    Matrishri Usha Jayaswal Mega Power Project DCPL-K9A052x270MW,CHANDWA TPS

    Page : 1

    Ref.: K9A05/DCH-4/E/BHEL Annexure-A -Dated 02.06.2011Comments/Observation:- Electrical

    Ref.: GENERATOR RELAY PANEL

    Drawings:

    1) Dwg. No. PE-DG-344-510-E001,Rev01 10 Shts: Single Line Diagram for Generator,GT& UAT Circuit

    Metering & Protection.

    2) Dwg. No. PE-DG-344-510-E002,Rev01 34Shts: Logic Diagram for Generator,GT& UAT Circui t

    Protection. & Annunciation.

    3) Dwg. No. PE-DG-344-510-E003,Rev01 7Shts: CT & VT Calculation for Generator,GT& UAT Circuit

    Metering & Protection.

    Action-4

    Please note the following :-

    1) Refer CT-1 :Provide CT with Ie 150mA at Vk/4 (Instead of Vk/4),BHELs clarification is not justified.

    2)Refer CT-2: Provide CT Burden =75VA.

    3) Refer CT-7: Provide CT Burden =75VA.

    4) Refer CT-8: Provide CT Burden =75VA.

    5) Refer CT-9: Note NGR current rating will 650A (BHEL,Rudrapur data sheet)

    6) Refer CT-10: (Refer BHEL, Bhopal GTs R&D plate) Bushing CT Ratio: 500/1A and other CTparameter are not same with calculation. Please check and confirm the rating and calculation for bothCore of CT-10.

    7) Refer CT-11: (Refer BHEL, Bhopal GTs R&D plate) Bushing CT Ratio: 500/1A and other CTparameter are not same with calculation. Please check and confirm

    8) Refer CT-13A/13B: Provide CT Ration:1000/1A

    9) Refer CT-14A/14B: Provide CT Ration:1000/1A

    10)Refer CT-16A/16B: (Refer BHEL, Jhansi UTs R&D plate) Bushing NCT Details are asbelow,please check and confirm.

    Core-1: 150/1A, 5P20, 30VA

    Core-2: 300/1A, PS,Vk 10(RCT +5)V, Ie 15 mA at Vk/2,

    11) Refer CT-17A/17B: (Refer BHEL, Jhansi UTs R&D plate) Bushing Line CT Details are asbelow,please check and confirm.

    CT Details: 300/1A, PS,Vk 100(RCT +5)V, Ie 15 mA at Vk/2,

    12) Refer CT-18A/18B: 6.6kV switchgear Incomer CT Details are as below, please check and

    Correct the doc.

    CT Details: 2500/1A, PS,Vk 585V, Ie 30 mA at Vk/2,

    13) Refer VT-3: Provide VT Burden =75VA

    14) Refer IVT-1: Provide IVT Burden =30VA

    15).CT-17A/B: BHELs clarification is not justified.CT-17A/B will be used for 64RUATA/B.The location ofCT will be at BCT of UAT-A/B not in 6.6Kv switchgear. Refer connection for64RGT sheet no. 9 of 10 ofthis drawing as well as JPL project.

  • 7/28/2019 Third Comment on Grp 02-06-11

    2/2

    Matrishri Usha Jayaswal Mega Power Project DCPL-K9A052x270MW,CHANDWA TPS

    Page : 2

    16)ProvideindependentCTforAVR.ThesamehasalsobeenconsideredinBHELEDNs DAVRdwg.17)ReferSheet8of10ofSLD,CTconnectionforfrequencyTransducerMKA02FE001Eisnotindicated.Indicatethesame.