turbine generator baseline testing30 0 synchronize 0 reduce excitation to obtain 30mvar leading...
TRANSCRIPT
-
Turbine Generator Baseline Testing
John Undrill November 2015
-
The Overall Context
Understand the equipment you are going to test
Understand the modeling of the equipment at the grid-simulation level
Test the equipment, deduce parameter values, verify that simulations made with the models are correct
Maintain a stable data base to support the use of the models
Monitor the modeling continuously to check validity of models and condition of plants
-
The Overall Requirement
Expertise with test equipment, signal processing software, and equipment operation is NOT SUFFICIENT
Expertise with the operation of a dynamic simulation program and the mathematics of dynamic models are NOT SUFFICIENT
You have to understand the equipment at the level of its dynamic behavior
You have to understand the dynamic simulation process
-
Getting Ready
SURVEY THE PLANT Go to the plant Search for all available documentation Scan and read everything Photograph nameplates Review and record base values Generator MVA Turbine rated/nominal power Turbine head
SELECT THE MODELS Build up a pro-forma model Run pre-test simulations
MAKE THE TEST PLANS Step by step for control room MW chronogram for power schedulers
-
Power Scheduling Chronogram
-100
-50
0
50
100
150
200
250
300
6.00 8.00 10.00 12.00 14.00 16.00 18.00 20.00 22.00
Time
Gen
erat
or M
W
GTMWSTMWSTMVARGTVAR
-
0 50 100 150 200 250Field current, Amps
0
0.2
0.4
0.6
0.8
1
1.2
Stat
or v
olta
ge, p
u
Magnetization Curve Oildale Energy LM6000
Red - Ifd test Black - Ifd model Blue - Air Gap LineAFAG = 134.00s1 = 0.12 s12 = 0.40
-
-20 -15 -10 -5 0 5 10 15 20Reactive Power, per unit
0
0.5
1
1.5
2
2.5
3
Fiel
d C
urre
nt, p
er u
nit
V curve Oildale Energy LM6000
Red - Ifd test Black - Ifd modelBlue - voltage Magenta - power
Mbase = 50.50 MVALd = 2.100 Lq = 2.000s1 = 0.120 S12= 0.400Ll = 0.200 Kis= 0.080Ra = 0.0050 Afag= 134.0If0 = 0.000
-
0.3 0.2 0.1 0 0.1 0.2 0.3 0.4 0.50
0.5
1
1.5
2
2.5
3
Reactive Power, per unit
Fiel
d C
urre
nt, p
er u
nit
V curve Bonanza
Red Ifd test Black Ifd modelBlue voltage Magenta power
Mbase = 523.00 MVALd = 1.900 Lq = 1.750s1 = 0.130 S12= 0.400Ll = 0.300 Kis= 0.140Ra = 0.0000 Afag= 52.0
-
-0.2 -0.1 0 0.1 0.2 0.3Reactive Power, per unit
0
0.5
1
1.5
2
2.5
Fie
ld C
urre
nt, p
er u
nit
V curve Lancaster GT 2
Black - Ifd test R,G,B - Ifd model
Blue - voltage Magenta - power
Mbase = 234.00 MVA
Ld = 2.200 Lq = 1.900
s1 = 0.100 S12= 0.250
Ll = 0.165 Kis= 0.140
Ra = 0.0000 Afag= 540.0
LancasterGTvee000.csv
-
Time MW Action Excitation
20:00 Normal Commence reducing load so as to be ready for no load testing at 2200 Normal22:00 Minimum Transfer unit auxiliaries to startup transformer Normal
Disable transfer trips from 52a/52b contacts as neededDisable reverse power relay
22:15 0 Reduce generator output to zero Mw and zero MVAR Auto or Man
22:30 0 Reduce excitation to run generator into leading power factor - 50 MVAR as required0 Increase excitation to return to 0 MVAR0 Increase excitation to run generator into lagging power factor - 50 to 60 MVAR0 Decrease excitation to return to 0 MVAR
0:00:00 0 Open generator circuit breaker (52) Auto or Man0 Reduce excitation as far as possible as required0 Raise excitation in gentle steps to raise voltage to 110 percent0 Return voltage to normal synchronizing value
0:30 0 Synchronize0 Reduce excitation to obtain 30MVAR leading Manual0 Open generator circuit breaker (52)
1:00 0 Synchronize0 Reduce Excitation to obtain 60 MVAR leading Manual0 Open generator circuit breaker (52)
1:30 0 Synchronize0 Reduce excitation to obtain 30 MVAR leading Auto 0 Open generator circuit breaker (52)
2:00 0 Synchronize0 Reduce Excitation to obtain 60 MVAR leading Auto0 Open generator circuit breaker (52)
2:30 0 Synchronize40 Increase generator power to 40MW and 30 MVAR leading Manual40 Open generator circuit breaker (52)
3:00 0 Restore reverse power relay to normal0 Remove transfer trip bypasses0 Testing Complete
-
Theoretical Basis
-
Test Simulation
-
Beware Theory assumes constant field voltage
Most static excitation systems work in constant-field-current mode when switched into manual operation
-
0 10 20 30 40 50 60Time, sec
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Stat
or v
olta
ge, p
u
../tests/T-15-10-27-1743-001.xls
3.8 3.9 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7Time, sec
0.8
0.82
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
1
Stat
or v
olta
ge, p
u
../tests/T-15-10-27-1743-001.xls
-
3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 80.99
1
1.01
1.02
1.03
1.04
Stat
or v
olta
ge, p
u
3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8Time, sec
0
1
2
3
4
5
Fiel
d vo
ltage
, pu
../tests/T-15-10-27-1442-001.xls
0 2 4 6 8 10 12 14 16 18 201.02
1.03
1.04
1.05
1.06
1.07
Stat
or v
olta
ge, p
u
0 2 4 6 8 10 12 14 16 18 200
1
2
3
4
5
Fiel
d vo
ltage
, pu
0 2 4 6 8 10 12 14 16 18 20-5
0
5
10
15
Rea
ctiv
e po
wer
, MVA
R
0 2 4 6 8 10 12 14 16 18 20Time, sec
30
32
34
36
38
40R
eact
ive
pow
er, M
VAR
../tests/T-15-10-27-1709-001.xls
-
Divx 10 Divy 10 0.0 Time 500.0
Name Min Max Col CpPu F Fa Fb Fc Fd
Data file: t3ag1.csv
Scale file: t3ag1.scl
GilaBend GT3A
..
...
....
.....
0 TNR 95.0 105.0 2 1.0 1 0.0 0.0 0.0 0.0
1 TNH 99.9 100.9 9 1.0 2 0.2 0.0 0.0 0.0____
2 DWATT 115.0 165.0 3 1.0 1 0.0 0.0 0.0 0.0
3 FSRN 60.0 100.0 1 1.0 1 0.0 0.0 0.0 0.0
4 FSRT 60.0 100.0 5 1.0 1 0.0 0.0 0.0 0.0
6 CPR 0.0 15.0 9 1.0 1 0.0 0.0 0.0 0.0
7 CSGV 0.0 100.0 6 1.0 1 0.0 0.0 0.0 0.0
Divx 10 Divy 10 0.0 Time 500.0
Name Min Max Col CpPu F Fa Fb Fc Fd
Data file: gtgov.chf
Scale file: gtgov.scl
GENS Output
.
.
.
.
8 pmech 115.0 165.0 3 1.0 1 0.0 0.0 0.0 0.0
12 Sp-c 0.6 1.0 5 1.0 1 0.0 0.0 0.0 0.0
13 Sp-d 0.6 1.0 1 1.0 1 0.0 0.0 0.0 0.0
-
Divx 10 Divy 10 20.0 Time 120.0
Name Min Max Col CpPu
Data file: t3ag1.csv
Scale file: t3ag1.scl
GilaBend GT3A
..
...
....
.....
0 TNR 95.0 105.0 2 1.0
1 TNH 99.5 104.5 9 1.0
2 DWATT 115.0 165.0 3 1.0
3 FSRN 60.0 100.0 1 1.0
4 FSRT 60.0 100.0 5 1.0
6 CPR 0.0 15.0 9 1.0
7 CSGV 0.0 100.0 6 1.0
Divx 10 Divy 10 25.0 Time 125.0
Name Min Max Col CpPu F Fa Fb Fc Fd
Data file: gtgov.chf
Scale file: gtgov.scl
GENS Output
.
.
.
.
8 pmech 115.0 165.0 3 1.0 1 0.0 0.0 0.0 0.0
12 Sp-c 0.6 1.0 5 1.0 1 0.0 0.0 0.0 0.0
13 Sp-d 0.6 1.0 1 1.0 1 0.0 0.0 0.0 0.0
-
Divx 10 Divy 10 160.0 Time 260.0
Name Min Max Col CpPu F Fa Fb Fc Fd
Data file: t3ag1.csv
Scale file: t3ag1.scl
GilaBend GT3A
..
...
....
.....
0 TNR 95.0 105.0 2 1.0 1 0.0 0.0 0.0 0.0
1 TNH 99.5 104.5 9 1.0 1 0.0 0.0 0.0 0.0
2 DWATT 115.0 165.0 3 1.0 1 0.0 0.0 0.0 0.0
3 FSRN 60.0 100.0 1 1.0 1 0.0 0.0 0.0 0.0
4 FSRT 60.0 100.0 5 1.0 1 0.0 0.0 0.0 0.0
6 CPR 0.0 15.0 9 1.0 1 0.0 0.0 0.0 0.0
7 CSGV 0.0 100.0 6 1.0 1 0.0 0.0 0.0 0.0
Divx 10 Divy 10 160.0 Time 260.0
Name Min Max Col CpPu F Fa Fb Fc Fd
Data file: gtgov.chf
Scale file: gtgov.scl
GENS Output
.
.
.
.
8 pmech 115.0 165.0 3 1.0 1 0.0 0.0 0.0 0.0
12 Sp-c 0.6 1.0 5 1.0 1 0.0 0.0 0.0 0.0
13 Sp-d 0.6 1.0 1 1.0 1 0.0 0.0 0.0 0.0