Page 1: Technical/insTallaTion informaTion - Metl-Span

LOKSEAM®

Technical/insTallaTion informaTion

Page 2: Technical/insTallaTion informaTion - Metl-Span

IMPORTANT NOTICEREAD THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE LOkSEAM® ROOFING SYSTEM. METL-SPAN DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE WARRANTIES WILL BE ISSUED.

ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY METL-SPAN IMMEDIATELY IF ANY PRODUCT IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT.

IF THERE IS A CONFLICT BETWEEN PROJECT ERECTION DRAWINGS PROVIDED OR APPROVED BY METL-SPAN AND DETAILS IN THIS MANUAL, PROJECT ERECTION DRAWINGS WILL TAkE PRECEDENCE.

Ice Dam DisclaimerMetl-Span designs its standing seam roofs to meet the load requirements dictated by governing codes and project specifications, including applicable snow loads. However, Metl-Span expressly disclaims responsibilty for weathertightness or roof point loading issues or other hazards resulting from ice dam situations. Any time ice and snow can melt on the main body of the roof and refreeze at the eave or in the shadow of an adjacent wall, an ice dam situation may develop. In addition to local climate, ice dam formation is affected by many other factors, including but not limited to, roof insulation R value, roof panel color, interior temperature of building, heater location in building, eave overhangs, parapet walls, shading of building roof areas from adjacent trees, parapets, buildings, etc. These factors are design and maintenance issues and are outside the control of Metl-Span. Metl-Span specifically disclaims any liability for damage due to ice dam formation, although the following issues should be taken into consideration concerning standing seam roofs installed in freezing climates:

• Alwaysusefieldseamedpanels.Thesemachine-foldedseamsaremoredurablewhensubjectedtooccasionalicing.

• Eliminate "cold" eave overhangs and parapet walls from the building design. Roof overhangs outside the heatedenvelope of the building will tend to be colder than the roof areas over the heated envelope. Simple roof designs arepreferred. Parapet walls at the eave allow ice and snow to collect due to shading effects and the lower roof temperaturescaused thereby.

• Make sure the interior of the building is adequately insulated and the heating is properly distributed. Inadequateinsulation in the roof and/or improper heat distribution causes heat flow though the main body of the roof. On days whenthe temperature is below freezing, this heat gain can cause ice and snow to melt and refreeze at the eave where theroof is colder.

• Layoutthebuildingtopreventtheeavesandotherroofareasfrombeingshadedduringthewinter.Thismaymeaneliminating adjacent trees or reconsidering roof geometries.

• Considerusingself-regulatingheatingcablesattheeavestomitigatetheeffectsoficedams.

• Onbuildingdesignsusingattics, over-insulate theattic floor andprovideadequate ventilation in theattic.Thiswillreduce heat transfer through the roof resulting in more consistent roof temperatures between eave and field of roof.

• Increasethedegreeofdiligencewithrespecttounderlaymentmaterialsatroofareaspronetoicing.Thismayincludevalleys, eaves, dormers and roof areas near dormers, parapets and the like where shading may occur.

Formoreinformationonthissubject,pleaserefertotheMCA'sMetalRoofDesignForColdClimatesmanual.

TheEngineeringdatacontainedhereinisfortheexpresseduseofcustomersanddesignprofessionals.Alongwiththisdata,itisrecommendedthatthedesignprofessionalhaveacopyofthemostcurrentversionoftheNorthAmericanSpecificationfortheDesignofCold-FormedSteelStructuralMemberspublishedbytheAmerican Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer.

Descriptionsandspecificationscontainedhereinwereineffectatthetimethispublicationwasapprovedforprinting.Inacontinuingeffort to refine and improve products, Metl-Span reserves the right to discontinue products at any time or change specifications and/or designs without incurring obligation. To ensure you have the latest information available, please inquire or visit our website at metlspan.com. Application details are for illustration purposes only and may not be appropriate for all environmental conditions, building designs or panel profiles. Projects should be designed to conform to applicable building codes, regulations and accepted industry practices. If there is a conflict between this manual and project erection drawings, the erection drawings will take precedence.

© 2019 Metl-Span, part of the Cornerstone Building Brands family. All Rights Reserved.Metl-Span’sSingleSkinproductlineismanufacturedbyMBCI.

Page 3: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-3

LokSeam®

TABLE OF CONTENTSLokSeam®

ROOFING SYSTEMGeneralDescription ......................................................................................................................................................LS-5Architect/EngineeringInformation .................................................................................................................................LS-6

ENGINEERINGUL90Requirements .....................................................................................................................................................LS-718”Properties/LoadTables ............................................................................................................................... LS-8-LS-916”Properties/LoadTables ............................................................................................................................LS-10-LS-1112”Properties/LoadTables ........................................................................................................................... LS-12-LS-13

SPECIFICATIONSSpecifications For Metal Roofing .................................................................................................................. LS-14-LS-20

GENERAL INFORMATIONProductChecklist .......................................................................................................................................... LS-21-LS-25Ordering Information .................................................................................................................................................. LS-26Preparatory Requirements ......................................................................................................................................... LS-27Unloading .............................................................................................................................................................. LS-28-29Handling/Panel Storage ............................................................................................................................................. LS-30

DETAILSSpecialErectionTechniques

RoofCurbInstallation ....................................................................................................................... LS-31-LS-34FieldHemmingPanelEnd ............................................................................................................................. LS-35Panel .............................................................................................................................................................. LS-36

DetailsOverPurlinsEndlap ............................................................................................................................................................ LS-37Hip .................................................................................................................................................................. LS-38Ridge .............................................................................................................................................................. LS-39VentedRidge ................................................................................................................................................. LS-40FloatingValley ................................................................................................................................................ LS-41FixedValley .................................................................................................................................................... LS-42HighEave ...................................................................................................................................................... LS-43FloatingEavewithEaveTrim ........................................................................................................................ LS-44FixedEavewithEaveTrim ............................................................................................................................ LS-45FloatingEavewithGutter .............................................................................................................................. LS-46FixedEavewithGutter .................................................................................................................................. LS-47SnowGutter ................................................................................................................................................... LS-48Floating Rake ................................................................................................................................................. LS-49ParapetHighEave ......................................................................................................................................... LS-50Floating Parapet Rake ................................................................................................................................... LS-51Roof Transition ............................................................................................................................................... LS-52

DetailsOverWoodDeckEndlap ............................................................................................................................................................ LS-53Hip .................................................................................................................................................................. LS-54Fixed Ridge .................................................................................................................................................... LS-55Floating Ridge ................................................................................................................................................ LS-56VentedRidge ................................................................................................................................................. LS-57FloatingValley ................................................................................................................................................ LS-58FixedValley .................................................................................................................................................... LS-59HighEave ...................................................................................................................................................... LS-60FloatingEavewithEaveTrim ........................................................................................................................ LS-61FixedEavewithEaveTrim ............................................................................................................................ LS-62FloatingEavewithGutter .............................................................................................................................. LS-63FixedEavewithGutter .................................................................................................................................. LS-64Floating Rake ................................................................................................................................................. LS-65Fixed Rake ..................................................................................................................................................... LS-66FloatingParapetHighEave ........................................................................................................................... LS-67FixedParapetHighEave ............................................................................................................................... LS-68Floating Parapet Rake ................................................................................................................................... LS-69Fixed Parapet Rake ....................................................................................................................................... LS-70Roof Transition ............................................................................................................................................... LS-71

Page 4: Technical/insTallaTion informaTion - Metl-Span

LS-4REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

TABLE OF CONTENTSLokSeam®

DETAILS CONTINUEDDetailsOverMetalDeck

RigidBoardInsulationOverMetalDeck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-72Endlap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-73Fixed Ridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-74VentedRidge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-75FloatingValley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-76FixedHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-77FloatingEavewithEaveTrim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-78FloatingEavewithGutter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-79Floating Rake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-80FixedParapetHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-81FloatingParapetHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-82

Page 5: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICE SEEmetlspan.comFORCURRENTINFORMATION REV00.02LS-5

LokSeam®

ROOFING SYSTEM

18", 16'', or 12''

1¾"

⅜"

CoverageWidths-18",16"or12"

MinimumSlope-3:12

PanelAttachment-StandardandUL90Clips(concealedfasteningsystems)

PanelSubstrate-Galvalume®(standard)

Gauge-Standard:24(18",16",12"widths);Optional:22(18",16",12"widths),26(12"widthonly)

Finishes-Striated(standard)*orEmbossedStriated

Coatings-Signature®200,Signature®300,Signature®300Metallic

Signature®isaregisteredtrademarkofCornerstone Building Brands family.GalvalumePlus®isaregisteredtrademark

ofBIECInternational. — Available in any quantity.

— Minimum quantity may be required.

Othercolors,finishes,gauges,andmaterialsavailable;pleaseinquire.* Striatedpanelsarestandardtoreduce“oilcanning”.

PRODUCTSignature®300Metallic Signature®300 Signature®200 GalvalumePlus®

26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga.LokSeam®

12"Wide

16"Wide

18"Wide

PRODUCT SELECTION CHART

GENERAL DESCRIPTION

Page 6: Technical/insTallaTion informaTion - Metl-Span

LS-6REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

ROOFING SYSTEMARCHITECT/ENGINEER INFORMATION

1. LokSeam®isasnap-together,integralbattenroofsystem,availableinthreewidths:18",16",and12".Factoryappliedmastic inside of female leg of panel is standard.

2.Theminimumrecommendedslopeis3:12.Forslopeslessthan3:12,callMetl-Span.3. LokSeam®isaUL90rated,structuralroofingpanel.Thispanelcanbeinstalleddirectlyoverpurlinsorbarjoists.Itdoes

notrequireasolidsubstructureforsupport(Caution:SeeNote14).4.Watertightandaestheticallypleasingendlapsmaybeaccomplishedthroughtheuseofswagedandprepunchedpanels

(16"panelscanbeswagedbutnotpunched).Metl-Spanrecommendstheuseofprepunchedback-upplatesattheendlapfor weathertightness. Prepunching of the panels is available for the endlap condition only. (Swaged endlaps require the roof erection to proceed from left to right as viewed from the eave looking toward the ridge.) Roofs with no endlaps maybeerectedfromeitherdirection.Forpanellengthsover40’,pleaseinquire.Whenusinganalternateendlapdetailasshown on Pages LS-37 and LS-53 do not order panels with prepunched endlaps.

5.PanelscanbeinstalledonroofswithatransitionbyusingMetl-Span’sdie-formedribcovers.6.Narrowerwidths,heaviergauges,striationsandembossingminimizeoilcanning.Industrystandardis18”wide,24-gauge.

Oil canning is not a cause for rejection.7.Thesubstructure(eavetoridge)mustbeonplanewithatoleranceof¼"in20’and⅜"in40'.8.Allpanelsrequireendsealantateaveandvalleyconditions;however,forillustrationpurposes,thissealantisnotshownon

all drawings. See Page LS-36 for panel end sealant detail.9.Forproperfastenerapplication,seePages LS-24 and LS-25.10.Alldrawingsandtrimdimensionsinthismanualarebasedona1¼"wallthickness(“R”Panel)andaslopeof3:12.

Other wall panel thicknesses as well as roof slopes may affect various dimensions on drawings and trim. If you have any questions, call Metl-Span.

11. The information in this manual is believed to be correct and accurate. It should not be used for any specific application without being reviewed by a registered professional engineer. All metal roofs should be designed by a registered, professonal engineer for loads specified by the governing code, including the higher pressures encountered at the edge zones of the roof.

12. Avoid restricting the thermal expansion and contraction of the LokSeam® panels. (ie: Do not attach panels to the substructure at both the eave and ridge.)

13. LokSeam® panels are not designed to be work platforms. Avoid any unnecessary foot traffic on LokSeam® panels. If foot traffic is required, protect the roof panels by using some type of roof pad, temporary deck, or walkway.

14. When installing LokSeam® panels over open framing with blanket insulation: (A) install insulation parallel to purlins or joists, or (B) install insulation across purlins or joists and compress it with pinch bars. (¼" thick radiant barrier insulation may be used as an alternative to blanket insulation.)

CAUTIONDiaphragmcapabilitiesandpurlinstabilityarenotprovidedbyMetl-Span’sLokSeam® roof system.

Therefore,otherbracingmayberequiredtoconformtoA.I.S.C.orA.I.S.I.specifications.

WARNINGAswithallstandingseamroofsystems,soundattenuation(example:blanketinsulation)shouldbeinstalledbetweenthepanelsandopenframing,suchaspurlinsorjoists,toprevent“roofrumble”duringwindyconditions.

Applications over solid deck such as rigid insulation over a metal deck or a wood deck may require additional acoustical consideration to ensure that thermal vibration noises are isolated from the building interior. This is especially important if the bottom of the deck is left open to the interior, in cathedral ceiling applications or when the attic space is used as a return air plenum.

A vapor retarder may be necessary to protect roofing components when high humidity is a factor. The need for a vapor retarder, as well as the type, placement and location should be determined by an architect or engineer. The following areexamplesofconditionsthatmayrequireavaporretarder:(A)aprojectwhereoutsidewintertemperaturesbelow40degreesF.areanticipatedandwhereaveragewinterinteriorrelativehumidityof45%orgreaterisexpected.(B)building usages with high humidity interiors such as indoor swimming pools, textile manufacturing operations, food, paperorotherwet-processindustrialplants.(C)Constructionelementsthatmayreleasemoistureaftertheroofisinstalled, such as interior concrete, masonry or plaster work and fuel burning heaters.

Page 7: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-7

LokSeam®

ENGINEERINGUNDERWRITERS LABORATORIES APPROVAL

Construction Number

Panel Width (in.)

Gauge Clip Type Clip Spacing Substrate

UL-2218 Impact

Resistance

UL-263 Fire

Rating

UL-580 Rating

254 12" 22min. UL90 5'-0" Open Framing Class4 ClassA Class90

254 12" 24min. UL90 4'-0" Open Framing Class4 ClassA Class90

255 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90

303 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90

342 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90

343 18"max. 24min. UL90 3'-0" Plywood Class4 ClassA Class90

414 18"max. 24min. UL90 3'-0" Plywood Class4 ClassA Class90

436 18"max. 24min. UL90 4'-0" Plywood Class4 ClassA Class90

445 12" 22min. UL90 5'-0" Open Framing Class4 ClassA Class90

445 12" 24min. UL90 4'-0" Open Framing Class4 ClassA Class90

446 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90

448 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90

486 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90

508A 18"max 24min. UL90 3'-0" CompositeSystem Class4 ClassA Class90

543 12"max. 22min. UL90 5'-0" Open Framing Class4 ClassA Class90

543 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90

544 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90

NOTES1. WinduplifttestproceduresareinaccordancewithUnderwritersLaboratoriesStandardUL-580under“TestsFor

UpliftResistanceofRoofAssemblies”.2. AdetailedinstallationmethodisavailableforeachConstructionNumberaboveandcanbefoundintheUL

RoofingMaterialsandSystemsDirectory.Thepanelsmustbeinstalledinacertainmannertoachievethepublished results.

3. ThepanelqualifiesforaClassAfireratingincompliancewithUnderwritersLaboratoriesStandardUL-263.4. ThepanelsystemislistedunderfollowingFireResistanceDesignNumbers:P225,P227,P230,P237,P265,

P268,P508,P510,P512,P701,P711,P720,P722,P726,P731,P734,P801,P815,andP819.RefertotheULFireResistanceDirectoryforspecificconstructionmethodsandhourlyratings.

5. LokSeam®panelscarryaClass4ratingunderUL-2218“TestStandardForImpactResistance”.

FLORIDA BUILDING CODE PRODUCT APPROVALLokSeam® Roofing System details and engineering load tables have been examined by the State of Florida and comply with the 5thEdition(2014)FloridaBuildingCodeProductApprovalNumber(FL#11819.3).

Page 8: Technical/insTallaTion informaTion - Metl-Span

LS-8REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

ENGINEERINGLokSeam® PANEL

18"

1¾"

SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING

PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)

24 50 1.25 0.0321 0.0403 1.2066 0.0682 0.0465 1.391222 50 1.60 0.0446 0.0594 1.7795 0.0957 0.0655 1.9620

NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof

theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project job site in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer.

Page 9: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-9

LokSeam®

ENGINEERINGLokSeam® PANEL

ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT

24- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 148.4 103.1 75.7 58.0 45.8 37.1 30.7

2-SPAN LIVELOAD 128.7 89.4 65.7 50.3 39.7 32.2 26.6

3-SPAN LIVELOAD 160.9 111.7 82.1 62.8 49.7 40.2 33.2

4-SPAN LIVELOAD 150.2 104.3 76.6 58.7 46.4 37.6 31.0

22- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 200.0 145.3 106.8 81.8 64.6 52.3 43.2

2-SPAN LIVELOAD 189.8 131.8 96.8 74.1 58.6 47.5 39.2

3-SPAN LIVELOAD 200.0 164.8 121.1 92.7 73.2 59.3 49.0

4-SPAN LIVELOAD 200.0 153.8 113.0 86.5 68.4 55.4 45.8

NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.

18"

1¾"

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.

Page 10: Technical/insTallaTion informaTion - Metl-Span

LS-10REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

ENGINEERINGLokSeam® PANEL

SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING

PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)

24 50 1.34 0.0361 0.0452 1.3527 0.0758 0.0520 1.557022 50 1.71 0.0500 0.0666 1.9938 0.1052 0.0731 2.1921

NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof

theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.

16"

1¾"

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.

Page 11: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-11

LokSeam®

ENGINEERINGLokSeam® PANEL

ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT

24- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 166.1 115.3 84.7 64.9 51.3 41.5 34.4

2-SPAN LIVELOAD 144.8 100.5 73.9 56.6 44.7 36.2 29.8

3-SPAN LIVELOAD 181.0 125.7 92.3 70.7 55.9 45.2 37.4

4-SPAN LIVELOAD 169.0 117.3 86.2 66.0 52.1 42.2 34.9

22- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 200.0 162.4 119.3 91.3 72.2 58.5 48.3

2-SPAN LIVELOAD 200.0 147.7 108.5 83.1 65.6 53.2 43.9

3-SPAN LIVELOAD 200.0 184.6 135.6 103.8 82.0 66.5 54.9

4-SPAN LIVELOAD 200.0 172.4 126.6 97.0 76.6 62.1 51.3

NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.

16"

1¾"

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.

Page 12: Technical/insTallaTion informaTion - Metl-Span

LS-12REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

ENGINEERINGLokSeam® PANEL

SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING

PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)

24 50 1.41 0.0472 0.0597 1.7888 0.0953 0.0682 2.042922 50 1.81 0.0663 0.0878 2.6292 0.1313 0.0954 2.8577

NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof

theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.

12"

1¾"

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.

Page 13: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-13

LokSeam®

ENGINEERINGLokSeam® PANEL

ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT

24- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 200.0 151.3 111.2 85.1 67.3 54.5 45.0

2-SPAN LIVELOAD 190.8 132.5 97.3 74.5 58.9 47.7 39.4

3-SPAN LIVELOAD 200.0 165.5 121.7 93.2 73.6 59.6 49.3

4-SPAN LIVELOAD 200.0 154.6 113.6 87.0 68.7 55.7 46.0

22- Gauge (Fy = 50 kSI)

SPAN TYPE

LOAD TYPE

SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5

SINGLE LIVELOAD 200.0 200.0 155.5 119.1 94.1 76.2 63.0

2-SPAN LIVELOAD 200.0 194.8 143.1 109.6 86.6 70.1 57.9

3-SPAN LIVELOAD 200.0 200.0 178.9 136.9 108.2 87.6 72.4

4-SPAN LIVELOAD 200.0 200.0 167.0 127.9 101.0 81.8 67.6

NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.

12"

1¾"

The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.

Page 14: Technical/insTallaTion informaTion - Metl-Span

LS-14REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

SPECIFICATIONS

PART 1 - GENERAL1.1 SECTION INCLUDES

A. Snap joint-seamed, standing seam metal roof panels, with related metal trim and accessories.

1.2 RELATED REQUIREMENTSSpecifier: If retaining this optional article, edit list below to correspond to Project.

A. Division01Section"SustainableDesignRequirements"forrelatedLEEDgeneralrequirements.

B. Division05Section"StructuralSteelFraming"forstructural steel framing supporting metal panels.

C. Division05Section"SteelDecking"forcontinuousmetal decking supporting metal panels.

D. Division05Section"Cold-FormedMetalFraming"forcold-formed metal framing supporting metal panels.

E. Division05Section"Cold-FormedMetalTrusses"forcold-formed metal trusses supporting metal panels.

F. Division06Section"Sheathing"forsheathingsubstrate for metal roof panels.

G.Division07Section["ThermalInsulation"]["RoofInsulation"]forthermalinsulationinstalledundermetalpanels.

H. Division07Section"AirBarriers"forairbarrierswithinroof assembly and adjacent to roof assembly.

I. Division07Section"MetalWallPanels"forfactory-formedmetalwall[andsoffit]panels.

J. Division07Section"SheetMetalFlashingandTrim"for formed sheet metal copings, flashings, reglets, and roof drainage items in addition to items specified in this Section.

K. Division07Section"ManufacturedRoofSpecialties"for manufactured copings, reglets, and roof drainage items in addition to items specified in this Section.

L. Division07Section"JointSealants"forfield-appliedjoint sealants.

M.Division13Section"MetalBuildingSystems"forsteelframing supporting metal panels.

1.3 REFERENCESSpecifier: If retaining this optional article, edit list below to correspond to Project.

A. AmericanArchitecturalManufacturer'sAssociation(AAMA):www.aamanet.org:1. AAMA621-VoluntarySpecificationsforHigh

PerformanceOrganicCoatingsonCoilCoatedArchitecturalHotDippedGalvanized(HDG)&Zinc-AluminumCoatedSteelSubstrates.

2. AAMA809.2-VoluntarySpecificationNon-DryingSealants.

B. AmericanSocietyofCivilEngineers(ASCE):www.asce.org/codes-standards: 1. ASCE7-MinimumDesignLoadsforBuildingsand

Other Structures.C. ASTMInternational(ASTM):www.astm.org:

1. ASTMA653-SpecificationforSteelSheet,Zinc-Coated(Galvanized)orZinc-IronAlloy-Coated(Galvannealed)bytheHot-DipProcess.

2. ASTMA755-SpecificationforSteelSheet,MetallicCoatedbytheHot-DipProcessandPrepaintedbytheCoil-CoatingProcessforExteriorExposedBuildingProducts.

3. ASTMA792/A792M-StandardSpecificationforSteelSheet,55%Aluminum-ZincAlloy-CoatedbytheHot-DipProcess.

4. ASTMA980-StandardSpecificationforSteel,Sheet,Carbon,UltraHighStrengthColdRolled.

5. ASTMC645-SpecificationforNonstructuralSteelFraming Members.

6. ASTMC920-SpecificationforElastomericJointSealants.

7. ASTMD226-StandardSpecificationforAsphalt-Saturated Organic Felt Used in Roofing and Waterproofing.

8. ASTMD2244-TestMethodforCalculationofColorDifferencesfromInstrumentallyMeasuredColorCoordinates.

9. ASTMD4214-TestMethodsforEvaluatingDegreeofChalkingofExteriorPaintFilms.

10. ASTME1592-StandardTestMethodforStructural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference.

11. ASTME1980-PracticeforCalculatingSolarReflectanceIndexofHorizontalandLow-SlopedOpaque Surfaces.

D. CoolRoofRatingCouncil(CRRC):www.coolroofs.org/productratingprogram.html: 1.CRRC-1-2008-CRRCProductRatingProgram.

E. InternationalAccreditationService(IAS):1. IASAC472-AccreditationCriteriaforInspection

ProgramsforManufacturersofMetalBuildingSystems,PartB.

F.UnderwritersLaboratories,Inc.(UL):www.ul.com:1. UL580-TestsforUpliftResistanceofRoof

AssembliesG.USEnvironmentalProtectionAgency:www.

energystar.gov/index.cfm: 1. EnergyStarReflectiveRoofProducts.

H. USGreenBuildingCouncil(USGBC):www.usgbc.org:1. LEED-LeadershipinEnergyandEnvironmental

Design(LEED)GreenBuildingRatingSystems.

SECTION 07 41 13Metal Roofing

Page 15: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-15

LokSeam®

SPECIFICATIONS1.4 ADMINISTRATIVE REQUIREMENTS

A. Preinstallation Meeting: Prior to erection of framing, conduct preinstallation meeting at site attended byOwner,Architect,manufacturer'stechnicalrepresentative, inspection agency and related trade contractors.1. Coordinatebuildingframinginrelationtometal

panel system. 2. Coordinateopeningsandpenetrationsofmetal

panel system.3. CoordinateworkofDivision07Sections"Roof

Specialties"and"RoofAccessories"andopeningsandpenetrationsandmanufacturer'saccessorieswith installation of metal panels.

1.5 QUALITY ASSURANCEA. Manufacturer/Source: Provide metal roof panel

assembly and accessories from a single manufacturer providing fixed-base roll forming, and accredited under IASAC472PartB.

B. ManufacturerQualifications:Approvedmanufacturerlisted in this Section with minimum five years experience in manufacture of similar products in successful use in similar applications.

Specifier: Retain paragraph below if Owner allows substitutions but requires strict control over qualifying of substituted manufacturers.

1. ApprovalofComparableProducts:Submitthefollowing in accordance with project substitution requirements, within time allowed for substitution review:a. Product data, including certified independent

test data indicating compliance with requirements.

b. Samples of each component.c. Sample submittal from similar project.d. Project references: Minimum of five

installations not less than five years old, with Owner and Architect contact information.

e. Sample warranty.f. IASAC472certificate.

2. SubstitutionsfollowingawardofcontractarenotallowedexceptasstipulatedinDivision01GeneralRequirements.

3. Approvedmanufacturersmustmeetseparaterequirements of Submittals Article.

Specifier:Reviewofmanufacturers'qualifyingofinstallersisrecommended for larger projects. Metl-Span requires Installer and supervisor certification when project requirements include extended warranty.

C. InstallerQualifications:ExperiencedInstaller[certifiedbymetalpanelmanufacturer]withminimumoffiveyears experience with successfully completed projects of a similar nature and scope.

1. Installer'sFieldSupervisor:Experiencedmechanic[certifiedbymetalpanelmanufacturer]supervisingwork on site whenever work is underway.

Specifier: Retain paragraph below and edit as appropriate for Federal projects and for public works projects utilizing Federal funds;consultwithprojectContractingOfficer.CoordinatewithSubmittals Article.

D. BuyAmericanCompliance:Materialsprovidedunderwork of this Section shall comply with the following requirements:1. BuyAmericanActof1933BAA-41U.S.C§§10a–10d.2. BuyAmericanprovisionsofSection1605ofthe

AmericanRecoveryandReinvestmentActof2009(ARRA).

1.6 ACTION SUBMITTALSA. ProductData:Manufacturer’sdatasheetsfor

specified products.Specifier: Retain and edit below to comply with Project requirementsforLEEDorothersustainabledesignrequirements.

B. LEEDSubmittals:1. CreditSS7.2HeatIslandEffect-Roof:Product

data indicating compliance with solar reflectance index requirement.

2. CreditMR4RecycledContent:Productdataindicating the following:a. Material costs for each product having recycled

content.b. Percentages by weight of post-consumer and

pre-consumer recycled content for each item.c. Total weight of products provided.

C. ShopDrawings:Showlayoutsofmetalpanels.Include details of each condition of installation, panel profiles, and attachment to building. Provide details ataminimumscale1-1/2-inchperfootshowingedgeconditions, joints, fastener and sealant placement, flashings, openings, penetrations, roof accessories, lightning arresting equipment, and special details. Make distinctions between factory and field assembled work.1. Indicatepointsofsupportingstructurethatmust

coordinate with metal panel system installation.2. Includedataindicatingcompliancewith

performance requirements.3. Includestructuraldataindicatingcompliancewith

requirements of authorities having jurisdiction.D. SamplesforInitialSelection:Foreachexposed

product specified including sealants. Provide representativecolorchartsofmanufacturer'sfullrangeof colors.

E. SamplesforVerification:Provide12-inch-(305mm-)long section of each metal panel profile. Provide color chip verifying color selection.

Page 16: Technical/insTallaTion informaTion - Metl-Span

LS-16REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

SPECIFICATIONS1.7 INFORMATIONAL SUBMITTALS

A. Product Test Reports: Indicating compliance of products with requirements, witnessed by a professional engineer.

B. QualificationInformation:ForInstallerfirmandInstaller’sfieldsupervisor.

C. IASAccreditationCertificate:Indicatingthatmanufacturer is accredited under provisions of IAS AC472.

Specifier: Retain one or more of three paragraphs below when required for project.

D. BuyAmericanCertification:Manufacturers'lettersof compliance acceptable to authorities having jurisdiction, indicating that products comply with requirements.

Specifier:FSBCcertificationbelowisavailablefor12and16inch wide panels.

E. FloridaStateBuildingCodeCertificate.F. Manufacturer'sWarranty:Samplecopyof

manufacturer'sstandardwarranty.

1.8 CLOSEOUT SUBMITTALSA. Maintenance data.B. Manufacturer'sWarranty:Executedcopyof

manufacturer'sstandardwarranty.

1.9 DELIVERY, STORAGE, AND HANDLINGA. Protect products of metal panel system during

shipping, handling, and storage to prevent staining, denting, deterioration of components or other damage. Protect panels and trim bundles during shipping.1. Deliver,unload,store,anderectmetalpanel

system and accessory items without misshaping panels or exposing panels to surface damage from weather or construction operations.

2. StoreinaccordancewithManufacturer'swritteninstructions. Provide wood collars for stacking and handling in the field.

1.10 COORDINATIONA. Coordinatesizes,profiles,andlocationsofroof

curbs and other roof-mounted equipment and roof penetrations, based upon sizes of actual selected equipment.

1.11 WARRANTYSpecifier:WarrantytermsbelowareavailablefromMetl-Span.Verifythatotherallowablemanufacturersfurnishwarrantymeeting requirements.

A. SpecialManufacturer’sWarranty:Onmanufacturer’sstandard form, in which manufacturer agrees to repair or replace metal panel assemblies that fail in materials and workmanship within one year from date ofSubstantialCompletion.

Specifier:Metl-Span'soptionalsinglesourceweathertightnesswarranties below are available for projects installed by an Metl-Span-certified installer under inspection by an Metl-Span field technical representative. Metl-Span representative can provide warranty cost estimate for desired combination of cost limitation and period of warranty desired by owner.

B. SpecialWeathertightnessWarranty:Onmanufacturer’sstandardform,inwhichmanufactureragrees to repair or replace metal panel assemblies that fail to remain weathertight, including leaks, [withoutmonetarylimitation][uptocostlimitationofsevendollars($7.00)persquarefootofcoveredarea][uptocostlimitationoffourteendollars($14.00)persquarefootofcoveredarea]within[5][10][15][20]yearsfromdateofSubstantialCompletion.

C. SpecialPanelFinishWarranty:OnManufacturer’sstandard form, in which Manufacturer agrees to repair or replace metal panels that evidence deterioration offactory-appliedfinishwithin[25]yearsfromdateofSubstantialCompletion,including:1. FluoropolymerTwo-CoatSystem:

Specifier:Confirmwarrantedperformancevaluesbelowforcustom colors. Second options in subparagraphs below are for Metl-SpanBrite-Red.

a. Colorfadinginexcessof[5][10]HunterunitsperASTMD2244.

b. ChalkinginexcessofNo.[8][6]ratingperASTMD4214.

c. Failure of adhesion, peeling, checking, or cracking.

2. ModifiedSilicone-PolyesterTwo-CoatSystem:Specifier:Confirmwarrantedperformancevaluesbelowforcustom colors. Second options in subparagraphs below are for Metl-SpanBrite-Red.Metl-SpanPolarWhitePolyesterdoesnot carry a warranty against chalking.

a. Colorfadinginexcessof[5][7]HunterunitsperASTMD2244,forverticalapplications.

b. Colorfadinginexcessof[7][10]HunterunitsperASTMD2244,fornon-verticalapplications.

c. ChalkinginexcessofNo.[8][7]ratingperASTMD4214,forverticalapplications.

d. ChalkinginexcessofNo.[6][5]ratingperASTMD4214,fornon-verticalapplications.

e. Failure of adhesion, peeling, checking, or cracking.

PART 2 - PRODUCTS2.1 MANUFACTURERSpecifier: Retain basis of design manufacturer and products listed in this Article where allowed. If inserting comparable manufacturers, carefully review products and engineering capabilities in relation to requirements of this Section, to ensure that other approved manufacturers offer products meeting Metl-Span'sstandards.

Page 17: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-17

LokSeam®

SPECIFICATIONSA. BasisofDesignManufacturer:Metl-SpanMetalRoof

andWallSystems,Metl-Span;Lewisville,TX.Tel:(972)221-6656;Email:[email protected]; Web:www.metlspan.com.1. Providebasisofdesignproduct[,orcomparable

productapprovedbyArchitectpriortobid].

2.2 PERFORMANCE REQUIREMENTSA. General:Providemetalroofpanelsystemmeeting

performance requirements as determined by application of specified tests by a qualified testing facilityonmanufacturer'sstandardassemblies.

Specifier:RecycledContentparagraphbelowdescribescalculationutilizedforLEED-NCCreditMR4.Modifyasrequired to meet project recycled content requirements, or delete if recycled content requirements are stipulated solely in Division01Section"SustainableDesignRequirements."

B. RecycledContent:ForSteelProducts:Postconsumer recycled content plus one-half of preconsumerrecycledcontentnotlessthan[25]percent.

Specifier: Retain one or more radiative property performance subparagraphs below based on project requirements. Retain SolarReflectanceIndexforLEEDprojects.RetainEnergyStarreferenceforprojectsseekingEnergyStarrating;productsmustbelistedonEPAEnergyStarwebsite.RetainCRRCcomplianceforprojectsrequiredtocomplywithCECrequirements.Verifyvalueswithmanufacturerforselectedpanelfinishes.ConfirmthatEnergyCoderequirementsarealso met by below.

C. RadiativePropertyPerformance:1. SolarReflectanceIndex:Minimum78forroof

slopesof2:12orlessand29forroofslopesgreaterthan2:12undermediumwindconditions,perASTME1980.

2. EnergyStarQualified:ListedonUSDoEENERGYSTARRoofProductsQualifiedProductList.

3. EnergyPerformance:ListedinCRRCRatedProductDirectory,withminimumpropertiesasrequiredbyapplicableEnergyefficiencyorHigh-PerformanceGreenBuildingstandard.

D. StructuralPerformance:Providemetalpanelassemblies capable of withstanding the effects of indicated loads and stresses within limits and under conditions indicated:

Specifier:Consultstructuralengineerandeditbelowasrequired by local codes. Insert structural data below if not indicated on drawings. Select applicable deflection limit.

1. WindLoads:Determineloadsbasedonuniformpressure, importance factor, exposure category, and basic wind speed indicated on drawings.a. WindUpliftTesting:Certifycapacityofmetal

panels by actual testing of proposed assembly perASTME1592.

2. SnowLoads:[___lbf/sq.ft.(___Pa)][Asindicated].

3. DeflectionLimits:Withstandinwardandoutwardwind-load design pressures in accordance with applicable building code with maximum deflection of[1/120][1/180][1/240]ofthespanwithnoevidence of failure.

4. SeismicPerformance:ComplywithASCE7,Section9,"EarthquakeLoads."

E. WindUpliftResistance:ComplywithUL580forwind-upliftclass[UL-30][UL-60][UL-90].

F. FloridaStateBuildingCodeCompliance:ComplywithrequirementsofFloridaStateBuildingCode.www.floridabuilding.org/pr/pr_app_srch.aspx

G. ThermalMovements:Allowforthermalmovementsfrom variations in both ambient and internal temperatures. Accommodate movement of support structure caused by thermal expansion and contraction. Allow for deflection and design for thermal stresses caused by temperature differences from one side of the panel to the other.

Specifier: Retain underlayment materials required for project.H. Self-Adhering, High-Temperature Underlayment:

Cold-appliedsheetunderlaymentminimum30mils(0.76mm)thick,consistingofslip-resistant,polyethylene-film top surface laminated to a layer of butylorSBS-modifiedasphaltadhesive,withrelease-paper backing. Provide primer when recommended by underlayment manufacturer for substrate.

I. FeltUnderlayment:Laminatedpolypropyleneandpolyethylenesheet,tear-resistant,UVresistant,manufactured with textured surface for slip resistance, meetingperformancerequirementsofASTMD226.

2.3 METAL ROOF PANELSA. Mechanically-seamed,ConcealedFastener,Metal

Roof Panels: Structural metal roof panel consisting of formed metal sheet with vertical ribs at panel edges, installed by lapping and mechanically interlocking edges of adjacent panels, and attaching panels to supports using concealed clips and fasteners in a weathertight installation.1. BasisofDesign:Metl-Span, LokSeam,

www.metlspan.com/lokseam.html.Specifier:MaterialdescriptionbelowcorrespondstoBIECInternational,Inc.http://galvalume.com/Galvalumesubstrate,available Prepainted from Metl-Span. Second paragraph belowdescribesGalvalumePluswithclearacryliccoatingforuse as exposed metallic finish.

2. Aluminum-ZincAlloy-CoatedSteelSheet:ASTMA792/A792M,structuralquality,Grade50,CoatingClassAZ50(Grade340,CoatingClassAZM150),prepainted by the coil-coating process per ASTM A 755/A755M.

3. Aluminum-ZincAlloy-CoatedSteelSheet:ASTMA792/A792M,structuralquality,Grade50,Coating

Page 18: Technical/insTallaTion informaTion - Metl-Span

LS-18REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

SPECIFICATIONSClassAZ55(Grade340,CoatingClassAZM165)unpaintedGalvalumePluscoating.

Specifier: Prior to selecting metal thickness and panel thicknessbelow,consultmanufacturer’sspantablesandreview selection against panel thickness requirements and span condition. Select appropriate panel configuration to meet requirementsofdesignwindpressure.Important:Consultthisdocument when specifying gauge with the intent that it meet a prescriptive decimal thickness requirement in addition to strengthperformancerequirements.(ClickHeretoView)

a. NominalCoatedThickness:[26gage][24gage][22gage].

b. PanelSurface:[Smoothwithstriationsinpan][Stuccoembossedwithstriationsinpan].

c. ExteriorFinish:[Modifiedsilicone-polyestertwo-coatsystem][Fluoropolymertwo-coatsystem][Fluoropolymertwo-coatmetalliccolorsystem][ExposedGalvalumePluscoating].

d. Color:[Asindicated][AsselectedbyArchitectfrommanufacturer'sstandardcolors][MatchArchitect'scustomcolor].

4. PanelWidth:[12inches(305mm)][16inches(406mm)][18inches(457mm)].

5. PanelSeamHeight:1.75inch(44.4mm).6. JointType:Snapjoint-seamed.

Specifier: Add underlayment materials if required for project. Metl-SpanLokSeamisawatertighttestedpanelthatdoesnotrely upon underlayment materials for waterproofing. Retain slip sheet when recommended by manufacturer for separating metal panels from underlayment or substrate materials.

2.4 METAL ROOF PANEL ACCESSORIESA. General:Providecompletemetalroofpanel

assembly incorporating trim, copings, fasciae, gutters and downspouts, and miscellaneous flashings, in[manufacturer'sstandardprofiles][profilesasindicated].Providerequiredfasteners,closurestrips,thermal spacers, splice plates, support plates, and sealantsasindicatedinmanufacturer'swritteninstructions.

B. FlashingandTrim:Matchmaterial,thickness,andfinish of metal panel face sheet.

C. PanelClips:ASTMC645,withASTMA653/A653M,G90(Z180)hot-dipgalvanizedzinccoating,configured for concealment in panel joints, and identical to clips utilized in tests demonstrating compliance with performance requirements.

D. PanelFasteners:Self-tappingscrewsandother acceptable corrosion-resistant fasteners recommendedbyroofpanelmanufacturer.Whereexposed fasteners cannot be avoided, supply fastenerswithEPDMorneoprenegaskets,withheadsmatching color of metal panels by means of factory-applied coating.

E. JointSealers:Manufacturer'sstandardorrecommended liquid and preformed sealers and

tapes, and as follows:1. Factory-AppliedSeamSealant:Manufacturer's

standard hot-melt type.2. TapeSealers:Manufacturer'sstandardnon-curing

butyltape,AAMA809.2.3. ConcealedJointSealant:Non-curingbutyl,AAMA

809.2.Specifier: Retain one or more of the following four optional paragraphs as required by Project.

F. SteelSheetMiscellaneousFramingComponents:ASTMC645,withASTMA653/A653M,G60(Z180)hot-dip galvanized zinc coating.

G.RoofAccessories:Approvedbymetalroofpanelmanufacturer.RefertoSection077200"RoofAccessories"forrequirementsforcurbs,equipmentsupports, roof hatches, heat and smoke vents, ventilators, and preformed flashing sleeves.

H. SnowGuards:Approvedbymetalroofpanelmanufacturer.RefertoSection077253"SnowGuards"forrequirementsforsnowguardsattachedtometal roof panels.

2.5 FABRICATIONA. General:Providefactoryfabricatedandfinished

metal panels and accessories meeting performance requirements, indicated profiles, and structural requirements.

B. Fabricatemetalpaneljointsconfiguredtoacceptfactory-applied sealant providing weathertight seal and preventing metal-to-metal contact and minimizing noise resulting from thermal movement.

C. Formpanelsincontinuouslengthsforfulllengthofdetailed runs, except where otherwise indicated on approved shop drawings.

D. SheetMetalFlashingandTrim:Fabricateflashingandtrimtocomplywithmanufacturer'swritteninstructions, approved shop drawings, and project drawings. Form from materials matching metal panel substrate and finish.

2.6 FINISHESA. Finishes,General:Prepare,pretreat,andapply

coating to exposed metal surfaces to comply with coatingandresinmanufacturers'writteninstructions.

Specifier: Retain one or more of the following three finish paragraphsasapplicabletotheproject.CoordinatewithWarrantyarticleinPart1.

B. ModifiedSilicone-PolyesterTwo-CoatSystem:0.20–0.25milprimerwith0.7–0.8milcolorcoat[,meetingsolarreflectanceindexrequirements].1.BasisofDesign:Metl-Span,Signature200.

Page 19: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-19

LokSeam®

SPECIFICATIONSSpecifier:Metl-Span'sfluoropolymercoatingsarebasedonArkema,Inc.Kynar500andSolvaySolexisHylar500PVF2resins. Retain optional requirement for solar reflectance index whenrequiredforproject;coordinatewithselectedcolor.

A. FluoropolymerTwo-CoatSystem:0.2–0.3milprimerwith0.7-0.8mil70percentPVDFfluoropolymercolorcoat,AAMA621[,meetingsolarreflectanceindexrequirements].1. BasisofDesign:Metl-Span,Signature300.

B. FluoropolymerTwo-CoatMetallicSystem:0.2–0.3milprimerwith0.7-0.8mil70percentPVDFmetallicfluoropolymercolorcoat,AAMA621[,meetingsolarreflectanceindexrequirements].1. BasisofDesign:Metl-Span,Signature300

Metallic.C. InteriorFinish:0.5miltotaldryfilmthickness

consisting of primer coat and wash coat of manufacturer'sstandardlight-coloredacrylicorpolyester backer finish.

PART 3 - EXECUTION3.1 EXAMINATION

A. Examinemetalpanelsystemsubstrateandsupportswith Installer present. Inspect for erection tolerances and other conditions that would adversely affect installation of metal panel installation. 1. Inspectmetalpanelsupportsubstratetodetermine

if support components are installed as indicated onapprovedshopdrawings.Confirmpresenceofacceptable supports at recommended spacing to match installation requirements of metal panels.

2. PanelSupportTolerances:Confirmthatpanelsupports are within tolerances acceptable to metal panel system manufacturer but not greater than the following:a. 1/4inch(6mm)in20foot(6.1m)inany

direction.b. 3/8inch(9mm)overanysingleroofplane.

B. Correctout-of-toleranceworkandotherdeficientconditions prior to proceeding with insulated metal roof panel system installation.

3.2 PREPARATIONA. Miscellaneous Supports: Install subframing,

girts, furring, and other miscellaneous panel supportmembersaccordingtoASTMC754andmanufacturer'swritteninstructions.

Specifier:Retainparagraph(s)belowformetalroofpanelsappliedoversolidroofsheathing.Retain"Self-AdheringSheetUnderlayment"or"FeltUnderlayment"Paragraphbeloworretain both if required.

B. Self-AdheringSheetUnderlayment:Applyinaccordancewithunderlaymentmanufacturer'swritteninstructions;applyprimerifrequired.Applyatlocations indicated below. Roll laps with roller. Retain

one of two subparagraphs below.1. Applyovertheentireroofsurface.2. Applyovertheroofareaindicatedbelow:

a. Roof perimeter for a distance up from eaves of 24inches(610mm)beyondinteriorwallline.

b. Valleys,fromlowestpointtohighestpoint,foradistanceoneachsideof18inches(460mm).

c. Rakeedgesforadistanceof18inches(460mm).

d. Hips and ridges for a distance on each side of 18inches(460mm).

e. Roof-to-wall intersections for a distance from wallof18inches(460mm).

f. Around roof penetrating elements for a distance fromelementof18inches(460mm).

C. FeltUnderlayment:Applyatlocationsindicatedbelow,inaccordancewithunderlaymentmanufacturer'swritten instructions.

Specifier: Retain one of two subparagraphs below or delete bothifindicatedonDrawings.

1. Applyovertheentireroofsurface.2. Applyonareaofroofnotcoveredbyself-adhering

sheetunderlayment.Lapoveredgesofself-adheringsheetunderlaymentnotlessthan6inches(150mm).

Specifier:Retain"SlipSheet"Paragraphbelowifrequired.D. Flashings:Provideflashingsasrequiredtocomplete

metal roof panel system. Install in accordance with Section076200"SheetMetalFlashingandTrim"andapproved shop drawings.

3.3 METAL PANEL INSTALLATIONA. Snap-Joint-Seamed,StandingSeamMetalRoof

Panels: Install weathertight metal panel system in accordancewithmanufacturer'swritteninstructions,approved shop drawings, and project drawings. Install metal roof panels in orientation, sizes, and locations indicated, free of waves, warps, buckles, fastening stresses, and distortions. Anchor panels and other components securely in place. Provide for thermal and structural movement.

B. Attachpanelstosupportsusingclips,screws,fasteners, and sealants recommended by manufacturer and indicated on approved shop drawings.1. Fastenmetalpanelstosupportswithconcealed

clips at each location indicated on approved shop drawings, with spacing and fasteners recommended by manufacturer.

2. SnapJoint:Neststandingseamsandfastentogether by interlocking and completely engaging factory-applied sealant.

3. Provideweatherproofjacksforpipeandconduitpenetrating metal panels of types recommended by manufacturer.

4. DissimilarMaterials:Whereelementsofmetal

Page 20: Technical/insTallaTion informaTion - Metl-Span

LS-20REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

SPECIFICATIONSpanel system will come into contact with dissimilar materials, treat faces and edges in contact with dissimilar materials as recommended by manufacturer.

3.4 ACCESSORY INSTALLATIONA. General:Installmetalpaneltrim,flashing,and

accessories using recommended fasteners and joint sealers, with positive anchorage to building, and with weather tight mounting. Provide for thermal expansion.Coordinateinstallationwithflashingsandother components.1. Installcomponentsrequiredforacompletemetal

panel assembly, including trim, copings, flashings, sealants, closure strips, and similar items.

2. Complywithdetailsofassembliesutilizedto establish compliance with performance requirementsandmanufacturer'swritteninstallation instructions.

3. Provideconcealedfastenersexceptwherenotedon approved shop drawings.

4. Setunitstruetolineandlevelasindicated.Installwork with laps, joints, and seams that will be permanently weather resistant.

B. JointSealers:Installjointsealerswhereindicatedandwhere required for weathertight performance of metal panelassemblies,inaccordancewithmanufacturer'swritten instructions.1. Preparejointsandapplysealantsperrequirements

ofDivision07Section"JointSealants."

3.5 FIELD QUALITY CONTROLSpecifier: Retain paragraph below when scope and complexity of metal roof panel installation justifies independent inspection and testing provisions.

A.TestingAgency:[Ownerwillengage][Engage]anindependent testing and inspecting agency acceptable to Architect to perform field tests and inspections and to prepare test reports.

3.6 CLEANING AND PROTECTIONA. Remove temporary protective films immediately in

accordancewithmetalroofpanelmanufacturer'sinstructions.Cleanfinishedsurfacesasrecommended by metal roof panel manufacturer.

B. Replacedamagedpanelsandaccessoriesthatcannotbe repaired to the satisfaction of the Architect.

END OF SECTION

Page 21: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-21

LokSeam®

GENERAL INFORMATION

18"

16"

12"

COLOR

SPECIFY ANGLE

95°120°

5¹⁄₂"

1¹⁄₄"

1" 2¹⁄₂"

¹⁄₂"

¹⁄₄"

³⁄₈" ¹⁄₂"

Ridge Flash for Vent

Ridge Flash for Vent

• For use with vent material

• For use with vent material

T-5089 q FL-540 q

5"3⅞"

1¾"

2¼"

PRODUCT CHECkLISTLokSeam® Panel

Clips Bearing PlateStandard

Back-Up Plate Floating Rake Support

• 16-gaugeredoxide• For use with rigid-

board insulation

• 20'Length• 14-gaugeredoxide• Factory slots

• For use at ridge and endlaps

• Prepunched• 16-gaugeredoxide

P-140 q

P-141 q

HW-7500 q

HW-4680 q

UL90-HW-6400 q

Standard-HW-6200 q

HW-776218" qHW-776616" qHW-776412" q

q q q

NOTE:Alltrimtobe24-gaugematerialunlessnoted

6½"

SPECIFY ANGLE

COLOR

Specify Roof Pitch

Ridge/Hip Flash, Fixed

Support Plates

Floating Ridge/Hip

Fixed Ridge

T-5075 q

2½"4"

SPECIFY ANGLE

120°120°

1¹⁄₄"

Ridge Flash, Floating

T-5087 q

SPECIFY ANGLE

COLOR10¼"

⅝"

5" 135°

Specify Roof Pitch

Peak Cap

T-5085 q

5"

COLOR

90°

135°

⅝"

4"Box Rake

T-5235 q

SPECIFY ANGLE

10¹¹⁄₁₆”

1”

SPECIFY ANGLE

11 ¹¹⁄₁₆ "

Page 22: Technical/insTallaTion informaTion - Metl-Span

LS-22REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

GENERAL INFORMATIONPRODUCT CHECkLIST

NOTE:Alltrimtobe24-gaugematerialunlessnoted

T-5151 q

SPECIFYANGLE

3"

⅝"

4"1 ¼"

COLOR

COLOR

SPECIFYANGLE

1" OPEN HEM

⅝"3"

1 ½"

2 ½

Eave Trimw Drip Edge

1"

6"

3" ⁵⁄₈"

⁵⁄₈" ¹⁄₂" ¹⁄₂"

4¹⁄₂"

5¹⁄₂"

SPECIFYANGLE

TO BE DETERMINEDBASED ON SLOPE

Snow Gutter

(PleaseInquire)

8"

2"

Gutter Strap

T-5281 q

4"SPECIFYANGLE

"A"

COLOR

T-5213q

Parapet High Side Eave Flash-Fixed

T-5211q

4"

2 ½"

1¼"

SPECIFYANGLE

4 ¾"

COLOR

Parapet High Side Eave Flash-Floating

T-5215q

COLOR

3½"

1"

OPENHEM

4¼"

90°

Parapet Rake Flash

T-5217 q

Parapet Rake Cleat

1"

1"COLOR

90°

T-5219 q

FILE:EAVE TRIM

3 ½"

"A"

⅝"

SPECIFYANGLE

COLOR

Eave Trim

T-5141q

5½" 4½"

1"⅝"

5¼"

6"

SPECIFYANGLE

COLOR

Box Gutter

T-5261 q

Specify Roof Pitch Specify Roof Pitch

Box Gutter w/Drip Edge

5½" 4½"

1"⅝"

5½"

6"

SPECIFYANGLE

COLOR

1½"

T-5271q

Gutter End

T-5291q

T-5093 q

SPECIFY ANGLE

45°

2"

11" 11"

COLOR

Standard30' or less

SPECIFY ANGL E

45°

2"

22" min. 22" min.

COLOR

ExtendedMore than 30'

Valley Trim - Standard Valley Trim - Extended

T-5097 q

Page 23: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-23

LokSeam®

GENERAL INFORMATIONPRODUCT CHECkLIST

Rib Cover

Tape Sealer Tape Sealer

Perforated Vent Drip

Panel Hemming ToolMetal Vent Material

Continuous Cleat

Tube Sealant

Triple Bead

Tri-Bead Triple Bead

Tri-Bead

1"

3¼" 1"

½"

1 "

PERFORATED 135°

2½" ½"

• For use at eave, ridge, and endlaps

• Paintable• Urethane

• For use at valleys with through fasteners

HW-540—WHITE q HW-541—GRAY q

HW-544—ALMOND q HW-542—MED.BRONZE q

FL-254 q

HW-525 q

HW-502 q

T-5121 q

HW-602 qFL-565 q

HW-504 q

90°

1"

30°

COLOR

2½"

½"

Counterflash

T-5255 q

1½"

⅛"1½"

½"

Offset Cleat

T-5131 q

1"

1¾"

1"

COLOR

Zee Closure

T-5014 q

1"

⅝"

150°

½"

¾"

COLOR⅝"

120°

150°

Alternate Counterflash

T-5221q

Page 24: Technical/insTallaTion informaTion - Metl-Span

LS-24REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

GENERAL INFORMATION

NOTE:Alltrimtobe24-gaugematerialunlessnoted

PRODUCT CHECkLISTFastener #1E

¼"-14x1¼"LongLifeDriller5⁄16"HexWasherHeadwith sealing washer

¼"-14x⅞"LapTek5⁄16"HexWasherHeadwith⅝"O.D.washer

¼"-14x1¼"ShoulderTek25⁄16"HexWasherHeadnowasher ¼"x1¼"NailDriveMasonryAnchor

12-11x1"PancakeHeadwith#3DrillPoint#2QuadrexDrive

12-11x1"PancakeHeadTypeA#2QuadrexDrive

Fastener #4

Fastener #12A

Fastener #5 Fastener #11

Fastener #13A

• Panel to eave strut• Standard endlap• Panel to valley plate (fixed)

• Floating Rake or Parapet Rake

• Rake support to purlin

• zee closure to panel atridge(withoutback-upplate)

q q

q

q

q

q

• Parapet rake flash to masonry parapet wall

• Cliptoplywood• zee closure to plywood• Offset cleat to plywood

• Cliptopurlin• Offset cleat/panel

starter to eave strut or valley plate

Page 25: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-25

LokSeam®

GENERAL INFORMATION

NOTE:Alltrimtobe24-gaugematerialunlessnoted

PRODUCT CHECkLISTFastener #14

⅛"x0.337"PopRivetstainless steel

⅛"x0.525"PopRivetstainless steel

14x4"DeckScrewDriller#3PhillipsTrussHead

12x24x1¼"#2QuadrexDrive

Fastener #211

Fastener #16

Fastener #14A

Fastener #210

Fastener #15D

• zeeClosuretoangleat floating hip

• Trim to trim• Trim to panel

• For clip attachment in a composite roof assembly

• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications

• Lengthtobedeterminedby insulation thickness and metal deck depth

• For clip attachment in a composite roof assembly

• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications

• Lengthtobedeterminedby insulation thickness and metal deck depth

• For clip attachment in a composite roof assembly

• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications

• Lengthtobedeterminedby insulation thickness and metal deck depth

• Cliptojoist• Offset cleat/panel

starter to joist

q

q

q

q

q

q

14x3"DeckScrew#3PhillipsTrussHead

14x6"DeckScrew#3PhillipsTrussHead

Page 26: Technical/insTallaTion informaTion - Metl-Span

LS-26REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

GENERAL INFORMATION

WhenorderingLokSeam® panels without technical assistance from Metl-Span, the following must be provided:

1. PanelLength-Thelengthofeachpanelshouldincludetheproperoverhangattheeave,endlap,andpeakasrequired. Refer to specific details in this manual for the proper overhang at these locations. Add 1½" to the panel length for all panels to be hemmed as shown on page LS-35.

2. PanelDesignations-Eachpanelmusthaveadesignationtobeproperlymanufactured. Thesedesignationsare:Blank,Peak,MidandEave.

3. Panelsmaybespecifiedas:“Notched”forfoldinghemateave.Add3”topanellength.Iffactorynotchingisrequested,

panelswillbenotched1½"atbothends.Note: Notching is only available for Blank Panels.

4. 16"widepanelscanbeswagedbutnotprepunched.

5. If you are using an endlap with an offset cleat as shown on pages LS-37 and LS-53, you must also specify that the panels not be prepunched. Panels will still be swaged as normal. If your specific detail is not in this manual or if you have questions concerning panel length, designation, or product application, call your Metl-Span sales representative.

INSTALLATION GUIDELINES I. Pre-Order

A. Prior to ordering panels, all dimensions should be confirmed by field measurement.

II.JobsiteStorageandHandlingA.Checktheshipmentagainsttheshippinglist.B.DamagedmaterialmustbenotedonBillofLading. C.Panelcratesshouldbehandledcarefully.Aspreaderbarofappropriatelengthisrecommendedforhoisting.D.Checktoseethatmoisturehasnotformedinsidethebundlesduringshipment.Ifmoistureispresent,panels

should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels.

III.ApplicationChecklistA.Checksubstructureforproperalignmentanduniformitytoavoidpaneldistortion.B.Periodiccheckofpanelalignmentiscrucialtoproperpanelalignment. C.Ifthereisaconflictbetweenthismanualandtheerectiondrawings,theerectiondrawingswilltakeprecedence.

ORDERING INFORMATION

BLANK

FEMALE

MALE

FEMALE

MALEEAVE

4½"

MID

1½"

PEAK

THREE OR MORE PANELS FROM EAVE TO PEAK

ONE PANEL FROM EAVE TO PEAK

MORE THAN ONE PANEL FROM EAVE TO PEAKMORE THAN ONE PANEL FROM EAVE TO PEAK

DOWN SLOPE 1½"

FEMALE

MALE

DOWN SLOPE

FEMALE

MALE

DOWN SLOPE

SWA

GED

EN

D

SWA

GED

EN

D

4½"

Page 27: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-27

LokSeam®

GENERAL INFORMATION

1. A single pitch eave strut must be used with the LokSeam® Roof System.

2. Make sure a rake angle or an alternate structural flat surface has been installed on top of the purlins to accept the“RakeSupport”.

3. The walls do not have to be erected before the roof is installed. However, for the purpose of this manual, we have assumed that the wall panels have been installed.

4. Thesubstructure(eavetoridge)mustbeonplanetoleranceof¼"in20'and⅜"in40'.

5. It is critical that the purlins or bar joists at the ridge and endlaps be located exactly as detailed and that they are straight from rafter to rafter. Any mislocation or bowing of these members can cause the fasteners at the ridge or endlaps to foul as the panels expand and contract.

6. PeakPurlinSpacing-FloatingRidge:18"(9"fromcenterlineofridgetowebofpurlin).-FixedRidge:10"(5"fromcenterlineofridgetowebofpurlin).

7. Metl-Span can furnish LokSeam®roofpanelsin18",16"and12"widths.However,forthepurposeofthismanual,wehaveassumedthattheroofpanelswillbe18"wide.

PREPARATORY REQUIREMENTS

CAUTIONApplication and design details are for illustration purposes only, and may not be appropriate for all environmental conditions or building designs. Projects should be engineered to conform to applicable building codes, regulations, and accepted industry practices.

CAUTIONDiaphragmcapabilitiesandpurlinstabilityarenotprovidedbyMetl-Span’sLokSeam® roof system. Therefore, other bracing may berequiredtoconformtoA.I.S.C.orA.I.S.I.specifications.

Page 28: Technical/insTallaTion informaTion - Metl-Span

LS-28REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

GENERAL INFORMATION

CAUTIONImproper unloading and handling of bundles and crates may cause bodily injury or material damage. The manufacturer is not responsible for bodily injuries or material damages during unloading and storage.

5' Minimum

RIGHT WAY

RIGHT WAY

WRONG WAY

WRONG WAYX

X

UNLOADING

Upon receiving material, check shipment against shipping list for shortages and damages. Metl-Span will not be responsible for shortages or damages unless they are noted on the shipping list.

Each bundle should be lifted at its center ofgravity.Wherepossible,bundlesshouldremainbanded until final placement on roof. If bundles must be opened, they should be retied before lifting.

When liftingbundleswithacrane,aspreaderbar and nylon straps should be used. NEVER USE WIRE, ROPE OR CHAIN SLINGS, THEY WILL DAMAGE THE PANELS.

When liftingbundleswitha forklift, forksmustbeaminimumoffivefeetapart.Donottransportopen bundles. Drive slowly when crossingrough terrain to prevent panel buckling.

Page 29: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-29

LokSeam®

GENERAL INFORMATIONUNLOADING(continued)

BLOCk AND BAND WITH CARDBOARD CARTON

This method of bundling is used for orders that are to be picked up by the customer or shipped bycommoncarrier.2x4’sarestrappedunderthe cartons to allow access for straps or a forklift. Bundles less than 25' long may behandled by a forklift. The forklift should have at least5'between forks.Cartons longer than25'shouldbeliftedutilizingaspreaderbarwithnylon straps.

FULL CRATE

This method is used on all overseas shipments orbycustomer’sorder.Handlingrequirementsare the same as block and band.

Page 30: Technical/insTallaTion informaTion - Metl-Span

LS-30REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

GENERAL INFORMATION

NOTEProtective gloves should always be used while handling panels. OSHA safety regulations must be followed at all times.

10' to 12'

10' to 12'

5'

RIGHT WAY

WRONG WAY

HANDLING/ PANEL STORAGE

Standing on one side of the panel, lift it by the seam. If the panel is over 10' long, lift it withtwo or more people on one side of the panel to prevent buckling.

Donotpickpanelsupbytheends.

Store bundled sheets off the ground sufficiently high to allow air circulation beneath bundle and to prevent rising water from entering bundle. Slightly elevate one end of bundle. Prevent rain from entering bundle by covering with tarpaulin, making provision for air circulation between draped edges of tarpaulin and the ground.

PROLONGED STORAGE OF SHEETS IN A BUNDLE IS NOT RECOMMENDED. If conditions do not permit immediate erection, extra care should be taken to protect sheets from white rust or water marks.

Check to see that moisture has not formedinside the bundles during shipment. If moisture is present, panels should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels.

Page 31: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-31

LokSeam®

DETAILS

Metl-Span recommends that only one-piece .080 Aluminum (Min.) roof curbs be used with the LokSeam® roof system. The roof curb will be installed under the roof panels on the upslope end and over the panels at the downslope end. To accomplish this, the roof panels must be endlapped at the upslope and downslope end of the curb. This allows both ends of the curb to shed water and places the heavier gauge metal of the curb under the roof panels for better resistance to foot traffic. The exception is at the downslope end where the curb is on top of the roof panels. Since there are endlaps at this area, back-up plates provide support.

Outsidecapcells(forbottom)areusedtosealthe panel to the roof curb. If the curb must be located in a precise location, order the cap cells loose for field installation.

For the purpose of these instructions, a curb with a factory attached cap cell is illustrated. Panels are assumed to be blank and installed right to left.

ROOF CURB INSTALLATION INSTRUCTIONS

CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.

DECKSCREW(2)PERCLIP(MIN. ³⁄₄"PENETRATION

INTOMETALDECK)

VAPORBARRIER(NOT BYMetl-Span)

FIELDNOTCHANDREMOVERIGIDINSULATION

RIGIDINSULATION(NOT BYMetl-Span)

BEARINGPLATE

METALDECK(NOT BYMetl-Span)

1½"

4½"

TRI-BEAD TAPESEALER

LOWERSWAGEDLokSeam® PANEL

UL90CLIP

BACK-UPPLATE

FASTENER#1E6 "

UPPERLokSeam®

PANEL

Page 32: Technical/insTallaTion informaTion - Metl-Span

LS-32REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

Full length panels may be installed up to the curb location. All panel runs affected by a roof curb must have field endlaps at the upslope and downslope end of the curb. Provision must be made for this condition by ordering two panels12" longer than thepanels immediatelyadjacent to the curb. The panels do not need to be ordered with pre-punched holes. Install all bottom panels, engaging backup plates and apply triple bead tape sealer to each panel as it is being installed. It is critical that the tape sealer be installed across the full panel width. Failure to follow this procedure will cause the curb to leak during rains coupled with high winds.

The first downslope panel immediately adjacent to the last full length panel will require field notchingof the female leg foradistanceof6".Notch the panel just above the lock in the female leg. The remaining portion of the female leg will needtobecrimpedwith“duckbill”visegrips.

The last downslope panel immediately adjacent to the first full length panel after the curb will require field notching of the male leg for a distance of 6". Notch the panel by removingthe male “lock” leg only. Apply two beads ofurethane sealant vertically to the downslope end of the notch.

ROOF CURB INSTALLATION INSTRUCTIONS (continued)

DIRECTION OFPANEL INSTALLATION

R OOF SLOPE

BACK-UP PLATE TRIPLE BEADTAPE SEALER

FRAMING OMITTED FOR CLARITY

FULL LENGTH PANEL

FRAMINGOMITTED FORCLARITY

URETHANE SEALANT

6"

FIELD NOTCH PANEL

FIELD NOTCH AND CRIMP WITH "DUCKBILL" VISE GRIPS

6”

ROOF SLOPE

TRIPLE BEADTAPE SEALER

TRIPLE BEADTAPE SEALER

TRIPLE BEADTAPE SEALER

DIRECTION OF PANELINSTALLATION

FASTENER #1E

CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.

Page 33: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-33

LokSeam®

DETAILS

Install curb on top of bottom panels and curb support framing.Whenusinga loose cap cell,the curb flange must be notched out to accept the panel rib. Apply triple bead tape sealer to the sides and upslope end of curb. Fasten the downslope end of curb to the bottom roof panels andback-upplateswithFastener#1Eat3"o.c.Fasteners must go through the tape sealer.

Install the top run of panels cutting the panels at each side of the curb to fit. Apply urethane sealant to seams of all panels on the upslope end of the curb.Endoftoppanelsshouldbeaminimumof12"fromthepointofthewaterdiverter.Thetoppanelshouldlapontothecurb6".

Install cinch straps at sides of curb to form a compression seal (cinch straps not by Metl-Span)FastencinchstrapsandtoppanelswithFastener#1Eat3"o.c.Fastenersmustgothrough the triple bead tape sealer.

Full length panels may now once again be used.

ROOF CURB INSTALLATION INSTRUCTIONS (continued)

ROOF SLOPE

12" MIN

DIRECTION OFPANELINSTALLATION

FIELD CUT PANELTO FIT CURB

FIELD CUTPANEL TOFIT CURB

FLAT CINCHSTRAP

FRAMINGOMITTED FORCLARITY

URETHANE SEALANT

6"

FIELD NOTCH PANEL

FIELD NOTCH AND CRIMP WITH "DUCKBILL" VISE GRIPS

6”

ROOF SLOPE

TRIPLE BEADTAPE SEALER

TRIPLE BEADTAPE SEALER

TRIPLE BEADTAPE SEALER

DIRECTION OF PANELINSTALLATION

FASTENER #1E

½"

SLOPE

DIRECTION OF INSTALLATION TRIPLE BEAD

TAPE SEALER

ROOF CURB

CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.

Page 34: Technical/insTallaTion informaTion - Metl-Span

LS-34REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

1. LokSeam® Panel2. Urethane Sealant3. Outside Cap Cell4. Back-up Plate5. Fastener #1E6. Tri-bead Tape Sealer7. Roof Curb Made From Structural

Aluminum (Min. .080 Thickness)8. Water Diverter9. Panel Fins (to be cut from panel length

equal to length of curb).

Whenorderingcurbs,specifyone-piececurbsas shown on this page.

ROOF CURB INSTALLATION INSTRUCTIONS (continued)

87

6

5

4

3

2

1

56

6"12" MIN.

18" MIN.

3

97

8

1

5

ROOF SLOPE

DIRECTION OFPANEL INSTALLATION

REMOVE 6" OF MALELEG (LOCK ONLY)

NOTCH FEMALE LEGOF LOWER PANEL

CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.

Page 35: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-35

LokSeam®

DETAILS

NOTES:1.Fieldnotchmaleandfemalelegsofpanel1½".(Factorynotchingisavailable,callMetl-Span)2.Engagepanelhemmingtoolontoprotrudingpanel.3.Bendpaneldowntoformanopenhem.4.Hemmaybetightenedwithapairofvisegrip“duckbills.”5.Panel engagement shown above is for panel runs up to 100' long. For panel runs over 100' long, please call Metl-Span.

1½"

FIELD NOTCH

PANEL HEMMINGTOOL

PANELHEMMING TOOL

PANELHEMMING TOOL

1½"

1½"

½"

½"

1"

FORMINGOPEN HEM

ENGAGINGHEMMING TOOL

NOTCHINGPANEL END

PANELENGAGEMENT

LokSeam® PANEL

LokSeam® PANEL

LokSeam® PANEL

FIELD HEMMING PANEL END

Page 36: Technical/insTallaTion informaTion - Metl-Span

LS-36REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

PANEL CLIP

FACTORY MASTIC

PANEL CLIP

FILL ENDWITH URETHANE

SEALANT

FACTORY MASTIC

LokSeam® PANEL

INSTALLED PANELCROSS SECTION

PANEL CLIPINSTALLATION

PANEL END SEALANT DETAIL

PANEL

NOTES:1.Fillendofpanelseamateaveandvalleyswithurethanesealant.2.ForUL90rating,UL90clipswithtwofastenersmustbeused.

Page 37: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-37

LokSeam®

DETAILS

2 4 53 1

1½"

4½"

1 0 "

TRI-BEAD TAPE SEALER

LOWER SWAGED LokSeam® PANEL

UL 90 CLIP

PURLIN

BACK-UP PLATE

FASTENER #12

OFFSET CLEAT

LOWER SWAGED LokSeam® PANEL

BA CK-UP PLA TE

PRE-PUNCHED PANEL HOLES

LOWER SWAGED LokSeam® PANEL

FASTENER #12 4" O. C.

UPPER LokSeam® PANEL

6"

"

FASTENER #1E

6 "

FASTENER #1E

3

UPPER LokSeam®

PANEL

UPPER LokSeam®

PANEL

CROSS SECTIONOF STANDARDENDLAP

ENDLAPINSTALLATIONSEQUENCE

CROSS SECTIONOF ALTERNATE ENDLAP

FASTENER SEQUENCE(FOR STANDARD ENDLAP ONLY)

ENDLAPOVER PURLINS

NOTES:1.A UL 90 rating is not available on roofs over open framing with endlaps.2.Installbottompanelsothattheeavehastheproperoverhang(refertoeavedetails).Theswaged,upslopeendofthepanelshould

be10"fromthewebofthepurlin.3.Slideaprepunchedback-upplateontotheendofthepanel;makesuretheteethontopoftheback-upplateareontopofthepanel.

Visuallychecktoseethattheholesintheback-upplatealignwiththeprepunchedholesinthepanel4.PlaceTri-Beadtapesealerovertheentirewidthofthepanel.Itmustbecentereddirectlyovertheprepunchedholes.5.Usinganawltoaligntheholes,installtoppanelbylappingitovertheswagedportionofthebottompanel.InstallFastener#1Ein

the prepunched holes in the proper sequence.6.Endlapsrequirerooferectiontoproceedfromlefttorightasviewedfromtheeavelookingtowardtheridge.7. When using the alternate endlap method, LokSeam® panels should be ordered without the prepunched endlap holes.

Panels will be swaged as normal. Order the upper endlap panel 1½" longer than normal for the panel hem. See Page LS-26 for ordering information.

8. When using the alternate endlap detail, use the offset cleat method of attachment at the eave or valley and the fixed detail at the ridge or hip.

Page 38: Technical/insTallaTion informaTion - Metl-Span

LS-38REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

4"FIXED RIDGE/HIPFLASH

2" 9"

TRI-BEADTAPE SEALER

FLOATING RIDGE/HIPFLASH

ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)

MIN 16-GA.SUPPORT PLATE

URETHANE SEALANT

2" x 2" x 16-GA.ANGLE (CONT.)

4" 9"

FASTENER#12

UL 90 CLIP

CROSS SECTIONOF FIXED HIP

CROSS SECTIONOF FLOATING HIP

TRI-BEADTAPE SEALER

ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)

UL 90 CLIP

MIN 16- GA.SUPPORT PLATE

URETHANE SEALANTIMPORTANT NOTE:TEMPORARILY SECUREPANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED LokSeam®

PANEL

LokSeam®

PANEL

FASTENER #14A4" O.C.

FASTENER #12

FASTENER #176" O.C.

FASTENER #14A4" O.C.

FASTENER #14A4" O.C.

2"

HIPOVER PURLINS

NOTES:Fixed Hip

1.Do not use this detail with the fixed eave or valley details.2.Installhipsupportplate,notchingdownturnedlegatpurlinlocations.3.Bevelcutandinstallpanelstofollowslopeofhip.4.InstallTri-Beadtapesealertopansofpanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromthecenterofthehip.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe4"fromcenterofhip.

Floating Hip1.Do not use this detail with the floating eave or valley details.2.Installhipsupportplate,notchingdownturnedlegatpurlinlocations.3.Bevelcutandinstallpanelstofollowslopeofhip.4.InstallTri-Beadtapesealertopanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromcenterofhip.5.Slidealengthof2"x2"x16-gaugeangleunderthepanels.Do not fasten 2" x 2" angle to hip support plate. This will restrain

the panels from floating.6.Bevelcutandinstallzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"

from center of hip. Seal sides and top of zee closures to panel seams with urethane sealant.

Page 39: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-39

LokSeam®

DETAILS

9 " 2"

2"

URETHANE SEALANT

FLOATING RIDGE FLASH

UL 90 CLIP

PURLIN ZEE CLOSURE

BACK-UP PLATE

LokSeam®

PANEL TRI-BEADTAPE SEALER

FASTENER #14 6" O. C.

FASTENER #12 FASTENER #17 6" O. C.

FLOATING RIDGE

RIDGEOVER PURLINS

NOTES:Floating Ridge

1.Do not use this detail with a floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.7.AttachridgeflashtozeeclosurewithFastener#4at6"o.c.

Fixed Ridge1.Use this detail with a fixed eave or valley detail.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.6.AttachridgeflashtozeeclosurewithFastener#4at6"o.c.

12"

2" 2"

RIDGE TRIM

PURLIN ZEE CLOSURE

RIDGE PLATE

LokSeam®PANEL

TRI-BEADTAPE SEALER

FASTENER #4 6" O. C.

FASTENER #12A FASTENER #1E 6" O. C.

URETHANE SEALANT

FIXED RIDGE

Page 40: Technical/insTallaTion informaTion - Metl-Span

LS-40REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

9"2"

2"

TRI-BEADTAPE SEALER

FASTENER #12

RIDGE FLASH

UL 90 CLIP

PURLIN

ZEE CLOSURE

BACK-UPPLATE

RIDGE WITH METALVENT

RIDGE WITHPERFORATED VENT DRIP

LokSeam®

PANEL

FASTENER #4

FASTENER #17 6" O.C.

WEATHER FILTER

FASTENER #4 6" O. C.

9"

2"

PERFORATEDVENT DRIP

RIDGE FLASH FOR VENT

TRI-BEADTAPE SEALER

FASTENER #12 PURLINUL 90 CLIP

ZEE CLOSURE

FASTENER #4 6" O. C.

BACK-UP PLATE

2"

LokSeam®

PANEL

FASTENER #4 12" O. C.

FASTENER #17 6" O.C.

VENTED RIDGEOVER PURLINS

NOTES:Ridge With Metal Vent

1. Do not use this detail with floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Balance vent exhaust at ridge with vent intake at eave or soffit.

Ridge With Perforated Vent Drip1.Do not use this detail with floating eave or valley details.2.Ventedridgedetailshouldbeusedinconjunctionwithsoffitand/oreaveventstoprovidepropercirculationandtopreventweather

infiltration during high winds.3.Installback-upplateandzeeclosureasinNotes2-6above.4.AttachventdriptozeeclosureswithFastener#4at6"o.c.Seallapsinventdripwithurethanesealant.5.AttachridgeflashtoventdripwithFastener#4at6"o.c.

Metal vent material must have urethane sealant at all lap conditions.

Page 41: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-41

LokSeam®

DETAILS

NOTES:VALLEY WITH OFFSET CLEAT

1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panels must be attached to substructure at the ridge, high eave or hip to prevent them from sliding downslope.3.OffsetcleatisinstalledcontinuousalongslopeofvalleyoverTri-beadtapesealerwithFastener#12Aat1'-0"o.c.Fasteners must

go through tape sealer.4.Add 1½" to panel length for the panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.

CROSS SECTION OFFLOATING OVER PURLINS

OFFSET CLEAT

VALLEYTRIM

TRI-BEADTAPE SEALER

WOOD DECK

MOISTUREBARRIER

FASTENER #12 1'-0" O. C.

(FASTENER MUST GOTHROUGH TAPE SEALER)

LokSeam®

PANEL

WOOD DECK MOISTUREBARRIER

ISOMETRIC VIEW OF VALLEY

BEVEL CUT PANEL TO MATCH SLOPEOF VALLEY TRIM

VALLEY TRIM

6" OVERLAP

VALLEY TRIM

FASTENER #12

URETHANESEALANT

SUPPORT PLATE

TRI-BEADTAPE SEALER

LokSeam®

PANEL

FASTENER #12 1'-0" O. C.(FASTENER MUST GO THROUGTHTAPE SEALER)

OFFSET CLEAT

4½" or 9"9" Valley dimension must be used in valleys longer than 30'-0".

MOISTUREBARRIER

MIN 16- GASUPPORT PLATE

FLOATING VALLEYOVER PURLINS

Page 42: Technical/insTallaTion informaTion - Metl-Span

LS-42REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:FIXED VALLEY

1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Do not use this detail with the fixed ridge or hip details.3.Endsofpanelsshouldbe4½"minimumfromtheverticallegofvalleytrim.4.InstallTripleBeadtapesealercontinuouslyunderLokSeam® panel.5.AttachpaneltosupportplatewithFastener#1Eat3"o.c.Fasteners must go through tape sealer under panel.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.

Valley must be designed to support the panels between the purlins.(ie: channel, angle or plate)

PURLIN

BEVEL CUT PANEL TO MATCH SLOPE OF VALLEY TRIM

VALLEY TRIM

FASTENER #1E

ISOMETRIC VIEW OF VALLEY

6" OVERLAP

VALLEY TRIM

FASTENER #12

URETHANESEALANT

SUPPORTPLATE

TRIPLE BEAD TAPE SEALER

FIXED VALLEY

TRIPLE BEAD TAPE SEALER

MIN 16-GA.SUPPORT PLATE

VALLEY TRIM

LokSeam®

PANEL

FASTENER #1E 4" O.C.(FASTENER MUSTGO THROUGH TAPE SEALER)

LokSeam®

PANEL

4½" or 9" 9" Valley dimension must be usedin valleys longer than 30'-0".

FIXED VALLEYOVER PURLINS

Page 43: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-43

LokSeam®

DETAILS

NOTES:Floating High Eave

1.Do not use this detail with the floating eave or valley details.2.Installpanelandclips.3,Installbackupplateontoendofpanel.4.Fieldcutzeeclosurestofitpanelwidth.5.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe6"fromtheendofthepanel.6.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe6½"fromendofpanel.7.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.8.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.

Fixed High Eave1.Use this detail with a floating eave or valley detail.2.Installpanelandclips.3,Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromtheendofthepanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.7.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.

CROSS SECTIONOF FIXED EAVE

TRI-BEADTAPE SEALER

PEAK CAP ZEE CLOSURE

URETHANE SEALANT

HIGH SIDE EAVE STRUT

TRI-BEADTAPE SEALER WALL PANEL

EPDM CLOSURE

OPTIONAL CONTINUOUS CLEAT

FASTENER #14A 6" O.C.

FASTENER #14

FASTENER #1E@ 6” O.C.

2"

CROSS SECTION OFFLOATING HIGH EAVE

TRI-BEADTAPE SEALER

PEAK CAP

UL 90 CLIP

ZEE CLOSURE

URETHANE SEALANT

FASTENER #12

WALL PANEL

6½"

EPDM CLOSURE

FASTENER #14A 6" O.C.

FASTENER #14 FASTENER #17@ 6” O.C.

BACK-UP PLATE

HIGH EAVEOVER PURLINS

Page 44: Technical/insTallaTion informaTion - Metl-Span

LS-44REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Eave with Offset Cleat

1.The offset cleat method of attachment should be used when ridge, high side eave or endlap is fixed to the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.

2.AttachoffsetcleattoeavestrutwithFastener#12Aat1'-0"o.c.3.Tofieldhempanel,seepageLS-31.4.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.

Eave with Drip Edge1.The eave with extended drip edge method of attachment should be used when ridge, high side eave or endlap is fixed to

the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.AttacheavetrimtoeavestrutwithFastener#14Aat2'-0"o.c.3.Tofieldhempanel,seepageLS-31.4.See “Panel End Sealant Detail” on page LS-32.

CROSS SECTION OF EAVE TRIM WITH OFFSET CLEAT

CROSS SECTION OF EAVE TRIMWITH EXTENDED DRIP EDGE

PANEL END DETAIL

OFFSET CLEAT

EAVE TRIM

EAVE STRUT

UL 90 CLIP

WALL PANEL

EPDM CLOSURE

UL 90 CLIP

EAVE STRUT EAVE TRIM

W/DRIP EDGE

EPDM CLOSURE

SEE PAGE LS-36 FOR PANEL ENGAGEMENT

PANEL END DETAIL SEE PAGE LS-36 FOR PANEL ENGAGEMENT

CONTINUOUSCLEAT

LokSeam® PANEL

FASTENER #14

FASTENER #14A

FASTENER #14

WALL PANEL

LokSeam® PANEL

FASTENER #12 1'-0" O. C.

FASTENER #12

FASTENER #14A

FASTENER #12

TRI-BEADTAPE SEALER

FLOATING EAVE WITH EAVE TRIMOVER PURLINS

Page 45: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-45

LokSeam®

DETAILS

NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttacheavetrimtoeavestrutwithFastener#14A(3fastenersper10'piece).3.ApplyTri-Beadtapesealertoslopelegofeavetrim.Edgeoftapesealershouldalignwithedgeofeavestrut.4.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.5.See"PanelEndSealantDetail"onpageLS-32tosealpanelends.

PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT

EAVE TRIM

WALL PANEL

EAVE STRUT

OUTSIDE CLOSURE

OPTIONAL CONTINUOUSCLEAT

LokSeam® PANEL

FASTENER #14

FASTENER #14A

FASTENER #1E

TRI-BEADTAPE SEALER

FIXED EAVE WITH EAVE TRIMOVER PURLINS

FASTENER SPACING @ EAVE

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

Page 46: Technical/insTallaTion informaTion - Metl-Span

LS-46REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Offset Cleat

1.The offset cleat method of attachment should be used when ridge, high eave or endlap is fixed to the substructure. 2.Panels must be attached at one of these points to prevent them from sliding downslope.3.AttachoffsetcleattoeavestrutwithFastener#12Aat1'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.6.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail

for these areas.

Gutter with Drip Edge1.The gutter with drip edge method of attachment should be used when ridge, high eave or endlap is fixed to the

substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.InstallguttertoeavestrutwithFastener#14Aat2'-0"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Thisdetailmaybeusedonroofswithpitchesof4:12orless.Forroofswithpitchesgreaterthan4:12,callMetl-Span.8.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail

for these areas.

CROSS SECTION OF GUTTER WITHDRIP EDGE

FASTENER #12 1'-0" O. C.

UL 90 CLIP

GUTTER STRAP

BOX GUTTER

OFFSET CLEAT

EAVE STRUT

WALL PANEL

UL 90 CLIP

GUTTER STRAP

BOX GUTTER W/DRIP EDGE EAVE STRUT

CROSS SECTION OF GUTTER WITHOFFSET CLEAT

PANEL END DETAIL SEE PAGE LS-35 FOR PANEL ENGAGEMENT

PANEL END DETAIL SEE PAGE LS-35 FOR PANEL ENGAGEMENT

LokSeam® PANEL

LokSeam® PANEL

WALL PANEL

FASTENER #14

FASTENER #14A FASTENER #14

FASTENER #12

FASTENER #12

TRI-BEADTAPE SEALER

FLOATING EAVE WITH GUTTEROVER PURLINS

Page 47: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-47

LokSeam®

DETAILS

NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertoeavestrutwithFastener#14A(3fastenersper10'piece).3.Installgutterstrapsevery3'-0"ofgutterlength.AttachtooutsidelegofgutterandtoeavestrutwithFastener#14A.4.ApplyTri-Beadtapesealertoslopelegofgutter.Edgeoftapesealershouldalignwithoutsideedgeofeavestrut.5.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.

FASTENER #1E (4 PER PANEL)

GUTTER STRAP

BOX GUTTER

TRI-BEAD TAPE SEALER

EAVESTRUT

EAVE STRUT

TRI-BEAD TAPE SEALER

GUTTER STRAP

BOX GUTTER

LokSeam® PANEL

LokSeam® PANEL

FASTENER #14

FASTENER #14A

CROSS SECTION OFFIXED EAVE WITH GUTTER

ISOMETRIC VIEW OFFIXED EAVE WITH GUTTER

FIXED EAVE WITH GUTTEROVER PURLINS

FASTENER SPACING @ EAVE

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

Page 48: Technical/insTallaTion informaTion - Metl-Span

LS-48REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

CROSS SECTION OF SNOW GUTTER WITH OFFSET CLEAT

UL 90 CLIP

GUTTER STRAP 3'-0" O. C.

OFFSET CLEAT

EAVESTRUT

WALL PANEL

FASTENER #12 (TWO PER CLIP)

SNOWGUTTER

TRI-BEADTAPE SEALER

CROSS SECTIONOF SNOW GUTTER THROUGH FASTENER

GUTTER STRAP 3'-0" O. C.

EAVESTRUT SNOW

GUTTER

TRI-BEADTAPE SEALER

FASTENER #1E

FASTENER #14

¹⁄₂”

½"

LokSeam® PANEL

LokSeam® PANEL

FASTENER #14

WALL PANEL

FASTENER #121'-0" O. C.

FASTENER #14A

FASTENER #14A

FASTENER #14A

FASTENER #14A

FASTENER SPACING @ EAVE

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

SNOW GUTTEROVER PURLINS

NOTES:Through Fastened

1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertoeavestrutwithFastener#14A(3fastenersper10'piece).3.AttachgutterstrapstogutterwithFastener#14at3'-0"o.c.4.ApplyTri-Beadtapesealertoslopelegofgutter.5.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.6.See “Panel End Sealant Detail at Eave” on page LS-32 to seal panel ends.

Page 49: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-49

LokSeam®

DETAILS

NOTES:1. The top dimension of the rake trim will be affected by the wall panel thickness.2. InstallfloatingrakesupportwithFastener#5at2'-0"o.c.3. Engagefemalelegofpaneloverrakesupport.4. ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.

FASTENERS MUST GO THROUGH RAkE SUPPORT.5. ApplyTri-BeadtapesealertotopofparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6. Use continuous cleat to hold bottom of rake trim in place. Fasten continuous cleat to each high rib of wall panel.7. If roof finishes on module, finishing detail will be similar to starting detail. If roof finishes off module, field cut and bend last panel run to fit

against floating rake support. Install parapet rake cleat, tape sealer and rake trim as previously described.8. If rake trim is not to be immediately installed, temporarily fasten panels to rake support to prevent wind damage.

TRI-BEADTAPE SEALER

FASTENER #14(@ 6" O.C.)

BOX RAKE

FLOATINGRAKESUPPORT

FASTENER #1E

RAKEANGLE

PURLIN

PARAPETRAKE CLEAT

PURLIN

RAKEANGLE

TRI-BEAD TAPE SEALER

BOX RAKE

WALL PANEL

FLOATINGRAKESUPPORT

EPDMCLOSURE

PARAPET RAKE CLEAT

5"

CONTINUOUSCLEAT

EPDMCLOSURE

CONTINUOUSCLEAT

CONTINUOUSCLEAT

FINISHING OFFMODULE

BEGINNINGON MODULE

FASTENER #5 @ 2" O.C.

FASTENER #14(@ 6" O.C.)

LokSeam®

PANEL

CONTINUOUSCLEAT

ISOMETRICVIEW OFBEGINNING ONMODULE

FLOATING RAkEOVER PURLINS

Page 50: Technical/insTallaTion informaTion - Metl-Span

LS-50REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Floating Parapet High Eave

1.Do not use this detail with the floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosuresshouldbezeefromendofpanels.6.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.7.AttachparapethighsideeavetrimtozeeclosurewithFastener#4Aat6"o.c.8.Sealcounterflashtoparapetwallwithurethanesealant.

Fixed Parapet High Eave1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.6.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.7.AttachparapethighsideeavetrimtozeeclosurewithFastener#4Aat6"o.c.

PARAPET HIGH EAVE OVER PURLINS

LokSeam® PANEL

ZEEPURLIN

BUILDINGDIM.

FIELDSAWCUT

FLEXIBLEMEMBRANE

TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE

TRI-BEAD TAPESEALER(HW-504) @TOP OFCLOSURE& TOP OF

FLEXIBLEMEMBRANE

TRI-BEAD TAPESEALER(HW-504)

MASONRYWALL(NOTBYMetl-Span)

PARAPETHIGHEAVETRIM

COUNTERFLASH(T-5225)

URETHANETUBESEALANTCONTINUOUS

14-10x2"DECKSCREW (FASTENER#209)@24"O.C.(PRE-DRILLHOLE)

UL90CLIP (HW-6400)

¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)(1)PERRIB

¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)

URETHANETUBESEALANT@CLOSUREENDS2"

2"7"

BACKUPPLATE(HW-7762)@18"PANEL(HW-7766)@16"PANEL(HW-7764)@12"PANEL

ZEECLOSURE(T-5014)(FIELDCUT TO FIT PANEL)

12-14x1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)

(2PERCLIP)

¹⁄₄"-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOT INSTALL THRU PANELRIB)

HIGHSIDE EAVEFLASH

TRI-BEADTAPESEALER

TRI-BEADTAPESEALER

ZEECLOSURE

PURLIN

PARAPETWALL

COUNTERFLASH

URETHANESEALANT

URETHANESEALANT

BACK-UPPLATE

ISOMETRIC VIEWOF HIGH SIDE EAVE

FASTENER#11

LokSeam®

PANEL

FASTENER#146"O.C.

Page 51: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-51

LokSeam®

DETAILS

NOTES:1.InstallfloatingrakesupportwithFastener#5at2'-0"o.c.Fastenersmustbeinstalledincenterofslot.2.Engagefemalelegofpaneloverrakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneandparapetrakecleattopanellegwithFastener#1Eat

2'-0"o.c.FASTENERS MUST GO THROUGH RAkE SUPPORT.4.EngageopenhemofparapetrakeflashontoparapetrakecleatandfastentoplegtoparapetwallwithFastener#11.5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun

to fit against floating rake support. Install parapet rake cleat, tape sealer, and parapet rake flash as previously described.6.Ifparapetrakeflashisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.

FLOATING PARAPET RAkEOVER PURLINS

BUILDINGDIM.

FEILDSAWCUT

FEILDSAWCUT

FEILDCUT&BENDUP1³⁄₄"LEG

TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE

TRI-BEAD TAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE

¹⁄₈ x ³⁄₈ POPRIVET(FASTENER14A)

¹⁄₈ x ³⁄₈ POPRIVET(FASTENER14A)

TRI-BEADTAPESEALER(HW-504)

TRI-BEADTAPESEALER(HW-504)

FLEXIBLEMEMBRANE

FLEXIBLEMEMBRANE

MASONRYWALL(NOTBYMetl-Span)

2x4x16GA.ANGLE

2x4x16GA.ANGLE

14-10x2"DECKSCREW (FASTENER#209)

@24"O.C.(PRE-DRILLHOLE)

14-10x2"DECKSCREW(FASTENER#209) @24"O.C.(PRE-DRILLHOLE)

ZEEPURLIN

LokSeam® PANEL

LokSeam® PANEL

UL90CLIP(HW-6400)

¹⁄₄"-14x1¹⁄₄"LONGLIFES.D.W/WASHER(FASTENER#1E)@12"O.C.

¹⁄₄"-14x1¹⁄₄"LONGLIFES.D.W/WASHER(FASTENER#1E)@12"O.C.

ZEECLOSURE(T-5014)

PARAPETRAKETRIM(T-5218)

PARAPETRAKETRIM(T-5218)

COUNTERFLASH(T-5225)

COUNTERFLASH(T-5225)

URETHANETUBESEALANTCONTINUOUS

URETHANETUBESEALANTCONTINUOUS

12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)(1)PERCONN.@EACHPURLIN

12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)(1)PERCONN.@EACHPURLIN

FINISHING OFF MODULE

Page 52: Technical/insTallaTion informaTion - Metl-Span

LS-52REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.Donotusethisdetailwiththefixedridgeorhipdetails.2.Fieldcutlegsofpanelsandbendtorequiredangle.3.Fillbothexposedendsofpanelwithurethanesealant.4.Fieldnotchribcovertoallowittobendtotheproperangle.5.Fieldapplyabeadofurethanesealantoverribbeforeapplyingribcover.6.Do not use this detail inside the building envelope.

RIB COVER

F ASTENER #12

EAVE STRUT

EAVE STRUT

URETHANE SEALANT BEND RIB COVER AND INSTALL ON PANEL

SEAL BOTH PANEL ENDS WITHURETHANE SEALANT

URETHANE SEALANT

FIELD NOTCH RIB COVER TO MATCH ROOF SLOPE

LokSeam® PANEL

LokSeam® PANEL

FASTENER #14

FASTENER #14

INSTALLATION DIRECTION

CROSS SECTIONOF ROOFTRANSITION

ISOMETRIC VIEWOF ROOF TRANSITION

UL 90 CLIP

UL 90 CLIP

ROOF TRANSITIONOVER PURLINS

Page 53: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-53

LokSeam®

DETAILS

NOTES:1.The above endlap detail must be used with the floating eave or valley details. The fixed detail must be used at the ridge

or hip. The above detail also requires that the LokSeam® panels be ordered without prepunched endlaps. Panels will be swaged as normal. Order the upper endlap panel 1½" longer than normal for the panel hem. See Page LS-26 for ordering information.

2.Installbottompanelsothateavehasproperoverhang(refertoEaveDetails).3.Atupslopeendofbottompanel,placeTri-Beadtapesealeroverentirewidthofpanel.Centeroftapesealershouldbe4½"fromend

of panel.4.Installoffsetcleatacrosswidthofpanel(overtapesealer)withFastener#13Aat4"o.c.Fasteners must go through tape sealer.5.Fieldnotchmaleandfemalelegsofpanel1½"andbendpaneltoformanopenhem.6.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels

ENDLAPOVER WOOD DECk

TRI-BEAD TAPE SEALER

OFFSET CLEAT

UL 90 CLIP

LOWER SWAGED LokSeam® PANEL

UPPER LokSeam®

PANEL

LOWER SWAGED LokSeam® PANEL

FASTENER #13 4" O.C.

MOISTURE BARRIER

TRI-BEAD TAPE SEALER

WOOD DECK

OFFSET CLEAT

3"UPPER LokSeam®

PANEL

FASTENER #13 4" O.C. CROSS SECTION

ENDLAP OVER WOOD DECK

ENDLAPSEQUENCEINSTALLATION

Page 54: Technical/insTallaTion informaTion - Metl-Span

LS-54REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Fixed Hip

1.Do not use this detail with the fixed eave or valley details.2.Bevelcutandinstallpanelstofollowslopeofhip.3.InstallTri-Beadtapesealertopanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromthecenterofthehip.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe4"fromcenterofhip.

Floating Hip1.Do not use this detail with the floating eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.Slidealengthof2"x2"x16-gaugeangleunderthepanels.5.Installzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"fromcenterof

ridge. Seal sides of zee closures to panel seams with urethane sealant.

HIPOVER WOOD DECk

4"FIXED RIDGE/HIP FLASH

2" 9"

TRI-BEADTAPE SEALER FLOATING RIDGE

FLASH

ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)

URETHANE SEALANT

2"x2"x16-GA.ANGLE (CONT.)

4"9"

FASTENER #13

2"

UL 90 CLIP

STANDARD FIXED HIP OVER WOOD DECK

TRI-BEADTAPE SEALER

ZEE CLOSURE(FIELD CUT TO LENGTH AND BEVEL CUTTO FIT PANEL)

UL 90 CLIP

URETHANE SEALANT IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED LokSeam®

PANEL

LokSeam®

PANEL

FASTENER #144" O.C.

FASTENER #13

FASTENER #136" O.C.

FASTENER #144" O.C.

MOISTUREBARRIER

WOOD DECK

WOOD DECK

MOISTUREBARRIER

STANDARD FLOATING RIDGE/HIP OVER WOOD DECK

FASTENER #14A4" O.C.

Page 55: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-55

LokSeam®

DETAILS

NOTES:1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners

must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.6.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels.

FIXED RIDGEOVER WOOD DECk

2"URETHANESEALANT

FIXED RIDGE FLASH

ZEE CLOSURE WOOD DECK

MOISTUREBARRIER

ZEE CLOSURE

URETHANESEALANT

MOISTUREBARRIER

FIXED RIDGE FLASH

2"

UL 90 CLIP

WOOD DECK

STANDARD RIDGE OVER WOOD DECK

ISOMETRICVIEW OF RIDGEOVER WOOD DECK

IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED

FASTENER #144" O.C.

TRI-BEADTAPE SEALER

TRI-BEADTAPE SEALER

FASTENER #144" O.C.

FASTENER #136" O.C.

FASTENER #13

FASTENER #136" O.C.

LokSeam®

PANEL

LokSeam®

PANEL

Page 56: Technical/insTallaTion informaTion - Metl-Span

LS-56REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1. Do not use this detail with floating eave or valley details.2. Field cut zee closures to fit panel width.3. InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromendofpanel.4. Slidealengthof2"x2"x16gaugeangleunderthepanels.5. Installzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"fromcenterof

ridge. Seal sides of zee closures to panel seams with urethane sealant.

FLOATING RIDGEOVER WOOD DECk

TRI-BEAD(HW-504)TAPESEALER

RIDGETRIM(T-5088)

ZEECLOSURE(T-5014)(FIELDCUTTOLENGTHANDBEVELCUTTOFITPANEL)

MOISTUREBARRIER(NOTBYMetl-Span) ⁵⁄₈"PLYWOODMIN.

(NOTBYMetl-Span)

URETHANETUBESEALANT @CLOSUREENDS

2"x2"x16-GA.BACKUPANGLE

9"

FASTENER#13A

2"

UL90CLIP(HW-6400)

LokSeam® PANEL

FASTENER#4@6"O.C.(DONOTINSTALLTHRUPANELRIB)

FASTENER#14A@4"O.C.

2"

ZEECLOSURE

URETHANESEALANT

MOISTUREBARRIER

FLOATINGRIDGEFLASH

WOODDECK

ISOMETRIC VIEW OF FLOATING RIDGEOVER WOOD DECk

TRI-BEADTAPESEALER

FASTENER#14A6"O.C.

Lok-Seam®

PANEL

FASTENER#4@6"O.C.

Page 57: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-57

LokSeam®

DETAILS

NOTES:Ridge With Perforated Vent Drip

1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners

must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Metalventmaterialmusthaveurethanesealantatalllapconditions.

Ridge With Metal Vent1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners

must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Balance vent exhaust at ridge with vent intake at eave or soffit. Metal vent material must have urethane sealant at all trim

lap conditions.

VENTED RIDGEOVER WOOD DECk

TRI-BEADTAPE SEALER

ZEE CLOSURE

URETHANESEALANT

MOISTUREBARRIER

RIDGE FLASHFOR VENT

WOOD DECK

IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED

LokSeam®

PANEL

PERFORATEDVENT DRIP

RIDGE FLASHFOR VENT

TRI-BEADTAPE SEALER

FASTENER #13 UL 90 CLIP

ZEE CLOSURE

FASTENER #46" O.C.

STANDARD RIDGE WITHPERFORATED VENT DRIP

LokSeam®

PANEL

FASTENER #412" O.C.

FASTENER #13 6" O.C.

MOISTUREBARRIER

URETHANESEALANT

2"2"

ISOMETRICVIEW OF METALVENT DRIP

Page 58: Technical/insTallaTion informaTion - Metl-Span

LS-58REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panels must be attached to substructure at the ridge or hip to prevent them from sliding downslope.3.OffsetcleatisinstalledcontinuousalongslopeofvalleyoverTri-BeadtapesealerwithFastener#13Aat1'-0"o.c.

FASTENERS MUST GO THROUGH TAPE SEALER.4.Add 1½" to the panel length for panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.

FLOATING VALLEYOVER WOOD DECk

OFFSET CLEAT

VALLEYTRIM

TRI-BEADTAPE SEALER

WOOD DECK

MOISTURE BARRIER

FASTENER #131'-0" O.C. (FASTENER MUST GOTHROUGH TAPE SEALER)

LokSeam®

PANEL

WOOD DECK MOISTURE BARRIER

BEVEL CUT PANEL TO MATCHSLOPE OF VALLEY TRIM

VALLEY TRIM

6" OVERLAP

VALLEY TRIM

FASTENER #13

URETHANESEALANT

WOOD DECK

TRI-BEADTAPE SEALER

LokSeam®

PANEL

FASTENER #131'-0" O.C.(FASTENER MUSTGO THROUGTHTAPE SEALER)

OFFSET CLEAT

4½" or 9"9" Valley dimension must be usedin valleys longer than 30'-0".

MOISTURE BARRIER

CROSS SECTION OFVALLEY OVER WOOD DECK

ISOMETRIC VIEW OFVALLEY OVER WOOD DECK

Page 59: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-59

LokSeam®

DETAILS

NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Do not use this detail with fixed ridge or hip details.3.ApplyTriple-BeadtapesealercontinuouslyunderLokSeam®panel.4.AttachpanelstowooddeckwithFastener#2Bat3"oncenter.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.

FIXED VALLEYOVER WOOD DECk

VALLEYTRIM

FILLENDOFRIBW/URETHANSEALANT

TRIPLE-BEADTAPESEALER MOISTUREBARRIER

(NOTBYMetl-Span)12-11xPANCAKEHEAD

SELF-TAPPER(FASTENER#13A)

@5'-0"O.C.

LokSeam® PANEL

WOODDECK MOISTURE BARRIER

BEVELCUT PANELTOMATCHSLOPEOFVALLEYTRIM

VALLEYTRIM

6"OVERLAP

VALLEYTRIM

FASTENER#13A

URETHANESEALANT

WOODDECK

TRIPLE-BEADTAPESEALER

LokSeam®

PANEL

OFFSETCLEAT

4½"or9"9"Valleydimensionmustbeusedinvalleyslongerthan30'-0".

MOISTURE BARRIER

CROSS SECTION OFVALLEY OVER WOOD DECk

ISOMETRIC VIEW OFVALLEY OVER WOOD DECk

¹⁄₄-14 x 1 LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)@3"O.C.(FASTENERMUSTGOTHROUGHTAPESEALER)

⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)

Page 60: Technical/insTallaTion informaTion - Metl-Span

LS-60REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Fixed High Eave

1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromtheendofthepanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.6.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.

Floating High Eave1.Do not use this detail with floating eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromtheendofthepanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.6.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.

HIGH EAVEOVER WOOD DECk

CROSS SECTION OF PEAk

FIXED HIGH EAVE

FLOATING HIGH EAVE

TRI-BEADTAPESEALER

TRI-BEADTAPESEALER

12-11X1"PANCAKEHEADSELF-TAPPER(FASTENER#13A)@6"O.C.

ZEECLOSURE

URETHANETUBESEALANT

PEAKCAP

WALLPANEL

2"

OUTSIDECLOSURE

CONTINUOUSCLEAT

¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.

¹⁄₄-14 x 1LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)

¹⁄₈X ³⁄₆POPRIVET(FASTENER#14A)

@6"O.C.(DONOT INSTALLTHRUPANELRIB)

MOISTURE BARRIER

(NOTBYMetl-Span)

⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)

LokSeam® PANEL

TRI-BEADTAPESEALER

TRI-BEADTAPESEALER

ZEECLOSURE

URETHANETUBESEALANT

PEAKCAP

UL90CLIP

WALLPANEL

2"

OUTSIDECLOSURE

¹⁄₈ x ³⁄₆POPRIVET(FASTENER#14)@12"O.C.

¹⁄₄-14 x 1LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)

1³⁄₄ x 2¹⁄₄x16GA.BACK-UPANGLE

¹⁄₈X ³⁄₆POPRIVET(FASTENER#14A)

@6"O.C.(DONOT INSTALLTHRUPANELRIB)

¹⁄₈X ³⁄₆POPRIVET(FASTENER#13A)

@6"O.C.12-11 x 1"PANCAKEHEADSELF-TAPPER(FASTENER#14A)

(2)PERCLIP

MOISTURE BARRIER(NOTBYMetl-Span)

⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)

IMPORTANTNOTE:TEMPORARILYSECUREPANELSATPEAKUNTILZEECLOSUREIS INSTALLED.

2"

LokSeam® PANEL

Page 61: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-61

LokSeam®

DETAILS

NOTES:EavewithOffsetCleat

1.Panels must be attached to substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.OffsetcleatisinstalledcontinuousalongeaveoverTri-BeadtapesealerwithFastener#13Aat1'-0"o.c.

FASTENERS MUST GO THROUGH TAPE SEALER.3.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels.4.Add 1½" to the panel length for the panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.

EavewithExtendedDripEdge1.Panels must be attached to substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.AttacheavetrimtothewooddeckwithFastener#13Aat2'-0"o.c.

FASTENERS MUST GO THROUGH TAPE SEALER.3.Tofieldhempanel,seepageLS-31.4.See "Panel End Sealant Detail" on page LS-32.

FLOATING EAVE WITH EAVE TRIMOVER WOOD DECk

PANEL END DETAIL

ISOMETRIC VIEW OF EAVE OVER WOOD DECK

CROSS SECTION OF EAVE OVERWOOD DECK

FASTENER #13

OFFSET CLEAT

EAVE TRIM

SEE PAGE LS-40 FOR PANEL ENGAGEMENT

EAVE TRIM

OFFSET CLEAT

UL 90 CLIP

WOOD DECK

TRI-BEADTAPE SEALER

CONTINUOUSCLEAT

CONTINUOUSCLEAT

WALL PANEL

WALL PANEL

FASTENER #13 1'-0" O.C.

EPDMCLOSURE

MOISTUREBARRIER

MOISTUREBARRIER

TRI-BEADTAPE SEALER

WOOD DECK

LokSeam® PANEL

LokSeam® PANEL

FASTENER #13

FASTENER #131'-0" O.C.

Page 62: Technical/insTallaTion informaTion - Metl-Span

LS-62REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttacheavetrimtowooddeckwithFastener#13A(3fastenersper10'piece).3.ApplyTri-Beadtapesealertoslopelegofeavetrim.Edgeoftapesealershouldalignwithedgeofwooddeck.4.INstallpanelandfastentowooddeckwithFastener#2B.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.

FIXED EAVE WITH EAVE TRIMOVER WOOD DECk

PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT

OPTIONAL CONTINUOUSCLEAT

WOOD BLOCKING

WOOD DECK

WALL PANEL

MOISTUREBARRIER

LokSeam® PANEL

EAVE TRIMW/DRIP EDGE

EPDM CLOSURE

FASTENER #14

FASTENER #13A(2) PER CLIP

¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)

¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)

FASTENER SPACING @ EAVE

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

Page 63: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-63

LokSeam®

DETAILS

NOTES:Offset Cleat

1.The offset cleat method of attachment should be used when ridge, peak or endlap is fixed to the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.

2.AttachoffsetcleattowooddeckwithFastener#13Aat1'-0"o.c.3.Tofieldhempanel,seepageLS-314.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.5.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail

for these areas.

Gutter with Drip Edge1.The gutter with drip edge method of attachment should be used when ridge, high eave or endlap is fixed to the

substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.InstallguttertowooddeckwithFastener#13Aat2'-0"o.c.3.AttachgutterstrapstogutterwithFastener#14at3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Thisdetailmaybeusedonroofswithpitchesof4:12orless.Forroofswithpitchesgreaterthan4:12,callMetl-Span.8.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail

for these areas.

FLOATING EAVE WITH GUTTEROVER WOOD DECk

CROSS SECTIONOF GUTTER WITHDRIP EDGE

FASTENER #131'-0" O.C.

UL 90 CLIP

GUTTER STRAP

BOX GUTTER

OFFSET CLEA T

WALL PANEL

UL 90 CLIP

GUTTER STRAP

BOX GUTTERW/DRIP EDGE

CROSS SECTIONOF GUTTER WITHOFFSET CLEAT

PANEL ENDDETAIL SEE PAGE LS-39 FOR PANEL ENGAGEMENT

PANEL ENDDETAIL SEE PAGE LS-39 FOR PANEL ENGAGEMENT

LokSeam® PANEL

LokSeam® PANEL

WALL PANEL

FASTENER #14

FASTENER #14 FASTENER #13

FASTENER #13

TRI-BEADTAPE SEALER

FASTENER #14 MOISTURE BARRIER

WOOD DECK

MOISTUREBARRIER

WOOD DECK

Page 64: Technical/insTallaTion informaTion - Metl-Span

LS-64REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:Fixed Eave with Gutter

1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertowooddeckwithFastener#13A(3fastenersper10'piece)3.Installgutterstrapsevery3'-0"ofgutterlength.AttachtooutsidelegofgutterandslopelegofgutterwithFastener#14.4.ApplyTri-Beadtapesealertoslopelegofgutter.Edgeoftapesealershouldalignwithedgeofwooddeck.5.Installpanelandfastentowooddeckwithfastener#2Batthespacingshownintheabovediagram.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForgreater.

FIXED EAVE WITH GUTTEROVER WOOD DECk

GUTTER STRAP

BOX GUTTERW/DRIP EDGE

LokSeam® PANEL

WALL PANEL

¹⁄₈ x ³⁄₁₆ POP RIVETFASTENER #14

WOOD BLOCKING

MOISTURE BARRIER

WOOD DECK

¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)

¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPER

W/WASHER (FASTENER #2B)

TRI-BEAD TAPE SEALER

FILL END OF RIB WITHURETHANE SEALANT

12-11 X 1" PANCAKE HEADSELF-TAPPER (FASTENER #13A)

@ 6" O.C.

PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT

FASTENER SPACING @ EAVE

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

Page 65: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-65

LokSeam®

DETAILS

NOTES:1.Thetopdimensionoftherakewillbeaffectedbythewallpanelthickness.2.InstallfloatingrakesupportwithFastener#13Aat2'-0"o.c.(InstallFastener#13Asoasnottorestrictthemovementoftherake

support).3.Engagefemalelegofpaneloverrakesupport.4.ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.

FASTENERS MUST GO THROUGH RAkE SUPPORT.5.ApplyTri-BeadtapesealertotopofparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6.Usecontinuouscleattoholdbottomofraketriminplace.Fastencontinuouscleattoeachhighribofwallpanel.Thebottomhemof

theraketrimis“open”.7.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun

to fit against floating rake support. Install parapet rake cleat, tape sealer and rake trim as previously described.8.Ifraketrimisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.

FLOATING RAkEOVER WOOD DECk

TRI-BEADTAPE SEALER

FASTENER #14

BOX RAKE

FLOATING RAKESUPPORT

FASTENER #1E

PARAPETRAKE CLEAT

WALL PANEL

WALL PANEL

EPDMCLOSURE

5"

CONTINUOUSCLEAT

EPDMCLOSURE

CONTINUOUSCLEAT

FINISHING OFFMODULE

BEGINNINGON MODULE

FASTENER #132" O.C.

WOOD DECK

MOISTUREBARRIER

TRI-BEADTAPE SEALER

BOX RAKE

FLOATING RAKE SUPPORT

PARAPET RAKE CLEAT

CONTINUOUSCLEAT

FASTENER #14

LokSeam® PANEL

FASTENER #132" O.C.

FASTENER #132" O.C.

OPEN HEMWALL PANEL

MOISTUREBARRIER

WOOD DECK CONTINUOUSCLEAT

ISOMETRICVIEW OFBEGINNINGON MODULE

Page 66: Technical/insTallaTion informaTion - Metl-Span

LS-66REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.ApplyTri-Beadtapesealertobottomlegofzeeclosure.2.InstallzeeclosuretopanelwithFastener#13Aat12"oncenter.3.ApplyTri-BeadtapesealertotoplegofzeeclosureandattachraketrimtozeeclosurewithFastener#14Aat12"oncenter.4.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutpanelandbenda1/3/4"

leg before installing zee closure.

FIXED RAkEOVER WOOD DECk

TRI-BEADTAPESEALER

ZEECLOSURE

WALLPANEL

OUTSIDECLOSURE

CONTINUOUSCLEAT

FINISHING OFFMODULE

BEGINNINGON MODULE

MOISTUREBARRIER

TRI-BEADTAPESEALERBOXRAKE

ZEECLOSURE

CONTINUOUSCLEAT

LokSeam® PANEL

12-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER

(FASTENER#3)

12-11x1"PANCAKEHEADSELF-TAPPER(FASTENER#13A)@24"O.C.

¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)

@12"O.C.

¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)

@12"O.C.

¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)@12"O.C.

FIELDCUTANDBENDUP1³⁄₄"LEG

¹⁄₄-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@12"O.C.

WALLPANEL

MOISTUREBARRIER

WOODDECK

CONTINUOUSCLEAT

ISOMETRICVIEW OFBEGINNINGON MODULE

BOXRAKETRIM

⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)WOODBLOCKING(NOTBYMetl-Span)

Page 67: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-67

LokSeam®

DETAILS

NOTES:1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.5.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.6.AttachparapethighsideeavetrimtozeeclosurewithFastener#4at6"o.c.7.Sealcounterflashtoparapetwallwithurethanesealant.

FIXED PARAPET HIGH EAVEOVER WOOD DECk

URETHANE SEALANT

COUNTERFLASH

URETHANE SEALANT

TRI-BEADTAPE SEALER

2"

2"

HIGH SIDE EAVE FLASH

UL 90 CLIP

ZEE CLOSURE

CROSS SECTIONOF HIGH SIDEEAVE

TRI-BEADTAPE SEALER

FASTENER #14

FASTENER #11

LokSeam®

PANEL

FASTENER #136" O.C.

FASTENER #13

WOOD DECK

MOISTUREBARRIER

TRI-BEADTAPE SEALER

ZEE CLOSURE

HIGH SIDEEAVE FLASH

TRI-BEADTAPE SEALER

PARAPET WALL

COUNTERFLASH

URETHANE SEALANT

URETHANE SEALANT

ISOMETRIC VIEWOF HIGH SIDE EAVE

FASTENER #11

LokSeam®

PANEL

FASTENER #14 6" O.C.

WOOD DECK MOISTUREBARRIER

Page 68: Technical/insTallaTion informaTion - Metl-Span

LS-68REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.5.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.6.AttachparapethighsideeavetrimtozeeclosurewithFastener#4at6"o.c.7.Sealcounterflashtoparapetwallwithurethanesealant.

FLOATING PARAPET HIGH EAVEOVER WOOD DECk

URETHANETUBESEALANTCONTINUOUS

COUNTERFLASH

URETHANESEALANT@CLOSUREENDS

TRI-BEADTAPESEALER@TOPOFCLOSURE&TOPOFFLEXIBLEMEMBRANE

2"2"

MASONARYWALL(NOTBYMetl-Span)

FLEXIBLEMEMBRANE

PARAPETHIGHEAVETRIM

PARAPETHIGHEAVETRIM

UL90CLIP

ZEECLOSURE(FIELD CUTTOFITPANEL

CROSS SECTIONOF HIGH SIDEEAVE

TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALER

¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL

THROUGHPANELRIB)

¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL

THROUGHPANELRIB)

14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)

14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)

FIELDSAWCUT

LokSeam® PANEL

12-11x1"PANCAKEHEADFASTENER#13A6"O.C.

12-11x1"PANCAKEHEADSELF-TAPPER

(FASTENER#13A) (2)PERCLIP

⁵⁄₈"PLYWOOD(NOTBYMetl-Span)

MOISTUREBARRIER(NOTBYMetl-Span)

TRI-BEADTAPESEALER

ZEECLOSURE

TRI-BEADTAPESEALER

PARAPETWALL

COUNTERFLASH

URETHANESEALANT

URETHANESEALANT

ISOMETRIC VIEWOF HIGH SIDE EAVE

LokSeam®

PANEL

WOODDECK MOISTUREBARRIER

Page 69: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-69

LokSeam®

DETAILS

NOTES:1.InstallfloatingrakesupportwithFastener#13Aat2'-0"o.c.(InstallFastener#13Asoasnottorestrictthemovementoftherake

support).2.Engagefemalelegofpaneloverrakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneandparapetrakecleattopanellegwithFastener#1Eat

2'-0"o.c. FASTENERS MUST GO THROUGH RAkE SUPPORT.

4.EngageopenhemofparapetrakeflashontoparapetrakecleatandfastentoplegtoparapetwallwithFastener#11.5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun

to fit against floating rake support. Install parapet rake cleat, tape sealer and parapet rake flash as previously described.6.Ifparapetrakeflashisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.

FLOATING PARAPET RAkEOVER WOOD DECk

URETHANE SEALANT URETHANE SEALANT COUNTERFLASH

PARAPET RAKEFLASH

TRI-BEADTAPE SEALER

ALTERNATECOUNTERFLASH

FASTENER #13A

FLOATING RAKESUPPORT

PARAPETWALL

PARAPET RAKECLEAT

BEGINNINGON MODULE

FASTENER #1E

FINISHINGOFF MODULE

FASTENER #11

LokSeam®

PANEL

WOOD DECK MOISTUREBARRIER

URETHANESEALANT

PARAPET RAKE FLASH

TRI-BEADTAPE SEALER

FLOATING RAKE SUPPORT

COUNTERFLASH

LokSeam®

PANEL FASTENER #11

ISOMETRIC VIEWOF STARTINGOFF MODULE

WOOD DECK

MOISTUREBARRIER

SAWCUT DETAIL(RECOMMENDED)

SURFACE MOUNTDETAIL

TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE

FLEXIBLE MEMBRANE

FLEXIBLE MEMBRANE

Page 70: Technical/insTallaTion informaTion - Metl-Span

LS-70REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFIXED PARAPET RAkE

OVER WOOD DECk

NOTES:1.ApplyTRi-Beadtapesealertobottomlegofzeeclosure.2.Installzeeclosuretopanelwithfastener#13Aat12"oncenter.3.ApplyTri-Beadtapesealertotoplegofzeeclosure.4.AttachflexiblemembranetoTri-BeadtapesealerontopofzeeclosureandaddasecondrunofTri-Beadtapesealerontopofthe

flexible membrane.5.AttachparapetraketrimtozeeclosurewithFastener#14Aat12"oncenter.6.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutpanelandbenda1ZZZ"

leg before installing zee closure.

URETHANE SEALANT URETHANE SEALANT COUNTERFLASH

PARAPET RAKE FLASH

TRI-BEADTAPE SEALER

PARAPETWALL

ZEE CLOSURE

ZEE CLOSURE

BEGINNINGON MODULE

FINISHINGOFF MODULE

14-10 x 2 DECK SCREW(FASTENER #209)@ 24” O.C. (PRE-DRILL HOLE)

14-10 x 2 DECK SCREW(FASTENER #209) @ 24” O.C.

(PRE-DRILL HOLE)

LokSeam®

PANEL

WOOD DECK

MOISTUREBARRIER

URETHANESEALANT PARAPET RAKE

FLASH

TRI-BEAD TAPE SEALER

COUNTER FLASH

LokSeam®

PANEL

ISOMETRIC VIEWOF STARTINGOFF MODULE

WOOD DECK

MOISTUREBARRIER

SAWCUT DETAIL(RECOMMENDED) SURFACE MOUNT

DETAIL

TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE

TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE

TRI-BEAD TAPE SEALER (HW-504)

FIELD CUT & BENDUP 1³⁄₄” LEG

FLEXIBLE MEMBRANE

FLEXIBLE MEMBRANE¹⁄₈" x ³⁄₁₆" POP RIVET(FASTENER #14A) @ 6" O.C.

¹⁄₈" x ³⁄₁₆" POP RIVET(FASTENER #14A) @ 6" O.C.

12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A)@ 24" O.C.

Page 71: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-71

LokSeam®

DETAILS

NOTES:1.Donotusethisdetailwiththefixedridgeorhipdetails.2.Fieldcutlegsofpanelsandbendtorequiredangle.3.Fillbothexposedendsofpanelwithurethanesealant.4.Fieldnotchribcovertoallowittobendtotheproperangle.5.Fieldapplyabeadofurethanesealantoverribbeforeapplyingribcover.6.Amoisturebarriermustbeinstalledandextendedaminimumof12"upslopeandbehindthefasciatothebottom.7. Do not use this detail inside the building envelope.

ROOF TRANSITIONOVER WOOD DECk

UL 90 CLIPRIB COVER

UL 90 CLIPFASTENER #13

URETHANESEALANT BEND RIB

COVER ANDINSTALL ONPANEL

SEAL BOTH PANELENDS WITHURETHANE SEALANT

URETHANE SEALANT

FIELD NOTCHRIB COVER TO MATCH ROOF SLOPE

LokSeam® PANEL

LokSeam® PANEL

FASTENER #14

FASTENER #14

WOOD DECK

MOISTUREBARRIER

WOOD DECK

MOISTUREBARRIER

CROSS SECTIONOF ROOFTRANSITION

ISOMETRIC VIEWOF ROOF TRANSITION

INSTALLATIONDIRECTION

Page 72: Technical/insTallaTion informaTion - Metl-Span

LS-72REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILS

NOTES:1.Metaldecktobe1½"deep,22-gauge.2.Rigidboardinsulationtobe1"-4"thick.3.ClipsandbearingplatestobeinstalledsimultaneouslywithtwoDeckFastenersintothemetaldeck.Lengthoffastenerstobe

determinedbythicknessofinsulationplusdepthofmetaldeck.Fastenersshouldextend¾"belowmetaldeck.4.Somecompositesystemsrequireadditionalacousticalconsideration.Contactyourarchitectand/orengineerforproperacoustical

design.

RIGID BOARD INSULATIONOVER METAL DECk

RIGID BOARD INSULATION

22-GAUGE1½" METAL DECK

BEARIN G PLA TE

UL 90 CLIP

PURLIN

PURLIN

RIGID BOARDINSULATION

22-GAUGE1½" METAL DECK

UL 90 CLIP

BEARING PLATE

VAPORBARRIER

VAPORBARRIER

LokSeam® PANEL

LokSeam® PANEL

FASTENER #15

ISOMETRIC VIEW OFRIGID BOARD INSULATIONOVER METAL DECK

CROSS SECTION OFRIGID BOARDINSULATION OVERMETAL DECK

Page 73: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-73

LokSeam®

DETAILSENDLAP

OVER METAL DECk

FASTENER SPACING AT ENDLAP

16"

12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"

1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"

18"

1" 1"4" 4" 4" 4"

NOTES:1.Installbottompanelsothattheeavehastheproperoverhang(refertoeavedetails).2.Slideaprepunchedback-upplateontotheupperendofthepanel;makesuretheteethoftheback-upplateareontopofthepanel.

Visuallychecktoseethattheholesintheback-upplatealignwiththeprepunchedholesinthepanel.3.PlaceTri-Beadtapesealerovertheentirewidthofthepanel.Itmustbecentereddirectlyovertheprepunchedholes.4.Usinganawltoaligntheholes,installtoppanelbylappingitovertheswagedportionofthebottompanel.InstallFastener#1Ein

the prepunched holes in the proper sequence.5.Endlapsrequirerooferectiontoproceedfromlefttorightasviewedfromtheeavelookingtowrdtheridge.

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION

INTOMETALDECK)

VAPORBARRIER(NOTBYMetl-Span)

FIELDNOTCHANDREMOVERIGIDINSULATION

RIGIDINSULATION(NOTBYMetl-Span)

BEARINGPLATE

METALDECK(NOTBYMetl-Span)

1½"

4½"

TRI-BEAD TAPESEALER

LOWERSWAGEDLokSeam® PANEL

UL90CLIP

BACK-UPPLATE

FASTENER#1E

6 " UPPERLokSeam®

PANEL

MOISTUREBARRIER(NOTBYMetl-Span)

Page 74: Technical/insTallaTion informaTion - Metl-Span

LS-74REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFIXED RIDGE

OVER METAL DECk

NOTES:1.Use this detail with a floating eave or valley detail.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosures.6.AttachridgeflashtozeeclosurewithFastener#4at6"oncenter.

12"

2" 2"

URETHANESEALANT

RIDGETRIM ZEECLOSURE

RIDGEPLATE

LokSeam®PANEL

TRI-BEADTAPESEALERTOPANDBOTTOMOFCLOSURE

FASTENER#4 6"O.C.

FASTENER#1E 6"O.C.

DECKSCREW@12”O.C.(MIN.3/4”PENETRATIONINTOMETALDECK)

MOISTUREBARRIER(NOTBYMetl-Span)

Page 75: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-75

LokSeam®

DETAILSVENTED RIDGE

OVER METAL DECk

NOTES:1.Do not use this detail with the offset cleat method of attachment at the eave or valley.2.Ventedridgedetailshouldbeusedinconjunctionwithsoffitand/oreaveventstoprovidepropercirculationandtopreventweather

infiltration during high winds.3.Installback-upplateandzeeclosureasinNotes2-6above.4.AttachventdriptozeeclosureswithFastener#4at6"o.c.Seallapsinventdripwithurethanesealant.5.AttachridgeflashtoventdripwithFastener#4at6"o.c.

12"

2"

PERFORATEDVENTDRIP

RIDGEFLASHFORVENTTRI-BEAD

TAPESEALER

ZEECLOSURE

FASTENER#4@6"O.C.

2"

URETHANETUBESEALANT@CLOSUREENDS

LokSeam®PANEL

FASTENER#4 @6"O.C.

DECKSCREW@12”O.C.(MIN.3/4”PENETRATION INTOMETALDECK

FASTENER#1E @6”O.C.

2x4x16GA.ANGLE

RIGIDINSULATION(NOTBYMetl-Span)METALDECK

(NOTBYMetl-Span)

VAPORBARRIER(NOTBYMetl-Span)

MOISTUREBARRIER(NOTBYMetl-Span)

Page 76: Technical/insTallaTion informaTion - Metl-Span

LS-76REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFLOATING VALLEYOVER METAL DECk

NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panelsmustbeattachedtothesubstructueattheridge,higheaveorhiptopreventthemfromsildingdownslope.3.OffsetcleatisinstalledcontinuouslyalongslopeofvalleyoverTri-BeadtapesealerwithFastener#12Aat1'-0"o.c.FASTENERS

MUST GO THROUGH TAPE SEALER.4.Add 1-1/2" to panel length for panel hem.5.See"PanelEndsealantDetail"onpageLS-32tosealpanelendsatvalley.

PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT

OFFSETCLEAT(T-5131)

FIELDNOTCHPANELLEGSANDBENDPANTOFORMOPENHEM

1¹⁄₂"

1¹⁄₂"

1¹⁄₂"

1" ¹⁄₂"¹⁄₂"

4 ¹⁄₂" TRI-BEADTAPESEALER(HW-504)

2"

¹⁄₂"

1'-0" MAX.UL90CLIP(HW-6400)

BEARINGPLATE(HW-7500)

VALLEYTRIM(T-5093)

OFFSETCLEAT(T-5131)

³⁄₈"

VALLEYSUPPORTPLATE(P-140)

LokSeam® PANEL

12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)@12"O.C.(FASTENERMUSTGOTHROUGHTAPESEALER)

VAPORBARRIER(NOTBYMetl-Span)

RIGIDINSULATION(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION

INTOMETALDECK)

DECKSCREW@12"O.C.(MIN.³⁄₄"PENETRATION

INTOMETALDECK)

12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)

@5”O.C.

MOISTUREBARRIER(NOTBYMetl-Span)

Page 77: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-77

LokSeam®

DETAILSFIXED HIGH EAVE

OVER METAL DECk

NOTES:1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealaertotopofzeeclosures.7.AttachpeakcaptozeeclosurewithFastener#4at6"oncenter.

3"x5"x14GA.BENTPLATE

STRUCTURALANGLE(NOTBYMetl-Span)

FASTENER#16@12"O.C.

LONG-LIFETEK4.5FASTENER#78

VAPORBARRIER(NOTBYMetl-Span)

RIGIDINSULATION(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

TRI-BEADTAPESEALER

TRI-BEADTAPESEALER

ZEECLOSURE

URETHANETUBESEALANT

PEAKCAP

WALLPANEL

2"

OUTSIDECLOSURE

¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.

¹⁄₈X³⁄₆POPRIVET(FASTENER#14A)

@6"O.C.(DONOTINSTALLTHRUPANELRIB)

LokSeam® PANEL

FASTENER#1E

PEAKCAP

CONTINUOUSCLEAT

OPTIONALCONTINUOUS CLEAT

¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.

Page 78: Technical/insTallaTion informaTion - Metl-Span

LS-78REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFLOATING EAVE WITH EAVE TRIM

OVER METAL DECk

NOTES:1.Panels must be attached to the substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.AttacheavetrimtobentplateateavewithFastener#12Aat12"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.

UL90CLIP

3"x5"x14GA.BENTPLATE

FILLENDOFRIBW/URETHANESEALANT

EAVETRIMW/EXTENDEDDRIPEDGE

WALLPANEL

STRUCTURALANGLE(NOTBYMetl-Span)

FASTENER#16@12"O.C.

FASTENER#14@12"O.C.

LONG-LIFETEK4.5FASTENER#78

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION

INTOMETALDECK)

VAPORBARRIER(NOTBYMetl-Span)

BEARINGPLATE

RIGIDINSULATION(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

LokSeam® PANEL

FASTENER#12A12"O.C.

PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT

OUTSIDECLOSURE

MOISTUREBARRIER(NOTBYMetl-Span)

Page 79: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-79

LokSeam®

DETAILSFLOATING EAVE WITH GUTTER

OVER METAL DECk

NOTES:1.The floating gutter detail should be used when ridge, high eave or endlap is fixed to the substructure. Panels must be

attached at one of these points to prevent them from sliding downslope.2.InstallguttertobentplateateavewithFastener#12Aat12"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail

for these areas.

UL90CLIP

GUTTERSTRAP

BOXGUTTERW/DRIPEDGE

3"x5"x14GA.BENTPLATE

FILLENDOFRIBW/URETHANESEALANT

WALLPANEL

STRUCTURALANGLE(NOTBYMetl-Span)

FASTENER#16@12"O.C.

LONG-LIFETEK4.5FASTENER#78

FASTENER#14

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION

INTOMETALDECK)

VAPORBARRIER(NOTBYMetl-Span)

BEARINGPLATE

RIGIDINSULATION(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

LokSeam® PANEL

FASTENER#12A12"O.C.

PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT

MOISTUREBARRIER(NOTBYMetl-Span)

Page 80: Technical/insTallaTion informaTion - Metl-Span

LS-80REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFLOATING RAkE

OVER METAL DECk

NOTES:1.Thetopdimensionoftheraketrimwillbeaffectedbythewallpanelthickness.2.InstallfloatingrakesupportwithFastener#12A,2'0"o.c.Installfastenersinthecenteroftheslotsintherakesupport(donotover

tightentoallowtherakesupporttofloat).3.Engagethefemalelegofthepanelovertherakesupport.4.ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.

FASTENERS MUST GO THROUGH THE RAkE SUPPORT.5.ApplyTri-BeadtapesealertothetopoftheparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6.Useacontinuouscleattoholdbottomofraketriminplace.Fastencontinuouscleatateachhighribofwallpanel.7.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun

to fit against floating rake support. Install parapet rake cleat and rake trim as previously described.8.Ifraketrimisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.

TRI-BEADTAPESEALER(HW-504)

12x14x1PANCAKEHEADSELF-DRILLER(FASTENER#12A)@24"O.C(DONOTOVER-TIGHTEN)

CONTINUOUSCLEAT(T-5121)

WALL PANEL

0/ODIMENSION(SEEPLAN)

DECKSCREW(2)PERCLIP (MIN. ³⁄₄"PENETRATIONINTOMETALDECK)

VAPORBARRIER(NOTBYMetl-Span)

RIGIDINSULATION(NOTBYMetl-Span)

STRUCTURAL ANGLE(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

2x4x16GA.ANGLEOUTSIDECLOSURE

BOXRAKETRIM

RAKESUPPORT ANGLE(HW-4680)

12-24x1¹⁄₄"PANHEADTEK4.5SELF-DRILLER

(FASTENER#16)@12"O.C.

12-24x1¹⁄₄"LONG-LIFETEK4.5W/WASHER

(FASTENER#78)

¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14)

@12"O.C.

¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.

PARAPETRAKECLEAT (T-5219)

¹⁄₈"x³⁄₈"POPRIVET(FASTENER#14A)@6"O.C.

LokSeam® PANEL

UL90CLIP(HW-6400)

BEARINGPLATE(HW-7500)

TRI-BEADTAPESEALER(HW-504)

CONTINUOUSCLEAT(T-5121)

0/ODIMENSION(SEEPLAN)

BOXRAKETRIM

RAKESUPPORT ANGLE(HW-4680)

¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14)@12"O.C.

FIELDCUT&BENDUP1³⁄₄"LEGTO FIT AGAINST RAKESUPPORT ANGLE

¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.

PARAPETRAKECLEAT (T-5219)

¹⁄₈"x ³⁄₈"POPRIVET(FASTENER#14A)@6"O.C.

LokSeam® PANEL

MOISTUREBARRIER(NOTBYMetl-Span)

MOISTUREBARRIER(NOTBYMetl-Span)

Page 81: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-81

LokSeam®

DETAILSFIXED PARAPET HIGH EAVE

OVER METAL DECk

NOTES:1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosures.7.InstallFlexiblemembraneoverTri-Beadtapesealer.ApplyasecondlayerofTri-Beadtapesealerontopoftheflexiblemembrane.8.AttachparapethigheavetrimtozeeclosurewithFastener#4at6"oncenter.

URETHANETUBESEALANTCONTINUOUS

COUNTERFLASH

URETHANESEALANT@CLOSUREENDS

TRI-BEADTAPESEALER@TOPOFCLOSURE&TOPOFFLEXIBLEMEMBRANE

2"2"

MASONARYWALL(NOTBYMetl-Span)

FLEXIBLEMEMBRANE

PARAPETHIGHEAVETRIM

UL90CLIP

ZEECLOSURE(FIELD CUTTOFITPANEL

TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALER

¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL

THROUGHPANELRIB)

14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)

FIELDSAWCUT

LokSeam® PANEL

¹⁄₄-14x1¹⁄₄"LONG-LIFE SELF-DRILLERW/WASHER(FASTENER#1E)@6"O.C.

2"x4"x16GA.ANGLE

RIGIDINSULATION(NOTBYMetl-Span)

VAPORBARRIER(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

STRUCTURAL ANGLE(NOTBYMetl-Span)

VAPORBARRIER(NOTBYMetl-Span)

Page 82: Technical/insTallaTion informaTion - Metl-Span

LS-82REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE

LokSeam®

DETAILSFLOATING PARAPET HIGH EAVE

OVER METAL DECk

NOTES:1.InstallfloatingrakesupportwithFastener#5,2'-0"o.c.Installfastenersinthecenteroftheslotsintherakesupport.2.Engagethefemalelefofthepanelovertherakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneovertheTri-Beadtapesealerandapplyasecondlayer

ofTri-Beadtapesealerovertheflexilemembrane.InstalparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.FASTENERS MUST GO THRUGH THE RAkE SUPPORT.

4.Engageopenhemofparapetraketrimontoparapetrakecleat.Attachflexiblemembraneandtoplegofparapetraketrimtoparapetwall with an appropriate fastener, depending upon wall substrate.

5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifroodfinishesoffmodule,fieldcutandbendlastpanelrunto fit against floating rake support. Install flexible membrane, parapet rake cleat and parapet rake trim as previously described.

¹⁄₄"-14x1¹⁄₄SHOULDERTEK2SELF-DRILLER

(FASTENER#5)@24"O.C

0/ODIMENSION(SEEPLAN)

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATIONINTOMETALDECK)

DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATIONINTOMETALDECK)

VAPORBARRIER(NOTBYMetl-Span)

RIGIDINSULATION(NOTBYMetl-Span)

STRUCTURAL ANGLE(NOTBYMetl-Span)

METALDECK(NOTBYMetl-Span)

PARAPETRAKETRIM

PARAPETRAKECLEAT

PARAPETRAKECLEAT

2”x4x16GA.ANGLE

RAKESUPPORTANGLE

TRI-BEADTAPESEALER(HW-504)EACHSIDEOFFLEXIBLEMEMBRANE ¹⁄₄"-14x1¹⁄₄"LONG-LIFE

SELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.

PARAPETRAKETRIM(T-5218)

MASONRYWALL(NOTBYMetl-Span)

URETHANETUBESEALANTCONTINUOUS

COUNTERFLASHFLEXIBLEMEMBRANE

LokSeam® PANEL

UL90CLIP(HW-6400)

BEARINGPLATE(HW-7500)

LokSeam® PANEL

URETHANETUBESEALANTCONTINUOUS

COUNTERFLASH

FLEXIBLEMEMBRANE

TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE

TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE

FIELDCUT&BENDUP1³⁄₄"LEGTOFITAGAINSTRAKESUPPORTANGLE

14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)

14-10x2"DECKSCREW(FASTENER#209)@24"O.C.

(PRE-DRILLHOLE)

FIELDSAWCUT

FIELDSAWCUT

MOISTUREBARRIER(NOTBYMetl-Span)

MOISTUREBARRIER(NOTBYMetl-Span)

Page 83: Technical/insTallaTion informaTion - Metl-Span

SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-83

LokSeam®

NOTES

Page 84: Technical/insTallaTion informaTion - Metl-Span

1720 lakepointe Drive suite #101 lewisville, Texas 75057

Toll-free: 877.585.9969 | Email: [email protected] Web: metlspan.com

© 2019 Metl-Span, part of the Cornerstone Building Brands family. All Rights Reserved. Printed in the U.S.A. | January 31, 2019 / Rev 01.01