The RS burners series covers a firing range from 81 to 2290 kW, and it has been designed for use in hot or superheater water boilers, hot air or steam generators, diathermic oil boilers. Operation is "two stage progressive"; the burners are fitted with a microprocessor control panel which supplies indication of operation and diagnosis of fault cause. Optimisation of sound emissions is guaranteed by the use of fans with reverse curve blades and sound deadening material incorporated in the air suction circuit. The elevated performance of the fans and combustion head, guarantee flexibility of use and excellent working at all firing rates. The exclusive design ensures reduced dimensions, simple use and maintenance. A wide range of accessories guarantees elevated working flexibility. TS0046UK03 RS SERIES TWO STAGE PROGRESSIVE GAS BURNERS RS 28 81/163 ÷ 325 kW RS 38 105/232 ÷ 440 kW RS 50 116/290 ÷ 580 kW RS 70 192/465 ÷ 814 kW RS 100 232/698 ÷ 1163 kW RS 130 372/930 ÷ 1512 kW RS 190 470/1279 ÷ 2290 kW

Upload: trancong

Post on 25-May-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

The RS burners series covers a firing range from 81 to 2290 kW, and it has been designedfor use in hot or superheater water boilers, hot air or steam generators, diathermic oilboilers.Operation is "two stage progressive"; the burners are fitted with a microprocessor controlpanel which supplies indication of operation and diagnosis of fault cause.Optimisation of sound emissions is guaranteed by the use of fans with reverse curveblades and sound deadening material incorporated in the air suction circuit.The elevated performance of the fans and combustion head, guarantee flexibility of useand excellent working at all firing rates.The exclusive design ensures reduced dimensions, simple use and maintenance. A widerange of accessories guarantees elevated working flexibility.

TS0046UK03

RS SERIESTWO STAGE PROGRESSIVE GAS BURNERS

RS 28 81/163 ÷ 325 kWRS 38 105/232 ÷ 440 kWRS 50 116/290 ÷ 580 kWRS 70 192/465 ÷ 814 kWRS 100 232/698 ÷ 1163 kWRS 130 372/930 ÷ 1512 kWRS 190 470/1279 ÷ 2290 kW

RS 38

105/232÷440

90/200÷378

10,5/23÷44

12/27÷51

4/9÷17

0,6

0,12

0,42

2,9

11

70

--

RS 50

116/290÷581

100/249÷500

11,6/29÷58

13,5/34÷68

4,5/11÷23

0,75

0,12

0,65

3 - 1,7

13,8 - 8

72

--

CE 0085AP0735

RS 70

192/465÷814

165/400÷700

19/46,5÷81,4

22/54÷95

7,4/18÷32

1,4

0,3

1,1

4,8 - 2,8

25 - 14,6

75

--

CE 0085AP0944

RS 100

232/698÷1163

200/600÷1000

23/70÷116

27/81÷135

9/27÷45

1,8

0,3

1,5

5,9 - 3,4

27,7 - 16

77

--

CE 0085AP0945

3N/50/230-400~(±10%) 3/50/230~(±10%)

SQN90

12

LKS210

15

RS 190

SQN31

15

470/1279÷2290

405/1100÷1970

47/128÷229

55/149÷266

18/50÷89

Straight blades

5,5

1

4,5

15,8 - 9,1

126 - 73

83

--

CE 0085AT0042

RS 130

372/930÷1512

320/800÷1300

37/93÷151

43/108÷176

14,4/36÷59

2,6

0,4

2,2

8,8 - 5,1

57,2 - 33,2

78,5

--

CE 0085AP0946

RS 28

81/163÷325

70/140÷280

8/16÷32

9,4/19÷38

3/6,5÷12,5

0,37

0,12

0,25

2,1

10

40

68

--

CE 0085AP0733

TECHNICAL DATAFu

el /

air

dat

aE

lect

rica

l d

ata

Em

issi

on

sA

ppro

val

Model

Burner operation mode

Modulation ratio at max. output

Type

Run time

Working temperature

Net calorific value G20 gas

G20 gas density

G20 gas delivery

Net calorific value G25 gas

G25 gas density

G25 gas delivery

Net calorific value LPG gas

LPG gas density

LPG gas delivery

Fan

Air temperature

Electrical supply

Auxiliary electrical supply

Control box

Total electrical power

Auxiliary electrical power

Protection level

Motor electrical power

Rated motor current

Motor start up current

Motor protection level

Operation

Sound pressure

Sound power

CO Emission

NOx Emission

Directive

Conforming to

Certification

Servo-motor

s

kW

Mcal/h

°C min./max.

kWh/Nm3

kg/Nm3

Nm3/h

kWh/Nm3

kg/Nm3

Nm3/h

kWh/Nm3

kg/Nm3

Nm3/h

Type

Max. °C

Ph/Hz/V

Ph/Hz/V

Type

kW

kW

IP

kW

A

A

IP

V1 - V2

I1 - I2

dB(A)

W

mg/kWh

mg/kWh

Heat output

Ignitiontransformer

Centrifugal with reverse curve blades

RS 38

105/232÷440

90/200÷378

10,5/23÷44

12/27÷51

4/9÷17

0,56

0,12

0,45

2 - 1,2

9,5 - 5,5

70

--

Two stage progressive

2 ÷ 1

0/40

10

0,71

8,6

0,78

25,8

2,02

60

1/50/230 ~ (±10%)

RMG

44

54

230V - 1x8 kV

1A - 20 mA

Intermittent (at least one stop every 24 h)

< 40

< 130

90/396 - 89/336 - 73/23 - 92/42 EEC

EN 676

Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, thetechnical data, the equipment and the accessories can be changed.This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shallnot be divulged, nor duplicated in whole or in part.

Reference conditions:Temperature: 20°CPressure: 1000 mbarAltitude: 100 m a.s.l.Noise measured at a distance of 1 meter.

CE 0085AP0734

1/50/230~(±10%)

2

FIRING RATES

Useful working field for choosing the burner

Modulation range (1st stage operation range)

Test conditions conforming to EN 676:Temperature: 20°CPressure: 1000 mbarAltitude: 100 m a.s.l.

0

2

4

6

5

3

1

7

9

8

10

100 kW

0

0

0

20

40

60

50

30

10

70

90

80

100

200 300 400 500 600 700

0

2

4

6

5

3

1

7

9

8

10

11

kW

12

13

14

0

0

0

20

40

60

50

30

10

70

90

80

100

110

120

130

140

15150

100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100

RS 50

RS 28

RS 38

RS 70

RS 100

RS 130

RS 190

hP

a (m

bar

)

- 1

mm

H2O

-10

hP

a (m

bar

)

- 1

mm

H2O

-10

Mcal/h100 200 300 400 500 600

Mcal/h

600400200 800 1000 1200 1400 1600 1800 2000 2200 2400

3

The burners are fitted with a butterfly valve to regulate the fueldelivery on 1st and 2nd stage, controlled by a variable profilecam servomotor.

Fuel can be supplied either from the right orleft hand sides.

The gas train can be selected to best fit systemrequirements depending on the fuel outputand pressure in the supply line.The gas train can be “Multibloc“ type(containing the main components in a singleunit) or “Composed” type (assembly of thesingle components).

GAS TRAIN

FUEL SUPPLY

Example of the variable profile cam on RS 70-100-130 burners.

Gas input pipework

Manual valve

Anti-vibration joint

Pressure gauge with pushbutton cock

Filter

Pressure regulator (vertical)

Minimum gas pressure switch

VS safety solenoid (vertical)

VR regulation solenoid (vertical)Two settings: - firing output (rapid opening)

- maximum output (slow opening)

Gasket and flange supplied with the burner

Gas adjustment butterfly valve

Burner

Seal control mechanism for valves 8-9. Accordingto standard EN 676, the seal control is compulsoryfor burners with maximum output above 1200 kW(in gas train with seal control)

Gas train-burner adapter

Maximum gas pressure switch

Combustion head pressure

Pressure downstream from the regulator

Pressure upstream from the filter

Gas train supplied separately, with the code given in the table

Installer’s responsibility

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

P1

P2

P3

L

L1

MULTIBLOC gas train type MBD 420

L L1

MULTIBLOC gas train type MBC 1200

COMPOSED gas train

L L1

12

P1

11

1015

14 9 8 P2 6 P3

4

3 2 15

12

7

12

13

4

P1

15 1110

14 6

L L1

9 13 8

7

5

4

P3P2 3 2 1

P1

1511

10

14 9 13 6 8

7

5

4

P3P2 3 2 1

MU

LTIB

LOC

GA

S T

RA

INS

Gas trains are approved bystandard EN 676 togetherwith the burner.

The overall dimensions ofthe gas train depends onhow they are constructed.The following table showsthe maximum dimensionsof the gas trains that canbe fitted to RS burners,intake and outlet diametersand seal control if fitted.Please note that the sealcontrol can be installed asan accessory, if not alreadyinstalled on the gas train.T h e m a x i m u m g a spressure of gas train“Multibloc” type is 360mbar, and that one of gastrain “Composed” type is500 mbar.MULTIBLOC guarantees arange of pressure towardthe burner from 3 to 60mbar. For version DN 65and DN 80 is from 20 to 40mbar.The range of pressure inthe MULTIBLOC with flangecan be modified choosingthe stabiliser spring (seegas train accessory).

CO

MP

OS

ED

GA

S T

RA

INS

Example of gas train “MULTIBLOC”type MBD

Name

MBD 407

MBD 410

MBD 412

MBD 412 CT

MBD 415

MBD 415 CT

MBD 420

MBD 420 CT

MBC 1200 SE 50

MBC 1200 SE 50 CT

MBC 1900 SE 65 FC

MBC 1900 SE 65 FC CT

MBC 3100 SE 80 FC

MBC 3100 SE 80 FC CT

Code

3970053

3970054

3970144

3970197

3970180

3970198

3970181

3970182

3970221

3970225

3970222

3970226

3970223

3970227

Ø i

3/4”

1”

1”1/4

1”1/4

1”1/2

1”1/2

2”

2”

2”

2”

DN 65

DN 65

DN 80

DN 80

Ø o

3/4”

3/4”

1”1/2

1”1/2

1”1/2

1”1/2

2”

2”

2”

2”

DN 65

DN 65

DN 80

DN 80

X mm

371

405

433

433

523

523

523

523

573

573

583

583

633

633

Y mm

196

217

217

217

250

250

300

300

161

290

237

300

240

320

Z mm

120

145

145

262

100

227

100

227

425

426

430

430

500

500

Seal Control

-

-

-

Incorporated

-

Incorporated

-

Incorporated

-

Incorporated

-

Incorporated

-

Incorporated

Y

Z X

Øi

Øo

Y

Z X

Øi

Øo

Example of gas train “MULTIBLOC”type MBC 1200

Y

ZX

Øo

Example of gas train“COMPOSED”type MBC 1900 - 3100

Øi

5

The diagrams indicate the minimum pressure drop of the burners with the various gas trains thatcan be matched with them; at the value of these pressure drop add the combustion chamberpressure.The value thus calculated represents the minimum required input pressure to the gas train.

RS 28 RS 28

RS 38 RS 38

PRESSURE DROP DIAGRAM

NATURAL GAS LPG

Gas train

MBD 412 CT

MBD 415

MBD 415 CT

Code

3970197

3970180

3970198

Adapter

-

-

-

Seal Control

Incorporated

Accessory

Incorporated

Gas train

MBD 407

MBD 410

MBD 412

Code

3970053

3970054

3970144

Adapter

3000824

3000824

-

Seal Control

Accessory

Accessory

Accessory

Gas train

MBD 407

MBD 410

MBD 412

MBD 412 CT

Code

3970053

3970054

3970144

3970197

Seal Control

Accessory

Accessory

Accessory

Incorporated

Gas train

MBD 415

MBD 415 CT

MBD 420

MBD 420 CT

Code

3970180

3970198

3970181

3970182

Adapter

-

-

3000822

3000822

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Adapter

3000824

3000824

-

-

kcal/h X 1000

10

25

15

20

30

5

0140 150 200 250 280

mb

ar

G25G20

0

5

15

25

30

35

20

10

40

35

40

45

45

50

55

kcal/h X 1000

10

25

15

20

30

5

0140 150 200 250 280

mb

ar

LPG

35

40

45

kW300200 250163 325

kcal/h X 1000

10

25

15

20

30

5

0

200 300250 350 378

mb

ar

G25G20

0

5

15

25

30

35

20

10

40MBD 410

MBD 412 - 412 CT

MBD 415 - 415 CT

MBD 420 - 420 CT

kcal/h X 1000

10

25

15

20

30

5

0

200 300250 350 378

mb

ar

LPG

MBD 410

MBD 412 - 412 CT

MBD 415 - 415 CT

MBD 420 - 420 CT

kW300 440400250 350232

400

45

35

40 MBD 407ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

pMBD 410

MBD 412 - 412 CT

MBD 407

MBD 410

MBD 412 - 412 CT

MBD 407

MBD 415 - 415 CT

kW300200 250163 325

kW300 440400250 350232

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

6

RS 50 RS 50

RS 70 RS 70

NATURAL GAS LPG

Gas train

MBD 407

MBD 410

MBD 412

MBD 412 CT

MBD 415

Code

3970053

3970054

3970144

3970197

3970180

Adapter

3000824

3000824

-

-

-

Seal Control

Accessory

Accessory

Accessory

Incorporated

Accessory

Gas train

MBD 412

MBD 412 CT

MBD 415

MBD 415 CT

Code

3970144

3970197

3970180

3970198

Adapter

-

-

3000843

3000843

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBD 415 CT

MBD 420

MBD 420 CT

MBC 1200 SE

MBC 1200 SE CT

Code

3970198

3970181

3970182

3970221

3970225

Adapter

-

3000822

3000822

3000822

3000822

Seal Control

Incorporated

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBD 420

MBD 420 CT

MBC 1200 SE

MBC 1200 SE CT

Code

3970181

3970182

3970221

3970225

Adapter

-

-

-

-

Seal Control

Accessory

Incorporated

Accessory

Incorporated

10

25

15

20

45

5

0

30

35

40

50

mb

ar

249 300 350 400 450kcal/h X 1000

500

G25G20

0

20

40

50

30

10

60

5

25

45

55

35

15

MBD 410

MBD 412 - 412 CT

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

10

20

0

30

40

50

mb

ar

249 300 350 400 450kcal/h X 1000

500

LPG

MBD 410

MBD 412 - 412 CT

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

kcal/h X 1000

mb

ar

30

20

40

0

10

50

400 500 600 700

G25G20

0

20

40

50

30

10

60

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

kcal/h X 1000

mb

ar

30

20

40

0

10

50

400 500 600 700

LPG

MBD 420 - 420 CT

ΔP

MBD 415 - 415 CT

kW400 550500350 450290 581

60MBD 407

kW600500 700465 814

MBC 1200 SE - 1200 SE CT

MBC 1200 SE - 1200 SE CT

MBC 1200 SE - 1200 SE CT

MBD 412 - 412 CT

kW400 550500350 450290 581

kW600500 700465 814

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

7

RS 100 RS 100

RS 130 RS 130

NATURAL GAS LPG

Code

3970221

3970225

3970222

3970226

Adapter

-

-

3000825

3000825

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBD 415

MBD 415 CT

MBD 420

MBD 420 CT

Code

3970180

3970198

3970181

3970182

Adapter

3000843

3000843

-

-

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBC 1200 SE

MBC 1200 SE CT

MBC 1900 SE

MBC 1900 SE CT

Code

3970225

3970222

3970226

3970223

3970227

Adapter

-

3000825

3000825

3000826

3000826

Seal Control

Incorporated

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBD 415

MBD 415 CT

MBD 420

MBD 420 CT

MBC 1200 SE

Code

3970180

3970198

3970181

3970182

3970221

Adapter

3000843

3000843

-

-

-

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Accessory

Gas train

MBC 1200 SE CT

MBC 1900 SE

MBC 1900 SE CT

MBC 3100 SE

MBC 3100 SE CT

kcal/h X 1000

mb

ar

10

20

30

kW

600 900800700 1000

800 900

0

1100700 1000

40

50

1163

G25

0

20

40

50

30

10

60

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

kcal/h X 1000m

ba

r

10

20

30

kW

600 900800700 1000

800 900

0

1100700 1000

40

50

1163

LPG

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

mb

ar

kW

900800 11001000

1300 140011001000 1200

1200 1300

930 1512

kcal/h X 1000

G25G20ΔP

mb

ar

kW

900800 11001000

1300 1400

0

11001000 1200

1200 1300

930 1512

kcal/h X 1000

LPG

MBD 415 - 415 CT

MBD 420 - 420 CT

ΔP

MBC 1200 SE - 1200 SE CT

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

10

40

20

30

50

0

60

70

80

90

100

110

0

20

40

50

30

10

60

70

80

90

100

110

120

130

140

MBD 415 - 415 CT

MBD 420 - 420 CT

MBC 3100 SE - 3100 SE CTMBC 1900 SE - 1900 SE CTMBC 1200 SE - 1200 SE CT

10

40

20

30

50

60

70

80

90

100

110

60

70

70

80

90

MBC 1900 SE - 1900 SE CTMBC 1200 SE - 1200 SE CT

60

70G20

MBC 1900 SE - 1900 SE CT

MBC 1200 SE - 1200 SE CT

8

Please contact the Riello Burner Technical Office for different pressure levels from thoseabove indicated and refer to the technical manual for the correct choice of the spring.

In LPG plants, Multibloc gas trains do not operate below 0°'a1C. They are only suitable forgaseous LPG (liquid hydrocarbons destroy the seal materials).

MBC 1200 gas train: the minimum operating pressure (*) is higher or equal to 10 mbar. The gastrain has to be installed next to the burner (if needed, only with the adapters listed in thecatalogue) and it has to operate in its own working field.

MBC 1900-3100 gas train: the minimum operating pressure (*) is higher or equal to 15 mbar.The gas train has to be installed next to the burner (if needed, with the adapters listed in thecatalogue) and it has to operate in its own working field.

(*) it is the upstream gas train pressure in full load operation conditions.

note

RS 190

mb

ar

20

80

40

60

100

kW

11001000 13001200

1700 1800

0

15001400 1600

1400 1500

19001279 2290

G25G20

0

40

80

100

60

20

120

kcal/h X 1000

MBC 1900 SE 65 FC - 1900 SE 65 FC CT

MBC 3100 SE 80 FC - 3100 SE 80 FC CT

MBD 420 - 420 CT

1600 1700 1800 1900

1200 2000 2100

2000

RS 190

mb

ar

20

80

40

60

100

kW

11001000 13001200

1700 1800

0

15001400 1600

1400 1500

19001279 2290

LPG

kcal/h X 1000

MBD 415 - 415 CT

MBD 420 - 420 CT

1600 1700 1800 1900

1200 2000 2100

2000

NATURAL GAS LPG

140

MBC 1200 SE 50 FC - 1200 SE 50 FC CT

MBC 1900 SE 65 FC - 1900 SE 65 FC CT

MBC 3100 SE 80 FC - 3100 SE 80 FC CTMBC 1200 SE 50 FC - 1200 SE 50 FC CT

Code

3970225

3970222

3970227

3970223

3970228

Adapter

3010128

3000831

3000831

3000832

3000832

Seal Control

Incorporated

Accessory

Incorporated

Accessory

Incorporated

Gas train

MBD 415

MBD 415 CT

MBD 420

MBD 420 CT

MBC 1200 SE 50

Code

3970180

3970198

3970181

3970182

3970221

Adapter

3000843

3000843

-

-

3010128

Seal Control

Accessory

Incorporated

Accessory

Incorporated

Accessory

Gas train

MBC 1200 SE 50 CT

MBC 1900 SE 65 FC

MBC 1900 SE 65 FC CT

MBC 3100 SE 80 FC

MBC 3100 SE 80 FC CT

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

9

SELECTING THE FUEL SUPPLY LINES

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 1 2 3 4 5 106 20

50 60 10080 200 400 800 1000600

3

69

12152230

45 61 76 95 122 152 V

PRESSURE DROP (mbar)

1 2 3 4 5 6 7 8 10 20 30 40

PIPE DIAMETER

1,4

PIPE LENGTH (m)

1/2

3/4

1"

1" 1/2

6"

1" 1/4

4"

3"2" 1/22"

= Gas output Nmc/h

f1 - G20

= 0,62 - G251,18 - G31{

fV

15,34

Figure A

The following diagram enables pressure drop in a pre-existing gas line to be calculated and to select thecorrect gas train.The diagram can also be used to select a new gas line when fuel output and pipe length are known. Thepipe diameter is selected on the basis of the desired pressure drop. The diagram uses methane gas asreference; if another gas is used, conversion coefficient and a simple formula (on the diagram) transformthe gas output to a methane equivalent (refer to figure A). Please note that the gas train dimensions musttake into account the back pressure of the combustion chamber during operations.

Control of the pressure drop in an existing gas line or selecting a new gas supply line.The methane output equivalent is determined by the formula fig. A on the diagram and the conversioncoefficient.

Once the equivalent output has been determined on the delivery scale ( ), shown at the top of thediagram, move vertically downwards until you cross the line that represents the pipe diameter; at thispoint, move horizontally to the left until you meet the line that represents the pipe length.Once this point is established you can verify, by moving vertically downwards, the pipe pressure dropof on the botton scale below (mbar).By subtracting this value from the pressure measured on the gas meter, the correct pressure value willbe found for the choice of gas train.

Example: - gas used G25- gas output 9.51 mc/h- pressure at the gas meter 20 mbar- gas line length 15 m- conversion coefficient 0.62 (see figure A)

- equivalent methane output = 9.51 = 15.34 mc/h0.62

- once the value of 15.34 has been identified on the output scale ( ), moving vertically downwards youcross the line that represents 1" 1/4 (the chosen diameter for the piping);

- from this point, move horizontally to the left until you meet the line that represents the length of 15 mof the piping;

- move vertically downwards to determine a value of 1.4 mbar in the pressure drop botton scale;- subtract the determined pressure drop from the meter pressure, the correct pressure level will be found

for the choice of gas train;

- correct pressure = ( 20-1.4 ) = 18.6 mbar

V

V

V

10

Different lengths of the combustion head can be chosen for theRS series of burners.

The choice depends on the thickness of thefront panel and the type of boiler.

Depending on the type of generator, check that thepenetration of the head into the combustion chamber iscorrect.

The internal positioning of the combustion head can easilybe adjusted to the maximum defined output by adjustinga screw fixed to the flange.

The ventilation circuit produces low noise levels with highperformance pressure and air output, inspite of the compact

dimensions.

Except for the RS 190 model, the use of reversecurve blades and sound-proofing material keeps noise level verylow. In the RS 190 model, noise has been reduced by the specialdesign of the air suction circuit.

A variable profile cam connects the fuel and air regulations, toobtain a perfect control of combustion during the change ofstage. When the burner is not operating the servomotor closescompletely the air damper to reduce heat dispersion from theboiler.A minimum air pressure switch stops the burner when there isan insufficient quantity of air at the combustion head.

COMBUSTION HEAD

VENTILATION

Example of a RS burner combustion head

Flame dimensions

Example of the air damper onRS 28 - 38 - 50 burners

Example:Burner thermal output = 2000 kW;L flame (m) = 2,7 m (medium value);D flame (m) = 0,8 m (medium value)

D

L

Burner output (MW)

3

1

2

4

Flam

e le

ng

ht

(m)

Flam

e d

iam

eter

(m

)

0 0

0,5

1

1,5

2

0 21 3 4

D max

D min

L max

L min

11

ADJUSTMENT

BURNER OPERATION MODE

On “two stage” operation, the burnergradually adapts the output to therequested level, by varying betweentwo pre-set levels (see picture A).

All RS series burners are fitted with a new microprocessor control panel for the supervision duringintermittent operation.For helping the commissioning and maintenance work, there are two main elements:

The lock-out reset button is the central operating element for resetting the burner controland for activating / deactivating the diagnostic functions.

The multi-color LED is the central indication element for visual diagnosis and interfacediagnosis.

Both elements are located under the transparent cover of lock-out reset button, as showed below.

There are two diagnostic choices, for indication of operation and diagnosis of fault cause:

- visual diagnosis :

- interface diagnosis : by the interface adapterand a PC with dedicateds o f t w a r e o r b y apredisposed flue gasanalyzer (see paragraphaccessories).

Switch

Switch

COMPUTER

or

FLUE GASANALYSER

INTERFACE ADAPTER

Picture A

Ou

tpu

tC

on

tro

lled

var

iab

le

Two stage operation

bar°C

MAX

MIN

Time

Time

12

RS 28-38-50-100-130-190

START UP CYCLE

time (s)

43 45

28

46

53

3

2

3

Off Yellow Green

0 s The burner begins the firing cycle.2 s The motor starts: pre-purge phase.43 s Ignition electrode sparks; safety valve VS and

adjustment valve VR open.45 s The spark goes out.53 s Output can be increased; start up cycle is concluded.

M

0

2°1°

0

2°1°

TL

TR

VRVS

RMGLED*

0

M

Indication of operation:

In normal operation, the various statues areindicated in the form of colour codes accordingto the table below.The interface diagnosis (with adapter) can beactivated by pressing the lock-out button for> 3 seconds.

Color code table

Operation statues

Stand-byPre-purgingIgnition phaseFlame OKPoor flameUndervoltage, built-in fuseFault, alarmFlame simulation

Color code table

LED off

Diagnosis of fault causes:

After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosisaccording to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3seconds.

The blinkers of red LED are a signal with this sequence:

(e.g. signal with n° 3 blinks – faulty air pressure monitor)

LED off3 sec. 3 sec. 3 sec.

Error code table

Possible cause of fault

No establishment of flame at the end of safety time : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner, no fuel- faulty ignition equipment

Faulty air pressure monitor

Extraneous light or simulation of flame on burner start up

Loss of flame during operation : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner

Wiring error or internal fault

Blink code

13

“TWO STAGE” OPERATION - Single-phase power supply

WIRING DIAGRAMS

Electrical connections must bemade by qualified and skilledpersonnel, according to the localregulations.

Example of plugs and sockets for electricalconnections for the RS 28-38-50 models

RS 28-38 - without seal control

RS 38-50 - without seal control RS 38-50 - with seal control

RS 28-38 - with seal control

h1 - Hour meterh2 - Hour meterIN - Manual switchMB - Burner auxiliary terminal boardX4 - 4 pin plugX6 - 6 pin plugX7 - 7 pin plugPG - Minimum gas pressure switchS - External lock-out signalTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVR - Adjustment valveVS - Safety valveT6A - 6A fuse

h1 - Hour meterh2 - Hour meterIN - Manual switchXP - Seal control plugX4 - 4 pin plugX6 - 6 pin plugX7 - 7 pin plugPG - Minimum gas pressure switchS - External lock-out signalS1 - External lock-out signal on the seal controlTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVPS - Seal controlVR - Adjustment valveVS - Safety valveT6A - 6A fuse

“TWO STAGE” OPERATION - Triple-phase power supply

h1 - Hour meterh2 - Hour meterIN - Manual switchMB - Burner auxiliary terminal boardX4 - 4 pin plugX5 - 5 pin plugX6 - 6 pin plugX7 - 7 pin plugPG - Minimum gas pressure switchS - External lock-out signalTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVR - Adjustment valveVS - Safety valveT6A - 6A fuse

h1 - Hour meterh2 - Hour meterIN - Manual switchXP - Seal control plugX4 - 4 pin plugX5 - 5 pin plugX6 - 6 pin plugX7 - 7 pin plugPG - Minimum gas pressure switchS - External lock-out signalS1 - External lock-out signal on the seal controlTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVPS - Seal controlVR - Adjustment valveVS - Safety valveT6A - 6A fuse

T6 T8

PP

P P

N123X6 PhN123X6 Ph N L1L3 L2X5 X7L1

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

T6A

PE

1,5 mm2

L1L3 L2

N L1L3 L2X5

T6A

PE

1,5 mm2

L1L3 L2

T8 T7 T6

TR

X7L1X4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

NB5

N V

VR VS

S1

NT8 T6T7 L1

PG

XP

VPS

B5

PG

N V

VR VSh1

ϑ Pϑ P

ϑ Ph1

ϑ Pϑ P

h2

~50Hz 230V ~50Hz 230V

X7L1

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

h1

ϑ Pϑ P

~50Hz 230V

P

P P

N123X6 Ph

PG

N V

VR VS

T8 T7 T6 B5X4

TR

h2

ϑ P

T6 T8

P

T8 T7 T6

TR

X7L1X4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

NN123X6 Ph B5

N V

VR VS

S1

NT8 T6T7 L1

PG

XP

VPS

B5

ϑ Ph1

ϑ Pϑ P

h2

~50Hz 230V

T8 T7 T6 B5X4

TR

h2

ϑ P

~M3~50Hz 230V3~3N 50Hz 400/230V ~M3~50Hz 230V3

~3N 50Hz 400/230V

14

EMISSIONS

The emission data has been measured inthe various models at maximum output,according to EN 676 standard.

The following table shows the supply lead sections and the type of fuse to be used.

Table A

RS 70-100-130-190 - without seal control RS 70-100-130-190 - with seal control

MB - Burner terminal boardIN - Manual switchPG - Minimum gas pressure switchS - External lock-out signalTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVR - Adjustment valveVS - Safety valveT6A - 6A fuseF - Fuse (see table A)L - Lead section (see table A)

MB - Burner terminal boardIN - Manual switchXP - Seal control plugPG - Minimum gas pressure switchS - External lock-out signalS1 - External lock-out signal on the seal controlTR - High/low flame setting thermostatTL - Threshold thermostatTS - Safety thermostatVPS - Seal controlVR - Adjustment valveVS - Safety valveT6A - 6A fuseF - Fuse (see table A)L - Lead section (see table A)

RS 28 RS 38 RS 50

230V

T61,5

400V

T61,5

230V

T61,5

400V

T61,5

RS 70 RS 100 RS 130

230V

T101,5

400V

T61,5

230V

T161,5

400V

T101,5

230V

T161,5

400V

T101,5

RS 190

230V

T252,5

400V

T202,5

Model

A

mm2

FL

400V

T61,5

230V

T61,5

RS 38

230V

T61,5

P

L1 L2 L3 N LMB 1 2

PE L1 L2 L3

T6A

N L

TS STL

IN

~50Hz 230V

3

F

7 8 N V

TR

4 5 6T8 T6

S1

NT8 T6T7 L1

PG

XP

VPS

B5

VN

VS VR

~

ϑ Pϑ P ϑ P

~M3~50Hz 230V33N 50Hz 400/230V

L

P

P P

L1 L2 L3 N LMB 1 2

L

PE L1 L2 L3

T6A

N L

TS STL

IN

~50Hz 230V

3

F

~M3

4 5

PG

N V

VRVS

6 7 8 N V

TR

~50Hz 230V3~3N 50Hz 400/230V

ϑ Pϑ P ϑ P

CO EMISSIONS

mg

/kW

h

0

10

20

30

40

50

RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190

NOISE EMISSIONS

dB

(A)

0

20

40

60

80

100

RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190

NO2 EMISSIONS

mg

/kW

h

0

50

100

150

75

25

RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190

125

15

OVERALL DIMENSIONS (mm)

BURNERS

PACKAGING

X - X (1)

Z

Y

RS 28

RS 38

RS 50

RS 70

RS 100

RS 130

RS 190

BURNER – BOILER MOUNTING FLANGE

Ø

D2

45°

45°

D1

RS 70 - 100 - 130

A

D

B C

O - O (1)

V

E

I

F - F (1)L

N

M

H

RS 28

RS 38

RS 50

RS 70

RS 100

RS 130

RS 190

A

D

B C

RS 190

RS 28 - 38 - 50

A

D

M8M8M8M12M12M12M16

ØD2160160160185185195230

224224224

275 - 325275 - 325275 - 325325 - 368

D1

Model X - X (1) Y kg

872 - 1007872 - 1007872 - 10071190 - 13251190 - 13251190 - 1325

1250

540540540692692692785

38404170737682

Z

550550550740740740725

Model

Model A B DC HF - F (1) L O - O (1)I VE M N

---

296312338366

476476476511527553681

352352352430430430430

---

215215215315

580580580840840840856

164164164214214214230

108108108134134134150

474474474555555555555

1”1/21”1/21”1/2

2”2”2”

DN80

168168168221221221186

S

140140152179179189222

810810810

1161 - 12961161 - 12961161 - 1296

1312

O - O (1)

S

367367367

----

(1) Length with extended combustion head

(1) Length with extended combustion head

RS 28

RS 38

RS 50

RS 70

RS 100

RS 130

RS 190

O - O (1)

216 - 351216 - 351216 - 351250 - 385250 - 385280 - 415372 - 530

V

N

E

I

F - F (1)L

H

M

E

FF (1)

H

I

N

MV

L

16

INSTALLATION DESCRIPTION

All the burners have slide bars, for easier installationand maintenance.

After drilling the boilerplate, using the supplied gasketas a template, dismantle the blast tube from the burnerand fix it to the boiler.

Adjust the combustion head.

Fit the gas train, choosing this on the basis of themaximum output of the boiler and considering theenclosed diagrams.

Refit the burner casing to the slide bars.

Close the burner, sliding it up to the flange.

Make the electrical connections to the boiler followingthe wiring diagrams included in the instructionhandbook.

Turn the motor to check rotation direction (if it is athree-phase motor).

Perform a first ignition calibration on the gas train.

On start up, check:- Gas pressure at the combustion head (to max. and

min. output)- Combustion quality, in terms of unburned substances

and excess air.

Installation, start up and maintenance must be carriedout by qualified and skilled personnel.All operations must be performed in accordance with thetechnical handbook supplied with the burner.

BURNER SETTING

ELECTRICAL CONNECTIONS AND START-UP

17

BURNER ACCESSORIES

Extended head kit

“Standard head” burners can be transformed into “extended head”versions, by using the special kit. The KITS available for the variousburners, giving the original and the extended lengths, are listed below.

Kit code

RS 28RS 38RS 50RS 70RS 100RS 130RS 190

Burner

3010076

3010077

3010078

3010117

3010118

3010119

3010196

‘Extended head’length (mm)

351351351385385415530

216216216250250280372

‘Standard head’length (mm)

Post-ventilation kit

To prolong ventilation for approximately 5 seconds after opening of thermostats chain, a special kitis available.

RS 28 - 38 - 50 - 70 - 100 - 130 - 190Burner Kit code

3010004

Post-ventilation kit

Spacer kit

If burner head penetration into the combustion chamber needs reducing, varying thickness spacersare available, as given in the following table:

RS 28 - 38 - 50RS 70 - 100 - 130RS 190

Burner Kit code

3010095

3010129

3000722S

Spacer thickness S (mm)

90135102

Spacer kit

Extended head kit

Continuous ventilation kit

If the burner requires continuous ventilation in the stages without flame, a special kit is available asgiven in the following table:

RS 28 - 38 - 50 - 70 - 100 - 130 - 190Burner Kit code

3010094

Continuous ventilation kit

18

RS 28RS 38RS 50RS 70RS 100RS 130RS 190

Burner

LPG kit

Kit code for‘extended head’

Kit code for‘standard head’

3010089

3010090

3010165

3010098

3010100

3010102

-

LPG kit

For burning LPG gas, a special kit is available to be fitted to the combustion head on the burner, asgiven in the following table:

3010089

3010090

3010165

3010097

3010099

3010101

3010166

Sound proofing box

If noise emission needs reducing even further, sound-proofing boxes are available, as given in thefollowing table:

RS 28 - 38 - 50RS 70 - 100 - 130RS 190

Burner Box code

3000777

3000778

3000779

C2C3C4

Box type

111414

Average noisereduction [dB(A)]

RS 28RS 38RS 50RS 70RS 100RS 130RS 190

Burner

Town gas kit

Town gas kit

For burning Town gas, a special kit is available:

3010283

3010284

3010285

3010286

3010287

3010288

3010297

(*) Without CE certification

Kit code forstandard head (*)

3010283

3010284

3010285

3010286

3010287

3010288

3010297

Kit code forextended head (*)

Sound proofing box

19

Ground fault interrupter kit

A “Ground fault interrupter kit” is available as a safety device for electrical system fault.

RS 28 - 38 - 50RS 70 - 100 - 130 - 190

Burner Kit code

3010321

3010329

Status Panel kit

The RS burners can be equipped with an exclusive electronic device “Status Panel” which continuouslymonitors and displays all the burner operational modes and picks up any anomalies during theoperational cycle.

RS 28 - 38 - 50 - 70 - 100 - 130 - 190Burner Kit code

3010322

Burner Kit code

Vibration reduction kit

The kit allow you to improve flame stability in some applications, where the boiler/flue assemblyis liable to resonate.

Vibration reduction kit

RS 28 TC - RS 28 TLRS 38 TC - RS 38 TLRS 50 TC - RS 50 TLRS 70 TC - RS 70 TLRS 100 TC - RS 100 TLRS 130 TCRS 130 TLRS 190 TC

3010198

3010199

3010200

3010201

3010202

3010373

3010374

3010375

Ground fault interrupter kit

Status Panel kit

20

Interface adapter kit

To connect the flame control panel to a personal computer for the transmission of operation, faultsignals and detailed service information, an interface adapter with PC software are available.

Burner Kit code

3002719

Interface adapter kit

RS 28 - 38 - 50 - 70 - 100 - 130 - 190

Connection flange kit

A kit is available for use where the burner opening on the boiler is of excessive diameter.

RS 28 - 38 - 50Burner Kit code

3010138

21

Connection flange kit

GAS TRAIN ACCESSORIES

Adapters

When the diameter of the gas train is different from the set diameter of the burners, an adapter mustbe fitted between the gas train and the burner. The following table lists the adapters for variousburners.

Adapters

Burner Gas train Dimensions Adapter code

1" 1/2 2"

1"1/23/4"

2" 1"1/2

1"1/2 2"

1"1/23/4"

1"1/23/4"

2" 1"1/2

1"1/2 2"

RS 28

RS 38

RS 50

RS 70

RS 100

RS 130

RS 190

MBD 407 - 410

MBD 407 - 410

MBD 420

MBD 407 - 410

MBD 420 - MBC 1200

MBD 415

MBC 1900

MBC 3100

MBD 415

MBC 1900

MBC 3100

MBD 415

MBC 1900

MBC 3100

MBD 420 - MBC 1200

MBC 1900

MBC 3100

DN 65

DN 80

DN 80

DN 80

3000824

3000824

3000822

3000824

3000822

3000843

3000825

3000826

3000843

3000825

3000826

3000843

3000825

3000826

3010128

3000831

3000832

DN 65 2"1/2

2"

1"1/2

1"1/2

2"

DN 65 2"1/2

DN 80 2"1/2 2"

2"

DN 80

DN 65 2"1/2

DN 80 2"1/2 2"

1"1/2

2"

DN 65 2"1/2

DN 80 2"1/2 2"

22

Stabiliser springs

Stabiliser spring

Accessory springs are available to vary the pressure range of the gas train stabilisers. The followingtable shows these accessories with their application range.

Please refer to the technical manual for the correct choice of spring.

Gas train Spring codeSpring

Seal control kit

To test the valve seals on the gas train, a special “seal control kit” is available. The valve seal controldevice is compulsory (EN 676) on gas trains to burners with a maximum output over 1200 kW. Thesealing control is type VPS 504.

All modelsBurner Kit code

Seal control kit

Gas train

3010367All models

23

MBC 1900MBC 3100MBC 5000

3010381

3010382

3010383

3010384

White from 4 to 20 mbarRed from 20 to 40 mbar

Black from 40 to 80 mbarGreen from 80 to 150 mbar

R S 130 TC FS1 230/50-60

A specific index guides your choice of burner fromthe various models available in the RS series.Below is a clear and detailed specification descriptionof the product.

SPECIFICATION

BASIC DESIGNATION

EXTENDED DESIGNATION

DESIGNATION OF SERIES

3/230-400/50

Size

Fuel : S Natural GasL Light oilLS Light oil/MethaneN Heavy oil

Series : R

ID:Differentialswitch

Setting : /1 Single stage /E Electronic cam... Two stage /P Proportioning air/gas valve/M Modulating /EV Electronic cam predisposed for variable speed (with inverter)

Emission : ... Class 1 EN267 - EN676MZ Class 2 EN267 - EN676BLU Class 3 EN267 - EN676

MXClass 2 EN267Class 3 EN676

Head : TC Standard headTL Extended head

Flame control system : FS1 Standard (1 stop every 24 h)FS2 Continuous working (1 stop every 72 h)

Auxiliary voltage :230/50-60 230V/50-60Hz110/50-60 110V/50-60Hz

Electrical supply to the system :1/230/50 1/230V/50Hz3/230/400/50 3/230V/400V/50Hz1/220-230/60 1/220-230V/60Hz3/220-230/380-400/60 3/220-230V/60Hz - 3/380-400V/60Hz3/254-265/440-460/60 3/254-265/60Hz - 3/440-460V/60Hz

24

AVAILABLE BURNER MODELS

Other versions are available on request.

RS 28 TC FS1 1/230/50 230/50-60RS 28 TL FS1 1/230/50 230/50-60RS 28 TC FS1 1/220-230/60 230/50-60RS 28 TL FS1 1/220-230/60 230/50-60

RS 38 TC FS1 1/230/50 230/50-60RS 38 TL FS1 1/230/50 230/50-60RS 38 TC FS1 1/220-230/60 230/50-60RS 38 TL FS1 1/220-230/60 230/50-60RS 38 TC FS1 3/230/400/50 230/50-60RS 38 TL FS1 3/230/400/50 230/50-60RS 38 TC FS1 3/220-230/380-400/60 230/50-60RS 38 TL FS1 3/220-230/380-400/60 230/50-60RS 38 TC FS1 3/254-265/440-460/60 230/50-60RS 38 TL FS1 3/254-265/440-460/60 230/50-60

RS 50 TC FS1 3/230/400/50 230/50-60RS 50 TL FS1 3/230/400/50 230/50-60RS 50 TC FS1 3/220-230/380-400/60 230/50-60RS 50 TL FS1 3/220-230/380-400/60 230/50-60RS 50 TC FS1 3/254-265/440-460/60 230/50-60RS 50 TL FS1 3/254-265/440-460/60 230/50-60

RS 70 TC FS1 3/230/400/50 230/50-60RS 70 TL FS1 3/230/400/50 230/50-60RS 70 TC FS1 3/220-230/380-400/60 230/50-60RS 70 TL FS1 3/220-230/380-400/60 230/50-60RS 70 TC FS1 3/254-265/440-460/60 230/50-60RS 70 TL FS1 3/254-265/440-460/60 230/50-60

RS 100 TC FS1 3/230/400/50 230/50-60RS 100 TL FS1 3/230/400/50 230/50-60RS 100 TC FS1 3/220-230/380-400/60 230/50-60RS 100 TL FS1 3/220-230/380-400/60 230/50-60RS 100 TC FS1 3/254-265/440-460/60 230/50-60RS 100 TL FS1 3/254-265/440-460/60 230/50-60

RS 130 TC FS1 3/230/400/50 230/50-60RS 130 TL FS1 3/230/400/50 230/50-60RS 130 TC FS1 3/220-230/380-400/60 230/50-60RS 130 TL FS1 3/220-230/380-400/60 230/50-60RS 130 TC FS1 3/254-265/440-460/60 230/50-60RS 130 TL FS1 3/254-265/440-460/60 230/50-60

RS 190 TC FS1 3/230/400/50 230/50-60RS 190 TC FS1 3/220-230/380-400/60 230/50-60RS 190 TC FS1 3/254-265/440-460/60 230/50-60

25

BurnerMonoblock forced draught gas burner with two stage operation, fully automatic, made up of:- Air suction circuit lined with sound-proofing material- Fan with reverse curve blades (straight blades on the 190 model) high performance with low sound

emissions- Air damper for air flow setting and butterfly valve for regulating fuel output on 1st and 2nd stage

controlled by a servomotor with variable cam- Starting motor at 2800 rpm, three-phase 400V with neutral, 50Hz (available also single-phase, 230V,

50Hz for the RS 28 and 38 models)- Combustion head, that can be set on the basis of required output, fitted with:

- stainless steel end cone, resistant to corrosion and high temperatures- ignition electrodes- ionisation probe- gas distributor- flame stability disk

- Minimum air pressure switch stops the burner in case of insufficient air quantity at the combustionhead

- Microprocessor-based flame control panel, with diagnostic functions- Plug and socket for electrical connections (RS 28-38-50 models)- Burner on/off selection switch- 1st - 2nd stage manual switch- Flame inspection window- Slide bars for easier installation and maintenance- Protection filter against radio interference- IP 44 electric protection level.

Gas trainFuel supply line, in the MULTIBLOC configuration (from a diameter of 3/4” until a diameter 2”) orCOMPOSED configuration (from a diameter of DN 65 until a diameter of DN 100), fitted with:- Filter- Stabiliser- Minimum gas pressure switch- Safety valve- Valve seal control (for output > 1200 kW)- One stage working valve with ignition gas output regulator.

Conforming to:- 89/336/EEC directive (electromagnetic compatibility)- 73/23/EEC directive (low voltage)- 92/42/EEC directive (performance)- 90/396/EEC directive (gas)- EN 676 (gas burners).

Standard equipment- 1 gas train gasket- 1 flange gasket- 4 screws for fixing the flange- 1 thermal screen- 4 screws for fixing the burner flange to the boiler- Wiring loom fittings for the electrical connection (RS 28 - 38 - 50)- 2 slide bar extensions (for extended head models and RS 190 model)- Instruction handbook for installation, use and maintenance- Spare parts catalogue.

Available accessories to be ordered separately- Extended head kit- Spacer kit- Continuous ventilation kit- Post-ventilation kit- Sound-proofing box- LPG kit- Town gas kit- Vibration reduction kit- Status panel kit- Ground fault interrupter kit- Interface adapter kit- Connection flange kit- Gas train adapter- Seal control kit- Stabiliser spring.

PRODUCT SPECIFICATION

26

27

ISO 9001 Cert. n. 0061

RIELLO S.p.A. - Via Ing. Pilade Riello, 5 - 37048 San Pietro di Legnago (VR) ItalyTel. ++39.0442630111 - Fax ++39.044221980

Internet: http://www.rielloburners.com - E-mail: [email protected]

Since the Company is constantly engaged in the production improvement, the aesthetic anddimensional features, the technical data, the equipment and the accessories can be changed.

This document contains confidential and proprietary information of RIELLO S.p.A.Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.

Line

agra

fica.

it

RIELLO S.p.A. - Via degli Alpini, 1 - 37045 LEGNAGO (VR) ItalyTel. ++39.0442630111 - Fax ++39.044221980

Internet: http://www.rielloburners.com - E-mail: [email protected] 9001 Cert. n. 0061

RL SERIES

TS0035UK01

RL 28 95/166 ÷ 332 kWRL 38 118/237 ÷ 450 kWRL 50 148/296 ÷ 593 kWRL 70 255/474 ÷ 830 kWRL 100 356/711 ÷ 1186 kWRL 130 486/948 ÷ 1540 kWRL 190 759/1423 ÷ 2443 kW

TWO STAGE LIGHT OIL BURNERS

The RL series of burners covers a firing range from 95 to 2443 kW, and they have beendesigned for use in hot or superheater water boilers, hot air or steam generators, diathermicoil boilers.Operation is "two stage"; the burners are fitted with an electronic device STATUS PANEL,which supplies complete diagnostic: hour counter, ignition meter, identification of troubleshooting.Optimisation of sound emissions is guaranteed by the use of fans with forward inclinedblades and sound deadening material incorporated in the air suction circuit. The elevatedperformance of the fans and combustion head, guarantee flexibility of use and excellentworking at all firing rates.The exclusive design ensures reduced dimensions, simple use and maintenance. A widerange of accessories guarantees elevated working flexibility.

Since the Company is constantly engaged in the production improvement, the aesthetic anddimensional features, the technical data, the equipment and the accessories can be changed.

This document contains confidential and proprietary information of RIELLO S.p.A.Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.

Line

agra

fica

Centrifugal with reverse curve blades

AL 65C

67

230V - 2x5 kV

1,9A - 30 mA

230V - 2x5 kV

1,9A - 35 mA

RL 38

118/237÷450

101/204÷387

10/20÷38

0,56

0,11

0,45

2 - 1,2

9,5 - 5,5

70

--

DIN 5G225/93

RL 50

148/296÷593

127/255÷510

12,5/25÷50

AL 75C

88

0,75

0,10

0,65

3 - 1,7

13,8 - 8

75

--

DIN 5G226/93

RL 130

486/948÷1540

418/816÷1325

41/80÷130

2,6

0,4

2,2

8,8 - 5,1

57,2 - 33,2

78,5

--

DIN 5G426/99

RL 190

759/1423÷2443

653/1224÷2100

64/120÷206

J7C

230

Straight blades

5,9

1,4

4,5

15,8 - 9,1

126 - 73

83,9

--

DIN 5G861/98

RL 28

95/166÷332

82/143÷286

8/14÷28

AN 57C

45

0,37

0,22

0,25

2,1

4,8

68

--

DIN 5G224/93

RL 100

356/711÷1186

306/612÷1020

30/60÷100

1,8

0,3

1,5

5,9 - 3,4

27,7 - 16

77

--

DIN 5G425/99

RL 70

255/474÷830

219/408÷714

21,5/40÷70

AL 95C

107

1,4

0,3

1,1

4,8 - 2,8

25 - 14,6

75

--

DIN 5G424/99

TECHNICAL DATAFu

el /

air

dat

aE

lect

rica

l d

ata

Em

issi

on

sA

ppro

val

Heat output

Net calorific value

Pump

Intermittent (at least one stop every 24 h)

Servo-

motors

kW

Mcal/h

Kg/h

°C min./max.

kWh/kg

Kcal/kg

mm2/s (cSt)

kg/h at 12 bar

bar

Max. °C

type

Max. °C

Ph/Hz/V

Ph/Hz/V

type

kW

kW

IP

kW

A

A

IP

V1 - V2

I1 - I2

dBA

W

mg/kWh

N° Bach.

mg/kWh

mg/kWh

Model

Burner operation mode

Modulation ratio to max. output

type

run time

Working temperature

Viscosity at 20°C

type

output

Atomised pressure

Oil temperature

Fan

Air temperature

Electrical supply

Auxiliary electrical supply

Control box

Total electrical power

Auxiliary electrical power

Protection level

Power electric motor

Rated motor current

Motor start current

Motor protection level

Ignitiontransformer

Working

Sound pressure

Sound output

CO emission

Grade of smoke indicator

CxHy emission

NOx emission

Directive

According to

Certification

Two stage

2 ÷ 1

--

--

0/40

11,8

10200

4 ÷ 6

12

50

60

1/50/230~(±10%)

RB0 522

44

54

< 40

< 1

<10 (after the first 20 s.)

< 200

73/23 - 89/336 - 98/37 - 92/42 EEC

EN 267

AJ 6CC

164

1/50/230~(±10%) 3N/50/400~(±10%) 3/50/230~(±10%)

RL 38

118/237÷450

101/204÷387

10/20÷38

0,6

0,18

0,42

2,9

11

70

--

DIN 5G225/93

Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, thetechnical data, the equipment and the accessories can be changed.This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shallnot be divulged, nor duplicated in whole or in part.

Reference conditions:Temperature: 20°CPressure: 1013.5 mbarAltitude: 100 m a.s.l.Noise measured at a distance of 1 meter.

Burner:Monoblock forced draught oil burner with two stage operation, fully automatic, made up of:- Air suction circuit lined with sound-proofing material- Fan with reverse curve blades (straight blades on the 190 model) high performance with low

sound emissions- Air damper for air setting controlled by an adjustable hydraulic ram- Starting motor at 2800 rpm, three-phase 400V with neutral, 50Hz (single-phase, 230V and 50Hz

for the 28 - 38 models)- Combustion head, that can be set on the basis of required output, fitted with:

- stainless steel end cone, resistant to corrosion and high temperatures- ignition electrodes- flame stability disk

- Gears pump for high pressure fuel supply, fitted with:- filter- pressure regulator- connections for installing a pressure gauge and vacuometer- internal by-pass for single pipe installation

- Valve unit with an oil safety valve and two delivery oil valves on the output circuit- Photocell for flame detection- Flame control panel, with lock-out pilot light and lock-out reset button- Electronic control device: control panel- Burner on/off switch- Flame inspection window- 1st - 2nd stage manual switch- Slide bars for easier installation and maintenance- Protection filter against radio interference- IP 44 electric protection level.

Conforming to:- 89/336/EEC directive (electromagnetic compatibility)- 73/23/EEC directive (low voltage)- 92/42/EEC directive (performance)- 98/37/EEC directive (machinery)- EN 267 (liquid fuel burners).

Standard equipment:- 2 flexible pipes for connection to the oil supply network- 2 gaskets for the flexible pipes- 2 nipples for connection to the pump- 4 screws for fixing the burner flange to the boiler- 1 thermal screen- Fairleads for electrical connections (RL 28 - 38 - 50 models)- 2 slide bar extensions (for the extended head models and the RL 190 model)- Instruction handbook for installation, use and maintenance- Spare parts catalogue.

Available accessories to be ordered separately:- Nozzles- Head extension kit (except for the RL 190 model)- Head length reduction kit- Sound-proofing box- Degasing unit (with or without filter)- Biodiesel kit- Connection flange kit- Status panel kit- Interface adapter kit.

PRODUCT SPECIFICATION

FIRING RATES

Useful working field for choosing the burner

1st stage operating rate

Test conditions conforming to EN 267:Temperature: 20°CPressure: 1013.5 mbarAltitude: 100 m a.s.l.

0

2

4

6

5

3

1

7

9

8

10

100 kW200 300 400 500 600 700

0

0

0

20

40

60

50

30

10

70

90

80

100

0

2

4

6

5

3

1

7

9

8

10

11

12

13

14

0

0

20

40

60

50

30

10

70

90

80

100

110

120

130

140

15150

16160

17

-1

170

100 kW300 500 700 900 1100 1300 15000 1700 1900 2100 2300 2500

RL 50

RL 28

RL 38

RL 70

RL 100RL 130

RL 190

hP

a (m

bar

)

- 1

mm

H2O

-10

hP

a (m

bar

)

mm

H2O

kg/h503010 604020

kg/h503010 70 90 110 130 150 170 190 210

HYDRAULIC CIRCUITS

FUEL SUPPLY

RL 28

RL 70 - 100 - 130 RL 190

A control device, on the basis of required output, regulates oildelivery valves opening, allowing light oil passage trough thevalves and the nozzle.Delivery valves opening supplies the two-stage hydraulic ramwhich regulates air delivery in relation to the fuel burnt.The pumping group is fitted whit a pump, an oil filter and aregulating valve, that adjust atomised pressure.

The burners are fitted with threevalves (a safety valve and two oildelivery valves).

Example of adjustable hydraulic ram ofRL 70 - 100 - 130 burners

P

VS

VF1

VF2

VC

MT

AD

U1

U2

Pump with filter and pressure regulator on the output circuit

Safety valve on the output circuit

1st stage valve

2nd stage valve

2nd stage control device

Hydraulic ram

Air damper

1st stage nozzle

2nd stage nozzle

RL 38 - 50

AD

MT

VF2 VF1U1U2

P

VC

AD

MT

VS

VF2 VF1U1U2

P

VC

LIST OF AVAILABLE MODELS

RL 28 TC FS1 1/230/50 230/50-60RL 28 TL FS1 1/230/50 230/50-60RL 28 TC FS1 1/230/50 230/50-60RL 28 TL FS1 1/230/50 230/50-60RL 28 TC FS1 1/220-230/60 230/50-60RL 28 TL FS1 1/220-230/60 230/50-60

RL 38 TC FS1 1/230/50 230/50-60RL 38 TL FS1 1/230/50 230/50-60RL 38 TC FS1 1/230/50 230/50-60RL 38 TL FS1 1/230/50 230/50-60RL 38 TC FS1 1/220/230/60 230/50-60RL 38 TL FS1 1/200/230/60 230/50-60RL 38 TC FS1 3/230/400/50 230/50-60RL 38 TL FS1 3/230/400/50 230/50-60RL 38 TC FS1 3/230/400/50 230/50-60RL 38 TL FS1 3/230/400/50 230/50-60RL 38 TC FS1 3/220-230/380-400/60 230/50-60RL 38 TL FS1 3/220-230/380-400/60 230/50-60RL 38 TC FS1 3/254-265/440-460/60 230/50-60RL 38 TL FS1 3/254-265/440-460/60 230/50-60

RL 50 TC FS1 3/230/400/50 230/50-60RL 50 TL FS1 3/230/400/50 230/50-60RL 50 TC FS1 3/230/400/50 230/50-60RL 50 TL FS1 3/230/400/50 230/50-60RL 50 TC FS1 3/220-230/380-400/60 230/50-60RL 50 TL FS1 3/220-230/380-400/60 230/50-60RL 50 TC FS1 3/254-265/440-460/60 230/50-60RL 50 TL FS1 3/254-265/440-460/60 230/50-60

RL 70 TC FS1 3/230/400/50 230/50-60RL 70 TL FS1 3/230/400/50 230/50-60RL 70 TC FS1 3/230/400/50 230/50-60RL 70 TL FS1 3/230/400/50 230/50-60RL 70 TC FS1 3/220-230/380-400/60 230/50-60RL 70 TL FS1 3/220-230/380-400/60 230/50-60RL 70 TC FS1 3/254-265/440-460/60 230/50-60RL 70 TL FS1 3/254-265/440-460/60 230/50-60

RL 100 TC FS1 3/230/400/50 230/50-60RL 100 TL FS1 3/230/400/50 230/50-60RL 100 TC FS1 3/230/400/50 230/50-60RL 100 TL FS1 3/230/400/50 230/50-60RL 100 TC FS1 3/220-230/380-400/60 230/50-60RL 100 TL FS1 3/220-230/380-400/60 230/50-60RL 100 TC FS1 3/254-265/440-460/60 230/50-60RL 100 TL FS1 3/254-265/440-460/60 230/50-60

RL 130 TC FS1 3/230/400/50 230/50-60RL 130 TL FS1 3/230/400/50 230/50-60RL 130 TC FS1 3/230/400/50 230/50-60RL 130 TL FS1 3/230/400/50 230/50-60RL 130 TC FS1 3/220-230/380-400/60 230/50-60RL 130 TL FS1 3/220-230/380-400/60 230/50-60RL 130 TC FS1 3/254-265/440-460/60 230/50-60RL 130 TL FS1 3/254-265/440-460/60 230/50-60

RL 190 TC FS1 3/230/400/50 230/50-60RL 190 TC FS1 3/220-230/380-400/60 230/50-60RL 190 TC FS1 3/254-265/440-460/60 230/50-60

Other versions are available on request.

0

30 60

90

0

30

60 90

0

3060

90

AD

MT

VS

VF2 VF1

U1U2

P

AD

MT

VS

VF2 VF1

U1U2

P

VC

Model

Diameter piping

+H, -H (m)

+4,0

+3,0

+2,0

+1,5

+1,0

+0,5

0

-0,5

-1,0

-1,5

-2,0

-3,0

-4,0

Ø10mm

L max (m)

63

55

48

44

40

37

33

29

25

21

17

10

4

Ø12mm

L max (m)

144

127

111

102

94

86

78

70

82

63

45

29

12

Ø14mm

L max (m)

150

150

150

150

150

150

150

133

118

103

88

58

28

Ø10mm

L max (m)

51

46

39

35

32

29

26

23

20

16

13

7

2

Ø12mm

L max (m)

112

99

86

79

73

65

60

54

47

40

34

21

8

Ø14mm

L max (m)

150

150

150

147

144

132

120

106

96

83

71

46

21

Ø12mm

L max (m)

71

62

58

51

44

40

36

32

28

23

19

10

3

Ø14mm

L max (m)

138

122

106

98

90

82

74

66

56

49

42

26

10

Ø16mm

L max (m)

150

150

150

150

150

150

137

123

109

95

81

53

25

Ø16mm

L max (m)

60

50

40

35

30

25

20

18

15

13

10

5

3

Ø18mm

L max (m)

80

70

60

55

50

45

40

35

30

25

20

10

6

RL 28 RL 38 - 50 RL 70 - 100 - 130 RL 190

H

Ø

P

V

1

2

3

4

5

6

7

8

9

10

7

10

9 5 V

P

+H

-H

8

1

4

10 cm2

57 3

9

6

6

DIMENSIONING OF THE FUEL SUPPLY LINES

The fuel feed must be completed with the safety devices required by the local norms.

The table shows the choice of piping diameter for the various burners, depending on the differencein height between the burner and the tank and their distance.

With ring distribution oil systems, the feasible drawings and dimensioning are the responsibilityof specialised engineering studios, who must check compatibility with the requirements andfeatures of each single installation.

MAXIMUM EQUIVALENT LENGTH FOR THE PIPING L[m]

Difference in height pump-foot valve

Internal pipe diameter

Height 10 m

Height 4 m

Burner

Burner pump

Filter

Manual shut off valve

Suction pipework

Bottom valve

Remote controlled rapid manualshut off valve(compulsory in Italy)

Type approved shut off solenoid valve(compulsory in Italy)

Return pipework

Check valve

note

R L 50 TC FS1 3/230/400/50 230/50-60

A specific index guides your choice of burner fromthe various models available in the RL series.Below is a clear and detailed specification descriptionof the product.

Size

Fuel : S Natural GasL Light oilLS Oil/MethaneN Heavy oil

Series : R

SPECIFICATION

ID :Differential switch

BASIC DESIGNATION

EXTENDED DESIGNATION

Setting : /1 Single stage... Two stage/M Modulating

Emission : ... Class 1 EN267 - EN676MZ Class 2 EN267 - EN676BLU Class 3 EN267 - EN676

MXClass 1 EN267Class 3 EN676

Head : TC Standard headTL Extended head

Flame control system : FS1 Standard (1 stop every 24 h)FS2 Continuous working (1 stop every 72 h)

Electrical supply to the system :

Auxiliary voltage :230/50-60 230V/50-60Hz110/50-60 110V/50-60Hz

DESIGNATION OF SERIES R BURNERS

1/230/50 1/230V/50Hz3/230/50 3/230V/50Hz3/400/50 3N/400V/50Hz3/230/400/50 3/230V/50Hz - 3N/400V/50Hz3/220-230/380-400/60 3/220-230V/60Hz - 3/380-400V/60Hz3/254-265/440-460/60 3/254-265V/60Hz - 3/440-460V/60Hz1/220-230/60 1/220-230V/60Hz

COMBUSTION HEAD

VENTILATION

The ventilation circuit produces low noise levels with highperformance pressure and air output, inspite of the compact dimensions.

Except for the RL 190 model, the use ofreverse curve blades and sound proofing material keepsnoise level very low.

In the RL 190 model, sound has been reduced by thespecial design of the air suction circuit.

An hydraulic ram allows to have a right air flow in anyoperational moment and the closure of the air damperwith burner in stand-by.

Different lengths of the combustion head can be chosen for theRL series of burners.

The choice depends on the thickness ofthe front panel and the type of boiler.

Depending on the type of generator, check that thepenetration of the head into the combustion chamber iscorrect.

The internal position of the combustion head can easilybe adjusted to the maximum defined output by adjustinga screw fixed to the flange.

Example of a RL burnercombustion head

Example of the air damper onRL 28 - 38 - 50 burners

Dimensions of the flame

RL 28RL 38RL 50RL 70RL 100RL 130RL 190

Burner Kit code

For burning Biodiesel fuel, a special kit is available.

Biodiesel kit

3010289

3010290

3010291

3010292

3010358

3010358

-

Biodiesel kit

Interface adapter kit

To connect the flame control panel to a personal computer for the transmission of operation, faultsignals and detailed service information, an interface adapter with PC software are available.

Burner Kit code

in progress

Interface adapter kit

RL 28 - 38 - 50 - 70 - 100 - 130 - 190Example:Burner thermal output = 2000 kW;L flame (m) = 2,7 m (medium value);D flame (m) = 0,8 m (medium value)

D

L

Burner output (MW)

3

1

2

4

Len

gh

t o

f th

e fl

ame

(m)

Dia

met

er o

f th

e fl

ame

(m)

0 0

0,5

1

1,5

2

0 21 3 4

D max

D min

L max

L min

RL 28 - 38 - 50Burner Kit code

3010138

Connection flange kit

A kit is available for use where the burner opening on the boiler is of excessive diameter.

Connection flange kit

Status Panel kit

The RL burners can be equipped with an exclusive electronic device “Status Panel” which continuouslymonitors and displays all the burner operational modes and picks up any anomalies during theoperational cycle.

Status Panel kit

RL 28 - 38 - 50 - 70 - 100 - 130 - 190

Burner Kit code

3010322

ADJUSTMENT

All RL series burners are fitted with a new microprocessor control panel for the supervision duringintermittent operation.For helping the commissioning and maintenance work, there are two main elements:

The lock-out reset button is the central operating element for resetting the burner controland for activating / deactivating the diagnostic functions.

The multi-color LED is the central indication element for visual diagnosis and interfacediagnosis.

Both elements are located under the transparent cover of lock-out reset button, as showed below.

There are two diagnostic choices, for indication of operation and diagnosis of fault cause:- visual diagnosis :

- interface diagnosis : by the interface adapterand a PC with dedicateds o f t w a r e o r b y apredisposed flue gasanalyzer (see paragraphaccessories).

Switch

COMPUTER

or

FLUE GASANALYSER

INTERFACE ADAPTER

Switch

A modulation ratio of 2:1 is reached, thanks to the “two nozzles”technique; the air is adapted to the hydraulic ram positions.On “two stage” operation, the burner gradually adjusts outputto the requested level, by varying between the two pre-set levels(see figure A).

Figure A

BURNER OPERATION MODE

With two stage operation, the RLburners can follow the temperatureload requested by the system.

Two stage operation

Ou

tpu

tC

on

tro

lled

var

iab

le

bar°C

MAX

MIN

time

time

Spacer kit

If burner head penetration into the combustion chamber needs reducing, varying thickness spacersare available, as given in the following table:

RL 28 - 38 - 50RL 70 - 100 - 130RL 190

Burner Kit code

3010095

3010129

3000722

Head length reduction kit

90135110

Spacer thickness S (mm)

Extended heads

“Standard head” burners can be transformed into “extended head” versions, by using the specialkit. The kits available for the various burners, giving the original and the extended lengths, are listedbelow.

Combustion head extension kits

RL 28RL 38RL 50RL 70RL 100RL 130RL 190

Burner ‘Extended’head length (mm)

351351351385385385

-

Kit code

3010073

3010074

3010075

3010114

3010115

3010116

-

‘Standard’head length (mm)

216216216250250250370

Sound proofing box

If noise emission needs reducing even further, sound-proofing boxes are available, as given in thefollowing table:

RL 28 - 38 - 50RL 70 - 100 - 130RL 190

Burner Box code

Sound proofing box

3000776

3000778

3000779

C1C3C4

Box type

Degasing unit

With single pipe systems, you can find air in the oil sucked by the pump that comes from the oil itselfdue to negative pressure or to a faulty seal.To solve this problem, we recommend fitting a degasing unit near the burner. Two versions areavailable with or without filter:

RL 28 - 38 - 50RL 70 - 100 - 130 - 190

Burner Degasing unit with filterCode

3010055

Degasing unit

Degasing unit without filterCode

3010054

S

START UP CYCLE

RL 28 - 38 - 50 - 70 - 100 - 130 - 190

BURNER ACCESSORIES

Nozzles type 60° B

Burner GPH Rated output (kg/h) Nozzle code

at 10 bar at 12 bar at 14 bar

RL 28 2,00 7,7 8,5 9,2 3042126

RL 28-38 2,50 9,6 10,6 11,5 3042140

RL 28-38-50 3,00 11,5 12,7 13,8 3042158

RL 28-38-50 3,50 13,5 14,8 16,1 3042162

RL 38-50 4,00 15,4 17 18,4 3042172

RL 38-50 4,50 17,3 19,1 20,7 3042182

RL 38-50-70 5,00 19,2 21,2 23 3042192

RL 50-70 5,50 21,1 23,3 25,3 3042202

RL 50-70 6,00 23,1 25,5 27,7 3042212

RL 50-70 6,50 25 27,6 30 3042222

RL 70-100 7,00 26,9 29,7 32,3 3042232

RL 70-100 7,50 28,8 31,8 34,6 3042242

RL 70-100 8,00 30,8 33,9 36,9 3042252

RL 70-100 8,50 32,7 36,1 39,2 3042262

RL 70-100-130 9,50 36,5 40,3 43,8 3042282

RL 70-100-130-190 10,00 38,4 42,4 46,1 3042292

RL 70-100-130-190 11,00 42,3 46,7 50,7 3042312

RL 100-130-190 12,00 46,1 50,9 55,3 3042322

RL 100-130-190 13,00 50 55,1 59,9 3042332

RL 100-130-190 14,00 53,8 59,4 64,5 3042352

RL 100-130-190 15,00 57,7 63,6 69,2 3042362

RL 100-130-190 16,00 61,5 67,9 73,8 3042382

RL 130-190 17,00 65,4 72,1 78,4 3042392

RL 130-190 18,00 69,2 76,4 83 3042412

RL 130-190 19,00 73 80,6 87,6 3042422

RL 130-190 20,00 76,9 84,8 92,2 3042442

RL 190 22,00 84,6 93,3 101,4 3042462

RL 190 24,00 92,2 101,8 110,6 3042472

RL 190 26,00 99,9 110,3 119,9 3042482

RL 190 28,00 107,6 118,8 129,1 3042492

Indication of operation :

In normal operation, the various statues areindicated in the form of colour codes accordingto the table below.The interface diagnosis (with adapter) can beactivated by pressing the lock-out button for> 3 seconds.

Diagnosis of fault causes :

After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosisaccording to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3seconds.

The blinkers of red LED are a signal with this sequence :

(e.g. signal with n° 3 blinks – faulty air pressure monitor)

Color code table

Operation statues

Stand-byPre-purgingIgnition phaseFlame OKPoor flameUndervoltage, built-in fuseFault, alarmExtraneous light

Color code table

LED off

Error code table

Possible cause of fault

No establishment of flame at the end of safety time : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner, no fuel- faulty ignition equipment

Faulty air pressure monitor

Extraneous light or simulation of flame on burner start up

Loss of flame during operation : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner

Wiring error or internal fault

Blink code

LED off3 sec. 3 sec. 3 sec.

0 s The burner begins the firing cycle:the motor and transformer aresupplied; the hydraulic ram opensin the pre-purge position.

20÷28 s Ignition: the VS and VF1 valvesare supplied.

5 s after firing: The ignition transformer switchesoff.If the control device TR is closedor has been replaced by a jumperwire, the 2nd stage valve VF2opens; the fuel is sprayed outthrough the 2nd stage nozzle andthe hydraulic ram opens the airdamper in the 2nd stage position.

A

A

0 s

TLTRM

VS VF1

VF2

time (s)

0

0

25

20

25

25

20

25

25

Nozzles

The nozzles must be ordered separately. The following table shows the features and codes on thebasis of the maximum required fuel output.

INSTALLATION DESCRIPTION

All the burners have slide bars, for easier installationand maintenance.

After drilling the boilerplate, using the supplied gasketas a template, dismantle the blast tube from the burnerand fix it to the boiler.

Adjust the combustion head.

Refit the burner casing to the slide bars.

Install the nozzle, choosing this on the basis of themaximum boiler output and following the diagramsincluded in the burner instruction handbook.

Check the position of the electrodes.

Close the burner, sliding it up to the flange, keepingit slightly raised to avoid the flame stability diskrubbing against the blast tube.

The burners are supplied for connection to two pipesfuel supply system.

Connect the ends of the flexible pipes to the suctionand return pipework using the supplied nipples.

Make the electrical connections to the burner followingthe wiring diagrams included in the instructionhandbook.

Prime the pump by turning the motor.

On start up, check:- Pressure pump (to max. and min.)- Combustion quality, in terms of unburned substances and excess air.

Installation, start up and maintenance must be carried outby qualified and skilled personnel.All operations must be performed in accordance with thetechnical handbook supplied with the burner.

BURNER SETTING

HYDRAULIC AND ELECTRICALCONNECTIONS AND START UP

RL 28 - 38single-phase electrical connection

~M3~50Hz 230V33N 50Hz 400/230V~

“TWO STAGE” OPERATION

WIRING DIAGRAMS

Electrical connections must be made byqualified and skilled personnel, accordingto the local norms.

Example of the terminal boardfor electrical connections onRL 28 - 38 burners

h1 - First stage hour meterh2 - Second stage hour meterIN - Manual switchX4 - 4 pin plugX7 - 7 pin plugS - External lock-out signalTL - Threshold thermostatTR - High/low flame setting thermostatTS - Safety thermostatT6A - 6a fuse

RL 38 - 50three-phase electrical connection

h1 - First stage hour meterh2 - Second stage hour meterIN - Manual switchX4 - 4 pin plugX5 - 5 pin plugX7 - 7 pin plug

The following tableshows the supplylead sections and thetype of fuse to beused.

Table A

RL 70 - 100 - 130 - 190 three-phase electrical connection

S - External lock-out signalTL - Threshold thermostatTR - High/low flame setting

thermostatTS - Safety thermostatT6A - 6a fuse

~M3~50Hz 230V3~3N 50Hz 400/230V

MB - Burner terminal boardTS - Safety thermostatS - External lock-out signalIN - Manual switchTL - Threshold thermostatTR - High/low flame setting thermostatT6A - 6A fuseF - Fuse (see table A)L - Lead section (see table A)

L1 L2 L3 N LMB 1 2

L

PE L1 L2 L3

T6A

N L

TS STL

IN

~50Hz 230V

3 4 5 6 7

TR

F

ϑ P

ϑ Pϑ P

T8 T7 T6 B5

TR

X 7L1X 4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

~ 50Hz 230V

T8 T7 T6 B5

TR

X 7L1X 4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

1,5 mm2

L3 N L1 X 5L2

L3 PE L1

1,5 mm2

L2

~ 50Hz 230V

ϑ P

h1h2

ϑ Pϑ P

ϑ P

h1h2

ϑ Pϑ P

RL 28 RL 38 RL 50

230V

T61,5

400V

T61,5

230V

T61,5

400V

T61,5

RL 70 RL 100 RL 130

230V

T101,5

400V

T61,5

230V

T161,5

400V

T101,5

230V

T161,5

400V

T101,5

RL 190

230V

T252,5

400V

T252,5

Model

A

mm2

FL

400V

T61,5

230V

T61,5

RL 38

230V

T61,5

EMISSIONS

The emission datahas been measuredin the various modelsat maximum output,according to EN 267standard.

mg

/kW

h

0

10

20

30

40

50

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

CO EMISSIONS

RL 70 - 100 - 130 - 190RL 28 - 38 - 50

A

D

F - F(1)E

F - F(1)

D

B C E

Ø

D2

45°

45°

D1

OVERALL DIMENSIONS (mm)

BURNER - BOILER MOUNTING FLANGE

BURNERS

PACKAGING

ØD2160160160185185195230

M8M8M8M12M12M12M16

224224224

275-325275-325275-325325-368

D1RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

Model

mg

/kW

h

0

50

100

150

200

250

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

dB

(A)

0

20

40

60

80

100

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

NO2 EMISSIONS

NOISE EMISSIONS

X - X (1)

Z

Y

O - O (1)

H

I

L

A

Z

550550550600600600725

Model

RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

X - X (1) Y kg

760760760960960960

1250

540540540652652652785

36383960636675

- 895- 895- 895- 1150- 1150- 1150 -

(1) Length with extended combustion head

Model A B DC I

RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

---

296312338366

476476476580599625756

352352352430430430430

---

284287287390

468468468680680680696

F (1)

474474474555555555555

H

140140152179179189222

F

351351351385385385

-

E

216216216250250250370

-------

O

672672672951951951

1102

O (1)

807807807

108610861086

-

------

-L

525252----

(1) Length with extended combustion head

H

I

O - O (1)

EMISSIONS

The emission datahas been measuredin the various modelsat maximum output,according to EN 267standard.

mg

/kW

h

0

10

20

30

40

50

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

CO EMISSIONS

RL 70 - 100 - 130 - 190RL 28 - 38 - 50

A

D

F - F(1)E

F - F(1)

D

B C E

Ø

D2

45°

45°

D1

OVERALL DIMENSIONS (mm)

BURNER - BOILER MOUNTING FLANGE

BURNERS

PACKAGING

ØD2160160160185185195230

M8M8M8M12M12M12M16

224224224

275-325275-325275-325325-368

D1RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

Model

mg

/kW

h

0

50

100

150

200

250

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

dB

(A)

0

20

40

60

80

100

RL 28 RL 38 RL 50 RL 70 RL 100 RL 130 RL 190

NO2 EMISSIONS

NOISE EMISSIONS

X - X (1)

Z

Y

O - O (1)

H

I

L

A

Z

550550550600600600725

Model

RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

X - X (1) Y kg

760760760960960960

1250

540540540652652652785

36383960636675

- 895- 895- 895- 1150- 1150- 1150 -

(1) Length with extended combustion head

Model A B DC I

RL 28

RL 38

RL 50

RL 70

RL 100

RL 130

RL 190

---

296312338366

476476476580599625756

352352352430430430430

---

284287287390

468468468680680680696

F (1)

474474474555555555555

H

140140152179179189222

F

351351351385385385

-

E

216216216250250250370

-------

O

672672672951951951

1102

O (1)

807807807

108610861086

-

------

-L

525252----

(1) Length with extended combustion head

H

I

O - O (1)

INSTALLATION DESCRIPTION

All the burners have slide bars, for easier installationand maintenance.

After drilling the boilerplate, using the supplied gasketas a template, dismantle the blast tube from the burnerand fix it to the boiler.

Adjust the combustion head.

Refit the burner casing to the slide bars.

Install the nozzle, choosing this on the basis of themaximum boiler output and following the diagramsincluded in the burner instruction handbook.

Check the position of the electrodes.

Close the burner, sliding it up to the flange, keepingit slightly raised to avoid the flame stability diskrubbing against the blast tube.

The burners are supplied for connection to two pipesfuel supply system.

Connect the ends of the flexible pipes to the suctionand return pipework using the supplied nipples.

Make the electrical connections to the burner followingthe wiring diagrams included in the instructionhandbook.

Prime the pump by turning the motor.

On start up, check:- Pressure pump (to max. and min.)- Combustion quality, in terms of unburned substances and excess air.

Installation, start up and maintenance must be carried outby qualified and skilled personnel.All operations must be performed in accordance with thetechnical handbook supplied with the burner.

BURNER SETTING

HYDRAULIC AND ELECTRICALCONNECTIONS AND START UP

RL 28 - 38single-phase electrical connection

~M3~50Hz 230V33N 50Hz 400/230V~

“TWO STAGE” OPERATION

WIRING DIAGRAMS

Electrical connections must be made byqualified and skilled personnel, accordingto the local norms.

Example of the terminal boardfor electrical connections onRL 28 - 38 burners

h1 - First stage hour meterh2 - Second stage hour meterIN - Manual switchX4 - 4 pin plugX7 - 7 pin plugS - External lock-out signalTL - Threshold thermostatTR - High/low flame setting thermostatTS - Safety thermostatT6A - 6a fuse

RL 38 - 50three-phase electrical connection

h1 - First stage hour meterh2 - Second stage hour meterIN - Manual switchX4 - 4 pin plugX5 - 5 pin plugX7 - 7 pin plug

The following tableshows the supplylead sections and thetype of fuse to beused.

Table A

RL 70 - 100 - 130 - 190 three-phase electrical connection

S - External lock-out signalTL - Threshold thermostatTR - High/low flame setting

thermostatTS - Safety thermostatT6A - 6a fuse

~M3~50Hz 230V3~3N 50Hz 400/230V

MB - Burner terminal boardTS - Safety thermostatS - External lock-out signalIN - Manual switchTL - Threshold thermostatTR - High/low flame setting thermostatT6A - 6A fuseF - Fuse (see table A)L - Lead section (see table A)

L1 L2 L3 N LMB 1 2

L

PE L1 L2 L3

T6A

N L

TS STL

IN

~50Hz 230V

3 4 5 6 7

TR

F

ϑ P

ϑ Pϑ P

T8 T7 T6 B5

TR

X 7L1X 4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

~ 50Hz 230V

T8 T7 T6 B5

TR

X 7L1X 4

PE N L

S3 T2 T1B4

T6A

TSTL

I N

1,5 mm2

S

N

1,5 mm2

L3 N L1 X 5L2

L3 PE L1

1,5 mm2

L2

~ 50Hz 230V

ϑ P

h1h2

ϑ Pϑ P

ϑ P

h1h2

ϑ Pϑ P

RL 28 RL 38 RL 50

230V

T61,5

400V

T61,5

230V

T61,5

400V

T61,5

RL 70 RL 100 RL 130

230V

T101,5

400V

T61,5

230V

T161,5

400V

T101,5

230V

T161,5

400V

T101,5

RL 190

230V

T252,5

400V

T252,5

Model

A

mm2

FL

400V

T61,5

230V

T61,5

RL 38

230V

T61,5

START UP CYCLE

RL 28 - 38 - 50 - 70 - 100 - 130 - 190

BURNER ACCESSORIES

Nozzles type 60° B

Burner GPH Rated output (kg/h) Nozzle code

at 10 bar at 12 bar at 14 bar

RL 28 2,00 7,7 8,5 9,2 3042126

RL 28-38 2,50 9,6 10,6 11,5 3042140

RL 28-38-50 3,00 11,5 12,7 13,8 3042158

RL 28-38-50 3,50 13,5 14,8 16,1 3042162

RL 38-50 4,00 15,4 17 18,4 3042172

RL 38-50 4,50 17,3 19,1 20,7 3042182

RL 38-50-70 5,00 19,2 21,2 23 3042192

RL 50-70 5,50 21,1 23,3 25,3 3042202

RL 50-70 6,00 23,1 25,5 27,7 3042212

RL 50-70 6,50 25 27,6 30 3042222

RL 70-100 7,00 26,9 29,7 32,3 3042232

RL 70-100 7,50 28,8 31,8 34,6 3042242

RL 70-100 8,00 30,8 33,9 36,9 3042252

RL 70-100 8,50 32,7 36,1 39,2 3042262

RL 70-100-130 9,50 36,5 40,3 43,8 3042282

RL 70-100-130-190 10,00 38,4 42,4 46,1 3042292

RL 70-100-130-190 11,00 42,3 46,7 50,7 3042312

RL 100-130-190 12,00 46,1 50,9 55,3 3042322

RL 100-130-190 13,00 50 55,1 59,9 3042332

RL 100-130-190 14,00 53,8 59,4 64,5 3042352

RL 100-130-190 15,00 57,7 63,6 69,2 3042362

RL 100-130-190 16,00 61,5 67,9 73,8 3042382

RL 130-190 17,00 65,4 72,1 78,4 3042392

RL 130-190 18,00 69,2 76,4 83 3042412

RL 130-190 19,00 73 80,6 87,6 3042422

RL 130-190 20,00 76,9 84,8 92,2 3042442

RL 190 22,00 84,6 93,3 101,4 3042462

RL 190 24,00 92,2 101,8 110,6 3042472

RL 190 26,00 99,9 110,3 119,9 3042482

RL 190 28,00 107,6 118,8 129,1 3042492

Indication of operation :

In normal operation, the various statues areindicated in the form of colour codes accordingto the table below.The interface diagnosis (with adapter) can beactivated by pressing the lock-out button for> 3 seconds.

Diagnosis of fault causes :

After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosisaccording to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3seconds.

The blinkers of red LED are a signal with this sequence :

(e.g. signal with n° 3 blinks – faulty air pressure monitor)

Color code table

Operation statues

Stand-byPre-purgingIgnition phaseFlame OKPoor flameUndervoltage, built-in fuseFault, alarmExtraneous light

Color code table

LED off

Error code table

Possible cause of fault

No establishment of flame at the end of safety time : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner, no fuel- faulty ignition equipment

Faulty air pressure monitor

Extraneous light or simulation of flame on burner start up

Loss of flame during operation : - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner

Wiring error or internal fault

Blink code

LED off3 sec. 3 sec. 3 sec.

0 s The burner begins the firing cycle:the motor and transformer aresupplied; the hydraulic ram opensin the pre-purge position.

20÷28 s Ignition: the VS and VF1 valvesare supplied.

5 s after firing: The ignition transformer switchesoff.If the control device TR is closedor has been replaced by a jumperwire, the 2nd stage valve VF2opens; the fuel is sprayed outthrough the 2nd stage nozzle andthe hydraulic ram opens the airdamper in the 2nd stage position.

A

A

0 s

TLTRM

VS VF1

VF2

time (s)

0

0

25

20

25

25

20

25

25

Nozzles

The nozzles must be ordered separately. The following table shows the features and codes on thebasis of the maximum required fuel output.

ADJUSTMENT

All RL series burners are fitted with a new microprocessor control panel for the supervision duringintermittent operation.For helping the commissioning and maintenance work, there are two main elements:

The lock-out reset button is the central operating element for resetting the burner controland for activating / deactivating the diagnostic functions.

The multi-color LED is the central indication element for visual diagnosis and interfacediagnosis.

Both elements are located under the transparent cover of lock-out reset button, as showed below.

There are two diagnostic choices, for indication of operation and diagnosis of fault cause:- visual diagnosis :

- interface diagnosis : by the interface adapterand a PC with dedicateds o f t w a r e o r b y apredisposed flue gasanalyzer (see paragraphaccessories).

Switch

COMPUTER

or

FLUE GASANALYSER

INTERFACE ADAPTER

Switch

A modulation ratio of 2:1 is reached, thanks to the “two nozzles”technique; the air is adapted to the hydraulic ram positions.On “two stage” operation, the burner gradually adjusts outputto the requested level, by varying between the two pre-set levels(see figure A).

Figure A

BURNER OPERATION MODE

With two stage operation, the RLburners can follow the temperatureload requested by the system.

Two stage operation

Ou

tpu

tC

on

tro

lled

var

iab

le

bar°C

MAX

MIN

time

time

Spacer kit

If burner head penetration into the combustion chamber needs reducing, varying thickness spacersare available, as given in the following table:

RL 28 - 38 - 50RL 70 - 100 - 130RL 190

Burner Kit code

3010095

3010129

3000722

Head length reduction kit

90135110

Spacer thickness S (mm)

Extended heads

“Standard head” burners can be transformed into “extended head” versions, by using the specialkit. The kits available for the various burners, giving the original and the extended lengths, are listedbelow.

Combustion head extension kits

RL 28RL 38RL 50RL 70RL 100RL 130RL 190

Burner ‘Extended’head length (mm)

351351351385385385

-

Kit code

3010073

3010074

3010075

3010114

3010115

3010116

-

‘Standard’head length (mm)

216216216250250250370

Sound proofing box

If noise emission needs reducing even further, sound-proofing boxes are available, as given in thefollowing table:

RL 28 - 38 - 50RL 70 - 100 - 130RL 190

Burner Box code

Sound proofing box

3000776

3000778

3000779

C1C3C4

Box type

Degasing unit

With single pipe systems, you can find air in the oil sucked by the pump that comes from the oil itselfdue to negative pressure or to a faulty seal.To solve this problem, we recommend fitting a degasing unit near the burner. Two versions areavailable with or without filter:

RL 28 - 38 - 50RL 70 - 100 - 130 - 190

Burner Degasing unit with filterCode

3010055

Degasing unit

Degasing unit without filterCode

3010054

S

COMBUSTION HEAD

VENTILATION

The ventilation circuit produces low noise levels with highperformance pressure and air output, inspite of the compact dimensions.

Except for the RL 190 model, the use ofreverse curve blades and sound proofing material keepsnoise level very low.

In the RL 190 model, sound has been reduced by thespecial design of the air suction circuit.

An hydraulic ram allows to have a right air flow in anyoperational moment and the closure of the air damperwith burner in stand-by.

Different lengths of the combustion head can be chosen for theRL series of burners.

The choice depends on the thickness ofthe front panel and the type of boiler.

Depending on the type of generator, check that thepenetration of the head into the combustion chamber iscorrect.

The internal position of the combustion head can easilybe adjusted to the maximum defined output by adjustinga screw fixed to the flange.

Example of a RL burnercombustion head

Example of the air damper onRL 28 - 38 - 50 burners

Dimensions of the flame

RL 28RL 38RL 50RL 70RL 100RL 130RL 190

Burner Kit code

For burning Biodiesel fuel, a special kit is available.

Biodiesel kit

3010289

3010290

3010291

3010292

3010358

3010358

-

Biodiesel kit

Interface adapter kit

To connect the flame control panel to a personal computer for the transmission of operation, faultsignals and detailed service information, an interface adapter with PC software are available.

Burner Kit code

in progress

Interface adapter kit

RL 28 - 38 - 50 - 70 - 100 - 130 - 190Example:Burner thermal output = 2000 kW;L flame (m) = 2,7 m (medium value);D flame (m) = 0,8 m (medium value)

D

L

Burner output (MW)

3

1

2

4

Len

gh

t o

f th

e fl

ame

(m)

Dia

met

er o

f th

e fl

ame

(m)

0 0

0,5

1

1,5

2

0 21 3 4

D max

D min

L max

L min

RL 28 - 38 - 50Burner Kit code

3010138

Connection flange kit

A kit is available for use where the burner opening on the boiler is of excessive diameter.

Connection flange kit

Status Panel kit

The RL burners can be equipped with an exclusive electronic device “Status Panel” which continuouslymonitors and displays all the burner operational modes and picks up any anomalies during theoperational cycle.

Status Panel kit

RL 28 - 38 - 50 - 70 - 100 - 130 - 190

Burner Kit code

3010322

Model

Diameter piping

+H, -H (m)

+4,0

+3,0

+2,0

+1,5

+1,0

+0,5

0

-0,5

-1,0

-1,5

-2,0

-3,0

-4,0

Ø10mm

L max (m)

63

55

48

44

40

37

33

29

25

21

17

10

4

Ø12mm

L max (m)

144

127

111

102

94

86

78

70

82

63

45

29

12

Ø14mm

L max (m)

150

150

150

150

150

150

150

133

118

103

88

58

28

Ø10mm

L max (m)

51

46

39

35

32

29

26

23

20

16

13

7

2

Ø12mm

L max (m)

112

99

86

79

73

65

60

54

47

40

34

21

8

Ø14mm

L max (m)

150

150

150

147

144

132

120

106

96

83

71

46

21

Ø12mm

L max (m)

71

62

58

51

44

40

36

32

28

23

19

10

3

Ø14mm

L max (m)

138

122

106

98

90

82

74

66

56

49

42

26

10

Ø16mm

L max (m)

150

150

150

150

150

150

137

123

109

95

81

53

25

Ø16mm

L max (m)

60

50

40

35

30

25

20

18

15

13

10

5

3

Ø18mm

L max (m)

80

70

60

55

50

45

40

35

30

25

20

10

6

RL 28 RL 38 - 50 RL 70 - 100 - 130 RL 190

H

Ø

P

V

1

2

3

4

5

6

7

8

9

10

7

10

9 5 V

P

+H

-H

8

1

4

10 cm2

57 3

9

6

6

DIMENSIONING OF THE FUEL SUPPLY LINES

The fuel feed must be completed with the safety devices required by the local norms.

The table shows the choice of piping diameter for the various burners, depending on the differencein height between the burner and the tank and their distance.

With ring distribution oil systems, the feasible drawings and dimensioning are the responsibilityof specialised engineering studios, who must check compatibility with the requirements andfeatures of each single installation.

MAXIMUM EQUIVALENT LENGTH FOR THE PIPING L[m]

Difference in height pump-foot valve

Internal pipe diameter

Height 10 m

Height 4 m

Burner

Burner pump

Filter

Manual shut off valve

Suction pipework

Bottom valve

Remote controlled rapid manualshut off valve(compulsory in Italy)

Type approved shut off solenoid valve(compulsory in Italy)

Return pipework

Check valve

note

R L 50 TC FS1 3/230/400/50 230/50-60

A specific index guides your choice of burner fromthe various models available in the RL series.Below is a clear and detailed specification descriptionof the product.

Size

Fuel : S Natural GasL Light oilLS Oil/MethaneN Heavy oil

Series : R

SPECIFICATION

ID :Differential switch

BASIC DESIGNATION

EXTENDED DESIGNATION

Setting : /1 Single stage... Two stage/M Modulating

Emission : ... Class 1 EN267 - EN676MZ Class 2 EN267 - EN676BLU Class 3 EN267 - EN676

MXClass 1 EN267Class 3 EN676

Head : TC Standard headTL Extended head

Flame control system : FS1 Standard (1 stop every 24 h)FS2 Continuous working (1 stop every 72 h)

Electrical supply to the system :

Auxiliary voltage :230/50-60 230V/50-60Hz110/50-60 110V/50-60Hz

DESIGNATION OF SERIES R BURNERS

1/230/50 1/230V/50Hz3/230/50 3/230V/50Hz3/400/50 3N/400V/50Hz3/230/400/50 3/230V/50Hz - 3N/400V/50Hz3/220-230/380-400/60 3/220-230V/60Hz - 3/380-400V/60Hz3/254-265/440-460/60 3/254-265V/60Hz - 3/440-460V/60Hz1/220-230/60 1/220-230V/60Hz

HYDRAULIC CIRCUITS

FUEL SUPPLY

RL 28

RL 70 - 100 - 130 RL 190

A control device, on the basis of required output, regulates oildelivery valves opening, allowing light oil passage trough thevalves and the nozzle.Delivery valves opening supplies the two-stage hydraulic ramwhich regulates air delivery in relation to the fuel burnt.The pumping group is fitted whit a pump, an oil filter and aregulating valve, that adjust atomised pressure.

The burners are fitted with threevalves (a safety valve and two oildelivery valves).

Example of adjustable hydraulic ram ofRL 70 - 100 - 130 burners

P

VS

VF1

VF2

VC

MT

AD

U1

U2

Pump with filter and pressure regulator on the output circuit

Safety valve on the output circuit

1st stage valve

2nd stage valve

2nd stage control device

Hydraulic ram

Air damper

1st stage nozzle

2nd stage nozzle

RL 38 - 50

AD

MT

VF2 VF1U1U2

P

VC

AD

MT

VS

VF2 VF1U1U2

P

VC

LIST OF AVAILABLE MODELS

RL 28 TC FS1 1/230/50 230/50-60RL 28 TL FS1 1/230/50 230/50-60RL 28 TC FS1 1/230/50 230/50-60RL 28 TL FS1 1/230/50 230/50-60RL 28 TC FS1 1/220-230/60 230/50-60RL 28 TL FS1 1/220-230/60 230/50-60

RL 38 TC FS1 1/230/50 230/50-60RL 38 TL FS1 1/230/50 230/50-60RL 38 TC FS1 1/230/50 230/50-60RL 38 TL FS1 1/230/50 230/50-60RL 38 TC FS1 1/220/230/60 230/50-60RL 38 TL FS1 1/200/230/60 230/50-60RL 38 TC FS1 3/230/400/50 230/50-60RL 38 TL FS1 3/230/400/50 230/50-60RL 38 TC FS1 3/230/400/50 230/50-60RL 38 TL FS1 3/230/400/50 230/50-60RL 38 TC FS1 3/220-230/380-400/60 230/50-60RL 38 TL FS1 3/220-230/380-400/60 230/50-60RL 38 TC FS1 3/254-265/440-460/60 230/50-60RL 38 TL FS1 3/254-265/440-460/60 230/50-60

RL 50 TC FS1 3/230/400/50 230/50-60RL 50 TL FS1 3/230/400/50 230/50-60RL 50 TC FS1 3/230/400/50 230/50-60RL 50 TL FS1 3/230/400/50 230/50-60RL 50 TC FS1 3/220-230/380-400/60 230/50-60RL 50 TL FS1 3/220-230/380-400/60 230/50-60RL 50 TC FS1 3/254-265/440-460/60 230/50-60RL 50 TL FS1 3/254-265/440-460/60 230/50-60

RL 70 TC FS1 3/230/400/50 230/50-60RL 70 TL FS1 3/230/400/50 230/50-60RL 70 TC FS1 3/230/400/50 230/50-60RL 70 TL FS1 3/230/400/50 230/50-60RL 70 TC FS1 3/220-230/380-400/60 230/50-60RL 70 TL FS1 3/220-230/380-400/60 230/50-60RL 70 TC FS1 3/254-265/440-460/60 230/50-60RL 70 TL FS1 3/254-265/440-460/60 230/50-60

RL 100 TC FS1 3/230/400/50 230/50-60RL 100 TL FS1 3/230/400/50 230/50-60RL 100 TC FS1 3/230/400/50 230/50-60RL 100 TL FS1 3/230/400/50 230/50-60RL 100 TC FS1 3/220-230/380-400/60 230/50-60RL 100 TL FS1 3/220-230/380-400/60 230/50-60RL 100 TC FS1 3/254-265/440-460/60 230/50-60RL 100 TL FS1 3/254-265/440-460/60 230/50-60

RL 130 TC FS1 3/230/400/50 230/50-60RL 130 TL FS1 3/230/400/50 230/50-60RL 130 TC FS1 3/230/400/50 230/50-60RL 130 TL FS1 3/230/400/50 230/50-60RL 130 TC FS1 3/220-230/380-400/60 230/50-60RL 130 TL FS1 3/220-230/380-400/60 230/50-60RL 130 TC FS1 3/254-265/440-460/60 230/50-60RL 130 TL FS1 3/254-265/440-460/60 230/50-60

RL 190 TC FS1 3/230/400/50 230/50-60RL 190 TC FS1 3/220-230/380-400/60 230/50-60RL 190 TC FS1 3/254-265/440-460/60 230/50-60

Other versions are available on request.

0

30 60

90

0

30

60 90

0

3060

90

AD

MT

VS

VF2 VF1

U1U2

P

AD

MT

VS

VF2 VF1

U1U2

P

VC

Burner:Monoblock forced draught oil burner with two stage operation, fully automatic, made up of:- Air suction circuit lined with sound-proofing material- Fan with reverse curve blades (straight blades on the 190 model) high performance with low

sound emissions- Air damper for air setting controlled by an adjustable hydraulic ram- Starting motor at 2800 rpm, three-phase 400V with neutral, 50Hz (single-phase, 230V and 50Hz

for the 28 - 38 models)- Combustion head, that can be set on the basis of required output, fitted with:

- stainless steel end cone, resistant to corrosion and high temperatures- ignition electrodes- flame stability disk

- Gears pump for high pressure fuel supply, fitted with:- filter- pressure regulator- connections for installing a pressure gauge and vacuometer- internal by-pass for single pipe installation

- Valve unit with an oil safety valve and two delivery oil valves on the output circuit- Photocell for flame detection- Flame control panel, with lock-out pilot light and lock-out reset button- Electronic control device: control panel- Burner on/off switch- Flame inspection window- 1st - 2nd stage manual switch- Slide bars for easier installation and maintenance- Protection filter against radio interference- IP 44 electric protection level.

Conforming to:- 89/336/EEC directive (electromagnetic compatibility)- 73/23/EEC directive (low voltage)- 92/42/EEC directive (performance)- 98/37/EEC directive (machinery)- EN 267 (liquid fuel burners).

Standard equipment:- 2 flexible pipes for connection to the oil supply network- 2 gaskets for the flexible pipes- 2 nipples for connection to the pump- 4 screws for fixing the burner flange to the boiler- 1 thermal screen- Fairleads for electrical connections (RL 28 - 38 - 50 models)- 2 slide bar extensions (for the extended head models and the RL 190 model)- Instruction handbook for installation, use and maintenance- Spare parts catalogue.

Available accessories to be ordered separately:- Nozzles- Head extension kit (except for the RL 190 model)- Head length reduction kit- Sound-proofing box- Degasing unit (with or without filter)- Biodiesel kit- Connection flange kit- Status panel kit- Interface adapter kit.

PRODUCT SPECIFICATION

FIRING RATES

Useful working field for choosing the burner

1st stage operating rate

Test conditions conforming to EN 267:Temperature: 20°CPressure: 1013.5 mbarAltitude: 100 m a.s.l.

0

2

4

6

5

3

1

7

9

8

10

100 kW200 300 400 500 600 700

0

0

0

20

40

60

50

30

10

70

90

80

100

0

2

4

6

5

3

1

7

9

8

10

11

12

13

14

0

0

20

40

60

50

30

10

70

90

80

100

110

120

130

140

15150

16160

17

-1

170

100 kW300 500 700 900 1100 1300 15000 1700 1900 2100 2300 2500

RL 50

RL 28

RL 38

RL 70

RL 100RL 130

RL 190

hP

a (m

bar

)

- 1

mm

H2O

-10

hP

a (m

bar

)

mm

H2O

kg/h503010 604020

kg/h503010 70 90 110 130 150 170 190 210

RIELLO S.p.A. - Via degli Alpini, 1 - 37045 LEGNAGO (VR) ItalyTel. ++39.0442630111 - Fax ++39.044221980

Internet: http://www.rielloburners.com - E-mail: [email protected] 9001 Cert. n. 0061

RL SERIES

TS0035UK01

RL 28 95/166 ÷ 332 kWRL 38 118/237 ÷ 450 kWRL 50 148/296 ÷ 593 kWRL 70 255/474 ÷ 830 kWRL 100 356/711 ÷ 1186 kWRL 130 486/948 ÷ 1540 kWRL 190 759/1423 ÷ 2443 kW

TWO STAGE LIGHT OIL BURNERS

The RL series of burners covers a firing range from 95 to 2443 kW, and they have beendesigned for use in hot or superheater water boilers, hot air or steam generators, diathermicoil boilers.Operation is "two stage"; the burners are fitted with an electronic device STATUS PANEL,which supplies complete diagnostic: hour counter, ignition meter, identification of troubleshooting.Optimisation of sound emissions is guaranteed by the use of fans with forward inclinedblades and sound deadening material incorporated in the air suction circuit. The elevatedperformance of the fans and combustion head, guarantee flexibility of use and excellentworking at all firing rates.The exclusive design ensures reduced dimensions, simple use and maintenance. A widerange of accessories guarantees elevated working flexibility.

Since the Company is constantly engaged in the production improvement, the aesthetic anddimensional features, the technical data, the equipment and the accessories can be changed.