topic ii. 4. dry weather design flowrates
DESCRIPTION
Topic II. 4. Dry Weather Design Flowrates. Basic Sewage Quantity Parameters I. Domestic Sewage flowrates Specific sewage flowrate - q s , l/d.ca q s = 0,9.q 0 Mean daily sewage flowrate - Q m.d , m 3 /d Q m.d = q s . N/1000 Maximal daily sewage flowrate - Q max.d , m 3 /d - PowerPoint PPT PresentationTRANSCRIPT
1
Topic II. 4. Dry Weather Design Flowrates
Basic Sewage Quantity Parameters
I. Domestic Sewage flowrates
Specific sewage flowrate - qs, l/d.ca
qs = 0,9.q0
Mean daily sewage flowrate - Qm.d, m3/d
Qm.d = qs.N/1000
Maximal daily sewage flowrate - Qmax.d, m3/d
Qmax.d = qs.N.Kh/1000
Kh - coefficient of hourly variability
2
Basic Sewage Quantity Parameters
Maximal hourly sewage flowrate - Qmax.h, m3/h
Qmax.h = qs.N.K0/24.1000
where K0 = 1 + 2,5/ (Qm.d)0,22 ; Qm.d - in l/s
K0 - maximal coefficient of general variability
Sewage flowrate module - qm , l/s.ha
qm = (Qm.d - Qs,conc) / F.86400
3
Basic Sewage Quantity Parameters
II. Industrial Sewage Flowrates
Mean daily sewage flowrate - Qm.d, m3/d
Qm.d = qind.Md/1000
Maximal hourly sewage flowrate - Qmax.d, m3/h
Qmax.h = qind.Mh.Kh/1000
4
Sewage Design Flowrates
Separate Sewer System
(Dry Weather Flow)
Sewage design flowrate - Qd, l/s
Qd = 2Qmax,h = 2(qm.f.K0 + Qs,conc + Qmax.h)
where K0 = 1 + 2,5/(qm.f)0,22