two minute drill number 23- residential improving your skill in code look up increasing speed drill...

83
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

Upload: dayna-gregory

Post on 02-Jan-2016

214 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

Two Minute Drill Number 23- ResidentialImproving your skill in code Look Up Increasing Speed Drill

Copyright 2008 Ted "Smitty" Smith

Page 2: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

Directions Left click on the presentation ICON located at the bottom of

the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in

2:00 minutes. The correct answer will transition in 15 seconds. As you progress through the slide show, the time for each question will be reduced.

Write down the correct answer to each question and the code reference as it is displayed so you can review them later.

This presentation is mostly residential installation. . We have included a few other categories just to help keep you sharp.

Copyright 2008 Ted "Smitty" Smith

Page 3: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

1. What is the MAXIMUM period allowed for temporary outdoor Christmas decoration lighting for residences?

a. 30 days b. 60 days c. 90 days d. 4 months

Copyright 2008 Ted "Smitty" Smith

Page 4: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

1. c 590.3(B)

Copyright 2008 Ted "Smitty" Smith

Page 5: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

2. When doing box fill calculations, a fixture stud in a ceiling mounted outlet box is an equivalent to _____ conductor(s).

a. zero b. one c. two d. three

Copyright 2008 Ted "Smitty" Smith

Page 6: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

2. b 314.16(B)(3)

Copyright 2008 Ted "Smitty" Smith

Page 7: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

3. A branch-circuit supplying more than one electric baseboard heater in a residential occupancy shall be rated a MAXIMUM of _____.

a. 15 amperes b. 20 amperes c. 30 amperes d. 50 amperes

Copyright 2008 Ted "Smitty" Smith

Page 8: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

3. c 424.3(A)

Copyright 2008 Ted "Smitty" Smith

Page 9: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

4. Disregarding exceptions, when installing electrical metallic tubing (EMT), the run of tubing is required to be securely fastened at LEAST every _____.

a. 6 feet b. 10 feet c. 15 feet d. 20 feet

Copyright 2008 Ted "Smitty" Smith

Page 10: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

4. b 358.30(A)

Copyright 2008 Ted "Smitty" Smith

Page 11: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

5. When calculating the demand load for a one-family dwelling, what total MINIMUM volt-amperes (VA) must be included in the calculations for the small-appliance and laundry circuit loads?

a. 4500 VA b. 3000 VA c. 1500 VA d. 6000 VA

Copyright 2008 Ted "Smitty" Smith

Page 12: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

5. a 210.11(C)(1) & (2) 220.52(A) & (B) 2- small appliance circuits @ 1500VA ea = 3000VA

1- laundry circuit @ 1500VA ea = 1500VA

Total = 4500VA

Copyright 2008 Ted "Smitty" Smith

Page 13: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

6. The NEC® mandates the ampacity of UF cable shall be that of _____ conductors.

a. 60ºC rated b. 75ºC rated c. 86ºF rated d. 90ºC rated

Copyright 2008 Ted "Smitty" Smith

Page 14: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

6. a 340.80

Copyright 2008 Ted "Smitty" Smith

Page 15: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

7. The front edge of a switch box installed in a wall constructed of wood, shall be _____ from the surface of the wall.

a. flush with or projected out b. set back a maximum of ¼ inch c. set back a maximum of ½ inch d. set back a maximum of 3/8 inch

Copyright 2008 Ted "Smitty" Smith

Page 16: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

7. a 314.20

Copyright 2008 Ted "Smitty" Smith

Page 17: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

8. For dwelling units, where 125 volt, single-phase, 15 and 20 ampere receptacle outlets are installed within at LEAST _____ of the outside edge of a sink in a laundry room, GFCI protection must be provided.

a. 4 feet b. 6 feet c. 8 feet d. 10 feet

Copyright 2008 Ted "Smitty" Smith

Page 18: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

8. b 210.8(A)(7)

Copyright 2008 Ted "Smitty" Smith

Page 19: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

9. For dwelling units, a branch-circuit supplying _____ receptacles outlets is permitted to also supply receptacle outlets in an attached garage.

a. outdoor b. bathroom c. laundry room d. kitchen small-appliance

Copyright 2008 Ted "Smitty" Smith

Page 20: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

9. a 210.52(B)(2) 210.11(C)(2) & (3)

Copyright 2008 Ted "Smitty" Smith

Page 21: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

10. A metal underground water pipe may serve as a grounding electrode if it is in direct contact with the earth for at LEAST ______feet or more.

a. 6 b. 8 c. 10 d. 12

Copyright 2008 Ted "Smitty" Smith

Page 22: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

10. c 250.52(A)(1)

Copyright 2008 Ted "Smitty" Smith

Page 23: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

11. What is the MAXIMUM allowable cord length for the cord supplying a cord-and-plug connected dishwasher installed under a kitchen counter in a dwelling unit?

a. 1 ½ feet b. 2 feet c. 3 feet d. 4 feet

Copyright 2008 Ted "Smitty" Smith

Page 24: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

11. d 422.16(B)(2)(2)

Copyright 2008 Ted "Smitty" Smith

Page 25: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

12. What is the MINIMUM size copper SE cable with type THHW insulation that may be used as ungrounded, service-entrance phase conductors for a 150 ampere-rated, 120/240-volt, single-phase, residential service?

a. 1/0 AWG b. 1 AWG c. 2 AWG d. 3 AWG

Copyright 2008 Ted "Smitty" Smith

Page 26: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

12. b Tbl. 310.15(B)(6)

Copyright 2008 Ted "Smitty" Smith

Page 27: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

13. For outlet boxes designed to support ceiling-suspended (paddle) fans that weigh more than ______ pounds, the required marking shall include the maximum weight to be supported.

a. 20 b. 30 c. 35 d. 70

Copyright 2008 Ted "Smitty" Smith

Page 28: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

13. c 314.27(D)

Copyright 2008 Ted "Smitty" Smith

Page 29: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

14. A connection to a driven or buried grounding electrode shall _____.

a. be accessible b. not be required to be accessible c. not be permitted to be buried d. be visible

Copyright 2008 Ted "Smitty" Smith

Page 30: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

14. b 250.68(A), Ex. 1

Copyright 2008 Ted "Smitty" Smith

Page 31: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

15. What is the MAXIMUM allowable standard size circuit breaker rating that may be used to protect a size 8 AWG copper NM-B cable supplying an electric range?

a. 30 amperes b. 40 amperes c. 50 amperes d. 60 amperes

Copyright 2008 Ted "Smitty" Smith

Page 32: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

15. b 334.80 Tbl. 310.16

Copyright 2008 Ted "Smitty" Smith

Page 33: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

16. The MAXIMUM number of size 10 AWG conductors permitted in a 4 inch X 1 ¼ inch octagon metal junction box is _____.

a. two b. four c. five d. six

Copyright 2008 Ted "Smitty" Smith

Page 34: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

16. c Tbl. 314.16(A)

Copyright 2008 Ted "Smitty" Smith

Page 35: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

17. Determine the MINIMUM number of 15-ampere, 120-volt general lighting branch-circuits required for a dwelling that has 2,600 square feet of habitable space.

a. three b. four c. five d. six

Copyright 2008 Ted "Smitty" Smith

Page 36: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

17. c 220.12 Tbl. 220.12 2600 Sq. Ft. X 3VA (total lighting VA of house) 120 volts X 15 amperes = 1800 VA (one circuit)

7800 VA (house) /1800 VA (one circuit) =4.3 = 5 circuits

Copyright 2008 Ted "Smitty" Smith

Page 37: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

18. When calculating the total load on a dwelling unit, how many VA per square feet must be included for the general purpose receptacle outlets?

a. none b. one c. two d. three

Copyright 2008 Ted "Smitty" Smith

Page 38: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

18. a 220.14(J)(1)

Copyright 2008 Ted "Smitty" Smith

Page 39: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

19. When calculating the total load for a dwelling unit, what is the MINIMUM load, in VA, that must be added for the two required small appliance branch-circuits?

a. 1200 VA b. 1500 VA c. 2400 VA d. 3000 VA

Copyright 2008 Ted "Smitty" Smith

Page 40: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

19. d 220.52(A) 1500 VA X 2 circuits required = 3000 VA

Copyright 2008 Ted "Smitty" Smith

Page 41: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

20. It shall be permissible to apply a demand factor of _____ percent to the nameplate-rating load of four or more fastened in place electric water heaters in a multi-family dwelling unit.

a. 50 b. 75 c. 80 d. 90

Copyright 2008 Ted "Smitty" Smith

Page 42: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

20. b 220.53

Copyright 2008 Ted "Smitty" Smith

Page 43: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

End of Drill Click the left mouse button to

advance back to the first question. Each question will now be repeated without the timer to give you a chance to review it and find the answer.

Clicking the left mouse button will advance the slide to the answer and the code

reference.

Copyright 2008 Ted "Smitty" Smith

Page 44: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

1. What is the MAXIMUM period allowed for temporary outdoor Christmas decoration lighting for residences?

a. 30 days b. 60 days c. 90 days d. 4 months

Copyright 2008 Ted "Smitty" Smith

Page 45: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

1. c 590.3(B)

Copyright 2008 Ted "Smitty" Smith

Page 46: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

2. When doing box fill calculations, a fixture stud in a ceiling mounted outlet box is an equivalent to _____ conductor(s).

a. zero b. one c. two d. three

Copyright 2008 Ted "Smitty" Smith

Page 47: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

2. b 314.16(B)(3)

Copyright 2008 Ted "Smitty" Smith

Page 48: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

3. A branch-circuit supplying more than one electric baseboard heater in a residential occupancy shall be rated a MAXIMUM of _____.

a. 15 amperes b. 20 amperes c. 30 amperes d. 50 amperes

Copyright 2008 Ted "Smitty" Smith

Page 49: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

3. c 424.3(A)

Copyright 2008 Ted "Smitty" Smith

Page 50: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

4. Disregarding exceptions, when installing electrical metallic tubing (EMT), the run of tubing is required to be securely fastened at LEAST every _____.

a. 6 feet b. 10 feet c. 15 feet d. 20 feet

Copyright 2008 Ted "Smitty" Smith

Page 51: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

4. b 358.30(A)

Copyright 2008 Ted "Smitty" Smith

Page 52: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

5. When calculating the demand load for a one-family dwelling, what total MINIMUM volt-amperes (VA) must be included in the calculations for the small-appliance and laundry circuit loads?

a. 4500 VA b. 3000 VA c. 1500 VA d. 6000 VA

Copyright 2008 Ted "Smitty" Smith

Page 53: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

5. a 210.11(C)(1) & (2) 220.52(A) & (B) 2- small appliance circuits @ 1500VA ea = 3000VA

1- laundry circuit @ 1500VA ea = 1500VA

Total = 4500VA

Copyright 2008 Ted "Smitty" Smith

Page 54: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

6. The NEC® mandates the ampacity of UF cable shall be that of _____ conductors.

a. 60ºC rated b. 75ºC rated c. 86ºF rated d. 90ºC rated

Copyright 2008 Ted "Smitty" Smith

Page 55: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

6. a 340.80

Copyright 2008 Ted "Smitty" Smith

Page 56: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

7. The front edge of a switch box installed in a wall constructed of wood, shall be _____ from the surface of the wall.

a. flush with or projected out b. set back a maximum of ¼ inch c. set back a maximum of ½ inch d. set back a maximum of 3/8 inch

Copyright 2008 Ted "Smitty" Smith

Page 57: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

7. a 314.20

Copyright 2008 Ted "Smitty" Smith

Page 58: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

8. For dwelling units, where 125 volt, single-phase, 15 and 20 ampere receptacle outlets are installed within at LEAST _____ of the outside edge of a sink in a laundry room, GFCI protection must be provided.

a. 4 feet b. 6 feet c. 8 feet d. 10 feet

Copyright 2008 Ted "Smitty" Smith

Page 59: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

8. b 210.8(A)(7)

Copyright 2008 Ted "Smitty" Smith

Page 60: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

9. For dwelling units, a branch-circuit supplying _____ receptacles outlets is permitted to also supply receptacle outlets in an attached garage.

a. outdoor b. bathroom c. laundry room d. kitchen small-appliance

Copyright 2008 Ted "Smitty" Smith

Page 61: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

9. a 210.52(B)(2) 210.11(C)(2) & (3)

Copyright 2008 Ted "Smitty" Smith

Page 62: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

10. A metal underground water pipe may serve as a grounding electrode if it is in direct contact with the earth for at LEAST ______feet or more.

a. 6 b. 8 c. 10 d. 12

Copyright 2008 Ted "Smitty" Smith

Page 63: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

10. c 250.52(A)(1)

Copyright 2008 Ted "Smitty" Smith

Page 64: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

11. What is the MAXIMUM allowable cord length for the cord supplying a cord-and-plug connected dishwasher installed under a kitchen counter in a dwelling unit?

a. 1 ½ feet b. 2 feet c. 3 feet d. 4 feet

Copyright 2008 Ted "Smitty" Smith

Page 65: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

11. d 422.16(B)(2)(2)

Copyright 2008 Ted "Smitty" Smith

Page 66: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

12. What is the MINIMUM size copper SE cable with type THHW insulation that may be used as ungrounded, service-entrance phase conductors for a 150 ampere-rated, 120/240-volt, single-phase, residential service?

a. 1/0 AWG b. 1 AWG c. 2 AWG d. 3 AWG

Copyright 2008 Ted "Smitty" Smith

Page 67: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

12. b Tbl. 310.15(B)(6)

Copyright 2008 Ted "Smitty" Smith

Page 68: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

13. For outlet boxes designed to support ceiling-suspended (paddle) fans that weigh more than ______ pounds, the required marking shall include the maximum weight to be supported.

a. 20 b. 30 c. 35 d. 70

Copyright 2008 Ted "Smitty" Smith

Page 69: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

13. c 314.27(D)

Copyright 2008 Ted "Smitty" Smith

Page 70: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

14. A connection to a driven or buried grounding electrode shall _____.

a. be accessible b. not be required to be accessible c. not be permitted to be buried d. be visible

Copyright 2008 Ted "Smitty" Smith

Page 71: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

14. b 250.68(A), Ex. 1

Copyright 2008 Ted "Smitty" Smith

Page 72: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

15. What is the MAXIMUM allowable standard size circuit breaker rating that may be used to protect a size 8 AWG copper NM-B cable supplying an electric range?

a. 30 amperes b. 40 amperes c. 50 amperes d. 60 amperes

Copyright 2008 Ted "Smitty" Smith

Page 73: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

15. b 334.80 Tbl. 310.16

Copyright 2008 Ted "Smitty" Smith

Page 74: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

16. The MAXIMUM number of size 10 AWG conductors permitted in a 4 inch X 1 ¼ inch octagon metal junction box is _____.

a. two b. four c. five d. six

Copyright 2008 Ted "Smitty" Smith

Page 75: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

16. c Tbl. 314.16(A)

Copyright 2008 Ted "Smitty" Smith

Page 76: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

17. Determine the MINIMUM number of 15-ampere, 120-volt general lighting branch-circuits required for a dwelling that has 2,600 square feet of habitable space.

a. three b. four c. five d. six

Copyright 2008 Ted "Smitty" Smith

Page 77: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

17. c 220.12 Tbl. 220.12 2600 Sq. Ft. X 3VA (total lighting VA of house) 120 volts X 15 amperes = 1800 VA (one circuit)

7800 VA (house) /1800 VA (one circuit) =4.3 = 5 circuits

Copyright 2008 Ted "Smitty" Smith

Page 78: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

18. When calculating the total load on a dwelling unit, how many VA per square feet must be included for the general purpose receptacle outlets?

a. none b. one c. two d. three

Copyright 2008 Ted "Smitty" Smith

Page 79: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

18. a 220.14(J)(1)

Copyright 2008 Ted "Smitty" Smith

Page 80: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

19. When calculating the total load for a dwelling unit, what is the MINIMUM load, in VA, that must be added for the two required small appliance branch-circuits?

a. 1200 VA b. 1500 VA c. 2400 VA d. 3000 VA

Copyright 2008 Ted "Smitty" Smith

Page 81: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

19. d 220.52(A) 1500 VA X 2 circuits required = 3000 VA

Copyright 2008 Ted "Smitty" Smith

Page 82: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

20. It shall be permissible to apply a demand factor of _____ percent to the nameplate-rating load of four or more fastened in place electric water heaters in a multi-family dwelling unit.

a. 50 b. 75 c. 80 d. 90

Copyright 2008 Ted "Smitty" Smith

Page 83: Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

20. b 220.53

Copyright 2008 Ted "Smitty" Smith