the basics of circuit breaker tripping units _ eep.pdf

Upload: sai-baba

Post on 28-Feb-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 The Basics Of Circuit Breaker Tripping Units _ EEP.pdf

    1/4

    5/23/2016 The Basics Of Circuit Breaker Tripping Units | EEP

    http://electrical-engineering-portal.com/the-basics-of-circuit-breaker-tripping-units

    Menu

    Search for articles, softwar

    Home

    Technical Articles

    Engineering Guides

    Electrical Software

    Video Trainings

    The Basics Of Circuit Breaker Tripping Units

    The Ba sics Of Circuit Breaker Tripping Units (on photo: Siemens molded case circuit breaker 'Sentron'

    Series 400 Amp Frame - 400 Amp Trip)

    Circuit breaker releases / Tripping units

    The main objective of circuit breaker tripping units and protective functions in general is to detect faults and to selectively isolate faulted parts of the system. It

    must also permit short clearance times to limit the fault power and the effect of arcing faults.

    The protective function of the circuit breaker in the power distribut ion system is determined by t he s election of the appropriate release (see Figure 1). Releases can

    be divided into:

    Thermal-magneti c t ripping units TMTU, also called electromechanical releases and

    Electronic tripping units ETU

    Figure 1 Variants of circuit breaker tripping curves

    Thermal-magnetic tripping units //

    The thermomagnet ic trip unit consists of two parts:

    The thermal trip unit Made up b y a bimetal thermal device which actuates the opening of a circuit breaker with a delay depending on the overcurrent value. This

    trip unit is intended for the protection against overloads.

    The magnetic trip unit Made up by a n electromagnetic device, with fixed (fixed instantaneous trip) or adjustable (adjustable instantaneous trip) threshold, which

    actuates the instantaneous trip of the circuit breaker on a pre-determined overcurrent value (multiple of the In) with a constant trip time (about some tens of

    milliseconds). This trip unit is intended for the protection against short circuit.

    Figure 2 TM thermal-magnetic and MA magnetic tripping units

    Go back to CB tripping units

    http://electrical-engineering-portal.com/maintenance-and-testing-of-the-overcurrent-protective-deviceshttp://electrical-engineering-portal.com/the-basics-of-circuit-breaker-tripping-unitshttp://electrical-engineering-portal.com/resourceshttp://electrical-engineering-portal.com/download-center/electrical-ms-excel-spreadsheetshttp://electrical-engineering-portal.com/download-center/books-and-guideshttp://electrical-engineering-portal.com/technical-articleshttp://electrical-engineering-portal.com/http://electrical-engineering-portal.com/
  • 7/25/2019 The Basics Of Circuit Breaker Tripping Units _ EEP.pdf

    2/4

    5/23/2016 The Basics Of Circuit Breaker Tripping Units | EEP

    http://electrical-engineering-portal.com/the-basics-of-circuit-breaker-tripping-units

    Electronic tripping units //

    The electronic trip units instead use a microprocessor to process the current signaland operate the circuit breaker opening in case of fault. In addition to this,

    electronic tripping units offer more tripping criteria which are not feasible with electromechanical releases.

    By digital processing of the signal, they provide the following protection functions:

    1. Long time-delay trip function (ANSI code: 51, AC time overcurrent relay)

    2. Short time-delay trip function (ANSI code: 51, AC time overcurrent relay)

    3. Instantaneous trip function (ANSI code: 50, instantaneous overcurrent relay)

    4. Ground-fault trip function (ANSI code: 51 N, AC time earth fault overcurrent relay).

    Figure 3 Microprocessor tripping unit (Overloads: Long time protection (Ir) Short-circuits: Short-time protection (Isd) Short-circuits: Instantaneous protection (Ii), Additional ground fault

    protection (Ig) and Neutral protection)

    1. Overload protection

    Designation: L (LT: long-time delay) , previously a-release.

    Depending on the type of release, inverse-time-delay overload releases are also available with optional characteristic curves.

    This adjustab le function simulates the effect of a bimetal conductor in a t hermal-magneti c c ircuit breaker. It reacts to overload conditions and determines how much

    current the circuit breaker will carry continuously.

    The nominal pickup point where a circuit breaker trip unit detects an overload is at 1.075 times the selected ampere rating . After the circuit breaker has picked up,

    t will not trip until the delay determined by the long-time delay adjustment has been achieved.

    2. Neutral conductor protection

    Inverse-time-delay overload releases for neutral conductors are available in a 50% or 100% ratio of the overload release . The neutral must have specific

    rotection if:

    It is reduced in size compared to the phases

    Nonlinear loads generating third order harmonics are installed

    It may be necessary to cut off the neutral for functional reasons (multiple source diagram) or safety reasons (working with power off).

  • 7/25/2019 The Basics Of Circuit Breaker Tripping Units _ EEP.pdf

    3/4

    5/23/2016 The Basics Of Circuit Breaker Tripping Units | EEP

    http://electrical-engineering-portal.com/the-basics-of-circuit-breaker-tripping-units

    3. Short-circuit protection, instantaneous

    Designation: I (INST: instantaneous), previously n-release

    Depending on the application, I-releases can either be used with a fixed or an adjustable release current Ii as well as with a switch-off or non-switch-off function.

    The instantaneo us pickup function simulates the magnetic characterist ic of a thermal-magnet ic circuit breaker. This function trips the circuit breaker with no

    ntentional time delay.

    In circuit breakers with both short-time and instantaneous pickup, the instantaneous pickup will override the short-time pickup if the instantaneous pickup is set at

    the same or lower setting than the short-time pickup.

    4. Short-circuit protection, delayed

    Designation: S (ST: short-time delay), previously z-release.

    To b e us ed for a t ime adjustment of protective functions in series. Besides the standard curves and settings, there are also optional functions for special application s:

    Definite-time overcurrent releases

    For this standard S function, the desired delay time (tsd) is defined as of a set current value (threshold I sd) (definite time, similar to the function of definite- time

    overcurrent-time protection (DMT) at the medium voltage level).

    Inverse-time overcurrent releases

    In this optional S function, the product of I 2t is always constant. In general, this function is used to improve the selectivity response (inverse time, similar to the

    function of inverse-time overcurrent-time protection at the medium voltage level.

    5. Earth-fault protection

    Designation: G (GF: ground fault) , previously g-release.

    Besides the standard function (definite-time) an optional function (I 2t = current-dependent delay) is also available.

    Figure 4 Ground-fault Characteristic Curve

    The ground-faul t function is divided into pickup and delay components (see Figure 4). The pickup portion determines at what point the circuit breaker will begin

    detecting a ground fault.

    The delay adjustment determines how long the circuit breaker will delay tripping after a ground-fault has been detected . It is supplied with both an It IN and an It OUT

    function on the circuit breakers.

    In a circuit breaker with the ground-fault function, there is a maximum unrestrained ground-fault delay provided. This delay determines the maximum amount of time

    the circuit breaker will delay during a ground-fault condition when not restrained by a downstream breaker. The maximum delay is shown by a single line and stays

    constant for all ground-fault delay switch settings.

    6. Fault-current protection

    Designation: RCD (residual current device), previously also DI (differential current interrupter).

    It detects differential fault currents up to 3 A, similar to the FI function for personal protection (max. 500 mA).

    Go back to CB tripping units

    References //

    Planning of Electric Power Distribution Technical Principles by SIEMENS

    Circuit Breaker Characteristic Trip Curves and Coordination by Schneider Electric

    Low Voltage Circuit Breakers complying with the Standards UL 489 and UL 1066 by ABB

    Recommended EE stuff //

    https://www.industry.usa.siemens.com/services/us/en/industry-services/training/self-study-courses/quick-step-courses/Documents/circuit_breakers.pdfhttp://electrical-engineering-portal.com/inspection-of-ground-fault-protection-systems
  • 7/25/2019 The Basics Of Circuit Breaker Tripping Units _ EEP.pdf

    4/4

    5/23/2016 The Basics Of Circuit Breaker Tripping Units | EEP

    http://electrical-engineering-portal.com/the-basics-of-circuit-breaker-tripping-units

    Share with engineers //

    About Author //

    Edvard Csanyi

    Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV high power busbar trunking (