July 2008 . English BROAD Central Air Conditioning Terminals Design & Model selection Manual Product category Fan coils cooling capacity: 1.8-25kW area coverage: 10-300m 2 Air handlers cooling capacity: 25-250kW area coverage: 200-4,000m 2 fresh air flow: 3,250-32,500m 3 /h for fresh air demand of 160-1,600 people Fresh air units fresh air flow : 50-40,000m 3 /h for fresh air demand of 2-2,000 people Hot water tanks capacity: 100-200 liters Applications Fan coils for all kinds of rooms Air handlers for big rooms as well as a whole building Fresh air units supply fresh air for a single room or a whole building Hot water tanks couple with BROAD villa air conditioning or other hot water supply equipment (primary heating water heats up city water in the tank)

Upload: goodwill-technology

Post on 18-Mar-2016

212 views

Category:

Documents


0 download

DESCRIPTION

aires acondicionados

TRANSCRIPT

Page 1: Terminales

July 2008 . English

BROAD Central Air Conditioning TerminalsDesign & Model selection Manual

■ Product category

● Fan coils cooling capacity: 1.8-25kW area coverage: 10-300m2

● Air handlers cooling capacity: 25-250kW area coverage: 200-4,000m2

fresh air flow: 3,250-32,500m3/h for fresh air demand of 160-1,600 people ● Fresh air units fresh air flow : 50-40,000m3/h for fresh air demand of 2-2,000 people ● Hot water tanks capacity: 100-200 liters

■ Applications

● Fan coils for all kinds of rooms● Air handlers for big rooms as well as a whole building● Fresh air units supply fresh air for a single room or a

whole building● Hot water tanks couple with BROAD villa air

conditioning or other hot water supply equipment (primary heating

water heats up city water in the tank)

Page 2: Terminales

CONTENTS

Fan coils

GeneralP&I diagramSpecificationsPerformance curves Model selectionAccessories and supply scopeDimensionsInstallation tips

Air handlers

GeneralSpecificationsPerformance curves Accessories and supply scopeDimensionsInstallation tips

Fresh air units

GeneralSpecificationsPerformance curves Accessories and supply scopeDimensionsInstallation tips

Tips for fresh air design

Hot water tanks

SpecificationsModelsAccessories and supply scopeDimensionsInstallation tips

13489111231

333536363739

404243434445

46

5050505152

Page 3: Terminales

Compared with motorcar, aircraft and other industrial technologies, BROAD fan coils had nothing to be proud of. However, once you know from the following "comparativism" how much BROAD has contributed to innovations of human air conditioning technologies in the past 100 years, you will have to term it a miracle.

1

Cooling capacity:1.8~25kW Area coverage: 10~300 m2

Suitable for all kinds of rooms

Health ScienceElectrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open design, all by a slight touchAcoustics• The inverter fan is equipped with stepless frequency control. • The ultra-thin aluminum fan blade operates without noise. • If the fan is operating at low speed, you can not hear any noise

but your own breathing in serene nights. Aesthetics• Not gaudy, no show-off, not even one redundancy. Only beauty. • Metal shell and coated with top quality car paint. It will still

appear new after several decades. • 139 varieties available in any color, match well with any interior

design style. Thermodynamics • As the density of cold air is greater than that of hot air, low

position installation of fan coils saves energy dramatically, namely 30-60% in cooling and 10-40% in heating operation.

• Customers can choose from a selection of over 100 varieties for low position installation.Economics• Use a heat meter to measure air conditioning consumption, implement energy saving management, and actualize cost evaluation.• The market price of a heat meter alone is more expensive than a conventional air-con, yet its energy-saving potentials are huge.• The heat meter uses an ultrasonic flow meter to measure the flow rate accurately and constantly. It cooperates with two thermometers at Class 0.01°C to measure cold/heat energy accurately. • Record energy consumption and expenses of the moment, today, this month, this year and last year.Engineering• All pipe fittings that were previously site mounted are now installed in the factory. • Factory fabrication eliminates quality risks and avoids redoing. • Achieving central air conditioning industrialization. Lazybones' Philosophy• Intelligent switch enables year-round operator-free . • Auto on/off per ambient temperature saves both labor and energy.

Fan coils

Note: Features, functions and accessories of all 139 fan coil models conform to this illustration. This product is compatible to any air conditioning system and applicable to both new and replacement projects.

Comparativism• The conventional central air conditioning indoor units (fan coils)

are nothing but a combination of “fan + coil + water pan + shell + filter”. The mesh of their filters is only a little bit smaller than a matchstick. Helplessly dirty inside, they have become seedbeds for pathogens, as their interiors are completely enclosed and never cleanable.

• The conventional split units are similar to “fan coils” with only an additional temperature control. Some products have introduced so called “hi-techs” such as photocatalyst, silver ion…which are usually a hoax.

General

Conventional fan coils

Conventional split units

2

Page 4: Terminales

P&I diagram

3

L1 L2 L3 L4

BBA RFM

YK XK

T2 T1 C H

dirty air inlet

SNKZDW

SS

power supply

CCQYA ZMK

HXT CDY

T4F1

F3

T3

CFK

GLQUSSP

EM A/C water supply

RSMJK

DRVFJ

condensate outlet

F2

XFN

PG

clean air outletcoarse filter

electrostatic cleaner

active carbon

A/C water return

Controlled objectsF1: CCQ:

FJ:XFN: L1:L2:L3:L4:

SensorsT1:T2:T3:T4:USH:C:

Control devicesSS:SNK:DRV:CDY:

EM:XK:YK:ZMK:CFK:RSM:

JK:RFM:

BBA:

OthersPG:YA:HXT:ZDW:SP:F2:

F3:GLQ:

A/C water motor valve electrostatic cleaner (positive tungsten filament + negative aluminum plate)fanfresh air valve*1 st loop lighting control*2nd loop lighting control*3rd loop lighting control*4th loop lighting control*

indoor temp. sensoroutdoor temp. sensor*A/C water inlet temp. sensorA/C water outlet temp. sensor ultrasonic flow meter*hygrometer*CO2 sensor*

safety switchfan coil control boardmotor driveelectrostatic cleaner power supplyintegraphcontrollerremote control*lighting control board*fresh air valve control board*wired communication module*central controller*wireless communication module*Building manager and gateway*

coilauto air vent active carboncoarse filterwater collection panmanual valve (shut off and regulating)manual valve (shut off)filter

Notes:1. * indicates options2. Signal output from actuator Signal input from sensor Communication3. Either optional wired or wireless

communication.

Page 5: Terminales

No. NameCode

Cooling

capacity

kW

Air

Āow

m3/h

Water

Āow

kg/h

Water

resist-

ance

kPa

Min.

noise

level

dB(A)

Max.

noise

level

dB(A)

Power

demand

W

Weight

kg

Dimensions

(L×W×H)

mm

A/C

W.

pipe

mm

Conden-

sate

pipe

mm

Air

distance

Energy

saving

rating

Installa-

tion

height

mm

Applica-

tions

1 Thin 1.8 360 221 30 23 37 45 18 1140x180x307 DN15 Φ16

m

200

2 2.7 540 331 30 25 39 50 23 1500x180x307 DN15 Φ16

a

above

3 AA 3.6 720 442 30 27 41 78 28 1800x180x307 DN15 Φ16 floor

4 Curve 1.8 360 221 30 23 37 45 16 1140x180x330 DN15 Φ16 8

5 2.7 540 331 30 25 39 50 20 1500x180x330 DN15 Φ16

a

6 AD 3.6 720 442 30 27 41 78 26 1800x180x330 DN15 Φ16

7 Bend 1.8 360 221 30 23 37 45 17 1140x195x328 DN15 Φ16 8

8 2.7 540 331 30 25 39 50 24 1500x195x328 DN15 Φ16

b

1800

9 AG 3.6 720 442 30 27 41 78 28 1800x195x328 DN15 Φ16 ~2000

10 Semi- 1.8 360 221 30 23 37 45 18 1140x195x355 DN15 Φ16 8 above

11 circle 2.7 540 331 30 25 39 50 25 1500x195x355 DN15 Φ16

b

floor

12 *AJ 3.6 720 442 30 27 41 78 29 1800x195x355 DN15 Φ16

13 Triangle 1.8 360 221 30 23 37 45 19 1140x270x375 DN15 Φ16 8

14 2.7 540 331 30 25 39 50 26 1500x270x375 DN15 Φ16

b

15 *AM 3.6 720 442 30 27 41 78 30 1800x270x375 DN15 Φ16

16 L.Thin 1.8 360 221 30 23 37 45 18 307x180x1140 DN15 Φ16 10 600

17 2.7 540 331 30 25 39 50 23 307x180x1500 DN15 Φ16

b

above

18 AB 3.6 720 442 30 27 41 78 28 307x180x1800 DN15 Φ16 floor

19 R.Thin 1.8 360 221 30 23 37 45 18 307x180x1140 DN15 Φ16 10 for

20 2.7 540 331 30 25 39 50 23 307x180x1500 DN15 Φ16

b

1.8kW

21 AC 3.6 720 442 30 27 41 78 28 307x180x1800 DN15 Φ16

22 L.Curve 1.8 360 221 30 23 37 45 16 330x180x1140 DN15 Φ16 10 350

23 2.7 540 331 30 25 39 50 20 330x180x1500 DN15 Φ16

b

above

24 AE 3.6 720 442 30 27 41 78 26 330x180x1800 DN15 Φ16 floor

25 R.Curve 1.8 360 221 30 23 37 45 16 330x180x1140 DN15 Φ16 10 for

26 2.7 540 331 30 25 39 50 20 330x180x1500 DN15 Φ16

b

2.7kW

27 AF 3.6 720 442 30 27 41 78 26 330x180x1800 DN15 Φ16

28 L.Bend 1.8 360 221 30 23 37 45 17 328x195x1140 DN15 Φ16 10 200

29 2.7 540 331 30 25 39 50 24 328x195x1500 DN15 Φ16

b

above

30 AH 3.6 720 442 30 27 41 78 28 328x195x1800 DN15 Φ16 floor

31 R.Bend 1.8 360 221 30 23 37 45 17 328x195x1140 DN15 Φ16 10 for

32 2.7 540 331 30 25 39 50 24 328x195x1500 DN15 Φ16

b

3.6kW

33 AI 3.6 720 442 30 27 41 78 28 328x195x1800 DN15 Φ16

34 L.Semi- 1.8 360 221 30 23 37 45 18 355x195x1140 DN15 Φ16 10

35 circle 2.7 540 331 30 25 39 50 25 355x195x1500 DN15 Φ16

b

36 *AK 3.6 720 442 30 27 41 78 29 355x195x1800 DN15 Φ16

37 R.Semi- 1.8 360 221 30 23 37 45 18 355x195x1140 DN15 Φ16 10

38 circle 2.7 540 331 30 25 39 50 25 355x195x1500 DN15 Φ16

b

39 *AL 3.6 720 442 30 27 41 78 29 355x195x1800 DN15 Φ16

40 L.Triangle 1.8 360 221 30 23 37 45 19 375x270x1140 DN15 Φ16 10

41 2.7 540 331 30 25 39 50 26 375x270x1500 DN15 Φ16

b

42 *AN 3.6 720 442 30 27 41 78 30 375x270x1800 DN15 Φ16

43 R.Triangle 1.8 360 221 30 23ß 37 45 19 375x270x1140 DN15 Φ16 10

44 2.7 540 331 30 25 39 50 26 375x270x1500 DN15 Φ16

b

45 *AO 3.6 720 442 30 27 41 78 30 375x270x1800 DN15 Φ16

Fan coils - specifications

室内机

4

Serie

s T

hin

Se

ries 8

Page 6: Terminales

5

Fan coils - specifications

Serie

s T

hic

k Se

ries

No. NameCode

Cooling

cap

kW

Air

Āow

m3/h

Water

Āow

kg/h

Water

resist-

ance

kPa

Min.

noise

level

dB(A)

Max.

noise

level

dB(A)

Power

demand

W

Weight

kg

Dimensions

(L×W×H)

mm

A/C

W.

pipe

mm

Conden-

sate

pipe

mm

Air

distance

Energysaving

rating

Installa-

tion

height

mm

Applica-

tions

52 Thick

DB

3.6 648 442 30 27 41 130 32 890x264x465 DN15 Φ16 12 a 250above

floor53 4.5 810 552 30 30 43 130 35 1060x264x465 DN20 Φ16

54 5.4 972 663 40 32 43 140 44 1260x264x465 DN20 Φ16

55 7.2 1296 884 40 34 45 140 50 1450x264x465 DN20 Φ16

56 9 1620 1105 40 36 48 245 61 1760x264x465 DN25 Φ16

57 12 2160 1473 50 40 50 260 70 2200x264x465 DN25 Φ16

52 L.Thick 3.6 648 442 30 27 41 130 32 465x264x890 DN15 Φ16 12 100

53 4.5 810 552 30 30 43 130 35 465x264x1060 DN20 Φ16

b

~500

54 DC 5.4 972 663 40 32 45 140 44 465x264x1260 DN20 Φ16 above

55 7.2 1296 884 40 34 46 140 50 465x264x1450 DN20 Φ16 floor

56 9 1620 1105 40 36 48 245 61 465x264x1760 DN25 Φ16

57 12 2160 1473 50 40 50 260 70 465x264x2200 DN25 Φ16

58 R.Thick 3.6 648 442 30 27 41 130 32 465x264x890 DN15 Φ16 12

59 4.5 810 552 30 30 43 130 35 465x264x1060 DN20 Φ16

b

60 DD 5.4 972 663 40 32 45 140 44 465x264x1260 DN20 Φ16

61 7.2 1296 884 40 34 46 140 50 465x264x1450 DN20 Φ16

62 9 1620 1105 40 36 48 245 61 465x264x1760 DN25 Φ16

63 12 2160 1473 50 40 50 260 70 465x264x2200 DN25 Φ16

64 Oval 3.6 648 442 30 27 41 130 36 1080x264x600 DN15 Φ16 12 1500

65 5.4 972 663 40 32 45 140 44 1480x264x660 DN20 Φ16

b

above

66 DQ 9 1620 1105 40 36 48 245 63 2000x264x680 DN25 Φ16 floor

67 12 2160 1473 50 40 50 260 78 2460x264x760 DN25 Φ16

68 L.Oval 3.6 648 442 30 27 41 130 36 600x264x1080 DN15 Φ16 15 Central

69 5.4 972 663 40 32 45 140 44 660x264x1480 DN20 Φ16

b

line

70 DR 9 1620 1105 40 36 48 245 63 680x264x2000 DN25 Φ16 1,200

71 12 2160 1473 50 40 50 260 78 760x264x2460 DN25 Φ16 ~1,600

72 R.Oval 3.6 648 442 30 27 41 130 36 600x264x1080 DN15 Φ16 15 above

73 5.4 972 663 40 32 45 140 44 660x264x1480 DN20 Φ16

b

floor

74 DS 9 1620 1105 40 36 48 245 63 680x264x2000 DN25 Φ16

75 12 2160 1473 50 40 50 260 78 760x264x2460 DN25 Φ16

76 Long- 7.2 1296 884 40 34 46 300 53 1450x304x465 DN20 Φ16 20 1800

77 rangeDE

12 2160 1473 50 40 50 450 79 2200x304x465 DN25 Φ16

c

abovefloor

78 Vertical 7.2 1296 884 40 34 46 300 53 465x304x1450 DN20 Φ16 20 100

79 Long- 12 2160 1473 50 40 50 450 79 465x304x2200 DN25 Φ16

b

~1,000

range above

DF floor

Page 7: Terminales

6

Serie

s W

all

Built

-in S

erie

s A

van

t-g

ard

e S

erie

s

No. NameCode

Cool-

ing

capa-

city

kW

Air

Āow

m3/h

Water

Āow

kg/h

Water

resist-

ance

kPa

Min.

noise

level

dB(A)

Max.

noise

level

dB(A)

Power

demand

W

Weight

kg

Dimensions

(L×W×H)

mm

A/C

W.

pipe

mm

Conden-

sate

pipe

mm

Air

distance

Energy

saving rating

Installa-

tion

height

mm

Applica-

tions

80 Piano 9 1350 1105 40 36 46 300 71 1080x430x900 DN25 Φ16 15 Floor

CC

a

standing

81 Cube 4.5 675 552 40 30 41 110 32 500x500x550 DN20 Φ16 10 Rear

82 CD 9 1350 1105 40 36 48 220 64 1000x500x550 DN25 Φ16

a

200

83 vase- 3.6 540 442 30 27 39 78 27 406x310x993 DN15 Φ16 10 against

stand*CE

a

wall

84 Diamond 3.6 720 442 30 27 41 90 36 820x180x1140 DN15 Φ16 8x2 700

85 *DP 5.4 1080 663 40 32 45 100 58 820x180x1500 DN15 Φ16

b

Above floor

86 Column 1.8 360 221 30 23 37 45 19 1020xΦ260 DN15 Φ16 8 1800

87 AP 2.7 540 331 30 25 39 50 23 1420xΦ260 DN15 Φ16

c

Above

88 3.6 720 442 30 27 41 78 30 1720xΦ260 DN15 Φ16 floor

89 Polygon 1.8 360 221 30 23 37 45 19 1020x225x290 DN15 Φ16 8

90 AR 2.7 540 331 30 25 39 50 23 1420x225x290 DN15 Φ16

c

91 3.6 720 442 30 27 41 78 30 1720x225x290 DN15 Φ16

92 Vertical 1.8 360 221 30 23 37 45 19 Φ260x1020 DN15 Φ16 10 100

93 Column 2.7 540 331 30 25 39 50 23 Φ260x1420 DN15 Φ16

b

Above

94 *AQ 3.6 720 442 30 27 41 78 30 Φ260x1720 DN15 Φ16 floor

95 Vertical 1.8 360 221 30 23 37 45 19 290x225x1020 DN15 Φ16 10 or floor

96 Polygon 2.7 540 331 30 25 39 50 23 290x225x1420 DN15 Φ16

b

standing

97 *AS 3.6 720 442 30 27 41 78 30 290x225x1720 DN15 Φ16 with a retainer

98 Jet 5.4 810 663 40 32 41 130 42 Φ600x750 DN15 Φ16 15 2000

CA

c

Above

floor

99 Wall 2.7 540 331 30 25 39 50 23 1500x210x315 DN15 Φ16 10 100

100 Built-in 3.6 720 442 30 27 41 78 31 1800x210x315 DN15 Φ16

a

Above

101 DG 4.5 810 552 30 30 43 130 36 1180x314x465 DN20 Φ16 floor

102 5.4 972 663 40 32 45 140 41 1380x314x465 DN20 Φ16

103 7.2 1296 884 40 34 46 140 50 1570x314x465 DN20 Φ16

104 9 1620 1105 40 36 48 245 55 1920x314x465 DN25 Φ16

105 12 2160 1473 50 40 50 260 74 2363x314x465 DN25 Φ16

106 L.Wall 2.7 540 331 30 25 39 50 23 315x210x1500 DN15 Φ16 10

107 Built-in 3.6 720 442 30 27 41 78 31 315x210x1800 DN15 Φ16

b

108 DH 4.5 810 552 30 30 43 130 36 465x314x1180 DN20 Φ16

109 5.4 972 663 40 32 45 140 41 465x314x1380 DN20 Φ16

110 7.2 1296 884 40 34 46 140 50 465x314x1570 DN20 Φ16

111 9 1620 1105 40 36 48 245 55 465x314x1920 DN25 Φ16

112 12 2160 1473 50 40 50 260 74 465x314x2363 DN25 Φ16

113 R.Wall 2.7 540 331 30 25 39 50 23 315x210x1500 DN15 Φ16 10

114 Built-in 3.6 720 442 30 27 41 78 31 315x210x1800 DN15

b

115 DI 4.5 810 552 30 30 43 130 36 465x314x1180 DN20 Φ16

116 5.4 972 663 40 32 45 140 41 465x314x1380 DN20 Φ16

117 7.2 1296 884 40 34 46 140 50 465x314x1570 DN20 Φ16

118 9 1620 1105 40 36 48 245 55 465x314x1920 DN25 Φ16

119 12 2160 1473 50 40 50 260 74 465x314x2363 DN25 Φ16

120 Wall Built 5.4 972 663 40 32 45 168 40 465x314x1380 DN20 Φ16 15

121 in Duct 9 1620 1105 40 36 48 310 66 465x314x1920 DN25 Φ16

b

122 DJ 12 2160 1473 50 40 50 450 71 465x314x2363 DN25 Φ16

123 Floor 3.6 720 442 30 27 39 78 35 1800x331x269 DN15 Φ16 6 Floor

124 DM 12 2160 1473 50 40 50 260 74 2363x511x377 DN25 Φ16

b

level

m

Page 8: Terminales

No. NameCode

Cool-

ing

capa-

city

kW

Air

Āow

m3/h

Water

Āow

kg/h

Water

resist-

ance

kPa

Min.

noise

level

dB(A)

Max.

noise

level

dB(A)

Power

demand

W

Weight

kg

Dimensions

(L×W×H)

mm

A/C

W.

pipe

mm

Conden-

sate

pipe

mm

Air

distance

Energy

saving rating

Installa-

tion

height

mm

Applica-

tions

125 Ceiling 4.5 810 552 30 30 41 140 50 1020x1020x190 DN15 Φ16 10 Ceiling

126 Square 7.2 1296 884 40 34 45 140 70 1020x1020x270 DN20 Φ16

d

mounted

*DN

127 Wing 4.5 810 552 30 30 41 168 37 1200x880x315 DN20 Φ16 15

128 *DO 7.2 1296 884 40 34 45 300 56 1600x880x315 DN20 Φ16

d

129 Ceiling Built- 4.5 810 552 30 30 43 168 35 1180x465x314 DN20 Φ16 15 Ceiling

130 in Duct 5.4 972 663 40 32 45 178 40 1380x465x314 DN20 Φ16

d

mounted and

131 DK 12 2160 1473 50 33 50 460 74 2363x465x314 DN25 Φ16 connected to air ducts

132 Ceiling 2.7 540 331 30 25 39 60 29 1500x315x210 DN15 Φ16 6 Ceiling

133 Built-in 4.5 810 552 30 30 43 140 34 1180x465x314 DN20 Φ16

d

mounted

134 DL 5.4 972 663 40 32 45 150 40 1380x465x314 DN20 Φ16

135 12 2160 1473 50 33 48 270 74 2363x465x314 DN25 Φ16

136 High 18 2700 2210 55 32 50 450 238 840x380x2590 DN25 Φ20 25 Inside

137 Board 25 3750 3100 60 34 53 620 298 840x380x3200 DN32 Φ20

b

the hall,

EH at wall

138 High 18 2700 2210 55 32 50 450 226 530x530x2590 DN25 Φ20 corner or

139 Stripe 25 3750 3100 60 34 53 620 282 530x530x3200 DN32 Φ20 against

*EK the wall

7

residences hotelrooms

officebuildings theatres hospitals

shops,restaurants,public places

publicpassages

airports,exhibition halls,supermarkets,lobbies

Notes:1. Rated conditions for cooling: inlet air dry bulb temperature: 27 oC, wet bulb temperature: 19.5 oC, chilled water outlet/inlet temperature: 14/7 oC rated conditions for heating: inlet air dry bulb temperature: 21 oC, heating water outlet/inlet temperature: 55/65 oC2. Heating capacity is 1.5 times of cooling capacity3. Noise level is measured 1m distance from the unit4. “Left” or “right” refers to air blow direction. Arrow indicates the angle between blow direction and installation plane. 45° downwards 0° downwards 45° leftwards 45° rightwards 0° leftwards 0° rightwards5. Energy saving rating a: 30~60%, b: 20~40%, c: 10~30%, d: 0% (comparison with conventional ceiling mounted fan coils. Higher the room, more energy saving)6. * means standard lights, and ※ means optional lights.

7. Nomenclature: code letter + cooling capacity(kW), e.g. 2.7kW thin model is named as AA2.78. Back pressure for wall built-in duct and ceiling built-in models: 4.5 kW:50Pa, 5.4 kW:55Pa, 12 kW:65Pa9.

Symbols for recommended applications:

Fan coils - specifications

Serie

s C

eili

ng

bu

ilt-in

Se

ries

Larg

e S

erie

s

m

Page 9: Terminales

0 20 40 60 80 100 120

Air flow %

140

100

50

DJ/DK12

DJ/DK5.4

DJ/DK4.5

Accessories(optional)

Common Colors (light paint)

8

Performance curves

Chilled water temperature vs.Cooling capacity

Chilled water flowrate vs. Cooling capacity

Air flow vs. static pressure (for wall built-in duct and ceiling built-in duct models)

140

120

100

80

60

40

23 24 25 26 27 28

Return air temp. ℃

5℃

6℃

7℃

8℃

9℃

10℃

100

95

90

85

80

75

7050 60 70 80 90 100

Flowrate %

Co

olin

g c

ap

ac

ity %

Co

olin

g c

ap

ac

ity %

Exte

rna

l sta

tic p

ress

ure

Pa

Wine red

Lilac

Ferrari yellow

Light brownish

Black

Skin

Ocean blue

Silver grey

Antique brass

Medium grey

Orange

Forest green

No. Name Applicable to Function

1 Retainer Vertical Column,

Vertical Polygon

for floorstandingfan coils

2 cone-tube supporter

Vertical Column,

Vertical Polygon

for floorstandingfan coils

3 Remote control

1 for each room or 1 for every

3 fan coils is recommended

control thefan coil and

lighting

4 Remote control socket

Remote control hold remote control

5 4-loop lighting control

Fan coils lighting remote control

6 Outdoor thermometer

Fan coils, air handlers

on/off per ambient

temperature

7 CO2 sensor price reduction if not selected

oxygen deficiency

alarm

8 Ultrasonicflowmeter

price reduction if not selected

energy metering

9 Wired communication module

Fan coils, air handlers

central control

10 Fresh air valve control Fan coils Control freshair valve

11 Bracket Thin,Curve, Thick models

For occasions where wall mounting is not possible

12 Bracket All vertically installed models

(i.e. left / right models)

13 Diagonal/ flat grille cover all models for concealed installation

(cellular coveris the standard)

interior decoration

14 Common colors all models matching the interior design

15 Optional colors and shell material

all models matching the interior design

Page 10: Terminales

LoadBROAD standard: 40-70W/m2 for apartments or hotels; 50-80W/m2 for offices; 60-90W/m2 for villas; 80-130W/m2 for shops ,restaurants or lobbies; 130-210W/m2 for theatres, exhibition halls or airports. High load is to be designed for places of high population density, high storey and high ratio of wall to floor area, and places of temporary use (quicker air conditioning effect can be achieved). The total cooling load of fan coils(including fresh air load) could be 15%-30% higher than that of the chiller. Fan coil selection is upon actual demand and doesn’t allow any redundancy. In case it’s insufficient, a fan coil of exposed installation can be easily replaced with a larger model.

QuantityUsually one for each room. 2 units can be considered for room over 100m2. More units make higher investment.

Style Usually a suitable fan coil is readily available to match the interior design once the interior design style is confirmed. The standard color is recommended. If customers want to change it even during the installation, it can be easily replaced with a cover of required color.

Energy savingLow position installation at wall corner can save 30%-60% energy compared with ceiling-mounted installation. Do not select ceiling suspended or ceiling built-in models except for the replacement of old system. Vertical models can be considered for rooms with limited space. Furthermore, heat meters may help facilitate behavioral energy saving greatly.

CostLow position installation of fan coils not only saves operating cost, but also reduces huge investment 1. reduce fan coil load 2. reduce chiller load3. save pipeline and installation cost 4. save building height.

ComfortSome people are even sensitive to very slight noise. If the inverter-controlled motor is adopted, no noise can be heard at low speed. Actually 90% of time air conditioning systems are operating under partial load. The units cannot blow straightly to places where people usually stay.

Features BROAD fan coils consist of 6 series & 139 varieties. A careful study of their features should be made before selection.Product photos and typical applications are available in our catalog.

• Thin series The delicate styled thin series fan coils have a great varieties and present vivid individualities. They can cover an area from 10-200m2. The prices are relatively higher. Curve and Thin Models are recommended for energy saving.Cooling capacity: 1.8kW, 2.7kW, 3.6kWHeating capacity: 2.7kW, 4kW, 5.4kWArea coverage: 10-50m2

• Thick seriesThick series with magnificent styles can serve an area of 20-1500m2. Their prices (per kW or RT cooling capacity) are relatively low. They are not only suitable for low-end places but also medium and up-market locations, especially the Oval Model with specially ordered cover ( such as mirror stainless steel cover, brushed stainless steel cover, or even the luxurious titanium cover). Thick Model is recommended as the priority, which is the most energy saving.Cooling capacity: 3.6kW,4.5kW,5.4kW,7.2kW, 9kW,12kWHeating capacity: 5.4kW,6.9kW,8.1kW,10.8kW, 13.5kW,18kWArea coverage: 20-160m2

• Avant-garde seriesVarious varieties with unique characteristics are completely different from conventional fan coils. They are suitable for places from 10-500m2, and with higher prices. Vertical Column Model and Polygon Model can be wall-mounted or at wall corner, or floor-standing with a retainer (1.8kW model even can be equipped with a cone-tube supporter). In this series Piano Model is recommended as the first choice, as it is suitable for most places with easy installation, small space occupancy (based upon cooling capacity) and energy saving. It can be multi-functional: a food table, a TV set stand, a podium, a reception desk or even a bar counter.Cooling capacity: 1.8kW,2.7kW,3.6kW,4.5kW, 5.4kW,9kWHeating capacity: 2.7kW,4kW,5.4kW,6.8kW, 8.1kW,13.5kWArea coverage: 10-120m2

99

Fan coils - model selection

Page 11: Terminales

• Wall built-in seriesSimplicity is the style, and it can serve an area of 15-500m2. Either wall built-in, floor built-in, or cabinet built-in, especially suitable for complicated public areas. Cellular cover is standard for Wall Built-in Model, but grille cover or diagonal grille cover is optional. Wall Built-in Model is recommended as the first choice for its energy saving. In addition, Wall Built-in Duct Model can connect multiple air ducts up to 2~6 rooms. In this case the initial cost and installation cost are reduced dramatically, which even can be affordable for low-cost houses (ducts are not long, not much dust inside, furthermore, the electrostatic cleaner can kill more than 90% bacteria inside).Cooling capacity: 2.7kW, 3.6kW, 4.5kW, 5.4kW, 7.2kW, 9kW, 12kWHeating capacity: 4kW, 5.4kW, 6.8kW, 8.1kW, 10.8kW, 13.5kW, 18kWArea coverage: 15~160m2

• Ceiling built-in seriesBROAD does not recommend this series due to its non energy saving (fan coils are highly ceiling built-in and whole room space consumes energy). It can be adopted to replacement for old buildings where all the fan coils are ceiling built-in. A special note: this series is not suitable for rooms of 3m+ high because of too much energy waste as well as initial cost waste( the model size of chiller and fan coils has to be increased).In addition, cellular cover is standard for Ceiling Built-in Model and CeilingBuilt-in Duct Model, but flat grille cover or diagonal grille cover is optional.Cooling capacity: 2.7kW, 4.5kW,5.4kW, 7.2kW, 12kWHeating capacity: 4kW, 6.8kW, 8.1kW, 10.8kW,18kWArea coverage: 15-100m2

• Large seriesThe style is designed to impress and inspire. It can serve any spacious area larger than 100m2 with 25m far-reaching air blow. It can be installed at the center or against wall. High Stripe Model even can be at the corner. Both sides of High Board Model have covers accessible to maintenance. It can be used as a billboard. The only inconvenience is that a ladder is needed for maintenance.Cooling capacity: 18kW, 25kWHeating capacity: 27kW, 37.5kWArea coverage: 100~300m2

Options

• CO2 sensorCustomers can select one piece only if several fan coils are installed in the room.

• Ultrasonic flow meterIt can be skipped if the customer doesn’t want to have air conditioning billing and energy saving management.

• Outdoor temp. sensorCustomer can select 1 piece if several fan coils are installed in the room. It is not necessary for a building of closed type which can not be cooled down by opening windows or fresh air.

• Lighting remote controlEach fan coil can control 4 lighting loops. It is not necessary if the customer doesn’t want to control lighting by fan coil remote control or implement illumination management for energy saving through BMS.

• Fresh air valve controlEach fan coil has optional 3-position control interface for fresh air valve upon CO2 concentration.

• Color"Standard" colors of each type are indicated on the first page of each series in the catalog of ‘REDEFINE LIFE’. 7% additional price to be charged for “basic” colors. “optional” colors can be offered on case base, but the additional cost may be very high. Colors can be mixed according to customer’s color palette. Special materials are also available for special orders, such as gold-plating in right figure (it is very expensive with long lead time)

• Remote controlIt controls not only temperature and air speed, but also the room lighting. We recommend one for each room. If several fan coils are installed in a room, one for every three fan coils is recommended. It may not be necessary for public places like hotel rooms.

1010

Page 12: Terminales

ModelName

Cooling Capacity

kW

Expansion bolt Controller

(pc)

Controller holder

(pc)

Active carbon

(pc)

Bellow with sealing gasket

Braze welded ends

Pre-installed valve

Specsmm

Qnty(pc)

Specsmm

Lengthmm

Qnty(pc)

Specsmm

Qnty(pc)

Specsmm

Qnty(pc)

Thin Series 1.8/2.7/3.6 M6×80 4 1 1 4 DN15 200 2 15 2 DN15 1

Thick

3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1

4.5/5.4/7.2 M8×80 4 1 1 4 DN20 200,150 1 each 22 2 DN20 1

9/12 M8×80 4 1 1 4/6 DN25 200,150 1 each 28 2 DN25 1

L.Thick 3.6 M8×80 4 1 1 4 DN15 150,300 1 each 15 2 DN15 1

4.5/5.4/7.2 M8×80 4 1 1 4 DN20 150,300 1 each 22 2 DN20 1

9/12 M8×80 4 1 1 4/6 DN25 150,300 1 each 28 2 DN25 1

R.Thick 3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1

4.5/5.4/7.2 M8×80 4 1 1 4 DN20 200 2 22 2 DN20 1

9/12 M8×80 4 1 1 4/6 DN25 200 2 28 2 DN25 1

Oval R.Oval

3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1

5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1

9/12 M8×80 4 1 / 4/6 DN25 200 2 28 2 DN25 1

L.Oval 3.6 M8×80 4 1 1 4 DN15 200,300 1 each 15 2 DN15 1

5.4 M8×80 4 1 / 4 DN20 200,300 1 each 22 2 DN20 1

9/12 M8×80 4 1 / 4/6 DN25 200,300 1 each 28 2 DN25 1

Long-range 7.2 M8×80 4 1 1 4 DN20 200 2 22 2 DN20 1

12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1

Vertical long-range

7.2 M8×80 4 1 1 4 DN20 200,250 1 each 22 2 DN20 1

12 M8×80 4 1 / 6 DN25 200,250 1 each 28 2 DN25 1

Piano 9 M8×80 4 1 1 4 DN25 300.500 1 each 28 2 DN25 1

Cube 4.5 M6×80 4 1 1 4 DN20 200,300 1 each 22 2 DN20 1

9 M6×80 4 1 1 4 DN25 200,300 1 each 28 2 DN25 1

Vase-stand 3.6 M6×80 4 1 1 4 DN15 200 2 15 2 DN15 1

Diamond 3.6 M6×80 8 2 2 4 DN15 200 4 15 4 DN15 2

5.4 M6×80 8 2 2 4 DN15 200 4 15 4 DN15 2

Column Polygon

1.8/2.7/3.6 M6×80 4 1 1 4 DN15 150 2 15 2 DN15 1

Jet 5.4 M10×80 4 1 / 4 DN15 200 2 15 2 DN15 1

Wall Built-in 2.7/3.6 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1

4.5/5.4/7.2 M8×80 4 1 / 4 DN20 250 2 22 2 DN20 1

9/12 M8×80 4 1 / 4/6 DN25 250 2 28 2 DN25 1

L.Wall Built-inR.Wall Built-in

2.7/3.6 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1

4.5/5.4/7.2 M8×80 4 1 / 4 DN20 250,300 1 each 22 2 DN20 1

9/12 M8×80 4 1 / 4/6 DN25 250,300 1 each 28 2 DN25 1

Wall Built-in Duct

5.4 M8×80 4 1 / 4 DN15 250,300 1 each 22 2 DN15 1

9/12 M8×80 4 1 / 4/6 DN25 250,300 1 each 28 2 DN25 1

Floor 3.6 M6×80 4 1 / 4 DN15 150,200 1 each 15 2 DN15 1

12 M8×80 4 1 / 6 DN25 350,200 1 each 28 2 DN25 1

CeilingSquare

4.5 M8×80 8 1 / 4 DN15 200 2 15 2 DN15 1

7.2 M8×80 8 1 / 4 DN20 200 2 22 2 DN20 1

Wing 4.5/7.2 M8×80 4 1 / 4 DN20 150,250 1 each 22 2 DN20 1

Ceiling Built-in Duct

4.5/5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1

12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1

CeilingBuilt-in

2.7 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1

4.5/5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1

12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1

Large Series 18 M12×100 4 1 1 12 DN25 200 2 28 2 DN25 1

25 M12×100 4 1 1 16 DN32 200 2 35 2 DN32 2

Note:1. Two pieces of 300mm bellow will be supplied for Thick models if installed with bracket.2. Two pieces of 400mm bellow will be supplied for Vertical Column models if installed with cone-tube supporter .3. Pre-installed valve and braze welded ends will be delivered before the system installation.

11

Fan coils - accessories and supply scope

Ce

ilin

g b

uilt

-in S

erie

s W

all

Built

-in S

erie

s A

van

t-g

ard

e S

erie

s T

hic

k Se

ries

Page 13: Terminales

Thin Series

Curve Model AD

Thin models enlarged scheme of pipe connection

Thin AA Triangle AM Semicircle AJ Bend AG

Thin Series

12

Note:dimension units are in mm, and it is the same on the following pages.

Fan coils - dimensions

Page 14: Terminales

Vertical Thin Series

Vertical Thin enlarged scheme of pipe connection

Left Curve Model AE

Left Bend Model AH

Left Semicicle Model AK

Left Thin Model AB

13

Left Triangle Model AN

Thin Series

Page 15: Terminales

L.Thick Model, R.Thick Model DC, DD

Thick Model DB

14

Thick Series

Page 16: Terminales

Oval Model DQ

L.Oval Model, R.Oval Model DR, DS

15

Thick Series

Page 17: Terminales

Long-range Model DE

Vertical Long-range Model DF

16

Page 18: Terminales

Piano Model CC

17

Avant-garde Series

Page 19: Terminales

Vase-stand Model CE

Cube Model CD

18

Page 20: Terminales

Diamond Model DP

Jet Model CA

19

Avant-garde Series

Page 21: Terminales

Column Model AP

Vertical Column Model AQ(wall-mounted and wall corner installation)

20

Page 22: Terminales

Polygon Model AR

Vertical Polygon Model AS(wall-mounted and wall corner installation)

21

Avant-garde Series

Page 23: Terminales

Floor standing vert ical column & polygon1.8kW instal lat ion with cone tube supporter

2.7kW, 3.6kW Vertical Column Model (installation with tray supporter)

22

Page 24: Terminales

Wall Built-in Model DG

2.7kW, 3.6kW

4.5kW~12kW

23

Wall Built-in Series

Page 25: Terminales

Left Wall Built-in Model, Right Wall Built-in Model DH, DJ

4.5~12kW2.7, 3.6kW

24

Page 26: Terminales

Wall Built-in Duct Model DJ

25

Wall Built-in Series

Page 27: Terminales

Floor Model DM3.6kW

12kW

26

Page 28: Terminales

Ceiling Square Model DN

Wing Model DO

27

Ceiling Built-in Series

Page 29: Terminales

Ceiling Built-in Model DL 2.7kW

4.5kW, 5.4kW, 12kW

28

Ceiling Built-in Duct Model DK

Page 30: Terminales

High Board Model EH

29

Large Series

Page 31: Terminales

High Stripe Model EK

30

Page 32: Terminales

A. Tips for installation location①Placed high in offices stuffed with desks.②Placed low in high-storey rooms. ③Do not select ceiling built-in models for those

places with rigid cleaning requirements such as hospitals, micro-electronics workshops, bedrooms, etc.

④The place should be good for air circulation of the whole room, and the air outlet cannot face people or bed straightly.

⑤Match the decoration and do not affect the room aesthetics.

⑥Convenient for pipe connection and condensate drain.

⑦Easy for maintenance. B. Tips for piping and wiring pre-installation① Pipes must be laid during construction period.② Copper tubes must be adopted in supply/ return

water pipes. Low temperature braze welding is recommended in connecting the pipes. The A/ C W. pipes should be covered with rubber plastic cold insulation material and non-metal tubes can be used for condensate pipe.

③BROAD pre-installed valve should be installed at the end of pipeline. Water supply valve is also a flow regulating valve which can balance the flowrate of each fan coil. It also has a shutoff function which facilitates filter washing. Filter must be re-fixed after washing.

Note: Please follow the marks to install and make sure not to mix up the supply & return W. pipes, otherwise the coils will be blocked!

④ After completion of whole building installation, keep the chilled water pump running

continuously for min. 5 days to accumulate impurities at each filter. Wash the filters before the Fan Coils are installed.

Installation items

BROAD Fan Coil Installation Tips

Installation proceduresA LocatingThe designer selects fan coils and decides their installation locations according to room function and decoration style to facilitate the pre-installation work like piping and wiring.

B Pre-installed piping and wiringDuring the construction, A/C water supply & return pipe (with pre-installed valve), condensate pipe, power supply cable, lighting output and outdoor thermometer cable shall be implemented to the installation place of fan coils.

C Shell installationFan coil is to be installed after the room decoration. Handle it with care to avoid any damage. Locate and drill holes on the wall against the screw holes on the shell back first, then insert expansion bolts and mount the unit.

D Pipe connectionConnect the pre-installed water supply pipe, water return pipe and condensate pipe to the fan coils. Flexible stainless steel bellow pipe can be used for water return & supply pipe.

F Lighting cable connectionLeading 9×0.75 mm2 lighting cables from fan coil wiring terminal to 4-loop lighting control can actualize coupled twin connection and control (30W for each loop). Energy efficient lamps are recommended. If the lamp power is more than 30W, an amplifier can be introduced.

H Outdoor thermometer installationLead a 2×0.3mm2 cable from fan coil wiring terminal. Install the sensor outside the window and avoid direct sunshine.

I Controller installationThe controller can be installed on a supporter supplied with the unit, or lead 3×0.15mm2 control cable from the wiring terminal and install the controller onto the wall nearby. The location should be convenient to operate and looks harmonious.

E Power connectionLead 3×1.0mm2 power cable from the wiring terminal to indoor power supply (1.5mm2 power cable to be used for ≥9kW models).

G Indoor thermometer installationLead a 2×0.3 mm2 cable from fan coil wiring terminal and install it onto the wall 2m away from the unit (~1.3m above floor). If the thermometer is too close from the indoor unit, it may indicate air blowing temperature instead of the average room temperature.

31

W. returnvalve

Bellow for temporary circulation

Condensatepipe

W. supply valve

Water filter

Pre-installed valve (BROAD supply)

e

power

Condensate a.fan coilb.controller (installed on the unit or on the wall)c.outdoor thermometer (installed out of window)d.indoor thermometere.lighting control (4 loops)

a

bd

c

e

e

e

e

Note: BROAD Fan Coils are totally different from the conventional fan coils both technology-wise and function-wise. The following instructions must be strictly followed in installation. BROAD Fan Coils are multi-functional products. Besides adjusting the indoor temperature and purifying the air, it also can actualize automatic on/ off according to ambient temperature, and lighting control through the remote control.All basic functions introduced here (not including optional items) must be installed (as the right diagram).

A/C w. returnA/C w. supply

Page 33: Terminales

N

K1 K2 K3 K4

L L41L32L31L22L21L12L11 L42light control box

Item Installa-tion

position

Material Applicable to

Material source

Scope

Power supply for

fan coils

Wiring terminal

3×1.0mm2 plastic

coated wire3×1.5mm2

plastic coated wire

1.8~7.2kW

9~25kW

user installer

Controller Wiring terminal

3×0.15mm2 communica-

tion cable (max. 10m)

wall built-in series,

ceiling built-in series

(special order

for other models)

BROAD installer

Outdoor temp. sensor

Wiring terminal

2×0.3mm2 communica-

tion cable (max. 5m)

fan coils(optional)

BROAD installer

Light control

Light control

box

9×0.75mm2

plastic coated wire

fan coils (optional)

user installer

Fresh air valve

control

Fresh air control

box

2×0.75mm2

plasticcoated wire

fan coils (optional)

user installer

Electric wiringList of site work

Note:①All electric materials and methods for installation

must comply with the local codes and standards.②Adopt the embedded PVC conduit inside wall for

indoor wiring layout.③The total cross sectional area of all wires should be

less than 40% of that of wiring conduits.④Power cable can be branched through junction

box, but communication cable can't be branched or intermediately connected.

⑤Eliminate the burr of PVC conduit ends or use jacket to protect wire insulation.Pull the wires evenly in order not to break it.

⑥A proper length should be reserved on wire outlets of junction box, which facilitates wire connection and repair.

32

Stainless steel bellow (BROAD supply)

Exterior wiring diagram

N

LNPE

GNDS5VT2T2L

T2 XK

AC 220-240V50/60Hzpower supply

outdoor thermometer

controller

control box

C. Tips for shell installation①Keep the shell horizontal with no more than 2 mm

gradient.②The expansion bolts should be strong enough to

support at least 3 times the weight of the shell (as there might be impact when the cover is being opened).

D. Tips for piping connection①Shut off the pre-installed valves (water return/

supply valves), take out and wash water filter, then fix them back.

②Take out the bellow for temporary circulation and send it back to BROAD.

③Connect the pre-installed valves with the fan coil by 2 stainless steel bellows of proper length.

④The condensate pipe must be with a certain gradient. No gradient is needed for A/C water pipes since auto air vent is available in the unit.

Wiring diagram of light control(only connect to L12/L22/L32/L42 when separate control is needed )

Power on inspection①After the installation is completed, check

the settings in fan coil controller item by item according to “Parameter Setting” chapter of the User's Manual.

②Pay special attention to the fan motor noise, outdoor/ indoor temperature and CO2 concentration.

③Check fan coil and lighting on/off through remote control.

A/C hydraulic balance commissioningStart up all the fan coils in the whole building for cooling or heating operation, use an infrared thermometer to test whether the air outlet temperature from each fan coil is the same. Turn up its flow regulating valve or turn down valves of nearby fan coils if the air temperature from a fan coil cannot reach the target. Repeat the adjustment till a hydraulic balance is reached.Generally the valve openness of those fan coils which are closer to the chiller should be smaller.

Air purification commissioningTake out the electrostatic cleaner after operating for a day and check dust collection. If not, there might be some faults. Please notify BROAD or BROAD authorized service provider.

Page 34: Terminales

Meeting a fresh air demand of 160~1600 peopleFresh air flowrate: 3250, 6500, 13000, 16900, 32500m3/hCooling capacity: 25kW, 50kW, 100kW, 130kW, 250kWArea coverage: 200~4000m2/unit

Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designComplete functions: air conditioning, fresh air, humidification and Electrostatic cleaner auto cleaningQuiet operation: inverter Fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building

General

Air handlers

33

Air handlers

Centrifugal fan

Inverter

Control box

Detergentreservior

Coil(the only shared part with conventional products)

Spraying nozzles for auto cleaning

Water make-up motor valve

Air outlet(flange to be supplied if connected to air ducts)

Electrostatic cleaner

Air inlet (flange to be supplied if connected to air ducts)

A/C Water motor valve

Heat meter

FilterWater collection pan

Page 35: Terminales

34

Heat recovery air handlers

Meeting a fresh air demand of 120~1200 peopleFresh air capacity: 2500, 5000, 10000, 13000, 25000m3/hCooling capacity: 25kW, 50kW, 100kW, 130kW, 250kWArea coverage: 200~4000m2/unitSuitable for icy and torrid areas to fully exert its energy saving function

Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designComplete functions: air conditioning, fresh air, exhaust air, heat exchange between fresh air and exhaust air, humidification and electrostatic cleaner auto cleaningSuper energy saving: Equipped with air heat exchanger to enable heat exchange between fresh and exhaust air, heat recovery efficiency 60~90%Contamination free: aluminum alloy heat exchanger eliminates cross contamination the conventional paper heat exchangers might have(complete heat exchanger)Quiet operation: inverter fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building

Fresh air fan

Inverter

Detergent reservoir

A/C Coils (the only shared part with conventional products)

Spraying nozzles for auto cleaning

Water collection pan

Water make-up motor valve

Fresh air inlet (flange to be supplied if connected to air ducts)

Control box

Electrostatic cleaner

Exhaust air inlet (flange to be supplied if connected to air ducts)

A/C Water motor valve

Heat meter

Filter

Exhaust air fan

Cleaning pump

Air heat exchanger (aluminum)

Exhaust air outlet(flange to be supplied if connected to air ducts)

Fresh air outlet (flange to be supplied if connected to air ducts)

Page 36: Terminales

No. Name& Code

Cooling capacity

kW

Air Flow

m3/h

Residualpressure

Pa

Water flow

m3/h

Waterresis-

tance

kPa

Min.noise level

dB(A)

Max.noise level

dB(A)

Power demand

kW

Weight

kg

DimensionsL×W×H

mm

A/C water

pipe

mm

Cond-ensate

pipe

mm

Installation

1 Air 25 3250 200 3.1 60 34 48 1.3 272 850x850x1850 DN32 Φ22 Against wall,

2 handler 50 6500 200 6.2 70 34 52 2.5 460 1640x850x1850 DN32 Φ22 inside the

3 EC 100 13000 200 12.4 75 34 58 5.0 840 3220x850x1850 DN50 Φ28 hall, inside

4 130 16900 300 16.1 80 36 60 9.5 900 2080x1000x2700 DN50 Φ28 machine room

5 250 32500 300 18.6 95 36 65 17.8 1814 4100x1000x2700 DN70 Φ35 or outdoors

6 Heat 25 2500 150 3.1 60 34 48 2.5 520 850x1800x2100 DN32 Φ22 inside the hall,

7 recovery 50 5000 150 6.2 70 34 52 5.0 1040 1640x1800x2100 DN32 Φ22 inside machine

8 air handler 100 10000 150 12.4 75 34 58 9.5 2000 3220x1800x2100 DN50 Φ28 room or

9 ED 130 13000 250 16.1 80 36 60 17.8 2520 2080x2000x2700 DN50 Φ28 outdoors

10 250 25000 250 18.6 95 36 65 35.0 4500 4100x2000x2700 DN70 Φ35

Air handlers - specifications

Note: 1. The above rated condition is tested under return air operation: inlet air dry bulb temperature: 27℃, wet bulb temperature: 19.5℃, chilled water outlet/inlet temperature: 14/7℃ rated conditions for heating: inlet air dry bulb temperature: 21℃, heating water outlet/inlet temperature: 55/65℃2. Heating capacity is 1.5 times of the cooling capacity.3. Cooling capacity under fresh air operation is 1.4 times of that under return air condition. rated conditions for cooling: inlet air dry bulb temperature: 34℃, wet bulb temperature: 28℃, chilled water outlet/inlet temperature: 14/7℃ rated conditions for heating: inlet air dry bulb temperature: -4℃, heating water outlet/inlet temperature: 55/65℃4. Noise level is measured 1m distance from the unit. 5. Nomenclature: code letter + cooling capacity(kW) e.g. 25kW air handler is named as EC25.

35

Page 37: Terminales

Air handlers - performance curves

36

Series Model

kW

Expansion bolt Bellow Adapter Sealing gasket Braze welding ends

Pre-installed valve

Model

mm

Qnty

pc

Model

mm

Length

mm

Qnty

pc

Model Qnty

pc

Model

mm

Qnty

pc

Model

mm

Qnty

pc

Model

mm

Qnty

pcAir

handlers25 M12×100 4 DN32 300 2 1" -11/2" 4 Φ43×Φ36.6×1.9

Φ49×Φ41×464

35 2 DN32 2

50 M12×100 4 DN32 300 2 11/4" -11/2"

4 Φ43×Φ36.6×1.9Φ49×Φ41×4

64

35 2 DN32 2

100 M12×100 4 DN50 400 2 2"-21/2" 4 Φ68×Φ58.6×3.1 10 54 2 DN50 2

130 M12×100 4 DN50 400 2 2"-21/2" 4 Φ68×Φ58.6×3.1 10 54 2 DN50 2

250 M12×100 4 DN70 500 2 21/2" -3" 4 Φ82×Φ74×4 10 76 2 DN70 2

Note: Pre-installed manual valve will be delivered with braze welding ends before the system installation.

Accessory supply list

Chilled W. temperature vs cooling capacity

140

120

100

80

60

40

23 24 25 26 27 28

5℃

6℃

7℃

8℃

9℃

10℃

Chilled W. flowrate vs cooling capacity

Air flow vs static pressure

500

400

300

200

100

0 20 40 60 80 100 120 140 160

EC130、250

EC25~100

ED25~100

ED130、250

100

95

90

85

80

75

7050 60 70 80 90 100

Air flow %

Air return temp. ℃ Flowrate %

Co

olin

g c

ap

ac

ity %

Co

olin

g c

ap

ac

ity %

Exte

rna

l sta

tic p

ress

ure

Pa

Page 38: Terminales

Air handlers - dimension

37

Air handler EC

Note:dimension units are in mm, and it is the same on the following pages.

Page 39: Terminales

38

Heat recovery air handler ED

Page 40: Terminales

A. LocatingThe designer selects air handler(or heat recovery air handler)and decides their installation locations according to the function and decoration style of the room to facilitate piping and wiring pre-installation.

B. Piping and wiring pre-installationDuring the construction, A/C water supply & return pipe (with pre-installed valve), water make-up pipe, drain pipe, power supply cable, lighting output cable shall be implemented to the installation place of air handler unit.

C. Hole opening on the wallFor new buildings, fresh air hole openings should be reserved according to designs. For existing buildings, the position and dimension of fresh air hole openings should be marked firstly in accordance with specified air handler models then make the hole openings based on designs.

E. Shell installationLocate (heat recovery) air handler against the prepared holes, then fix it with expansion bolts.

I. Outdoor thermometer installationLead a 2×0.3mm2 cable from air handler unit wiring terminal. Install the sensor outside the window avoiding direct sunshine.

G. Power connectionLead three-phase power cable from the wiring terminal to indoor power supply.

D. Air duct installationAir ducts should be pre-installed according to fresh air demands and the installation place of air handler unit, and the duct dimension as well as installation methods should meet requirements.

F. Pipe connectionConnect the pre-installed water supply pipe, water return pipe, water make-up pipe, drain pipe and air duct to the unit. Flexible stainless steel bellow pipe can be used as water return & supply pipe.

J. Controller installationUsually the controller is installed on the supporter attached with the unit. Another way is to lead a 3×0.15mm2 cable from the wiring terminal and install it on the wall nearby with convenience for control and without undermining the indoor decoration design.

H. Indoor thermometer installationLead a 2×0.3 mm2 cable from air handler unit wiring terminal and install it onto the wall 5m away from the unit (1.3m above floor). If the thermometer is too close to the indoor unit, it will indicate the air blowing temperature from the unit instead of the average temperature of the room.

Air handler Installation TipsElectric wiring

Item Installation position

Material applicable to

Material source

Scope

Power supply

Inside control

cabinet

3x2.5+1x1.5mm2

cable

3x4.0+1x2.5mm2

cable3x6.0+1x4.0mm2

cable3x16+1x10mm2

cable3x25+1x16mm2

cable

EC/ED25

EC/ED50

EC100

EC130

ED100

EC250

ED130

ED250

users installer

Controller Wiring terminal

3x0.15mm2

communication cable

(max. 10m)

All models

BROAD installer

Outdoor thermometer

Wiring terminal

2x0.3mm2

communication cable

(max. 5m)

All models

(optional)

BROAD installer

Exterior wiring diagram

Scope of site work

Power on inspection,A/C hydraulic balance commissioning and air purification commissioning

The same as BROAD Fan Coil Installation Tips(Please refer to P32. )

Installation procedures

N

NPE

GNDS5VT2

T2

L1

XK

3N 380-410V 50/60Hz

Power supplyOutdoor thermometer

Controller

L3L2 T2

L1 L3L2

39

Page 41: Terminales

exhaust air inlet

air heat exchanger (aluminum)

electrostatic cleaner

active carbon

fresh air fan

fresh air outlet

inverter motor

exhaust air outlet

exhaust air fan

fresh air inlet

General

Meeting a fresh air demand of 5~20 peopleFresh air capacity: 100, 240, 400m3/hArea coverage: 200~4000m2/unitInstallation: wall mounted (two oval openings to be made on the wall)Suitable for icy and torrid areas to fully exert its energy saving function

Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designSuper energy-saving: Equipped with air heat exchanger to enable heat exchange between fresh and exhaust air, heat recovery efficiency 50~80%Contamination free: Aluminum alloy heat exchanger eliminates cross contamination the conventional paper heat exchangers might have(total heat exchanger)Easy installation: plug and play, instantly eliminates urban pollutionQuiet operation: inverter Fan, noiseless at low speed

Fresh air units

40

Heat recovery fresh air units

co2 sensor

Page 42: Terminales

Fresh air units Large fresh air units

Meeting a fresh air demand of 2~2000 peopleApplicable for air purifying indoor and outdoorLarge fresh air unit with electrostatic cleaner auto cleaning function

41

Large fresh air unit

Fresh air capacity: 4000, 8000, 16000, 20000, 40000 m3/hArea coverage: 1000~10000m2

the same structure as air handler, only without A/C coil.

CO2 sensor

Air intake pipe(Inserted into wall)

Inverter fan

Electrostatic cleaner

Active carbon

Controller

Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designEasy installation: plug and play, instantly eliminates urban pollutionQuiet operation: inverter Fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building

Fresh air unit

Fresh air capacity: 50, 100, 240, 400, 1000 ,2000m3/hArea coverage: 10~500m2

Page 43: Terminales

No. Name Code

Air flow

m3/h

Residual pressure

Pa

Min.noise level

dB(A)

Max.noise level

dB(A)

Power demand

W

Weight

kg

SizeL×W×H

mm

Installation

1 Heat recovery 100 / 28 37 35 12 330x150x570 Wall mounted

2 fresh air 240 / 28 37 150 34 520x255x8503 unit 400 / 30 39 200 45 580x320x960

SA4 Fresh air 100 / 22 32 20 4.5 340x150x240 Wall mounted5 unit 240 / 22 35 35 6.5 340x150x500

6 TAWF 400 / 24 35 40 9 340x150x745

7 1000 / 26 40 90 27 480x230x848 Floor standing8 2000 / 28 42 150 45 480x230x15639 Big fresh 4000 150 34 48 1300 165 850x850x1850 Floor standing10 air unit 8000 150 34 52 2500 330 1640x850x1850 Holes to be11 THWH 16000 150 34 54 5000 670 3220x850x1850 opened on the 12 20000 250 36 54 9500 850 2080x1000x2700 wall for these 413 40000 250 36 56 17800 1600 4100x1000x2700 models

14

Window fresh air

unitTDWD

50 / 27 42 5 1.5 200x143x225 Against the window (holes to be opened

on the window)

Fresh air units - specifications

Fresh air units

Fresh air accessories

No. Name Code

Air flow

m3/h

Residual pressure

Pa

Min.noise level

dB(A)

Max.noise level

dB(A)

Power demand

W

Weight

kg

SizeL×W×H

mm

Installation

1 Ventilator 100 / 28 43 58 3 170x72x170 near a fan coil2 VA 240 / 33 48 81 5 190x98x1903 400 / 38 54 126 8 220x99x2204 800 / 42 56 213 14 310x108x3105 Big ventilator 2000 500 45 63 300 28 505x239x528 near an air handler 6 VC 4000 540 48 64 750 55 580x290x5837 Fresh air box 600 / / / / 6 890x264x140 Air inlet of the8 WB 800 / / / / 7 1060x264x140 “Thick” units9 1000 / / / / 8 1260x264x14010 1300 / / / / 9 1450x264x14011 1600 / / / / 10.5 1760x264x14012 2100 / / / / 12.2 2200x264x14013 Big fresh 4000 20 38 614x6841170 Air inlet of the14 air valve

WF

10000 20 57 1114x929x1795 air handler andheat recovery air

handler

42

Note: 1. Fresh air units do not have air conditioning function.2. Noise level is measured 1m distance from the unit. 3. Nomenclature: code letter + air flow e.g. 100m3/h fresh air unit is named as TAWF100.

Note: 1. Fresh air accessories are coupled with fan coils and air handlers.2. Noise level is measured 1m distance from the unit. 3. Nomenclature: code letter + air flow e.g. 100m3/h fresh air ventilator is named as VA100.

Page 44: Terminales

Fresh air units - performance curves

43

Accessory supply list

Name Model

m3/h

Expansion bolts Active carbon

pcsModel

mmQnty

pcs

Heat recovery fresh air unit

100 M6×80 4 4

240~400 M6×80 6 4

Fresh air unit 100~2000 / / 4

Big fresh air unit 4000~40000 M12×100 4 /

Window fresh air unit

50 / / 4

Big fresh air unit air flow vs static pressure

0 20 40 60 80 100 120

500

400

300

200

100

Air flow %

THWH20000、40000

THWH4000~16000

Exte

rna

l sta

tic p

ress

ure

Pa

Page 45: Terminales

Fresh air units - dimensions

Heat recovery fresh air unit SA

Fresh air unit TAWF

Big fresh air unit THWH The dimension for big fresh air units is the same as air handlers; please refer to P37.

44

TAWF100 TAWF240~2000

Page 46: Terminales

Big fresh air unit exterior wiring diagram

GND

XK

N

NPE

S5VL1

3N 380-410V 50/60Hz

Power supplyController

L3L2

L1 L3L2

Control box

NPE L

N L

Control box

AC 220-240V 50/60Hz

Power supply

Fresh air unit/ heat recovery fresh air unit exterior wiring diagram

Item Installation position

Material Applicableto

Material source

Installation

Power supply

Inside the control

cabinet

3x1.0mm2plastic coated wire

3x2.5+1x1.5mm2

cable

3x4.0+1x2.5mm2

cable3x16+1x10mm2

cable

SA100~400

TAWF100

~2000

TAWH4000

~16000

TAWH20000

TAWH40000

users installer

Controller Wiring terminal

3x0.15mm2

communication cable (max. 10m)

All models BROAD installer

List of site Installation

F. Power on inspectionAfter the proper installation is confirmed, turn on the unit, adjust the fan frequency, test the sound of fan, and check the CO2 concentration displayed on the controller.

A. LocatingThe designer selects the model of fresh air unit according to fresh air solution, and locates the installation position for opening.

B. Making holes in the wallFor new buildings, openings should be reserved according to the design. For existing buildings, mark the position and dimension of openings according to different models, then open fresh air holes, and polish them with cement. After the structure construction, indoor walls and floor flatting get finished, recheck the position and dimension of installation, and immediate modifications are needed if it can not meet the requirements (in order to prevent rainfall from flowing indoor, through-wall hole should be higher on the indoor side and lower on the outer side. They also should look neat and nice).

C. Open-box inspectionCheck the product number, product name and model: inspect the shell and accessories to see if they are complete and in good condition. If there is any damage, please notify the supplier.

D. Shell installationFor fresh air unit: inset the fresh air inlet/ outlet pipe into cement holes, After the cement is hardened and the pipes are fixed, steadily install the fresh air unit.For heat recovery fresh air unit and large fresh air unit: locating the unit to the fresh air inlet/outlet hole,and fix it with expanded bolt.

E. Power connectionLead power cable from the wiring terminal to indoor power supply.

45

Fresh air units - Installation Tips

Installation procedures Electric wiring

Page 47: Terminales

Item Focuses or Disputes BROAD Solutions

Fresh air amount

What’s the suitable rate?

20m3/h per capita. For low occupancy density rooms such as villas, 2m3/h per square meter.

Air outlet

How to use fresh air effectively?

Locate the fresh air outlet and exhaust air outlet as far as possible so that fresh air can be fully used.

Air duct How to avoid air duct pollution?

Air ducts are seedbeds for pathogens. The solution is not to use air ducts

Cost How to minimize the cost?

Install fresh air boxes on fan coils to draw fresh air from outside

Energy-saving

Is it worth increasing investment to save energy?

1. In icy areas (temp <-10°C in winter), the payback can be within 1-3 years if fresh air heat recovery system is introduced.

2. In areas with mild climate (16-26°C), by selecting larger fresh air units and using fresh air for cooling in transitional season, the payback can be within 2-6 years.

46

Fresh air unit model selection tips

Tips for fresh air system selection

How much fresh air are we breathing?Staying in a room lacking of fresh air is like living on the sea without freshwater. You can breathe (drink seawater), but will be suffocated to death (thirst). According to authoritative investigations, everybody in the world has more or less suffered from fresh air deficiency (oxygen deficiency), e.g.:• In cold seasons people always close doors and

windows to keep warm and save energy. Their faces turn red, not because of the warmth but of oxygen deficiency.

• In hot seasons people always close doors and windows to keep cool and save energy. People are lethargic, not because of fatigue but of oxygen deficiency.

• The ultimate tightness of doors and windows due to quality advancement in recent years makes oxygen deficiency problem more serious.

• Some modern buildings that appear to be full of hi-techs are still using the conventional “low-tech” design and management of ventilation system, which leads to :• Oxygen deficiency• Toxic gases from refurbishing & building materials,

furniture, carpets can not be emitted in time.• Hundreds of people are breathing the same

mouthful of air that is cross contaminated.• A great number of pathogens are bred inside air ducts.

What kind of houses can breathe?Each BROAD fan coil is equipped with an expensive optical instrument – CO2 sensor to monitor oxygen deficiency any minute. People inhale O2 and exhale CO2, by measuring the CO2 level oxygen deficiency is to be indicated.To “know” is very important, but to “do” is even more. To meet different building constructions, functions, purchasing power and climates, BROAD has developed dozens of fresh air products that are totally different from conventional products but cheaper and more energy efficient. They can solve all fresh air problems comprehensively and let each building/room breathe freely.

What‘s the harm of oxygen deficiency?Deficiency of fresh air inside a room will lead to oxygen (O2) deficiency and carbonic acid (CO2) concentration increase in our blood, causing insufficient O2 supply to the brain, headache, chest pain, cold limb and sleepiness, etc. Extended stay in an oxygen-deficient environment will result in skin-coarsening, premature senility, hypomnesia, slow of response, or most seriously heart diseases, brain damnification and stroke. People in serious oxygen deficiency may even lose their lives unconsciously.

What are the features of conventional “low-tech” modes?

• Just “go with your heart”– do not take even fundamental technical measures (such as CO2 sensor) to verify the design, guide the commissioning and check the operation.

• “30/70 ratio” fresh air –in the whole ventilation system, 70% air circulation is from indoor exhaust air and 30% from outdoor fresh air, resulting in cross contamination. All people in the building are breathing the same air. If someone gets sick, it may pass on to everyone.

• Short circuit between fresh and exhaust air system – the fresh air inlet and outlet are too close. Part of fresh air is expelled before people can breathe it.

• Pathogens are easily bred inside fresh air ducts.• As no technical instrument is introduced, it turns out

not enough fresh air in some places and excessive fresh air in other places (which is energy wasting). It also wastes a lot of energy without using heat recovery devices.

Page 48: Terminales

BROAD Fresh Air System Conventional Fresh Air System

Eliminates pollution from outdoors

Outdoor fresh air is purified by electrostatic cleaner and active carbon before entering the room.

Outdoor air incompletely filtered Filters are widely used, which cannot filter micro particles.

Eradicates pollution inside air ducts • Small buildings – the fresh air units can draw outdoor air into each room directly. • Large buildings – fresh air can be supplied to the passages by large-sized air ducts, then pumped into individual room by suction ducts from the interior windows. • In order to match perfectly different construction styles, BROAD provides dozens of products and optional accessories.

Serious pollution inside air ducts • Fresh Air ducts are extended to each room. Air ducts in a mansion may outstretch several or scores of kilometers. The air ducts are mixed and anfractuous, becoming the pollution sources. • The air ducts are not cleaned in years or even the whole lifespan. Pathogens are bred rapidly inside, making the air ducts even dirtier than inside drains.

Well-proportioned fresh air Fan coils and fresh air units in each room are equipped with CO2 sensor, which is monitoring fresh air deficiency and excess 24/ 7.

Unbalanced fresh air CO2 sensors are not used, only a few to be installed in 5-star hotels. It may result in excessive fresh air in some rooms and not enough fresh air in other rooms.

Many alternatives • 5 modes, 30+ products and dozens of accessories available. • Custom design can be made according to building structures, functions, energy saving objectives,budgets, etc. • Suitable for fresh air system modifications of old buildings.

Few choices Only two modes all over the world.

Space saving • “Direct fresh air system” takes almost no space. • “Exhaust air duct system” is 50% space saving. • The space saving cost is possibly higher than the investment on equipment.

Large space taking Air ducts outstretch horizontally and vertically into a building and occupy very large space.

47

BROAD Fresh Air System vs. Conventional Fresh Air System

BROAD fresh air system solutionFor conventional central air conditioning system, fresh air duct system is very complicated. It looks like blood vessels stretching every corner of buildings. In a large building, there are several dozen kilometers of fresh air ducts. In the past few people noticed what was inside fresh air ducts. In recent years “sick building syndrome” (SBS) broke out worldwide, more and more people learned about it. Before Beijing Olympic Games, the investigation into indoor air quality of more than 10,000 large-scale buildings revealed that less than 1% of fresh air ducts in these buildings were cleaned. Similar situation exists worldwide. Furthermore in those cleaned buildings only less than 40% fresh air ducts can be cleaned even with cleaning robots.

Now, the question we are facing is to develop smaller and more practical robots to clean fresh air ducts, or not to use fresh air ducts completely.

If the first choice is taken, besides technical difficulties, how to afford the costly cleaning fee (approximate USD14/m2, which is nearly the same as an initial cost) and how to stand the polluted air during hundred days between two cleaning intervals, so the only solution to prevent pollution is not to use fresh air ducts.

Page 49: Terminales

Category Solutions Selected products Advantages Disadvantages ApplicationDirect fresh air system

Solution 1 Fresh air unit to get outdoor fresh air directly

Easy and simple installation

High costOnly suitable for rooms with outer wall

Any buildings including buildings without BROAD fan coils and renovated old buildings

Solution 2 Heat recovery fresh air unit to get outdoor fresh air and vent indoor air

Easy and simple installationEnergy-saving

Very high costOnly suitable for rooms with outer wall

Solution 3 Fresh air box to get outdoor fresh air directly by fan

Easy and simple installationFresh air box is cheap

Only suitable for rooms with outerwall (an opening on the wall)

Only for buildings equipped with BROAD fan coils

Solution 4 Ventilator to get outdoor fresh air to rooms

Easy and simple installationVentilator is cheap

Only suitable for rooms with outerwall or close to outer wall

Exhaust ventilation system

Solution 5 Exhaust duct purified fresh air will be pumped into rooms from passages

For big areasNo opening on the outer wallnot affecting building profile

High engineering cost Much space-taking

Buildings inconvenient for making an opening on the outer wall

Item 1 Air handler exhaust ventilator: Air handler will supply fresh air to passages; Fresh air will be pumped into individual rooms with exhaust ventilator and exhaust duct

Very high cost

Item 2 Heat recovery air handler will supply fresh air to passages; Fresh air will be pumped into individual rooms with exhaust duct

Energy-saving High cost Buildings inconvenient for making an opening on the outer wall, and in icy or torrid areas

48

BROAD fresh air system solution

Ventilator

Solution 3

Solution 5

Solution 4

Solution 5

Solution 5

Solution 5

Exhaust duct

Solution 1

Solution 2

Fresh air unit

Fresh air boxHeat recovery fresh air unit

Fresh air

exhaust air

air condi-tioning

Solution 5(Item 2) Solution 5(Item 1)

Heat recovery air handlerAir handler

Exhaust ventilator

air conditioning

Page 50: Terminales

Applications:Matching with BROAD villa air conditioning or other chillers to provide hot water (external primary heating water heats city water in the tank).

Working principle:The cycling of primary heating water in coils heats the city water in the tank, making the temperature of city water inside reach the setting temperature.The heat exchange coil connects to the primary heating water (60~120℃) from outside devices. When hot water temperature is at the setting temperature, the motor valve will shut off the primary heating water. When the temperature is lower than the setting, the motor valve will reopen and thus heat the hot water. The heating and temperature control are actualized in this way.

Features:• All-copper interior and coil are bacteria-killing.• Hand access hole design, easy to open for cleaning.• It adopts separate hot water tank system to

materialize 30% energy saving than centralized systems. The reason is that the valve will be closed automatically once the hot water is heated to the setting temperature. Thus, heat loss and electricity consumption can be minimized.

• Tanks are installed near the place where water is used so hot water comes out as soon as the valve is opened. It is unnecessary to keep circulation pump running 24 hours a day to maintain hot water temperature.

• Separate tank system maintains stable hot water temperature.

Hand hole cover is easily removable

Hot water tanks

100% pure copper interior

Pure copper heat exchange coil

Heat insulation

Controller(link with BMS)

Steel shell &car paint

Automatic valve and water inlet/outlet pipe system

Removable lower cover ( facilitate installation and interior cleaning )

49

Page 51: Terminales

Hot water tanks - specifications Accessory supply list

Models

Item Specifications

Hot water temperature

20~85℃

Primary heating water temperature

60~120℃

Pressure ≤0.8MPa

Power demand

10W

Power supply 220~240V, 50/ 60Hz (special orders for other power supplies)

Material Shell (steel sheets), interior(copper)

Sealing parts Fluorine rubber

Protection level

IP44

Installation Vertical up (wall-mounted or bracket-mounted)

Model Volume

L

SizeL×W×H

mm

Operation weight

kg

Pipe connection diameter

mm

RL100 100 430x345x1790 145 DN15Copper tube is recommendedRL200 200 530x430x2150 270

No. Name Quantity Specifi-cation

Application Remark

1 Expansion bolt

2 sets M10 Fixing the tank on the wall or bracket

/

2 Controller 1 piece / Controlling hot water temperature in the tank

/

3 Plastic flexible conduit

1 piece φ10 Connecting to the cone-shaped drain outlet

/

4 Bracket 1 set / Floor standing installation of hot water tank

Optional

5 Bolt 4 sets M16 Fixing the tank on the bracket

6 Bellow 4 piece DN15x300

Pipe Connection

/

Note:1. Nomenclature: Code + capacity e.g. 100L Hot water tank to be named as RL1002. For floor-standing installation with a bracket,the price will

be 10% higher.

50

Page 52: Terminales

51

Note:dimension units in mm.

Hot water tank - dimensions

Page 53: Terminales

Tips for piping and wiring pre-installation• Pipes must be laid during construction phase.• All pipes except city water pipe must be copper tubes with rubber plastic insulation.• Only BROAD valve set could be installed. Note: Please check the marks to avoid any

mistakes in matching pipes.• After completion of whole building installation,

keep the hot water pump running continuously for min. 1 day to collect all impurities of primary heating water to filters.Then clean all the filters.

Tips for tank installation• Tanks must be installed vertically, wall mounted or floor standing with brackets.• The installation strength of expansion bolts must be at least 3 times more than the operating weight.

Hot water tank - installation tips

Exterior wiring diagram

Electric wiring

PE

N

LN

GNDS5VL

XK

AC 220-240V50/60HzPower supply

Controller

B A G

485 communication

Control box

Item Install-ation

position

Material Appli-cable

to

Material source

Installation

Power supply

Wiring terminal

3x1.0mm2

plastic coated

wire

All users installer

485 communi-

cation

Wiring terminal

2x0.3mm2

double stranded

wire

All users installer

List of Installation

Installation procedure

52

D. Pipe connectionConnect the pre-installed primary heating water outlet & inlet pipe, city water make-up pipe and hot water outlet pipe to the hot water tank through bendable stainless steel bellows.

E. Electrical wiringLead power cable from the wiring terminal to indoor power supply. Lead 485 communication cables in if there is a central controller.

C. Tank installationRL100 and RL200 are usually wall amounted, or floor standing installation with a bracket, while RL300 and RL500 can only use brackets. After the building decoration, screw hole lofting of wall fixture or brackets, drilling, expansion bolts installation, fixing wall fixture or brackets, and tank installation shall be conducted step by step.

J. Power on inspectionAfter the proper installation is comfirmed, turn on the unit to check whether the controller and temperature control are OK.

A. LocatingThe designer selects hot water tanks according to requivement for hot water,and decides the installation location to facilitate the pre-installation work.

B. Piping and wiring pre-installationA/C primary heating water outlet & inlet pipe, city water make-up pipe, hot water outlet pipe, drain pipe, power supply cable and 485 communication cables should be pre-installed during construction.

F. Controller installationUsually the controller is installed on the supporter attached with the unit. Another way is to lead a 3×0.15mm2 cable from the wiring terminal and install it onto the wall nearby with convenience for control and without undermining the indoor decoration design.