Page 1: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

©Ted “Smitty” Smith 2008

Page 2: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead of two minutes.

Attempt to answer the questions and then when the slide show completes, Check your answer. When you reach the end of the drill all of the slides will be repeated without the timer so you will have time to check and verify your answers at that time.

Click on the left mouse button to begin.

Page 3: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the minimum sized THHN wire that can be used to feed the following motor:

Three Phase, squirrel cage, 30 HP, 480 Volts, 33.6 amperes FLC, 1.15 marked service factor and Design K.

Page 4: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

6 AWG THHN Based on the 60 degree column of

310.16 based on 110.14(C)

Page 5: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 1/0 AWG THHN conductor installed in an ambient temperature of 103 degrees F. will have an ampacity of _________.

Copyright 2005 Ted "Smitty" Smith

Page 6: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• 154.70 Amperes

Page 7: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the minimum sized THHN copper conductor that can be used to feed six arc welders with the following ratings:

1. 50 A at 30 Duty Cycle 2. 60 A at 40 duty cycle 3. 100 at 10 duty cycle 4. 100 A at 10 duty cycle 5. 75 A at 50 duty cycle 6. 44.6 A at 60 duty cycle

Page 8: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

250 KCMIL Determined by 6301.11 (A )and (B) Table 310.16 Column 60 degrees C

based on 110.14(C)

Page 9: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the ampacity of a 250 kCMIL aluminum THW conductor installed in an ambient temperature of 44 degrees Celsius?

Copyright 2005 Ted "Smitty" Smith

Page 10: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

168.100 amperes

Page 11: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• What is the volume allowance required for the following junction box which has a total of nine 12 AWG THHN conductors entering the junction box, one of which is an equipment grounding conductor. The box will contain one duplex receptacle, has no internal clamps, and no luminairie studs or hickeys.

Page 12: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

24.75

Page 13: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• What is the demand on the main service entrance of a range that has a nameplate rating of 240V and 9.5 kW?

Page 14: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

8000 watts

Page 15: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A load of 23 amperes is being fed by a circuit consisting of 10 AWG THHN copper conductors. The conductors are installed in a conduit that is installed on a rooftop in the direct sunlight. The conduit is installed 12” above the roof from the bottom of the conduit. The average ambient temperature for the area in which the conduit is installed is 87 degrees F. The conduit contains a total of three current carrying conductors. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 16: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes, it is rated to carry 32.8 amperes.

Page 17: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Three 10 AWG THHN, four 6 AWG THW and five 8 AWG TW conductors are installed in a one and one half inch electrical metallic tubing conduit that is 280 feet in length. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 18: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes, the wires make up a volume of .5722 and at 40% fill an EMT 1 1/2” conduit is .814.

Copyright 2005 Ted "Smitty" Smith

Page 19: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the ampacity of 2 AWG TW aluminum conductor installed in a conduit that is installed in a boiler room with an ambient temperature of 103 degrees F and the conductor is installed in a conduit with a total of 17 current carrying conductors?

Page 20: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

30.75 Amperes

Page 21: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a dwelling unit for a range that has a nameplate rating of 14.5 kW at 240 volts?

Page 22: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

9200 watts

Page 23: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 4 x 1 ½ square metal box is installed with two duplex receptacles. The box has a total of three 12 AWG MC cables entering the box, each MC cable is a 12/2 with ground. The box contains no internal cable clamps, and no luminairie studs or hickeys. Is this an acceptable installation?

Page 24: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

No, the conductors and devices require a volume allowance of 24.75 and Table 314.16(A) lists a 4 x 1 ½” metal box as having a volume of 21.0

Page 25: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Is it allowable to add three 10 AWG THHN conductors to an existing conduit that is 150 feet in length and currently has eight 6 AWG THWN conductors and one 12 AWG THHN conductor installed? The conduit is a 1 ¼” inch electrical metallic tubing.

Page 26: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

No. The total area used by the conductors once the three 10 AWG conductors are added will be .4822 inches and a 1 ¼” EMT at 31% fill has an allowance of only .464 inches.

Page 27: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a single family dwelling for a range that has a rating of 14.2 kW at 240 volts?

Page 28: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

8800 VA

Page 29: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for the following ranges:

9.6 kW at 240 V 12.9 kW at 240 V 16.8 kW at 240 V 21.2 kW at 240 V 11.5 kW at 240 V

Page 30: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

23 kW

Page 31: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

How many 15 ampere lighting circuits will be required for a single family dwelling that is 2650 square feet to meet the minimum requirements of the National Electric Code?

Page 32: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

5

2650 x 3= 7950/120=66.25 amperes/ 15= 4.41

Total of 5 circuits

Page 33: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for 15 electric clothes dryers that are rated at 4.4 kW at 240 volts?

Page 34: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

32250 VA

5000 x 15= 75000 75000 x .43= 32250 VA

Page 35: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for the lighting and receptacle loads for 20 apartments if each apartment is 1300 square feet?

Page 36: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

55950 VA

3 x 1300 x 20= 78000 4500 x 20= 90000 78000 + 90000= 168000- 3000=

165000 165000- 117000= 48000 117000

x .35= 40950 48000 x .25= 12000 12000 + 40950 + 3000= 55950 VA

Page 37: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 39.6 ampere load is fed with a 6 AWG THW conductor that is installed in a conduit with a total of 7 current carrying conductors. The conduit is installed in a room that has an ambient temperature 38 degrees Celsius. Is this an acceptable installation?

Page 38: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes it is acceptable. The conductor is rated at 40.04 amperes.

Page 39: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the maximum sized instantaneous trip breaker that can be used to protect the following motor for short circuit protection:

50 HP, 208V, three phase, squirrel cage motor, 116.8 amperes FLC, marked service factor of 1.15?

Page 40: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

1200 Amperes Based on T430.52 and 240.6 for

standard sized fuses and circuit breakers.

Page 41: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

This is the end of the presentation.

You can now review the slides and answers without the timer.

Click the slide to advance to the next slide

Page 42: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the minimum sized THHN wire that can be used to feed the following motor:

Three Phase, squirrel cage, 30 HP, 480 Volts, 33.6 amperes FLC, 1.15 marked service factor and Design K.

Page 43: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

6 AWG THHN Based on the 60 degree column of

310.16 based on 110.14(C)

Page 44: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 1/0 AWG THHN conductor installed in an ambient temperature of 103 degrees F. will have an ampacity of _________.

Copyright 2005 Ted "Smitty" Smith

Page 45: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• 154.70 Amperes

Page 46: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the minimum sized THHN copper conductor that can be used to feed six arc welders with the following ratings:

1. 50 A at 30 Duty Cycle 2. 60 A at 40 duty cycle 3. 100 at 10 duty cycle 4. 100 A at 10 duty cycle 5. 75 A at 50 duty cycle 6. 44.6 A at 60 duty cycle

Page 47: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

250 KCMIL Determined by 6301.11 (A )and (B) Table 310.16 Column 60 degrees C

based on 110.14(C)

Page 48: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the ampacity of a 250 kCMIL aluminum THW conductor installed in an ambient temperature of 44 degrees Celsius?

Copyright 2005 Ted "Smitty" Smith

Page 49: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

168.100 amperes

Page 50: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• What is the volume allowance required for the following junction box which has a total of nine 12 AWG THHN conductors entering the junction box, one of which is an equipment grounding conductor. The box will contain one duplex receptacle, has no internal clamps, and no luminairie studs or hickeys.

Page 51: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

24.75

Page 52: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

• What is the demand on the main service entrance of a range that has a nameplate rating of 240V and 9.5 kW?

Page 53: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

8000 watts

Page 54: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A load of 23 amperes is being fed by a circuit consisting of 10 AWG THHN copper conductors. The conductors are installed in a conduit that is installed on a rooftop in the direct sunlight. The conduit is installed 12” above the roof from the bottom of the conduit. The average ambient temperature for the area in which the conduit is installed is 87 degrees F. The conduit contains a total of three current carrying conductors. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 55: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes, it is rated to carry 32.8 amperes.

Page 56: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Three 10 AWG THHN, four 6 AWG THW and five 8 AWG TW conductors are installed in a one and one half inch electrical metallic tubing conduit that is 280 feet in length. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 57: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes, the wires make up a volume of .5722 and at 31% fill an EMT 1 1/2” conduit is .631.

Copyright 2005 Ted "Smitty" Smith

Page 58: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the ampacity of 2 AWG TW aluminum conductor installed in a conduit that is installed in a boiler room with an ambient temperature of 103 degrees F and the conductor is installed in a conduit with a total of 17 current carrying conductors?

Page 59: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

30.75 Amperes

Page 60: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a dwelling unit for a range that has a nameplate rating of 14.5 kW at 240 volts?

Page 61: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

9200 watts

Page 62: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 4 x 1 ½ square metal box is installed with two duplex receptacles. The box has a total of three 12 AWG MC cables entering the box, each MC cable is a 12/2 with ground. The box contains no internal cable clamps, and no luminairie studs or hickeys. Is this an acceptable installation?

Page 63: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

No, the conductors and devices require a volume allowance of 24.75 and Table 314.16(A) lists a 4 x 1 ½” metal box as having a volume of 21.0

Page 64: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Is it allowable to add three 10 AWG THHN conductors to an existing conduit that is 150 feet in length and currently has eight 6 AWG THWN conductors and one 12 AWG THHN conductor installed? The conduit is a 1 ¼” inch electrical metallic tubing.

Page 65: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

No. The total area used by the conductors once the three 10 AWG conductors are added will be .4822 inches and a 1 ¼” EMT at 31% fill has an allowance of only .464 inches.

Page 66: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a single family dwelling for a range that has a rating of 14.2 kW at 240 volts?

Page 67: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

8800 VA

Page 68: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for the following ranges:

9.6 kW at 240 V 12.9 kW at 240 V 16.8 kW at 240 V 21.2 kW at 240 V 11.5 kW at 240 V

Page 69: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

23 kW

Page 70: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

How many 15 ampere lighting circuits will be required for a single family dwelling that is 2650 square feet to meet the minimum requirements of the National Electric Code?

Page 71: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

5

2650 x 3= 7950/120=66.25 amperes/ 15= 4.41

Total of 5 circuits

Page 72: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for 15 electric clothes dryers that are rated at 4.4 kW at 240 volts?

Page 73: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

32250 VA

5000 x 15= 75000 75000 x .43= 32250 VA

Page 74: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the demand on the main service entrance of a multifamily dwelling for the lighting and receptacle loads for 20 apartments if each apartment is 1300 square feet?

Page 75: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

55950 VA

3 x 1300 x 20= 78000 4500 x 20= 90000 78000 + 90000= 168000- 3000=

165000 165000- 117000= 48000 117000

x .35= 40950 48000 x .25= 12000 12000 + 40950 + 3000= 55950 VA

Page 76: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

A 39.6 ampere load is fed with a 6 AWG THW conductor that is installed in a conduit with a total of 7 current carrying conductors. The conduit is installed in a room that has an ambient temperature 38 degrees Celsius. Is this an acceptable installation?

Page 77: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

Yes it is acceptable. The conductor is rated at 40.04 amperes.

Page 78: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

What is the maximum sized instantaneous trip breaker that can be used to protect the following motor for short circuit protection:

50 HP, 208V, three phase, squirrel cage motor, 116.8 amperes FLC, marked service factor of 1.15?

Page 79: ©Ted “Smitty” Smith 2008.  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead

1200 Amperes Based on T430.52 and 240.6 for

standard sized fuses and circuit breakers.