6 adjustable tripping settings of a circuit breaker you must understand

Upload: armando-huaraya

Post on 01-Mar-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    1/10

    Google+

    6 Adjustable Tripping Settings of a Circuit Breaker You MUST

    Understand

    electrical-engineering-portal.com/6-adjustable-tripping-settings-circuit-breaker

    6 Adjustable Tripping Settingsof a Circuit BreakerYou MUST Know

    Basic tripping settingsof CB

    There are (at least) six basic adjustable tripping settings(functions)you must understand in order to fully

    understand how circuit breakeractually works. All these adjustable functions actually shape the time-current curveof

    circuit breakerand allows proper tripping according to the network parameters and also the proper coordination

    between upstream and downstream devices.

    Note that modern circuit breakers (MCCB, ACB) mostly have an electronic tripping unitwhich is much more

    advanced comparing to these explained here, but the basics are the same, very same.

    So, lets start with explanation!

    1. Continuous Amps (Ir)

    2. Long-Time Delay

    3. Short-Time Pickup

    1/1

    http://electrical-engineering-portal.com/example-for-coordination-of-cascaded-circuit-breakershttp://electrical-engineering-portal.com/6-adjustable-tripping-settings-circuit-breaker
  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    2/10

    4. Short-Time Delay

    5. Instantaneous Pickup

    6. Ground Fault Pickup

    Circuit breakeradjustable tripping functions

    The below time-current curvereflects one possible setup for a 1200 ampere circuit breakerwith a nominal

    (maximum continuous ampere) rating of 1000 amps. This time-current curvewill be the basis for

    discussing adjustable tripping settingsof the circuit breakers.

    2/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    3/10

    Time-current curveof a circuit breaker

    1. Continuous Amps (Ir)

    Continuous Amps (Ir) varies the level of current the circuit breaker will carry without tripping. Ir is a percentage

    of the circuit breakers nominal rating (In). Continuous amps can be adjusted from 20 to 100 percentof the circuit

    breakers nominal rating.

    For example, a 1000 amp breaker can be changed from 1000 amps to 800 amps by adjusting the

    breaker continuous amps setting to 80%.

    3/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    4/10

    Continuous current [Amps]

    Go back to CB tripping settings

    2. Long-Time Delay

    Long-time delaycauses the breaker to wait a certain amount of time to allow temporary inrush currents, such as

    those encountered when starting a motor, to pass without tripping.

    The adjustment is from 2.2 to 27 seconds at six times the continuous amps (Ir) setting.

    As shown below, the long-time delayeffects the position of an I2T slope. This means that lower levels of current will

    allow the breaker to remain online for longer periods of time.

    4/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    5/10

    Long time delay tripping settings

    Go back to CB tripping settings

    3. Short-Time Pickup

    Short-time pickupis used for selective tripping.The short-time pickupfunction determines the amount of current

    the breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits withouttripping the upstream device.

    Short-time pickupis adjustable from 1.5 to 10 times the trip unit ampere setting (Ir) .

    For example, a 1000 ampere frame can be adjusted to trip anywhere from 1500 to 10,000 amps. The switch also has

    an OFF position to eliminate short-time pickupand short-time delay.

    5/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    6/10

    Short-time pickupused for selective tripping

    Go back to CB tripping settings

    4. Short-Time Delay

    Short-time delay, used in conjunction with short-time pickup, controls the time involved in postponing a short-time

    pickuptrip.

    There are two modes: fixed time, or I 2T ramp.Fixed time is adjustable from .05 to .5 seconds.The I2T ramp

    mode is adjustable from .18 seconds to .45 seconds, providing a short inverse time ramp.

    This allows better coordination with downstream thermal-magnetic circuit breakers and fuses. A fixed instantaneous

    trip point of 10,000 amps trips the breaker automatically and overrides any pre-programmed instructions.

    6/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    7/10

    Short-time delay, used in conjunction with short-time pickup

    Go back to CB tripping settings

    5. Instantaneous Pickup

    Instantaneous pickupis used to trip the circuit breakerwith no intentional delayat any current between 2 and 40

    times the breakers continuous ampere setting (Ir).

    In this example instantaneous pickuphas been set to 10 times the continuous amp setting , or 10,000 amps (10 x

    1000) with a continuous amp setting of 1000 amps. In this case a higher setting would still trip at 10,000 amps due to

    a fixed instantaneous override of 10,000 amps which automatically trips the breaker regardless of the instantaneous

    pickupsetting.

    If the continuous amp setting had been 300 amps, setting the instantaneous pickupat 10 would make

    the instantaneous setting equal to 3000 amps, well below the fixed instantaneous override.

    7/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    8/10

    Instantaneous pickup Used to trip the circuit breakerwith no intentional delay at any current between 2 and40 times the breakers continuous ampere setting (Ir)

    Go back to CB tripping settings

    6. Ground Fault Pickup

    Ground fault pickupcontrols the amount of ground fault currentthat will cause the breaker to interrupt the circuit. The

    adjustment can be set from 20 to 70% of the maximum breaker rating. In compliance with NEC 230-95 (A), no trip

    point setting exceeds 1200 amps.

    Theground fault pickupis divided into three sections; .1s, .2s, and .4s.This feature adds a

    time delay of .1, .2, or .4 seconds to the breakers trip when a ground fault occurs.

    8/1

    http://electrical-engineering-portal.com/grounding-transformer-zig-zag-grounded-wye-delta
  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    9/10

    Ground fault pickupcontrols the amount of ground fault current that will cause the breaker to interrupt thecircuit

    Circuit breaker coordination

    The ground fault pickuptime delay feature is useful for circuit breaker coordination. In the following scheme,

    upstream breaker A has been set to .2sand downstream breakers B and C have been set to .1s.

    A ground fault occurring in the circuit supplied by B will trip the B breaker without disturbing A or C .

    Go back to CB tripping settings

    Reference //STEP 2000 Molded Case Circuit Breakers (MCCB) by SIEMENS

    9/1

  • 7/26/2019 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

    10/10

    The ground fault pickuptime delay feature is useful for circuit

    breakercoordination

    10/1