Room/Area 1. Stauwell.S 2. Women's bathroom (LL) 3. Near LL sprinkler room 4. Sprinkler room (LL) 5. Fountain (LL) The Lodge, May 20, 2015 Item Com ustffites m stairwe Loose faucet Loose outlet Door won 't latch Ceiling tiles missing Exposed wire in light fixture Loose outlet Surge protector Exposed wires No blanks in panel No panel schedule in smaller unit Timer cover missing Loose conduit rack Water heater conduits hanging loose 480v light fixture Extension cord and open wires Armored cable present Pump in fountain 6. Banquet rooms (ll) 7. 8. 9. 10. 11. HalVtunnel outside banquet Panel cover missing rooms Cords present No knockout No automatic closers on fire-rated doors Large ballroom at base of No door closer stairs (ll) Extension cord near bar Loose outlet by bar Women's bathroom (LL) Ceiling damaged Men's bathroom (LL) Switchplate damaged Dumbwaiter closet (LL) Dumbwaiter powered by electric cord Junction box not fastened Wrong cord for ice machine Mold on wall from water damage Outlet near ice machine corroded 12 . Boiler room LL) Armored cable unsupported Open slot in panel Boiler room cluttered Corrective Action Remove combustmles Tighten faucet to vanity Tighten outlet Repair Install ceiling tiles lnstalljunction box/rewire Tighten outlet Remove Cover exposed wires Install UL listed panel blank Label panel Install cover Re -anchor rack Re-support water heater conduits Disconnect 480v outlet Remove Eliminate Eliminate Install cover Remove Install knockout plug Fire -rated doors must have working self-closers and are required to be closec and latched properly at all times Install workmg self-closer on door Remove outlet Repair, including underlying cause Replace switchplate, using entire plate Hard wire power to dumbwaiter Fasten junction box Replace with properly sized cord Repa ir, including underlying cause Replace, including underlying cause Appears as though outlet was under water Install supports Install UL listed panel blank Remove clutter and maintain clearance

Upload: others

Post on 23-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Room/Area

    1. Stauwell.S

    2. Women's bathroom (LL)

    3. Near LL sprinkler room

    4. Sprinkler room (LL)

    5. Fountain (LL)

    The Lodge, May 20, 2015

    Item

    Com ustffites store

  • Room/Area Item Corrective Action 13. Elec room (l[) Swttcnplite cover mLSsmg lnstau -Swttcnptate

    Sump pump cover missing lnstaU sump pump cover No panel clearance Clear 3-foot area around panel No cover on blower fan lnstaU cover

    14. Access hallway to work Damaged support brackets on sprinkler Install new support brackets room (LL) system main pipe

    Access blocked by sundry items Clear appropriate width for access at least the width of the fire doors)

    15. Hallway to laundry (LL) Emergency light powered by cord Hard wire emergency light Holes in walls and ceilings Repair holes in ceiling and walls to

    maintain required fire protection

    16. laundry room (ll) Cords on dryers C:lamaged Repalf' cords Junction boxes and plugs not covered lnstaU covers No covers or guards on washers lnstaU covers/guards No fire-rated door with auto-closure lnstaU fire-rated metal door with auto-(removed at some point in the past and matic closure (must remain closed at aU the opening was enlarged) times unless it has a magnetic hold

    device that is connected to fire alarm)

    17. Exit near laundry room (LL) No door (removed at some point in the Install fire-rated door with an automatic past) closure on the exit stairwell doorway

    next to laundry room. (Door must remain closed at all times)

    18. Small room off laundry (LL) Ceiling light fail Install a UL listed fan box Tables in front of disconnect Move tables Extension cords Remove Water heater cover missing Install cover

    19. Woi1C room (ll) Items stoii

  • Room/Area Item

    24. Outside elevator room (LL) Loose outlet/switchplate

    25.

    26. Mech room off hallway (LL) Wires present by main switch gear Plug on panel missing

    27. Men's bathroom/library Toilet running continuously Outlet polarity reversed

    28. Restaurant Brass railing loose Openings in rywall

    29. Restaurant/upper level Openmgs in Cfrywall

    30. Openings m drywall

    31. ~,;,;,;.~.;;.;.;.. _______ _. Seal tight improperly installed Multiplex Extension cords Steamer cover missing Outlet on south end damaged by water

    32. Exit SlQn missing

    33. mall l>alliOOm wittll>ar exit not clear

    34. Women's bathroom near Loose faucet handle Black Bear lounge

    35. Black Bear Lounge Multiplex behind bar Flex cable present Exposed armored cable Multiplex in raised seating Junction box loose

    36. k Bear Com ustililes stored in stauw

    37. Hallway outside offices Loose outlet

    38. GM office Multiplex Surge protector

    Corrective Action

    Tighten outletjswitchplate

    Install fasteners

    Eliminate wires Install plug

    Repair Rewire

    Tighten railing Repau- rywall to mamtain requir 1 hour fire rotection ratin

    Repair drywall to mamtain requu-1 hour fire rotection ratin

    Install seal tight properly Remove

    Repair or replace faucet handle

    Remove Eliminate or install hard pipe Pipe armored cable Remove Tighten

    No storage LS allowea in exit stauweli.S

    Tighten outlet

    Remove Remove

  • Room/Area Item Corrective Action

    39. Sales office Multiplex Remove

    40. Accounting Multiplex Remove Surge protector Remove

    41. Hallway outside Loose outlet cover Tighten outlet lobby desk

    42. PTAC\W UlCorrectty Rewire PTAC Ice maker wired incorrectt Rewire ice maker

    43. Kinks in ervents Shorten and stra!ghten d ervents Multiplex (2) Remove No GFCI Install GFCI

    o ctoor clOser Install workin

    44. Exerctse room PTAC cover miSSmg lnstaU cover Box corroded Repair AND replace junction box PT AC unit on E side of room shows Repair AND replace PTAC unit signs of fire Outside wall shows signs of leakage Repair water damage, including

    underlying cause

    45. Women's locker Extension cord by door Remove Tiles missing behind toilets Replace tiles Furnace has no switch or cover Install switch and cover

    46. No exits' n

    47. No exits' n

    48. Pool Chemical room cluttered with cords Remove cluttered cords

    49. 103 Bath light doesn 't work Repair/replace light/switch as needed Water damage Repair water damage, including

    underlying cause Shower running continuously Repair/replace shower fixture Junction box improperly installed Replace

    50. 105 Loose light switch Tighten switch Loose outlet under light switch Tighten outlet

    51. 106 Reverse polarity on GFI/won't trip Replace with GFCI No self-close door Install working self-closer on door

    52. 110 No self-close door Install working self-closer on door

    53. 120 No self-close door Install working self-closer on door Reverse polarity on PTAC outlet Repair or replace outlet

    54. 121 ok

    55. 122 No self-close door Install working self-closer on door

    56. Landing near 122 Exit egress not clear Remove obstructions from exit egress

  • Room/Area Item Corrective Action UinCiing near 122 cont) EXit ctoor liar ware not wo UlQ Repair7reptace exit Cloor liarCIWare anct

    maintain

    57. 123 Install working self-closer on door Re~lace smoke detector

    58. 124 Loose light switch Tighten switch

    59. Elec room (1) No cover on timer Install cover Surge protector Remove No panel clearance Clear 3-foot area around panel

    60. 142 Loose light switch Tighten switch Light flickers Repair or replace GFI fail Replace with GFCI No self-close door Install working self-closer on door

    61. Hallway near 142 Broken outlet cover Replace outlet cover

    62. 144 Loose outlet by frig Tighten outlet

    63. "Exit" behind bar No clear path Clear junk from path near end of first floor dead Wires coming out of transformer end corridor (south)

    No outlet cover Install outlet cover Armored cable present Eliminate armored cable

    64. Corrictor (1) South First floor dead end comaor 75 feet Maximum Clistance for Cleact enCI corridor is 50 feet f"lf'St floor south corridor has a dead end corridor of 75 feet.

    Original exit door has been eliminated Exit door and exit path must be maintained as required. Exit sign must be installed at this location.

    65. 147 PTACfaU Re lace PTAC unit Surge protector Remove No outlet cover behind TV Install outlet cover Loose outlet by door Tighten outlet

    66. Elec room (1) Surge protector Remove

    67. Mech room (1) Cluttered cords Eliminate cords Open junction box (2) Cover junction boxes

    68. Open wire on floor Cover wire No cover on AC/furnace unit Install cover Flex on floor Eliminate

    69. 150 PT AC outlet corroded

    70. 151 PT AC oUtlet corroded

  • Room/Area 151 (cant)

    71. 152

    72. 153

    73. 154

    74. 155

    Item Outlet on west wall rusty Loose switchplate

    PT AC outlet corro eel

    PTAC water aamagecf PTAC outlet melted/shorted out from water damage GFI won't trip

    Multiplex

    PT AC outlet ctamagecl Water damage

    Corrective Action Replace outlet Tighten switchplate

    Replace PTAC unit Replace PT AC outlet

    Replace with GFCI

    Remove

    Replace outlet/seal opening Repair, including any underlying damage

    75. ~1_5_6--------------~~PT~A_c_c_o_v_er_m~~-sin~--------------~ln~s~~~c-o_ve_r __________________ ~

    76. Elec room (1)

    78. 201

    No panel clearance

    Heater cover m~sin

    No self-close door Polarity reversed on outlet No working smoke detector

    Clear 3-foot area around panel

    In~ cover

    Install working self-closer on door Rewire outlet Replace smoke detector

    79. ~2-0~2----------------~N~o~se~~~-c~l-os~e-d~o_o_r~--------------~ln_s~~u_w_o_r~~-n~se_L~~~c-ID~se-r~o~n~d-o_o_r __ ~ Room light inoperable Repair/replace light/switch as necessary PTAC fail- fire damage Replace PTAC unit

    80. c2~03~--------------~N~o~se~~~-c~l~os~e~a-oo~r--------------~~~~~~~~se~r~o~n~ct~oo~r --~ PT AC fail - water damage Cover plate missing

    81. c2~----------------~N~o~se=~~--ct~os_e~a-o~o~r--------------~~~~~~~~~~~~--~ Loose outlet by door Surge protector

    82. ~2_06 ___________________ N~o~se~~--c~ose~a~oo~r----------------=ln~~~u-s_e_~--c~~~se~r_o_n_d_o_o~r --------~ Loose outlet by door Tighten outlet

    83. Outside 210 Loose outlet

    84. Storage room by 210 Damaged drywall

    Tighten outlet

    Repair drywall to maintain required 1 hour fire protection rating

    85. ~2-16------------------~o--se_~~--cl_ose=-d~oo~r--------------~~~~~~--~~~~~----Surge protector (2) Remove Smoke detector inoperable Replace smoke detector

    86. ~2=2~1 ________________ ~S=m~o~~=e_a_e_tect __ o_r_i_no~~~-6~le~--------~R-e~ta_c_e_s~m~o-~_e_a_e_tect __ o~r----------~

    87. Elec room near 222 No panel clearance Clear 3-foot area around panel

    88. ~2~23 ___________________ s_m~o~k_e_d_e_tect __ o_r_i_no~~~e-~~6~l~e __________ ~Re~~c_e_s~m~o~~-e_ct_e~tect~o~r----------~

  • Room/Area

    89. 226

    Item

    GFI fail Multiplex Surge protector - burn mark present

    Corrective Action

    Replace with GFCI Remove Remove

    90. 227 PTAC cover missin Re lace A.C cover --------------------~~~~~~~~---------------7~~~~~~~~~--------~

    91. Ice machine near 228

    Bath light inoperable Repair/replace light/switch as necessary Surge protector (2) Remove Upstairs outlet burned Replace outlet, including repair of

    underlying damage

    Wrong cord Replace improperly-sized cord

    93. ~2_3_o ________________ ~S~m~o~k~e~a~e~tect~o~r~in~o~e~r=at>~te~--------~R~e~c~e~s~m~o~k~e~d~e~tect~o~r~--------~

    Emergency ligtlt inoperat>te

    95. Elec room by 231 Damaged drywall

    RepaU" emergency fig t (must have backu~

    Repair drywall to maintain required 1 hour fire protection rating

    98. 236 No self-close door Install woriCin self-closer on ctoor ~~----------------~L~o~o~se~ou~t~le~t~i-n~b~a~th_r_o_o_m------------=Ti~g~h~te~n~o~u~t~le~t~~~----------~

    99. Outside 238

    100. Outside 239

    101. 238

    Loose outlet by desk Tighten outlet moiCe ctetector mo rat>te Re ce smoiCe ctetector

    Outlet cover broken

    Dangling can light

    No self-close door GFI fail, not tripping Smoke detector inoperable

    Replace outlet cover

    Replace fixture

    Install workmg self-closer on ctoor Replace with GFCI Replace smoke detector

    102. ~2-39------------------~N-o~s_e_u_-c_w~s~e~ct~o~o-r __ ~~----------~ln_st_a~ll~w~o-rk~in~~se_L~~-cl_o~se_r~o-n~ct-oo __ r __ ~ Bathroom light inoperable Repair/replace light/switch as necessary Loose outlet cover by door Tighten outlet cover

    103. ~2~~-1----------------~S~m~o_JC_e~ct-e~tect~o~r~ino~~~e~r~ab~l~e------~~-Re~~~la~c~e~s~m_o~IC~e~e~tect~o~r----------~

    105. Storage room near 243 Items stored too close to ceiling Storage must be kept at least 24 inches from ceiling and at least 18 inches from sprinkler heads

    106. ~2~4~5 ----------------~N~o~se~H~-:cw=se~ct~oo~r ______________ _.ln~sta--ll~w~o--m~-se_u_-_ct_os_e_r~o-n~ct-o_o_r __ ~

  • 107.

    110. 251

    Item mo e

  • Room/Area Item

    126. Hallway near 310 No escutcheon plate on sprinkler head

    127. o self-close Cloor Smoke detector ino erable

    Corrective Action

    Install escutcheon plate

    Install working sel -clOser on Cloor Re lace smoke detector

    129. ~3_2_3 __________________ N_o._se~~~--cl_o~se~a_oo~r----------------~ln~sta~ll~w~o~~~in~~s-el_~~c~to_se_r~o~n~~--~

    130. 324 o self-close door GFI fail Surge protector

    Install working self-closer on Cloor Re lace with GFCI Remove

    132. ~3-2~7--------------~-N_o __ se_t_~_cl~o~se~a~o~o~r--------------~n~~~a~ll~w~o~~~in~~se_t_~_clO~se~r~o~n~a~oo~r--~ Loose switchplate Tighten switchplate

    Surge protector Remove Bath light inoperable Repair/replace light/switch as necessary

    135. ~3_3_3 ________________ ~S~m~o~~~e~a~e-tect~o-r~m-o~e~r~ab_t_e ___________ Re~~-~~c~e~s_m_o~~~e~e-tect~o_r __________ ~

    136. ln~aU workin self-closer on

    137. Re ce smoiCe ctetector

    138. No self-clOse oor lntall self-closer on Cloor Loose outlet in bathroom Tighten outlet

    142. 347 GFI ail Rep ceGFCI No self-close door Install working self-closer on door

    143. 350 Multiplex Remove

    144. 351 Multiplex Remove

    145. ~3_s_2 __________________ P~T-~~C~c~o-ve~r~m~~-si~n~--------------=ln~sta~ll~c_o_ve_r __________________ ~ Loose outlet by microwave Tighten

    146. 353

    Multiplex Remove

    PTAC fail No round on cord for PTAC Multiplex

    Repair or rep~ce Re lace cord Remove

  • Room/Area

    147. Stairwetr3.5

    148. Elec room (3)

    151. Near elevator 4

    152.

    153. 2

    154.

    155. ~

    156.

    157.

    159. rElec room (4)

    Item

    Heater cover miSsing Emergency light inoperable

    No panel clearance No breaker for surge protector

    GFI won'tt~ Bathtub caulk missing

    EXit li ht bulb bumect out

    No self-close Cloor

    No set -close door PTAC cover missin

    Sprinkler head damaged No self-close door Smoke detector inoP.,erable Loose outlet behind bed Water damage to ceiling

    No self-dose Cloor

    No self-close Cloor

    Surge protector !Emergency liglit moperable

    Damaged drywall

    Corrective Action

    Install heater cover Repair or replace emergency light (must have backuQ QOwer)

    Clear 3-foot area around panel Install breaker

    Re lace bulb in exit light

    Repair/replace light/switch as necessary ReQair or re lace PTAC umt Rewire outlet

    Install woi'k:in self-clOser on Cloor

    lnsta working self-closer on door Install PTAC cover

    Replace spnnkler head Install working self-closer on door Replace smoke detector Tighten outlet Repair ceiling, including underlying damage

    Remove Repair or replace emergency ligtlt (must have backup power) Repair drywall to maintain required 1 hour fire protection rating

    160. L.,;4.,;;;;;2.;;;;.1 ________ ___;,N..;;.;o~se;.;.lf;....-c.;;;.;l..;;.;os;;;..;e;....d;.;..o;;..;o;....r ________ .;.;.ln;.;;;.st.;.;;a;.;.;ll....;.w.;;..;o;;.;..rk.;.;;.in~g se f-closer on door

    161. Outsiete 422 Emergency lig t mopera6le

    162. Stairwell (4)

    163. 423 No self- se door Smoke detector ino erable

    Repatr or replace emergency lig t must have backu

    Repatr or replace emergency lig t must have backu wer

    Install working self-c oser on door Re lace smoke detector

  • Room/Area 423 (cont)

    Item Loose outlet

    Corrective Action Tighten outlet

    164. ~~~2~~----------------~N~o~se~U~-c~os_e~a_o_o~r~~------------~ln_s_~~n~w~o~~~i~n~s=el~-~c~w~~~r~o~n~d~o~o~r--~ Water damage on ceiling Repair, including underlying cause

    167. 431

    Outlet burned Replace outlet, incweting repair to underl · n dama e

    SmoiCe Ctetector ino ra6te

    Room light inoperable Smo e Ctetector mtSSing PTAC outlet cover loose Loose outlet near door No self-close Ctoor

    169. ~4~3~3 _________________ N~o~se~L~~~cl~o~se~d~o~o~r ______________ ~ln~~~n~w~o~~~in~~se~l~~~c~~~r~o~n~Ct~oo~r--~

    170. ~37 rable

    172. 439 Surge protector Out of commission Room light/switch inoperable

    No se f-do~ door

    173. ~1 Surge protector No ~lf-close door

    ln~n wo ing ~lf-cl~r on aoor Re lace smoke detector Remove

    Remove Repair light/switch ln~n workin sel -closer on aoor

    Remove lnstan workm self-closer on aoor

    174. ~44~3----------------~N~o~se~ff~-~cl~o~~a~oo~r~~----------~ln~~~a~n~w~o~rk~in~~se~U~-~cl~os~e~r~o~n~a~o~o~r --~ Loose outlet behind TV Tighten outlet

    176. ~~~----------------~N~o~se~U~-~cl~os~e~d~oo~r--------------~~~~~~~~~~~~--~ Surge protector Loose outlet by door

    177. ~4~5~1----------------~P~T~A~C~c~o~ve~r~m=iss==in~~~----------~ln~~~n~c~o~ve~r~----------------~ Loose outlet near refrigerator Tighten outlet

    178.

    Multiplex Remove

    Loose bathroom outlet Shower leaking Shower tile missing

    Remove Re~ir/re lace PTAC umt Tighten outlet Repair Replace tile/recaulk

  • Room/ Area Item Corrective Action 179. ~4~5~6----------------~PT~A~C~m~o~~~e~~~o~t~e----------------~Re~Q~a~rr~o~r~r~e~~~ce~PT~A~C~un~i~t ------~

    Tile falling off Replace tiles/recaulk

    180. Elec room (4) Broken outlet Items hanging on conduit No cover plate on light switch

    Replace outlet Remove hanging items Install switchplate

    181. ~5~5=1 ________________ ~P7T~A~C~c~o~ve=r~l=oo~s_e ________________ -=n~t~e~n~c~o~ve=r~--------------~ Multiplex Remove Surge protector Remove

    182. 552 Multiplex Remove

    183. ~5~5~3----------------~P~T~A~C~f~aW~t~· ~ed~o~n~re~a~e_r ________ ~~~~~~~c~e~u~n~«~----------~ Toilet leaking

    184. Elec room (5)

    185. 555

    186. Elec room (6)

    187. StairweU 6.5 N

    188. 650

    189. Souttl haUwa (6

    190.

    Storage room (6)

    191. 652

    192. 653

    193. 654

    194. 655

    195. Stairwell 7.5

    196.

    197. Tower stairwell (N) (7)

    Cable coax cover detached Loose outlet by microwave GFCI frozen S rinlder head dama ed

    Surge protector Outlet cover missing

    PTAC cover misslfl Outlet cover off wall

    Loose outlet Surge protector

    eater cover mtSsm

    PTAC cover misslflg

    PTAC cover missm

    Extension cords

    Multiplex

    Mulitplex

    Worn bearing in exhaust fan Multiplex Extension cord

    Multiplex

    Heater cover missing

    No connector on ice maker cord Ice maiCer com uooersizea

    Emergency light loose

    Remove Replace outlet cover

    Install cover Replace cover

    Tighten outlet Remove

    Re ce cover

    Install cover

    Install cover

    Remove extension cords

    Remove

    Remove

    Replace bearing Remove Remove

    Remove

    Replace cover

    Install connector Install correct cor

    Remount emergency light

  • Room/Area 198. 7 3

    199.

    200.

    201. Near N stairwell (7)

    202. Mech room (8) by 854

    203. 851

    204. Elevator (8)

    Item PT AC cover mtssm Outlet by microwave unsealed

    P 7K outlet fail

    Emergency light loose

    Extension cords

    PTAC outlet cover unsea Lamp cord worn GFiloose

    PTAC selZ PTAC outlet fail

    Corrective Action Install cover Seal outlet

    Re~lace outlet

    Remount emergency light

    Remove extensions cords

    Seal out t cover Replace cord Tighten outlet/install spacer

    Repair or rep ce PTAC unit Re lace outlet

    205. 853 Outlet near microwave-reversed polarity Repair Ground wire external to cord Replace cord

    206. 854

    207. Stairwell (9)

    No cover on GFI

    Open WU'es Opening in ceiling

    Install cover

    RepaLr/replace wiring to code Repair opening to maintain required 1 hour fire_Qrotection

    208. ~9~5~0----------------~P~~~c~·~u~nct==w~n~6~o~x~d~~=a~ch~ed~f~ro~m~w~a~U--~~~~~~ce~------------~ Multiplex Remove Junction box by microwave detached Repair or replace Water damage on ceiling Repair, including underlying cause

    210. 952

    211. 953

    GFiloose Portable AC/HTR cord too small PTAC outlet uncovered Loose plaster on vaulted ceiling

    ok

    212. 954 PTAC outlet uncovered Switchplate loose Light in closet does not work

    213. Roof above mech room (9) Extension cords not allowed Roof exhaust vents damaged

    214. Mech room (9) Fire extinguisher not mounted No cover plate on elevator control motor Drywall damaged on ceiling by roof hatch

    215. Entry canopy Recessed lighting fixtures broken

    Tighten Replace cord with properly sized one Install outlet cover Repair, including underlying cause

    Install cover Tighten or replace Repair

    Remove all extension cords Repair/replace damaged vents

    Mount fire extinguisher Install cover plate

    Repair drywall in order to maintain the required 1 hour fire protection

    Repair or replace as necessary

  • Room/Area Item 216. Egress patnway Pathway obstructea

    Outlet near window exQosed Conduit to generator unfastened PT AC not covereCI Dryer? vent open to elements Wu-es ex osea to elements

    217. ExteriorwooCI WooCI weattier-Ciama eo

    218. [Roof ASptialt stiingles severely damaged Wood stored on roof

    219. [EXterior of entire structure Ceaar wood shake shingles not fife-retardant

    220. Stairwell doors

    221. AU-facility Cloors

    222. 5th floor

    Doors must fully close with automatic closers

    Conduit not fastened

    Corrective Action Clear t>rusti, Clet>ris, planters, PVC, ramp from area and maintain clearance Eliminate outlet to fixtures

    TAC stiielct

    Paint aU exterior wooCI elements

    Asptialt shingles must be replaced AU miscellaneous wood currently being stored on roof must be removed immediately.

    AU cedar wood shake shingles must be treated with a fire retardant or removed from building. If treated, certification of treatment must be provided to Fire ~P-_artment

    All stairwell Cloors must tiave a workmg automatic closure device to ensure the door closes fully and properly.

    AU doors must have a working automatic closure device to ensure the door closes full~ and QrOQerly.

    Strap conduit to roof