training manual trouble shooting - rational ag · training manual trouble shooting scc line self...
TRANSCRIPT
Training manualTrouble Shooting
SCC Line Self Cooking Center - Combi Master
- 2 - V03 EN, Trouble Shooting
General hints:
Isolate the appliance from mains supply before opening the appliance
When working with chemicals, i.e. aggressive cleaning materialsalways wear protective clothing, goggles and gloves!
After maintenance / repair the appliance must be checked for electric safety in accordance with your national, state and local requirements!
Whenever working on any gas component like:Gas valve, gas blower and / or changing connected type of gas a detailed
flue gas analysis MUST be done using adequate CO and CO2 measuring equipment! This shall ONLY be done by trained technicians!
Always check appliance for possible gas leakages!
- 3 - V03 EN, Trouble Shooting
Trouble shooting
Fault tree
Miscellaneous
Main Fan Motor SCC Line 4Humidity Control SCC / CM 6Clima Valve SCC Line 8Cleanjet +Care 10Solid State Relais - SSR 12SCC - Main Printed Circuit Board (PCB) 42.00.002 14SCC - Software 16Bus Control 18Gas 20
Selftest 22Service 10 (SC Pump) 23Service 11 (CDS Sensor) 24Service 25 (Cleanjet Pump) 25Service 26 (Drain Valve) 26Service 27 (Drain Valve) 26Service 32 (only gas unit) 27Service 34 (Bus) 27Service 40 (Care Pump) 28Service 41 (Y3 Moistening solenoid) 29Service 42 (Y4 Care solenoid) 30Service 43 (triple solenoid valve) 31Service 44 (Steam Heating) 31Service 100 (Main Contactor) 32Service 110 (SC-Pump) 32Service 120 (Y1 Filling solenoid, Level electrode) 33No display - safety circuit - SCC 34No or too low steam production - SCC 35Service 12 / Indication descaling - SCC 36Buzzer sounds - SCC 37„RESET“ indication (Gas units) - SCC 38Check polarity (Gas units) - SCC 38Indication „E13“ (SC-Automatic) - CM 39No function- safety circuit - CM 40No Steam - CM 41Indication „rES“ (=reset) - CM 42CHnG POL (check polarity) - CM 42Buzzer sounds - CM 43
Circuit diagram Power Circuit 45SCC Service Reference 50CM Service Reference 52
- 4 - V03 EN, Trouble Shooting
Fan Motor SCC Line
Fan Motor SCC Line 40.00.274 1NAC 100-240V (L1, N, PE) 40.00.276 3AC 400-480V (L1, L2, L3, PE)
1. Standard operation
The green LED shows when power is supplied from the secondary side main contactor.
The running signal is coming via BUS connection from the main PCB (CM) or I/O PCB (SCC). This signal also determines the speed of the motor.The motor speed differs depending on the unit size the motor is build in (examples):CM: 1800 (450) rpm (all sizes)SCC 61: 500 – 1900 rpm SCC 202: 500 – 2200rp
The BUS cable (RJ45 connection) can be connected to either the left or right RJ45 socket.
The motor is shipped with the motor shaft gasket (22.00.083), an optional jumper (40.01.581) and a venting pipe con-version kit 87.00.325.
In floor models 201 and 202 two motors of the same kind are used. In this case the upper motor must get the jumper onto the right two pins as indicated.
2. Mounting sequence:
When mounting a new motor please observe the following mounting sequence:
When fitting a new motor ALWAYS use a new motor shaft gasket (which is supplied with the motor)! Fix the motor bolts first hand-tight only, followed by the new gasket in its mounting ring very loose, now tighten the motor bolts: This allows the gasket in its bracket to center itself before you tighten the 4x flat 10mm nuts 1106.0220 of the gasket mounting ring.
Make sure the off-centered hole in the holding frame is mounted in 12 o’clock position.
Only with this sequence you assure that the motor shaft gasket is mounted centered.
The fan wheel screw must be tightened with torque 38 Nm.
NOTE: After mounting the motor and fan wheel the unit must be newly calibrated for humidity.
- 5 - V03 EN, Trouble Shooting
3. Possible fan motor problems
• Bus connection: CM shows error code E12; cabinet temp. display shows 1 ST: Motor bottom short circuit CM shows error code E12; cabinet temp. display shows 1 CO: Bus problem bottom motor
2 ST and 2 CO refer to the upper motor.
SCC shows Service 34.2 Bus problem bottom motor SCC shows Service 34.4 Bus problem upper motor
If bus connection problem is indicated, change RJ45 connection position first (left – right). If Indication chan-ges from 1CO to 2CO or 34.2 to 34.4., change fan motor, otherwise change bus cable (40.00.472)
• Motor doesn’t turn at all: Green LED is not ON. Check secondary side of main contactor.
Note: LED is located at bottom left hand corner of motor behind the hose from the Self Clean pump.
• Power on main contactor ok, LED does not show. Disconnect power plug from Motor and check if power is present at plug. If yes, motor has developed short circuit. Most likely reason: Water caused by condensation dropped onto motor.
• Check if the venting pipe above the motor is made of stainless steel pipe or silicone hose. If it is silicone hose replace by modification kit 87.00.325 (TI 12/2007) supplied with the motor.
• When mounting the venting pipe make sure to have it centered under the mounting hole in the unit cover to avoid water damage from this position.
• For bottom motor install collector plate 40.02.481. This collector plate is used in all units since 09/2007.
For top motor install protection plate 40.03.387 (refer to modification instruction MI0907). •
• In case the plug of the power supply cable fan motor is damaged it can be replaced using the repair kits 40.02.611 (3 pole plug) or 40.02.612 (4pole plug)
• LED blinking code: The LED might show in a blinking manner. Please refer to below table:
Reason Remedy1 Motor doesn’t start, no signal from hallsensor Check for motor blockage or change motor.2 Voltage too low on motor pcb Check supply voltage or change motor.3 Voltage too high on motor pcb Check supply voltage or change motor.4 rpm measurement defective Change motor.5 Motor pcb temperature >105°C Check cooling system (cooling fan, air filter), otherwise change motor6 Supply voltage <80V Check power supply (F1-F2)7 Motor pcb defective Change motor.8 Motor pcb defective Change motor.
- 6 - V03 EN, Trouble Shooting
1. Humidity control SCC
Humidity is permanently controlled inside the cabinet. 3 values are used for this control:
- Temperature of the cabinet is measured by thermocouple B4 (located behind motor mounting plate) - Fan motor speed (controlled and measured by Bus cable from Motor to PCB)
- Voltage signal from pressure sensor P1 The voltage signal is higher when the fan motor is running at higher speed. There is no humidity control possible when the motor is not turning at all. At any specific given fan motor speed:
The voltage signal of P1 is at its highest when the cabinet is cold and dry. The voltage signal of P1 is at its lowest when the cabinet is hot and moist. An average voltage signal for a dry and cold climate (40°C) at standard fan speed (1800rpm) would be between 2,8 and 3,2 Volt. This can be seen in Diagnostic mode 15 as output voltage.
In Steam Mode humidity is set to 100% and generated by the steam generator. Humidity can NOT be adjusted in Steam mode. In Combi mode humidity is set default to 90% but can be manually changed between 0% and 100%. Humidity is generated by the steam generator and the food. In Hot Air mode humidity is generated by the cooking food ONLY. This value is set default to 100% and can be limited to any value between 0% and 100%
2. Operational sequence (in general) When the CPU detects that the actual humidity is above the set level, the steam heating elements will be de-energised. The clima valve will open. Dry air is sucked into the cabinet and displaces the moist air through the cabinet drain. After the humidity level falls under the set level the clima valve will close again and steam will be generated if needed.
3. Humidity calibration SCC units with index G (produced since October 2008) will automatically run a self test when they are installed at the customer site. To run this self test the temperature of the unit (sensors B1, B2 and B4 must be below 40°C (104°F). During this self test the humidity values for a cold and dry climate and the humidity values under steam condi-tion will be evaluated in default fan speed (i.e. SCC 101: 1800 rpm). Values for other fan speeds and Combi mode are derived from these and can be identified in Diagnostic 16 by a value which can be divided by 100. Units which are predominantly used for baking must be manually be calibrated at the customer site. Manual calibration is done in service level, Basic settings 1.1 To start manual calibration the temperature of the unit must be below 40°C (104°F). The cabinet should be clean and dry. The cabinet space should be divided into 3 (floor units: 4) sections. To do so use 20mm closed containers - no grids!- and place them upside down onto rack level 3 and 7 (floor unit: trolley level 3, 10 and 17) Close the door and press start.
Humidity Control SCC / CM
RPMB4
P1
- 7 - V03 EN, Trouble Shooting
4. Possible humidity control problems
General Humidity control problems: • - Pipes and hoses from cabinet to Pressure sensor P1 might be blocked with fat or dirt particles. - Water might block the hoses leading to the pressure sensor P1; - Temperature of Quenching sensor B2 must react directly to cold water spray when quenching is active; if temperature remains high check positioning of quenching nozzle to quenching sensor. This can be checked by operating steam mode and observing the quenching sensor B2 in Diagnostic mode 2. - The silicone hose connections to the pressure sensor are as follows: The hose connecting closer to the center of the motor shaft is connected closer to the center of pressure sensor P1.
Vent pipe might be extended locally to avoid steam condensation under ceiling. • Such extension shall only be done when an air gap is provided. Use condensation breaker part number 8710.1309 for units 61, 101 and 62. At present there is no air break connection available for 102, 201 and 202.
Unit is permanently quenching when in any steam mode • Check clima valve for proper closed status. If clima valve leaks air into the cabinet unit will run into humidity emergency control. In this case the quenching sensor is responsible for humidty control (like in CM units). In this case you will find a ring or solid circle behind function key - Model type. This circle can also be visible in other cooking modes.
Customer complains about steam not being visible inside the cabinet • Check if temperature is above 110°C (230°F). At this temperature steam is invisible. Caution: Danger of scald-ing if door is opened. In an empty cabinet at 100°C steam will disappear because there will be no demand for humidity after some time.
Some humidity values in Diagnostic mode 16 show „0“ or „85000“ • Unit must be manually calibrated
When changing Thermocouple B4 (SP # 40.00.399) make sure the insulation is covering the mounting position • again properly.
Customer with baking application complains about uneven browning result • Calibrate the unit manually. Make sure customer does not use grids while baking; only flat trays (aluminum baking tray) should be used to achieve proper results; Check if the customer is using the SCC baking process. Baking in manual mode (hot air without humidity control) does not achieve good results!
Drain connection is extended over several meters before ending in an • open floor drain or connected directly via P-trap Venting the drain pipe within 0,5 meter from drain connection might help the humidity control to maintain a set level.
Motor
Center
Center
P1
E11SE0707200......
SW: SCC-04-01-05
Mod: SCC_101
English
30-40cm (12“-16“)X
3x 45°
D=50mm
- 8 - V03 EN, Trouble Shooting
Clima Valve SCC Line
Clima Valve SCC Line 22.00.568 SCC 61 / 62 (pipe 108 mm) 22.00.576 SCC 101 / 102 (pipe 238 mm) 22.00.577 SCC 201 / 202 (pipe 228mm)
1. Standard operation The clima valve is normally in closed position. When the door is opened the valve opens automatically.
The turning fan wheel (with the small fins on the rear side) creates a nega-tive pressure (suction) below the closed clima valve. This negative pressure increases with increasing fan speed.
If too much humidity is detected inside the cabinet, the clima valve motor will turn the clima valve (time: ¾ of cpl. turning time) for 270 degrees; The valve will now stand in vertical position allowing dry kitchen air to be sucked into the cabinet. This dry air will displace the humid air, which is now discharged through the cabinet drain into the quenching box.Humidity displacement is most effective when fan wheel is at high speed.
After the set humidity is reached, the clima valve motor will close again. Closed position is detected by the micro switch S4.
2. Mounting sequence
When mounting a new clima valve make sure the top end of the stainless steel pipe is positioned centrally under the top cover hole.
Secure this position with the spacer ring and vent cover.
The connection to the elbow pipe to the cabinet is done with the gasket 22.00.564 and 2x hose clamps. Please mount the gasket as shown here: facing top The combined clima valve and pipe (as a replacement for the silicone hose connection) is used in production since January 2008.
Units prior to this production date can be retrofitted with a stainless steel pipe (to replace the silicone hose) with conversion kit 87.00.325. This kit is shipped together each motor 40.00.274 and 40.00.276. (subject to change)
S4
- 9 - V03 EN, Trouble Shooting
3. Possible Clima valve problems
Unit does not reach steam temperature 100°C• Cooking time is longer than normal;Humidity valve is permanently leaking fresh air to the inside of the cabinet causing displacement of steam;To proof close the cabinet door to allow the clima valve to close. Run the unit on standard (high) speed in any mode. Remove the top vent cover on top of the unit.
Now place a light paper or a burning match (lighter) over the opening. Should the flame or paper be sucked downwards the fan wheel is sucking air through the clima valve.
Customer complains about inconsistent cooking results• Customer is producing steaks / ribs at high temperatures; this application might result in excessive carbon build up on the valve and damage the valve gasket;Please include a visual inspection of the clima valve in your scheduled maintenance routine.
Humidity control faulty • If the clima valve does not find its end position the SCC will show “Service 21”. Also after each software update the clima valve will initialise itself automatically. Should this initialisation run not be successful the flap time (in Basic Settings 1.2) might show a time like -0.2 sec. The normal running time of the clima valve is 18-21 sec. If the actual time indicated in Basic Settings 1.2 is not in that range, press “START” “FLAP” in order to re-initialise the clima valve.
CM:For your record purposes only: The safety valve pipe of the units Combi Master CM (without clima valve, but at the same position) have the following service part numbers: 22.00.578 CM 61 / 62 (pipe 108 mm) 22.00.579 CM 101 / 102 (pipe 238 mm) 22.00.580 CM 201 / 202 (pipe 228mm)
- 10 - V03 EN, Trouble Shooting
1. Standard operation
Cleanjet +Care is the cleaning and care function of SCC with index G produced since October 2008.
2 different chemicals are used for Cleanjet +Care: Cleaner tabs: part number 56.00.210 Bucket of 100 each Care tabs: part number 56.00.562 Bucket of 100 each tab packets
• The unit will prompt the user with a recommended Cleanjet +Care program. This program will be indicated in red color.
The needed amount of chemicals will be indicated too.• The cleaner tabs are taken out of the plastic wrapping and placed into the basket of the air baffle inside the
cabinet• The care tabs (1 tab portion is equivalent to the content of 1 bag = 6 pcs) are taken out of the plastic wrapping
and placed into the care container next to the hand shower.• Make sure the hinged racks and the air baffle in units 61-102 are placed properly in position and the trolley is
standing vertically inside the cabinet in units 201-202.• Close the cabinet door and the care container and start the recommended Cleanjet +Care program.
2. Operational sequence (in general) CleanJet:
• The unit will start with a functional self test. SC-Pump and the 3 solenoid valves (Y1-Y3-Y4) are operated for a short time to verify the functionality.
• The care solenoid will fill some water into the care container to start dissolving the care tabs.• The drain valve will close, the quenching solenoid will fill water into the quenching box and the Cleanjet pump
M6 pumps this water into the cabinet.• The water jet must hit level 3-4 from top of the hinged rack / trolley in both table and floor units.• The air flow inside the cabinet draws the water via the cleaner tabs in the air baffle basket onto the fan wheel.
Now the cleaner tabs start dissolving.• The sufficient water flow is detected by the speed of the fan motor. This speed will decrease when water hits
the fan. The decreasing motor speed is sent to the processor via BUS connection.• After some time the pump will stop and the drain valve will open to allow the dirty water to drain off.• Depending on the program selected the above sequence will repeat one or more times (functional self test is
not repeated).• After completion of the cleaning cycle the steam generator will be pumped off.
Care:
• The care container will be filled with water and pumped off into the empty steam generator. This is done 3 times.
• The drain valve will close;• The filling solenoid will fill the steam generator with fresh water up to level electrode;• Part of the care volume inside the steam generator is now pumped off into the quenching box with the SC pump
and topped up by moistening valve Y3• The filling solenoid will fill the steam generator with fresh water above the level electrode;
The care volume inside the steam generator is heated to 80°C• The Cleanjet pump M6 pumps the care volume of the quenching box through the cabinet to rinse it;• The drain valve will open;• The care container will be rinsed with water, at the same time the care pump will discharge the water from the • care container in to the steam generator and the SC pump will pump off the steam generator.The steam generator is filled, pumped off and refilled again.• Finally the cabinet is neutralized by steam•
CleanJet +Care
- 11 - V03 EN, Trouble Shooting
3. Possible CleanJet +Care problems
Unit develops excessive foam • The water hardness is too low for the amount of cleaner tablets used. If a water softener is installed, the supply water must be blended to minimum 5°dH, 9°f, 6°e, 90ppm, 5,2 gr/gal(US). Note: We strongly advise NOT to use sodium ion exchanger treatment systems (corrosion etc). To indicate less cleaner tabs switch unit to Softwater ON in Basic settings 26.
Timer is counting up • The fan motor detects the water flow rate during cleanjet. If the water jet from the cabinet ceiling does not hit level 3-4 on both table and floor model rack / trolley, the motor does not detect enough water flow and the quenching solenoid will refill the quenching box. This leads to timer counting up. Make sure no containers are left inside the cabinet, fix left rack properly in locating pins, trolley must be inside cabinet on floor units, align trolley vertically; Defective door gaskets can lead to water loss during cleanjet process resulting in the need to refill.
Service 25 • Water flow recognition by rpm drop of main fan motor doesn‘t work Possible reasons: - Water tap closed - Cleanjet Pump defective - Foreign particle in pumping pipe is blocking water flow - Foreign particle at pipe end diverts water jet direction; water must hit level 3-4 of the rack or floor unit trolley - Drain valve does not close properly - Check running time of drain valve in Basic Settings 1.2; Times t0 - t1 should be appr. 9 / 27 sec (1:3) If necessary reinitialise drain valve in Basic Settings 1.2.
Service 40 • Care pump does not supply enough care solution into steam generator - Care pump defective (check if pumping rate is sufficient, impeller damaged / blocked) - Hose from care pump to steam generator kinked;
Service 41 • At the beginning of Cleanjet+Care process the moistening solenoid Y3 is tested automatically. - Solenoid Y3 defective, error is detected by CDS sensor; Change triple solenoid valve
Service 42 • At the beginning of Cleanjet+Care process the care solenoid Y4 is tested automatically. - Solenoid Y4 defective, error is detected by CDS sensor; Change triple solenoid valve
Service 43 • During the testing of solenoids Y1,Y3 and Y4 the CDS sensor detected that at least 1 of the three solenoid valves does not close after de-activation - Change triple solenoid valve
Service 44 • During the water heating process in the steam generator at beginning of the Cleanjet+Care process the ther-mocouple B1 does not detect temperature rising. - Check B1, heating elements, SSR
Service 110 • SC pump did not work properly when care chemical was inside steam generator. - Change / repair SC Pump.
Service 120 • Level electrode does not detect water level after care chemical was pumped in and water was topped up. - Check Filling solenoid Y1 and level electrode - wiring and operation. Reset of errors 40-43 is done after repair and successfull completion of a CleanJet +Care program, rinse, program light, medium or strong; Reset of error 44, 110 and 120 after reapir and completion of abort program;
- 12 - V03 EN, Trouble Shooting
1. General function A solid state relay is an electronic circuit which acts as a relay. A 12V DC signal is used as control voltage for switching the working voltage of 200-277V AC Should a solid state relay fail because of a secondary side short circuit it will fail most likely in closed position causing the connected load to be permanent on.
2. SSR connection 12V DC control voltage is supplied from I/O pcb terminal X24. Terminal A1 / B1 is the shared 200 - 277V input for the load supply. The I/O pcb supplies either section (channel) A or section (channel) B. Both channels are never switched on at the same time! Depending which Section - A or B - is supplied with 12V DC the channel A1/B1 to A2 or A1/B1 to B2 is closed. A2 connects always to steam elements, B2 connects always to Hot Air elements.
3. Measuring SSR Solid state relay can NOT be tested with an Ohm meter! Solid state relay are either tested using a clamp meter or Volt meter! To test a SSR power must be supplied to your equipment. Open the cabinet door to avoid control voltage supply from the I/O pcb.
Testing with clamp meter (cabinet door is open): • Put your clamp meter around the wire to A1 / B1 of each SSR. Meter must read zero Amps at all times. Should you measure any current the SSR is damaged and must be replaced!
Testing with Volt meter (cabinet door is open): • Put your volt meter across A1 / B1 and A2 or B2 of each SSR. Meter must read your system voltage, i.e. 400V in case your system supply is 3NAC 400V. Should you measure less than your connected system voltage or even 0 Volt, the SSR is damaged and must be replaced!
Solid State Relay - SSR
Wor
king
vol
tage
(200
V - 2
40V,
380
V - 4
00V,
440
V an
d 48
0V)
A +
A -
Phototransistor
Light
A 1
A 2
LED
Sign
al w
ith lo
w
volta
ge (1
2V D
C)
ThyristorThyristor
Opt
ocou
pler
Rational Part.- No.:40.00.453P
Section A
Section B
+-+-
A1 / B1
A2
B2
12V DC
0V DC
0 Amp = OKRational Part.- No.:40.00.453P
Section A
Section B
+-+-
A1 / B1
A2
B2
Volt Volt
400V = OK400V = OKRational Part.- No.:
40.00.453P
Section A
Section B
+-+-
A1 / B1
A2
B2
- 13 - V03 EN, Trouble Shooting
4. Mounting of SSR When mounting the SSR please make sure: A stainless steel (silver) colour heat transfer foil is attached to the rear side of the SSR. Do not damage this foil during storage or mounting. Should the old SSR have been fixed with a red heat transfer foil, remove this prior to fixing the new SSR. The 2 fixing screws must be tightend adequately to ensure equal pressure of the SSR base foil to the sup-porting surface. Should the SSR be fixed on a perforated aluminum base (CPC units), clean the holes of the mounting base from any dirt and dust;
5. Typical SSR connections to heating elements NOTE: The violet wire (L3) is connected directly to the main contactor and is NOT switched by SSR! Below you find some samples of SSR circuits connecting to Steam elements (A2). Note: If only 1 SSR is switched on, the unit is operating on partial load as 1 element is out of circuit. 3NAC 400-480V 3AC 200-240V
A1/B1 B2
A2+-+-
A
B
A1/B1 - A2 Steam / DampfA1/B1 - B2 Hot Air / Heißluft
A1/B1 B2
A2+-+-
A
B
L3
L2
L1
PCB
12V DC0V DC
Violet
Orange
Black
B5
12V DC
0V DC
A1/B1 B2
A2+-+-
A
B
A1/B1 - A2 Steam / DampfA1/B1 - B2 Hot Air / Heißluft
A1/B1 B2
A2+-+-
A
B
L3
L2
L1
PCB
Orange
Black
B5
12V DC
0V DC
12V DC
0V DC
- 14 - V03 EN, Trouble Shooting
1. Standard operation
The SCC pcb 42.00.002 works together with the I/O pcb 42.00.064. Power supply for the processor and information flow is via the Bus cable from the I/O pcb to the main pcb. Connected to the main pcb is an external EEPROM which stores the unit specific data. This memory is copied on the main pcb. Data on the main pcb are updated once per hour to the external EEPROM. The operation of the PCB is done mainly by touch pad, which is stuck onto the display and connected by a flat green cable. The SRAM of the CPU is backed up by a battery. Should this battery be removed the SRAM will be reset. NOTE: In this case the only information back up is the external EEPROM. Should the EEPROM carry inconsistant data the unit will be out of function. In this case you must run the Soft-ware Repair program to bring the unit back to operation. All DIP switches of the pcb must be set to OFF during normal operation. To enter into service mode set DIP switch 1 to ON. To exit service mode set DIP switch 1 to OFF or switch unit off and on again. (For details on service mode please refer to the training manual.)
2. Operational sequence (in general) If the pcb is switched OFF the unit will automatically re-boot itself. As there is permanent power to the I/O pcb the necessary power for rebooting is coming via BUS cable from I/O pcb to main pcb. This booting process needs approx. 30 seconds. During this time the green LED is on and the red LED will blink once. If now the pcb is switched on the display comes up at once and the clima valve and the drain valve will turn once. If the pcb is switched OFF and immediately ON again the SCC display needs approximately 30 seconds to be operational again.
3. Software upgrade
Software upgrade can ONLY be done by using the Rational USB Software stick 87.00.010. Other type USB sticks are NOT capable to correspond with the pcb hard/software. Connect the USB stick to USB interface at bottom left hand corner of control panel. Make sure the USB stick is recognized by the pcb. (Press Funktion key followed by USB key)
SCC - Main Printed Circuit Board (PCB) 42.00.002
- 15 - V03 EN, Trouble Shooting
4. Possible PCB problems
PCB does not recognize USB Stick • Open control panel and connect USB stick directly to X54 using USB interface cable 40.00.470. Should the USB stick be recognized now replace interface cable.
During software upgrade there is a 1 sec. on - off relais sound on the pcb; Software upgrade does not work • The USB stick is not formatted in FAT (16) mode. Safe the data on your computer and reformat USB stick to FAT (16)
Touch pad does not react • Disconnect flat green cable from terminal X102. Wipe end of cable clean. Reinsert into terminal X102; Should the touch pad still not respond change pcb; Experienced technicians can change this touch pad separately (SP number: 42.00.067). On PCBs from July 2009 this X102 connection is sealed with white silicone. Remove this silicone before reinserting the new touch pad connection.
PCB display shows VFD after software upgrade • Switch unit OFF and ON again and repeat software upgrade. Should re flashing software not help: PCB basic software is corrupt, change PCB
PCB only shows „ON-PLEASE WAIT“ after software upgrade; • There has been a communication interrupt during software upgrade; switch unit OFF and ON again and repeat Software upgrade.
PCB does not function • Check LED indication on pcb; green LED must be always on when unit is on. red LED must only blink once while rebooting and must be off all other times. yellow LED must be off at all times.
PCB shows water marking from condensation • - Check air filter, - Avoid steam intake from drain installation, - Make sure the vent pipe is properly installed to top cover and no water can sip in, - All connections of heating elements, sensors and motor shaft are steam tight, - Door gaskets are not damaged, - Interior light seal is ok, - Unit is not installed in cold rooms where humidity condensates on cold surfaces.
PCB looses programs • SRAM backup battery has low power; replace by TR 2032 3V Li cell.
Only SCC key, hot air and steam key are illuminated, display is dark, but touch pad is reacting • Check 2,5-0-2,5V supply from transformer to PCB terminal X110
PCB display shows: “Change Air filter” or “Service 29” • Cooling of left side panel is insufficient. Change air filter is shown when PCB is 75°C hot, Service 29 is shown when PCB is 85°C hot. Check cooling fan, external heat sources, install left side heat shield if necessary;
- 16 - V03 EN, Trouble Shooting
1. Software upgrade:
Software upgrade can ONLY be done using the Rational USB Software stick 87.00.010. This USB stick is formated in FAT. Other type of USB sticks are NOT capable to correspond with the pcb hard/software. Connect the USB stick to USB interface at bottom left hand corner of control panel. Make sure the USB stick is recognized by the pcb. (Press Function key followed by USB key) When the stick is recognised swith the unit OFF and ON again to start the update. After successful update check the software version and the serial number. The blue colour USB stick can be used on units with any software version. The grey colour USB stick is only recognised by units which have at least software version 01_07_11 (since May 2006). Units with software prior to this must be upgraded using the blue USB stick. If the USB stick is not recognised connect the USB stick directly to X54 using the USB interface cable 40.00.470 and replace original interface cable if needed.
2. Software download onto the USB stick On the original Rational USB Software stick 87.00.010 you find a file “update.exe”. Connect your computer to the internet, connect the USB stick and double click the file “update.exe” in the explorer. The integrated soft-ware will automatically connect to the Rational server. Press “Check for updates”. You will be prompted if a new firmware is detected. Follow the online instructions.
3. Software structure The standard Rational software has the following structure: Make sure ONLY the software files are existing on your software update USB stick. Make sure the files are not zipped on your USB stick Do NOT store other data on this memory stick!
4. Software structure chain account / OEM Software for chain accounts has the following structure: Note: The folder script must stay as a folder on the USB stick. Make sure there is no zip file on the USB stick. If the entire software package is sent to you as a zip file, unpack the content onto your USB stick. The chain software can not be updated on the web. There is no “update.exe” file existing. New software versions are ONLY available directly from Rational.
SCC - Software
- 17 - V03 EN, Trouble Shooting
5. Additional software information Software can only be upgraded to a newer version.
Standard Rational software: • During software update the following display will be shown in sequence: - All 4 windows: UPDATE (if shown only for a few seconds the software on the pcb is latest version already) - Window 3: ON please wait; - SCC display will show for 1 second; - Window 3: Please don’t touch (during this time the drain valve and clima valve will initialise) - Unit will switch OFF and ON again automatically; - UPDATE will show again; - ON please wait; - Unit will switch OFF and ON again automatically; - ON please wait; - After re booting of the pcb the SCC display will show and the steam generator will be automatically flushed; (disconnect the USB stick now)
Chain account software: • During software update the following display will be shown in sequence: - All 4 windows: UPDATE - please wait; - All 4 windows: script (during this time the drain valve and clima valve will initialise) - unplug stick (disconnect the USB stick now) - ON please wait; - Units will switch OFF and ON again automatically; - ON please wait; After re booting of the pcb is finished the chain display will show;
Software update does not delete any information which was entered by the customer before. • All information as entered in Basic Setting will remain valid;
If during software upgrade VFD is shown, leave the USB stick connected and switch the unit OFF and ON • again. If VFD remains on the display, the internal software structure on the PCB is corrupt and the PCB must be changed.
Unit without function after SW upgrade • - External EEPROM corrupt, contact Rational for EEPROM repair
Should there be a 1 sec. on - off relais sound on the pcb during software upgrade and Software upgrade • does not work: The USB stick is not formatted in FAT (16) mode. Safe the data on your computer and reformat USB stick to FAT (16);
- 18 - V03 EN, Trouble Shooting
1. Bus layout The main electronic components are connected by a bus cable. This bus connects:
I/O PCB• Main PCB• Main fan motor (201-202 units: 2x, top motor with jumper)• Ignition box on gas units (201-202 units: 2x, bottom ignition box with jumper)• Ultravent (optional) •
Table unit Floor unit Motor bottom Motor Top Main pcb I/O pcb
Electric unit Gas unit ignition top ignition bottom
2. Sequence of connection (RJ 45 terminal) One bus cable connects the I/O PCB to the main pcb. The second bus connects from the I/O pcb to the main fan motor, on floor units from the bottom fan motor to the top fan motor, on gas units it continues to the ignition boxes. The top fan motor needs a jumper on the right pair of pins for identification: On gas units the bottom ignition box needs a jumper as identification (ref. oval insert) I/O pcb, motor and ignition box have 2 bus terminals each. Both connections are identical and bus connection can be done to either terminal. The sequence of connection can be chosen freely, i.e. the bus cable can also be routed from the I/O pcb to the top motor first before the bottom motor or on gas units it may be connected to the ignition box first.
Bus Control
T1
K1:L1F2: N
LED GrLED Ye
X 24.1
X 25.1
X 26.1
X 27.1
X 15.1
X 17.1
X 16.1
X 23.1
X 75
X 20.1
X 19.1
X 18.1
ON
1234
X21
BUS BUS
X 3X 4
X14
X12
X11
X1
X8X7
X110X2
42.00.002 REV 802 Operator PCB
CPU
X54X52
X102
X10
X50
X5 X2 X6 X4 X3
V10 V9 V8
X51
X7 X8
X103
Battery
CPU
230V
12V AC
Jumper
1 2 4
8 16
- 19 - V03 EN, Trouble Shooting
3. General function The transformer supplies 12VAC power to the I/O pcb. The power supply for the processor on the main pcb is generated on the I/O pcb and sent via bus from the I/O pcb to the main pcb. All information from the main PCB to the I/O pcb, fan motor(s) and ignition box(es) is send via this bus system. As each component has its own unique address, the information can be routed correctly. Address of Components: 1 - I/O pcb: 2 - Fan motor (table unit), Fan motor bottom (floor unit) 4 - Fan motor top (floor unit); NOTE: Jumper must be set! 8 - Ignition box (Table unit), Ignition box top (floor unit) 16 - Ignition box bottom (floor unit); NOTE: Jumper must be set!
4. Fault finding Error code 34.1 Bus I/O pcb; change point of RJ45 connection Error code 34.2 Bus fan motor bottom; Check if green LED on fan motor is on (100-240V connected to motor?; check main contactor); Connect bus to second terminal Error code 34.3 Bus I/O pcb AND fan motor bottom; Check if green LED on fan motor is on (100-240V connected to motor?; check main contactor); Connect bus to second terminal Check all bus connections; Error code 34.4 Bus fan motor top; Check all bus connections, motor LED and main contactor Error code 34.5 (1+4) Bus I/O pcb AND Check all bus connections, motor LED and main contactor fan motor top of the floor unit;
Error code 34.6 (2+4) Bus at both fan motor of the floor unit; Check all bus connections, motor LED and main contactor Error code 34.7 (1+2+4) etc. Error code 34.8 Ignition box table unit Check all bus connections Error code 34.9 (1+8) etc. etc
When any error code is present, try to connect the bus cable to the second bus terminal of the component. • Should the error code change, the individual bus connection is defective;
When any error code is present, try to change the bus cable (40.00.472) in between the components to • locate defective cables and exclude any open circuit.
NOTE: Do not allow the bus cable to touch ANY hot surface, i.e. Steam heating elements. The insulation of the single wire strands inside the black bus cable might melt and wires can short circuit.
Attention: A short circuit on the bus can damaged the main pcb, I/O pcb, fan motor and ignition box at the same time!
- 20 - V03 EN, Trouble Shooting
Gas
1. Standard operation
NOTE: The gas components and ignition sequence are identical for SCC and CM units. A blower motor starts on “Start speed” and purges possible remaining gas from the gas heat exchanger with fresh air. Ignition starts for 5 seconds. During this time the gas valve will open. If the flame establishes and is recognised by the ignition and monitoring electrode and the ignition box, the gas blower speed may rev up to MAX rpm or MIN rpm depending on the amount of energy needed. Flame current is visible in Function test 14-16 and should be between 5,0 and 5,75μA. Should the flame recognition fail (below 3,5μA) , the heat exchanger will be purged again and the ignition se-quence will repeat. After 5 unsuccessful ignition restarts the unit will show RESET (CM - reS)
2. Component / connection identification Gas valve: 1. Gas supply pipe 2. Test nozzle for dynamic input pressure 3a / 3b. Electric solenoid 4. Pressure compensation hose 5. CO2 screw 6. Output pressure nozzle (not used in practice) 7. Valve outlet to blower premix chamber Gas blower: 1. Gas supply pipe 2. Gas valve 3. Ignition box 4. Pressure compensation hose 5. Air supply 6. Whirlwind (stationary) 7. Blower motor 8. Blower impeller housing 9. Discharge of gas / air mix to heat exchanger 10. Burner
Make sure the gas compensation hose (hot air and steam) is not kinked and is properly fixed in its position.
3. Media flow
Blower (7) and gas valve (2) are controlled by the ignition box (3). Blower (7) pulls air through air supply (5) and purges heat exchanger. Now ignition box (3) starts ignition at the burner head and opens gas valve (2). The pulled air is brought into rotation and mixed with the supplied gas in the stationary whirlwind disc. The fully premixed gas / air mixture is discharged through opening (9) into the burner.
2 3a 3b 4 5
1 7
6- +
-+
1 2
4
3
5
6
7
8
9 6
6
7, 8
- 21 - V03 EN, Trouble Shooting
4. Flue gas analysis Flue gas analysis is only done in „Function Test“. SCC: FT 14: Steam, FT 15: Hot air top, FT 16: Hot air bottom Adjustment of CO2 with the CO2 screw on the gas valve is only done in FT 14 in max rpm Steam, FT 15 in max rpm hot air top and FT 16 in max rpm hot air bottom, In the respective MIN rpm the CO2 is only checked for correct value, but NOT adjusted! CM: F 19-21: Steam, F22-24: Hot air top, F25-27: Hot air bottom (ref. CM module page 23) Adjustment of CO2 with the CO2 screw on the gas valve is only done in F 21 (max rpm Steam), F24 (max rpm Hot air top), F 27 (max rpm Hot air bottom) CO2 Screw: Turning clockwise decreases the CO2 value, turning anti clockwise increases the CO2 value. Adjust the value always from low to high!
5. Possible gas problems
Unit shows reset
Check if gas supply is open1. Dynamic gas pressure has to be measured with all other gas consumers on high flame.2. Gas supply pipe in the kitchen must cater for combined gas load of all gas consuming appliances, minimum 3. gas diameter for SCC / CM is 3/4“.If reset only happens in the morning when unit is cold: check flue gas analysis. CO4. 2 Values in MAX rpm might be too low, air gas mixture is too lean; adjust if necessary;If reset only happens during cooking when unit is warm: check flue gas analysis. CO5. 2 Values in MAX and MIN rpm might be too low, air gas mixture is too lean; if CO2 in MAX and in MIN rpm are 0.5% below standard set value, burner surface might be blocked by foreign particles. (Gas error code 19, 29, 22, 32) Clean burner head with compressed air from outside to inside or wash in dishwasher and blow dry after that (refer to TI 03/2007). Also clean the flexible air supply hoses from any dirt and dust / fat particles. After rebuilding burner flue gas analysis must be performed to confirm proper burning and adjustment must be done if needed. Should reset happen more than 3x a year despite having cleaned the burner, install external supply air filter. Make sure no source of dust and fat is located next to the fresh air intake of the unit.Check flue ducting inside the unit and inside ventilation hood. 6.
Unit makes popping sound when startingInstall gas valve with date stamp 0848 or later (applies to hot air gas valve only)1. Check hot air ignition electrode. Replace by electrode with non-gloss finish.2. Make sure no welding spots are directly under the ignition electrode location. Change burner if needed. 3.
Unit makes growling / whistling sound when in operationPlease check if the correct type of gas is set in Basic Settings 2. Check gas type with delivery note / invoice 1. of local gas supply company.Fresh air supply for burner is inadequate. Air supply can be altered by freeing the existing holes in the black 2. whirl wind housing from dust / fat particlesMake sure the compensation hose is not kinked and located on the black stud of the whirl wind housing, 3. Do NOT connect to the grey colour stud.
External exhaust pipes shall only be connected to the original draft diverter ex factory. Make sure the is sufficient fresh air supply in the kitchen and no negative pressure is existing (open kitchen door without air resistance.
If any gas error code other than 19, 29, 22, 32 is shown in gas error history frequently: refer to Training manual page: Download Service Data / Gas Error List
- 22 - V03 EN, Trouble Shooting
After initial installation of a SCC the „Selftest“ program will start. During „Selftest“ the hu-midity values of the actual installation altitude are evaluated. Some basic conditions apply to start „Selftest“:
Selftest is displayed but Start key does not show
Selftest
Initialization of ball valve and/or humidity flap is not
yet finished
Thermocouple B1, B2 or B4 is too hot (Temperature must
be below 40°C/104°F)Door contact not closed
Wait until initialization is finished Cool down unit using
function test Adjust door contact
Selftest and lack of water is always shown when the unit
is switched on
During the first selftest lack of water was recognised and
is still existing.
Eliminate lack of water
During selftest timer counts down to 4 minutes and then
changes to 12 minutes
Calibration data of cold and/or wet unit are out of the acceptable range. An additional calibration at combination mode is started.
Check components of the humidity control (P1, B4, Motor) and additionally
check humidity flap.
1
2 3
- 23 - V03 EN, Trouble Shooting
Service 10 (SC Pump)
Level electrode of the steam generator did not recognise a reduction of the water level during last SC-Automatic
Indication Service 10
Activate function test
Select step 8SC Pump M4
and touch „Start“ key
Check pump for scale depo-sits or other dirt, that blocks
the impeller
Clean housing of the pump, descale steam generator
and /or change pump
Short circuit level electrode or check drain system and quen-
ching box for dirt,clean if necessary
Check cable, connector and pump. Change defective part
Change auxiliary contact or contactor
Change I/O-pcb
Change fuse Check cable and pump for short
circuit
YES
YES
YES
NO
NO
NO
YES
NO
Pump active, water is pumped off
230V output at I/O-pcb X18 1/2 during function
test?
Auxiliary contact 13/14 of contactor K1 ok?
Fuses F6/F6.1 (on I/O pcb) ok?
- 24 - V03 EN, Trouble Shooting
Service 11 (CDS Sensor)
Actual measured filling volume above reference volume of steam generator
Indication Service 11
Eliminate leak
NO
NO
YES
YES
Water supply from CDS to steam genera-
tor leaking ?
Check valve in the water supply line to
the steam generator.Valve working correctly?
Change valve
Start volume measuring by activating pumping function, open cabinet door, touch function-followed by service - and finally key
for emptying steam generator
Level electrode clean, cable and con-
nector ok ?Clean electrode,
change defective part
YES
NO
- 25 - V03 EN, Trouble Shooting
Service 25 (Cleanjet Pump)
CleanJet does not deliver enough water to the fan wheel of the motor.Typical indication: The running time of the program will be exceeded.Check correct position of left rack and / or floor unit trolley!
Indication Service 25
Check water filter, pressure, supply line.
NO
YES
Water supply sufficient?
Does the water jet hit the 3rd or 4th left rack
inside the cabinet?
Check correct positioning of left rack, straight alignment of floor unit trolley
NO
NO
YES
YES
NO
Is cabinet door leak tight?
Check door gasket and trolley gasket (only floor models).Check door for correct adjustment
Output voltage of I/O pcb X18 3/4 present?
Output voltage of I/O pcb X19/5 present?
Check ball valve and change if necessary
Check pump, cable and con-nector, change defective part
Change fuse of I/O pcb or pcb.
YES
YES
Activate CleanJet-Pump (M6) in the
function test. Is pump running?
Activate solenoid valve quenching (Y2) in
the function test. Function ok?
Program was finished completely?
(enough water is coming out of the nozzle, fan mo-
tor reduces speed)
CleanJet-Pump and corresponding water supply lines leak tight and
pipes clean?
Remove all grids and con-tainers from interior cabinet,
Install air baffle correctly.Start a CleanJet-program.
Failure appeared because of miss handling. Inform custo-
mer of correct handling.
Change fuse of I/O pcb or pcb.
Test valve, cable and connec-tor, if any part is defective
change it. Check quenching box and nozzle for scale,
descale if necessary
Eliminate leaks and/or dirt.
NO
YES
NO
NO
NO
NO
YES
YES
- 26 - V03 EN, Trouble Shooting
Service 26 (Drain Valve)
Micro switch ball valve in permanent closed position.Unit out of order
Indication Service 26
Activate ball valve in the func-tion test.
NOYESOutput voltage at
I/O pcb X25 7/8 (12V DC) present? Change I/O pcb
Check motor ball valve, micro switch, cable, connector. Com-
plete ball valve unit must be changed.
NO
Service 27 (Drain Valve)
Micro switch ball valve in permanent open position.CleanJet can not be used
Indication Service 27
Separate unit from mains (switching off and on with
main switch is not enough). Af-ter approx. 5 seconds connect
unit to mains .
YES
YES
Is Service 27 deleted?Start a CleanJet-program and
check for correct function
Change I/O pcb
NO
Output voltage at I/O pcb X25 7/8 (12V DC)
present?
Ball valve blocked by dirt.Motor of ball valve, micro
switch, cable and/or connec-tor defective. Change unit if
necessary
Activate ball valve with the function test
NO
Should Service 27 appear more often and I/O-pcb with revision status 402 respec. 403 is installed, change I/O-pcb
- 27 - V03 EN, Trouble Shooting
Service 34 (Bus)
Bus failure - Indication of the faulty knot with the following code (combination of different faults possible):- 1: I/O pcb- 2: Bottom motor- 4: Top motor- 8: Top ignition box - 16: Bottom ignition box
Indication Service 34.1 up to 34.31
Disconnect and reconnect bus cable of the indicated faulty
part.
YESIs Service 34.1 indica-ted and the yellow LED on
the I/O pcb is flashing?
Check I/O pcb.Change it if necessary
Change corresponding part
NO
Are all dip switches „off“?
Set dip switches to off and disconnect unit from mains.
Switching unit off and on is not enough
Failure eliminated? Carry out test run
Carry out test runChange bus cable Failure eliminated?
NO
YES
NO
YESNO
YES
NO
Service 32 (only gas unit)
Internal fault of ignition boxService 32.1 Table models and floor models upper box Service 32.2 Floor models lower box
Indication Service 32.1 or 32.2
Switch unit off and on again
YESIs unit working again?
Change correspondingignition box
Carry out test run
If the unit was switched off and on again 3 times and the ignition box did not reset, then
„No Function“ is shown
NO
- 28 - V03 EN, Trouble Shooting
Service 40 (Care Pump)
Care Pumpe defective respectively does not pump enough care solution into steam generator
Display Service 40
NO
YES
YES
Operate Care Pumpe in function test 10.1
Check 230V at plug from I/O PCB to care
pump.
Reset error by successful comple-tion of RinseProgram
Change Care pump
NO
Check Voltage input at I/O pcb X21
YES
Check voltage on auxilliary contact K1
NO
Logic error; Check plugs and cables or
change I/O pcb
YES Check if pump from care pump is kinked
- 29 - V03 EN, Trouble Shooting
Service 41 (Y3 Moistening solenoid)
Solenoid valve Y3 defective of moistening nozzle blocked;CDS does not send any pulses; First time display: Descale moistening nozzle, Second time display: Servcie 41
Display Service 41
NO
YES
Operate Solenoid val-ve Y3 in function test 10
In function test 10 check voltage 230V
at coil solenoid valve Y3
Logic error; Check plugs and cables
or change I/O pcb
Check Voltage input at I/O pcb X21 YES
Check voltage on auxilliary contact K1
NO
Moistening nozzle blockedYES
Descale nozzle
NO
NO
Change triple solenoid 50.01,.050
Solenoid valve opens
YES
Check CDS sensorYES
Reset error by successful comple-tion of RinseProgram
- 30 - V03 EN, Trouble Shooting
Service 42 (Y4 Care solenoid)
Solenoid valve Y4 defective or feeding hose to care container blocked CDS does not send any pulses
Display Service 42
NO
NO
YES
Operate Solenoid valve Y4 in function test
10.1
In function test 10.1 check voltage 230V
at coil solenoid valve Y4
Logic error; Check plugs and cables or
change I/O pcb
Change triple solenoid 50.01,.050
Solenoid valve opens
Check Voltage input at I/O pcb X21
YES
Check voltage on auxilliary contact K1
NOYES
Check CDS sensorYES
Reset error by successful comple-tion of RinseProgram
- 31 - V03 EN, Trouble Shooting
Service 43 (triple solenoid valve)
CDS Sensor sends permanent pulses during start of Care process
Display Service 43
YES
Deselect all modes
Water drains from unit drain pipe?
Change triple solenoid 50.01,.050
YES
Display Service 44
Measure current draw in function test 2
Current draw accor-ding to spec?
In function test 2 check thermocouple B5 for
function
YES
Service 44 (Steam Heating)
No steam heating during Care Phase
NO Check heating elements / SSR for function
Reset error by successful comple-tion of Rinse Program
Reset error by successful comple-tion of Abort Program
- 32 - V03 EN, Trouble Shooting
Service 100 (Main Contactor)
Reason: Main contactor didn‘t disengage during last switch off or main switch on pcb defective
Display Service 100
Change pcbVoltage on coil K1 ?
NO
YES
Switch unit off by I/O switch (voltage present on main contac-
tor secondary side?)
Change main contactor
Service 110 (SC-Pump)
SC pump not functioning during the time when there is care solution inside the steam generator; Care solution could not be pumped off; unit without function;
Follow error tree Service 10!
Display Service 110
Switch unit OFF with I/O switch on pcb;1. Remove control fuse (F1-F2) for a short while and reset again; 2. Let unit stand idle for 2 minutes without switching it ON;3. Only now switch unit ON with I/O switch;4.
NO
Reset error by successful completion of Abort Program
- 33 - V03 EN, Trouble Shooting
Service 120 (Y1 Filling solenoid, Level electrode)
After Filling steam generator via M12 the steam generator does not fill with water via the filling solenoid.Detection: level electrode does not get contact with water; Steam generator can not be flushed; unit is without function.
Display Service 120
NO
YES
YES
Test solenoid valve Y1 in Function test 7
Logic errorCheck plugs, cable and I/O
pcb
Check function, wiring, con-nection at level electrode
Solenoid valve opens
Check power sup-ply at I/O pcb X21
YES
Check Power supply at auxilliary contact k1
NO
YES
Open water tap
Reset error by successful completion of Abort Program
- 34 - V03 EN, Trouble Shooting
No display - safety chain - SCC
No display
Check main fuse of the power supply and earth leakage breaker
NO
NO
YES
YES
NO
Power supply ok?
Fuse F1/F2 and contac-tor K1 ok?
Press dry up protector of steam generator
Replace defective part and find reason for tripping
DIsplay on?
Display on?
Is main switch S1 wor-king?
Input voltage at control transformer T1 present
Is green LED on I/O pcb on
Is green LED on pro-cessor pcb on
Input voltage at con-nector X1 (2,5V) of control pcb present
Ribbon cable between operator and processor pcb connected correctly?
Check cable and connectionCheck/change processor pcb
Check control transformer cable and connector
Check bus cable between I/O and processor pcb (X51)Check processor pcb
Check control transformer cable and connector
Check steam heating elements, SSR, water supply, scale build up
Press safety thermostat of interior cabinet
Change safety thermostat.Check SSR, hot air heating element
12 V supply at X14 pin 3 and 4 present
Check I/O pcb Check cable and connector
Check switch,Change pcb if necessary
YES
YES
NO
NO
YES
NO
YES
NO
NO
YES
YES
NO
YES
NO
NO
YES
YES
- 35 - V03 EN, Trouble Shooting
No or too low steam production - SCC
Steam above 110°C is not visible, it does not condensate on the cabinet door!
Humid cooking mode is selected but no/not enough steam is visible
Check:- Pressure sensor P1;- Hoses of pressure sensor P1;- Thermocouple humidity control B4- Thermocouple quenching B2For testing refer to training manual
Check hot air element/SSR in diagnostic test.Measure current draw with clamp meter
Check solenoid valve filling Y1 for proper function
YES
Close door, check door contact switch
NO
Check level electrode S2 with diagnostic program (item 13) indication must be „ 1 „?
Indication Service 14?or sensor steam generator defect?
Check level electrode,osmosis water supply (check water quality), Check sensor steam generator with dia-gnostic program (655/900°C)
NO
YES
YES
Service 21: Check flap motor M3 and end switch S4Service 28: Temperature SG>180°C, Check scale level
Check steam heating/SSR with diagnostic program.Measure current withclamp meter
Check with diagnostic program step 15Cooking mode steamTemp. 98 - 103°C humidity > 70%Temp. 104 -130°C humidity > 85%
Check quenching system.Calibrate unit as described in trai-ning manual
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Clean filters of the water supply
NO
Door closed ?
Is the water tap symbol flashing on the display?
Is water tap open?Is hand shower working?
Has steam production failed completely
Press function, service and finally mod key.
Emergency humidity control active
Indication Service 21or Service 28
Steam heating elements ok?
Humidity value ok?
- 36 - V03 EN, Trouble Shooting
Service 12 / Indication descaling - SCC
Steam generator scaled up; CDS display shows 9 red bars
Indication „Descaling ofsteam generator necessary“
YESIs additionally Service 12 shown?
CDS-Sensor does not create pulsesCheck CDS-Sensor, cable andconnector.
Touch function key:degree of scale is shown
Only 2 to 3 red bars are shown on ?
Repeat descaling procedure
NO
NO
Activate and run descaling pro-gram. At the end of the program the new filling volume is genera-ted automatically.
Was the descaling procedure sufficient?
(Visual check via level elec-trode)
Unit ready for workYES
NOWater supply not sufficient:- Water pressure too low (below 50 kPa)- Water filter soiled- CDS Sensor soiled- Water intake pipe of steam
generator scaled up (Pipe must be descaled separa-
tely)
YESNO
- 37 - V03 EN, Trouble Shooting
Buzzer sounds - SCC
Reason: Any thermocouple is defectiveDifferent buzzer intervals depending which thermocouple is defective
Buzzer sounds for 30 seconds after fault identification and every time unit is switched on
YESIndication Service 20?Interior cabinet sensor B1 defective unit out of order
Change defective thermocouple
NO
NO
Check which ther-mocouple shows actual
values > 654°C,This indicates, that the corre-
sponding „Thermocouple is broken“
Check connector of the thermo-couple for sufficient contact
NO
IndicationCT probe defect?
IndicationService 31.1 up to 31.6?
- More than 3 measuring points of the probe are defective.
- SCC program‘s and manual cooking program‘s with core temperature can not be used
- Less than 3 measuring points of the probe are defective
- SCC program‘s and manual cooking program‘s with core temperature are running on emergency control
Activate diagnostic program Step 1 - 11
YES
NO
YES
YES
Buzzer frequency by failure of thermocouple (counting in 5 sec.)
B1 12 in 5 sec.B2 6 in 5 sec.B4 5 in 5 sec.B5 8 in 5 sec.Core temperature sensor 20 in 5 sec.
- 38 - V03 EN, Trouble Shooting
Change polarity (Gas units) - SCC
For flame monitoring mains must be connected with correct polarity
Unit showsChange polarity
Check power connection for correct polarity, colour code:
Life = brown or blackNeutral = blue
„RESET“ indication (Gas units) - SCCReason:Flame monitoring does not work after ignition
Indication „RESET“
NODoes the connected gas type comply with the gas type
on the name plate?
Open gas supplySwitch on ventilation system
Convert unit to connected gas type.
Follow instruction of training manual
Attention: Carry out flue gas analysis
Reset was carried out several times? Service 33 comes up if reset was carried out 4 times.Service 33 can be deleted by switching unit off and on again (function implemented as of soft-ware version 01_07_08)
YES
Gas supply openExternal Ventilation system on?
- Cross section of the gas supply pipe is too small- Flow gas pressure is too
Reset only in case all gas appliances of the kitchen are switched on ?
Install sufficient supply pipe,and/or increase gas pressure
Check ignition-electrode, -cable, -box and gas valve
YES
NO
YES
NO
- 39 - V03 EN, Trouble Shooting
Indication „E13“ (SC-Automatic) - CM
Level electrode of the steam generator did not recognise a reduction of the water level during last SC-automatc
Indication E13
Short cicuit electrode or check drain system and quenching box fpr dirt, clean if necessary
NO
NO
YES
YES
Is pump active and water is pumped out?
230V output at connec-tor X18 1/2 during funtion test
present?
Check cable, connector and pump. Change faulty part.
Clean housing of the pump, descale steam generator and/or change pump.
Aux. contact 13/14 of contactor K1 OK? Change aux. contact or contactor
YES
NO
Activate function test
Select step F14 SC Pump M4 by pressing timer key, activate func-tion with core temp. key.
Check pump for scale deposits or other dir, thet blocks the impeller
YES
Fuse F2 on pcb OK? NO Change pcb
Change fuse, check cable anf pump for short citcuit
- 40 - V03 EN, Trouble Shooting
No function- safety circuit - CM
No function
Check main fuse of the power supply and earth leakage breaker
NO
NO
YES
NO
Power supply OK?
Fuses F1/F2and contactor K1 OK?
Press dry up protector of steam generator
Replace defective part and find reason for tripping
Is unit on now?
Is unit on now?
Input voltage at connec-tor X7 present?
Main switch S1 on pcb OK?
Fuse F1 on pcb OK?Change pcb Change fuse
Check switch, if necessary chan-ge pcb
Check steam heating elements, SSR, water supply, scale built up
Press safety thermostat of interior cabinet
Check SSR, hot air heating element
Change cable and connector
YES
YES
NO
NO
YES
NO
YES
NOYES
- 41 - V03 EN, Trouble Shooting
No Steam - CM
Attention: Steam above 110°C is not visible, it does not condensate on the cabinet door!
Wet cooking mode is activated but no steam is visible
E16: Temperature DG>180°CCheck for scale build upE17: Temperature DG<-5°C: warm up the cabinet with warm water
Check solenoid valve filling Y1
YES
Close dooe and / or check door contact switch
NO
Check level electrode S2 with diag-mostic program (dP8) Indication „1“? Unit connected to treated water?
NO
YES
YES
E6: Check sensor steamgenerator B5 with diagnostic program (999°C)
E4: Check quenching sensor B2 with diagnostic program (999°C)
Change sensor
Check steam heating elements/SSR with diagnostic program. Mes-sure current with clamp meter
YES
YES
NO
NO
Door closed ?
Indication H2O OPEN?
Water tap open?Sediment filter at water con-
nection to unit clean?
Indication E6 or E4?
Indication E16 or E17 ?
NO Open water tap, clean sediment filter
- 42 - V03 EN, Trouble Shooting
CHnG POL (change polarity) - CM
For flame monitoringL1 mains must be connected with correct polarity
Indication„CHnG POL“
Check power connection for cor-rect polarity, colour code:Live = brown or blackNeutral = blue
Indication „rES“ (=reset) - CM
Reason:No flame sensing after ignition
Indication „rES“
NODoes the connected gas type comply with the gas type
on the name plate ?
Open gas supplySwitch on ventilation
- Convert unit to connected gas type.
- Follow instruction of training manual
Attention: Carry out flue gas analysis
Press reset key, if after several attempts unit still is not working
YES
Gas supply open?External Ventilation system?
- Cross section of the das sup-ply pipe is to small
- Flow gas pressure is to low
Reset only in case all gas appliances of the kitchen are switched on??
Install sufficient supply pipe, increase gas pressure
Check ignition-electrode, -cable, -box and gas valve.
YES
NO
YES
NO
- 43 - V03 EN, Trouble Shooting
Buzzer sounds - CM
Reason of fault: Any thermocouple is faulty
Buzzer sounds after fault identifi-cation and after switching on the unit.
YESIndication E7?Thermo couple of pcb faulty, change pcb
NO
Check connector of thermocouple for sufficient contact.Change faulty thermocouple.
Indication E3 or E4 or E5 or E6?
E3: Interior cabinet sensor B1 Unit out of orderE4: Quenching sensor B2E5: Core temp. sensor B3E6: Steam generator sensor B5 Change faulty sensor
NO
YES
- 44 - V03 EN, Trouble Shooting
- 45 - V03 EN, Trouble Shooting
Rat
ion
al S
CC
-Lin
ie:
Leis
tun
gst
eil
Rat
ion
al S
CC
-Lin
e:
Po
wer
cir
cuit
Rat
ion
al L
inea
SC
C:
Cir
cuit
o d
i alim
enta
zio
ne
Rat
ion
al S
CC
-Lin
e:
Cir
cuit
de
pu
issa
nce
Rat
ion
al L
inea
SC
C:
Cir
cuit
o d
e la
en
erg
ía
K1
BN BU
M5
M 1 ~A2
A1
N/O
1 2
BK
3 4
OG
5 6
VT
W17
A2 Ope
rato
r PC
B
K1 N/O
14 13
X7
11
GY RD BN
F31 2
F41 2
33
Ein/
Aus
Sch
alte
rS1
K1A
1
A222
RD
GY BN BU
W10
WH
WH
WH
X10 11
X46
11
T1St
euer
traf
oC
ontr
oltr
ansf
orm
er
2,5V
0V
2,5V
11,5V
11,5V
12V
12V
250V
240V
230V
220V
208V
200V
0V
22 22
33 33
A1
I/O
-PC
B
F5 1,6A
.
W13
WH
WH
WH
WH
X14 11 11
22 22
33 33
44
X56
44
11
F6.1
2AT .
X21 11
22
F6 2AT
W0
BK
BN
BK
BU
PE
YE/GN YE/GN
BKF1 6,
3A F2 6,3A
Z1
L1 L2 L3 N PE
X57
7766
5544
3322
VT
R1
3x3k
W9k
W D
1/D
2
1 2
V1
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
3 4
5 6
X33
1122 R2
3x3k
W9k
W D
1/D
2
1 23
D1
H
L2
4
3 4
5 6
V2
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
R4
6x3k
W18
kW H
L1/H
L2
1 2
X34
1122
3 4
3
D2
H
L1
5 64
7 8
9 10
11 12
BK OG VT BU
YE/G
N
3N
AC
40
0 -
41
5V
M1
M ~F2
0
6,3A .
F21
6,3A .
33 22
X2211
BN
77 66 55 44 33 22BU
T4
~-
12V
0V
0V200V
208V
220V
230V
240V
250V
X5911
22
X6711
M5
M2
01
-20
2
Wiring diagram Power Circuit
- 46 - V03 EN, Trouble Shooting
Rat
ion
al S
CC
-Lin
ie:
Leis
tun
gst
eil
Rat
ion
al S
CC
-Lin
e:
Pow
er c
ircu
itR
atio
nal
Lin
ea S
CC
: C
ircu
ito
di a
limen
tazi
on
eR
atio
nal
SC
C-L
ine:
C
ircu
it d
e p
uis
san
ceR
atio
nal
Lin
ea S
CC
: C
ircu
ito
de
la e
ner
gía
K1
BN BU
M5
M 1 ~A2
A1
N/O
1 2
BK
3 4
OG
5 6
VT
W17
A2 Ope
rato
r PCB
K1 N/O
14 13
X7
11
GY RD BN
F31 2
F41 2
33
Ein/
Aus
Sch
alte
rS1
K1A
1
A222
RD
GY BN BU
W10
WH
WH
WH
X10
11
X46
11
T1St
euer
traf
oC
ontr
oltr
ansf
orm
er
2,5V
0V
2,5V
11,5V
11,5V
12V
12V
250V
240V
230V
220V
208V
200V
0V
22 22
33 33
A1
I/O-P
CB
F5 1,6A
.
W13
WH
WH
WH
WH
X14
11 11
22 22
33 33
44
X56
44
11
F6.1
2AT .
X21
1122
F6 2AT
W0
BK
BN
BK
BU
PEX0
YE/GN YE/GN
BK BU
F1 6,3A F2 6,3A
BN
Z1
L1 L2 L3 PE
X57
7766
5544
3322
BK BU
YE/G
N
M1
M ~F2
0
6,3A .
F21
6,3A .
33 22
X2211
BK OG VT
YE/G
N
3AC
200
-240
V
R1
3x3k
W9k
W D
1/D
2
1 2V1
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
3 4
5 6
X33
1122 R2
3x3k
W9k
W D
1/D
2
1 233
D1
H
L2
44
3 4
5 6
V2
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
X34
11
R4
6x3k
W18
kW H
L1/H
L2
1 2
22
3 433
D2
H
L1
44
5 6
7 8
9 10
11 12
BN
77 66 55 44 33 22BU
T4
~-
12V
0V
0V200V
208V
220V
230V
240V
250V
X5911
22
X6711
M5
M20
1-20
2
- 47 - V03 EN, Trouble Shooting
Rat
ion
al S
CC
-Lin
ie:
Leis
tun
gst
eil
Rat
ion
al S
CC
-Lin
e:
Pow
er c
ircu
itR
atio
nal
Lin
ea S
CC
: C
ircu
ito
di a
limen
tazi
on
eR
atio
nal
SC
C-L
ine:
C
ircu
it d
e p
uis
san
ceR
atio
nal
Lin
ea S
CC
: C
ircu
ito
de
la e
ner
gía
55 44 33 22
T3
Sond
ertr
afo
Spec
ial t
rans
form
er
0V400V
415V
440V
480V
0V230V
X7211
F7 0,8A
22
X71
11
F86,
3A
F96,
3A
F10
6,3A
M1
M ~44 33 22
X22
11
K1
BN BU
M5
M 1 ~A2
A1
N/O
1 2
BK
3 4
OG
5 6
VT
W17
A2 Ope
rato
r PCB
K1 N/O
14 13
X7
11
GY RD BN
F31 2
F41 2
33
Ein/
Aus
Sch
alte
rS1
K1A
1
A222
RD
GY BN BU
W10
WH
WH
WH
X10
11
X46
11
T1St
euer
traf
oC
ontr
oltr
ansf
orm
er
2,5V
0V
2,5V
11,5V
11,5V
12V
12V
250V
240V
230V
220V
208V
200V
0V
22 22
33 33
A1
I/O-P
CB
F5 1,6A
.
W13
WH
WH
WH
WH
X14
11 11
22 22
33 33
44
X56
44
11
F6.1
2AT .
X21
1122
F6 2AT
W0
BK
BN
BK
BU
PE
YE/GN YE/GN
BKF1 6,
3A F2 6,3A
BN
Z1
L1 L2 L3 N PE
X57
7766
5544
3322
YE/G
N
VT
R1
3x3k
W9k
W D
1/D
2
1 2
V1
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
3 4
5 6
X33
1122 R2
3x3k
W9k
W D
1/D
2
1 233
D1
H
L2
44
3 4
5 6
V2
Leis
tung
shal
blei
ter
solid
sta
te re
lay
A+
A-
B+B-
A1/
B1
A2
B2
R4
6x3k
W18
kW H
L1/H
L2
1 2
X34
1122
3 4
33
D2
H
L1
5 644
7 8
9 10
11 12
BK OG VT
YE/G
N
3AC
400
-480
V
BN
77 66 55 44 33 22BU
T4
~-
12V
0V
0V200V
208V
220V
230V
240V
250V
X5911
22
X6711
M5
M20
1-20
2
- 48 - V03 EN, Trouble Shooting
Rat
ion
al S
CC
-Lin
ie:
Leis
tun
gst
eil
Rat
ion
al S
CC
-Lin
e:
Pow
er c
ircu
itR
atio
nal
Lin
ea S
CC
: C
ircu
ito
di a
limen
tazi
on
eR
atio
nal
SC
C-L
ine:
C
ircu
it d
e p
uis
san
ceR
atio
nal
Lin
ea S
CC
: C
ircu
ito
de
la e
ner
gía
Z1
W0
K1 N/O
1 2BK BK BK
3 4BU BU BU
GN/YE GN/YE
BK BU
F1 6,3A F2 6,3A
BNW17
A2
Ope
rato
r PCB
K1 N/O
13 14
X7
1
GY BNRD
F31 2
F41 2
3
Ein/
Aus
Sch
alte
rS1 K1
A1
A22
GY
BN BU RD
W10
WH
WH
WH
X10
1
X46
1
X57
7
T1
Steu
ertr
afo
Con
trol
tran
sfor
mer
2,5V
0V
2,5V
11,5V
11,5V
12V
12V
250V
240V
230V
220V
208V
200V
0V
2 2 6
3 3 5
A1
I/O-P
CB
F5 1,6A
.
W13
WH
WH
WH
WH
X14
1 1 4
2 2 3
3 3 2
4
X56
4 1
F6.1
2AT .
X21
12
F6 2AT .
Gasgebläse (HL1)Gasblower
M8
1M ~
NL1
PE GN
D
U/m
in
PWM
X60
12
3
W15
X51 3 4 2
W18
A5
Feue
rung
saut
omat
(HL1
un
d D
)Ig
nitio
nbox
BUS
BUS
NEP
L1 1 24
356
W14
GasventilGas valve
Y12
X65
12
3
Elektrode GasbrennerElectrode gas burner
B12
4
HL
1
RJ 45
Elektrode GasbrennerElectrode gas burner
B11
RJ 45
GasventilGas valve
Y11
D
X52
3 4 2
W18
W15
Gasgebläse (D)Gasblower
M9
1M ~PW
M
U/m
in
GN
D
NL1
PE
X61
12
3
M1
M ~
..
F20
6,3A .
F21
6,3A .
3 2
X221
M5
M 1 ~A2
A1
1NA
C 2
30V
- G
as
BN
7 6 5 4 3 2BU
T4
~-
12V
0V
0V200V
208V
220V
230V
240V
250V
X591
2
X671
M5
M20
1-20
2
- 49 - V03 EN, Trouble Shooting
Rat
ion
al S
CC
-Lin
ie:
Leis
tun
gst
eil
Rat
ion
al S
CC
-Lin
e:
Pow
er c
ircu
itR
atio
nal
Lin
ea S
CC
: C
ircu
ito
di a
limen
tazi
on
eR
atio
nal
SC
C-L
ine:
C
ircu
it d
e p
uis
san
ceR
atio
nal
Lin
ea S
CC
: C
ircu
ito
de
la e
ner
gía
X72
010199
2233
4455
6677
88
F7 0,8A
.
X71
22
T3So
nder
traf
oSp
ecia
l tra
nsfo
rmer
0V
100V
110V
120V
127V
200V
208V
220V
230V
240V
0V
230V
11 11
2
1
A2
Ope
rato
r PCB
K1 N/O
13 14
X7
11GY BNRD
F31 2
F41 2
33
Ein/
Aus
Sch
alte
rS1 K1
A1
A222
GY
BN BU RD
W10
WH
WH
WH
X10
11
X46
11
X57
77
T1
Steu
ertr
afo
Con
trol
tran
sfor
mer
2,5V
0V
2,5V
11,5V
11,5V
12V
12V
250V
240V
230V
220V
208V
200V
0V
22 22 66
33 33 55
A1
I/O-P
CB
F5 1,6A
.
W13
WH
WH
WH
WH
X14
11 11 44
22 22 33
33 33 22
44
X56
44 11
F6.1
2AT .
X21
1122
F6 2AT .
Gasgebläse (HL1)Gasblower
M8
1M ~
NL1
PE GN
D
Act
. spe
ed U
/min
Set
spee
d PW
M
X60
1122
33 W15
X51 33 44 22
W18
A5
Feue
rung
saut
omat
(HL1
un
d D
)Ig
nitio
nbox
BUS
BUS
NEP
L1 1 24
356
W14
GasventilGas valve
Y12
X65
12
3 Elektrode GasbrennerElectrode gas burner
B12
HL
1
RJ 45
Elektrode GasbrennerElectrode gas burner
B11
RJ 45
GasventilGas valve
Y11
D
X52
33 44 22
W18
W15
Gasgebläse (D)Gasblower
M9
1M ~PW
M
U/m
in
GN
D
NL1
PE
X61
1122
33
M1
M ~
..
F20
6,3A .
F21
6,3A .
33 22
X2211
M5
M 1 ~A2
A1
BN
77 66 55 44 33 22BU
T4
~-
12V
0V
0V200V
208V
220V
230V
240V
250V
X5911
22
X6711
Z1
W0
K1 N/O
1 2BK BK BK
3 4BU BU BU
GN/YE GN/YE
BK BU
F1 6,3A F2 6,3A
BN
1NA
C 1
00 -
127V
, 1N
AC
240
V, 2
AC
200
- 24
0V -
Gas
M5
M20
1-20
2
- 50 - V03 EN, Trouble Shooting
SCC
Ser
vice
Ref
eren
ce
SC
C k
ey c
Func
tion
key
a
Pro
g ke
y b
Set
tings
Sta
rttim
e
Cle
anJe
t
1 2 3 4
(sin
ce S
W S
CC
02_
xx_x
x to
03_
xx_x
x)(s
ince
SW
SC
C 0
4_xx
_xx)
Set
tings
Sta
rttim
e
Ca
reC
on
tro
l
Cle
anJe
t +car
e
10:2
4
eng
lisham
/pm
24 h
h:m m:s IP
10/2
2/06
22.1
0.06
°C /
°F
Ty
pdesc
ale
CD
S
Ser
vice
Info
Set
tings
Set
ting
of l
angu
age
rese
t to
fact
ory
setti
ng
Set
ting
Cle
anJe
t req
uest
(onl
y ac
tiv
whe
n fra
me
show
s in
red)
Des
calin
g pr
ogra
m: a
utom
atic
pro
cess
empt
y st
eam
gen
erat
or (D
oor m
ust
be o
pen!
)
Dis
play
of s
cale
leve
l ins
ide
stea
m
gene
rato
r
Dis
play
of s
oftw
are
vers
ion,
Ser
ial
num
ber
eras
e al
l cus
tom
er p
rogr
ams
„Pro
gram
lock
“ Pas
swor
d;12
345;
TT
RE
U
setti
ng b
uzze
r (so
und-
dura
tion)
Cop
y cu
stom
er p
rogr
am to
stic
kR
eloa
d cu
stom
er p
rogr
ams
from
stic
k to
uni
tE
rase
cus
tom
er p
rogr
ams
Dow
nloa
d of
HA
CC
P-D
ata
Sof
twar
e up
date
s (Ic
on o
nly
show
s w
hen
unit
dete
cts
valid
sof
twar
e on
th
e us
b st
ick;
Dow
nloa
d of
ser
vice
dat
a to
stic
k.
HACC
PP
rog
Pro
gP
rog
Info
upda
te
P,
H, I
05,
S05
Che
f
L
ine
h:m
m:s
Pro
g Pro
g
Show
Mod
e - s
witc
h of
f or o
nO
Npr
ess
func
tion
key
„a“ f
ollo
wed
by
prog
ram
key
„b“ a
nd
SC
C k
ey „c
“ for
10
seco
nds
until
-ac
oust
ic s
igna
l - B
eep
and
door
han
dle
in ic
on fu
nctio
n ke
y „a
“ sho
ws
in re
d
OFF
pres
s fu
nctio
n ke
y „a
“ fol
low
ed b
y pr
ogra
m k
ey „b
“ and
S
CC
key
„c“ f
or 1
0 se
cond
s un
til -
acou
stic
sig
nal -
Bee
pan
d do
or h
andl
e in
icon
func
tion
key
„a“ s
how
s in
blu
e
Abo
rt C
lean
Jet
switc
h un
it of
f and
on
agai
n
Abo
rt d
e-sc
alin
g pr
ogra
mbe
fore
filli
ng d
e-sc
alin
g liq
uid
- use
„BA
CK
“ arr
ow
afte
r filli
ng d
e-sc
aler
into
ste
am g
ener
ator
- sw
itch
unit
off a
nd o
n ag
ain
- pre
ss A
BO
RT
key
- rem
aini
ng ti
me
will
be
adju
sted
aut
omat
i-ca
lly- s
witc
h un
it of
f and
on
agai
n- p
ress
AB
OR
T ke
y - t
ime
will
be
adju
sted
aut
omat
ical
ly 2
x- u
se s
team
mod
e fo
r 15
min
. and
rins
e in
terio
r cab
inet
Ente
r Ser
vice
leve
lse
t dip
sw
itch
„1“ o
n pc
b to
ON
pos
ition
Dia
gnos
ticR
unni
ngTi
mes
Func
tion
Test
Bas
ic S
ettin
gs
12
34
on
- 51 - V03 EN, Trouble Shooting
Serv
ice
erro
r cod
e:S
ervi
ce 4
0C
lean
jet n
ot p
ossi
ble,
C
are
pum
p fa
ulty
Ser
vice
41
CD
S d
oes
not s
end
any
puls
es; s
olen
oid
valv
e Y
3 de
fect
ive
or m
oist
enin
g va
lve
bloc
ked;
Ser
vice
42
CD
S d
oes
not s
end
any
puls
es; S
olen
oid
Y4
Car
e de
fect
ive
or h
ose
to c
are
cont
ai-
ner b
lock
ed u
p or
kin
ked;
Ser
vice
43
CD
S s
enso
r sen
ds a
lway
s pu
lses
; Sol
eno-
id Y
1, Y
3 or
Y4
is p
assi
ng w
ater
Ser
vice
44
Ste
am h
eatin
g or
SS
R fa
ulty
Ser
vice
100
Mai
n co
ntac
tor -
pcb
on
off s
witc
h
Ser
vice
110
SC
pum
p fa
ulty
or l
evel
ele
ctro
de c
alci
fies
Ser
vice
120
Car
e P
ump
M12
or l
evel
ele
ctro
de d
efec
-tiv
e
Gas
-set
tings
- va
lues
Dyn
. pre
ssur
e LP
G27
-57
mba
r; 2,
7-5,
7 kP
a
Dyn
. pre
ssur
e na
tura
l gas
18-2
5 m
bar;
1,8-
2,5
kPa
CO
2 m
ax L
PG
(G30
) 3B
P10
,4%
+/-
0,2%
for t
ype
61-2
02
CO
2 m
ax L
PG
(G31
) 3P
11,1
% +
/- 0,
2% fo
r typ
e 61
-202
CO
2 m
ax n
atur
al g
as H
(G20
)9,
4% +
/- 0,
2% fo
r typ
e 61
-201
9,5%
+/-
0,2%
for t
ype
202
CO
2 m
ax n
atur
al g
as L
(G25
) 9,
3% +
/- 0,
2% fo
r typ
e 61
-201
9,4%
+/-
0,2%
for t
ype
202
Cal
ibra
tion
SC
C
Cal
ibra
tion
at th
e cu
stom
ers
site
mus
t be
done
und
er th
e fo
llow
ing
cond
ition
s: C
hang
ing
of:
1 P
ress
ure
sens
or P
1,
2 B
4 hu
mid
ity s
enso
r,3
fan
mot
or,
4 pc
b,5
exte
rnal
EE
PR
OM
, 6
deta
chin
g of
the
fan
whe
el,
7 re
plac
ing
the
air b
affle
or d
ivid
er p
late
bet
wee
n th
e 2
fan
mot
ors
of a
floo
r mod
el,
8 in
stal
latio
n of
the
appl
ianc
e ab
ove
1000
m (3
000f
t) ab
ove
sea
leve
l or b
elow
sea
leve
l (de
ad s
ea),
inst
allin
g w
ith U
ltrav
ent o
f
vent
ing
exte
nsio
n or
as
a C
ombi
Duo
9 U
sage
of a
diff
eren
t sta
ndar
d ra
ck10
Cus
tom
er c
ompl
aint
for u
neve
n co
okin
g re
sults
Bas
ic c
ondi
tion
Tem
pera
ture
s: C
abin
et s
enso
r
Q
uenc
h. s
enso
r
H
umid
ity s
enso
r
B
1 <4
0°C
B2
<45°
C
B
4 <
40°
C
Bas
ic c
ondi
tion
Har
dwar
e:H
eatin
g: O
FF F
an m
otor
: OFF
Hum
idity
flap
: Clo
sed
Sid
e pa
nel m
ust b
e fit
ted;
Uni
t mus
t be
clea
n, b
ut m
ay b
e w
etIn
ord
er to
ach
ieve
the
best
pos
sibl
e ca
libra
tion
valu
es, i
nser
t2
GN
-con
tain
er 2
0 or
40
mm
dee
p w
ith th
e op
enin
g fa
cing
do
wnw
ards
in 6
1 an
d 62
uni
ts in
to ra
il 2
and
5in
101
and
102
uni
ts in
to ra
il 3
and
7in
201
and
202
uni
ts 3
GN
con
tain
er in
to ra
il 3,
10
and
17
To s
tart
cal
ibra
tion:
Set
DIP
sw
itch
1 in
on
pcb,
Sel
ect:
Bas
ic S
ettin
gs, P
kt. 1
.1: S
TAR
T
Se
rvic
e er
ror c
ode:
Ser
vice
10
SC
-Pum
p w
ithou
t Fun
ctio
n
Ser
vice
11
leve
l ele
ctro
de (O
smos
is w
ater
) or c
heck
va
lve
abov
e st
eam
gen
erat
or fo
r lea
kage
Ser
vice
12
CD
S s
enso
r no
outp
ut s
igna
l
Ser
vice
13
chan
ge le
vel e
lect
rode
Ser
vice
14
Leve
l ele
ctro
de (O
smos
is w
ater
)
Ser
vice
16
sinc
e 01
-07-
09,
flash
new
sof
twar
e ve
rsio
n fir
st
Ser
vice
17
exte
rnal
EE
PR
OM
faul
ty
Ser
vice
20
ther
moc
oupl
e B
1 fa
ulty
Ser
vice
21
mic
ro s
witc
h cl
ima
cont
rol f
aulty
Ser
vice
22
Ser
vice
23
SS
R s
team
sho
rt ci
rcui
t
Ser
vice
24
SS
R h
ot a
ir sh
ort c
ircui
t
Ser
vice
25
Cle
anJe
t wat
er c
ircul
atio
n fa
ulty
- wat
er d
oesn
‘t hi
t fan
whe
el- c
heck
pum
p, fo
reig
n bo
dies
in w
ater
pi
pe, r
acks
/ tro
lley
mus
t be
insi
de c
abin
et
Ser
vice
26
drai
n va
lve
clos
ed
Ser
vice
27
drai
n va
lve
does
n‘t c
lose
,C
lean
Jet w
ithou
t fun
ctio
n
Ser
vice
28
B5
in s
team
gen
erat
or a
bove
180
°C
(356
°F),
de-s
cale
ste
am g
ener
ator
Ser
vice
29
pcb
tem
pera
ture
too
high
(abo
ve 8
5°C
/ 18
5°F)
; cha
nge
air fi
lter
Ser
vice
30
hum
idity
con
trol f
aulty
Ser
vice
31.
Xco
re p
robe
faul
ty
Ser
vice
32.
Xig
nitio
n bo
x fa
ulty
, cha
nge
igni
tion
box
0-to
p; 1
-bot
tom
; 2-b
oth
Ser
vice
33.
X4x
Res
et w
ithou
t fun
ctio
n,ch
ange
igni
tion
box;
1-to
p; 2
-bot
tom
Ser
vice
34.
XB
US
sig
nal e
rror
1-I/O
pcb
, 2-m
otor
bot
tom
; 4-m
otor
top;
8-ig
nitio
n bo
x to
p; 1
6-ig
nitio
n bo
x bo
ttom
- 52 - V03 EN, Trouble Shooting
Ente
r Ser
vice
leve
l (D
iagn
ostic
, Set
tings
, Run
ning
tim
es)
Set
dip
sw
itch
1 on
pcb
to „O
N“ p
ositi
on
Ente
r fun
ctio
n te
stS
et d
ip s
witc
h 3
on p
cb to
„ON
“ pos
ition
CM
Ser
vice
Ref
eren
ceS
CC
Lin
e
12
34
on 12
34
on1Mod
e di
al
2 C
abin
et te
mp.
dial
4 Ti
me
key
6 Ti
me
/ cor
e tm
p.di
al
5 C
ore
tem
p. k
ey
Key
cod
e C
M (S
CC
line
)C
lean
ing
prog
ram
sele
ct C
ool D
own
with
„1“
pres
s ke
y „5
“ for
10
sec.
„CLE
n“ is
sho
wn
in te
mpe
ratu
re d
ispl
aypr
ess
key
„4“ 1
x;
De-
scal
ing
prog
ram
sele
ct C
ool D
own
with
„1“
pres
s ke
y „5
“ for
10
sec.
„CLE
n“ is
sho
wn
in te
mpe
ratu
re d
ispl
ayse
lect
„CA
LC“ w
ith „2
“pr
ess
key
„4“ 1
x;
empt
y st
eam
gen
erat
orse
lect
Coo
l Dow
n w
ith „1
“pr
ess
key
„5“ f
or 1
0 se
c.„C
LEn“
is s
how
n in
tem
pera
ture
dis
play
sele
ct „S
C“ w
ith „2
“; op
en d
oor,
pres
s ke
y „4
“ 1x;
sele
ct °C
- °F se
lect
any
coo
king
mod
epr
ess
key
„4“ a
nd „5
“ for
10
seco
nds
Erro
r cod
eTi
me
disp
lay
Cab
inet
di
spla
yop
en w
ater
tap
chan
ge p
olar
ity o
f mai
ns s
uppl
y
Ext
erna
l EE
PR
OM
dat
a er
ror
heat
ing
bloc
ked
by e
nerg
y op
timis
ing
B1
cabi
net s
enso
r def
ectiv
e
B2
quen
chin
g se
nsor
def
ectiv
e
B3
core
pro
be s
enso
r def
ectiv
e
B5
stea
m g
ener
ator
sen
sor d
efec
tive
Ther
mo
sens
or o
n pc
b de
fect
ive
pote
ntio
met
er c
abin
et te
mp.
def
ectiv
e
pote
ntio
met
er ti
me
/ cor
e pr
obe
defe
ctiv
e
Ext
erna
l EE
PR
OM
def
ectiv
e
mod
e sw
itch
defe
ctiv
e
fan
mot
or b
otto
m B
us e
rror
(LE
D s
how
s?)
fan
mot
or b
otto
m d
efec
tive
fan
mot
or to
p B
us e
rror
(LE
D s
how
s?)
fan
mot
or to
p de
fect
ive
M4
SC
-pum
p de
fect
ive
or b
lock
ed
fil
ling
sole
noid
def
ectiv
e / s
ieve
blo
cked
pc
b te
mp.
abo
ve >
85°C
(185
°F),
chan
ge a
ir fil
ter
B5
stea
m g
ener
ator
sen
sor a
bove
18
0°C
(356
°F),
de-s
cale
ste
am g
ener
ator
B5
stea
m g
en. s
enso
r bel
ow -5
°C (2
3°F)
B1
cab.
sen
sor a
bove
340
°C (6
40°F
) (S
SR
?)Ig
nitio
n bo
x to
p bu
s er
ror
Igni
tion
box
botto
m b
us e
rror
1xx
- Ste
am,
2xx
- Hot
air
top
3xx
- Hot
air
botto
mIg
nitio
n bo
x de
fect
ive
- cha
nge
box
1xx
- Ste
am,
2xx
- Hot
air
top
3xx
- Hot
air
botto
mIg
nitio
n el
ectro
de, I
gniti
on b
ox, c
able
flash
new
sof
twar
e fir
st
- 53 - V03 EN, Trouble Shooting
Dia
gnos
tic p
rogr
am
Sof
twar
e ve
rsio
n
B1
cabi
net s
enso
r
B2
quen
chin
g se
nsor
B3
core
pro
be s
enso
r
B5
sens
or s
team
gen
erat
or
PC
B te
mpe
ratu
rem
ust b
e be
low
75°
C
(167
°F)
S3
door
con
tact
o - o
pen;
1 -
clos
ed
S2
leve
l ele
ctro
de0
- no
wat
er; 1
- ok
stea
m e
lem
ent e
nerg
ised
0 ; 1
=50%
; 2=1
00%
ho
t air
elem
ent e
nerg
ised
0 ; 1
=50%
; 2=1
00%
rpm
fan
mot
or b
ottto
m
rpm
fan
mot
or to
p
Sic
otro
nic
ener
gy o
ptim
i-si
ng
Uni
t typ
e an
d si
ze
Gas
- Fl
ame
curr
ent s
team
norm
al: 4
,5 -
5,5μ
A
Gas
- Fl
ame
curr
ent h
ot
air t
opno
rmal
: 4,5
- 5,
5μA
Gas
- Fl
ame
curr
ent h
ot a
ir bo
ttom
norm
al: 4
,5 -
5,5μ
AR
T - R
unni
ng T
imes
S3
door
ope
ning
s
Tota
l tim
e Y
1 va
lve
fillin
g
Tota
l tim
e Y
2 va
lve
quen
chin
g
Tota
l tim
e M
4 S
C-p
ump
Tota
l tim
e st
eam
hea
ting
time
Tota
l tim
e ho
t air
heat
ing
time
Tota
l tim
e st
eam
mod
e
Tota
l tim
e ho
t air
mod
e
Tota
l tim
e co
mbi
natio
n m
ode
Tota
l tim
e va
rio s
team
mod
e
Tota
l tim
e fin
ishi
ng m
ode
Tota
l tim
e cl
eani
ng p
rogr
am
Tota
l run
ning
tim
e un
it
SE -
Bas
ic S
ettin
gs
Ste
am h
eatin
g tim
e si
nce
last
SC
-Aut
omat
ic
Pre
set S
team
hea
ting
time
until
SC
-Aut
omat
ic
Flus
hing
tim
e S
C-A
utom
atik
Ope
ratio
n st
eam
gen
erat
or p
ump
Sho
w m
ode
Set
ting
new
gas
type
Pre
setti
ng o
f CO
2 sc
rew
in m
m
inst
alla
tion
altit
ude
abov
e se
a le
vel
rpm
blo
wer
mot
or s
team
MIN
rpm
blo
wer
mot
or s
team
Sta
rt
rpm
blo
wer
mot
or s
team
MA
X
rpm
blo
wer
mot
or h
ot a
ir to
p M
IN
rpm
blo
wer
mot
or h
ot a
ir to
p S
tart
rpm
blo
wer
mot
or h
ot a
ir to
p M
AX
rpm
blo
wer
mot
or h
ot a
ir bo
ttom
MIN
rpm
blo
wer
mot
or h
ot a
ir bo
ttom
Sta
rt
rpm
blo
wer
mot
or h
ot a
ir bo
ttom
MA
X
F --
Fun
ctio
n te
st
Set
DIP
sw
itch
3 to
„ON
“ pos
ition
!In
Fun
ctio
n te
st c
ompo
nent
s ar
e N
OT
prot
ecte
d ag
ains
t ove
rload
!Fu
nctio
nC
abin
et
disp
lay
Tim
e
disp
lay
Ste
am 5
0%, E
lect
ric u
nit
act.
tem
p.B
5 st
eam
gen
erat
or1
/ 0
Ste
am 1
00%
, Ele
ctric
uni
tac
t. te
mp.
B5
stea
m g
ener
ator
1 / 0
Hot
air
50%
, Ele
ctric
uni
tac
t. te
mp.
B1
cabi
net
1 / 0
Hot
air
100%
Ele
ctric
uni
tac
t. te
mp.
B1
cabi
net
1 / 0
Ste
am G
as u
nit
act.
tem
p.B
5 st
eam
gen
erat
or1
/ 0
Hot
air
top,
Gas
uni
tac
t. te
mp.
B1
cabi
net
1 / 0
Hot
air
botto
m, G
as u
nit
act.
tem
p.B
1 ca
bine
t1
/ 0
Bot
tom
Mot
or M
AX
rpm
Set
rpm
act.
rpm
Bot
tom
Mot
or M
IN rp
mS
et rp
mac
t. rp
m
Top
Mot
or M
AX
rpm
Set
rpm
act.
rpm
Top
Mot
or M
IN rp
mS
et rp
mac
t. rp
mS
olen
oid
valv
equ
ench
ing
actu
al te
mp.
B
2 qu
ench
ing
Y2
1 / 0
Sol
enoi
d va
lve
fillin
gLe
vel e
lect
rode
S
2, 1
/ 0
Y1
1 / 0
SC
Pum
pLe
vel e
lect
rode
S
2, 1
/ 0
M4
1 / 0
Buz
zer
1 / 0
All
Dis
play
s / L
ED
Rel
ais
Ultr
aven
t(d
oor o
pen
/ clo
se)
1 / 0
no fu
nctio
n
Gas
blo
wer S
team
MIN
rpm
actu
al rp
mS
et C
O2
Gas
blo
wer S
team
Sta
rt rp
mac
tual
rpm
Gas
blo
wer S
team
MAX
rpm
actu
al rp
mS
et C
O2
Gas
blo
wer
Hot
air
top
MIN
rpm
actu
al rp
mS
et C
O2
Gas
blo
wer
Hot
air
top
Sta
rt rp
mac
tual
rpm
Gas
blo
wer
Hot
air
top
MA
X rp
mac
tual
rpm
Set
CO
2
Gas
blo
wer
Hot
air
bot-
tom
MIN
rpm
actu
al rp
mS
et C
O2
Gas
blo
wer
Hot
air
bot-
tom
Sta
rt rp
mac
tual
rpm
Gas
blo
wer
Hot
air
bot-
tom
MA
X rp
mac
tual
rpm
Set
CO
2
- 54 - V03 EN, Trouble Shooting
- 55 - V03 EN, Trouble Shooting
80.51.084 - V03 EN - RTS/Sc - 10/2010
RTS Contact Germany
Fax: +49 (0)8191-327397e-mail: [email protected]: http://service.rational-online.com
Service Parts:Fax: +49 (0)8191-327408e-mail: [email protected]
Chef Line:Phone: +49 (0)8191-327300
Please note that any technical information concerning Rational products must NOT be forwarded to any third party.