type 2 co ordination in lv switchgear

Upload: kapil

Post on 07-Apr-2018

252 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    1/46

    TOPICS

    1) REQUIREMENTS AS PER STANDARDS.

    2) FAULT LEVEL CALCULATIONS.

    3) TYPE 2 CO-ORDINATION

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    2/46

    L.V. SWITCHGEAR STANDARDSIEC 60947/IS:13947

    PART 1

    PART 2

    PART 3

    PART 4

    FUSES

    MCBs

    GENERAL RULES

    CIRCUIT BREAKERS

    SDF/SD

    CONTACTORS,RELAYS, STARTERS,

    IS:13703

    IS:8828/IEC 60898

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    3/46

    Standards for Circuit Breakers

    IS 13947 ( Part 2 )

    IEC 60947-2

    EN 60947-2

    BSEN 60947-2

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    4/46

    Highlights of New Standards

    Utilization category - A & B New short circuit duties - Ics, Icu & Icw

    Special Sequence of testing

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    5/46

    UTILIZATION CATEGORY

    Category : A

    Circuit breakers not specifically intendedfor selectivity under short circuitconditions

    (i.e.) without an intentional time delay andtherefore without a short time withstandcurrent rating

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    6/46

    UTILIZATION CATEGORY

    Category : B

    Circuit breakers specifically intended for

    selectivity under short circuit conditions.Such breakers must have an intentional timedelay option and a short time withstandrating (Icw).

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    7/46

    TEST SEQUENCEAs Per IS 13947 (Part 2) / IEC 60947.2

    Test Sequence I - Tests

    General performanceTripping limits & characteristics

    Dielectric properties characteristics

    Mechanical operation and electrical operations

    Overload performance (6In, 12 operations)Verification of dielectric withstand

    Verification of temperature rise

    Verification of overload release

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    8/46

    Minimum expectations

    Ie (A)No. of Operating Cycles

    Without

    Current

    With

    Current

    Total

    0 - 100 8500 1500 10000

    100 - 315 7000 1000 8000

    315 - 630 4000 1000 5000

    630 - 2500 2500 500 3000

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    9/46

    Implication of Sequence 1

    Minimum mechanical and electrical lifespecified for different current ratings

    Temperature rise to be done on breakerafter the mechanical/electrical life/overload tests are done.

    Re-Verification of dielectric test and

    overload characteristics at the end ofmechanical /electrical/overload tests

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    10/46

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    11/46

    TEST SEQUENCEAs Per IS 13947 (Part 2) / IEC 60947.2

    Test Sequence II - Tests

    Rated service S/C breaking capacity

    (O-CO-CO)Verification of operational capability(Electrical life = 5%)

    Verification of dielectricwithstandVerification of temperature riseVerification of overload release

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    12/46

    Implication of Ics rating

    Must clear three S.C. faults: O - CO - COcycle

    Must pass dielectric strength test

    Overload characteristics to be maintained Must be able to carry full load current

    without excessive temperature rise (

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    13/46

    TEST SEQUENCEAs Per IS 13947 (Part 2) / IEC 60947.2

    Test Sequence III - Tests

    Verification of overload release

    Rated ultimate s/c breaking capacity (O-CO)

    Verification of dielectric withstand

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    14/46

    Implication of Icu rating

    Must clear two S.C. shots : O - CO Cycle

    Must pass dielectric strength test

    May not be able to carry full load current

    Needs immediate replacement

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    15/46

    TEST SEQUENCEAs Per IS 13947 (Part 2) / IEC 60947.2

    Test Sequence IV - Tests

    Rated Short Time Withstand current (Icw)

    Pass claimed value of Icw for claimed time.

    Combined Sequence

    Do Icw, Ics on the same breaker

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    16/46

    FAULT LEVEL

    CALCULATIONS(As per IS 13234 : 1992 &

    IEC Pub 909 : 1988)

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    17/46

    FAULT LEVEL AT ANY

    GIVEN POINT OF THEINSTALLATION IS THEMAXIMUM CURRENT THAT

    CAN FLOW IN CASE OFS/C AT THAT POINT

    WHAT IS FAULT LEVEL

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    18/46

    PURPOSE OF FAULT LEVELCALCULATIONS

    FOR SELECTING S.C.P.Ds OF ADEQUATES/C BREAKING CAPACITY

    FOR SELECTING BUSBARS, BUSBARSUPPORTS, CABLES & SWITCHGEARS,DESIGNED TO WITHSTAND THERMAL &MECHANICAL STRESSES BECAUSE OF S/C

    TO DO CURRENT BASED DISCRIMINATIONBETWEEN CBs

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    19/46

    FAULT LEVEL CALCULATIONS

    TYPES OF FAULTS

    SYMMETRICAL ASYMMETRICAL

    LINE TO LINE

    DOUBLE LINE TO

    EARTH

    LINE TO EARTH

    THREE PHASE FAULT

    LVSM4.PPT/NRS

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    20/46

    SOURCES OF SHORTCIRCUIT CURRENTS

    ELECTRIC UTILITY SYSTEMS

    D.G SETS CONDENSERS

    MOTORS

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    21/46

    NATURE OF SHORT CIRCUITCURRENT

    THE SHORT CIRCUIT CURRENT WILL

    CONSIST OF FOLLOWING COMPONENTS :

    THE AC COMPONENT WITH CONSTANTAMPLITUDE

    THE DECAYING DC COMPONENT

    SOURCE : UTILITY SYSTEM

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    22/46

    NATURE OF SHORT CIRCUIT CURRENT

    TOP ENVELOPE

    DECAYING DC COMPONENT

    CURRENT

    BOTTOM ENVELOPE

    IP

    TIME

    WAVEFORM

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    23/46

    CALCULATION ASSUMPTIONS

    TYPE OF SHORT CIRCUIT : THREE PHASEBOLTED SHORT CIRCUIT

    IMPEDANCES OF BUSBAR/SWITCHGEAR/C.T.

    /JOINTS ARE NEGLECTED TRANSFORMERS ARE CONNECTED TO

    INFINITE BUS ON H.T. SIDE

    TRANSFORMER TAP IS IN THE MAX. POSITION

    S/C CURRENT WAVEFORM IS A PURE SINEWAVE

    DISCHARGE CURRENT OF CAPACITORS ARENEGLECTED

    WHAT ?

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    24/46

    CALCULATION OF SHORT CIRCUIT CURRENT

    LVSM4.PPT/NRS

    IS/C =

    1 . 05 * LINE VOLTAGE

    3 * ( Z TR + Z CABLE )

    Z TR =

    (in ohms)

    % Z * 10 * KV 2

    KVA

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    25/46

    CASE STUDY

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    26/46

    STEP 1 : SINGLE LINE DIAGRAM

    )

    )

    )

    )

    )

    )

    F1

    F2

    PCC

    MCC BUSBAR

    U/G CABLE

    M2M1 M3 M4

    11

    21 22 23 24

    31

    150HP 100HP 100HP 150HP

    ) CB

    SDF

    STARTER

    G

    )

    )

    12

    13

    STANDBY GENERATOR

    1250 KVA

    TRANSFORMER

    1600 KVA

    350 A 300 A 300 A

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    27/46

    STEP 2 : SYSTEM DATA

    TRANSFORMER: 11/0.433 KV1600 KVA

    %R = 0.94

    %X = 5.46%Z = 5.54

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    28/46

    STEP 2 : SYSTEM DATA

    CABLE : R = 0.062 /KMX = 0.079 /KM

    LENGTH OF CABLE, 21 TO 31= 100M

    INDUCTION MOTORS : M1, IrM = 200AM2, I

    rM= 135A

    M3, IrM = 135A

    M4, IrM = 200A

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    29/46

    STEP 3 : CALCULATION OFRT & XT

    RT =10 (%R)(SECONDARY KV)2

    KVA

    10 (0.94)(0.433)2

    1600= = 0.001102 OHMS

    XT

    =10 (%X)(SECONDARY KV)2

    KVA

    10 (5.46)(0.433)2

    1600= = 0.006398 OHMS

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    30/46

    STEP 4 : CALCULATION OFRL & XL

    RL = 0.062

    0.1 = 0.0062 OHMS

    XL = 0.079 0.1 = 0.0079 OHMS

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    31/46

    STEP 5 : CALCULATION OFZ UP TO THE POINT OF

    FAULT

    TOTAL Z UP TO FAULT LOCATION F1

    = (RT)2 + (XT)2 = (0.001102)2 + (0.006398)2= 0.00649

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    32/46

    STEP 5 : CALCULATION OF

    Z UP TO THE POINT OFFAULT

    TOTAL Z UP TO FAULT LOCATION F2

    = (RT + RL)2 + (XT + XL)2 = (0.007302)2 + (0.01430)2= 0.01606

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    33/46

    STEP 6 : CALCULATION OF RMSVALUE OF S/C CURRENT AT

    THE POINT OF FAULT

    IK AT FAULT LOCATION F1 = c Un3 Z= 1.05 4153 0.00649= 38765 A OR 38.77 kA

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    34/46

    STEP 6 : CALCULATION OF RMSVALUE OF S/C CURRENT AT

    THE POINT OF FAULT

    IKAT FAULT LOCATION F2 = c Un3 Z=

    1.05 4153 0.01606

    = 15665 A OR 15.67 kA

    STEP 7 : CALCULATION OF

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    35/46

    STEP 7 : CALCULATION OFMAKING CAPACITY AS PER

    STANDARD IEC 60947-2

    2.20.250< I

    2.10.2520< I

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    36/46

    STEP 8 : CALCULATION OF

    PEAK VALUE OF S/CCURRENT AT THE POINT OFFAULT

    IP AT FAULT LOCATION F1 = 2.138.77

    = 81.41 kA (PEAK)

    IP AT FAULT LOCATION F2 =2 15.67

    = 31.34 kA (PEAK)

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    37/46

    CALCULATION OF X AND R FORGENERATOR

    The value of xd will be given in percentageterms.

    Calculate xd in ohms.

    Calculate R in ohms as per data in standard: Rg =0.15 xd for generators less than 1000V Rg =0.07 xd for generators up to 100MVA Rg =0.05 xd for generators 100MVA and

    above.Apply correction factor and recalculate R and X. Find Z and use in the formulae.

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    38/46

    TYPE 2 CO-ORDINATION WITHFUSES/MCCB/MPCB

    for

    MOTOR FEEDERS

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    39/46

    MOTOR FEEDER

    S.C.P.D.: Fuse / MCCB/MPCB(Isolation & Short Circuit Protection)

    Starter:

    Contactor - Normal / overloadoperations

    +

    Relay - Overload protectionup to locked rotor currentM

    S.C.P.D.

    Starter

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    40/46

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    41/46

    Types of Co-ordination( IS 13947 / IEC 60947 )

    TYPE 1

    Damage to contactor & overload relay is

    acceptable. No discharge beyond the enclosure is

    permitted.TYPE 2

    No damage to overload relay or other parts is

    allowed. Light welding of contacts of the contactoris permitted if they can be easily separated (e.g. bya screw driver) without significant deformation

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    42/46

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    43/46

    Ie(AC3) Prospective current r in A

    0-16A 1kA

    16-63A 3kA

    63-125A 5kA

    125-315A 10kA

    315-630A 18kA

    630-1000A 30kA1000-1600A 42kA

    r current values

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    44/46

    CURRENT

    TIME

    CONTACTOR BREAKING

    CAPACITY

    Relay H.R.C. Fuse

    Ico

    Discrimination

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    45/46

    Type 2 Co-ordination benefits

    Safe and reliable performance of productsduring normal and overload conditions

    Proper and proven co-ordination with short

    circuit protective device

    IS / IEC / EN now make verification of co-ordination with S.C.P.D. a mandatoryrequirement

  • 8/4/2019 Type 2 Co Ordination in LV switchgear

    46/46

    THANK YOU