tec2245-2 lonworks networked thermostats with single
TRANSCRIPT
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan ControlTechnical Bulletinxxxx-xxxxx
Code No. LIT-12011174Issued May 25, 2006
Network Variables (NVs) and Configuration Properties (CPs) List. . . . . . . . . . . . . . 3
Network Variable Inputs (NVIs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables . . . . . . . . . . . . . 10
NVI RemLockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Network Variable Outputs (NVOs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configuration Network Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Commissioning the Thermostat Using a LONWORKS Network Configuration Tool . . . 18
Understanding LONWorks Network Configuration Tools’ Differences . . . . . . . . . . . . . 18
Changing the Thermostat’s Settings Using a LONWORKS Network Configuration Tool19
Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Adding a Thermostat to the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LONWORKS Thermostat Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Space Comfort Controller Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Thermostat Command Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Commanding the Maximum Heating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Commanding the Minimum Cooling Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Commanding the Cal RS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Status Light-Emitting Diode (LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
TEC2245-2 LonWorks Network Thermostat with Single Proportional Output and One-Speed Fan Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1TEC2245-2 LONWORKS® Networked Thermostats with Single Output andOne-Speed Fan Control Technical Bulletin
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
2
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
Network Variables (NVs) and Configuration Properties (CPs) List
Table 1 shows the NVs and CPs for the TEC2245-2 Series thermostat. Each Network Variable Input (NVI), Network Variable Output (NVO), and Network Configuration Input (NCI) has a reference number, and some objects have a subcategory number. The Sub column lists the thermostat’s Enumeration (Enum) options for the NV or CP. The Byte column shows the actual byte number used for commanding the NV nvoSccStatus and nciGenOpts NVs.
Note: When you use a LONWORKS® network configuration tool to view the Status/Command screen:
• nvoSccStatus is a 64 bit (bit 0 to bit 63) field.
• nciGenOpts is a 25 bit (bit 0 to bit 24) field. Table 1: NV and CPs By Model (Part 1 of 3)No Sub Bit NV or CP Name Model
TEC2245-20 nviSpaceTemp X
1 nviOutdoorTemp X
2 nviSetpoint X
3 nviSpaceRH N/A
4 nviFanSpeedCmd X
5 nviAuxHeatEnable X
6 nviOccCmd X
7 nviApplicMode X
8 nviHeatCool X
9 nviRemLockout X
10 nviDhumiLCK N/A
11 nviAuxOut X
12 nvoSpaceTemp X
13 nvoDischAirTemp X
14 nvoSpaceRH N/A
15 nvoEffectOccup X
16 nvoUnitStatus X
1 mode x
2 heat_output_primary x
3 heat_output_secondary x
4 cool_output x
5 econ_output x
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
3
6 fan_output x
7 in_alarm x
17 nvoSccStatus X
1 0 State Terminal BO5 x
2 1 Fan High x
3 2 UI 3 Status x
4 3 BI 2 Status x
5 4 BI 1 Status x
6 5 Service Alarm x
7 6 Filter Alarm x
8 7 Window Opened x
18 nvoTerminalLoad X
19 nciSetPts X
1 occupied_cool x
2 standby_cool N/A
3 unoccupied_cool x
4 occupied_heat x
5 standby_heat N/A
6 unoccupied_heat x
20 nciRHmodel N/A
1 RHdisplay N/A
2 RHsetpoint N/A
3 DehumHyst N/A
4 DehumCool N/A
5 RHcalib N/A
21 nciGenOpts X
1 0 Control Type N/A
2 1 Drive Time N/A
3 2 Cycles Per Hour N/A
4 3 Reverse Acting Output x
5 4 BI 1 Configuration x
6 5 BI 2 Configuration x
7 6 UI 3 Configuration x
8 7 MenuScroll x
9 8 Auto Mode x
10 9 Temperature Scale x
11 10 Number of Pipe (System) N/A
12 11 Sequence of Operation x
13 12 Fan Mode x
14 13 Maximum Heating Setpoint (Range) x
15 14 Maximum Heating Setpoint (Value) x
Table 1: NV and CPs By Model (Part 2 of 3)No Sub Bit NV or CP Name Model
TEC2245-2
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
4
16 15 Minimum Cooling Setpoint (Range) x
17 16 Minimum Cooling Setpoint (Value) x
18 17 Setpoint Type x
19 18 Temporary Occupancy Time x
20 19 Door Time x
21 20 Deadband x
22 21 Calibration Room Sensor (Range) x
23 22 Calibration Room Sensor (Value) x
24 23 Auxiliary Contact BO 5 Configuration x
25 24 Reheat Output BO 5 Time Base x
22 nciSccModel X
1 0 Thermostat Model Number x
2 1 Software Version x
23 nciHvacType X
24 nciSndHrtBt X
25 nciMinOutTm X
26 nciRcvHrtBt X
27 nciMajVer X
28 nciMinVer X
Table 1: NV and CPs By Model (Part 3 of 3)No Sub Bit NV or CP Name Model
TEC2245-2
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
5
FF) represents
upied and standby or written to, the longer used.
FF) represents
on to the thermostat . Once bound, the
) represents invalid
cupied mode to be are not changed.
d Fan Speed
usedusedt used Not used
edt used
usedused)used
h to the node or to ed controlled by the th the FanMenu bit
Network Variable Inputs (NVIs) Table 2: NVIs (Part 1 of 4)Parameter NVI Name and
SNVT TypeRange and Enumeration Definition
Room Temperature
nviSpaceTempSNVT_temp_p
Valid Range: 14°F/ -10.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7Finvalid data.Note: This NVI allows the temperature setpoint for the occ
mode to be changed via the network. When bound internal temperature reading (internal sensor) is no
Outdoor Air Temperature
nviOutdoorTempSNVT_temp_p
Valid Range: -40°F/-40.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7Finvalid data.Note: This NVI provides outdoor air temperature informati
from a bound network outside air temperature valuethermostat automatically displays the value.
Occupied Cooling and Heating Setpoints1
nviSetpointSNVT_temp_p
Valid Range: Occupied Cooling 54°F/12°C to 100°F/37.5°CValid Range: Occupied Heating 40°F/4.5°C to 90°F/32.0°CStandby Cool Setpoint (Not used)Standby Heat Setpoint (Not used)Default Null (release) Value: 621.8°F/327.67°C or (0x7FFFdata.Note: This NVI allows the temperature setpoints for the oc
changed via the network. The unoccupied setpoints
Room Humidity nviSpaceRHSNVT_lev_percent
Not used.
Fan Mode nviFanSpeedCmdSNVT_switch
Fan Menu Value
State Value Equivalent Percent
Requeste
0 0111110xFF
N/A01-6667-133134-200201-255N/A
N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A
Off - Not Off - Not Low - NoMedium -High3 - Not usAuto - No
4 01110xFF
N/A01-200201-255N/A
N/A0%0.5 to 100%100%N/A
Off - Not Off - Not On (HighOn - Not Auto
Note: This NVI is used to bind an external fan speed switcallow any supervisory device to override the fan spenode’s control algorithm. It is used in conjunction wiin nciGenOpts.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
6
Heat Operation
(Not used)
nabled (Not used)
Invalid)
e. It is used in le 3 for information eqOpera Variables.
nto different ry node to manually led occupancy.
ith any supervisory ater). It is used as with nviApplicMode
Sequence of Operations and Auxiliary Heat
nviAuxHeatEnableSNVT_switch
State Value EquivalentPercentage
Auxiliary
0 N/A N/A Disabled
1 0 0% Disabled
1 1 to 199
0.5 to 99.5% Partially E
1 200 to 255
100% Enabled
0xFF N/A N/A Enabled (
Note: This NVI enables or disables the auxiliary heat stagconjunction with nviHeatCool and SeqOper. See Tabon using the nviHeatCool, nviAuxHeatEnable, and S
Occupancy nviOccCmdSNVT_occupancy
0 = OC_OCCUPIED1 = OC_UNOCCUPIED2 = OC_BYPASS (Not used)3 = OC_STANDBY (Not used)0XFF = OC_NUL (Release to internal schedule)Note: This NVI commands the Space Comfort Controller i
occupancy modes. It is typically sent by a supervisocontrol occupancy modes, or to override the scheduDefault Null Value: OC_NUL = 0xFF
System Mode nviApplicModeSNVT_hvac_mode
0 = HVAC_AUTO (Default)1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not used)3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not used)5 = HVAC_PRE_COOL (Not used)6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not used)9 = HVAC_FAN_ONLY (Not used)10 = HVAC_FREE_COOL (Not used)11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not used)13 = HVAC_ECONOMY (Not used)14 = HVAC_DEHUMID (Not used)15 = HVAC_CALIBRATE (Not used)16 = HVAC_EMERG_COOL (Not used)17 = HVAC_EMERG_STEAM (Not used)0XFF = HVAC_NUL (Not used)Note: This NVI coordinates the Space Comfort Controller w
controller providing the supply energy (hot or cold wheat/cool changeover. It is also used in conjunction and SeqOper.
Table 2: NVIs (Part 2 of 4)Parameter NVI Name and
SNVT TypeRange and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
7
ith any supervisory ater). It is used as with nviApplicMode
with any node that it. It is overridden by TO. If etermines the
uxHeatEnable, and
rmostat.
y Output (BO5), alue of 5 for this
d Fan Speed
Sequence of Operation
nviHeatCoolSNVT_hvac_mode
0 = HVAC_AUTO (Default)1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not used)3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not used)5 = HVAC_PRE_COOL (Not used)6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not used)9 = HVAC_FAN_ONLY (Not used)10 = HVAC_FREE_COOL (Not used)11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not used)13 = HVAC_ECONOMY (Not used)14 = HVAC_DEHUMID (Not used)15 = HVAC_CALIBRATE (Not used)16 = HVAC_EMERG_COOL (Not used)17 = HVAC_EMERG_STEAM (Not used)0XFF = HVAC_NUL (Not used)Note: This NVI coordinates the Space Comfort Controller w
controller providing the supply energy (hot or cold wheat/cool changeover. It is also used in conjunction and SeqOper.
Note: This NVI coordinates the Space Comfort Controller needs to control the heat/cool changeover of the unnviApplicMode, unless nviApplicMode is HVAC_AUnviApplicMode is HVAC_AUTO, then nviHeatCool deffective mode of the unit.
See Table 3 for information on using the nviHeatCool, nviASeqOpera variables.
Lockout nviRemLockoutSNVT_count
See Table 4 for Lockout information.Note: This NVI enables or disables user access to the the
DehumiLCk nviDhumiLCK Not used.
Aux Contact nviAuxOutSNVT_switch
0 = Auxiliary contact Off1 = Auxiliary contact On5 = Follow secondary network commandNote: If this NVI is used to remotely command the Auxiliar
then the Auxiliary Output must be configured to a vfunction to operate.
Room Humidity nviSpaceRHSNVT_lev_percent
Not used.
Fan Mode nviFanSpeedCmdSNVT_switch
Fan Menu Value
State Value Equivalent Percent
Requeste
Table 2: NVIs (Part 3 of 4)Parameter NVI Name and
SNVT TypeRange and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
8
usedused
edt used
usedused
edt used
usedused
ed
usedused
ed
usedused)used
h to the node or to ed controlled by the h the FanMenu byte
Occupied Cool stat to maintain the
0 0111110xFF
N/A01-6667-133134-200201-255N/A
N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A
Off - Not Off - Not LowMediumHigh3 - Not usAuto - No
1 011110xFF
N/A00-100101-200201-255N/A
N/A0%0.5 to 50%50.5 to 100%100%N/A
Off - Not Off - Not LowHigh2 - Not usAuto - No
2 0111110xFF
N/A01-6667-133134-200201-255N/A
N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A
Off - Not Off - Not LowMediumHigh3 - Not usAuto
3 011110xFF
N/A00-100101-200201-255N/A
N/A0%0.5 to 50%50.5 to 100%100%N/A
Off - Not Off - Not LowHigh2 - Not usAuto
4 01110xFF
N/A01-200201-255N/A
N/A0%0.5 to 100%100%N/A
Off - Not Off - Not On (HighOn - Not Auto
Note: This NVI is used to bind an external fan speed switcallow any supervisory device to override the fan spenode’s control algorithm. It is used in conjunction witin nciGenOpts.
1. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint andSetpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermominimum deadband between the two setpoints.
Table 2: NVIs (Part 4 of 4)Parameter NVI Name and
SNVT TypeRange and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
9
Pipes
Pipes
Reheat
Pipes
Pipes
Reheat
Reheat Reheat
cupiedide
cess
ess
ed
ed
cess
ess
.
Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables
NVI RemLockout
Table 3: nviHeatCool, nviAuxHeatEnable, and SeqOpera VariablesCurrent nviHeatCool
nviAuxHeatEnable SeqOpera If nviHeatCool Changed To:
SeqOpera
2 and 4 Pipe Application
3 = HVAC_COOL Disabled 0 = Cooling only 0 = HVAC_AUTO1 = HVAC_HEAT
4 = Cool/Heat 41 = Heating only
3 = HVAC_COOL Enabled 2 = Cooling and Reheat
0 = HVAC_AUTO
1 = HVAC_HEAT
5 = Cool/Heat 4and Reheat3 = Heating and
1 = HVAC_HEAT Disabled 1 = Heating only 0 = HVAC_AUTO3 = HVAC_COOL
4 = Cool/Heat 40 = Cooling only
1 = HVAC_HEAT Enabled 3 = Heating and Reheat
0 = HVAC_AUTO
3 = HVAC_COOL
5 = Cool/Heat 4and Reheat2 = Cooling and
4 Pipe Application
0 = HVAC_AUTO Disabled 4 = Cooling only 0 = HVAC_HEAT3 = HVAC_COOL
1 = Heating only0 = Cooling only
0 = HVAC_AUTO Enabled 5 = Cooling and Reheat
0 = HVAC_HEAT3 = HVAC_COOL
3 = Heating and2 = Cooling and
Table 4: NVI RemLockoutParameter NV and SNVT
TypesLockout Menu Value
Occupied Temperature Setpoints
System Mode Settings
Fan Mode Settings
UnocOverr
Lockout nviRemLockoutSNVT_count
0 Yes access Yes access Yes access Yes ac
1 Yes access Yes access Yes access No acc
2 Not used No access No access Not us
3 Not used No access No access Not us
4 No access No access No access Yes ac
5 No access No access No access No acc
Note: This NVI enables or disables user access to the thermostat
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
10
) in the
ensor t echoes r that of
)
ves the to (SS)
unit. ontroller ordinate itiated is only enOpts), or an
l input. e of the
Network Variable Outputs (NVOs)Table 5: NVOs (Part 1 of 3)Parameter NVO Name and
SNVT TypeRange and Enumeration Definition
Room Temperature
nvoSpaceTempSNVT_temp_p
Valid Range: 14°F/-10.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7FFFrepresents invalid data. This value is sent as an invalid valueevent of a sensor failure.Note: This NVO monitors the effective space temperature s
that the Space Comfort Controller is using for control. Ithe internal value on the device temperature sensor onviSpaceTemp if it is bound, or a value is written to it.
Supply Temperature
nvoDischAirTempSNVT_temp_p
Valid Range: -40°F/-40.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7FFFrepresents invalid data.Note: This NVO monitors the temperature of the air that lea
Space Comfort Controller. UI3 needs to be configuredsupply air sensor monitoring.
Room Humidity
nviSpaceRHSNVT_lev_percent
Not used.
Occupancy nvoEffectOccupSNVT_occupancy
0 = OC_OCCUPIED1 = OC_UNOCCUPIED2 = OC_BYPASS1
3 = OC_STANDBY (Not used)4 = OC_NULNote: This NVO indicates the actual occupancy mode of the
This information is typically reported to a supervisory cor provided to another Space Comfort Controller to cothe operation of multiple units. OC_BYPASS can be inby either nviOccCmd or a local input. NvoEffectOccupin OC_BYPASS for the duration of the ToccTime (nciGuntil reinitiated by either a transition of the local input update to nviOccCmd.
1OC_BYPASS can be initiated by either nviOccCmd or a locaNvoEffectOccup is only in OC_BYPASS for the duration of thToccTime (nciGenOpts), until reinitiated by either a transitionlocal input or an update to nviOccCmd.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
11
used)
used))
sed))sed)
d)d))
ed) used)ot used)
ce and s the city of and an present
alid)
alid)
alid)
msn
rm ot used.
ntroller f heating present
Unit Status nvoUnitStatusSNVT_hvac_status
Sub Name Valid Value
01 Mode 1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not 5 = HVAC_PRE_COOL (Not used6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not u9 = HVAC_FAN_ONLY (Not used10 = HVAC_FREE_COOL (Not u11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not use13 = HVAC_ECONOMY (Not use14 = HVAC_DEHUMID (Not used15 = HVAC_CALIBRATE (Not us16 = HVAC_EMERG_COOL (Not17 = HVAC_EMERG_STEAM (N18 = HVAC_NUL (Not used)Note: This NVO reports the Spa
Comfort Controller inputs’outputs’ status. It combineoperating mode, the capaheating and cooling used,indication if any alarms arein the object.
02 heat_output_primary 0-100%0xFFF (inv
03 heat_output_secondary Not used.
04 cool_output 0-100%0xFFF (inv
05 econ_output Not used.
06 fan_output 0-100%0xFFF (inv
07 in_alarm 0 = No alar1 = Alarm O0x7FF (Aladisabled) N
Note: This NVO is available to report the Space Comfort Costatus. It combines the operating mode, the capacity oand cooling used, and an indication if any alarms are in the object.
Table 5: NVOs (Part 2 of 3)Parameter NVO Name and
SNVT TypeRange and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
12
ue
ivated
ivated
m
m
m
ntroller
and of s in use ues mfort
Thermostat I/O Status
nvoSccStatusUNVT_fc_thermo
Sub Name Valid Value Default Val
01 State Terminal BO2
0 = Off1 = On
0 = Off
02 State Terminal BO1
0 = Off1 = On
0 = Off
03 State Terminal BO4
0 = Off1 = On
0 = Off
04 State Terminal BO3
0 = Off1 = On
0 = Off
05 State Terminal BO5
0 = Off1 = On
0 = Off
06 Fan Low Not used. N/A
07 Fan Med Not used. N/A
08 Fan High Not used. N/A
09 UI 3 Status -40×F/-40.0×C to122×F/50.0×C40×F = Open122×F = Close
N/A
10 BI 2 Status 0 = Activated1 = Not activated
1 = Not act
11 BI 1 Status 0 = Activated1 = Not activated
1 = Not act
12 Service Alarm 0 = No alarm1 = Alarm On
0 = No alar
13 Filter Alarm 0 = No alarm1 = Alarm On
0 = No alar
14 Window Opened 0 = No alarm1 = Alarm On
0 = No alar
15 Dehumidification Active
Not used. N/A
Note: This NVO reports the status of the Space Comfort Coinputs and outputs.
Heating/Cooling Demand
nvoTerminalLoadSNVT_lev_percent
Valid Range: -100 to +100%Note: This NVO indicates the current heat/cool energy dem
the unit. Positive values indicate that cooling energy iby the space comfort controller, whereas negative valindicate that heating energy is in use by the space cocontroller.
Table 5: NVOs (Part 3 of 3)Parameter NVO Name and
SNVT TypeRange and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
13
rious
by the ode.
efault
5°F/4°C
ot sed.
0°F/6.5°C
2°F/2°C
ot sed.
2°F/6.5°C
efault
/A
/A
/A
Configuration Network VariablesTable 6: Configuration Network Variables (Part 1 of 4)Parameter NCI Name and
SNVT, UNVT or SCPT Name
Range and Enumeration Definition
Temperature Setpoints1
nciSetPtsSNVT_temp_setpt
This CP defines the space temperature setpoints for vaheat, cool and occupancy modes.The stand-by setpoints can be modified but are not usedcontroller, as it does not support Stand-By occupancy m
Sub Mode Min. Max. D
01 occupied_cool 54°F/12°C 100°F/37.5°C
72
02 standby_cool Not used. Not used.
Nu
03 unoccupied_cool 54°F/12°C 100°F/37.5°C
82
04 occupied_heat 40°F/4.5°C 90°F/32°C
72
05 standby_heat Not used. Not used.
Nu
06 unoccupied_heat 40°F/4.5°C 90°F/32°C
61
RH Options nciRHmodelUNVT_gen_opts
Not used
Thermostat’s Common CPs
nciGenOptsUNVT_fc_gen_opts
Sub Name Valid Range D
01 Not used. Not used. N
02 Not used. Not used. N
03 Not used. Not used. N
04 Reverse Acting Output
0 = Direct Acting (DA)1 = Reverse Acting (RA)
0
05 BI12 0 = None1 = Rem NSB2 = Motion NO3 = Motion NC4 = Window
0
06 BI22 0 = None1 = Door Dry2 = Override3 = Filter4 = Service
0
07 UI32 0 = None1 = COC/NH2 = COC/NC3 = COS4 = SS
0
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
14
/A
= eating nly
0°F2°C)
4°F2°C)
hours
inutes
°F °C)
°F°C)
Thermostat’s Common CPs
08 Menu Scroll 0 = No scroll1 = Scroll active
1
09 Not used. Not used. 0
10 Temperature Scale
0 = °C1 = °F
°F
11 Not used. Not used. N
12 Sequence of Operation
0 = Cooling Only1 = Heating Only2 = Cooling & Reheat3 = Heating & Reheat
1HO
13 Fan Menu 0 = On4 = Auto
0
14 Heat Maximum Setpoint
40 to 90°F(4.5 to 32° C)
9(3
15 Cool Minimum Setpoint
54 to 100°F(12 to 37.5° C)
5(1
16 Setpoint Type 0 = Permanent1 = Temporary
0
17 Temporary Occ Time
0, 1, 2, 3, up to 24 hours
2
18 Door Time 1, 2, 3, up to 10 minutes
2m
19 Deadband 2, 3, 4, or 5°F(1.0 to 2.5°C)
2(1
20 Calibration Room Sensor
-5 ° to +5°F(-2.5° to 2.5°C)
0(0
Table 6: Configuration Network Variables (Part 2 of 4)Parameter NCI Name and
SNVT, UNVT or SCPT Name
Range and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
15
uration
efault
epends n model use.
version
Thermostat’s Common CPs
21 Aux Contact Config
0 = Aux Contact function not used or used for reheat.Note: If Sequence is
set to Reheat through network or local, ignore this parameter (Sequence 1, 2, or 5).
The output directly follows the occupancy of the thermostat.1 = Aux N.O., Occupied = Contact Closed2 = Aux N.C. Occupied = Contact OpenThe output follows the secondary network occupancy command.3 = Not used.4 = Not used.5 = Aux On/Off control from a separate and dedicated network variable.
0
22 Reheat Time Base
0 = 15 minutes1 = 10 seconds
0
Note: This CP defines the thermostat’s common configparameters and their settings.
Thermostat’s Model Number
nciSccModelUNVT_model_number
Sub Name Valid Range D
01 Thermostat Model 41 = TEC2216-242 = TEC22216H-243 = Not used44 = TEC2226-245 = Not used46 = TEC2226H-247 = Not used48 = TEC2246-249 = Not used50 = TEC2246H-251 = Not used
Doin
02 Software Version 0 0
Note: This CP defines the model number and software of the thermostat.
Table 6: Configuration Network Variables (Part 3 of 4)Parameter NCI Name and
SNVT, UNVT or SCPT Name
Range and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
16
al
it
tor
ing
g Unit
ned
t being
rtbeat
t ally
)end
een
artbeat
t efore fault
by the
HVAC Unit Type Identifier
nciHvacTypeSNVT_hvac_type
Value Identifier Name
0 HVT_GENERIC - Not used Generic
1 HVT_FAN_COIL Fan Coil
2 HVT_VAV VAV Termin
3 HVT_HEAT_PUMP Heat Pump
4 HVT_ROOFTOP Rooftop Un
5 HVT_UNIT_VENT - Not used Unit Ventila
6 HVT_CHIL_CEIL - Not used Chilled Ceil
7 HVT_RADIATOR Radiator
8 HVT_AHU - Not used Air Handlin
9 HVT_SLF_CONT - Not used Self-ContaiUnit
Invalid HVT_NUL - Not used
Note: This CP helps you identify the type of equipmenmonitored.
Maximum Send Time
nciSendHrtBtSNVT_time_sec
Valid Range: 0 to 6,553.4 secondsDefault Null Value = 0.0 seconds (no automatic update)Note: Setting nciSendHrtBt to 0 disables the Send Hea
mechanism.Note: This CP defines the maximum period of time tha
expires before the specified NVOs are automaticupdated.
Minimum Send Time
nciMinOutTmSNVT_time_sec
Valid Range: 0 to 6,553.4 secondsDefault Null Value: 0.0 seconds (no minimum send timeNote: Setting nciRcvHrtBt to 0 disables the Minimum S
Time mechanism.Note: This CP defines the minimum period of time betw
automatic NVO transmissions.
Minimum Receive Time
nciRcvHrtBtSNVT_time_sec
Valid Range: 0 to 6,553.4 secondsDefault Null Value: 0.0 seconds (no failure detected)Note: Setting nciRcvHrtBt to 0 disables the Receive He
mechanism.Note: This CP is used to control the maximum time tha
elapses after the last update to a specified NVI bthe Space Comfort Controller starts to use its devalues.
Major Hardware or Software Revisions
nciMajVerSCPT_maj_ver
Valid Range: 0 to 255Note: This CP defines the major module hardware and
software revisions.
Minor Hardware or Software Revisions
nciMinVerSCPT_min_ver
Valid Range: 0 to 255Note: This CP defines the minor module hardware and
software revisions.
1. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint andOccupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjustedthermostat to maintain the minimum deadband between the two setpoints.
2. The BI object type status is available even if the configuration is set to None.
Table 6: Configuration Network Variables (Part 4 of 4)Parameter NCI Name and
SNVT, UNVT or SCPT Name
Range and Enumeration Definition
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
17
Commissioning the Thermostat Using a LONWORKS Network Configuration Tool
A thermostat must first be commissioned using a LONWORKS network configuration tool before it can be added to the LON Integration of the Network Automation Engine (NAE). This process implements the initial configuration and assigns the Neuron® ID of the thermostat.
Understanding LONWorks Network Configuration Tools’ Differences
LONWORKS network configuration tools use different numbering schemes in their Status/Command screens. Metasys system Connectivity to LONWORKS network (MCL) Tool begins its first entry with byte 0, while Lonwatcher begins with byte 1. Figure 1 shows the nciGenOpts Status/Command screen in MCL Tool on the left, with the equivalent Lonwatcher screen on the right.
Table 7: LONWORKS Network Configuration Tool Terminology DifferencesLONWORKS Network Configuration Tool
nvoSccStatus Screen nciGenOpts Screen
MCL Tool Bit 0 to Bit 63 Byte 0 to Byte 24
Lonwatcher Bit 1 to Bit 64 Byte 1 to Byte 25
LonMaker Not directly changeable Not directly changeable
Figure 1: MCL Tool and Lonwatcher Status/Command Screens
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
18
Changing the Thermostat’s Settings Using a LONWORKS Network Configuration Tool
Once a thermostat is configured and online, you can use a LONWORKS network configuration tool to change its settings. This means you do not have to go to the thermostat and manually make the changes.
To change most of the thermostat’s configuration properties:
1. Using a LONWORKS network configuration tool, open the thermostat’s nciGenOpts Status/Command screen.
2. From Table 8, find the desired configuration property and enter the corresponding value into its respective byte location in the nciGenOpts Status/Command screen.
Note: Some configuration properties require you to enter a range number in a specific byte location, followed by a corresponding value in the next byte location. You must enter both the range number and value before commanding the thermostat.
3. Enter additional configuration property changes if desired.
4. Command the thermostat. The new configuration changes are implemented.
Note: The Lockout settings must be made at the thermostat.
Service PinTo broadcast the thermostat’s Neuron ID over the LONWORKS network:
1. Simultaneously press and hold the Up Arrow and Down Arrow for 5 seconds. A small green light under the thermostat cover (on the left edge when facing the thermostat) flashes to indicate the thermostat’s Neuron ID is being broadcast on the LONWORKS network.
2. For manual entry, the Neuron ID is also on a label on the Echelon® chip under the thermostat cover.
Adding a Thermostat to the NAEOnce you commission a thermostat, you must add it to the NAE before its points can be mapped. To do this, select the LONWORKS Integration under the NAE (refresh the tree view if required to see a newly added LONWORKS Integration) and choose Field Device from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add a new thermostat online; however, this requires that the new thermostat is connected and ready to communicate. Refer to the LONWORKS Network Integration with NAE Technical Bulletin (LIT-1201668) for instructions on how to add a LONWORKS device.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
19
LONWORKS Thermostat Mapping
PreparationBefore mapping a TEC2245-2 Thermostat into an NAE:
1. Decide which point objects within the thermostat need to be mapped. Only map the point objects that need to be viewed on a regular basis, since excessive mapping lowers system performance. Suggested point objects for mapping include: Room Temp, System Mode, Fan Status, Occupied Heat Setpoint, Occupied Cool Setpoint, Unoccupied Heat Setpoint, and Unoccupied Cool Setpoint. In addition, alarm points may be mapped if they are used, and other point objects may be mapped if required. Use the Engineering view to examine infrequently used point objects.
2. Verify that a LONWORKS Integration is defined in the NAE. The commissioned thermostat is mapped as a LONWORKS device under a LONWORKS Integration. Refer to the LONWORKS® Network Integration with NAE Technical Bulletin (LIT-1201668) for instructions on how to define a LONWORKS network Integration.
At this point, you can map the thermostat and the required point objects inside the thermostat.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
20
Space Comfort Controller Object
Figure 2: TEC2245-2 Space Comfort Controller Object
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
21
ve
tt
r from
r from
r from
r from
Thermostat Command TableUse Table 8 to configure the thermostat with a LONWORKS network configuration tool. Table 8: Thermostat Command Table (Part 1 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)
Stat Menu Name
Description Byte and Range
0 (1) Not used. Not used.
1 (2) Not used. Not used.
2 (3) Not used. Not used.
3 (4) RA/DA Reverse acting output 0 = Direct Acting1 = Reverse Acting
4 (5) BI1 Configuration of Binary Input1. 0 = None1 = Rem NSB2 = Motion NO3 = Motion NC4 = Window
5 (6) BI2 Configuration of Binary Input2. 0 = None1 = Door Dry2 = RemOVR3 = Filter4 = Service
6 (7) UI3 Configuration of Universal Input3. 0 = None1 = COC/NH2 = COC/NC3 = COS4 = SS
7 (8) MenuScro Enables menu scrolling. 0 = Off = Scroll not acti1 = On = Scroll active
8 (9) AutoMode System Mode 0 = Off1= On
9 (10) C or F Displayed temperature scale. 0 = °C1 = °F
10 (11) Not used. Not used.
11 (12) SeqOpera Determines the sequence of operation. 0 = Cooling Only1 = Heating Only2 = Cooling with Rehea3 = Heating with Rehea
12 (13) Fan mode Fan On or Fan Auto 0 = Fan On1 = Fan Auto
13 (14) Heat max Occupied and Unoccupied maximum Heating setpoint range number.
Enter the range numbeTable 9.
14 (15) Heat max Occupied and Unoccupied maximum Heating setpoint value number.
Enter the value numbeTable 9.
15 (16) Cool min Occupied and Unoccupied minimum Cooling setpoint range number.
Enter the range numbeTable 10.
16 (17) Cool min Occupied and Unoccupied minimum Cooling setpoint value number.
Enter the value numbeTable 10.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
22
17 (18) Set type Temporary setpoint enable. 0 = Permanent1 = Temporary
18 (19) TOccTime Minimum occupancy time. 0 = 0 Hours1 = 1 Hours2 = 2 Hours3 = 3 Hours4 = 4 Hours5 = 5 Hours6 = 6 Hours7 = 7 Hours8 = 8 Hours9 = 9 Hours10 = 10 Hours11 = 11 Hours12 = 12 Hours13 = 13 Hours14 = 14 Hours15 = 15 Hours16 = 16 Hours17 = 17 Hours18 = 18 Hours19 = 19 Hours20 = 20 Hours21 = 21 Hours22 = 22 Hours23 = 23 Hours24 = 24 Hours
19 (20) Door Time Engages the Unoccupied mode if the door stays open minimally for the time specified.
1 = 1 minute2 = 2 minutes3 = 3 minutes4 = 4 minutes5 = 5 minutes6 = 6 minutes7 = 7 minutes8 =8 minutes9 = 9 minutes10 = 10 minutes
Table 8: Thermostat Command Table (Part 2 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)
Stat Menu Name
Description Byte and Range
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
23
r from
r from
Closed
t Open
from a
Commanding the Maximum Heating SetpointEnter the range byte (MCL Tool Byte Number 13, Lonwatcher Byte Number 14) and value byte (MCL Tool Byte Number 14, Lonwatcher Byte Number 15) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat. See Table 9.
Note: You must enter both values before commanding the thermostat.
20 (21) Deadband Sets the minimum deadband between the heating and cooling setpoints.
11 = 2°F17 = 3°F22 = 4°F28 = 5°F
21 (22) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.
Enter the range numbeTable 11.
22 (23) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.
Enter the value numbeTable 11.
23 (24) Aux cont Determines the auxiliary contactfunction and configuration.
0 = Used for reheat1 = Aux N.O., Occupied = Contact2 = Aux N.C. Occupied = Contac3 = Not used.4 = Not used.5 = Aux On/Off control separate and dedicatednetwork variable.
24 (25) Reheat Reheat time base 0 = 15 minutes1 = 10 seconds
Table 8: Thermostat Command Table (Part 3 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)
Stat Menu Name
Description Byte and Range
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
24
e 14
sis. l.
Table 9: Maximum Heat Setpoint Range Adjustment ValuesMax-HeatSet-point Setting
Range Byte 13 (14)
Value Byte 14 (15)
Max-Heat Set-point Setting
Range Byte 13 (14)
Value Byte 14 (15)
Max-Heat Set-point Setting
Range Byte 13 (14)
ValuByte(15)
40°F 1 188 57°F 5 108 74°F 9 29
40.5°F 1 216 57.5°F 5 136 74.5°F 9 57
41°F 1 244 58°F 5 164 75°F 9 84
41.5°F 2 15 58.5°F 5 192 75.5°F 9 112
42°F 2 43 59°F 5 220 76°F 9 140
42.5°F 2 71 59.5°F 5 247 76.5°F 9 168
43°F 2 99 60°F 6 19 77°F 9 196
43.5°F 2 126 60.5°F 6 47 77.5°F 9 223
44°F 2 154 61°F 6 75 78°F 9 251
44.5°F 2 182 61.5°F 6 102 78.5°F 10 23
45°F 2 210 62°F 6 130 79°F 10 51
45.5°F 2 238 62.5°F 6 158 79.5°F 10 78
46°F 3 9 63°F 6 186 80°F 10 106
46.5°F 3 37 63.5°F 6 214 80.5°F 10 134
47°F 3 65 64°F 6 241 81°F 10 162
47.5°F 3 93 64.5°F 7 13 81.5°F 10 190
48°F 3 120 65°F 7 41 82°F 10 217
48.5°F 3 148 65.5°F 7 69 82.5°F 10 245
49°F 3 176 66°F 7 96 83°F 11 17
49.5°F 3 204 66.5°F 7 124 83.5°F 11 45
50°F 3 232 67°F 7 152 84°F 11 72
50.5°F 4 3 67.5°F 7 180 84.5°F 11 100
51°F 4 31 68°F 7 208 85°F 11 128
51.5°F 4 59 68.5°F 7 235 85.5°F 11 156
52°F 4 87 69°F 8 7 86°F 11 184
52.5°F 4 114 69.5°F 8 35 86.5°F 11 211
53°F 4 142 70°F 8 63 87°F 11 239
53.5°F 4 170 70.5°F 8 90 87.5°F 12 11
54°F 4 198 71°F 8 118 88°F 12 39
54.5°F 4 226 71.5°F 8 146 88.5°F 12 66
55°F 4 253 72°F 8 174 89°F 12 94
55.5°F 5 25 72.5°F 8 202 89.5°F 12 122
56°F 5 53 73°F 8 229 90°F 12 150
56.5°F 5 81 73.5°F 9 1
Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parentheSee Table 7 for more information on Bit/Byte use in each LONWORKS network configuration too
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
25
ue e 16 )
sis. l.
Commanding the Minimum Cooling SetpointUsing a LONWORKS network configuration tool, enter the range byte (MCL Tool Byte Number 15, Lonwatcher Byte Number 16) and value byte (MCL Tool Byte Number 16, Lonwatcher Byte Number 17) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat.
You must enter both values before commanding the thermostat. Table 10: Minimum Cooling Setpoint Range Adjustment ValuesMinCool Set-point Setting
Range Byte 15 (16)
Value Byte 16 (17)
Min-Cool Set-point Setting
Range Byte 15 (16)
Value Byte 16 (17)
MinCool Set-point Setting
Range Byte 15 (16)
ValByt(17
54°F 4 198 69.5°F 8 35 85°F 11 128
54.5°F 4 226 70°F 8 63 85.5°F 11 156
55°F 4 253 70.5°F 8 90 86°F 11 184
55.5°F 5 25 71°F 8 118 86.5°F 11 211
56°F 5 53 71.5°F 8 146 87°F 11 239
56.5°F 5 81 72°F 8 174 87.5°F 12 11
57°F 5 108 72.5°F 8 202 88°F 12 39
57.5°F 5 136 73°F 8 229 88.5°F 12 66
58°F 5 164 73.5°F 9 1 89°F 12 94
58.5°F 5 192 74°F 9 29 89.5°F 12 122
59°F 5 220 74.5°F 9 57 90°F 12 150
59.5°F 5 247 75°F 9 84 90.5°F 12 178
60°F 6 19 75.5°F 9 112 91°F 12 205
60.5°F 6 47 76°F 9 140 91.5°F 12 233
61°F 6 75 76.5°F 9 168 92°F 13 5
61.5°F 6 102 77°F 9 196 92.5°F 13 33
62°F 6 130 77.5°F 9 223 93°F 13 60
62.5°F 6 158 78°F 9 251 93.5°F 13 88
63°F 6 186 78.5°F 10 23 94°F 13 116
63.5°F 6 214 79°F 10 51 94.5°F 13 144
64°F 6 241 79.5°F 10 78 95°F 13 172
64.5°F 7 13 80°F 10 106 95.5°F 13 199
65°F 7 41 80.5°F 10 134 96°F 13 227
65.5°F 7 69 81°F 10 162 96.5°F 13 255
66°F 7 96 81.5°F 10 190 97°F 14 27
66.5°F 7 124 82°F 10 217 97.5°F 14 54
67°F 7 152 82.5°F 10 245 98°F 14 82
67.5°F 7 180 83°F 11 17 97.5°F 14 110
68°F 7 208 83.5°F 11 45 99°F 14 138
68.5°F 7 235 84°F 11 72 99.5°F 14 166
69°F 8 7 84.5°F 11 100 100°F 14 193
Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parentheSee Table 7 for more information on Bit/Byte use in each LONWORKS network configuration too
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
26
red. Use a ORKS network.
a LONWORKS
Commanding the Cal RS SettingsUsing a LONWORKS network configuration tool, enter the Byte 21 (22) range number and Byte 22 (23) value number (Table 11) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat.
Note: You must enter both values before commanding the thermostat.
Status Light-Emitting Diode (LED)The status LED shows the operational status of the thermostat. The Status LED is a small green light under the thermostat cover (under the LONWORKS daughter board on the left edge when facing the thermostat).
Table 11: Cal RS Command SettingsCal RS Setting Byte 21 (22) Range Byte 22 (23) Value5°F 1 21
4°F 0 222
3°F 0 166
2°F 0 111
1°F 0 55
0°F 0 0
-1°F 255 201
-2°F 255 145
-3°F 255 90
-4°F 255 34
-5°F 255 235
Note: Lonwatcher Range byte location numbers and Value byte location numbers are shown in parenthesis. See Table 7 for more information on byte use in each LONWORKS network configuration tool.
Table 12: Status LED ExplanationStatus LED Condition ExplanationContinuously On The thermostat does not have an application loaded in its memory.
Flashing at a 0.5 Hz Rate The thermostat has an application loaded in its memory but is unconfiguLONWORKS network management tool to bind the thermostat to a LONW
Continuously Off The thermostat has an application loaded in its memory and is bound tonetwork.
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
27
t be the same e before the
table.
to respond.
table.
table.
, Class 2 or
r UI3
WG (1.0 mm
a Repeater;
Troubleshooting
Technical Specifications
Table 13: Troubleshooting DetailsSymptom Probable CausesMultiple Symptoms
Excessive bus errors may be occurring.
A device may have been added or changed with a duplicate Neuron ID (may noaddress as some devices having problems, and may have happened sometimproblem was noticed).
Wiring errors or wire problems may exist.
A download may be in progress.
There may be a fault at a device.
A repeater may be needed or may be configured incorrectly.
Poor Performance See the probable causes listed in the Multiple Symptoms section earlier in this
Excessive bus traffic may exist (bus overload).
There may be too many devices on the network.
There may be unaccounted devices on the network (not mapped to the NAE).
There may be unusually slow devices on the network or devices that are slow
Thermostat Goes Offline
See the probable causes listed in the Multiple Symptoms section earlier in this
A power failure or other failure may have occurred at the thermostat.
Communication may have been disabled at the thermostat.
Thermostat Will Not Come Online.
See the probable causes listed in the Multiple Symptoms section earlier in this
A thermostat may be connected to the wrong bus.
TEC2245-2 LONWORKS Network Thermostat with Single Proportional Output and One-Speed Fan Control (Part 1 of 2)Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal
Safety Extra-Low Voltage (SELV)
Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum)
Fan Relay Output Rating 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Auxiliary Output Rating
Triac Output 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, o
Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 ADiameter) Recommended
LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with6,250 ft (1,905 m) Maximum (Bus Topology)
Thermostat Measurement Range
-40.0°F/-40.0°C to 122.0°F/50.0°C
Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Resolution ±0.2F°/±0.1C°
Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Control Range
Heating 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments
Cooling 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient Conditions
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
28
g Equipment
beyond these from misapplication or
FCC Rules. These mmercial
ccordance with the area is likely to cause
.
Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating EquipmentFCC Compliant to CFR 47, Part 15, Subpart B, Class ALONMARK® Certification 3.4 (pending)
Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and RegulatinIndustry Canada, ICES-003
Europe CE Mark, EMC Directive 89/336/EEC
Australia and New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting misuse of its products.United States Emissions Compliance:This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of thelimits are designed to provide reasonable protection against harmful interference when this equipment is operated in a coenvironment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in ainstruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residentialharmful interference, in which case the user will be required to correct the interference at his/her own expense.Canadian Emissions Compliance:This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada
TEC2245-2 LONWORKS Network Thermostat with Single Proportional Output and One-Speed Fan Control (Part 2 of 2)
Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.
© 2006 Johnson Controls, Inc.
Controls Group507 E. Michigan StreetMilwaukee, WI 53202
Published in U.S.A. www.johnsoncontrols.com
TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin
29