
Time-delay indicating Low-Peak110-400 A 9000
Time-delay non-indicating Low-Peak
Available lugs, conductor ratings and terminal torques
Catalog no. DescriptionLugs per cat. no.
Wire range AWG (mm2)
Wire type/temp.
Conductor torque N•m
(lb-in)Lug mounting screw
torque N•m (lb-in)200/225 A holdersCCP2-L2-1 Stainless steel lug 1 350-4 (185-25) Cu 75°C 20.3 (180) 0.9 (8)CCP2-L2-1A Aluminum lug* 1 350-4 (185-25) Cu/Al 75°C 28.2 (250) 13.5 (120)CCP2-MW2-3 3-port multi-wire terminal with shroud*† 3 2-14 (35-2.5) Cu/Al 75°C 7.9 (70) 10.8 (95)CCP2-MW2-6 6-port multi-wire terminal with shroud*† 3 6-14 (16-2.5) Cu/Al 75°C 2.8 (25) 10.8 (95)* These lugs also accept 1/4” quick connect control wire terminals. Order catalog number CCP2-CWK2 (package of 12 terminals).
400 A holders
CCP2-L4-1 Stainless steel lug 1 500-3 (240-35) Cu 75°C 42.0 (375)
22.0 (200)
CCP2-L4-1A Aluminum lug 1 500-3 (240-35) Cu/Al 75°C 42.0 (375)CCP2-L4B-3 Stainless steel lug kit with shroud† 3 750-500 (400-240) Cu 75°C 57.0 (500)CCP2-L4B-3A Aluminum lug kit with shroud† 3 750-500 (400-240) Cu/Al 75°C 62.0 (550)CCP2-L6-3 2-port stainless steel lug kit with shroud 3 (2) 500-2 (240-35) Cu 75°C 42.0 (375)CCP2-L6-3A 2-port aluminum lug kit with shroud 3 (2) 500-2 (240-35) Cu/Al 75°C 42.0 (375)
CCP2-MW6-6 6-port multi-wire terminal with shroud† 3 1/0-14 (50-2.5) Cu/Al 75°C
10-14 = 3.9 (35)
8 = 4.5 (40)4-6 = 5.0 (45
1/0-2 = 5.6 (50)† This is a lug kit with three lugs and a shroud for installation on three ganged CUBEFuse holders.
Carton quantity
Catalog no. Description Qty.
200/225 A holdersTCFH200N 1-pole 200 A holder 1TCFH225N 1-pole 225 A holder 1CCP2-L2-1 Stainless steel lug 1CCP2-L2-1A Aluminum lug 1CCP2-MW2-3 3-port multi-wire terminal with shroud 3CCP2-MW2-6 6-port multi-wire terminal with shroud 3CCP2-CWK2 1/4” quick connect control wire terminals 12CCP2-TS2-3 3-pole terminal shroud 1CCP2-PB2 Phase barriers (pack of 2) 2
400 A holders
TCFH400N 1-pole 400 A holder 1
CCP2-L4-1 Stainless steel lug 1
CCP2-L4-1A Aluminum lug 1CCP2-L4B-3 Aluminum lug kit with shroud 3CCP2-L4B-3A Aluminum lug kit with shroud 3CCP2-MW6-6 6-port multi-wire terminal with shroud 3CCP2-TS6-3 3-pole terminal shroud 1CCP2-PB6 Phase barriers (pack of 2) 2
Lug
Terminal shroud
All 200, 225 and 400 amp holders require installing lugs. Only three ganged holders can accept terminal shrouds. See table below.
4
Technical Data 9007Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
167.7(6.6)
27.5(1.1)
43.66(1.7)
2xØ 4.2 (0.2)
33.4(1.3)
400 A holder
276.0(10.9)
99.6(3.9)
139.2(5.5)
3-pole ganged 400 A holder with installed shroud
40.7(1.6) 25.3
(1.0)
34.9(1.4)
23.9(0.9)
124.5(4.9)
2xØ 4.2 (0.2)
Dimensions — mm (in)
200/225 A holder
87.6(3.4)
282.6(11.1)
104.84.1)
108.1(4.2)
3-pole ganged 200 A holder with installed shroud
5
Technical Data 9007Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
Ordering a complete 200/225 A holder installation
For a complete installation, select from the following required and optional components, and accessories.
Catalog no.
Holders Amps Poles
Req
uir
ed
TCFH200N 200
1
Order required quantity for installation
TCFH225N 225
And
Lug kits Description
CCP2-L2-1 Stainless steel lug, 75° Cu only, 350 kcmil-4, 1 per pack
CCP2-L2-1A Aluminum lug, 75°C Cu/Al, 350 kcmil-4, 1 per pack
CCP2-MW2-3 3-port multi-wire lug, 75°C Cu/Al, 2-14, 3 per pack, includes terminal shroud
CCP2-MW2-6 6-port multi-wire lug, 75°C Cu/Al, 6-14, 3 per pack, includes terminal shroud
And
Acc
esso
ries
Terminal shrouds Description
CCP2-TS2-3 3-pole terminal shroud with phase shields, 1 per pack
Phase barriers Description
CCP2-PB2 Phase barriers, 2 per pack
And
Control terminals Description
CCP2-CWK2 1/4” quick-connect control wire terminals - mounts on installed lug (cannot be used with lug CCP2-L2-1), 12 per pack
UL Class CF CUBEFuse holdersTechnical Data 9007Effective March 2019
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton, Bussmann, CUBEFuse, and Low-Peak are valuable trademarks of Eaton in the US and other countries. You are not permitted to use the Eaton trademarks without prior writ-ten consent of Eaton.
CSA is a registered trademark of the Canadian Standards GroupUL is a registered trademark of the Underwriters Laboratories, Inc.
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com
Bussmann Division114 Old State RoadEllisville, MO 63021United StatesEaton.com/bussmannseries
© 2019 EatonAll Rights ReservedPrinted in USAPublication No. 9007 – BU-SB18087March 2019
For Eaton’s Bussmann series product information, call 1-855-287-7626 or visit:Eaton.com/bussmannseries
Follow us on social media to get the latest product and support information.
Ordering a complete 400 A holder installation
For a complete installation, select from the following required and optional components, and accessories.
Catalog no.
Holder Amps Poles
Req
uir
ed
TCFH400N 4001
Order required quantity for installation
AndLug kits Description
CCP2-L4-1 Stainless steel lug, 75° Cu only, 500 kcmil-3, 1 per pack
CCP2-L4-1A Aluminum lug, 75° Cu only, 500 kcmil-3, 1 per pack
CCP2-L4B-3 Stainless steel lug, 75° Cu only, 750-500 kcmil, 3 per pack, includes terminal shroud
CCP2-L4B-3A Aluminum lug, 75°C Cu/Al, 750-500 kcmil, 3 per pack, includes terminal shroud
CCP2-L6-3 2-port stainless steel lug, 75° Cu only, 500 kcmil-2, 3 per pack, includes terminal shroud
CCP2-L6-3A 2-port aluminum lug, 75° Cu only, 500 kcmil-2, 3 per pack, includes terminal shroudCCP2-MW6-6 6-port multi-wire lug, 75°C Cu/Al, 1/0-14, 3 per pack, includes terminal shroud
And
Acc
esso
ries
Terminal shrouds Description
CCP2-TS6-3 3-pole terminal shroud with phase shields, 1 per pack
Phase barriers Description
CCP2-PB6 Phase barriers, 2 per pack