tec2245-2 lonworks networked thermostats with single

29
1 TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin Network Variables (NVs) and Configuration Properties (CPs) List . . . . . . . . . . . . . . 3 Network Variable Inputs (NVIs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables . . . . . . . . . . . . . 10 NVI RemLockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Network Variable Outputs (NVOs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Configuration Network Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Commissioning the Thermostat Using a LONWORKS Network Configuration Tool . . . 18 Understanding LONWorks Network Configuration Tools’ Differences . . . . . . . . . . . . . 18 Changing the Thermostat’s Settings Using a LONWORKS Network Configuration Tool19 Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Adding a Thermostat to the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 LONWORKS Thermostat Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Space Comfort Controller Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Thermostat Command Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Commanding the Maximum Heating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Commanding the Minimum Cooling Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Commanding the Cal RS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Status Light-Emitting Diode (LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 TEC2245-2 LonWorks Network Thermostat with Single Proportional Output and One-Speed Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin xxxx-xxxxx Code No. LIT-12011174 Issued May 25, 2006

Upload: others

Post on 10-Jan-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TEC2245-2 LonWorks Networked Thermostats with Single

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan ControlTechnical Bulletinxxxx-xxxxx

Code No. LIT-12011174Issued May 25, 2006

Network Variables (NVs) and Configuration Properties (CPs) List. . . . . . . . . . . . . . 3

Network Variable Inputs (NVIs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables . . . . . . . . . . . . . 10

NVI RemLockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Network Variable Outputs (NVOs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Configuration Network Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Commissioning the Thermostat Using a LONWORKS Network Configuration Tool . . . 18

Understanding LONWorks Network Configuration Tools’ Differences . . . . . . . . . . . . . 18

Changing the Thermostat’s Settings Using a LONWORKS Network Configuration Tool19

Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Adding a Thermostat to the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

LONWORKS Thermostat Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Space Comfort Controller Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Thermostat Command Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Commanding the Maximum Heating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Commanding the Minimum Cooling Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Commanding the Cal RS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Status Light-Emitting Diode (LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

TEC2245-2 LonWorks Network Thermostat with Single Proportional Output and One-Speed Fan Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

1TEC2245-2 LONWORKS® Networked Thermostats with Single Output andOne-Speed Fan Control Technical Bulletin

Page 2: TEC2245-2 LonWorks Networked Thermostats with Single

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

2

Page 3: TEC2245-2 LonWorks Networked Thermostats with Single

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

Network Variables (NVs) and Configuration Properties (CPs) List

Table 1 shows the NVs and CPs for the TEC2245-2 Series thermostat. Each Network Variable Input (NVI), Network Variable Output (NVO), and Network Configuration Input (NCI) has a reference number, and some objects have a subcategory number. The Sub column lists the thermostat’s Enumeration (Enum) options for the NV or CP. The Byte column shows the actual byte number used for commanding the NV nvoSccStatus and nciGenOpts NVs.

Note: When you use a LONWORKS® network configuration tool to view the Status/Command screen:

• nvoSccStatus is a 64 bit (bit 0 to bit 63) field.

• nciGenOpts is a 25 bit (bit 0 to bit 24) field. Table 1: NV and CPs By Model (Part 1 of 3)No Sub Bit NV or CP Name Model

TEC2245-20 nviSpaceTemp X

1 nviOutdoorTemp X

2 nviSetpoint X

3 nviSpaceRH N/A

4 nviFanSpeedCmd X

5 nviAuxHeatEnable X

6 nviOccCmd X

7 nviApplicMode X

8 nviHeatCool X

9 nviRemLockout X

10 nviDhumiLCK N/A

11 nviAuxOut X

12 nvoSpaceTemp X

13 nvoDischAirTemp X

14 nvoSpaceRH N/A

15 nvoEffectOccup X

16 nvoUnitStatus X

1 mode x

2 heat_output_primary x

3 heat_output_secondary x

4 cool_output x

5 econ_output x

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

3

Page 4: TEC2245-2 LonWorks Networked Thermostats with Single

6 fan_output x

7 in_alarm x

17 nvoSccStatus X

1 0 State Terminal BO5 x

2 1 Fan High x

3 2 UI 3 Status x

4 3 BI 2 Status x

5 4 BI 1 Status x

6 5 Service Alarm x

7 6 Filter Alarm x

8 7 Window Opened x

18 nvoTerminalLoad X

19 nciSetPts X

1 occupied_cool x

2 standby_cool N/A

3 unoccupied_cool x

4 occupied_heat x

5 standby_heat N/A

6 unoccupied_heat x

20 nciRHmodel N/A

1 RHdisplay N/A

2 RHsetpoint N/A

3 DehumHyst N/A

4 DehumCool N/A

5 RHcalib N/A

21 nciGenOpts X

1 0 Control Type N/A

2 1 Drive Time N/A

3 2 Cycles Per Hour N/A

4 3 Reverse Acting Output x

5 4 BI 1 Configuration x

6 5 BI 2 Configuration x

7 6 UI 3 Configuration x

8 7 MenuScroll x

9 8 Auto Mode x

10 9 Temperature Scale x

11 10 Number of Pipe (System) N/A

12 11 Sequence of Operation x

13 12 Fan Mode x

14 13 Maximum Heating Setpoint (Range) x

15 14 Maximum Heating Setpoint (Value) x

Table 1: NV and CPs By Model (Part 2 of 3)No Sub Bit NV or CP Name Model

TEC2245-2

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

4

Page 5: TEC2245-2 LonWorks Networked Thermostats with Single

16 15 Minimum Cooling Setpoint (Range) x

17 16 Minimum Cooling Setpoint (Value) x

18 17 Setpoint Type x

19 18 Temporary Occupancy Time x

20 19 Door Time x

21 20 Deadband x

22 21 Calibration Room Sensor (Range) x

23 22 Calibration Room Sensor (Value) x

24 23 Auxiliary Contact BO 5 Configuration x

25 24 Reheat Output BO 5 Time Base x

22 nciSccModel X

1 0 Thermostat Model Number x

2 1 Software Version x

23 nciHvacType X

24 nciSndHrtBt X

25 nciMinOutTm X

26 nciRcvHrtBt X

27 nciMajVer X

28 nciMinVer X

Table 1: NV and CPs By Model (Part 3 of 3)No Sub Bit NV or CP Name Model

TEC2245-2

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

5

Page 6: TEC2245-2 LonWorks Networked Thermostats with Single

FF) represents

upied and standby or written to, the longer used.

FF) represents

on to the thermostat . Once bound, the

) represents invalid

cupied mode to be are not changed.

d Fan Speed

usedusedt used Not used

edt used

usedused)used

h to the node or to ed controlled by the th the FanMenu bit

Network Variable Inputs (NVIs) Table 2: NVIs (Part 1 of 4)Parameter NVI Name and

SNVT TypeRange and Enumeration Definition

Room Temperature

nviSpaceTempSNVT_temp_p

Valid Range: 14°F/ -10.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7Finvalid data.Note: This NVI allows the temperature setpoint for the occ

mode to be changed via the network. When bound internal temperature reading (internal sensor) is no

Outdoor Air Temperature

nviOutdoorTempSNVT_temp_p

Valid Range: -40°F/-40.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7Finvalid data.Note: This NVI provides outdoor air temperature informati

from a bound network outside air temperature valuethermostat automatically displays the value.

Occupied Cooling and Heating Setpoints1

nviSetpointSNVT_temp_p

Valid Range: Occupied Cooling 54°F/12°C to 100°F/37.5°CValid Range: Occupied Heating 40°F/4.5°C to 90°F/32.0°CStandby Cool Setpoint (Not used)Standby Heat Setpoint (Not used)Default Null (release) Value: 621.8°F/327.67°C or (0x7FFFdata.Note: This NVI allows the temperature setpoints for the oc

changed via the network. The unoccupied setpoints

Room Humidity nviSpaceRHSNVT_lev_percent

Not used.

Fan Mode nviFanSpeedCmdSNVT_switch

Fan Menu Value

State Value Equivalent Percent

Requeste

0 0111110xFF

N/A01-6667-133134-200201-255N/A

N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A

Off - Not Off - Not Low - NoMedium -High3 - Not usAuto - No

4 01110xFF

N/A01-200201-255N/A

N/A0%0.5 to 100%100%N/A

Off - Not Off - Not On (HighOn - Not Auto

Note: This NVI is used to bind an external fan speed switcallow any supervisory device to override the fan spenode’s control algorithm. It is used in conjunction wiin nciGenOpts.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

6

Page 7: TEC2245-2 LonWorks Networked Thermostats with Single

Heat Operation

(Not used)

nabled (Not used)

Invalid)

e. It is used in le 3 for information eqOpera Variables.

nto different ry node to manually led occupancy.

ith any supervisory ater). It is used as with nviApplicMode

Sequence of Operations and Auxiliary Heat

nviAuxHeatEnableSNVT_switch

State Value EquivalentPercentage

Auxiliary

0 N/A N/A Disabled

1 0 0% Disabled

1 1 to 199

0.5 to 99.5% Partially E

1 200 to 255

100% Enabled

0xFF N/A N/A Enabled (

Note: This NVI enables or disables the auxiliary heat stagconjunction with nviHeatCool and SeqOper. See Tabon using the nviHeatCool, nviAuxHeatEnable, and S

Occupancy nviOccCmdSNVT_occupancy

0 = OC_OCCUPIED1 = OC_UNOCCUPIED2 = OC_BYPASS (Not used)3 = OC_STANDBY (Not used)0XFF = OC_NUL (Release to internal schedule)Note: This NVI commands the Space Comfort Controller i

occupancy modes. It is typically sent by a supervisocontrol occupancy modes, or to override the scheduDefault Null Value: OC_NUL = 0xFF

System Mode nviApplicModeSNVT_hvac_mode

0 = HVAC_AUTO (Default)1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not used)3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not used)5 = HVAC_PRE_COOL (Not used)6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not used)9 = HVAC_FAN_ONLY (Not used)10 = HVAC_FREE_COOL (Not used)11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not used)13 = HVAC_ECONOMY (Not used)14 = HVAC_DEHUMID (Not used)15 = HVAC_CALIBRATE (Not used)16 = HVAC_EMERG_COOL (Not used)17 = HVAC_EMERG_STEAM (Not used)0XFF = HVAC_NUL (Not used)Note: This NVI coordinates the Space Comfort Controller w

controller providing the supply energy (hot or cold wheat/cool changeover. It is also used in conjunction and SeqOper.

Table 2: NVIs (Part 2 of 4)Parameter NVI Name and

SNVT TypeRange and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

7

Page 8: TEC2245-2 LonWorks Networked Thermostats with Single

ith any supervisory ater). It is used as with nviApplicMode

with any node that it. It is overridden by TO. If etermines the

uxHeatEnable, and

rmostat.

y Output (BO5), alue of 5 for this

d Fan Speed

Sequence of Operation

nviHeatCoolSNVT_hvac_mode

0 = HVAC_AUTO (Default)1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not used)3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not used)5 = HVAC_PRE_COOL (Not used)6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not used)9 = HVAC_FAN_ONLY (Not used)10 = HVAC_FREE_COOL (Not used)11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not used)13 = HVAC_ECONOMY (Not used)14 = HVAC_DEHUMID (Not used)15 = HVAC_CALIBRATE (Not used)16 = HVAC_EMERG_COOL (Not used)17 = HVAC_EMERG_STEAM (Not used)0XFF = HVAC_NUL (Not used)Note: This NVI coordinates the Space Comfort Controller w

controller providing the supply energy (hot or cold wheat/cool changeover. It is also used in conjunction and SeqOper.

Note: This NVI coordinates the Space Comfort Controller needs to control the heat/cool changeover of the unnviApplicMode, unless nviApplicMode is HVAC_AUnviApplicMode is HVAC_AUTO, then nviHeatCool deffective mode of the unit.

See Table 3 for information on using the nviHeatCool, nviASeqOpera variables.

Lockout nviRemLockoutSNVT_count

See Table 4 for Lockout information.Note: This NVI enables or disables user access to the the

DehumiLCk nviDhumiLCK Not used.

Aux Contact nviAuxOutSNVT_switch

0 = Auxiliary contact Off1 = Auxiliary contact On5 = Follow secondary network commandNote: If this NVI is used to remotely command the Auxiliar

then the Auxiliary Output must be configured to a vfunction to operate.

Room Humidity nviSpaceRHSNVT_lev_percent

Not used.

Fan Mode nviFanSpeedCmdSNVT_switch

Fan Menu Value

State Value Equivalent Percent

Requeste

Table 2: NVIs (Part 3 of 4)Parameter NVI Name and

SNVT TypeRange and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

8

Page 9: TEC2245-2 LonWorks Networked Thermostats with Single

usedused

edt used

usedused

edt used

usedused

ed

usedused

ed

usedused)used

h to the node or to ed controlled by the h the FanMenu byte

Occupied Cool stat to maintain the

0 0111110xFF

N/A01-6667-133134-200201-255N/A

N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A

Off - Not Off - Not LowMediumHigh3 - Not usAuto - No

1 011110xFF

N/A00-100101-200201-255N/A

N/A0%0.5 to 50%50.5 to 100%100%N/A

Off - Not Off - Not LowHigh2 - Not usAuto - No

2 0111110xFF

N/A01-6667-133134-200201-255N/A

N/A0%0.5 to 33%33.5 to 66.5%67 to 100%100%N/A

Off - Not Off - Not LowMediumHigh3 - Not usAuto

3 011110xFF

N/A00-100101-200201-255N/A

N/A0%0.5 to 50%50.5 to 100%100%N/A

Off - Not Off - Not LowHigh2 - Not usAuto

4 01110xFF

N/A01-200201-255N/A

N/A0%0.5 to 100%100%N/A

Off - Not Off - Not On (HighOn - Not Auto

Note: This NVI is used to bind an external fan speed switcallow any supervisory device to override the fan spenode’s control algorithm. It is used in conjunction witin nciGenOpts.

1. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint andSetpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermominimum deadband between the two setpoints.

Table 2: NVIs (Part 4 of 4)Parameter NVI Name and

SNVT TypeRange and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

9

Page 10: TEC2245-2 LonWorks Networked Thermostats with Single

Pipes

Pipes

Reheat

Pipes

Pipes

Reheat

Reheat Reheat

cupiedide

cess

ess

ed

ed

cess

ess

.

Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables

NVI RemLockout

Table 3: nviHeatCool, nviAuxHeatEnable, and SeqOpera VariablesCurrent nviHeatCool

nviAuxHeatEnable SeqOpera If nviHeatCool Changed To:

SeqOpera

2 and 4 Pipe Application

3 = HVAC_COOL Disabled 0 = Cooling only 0 = HVAC_AUTO1 = HVAC_HEAT

4 = Cool/Heat 41 = Heating only

3 = HVAC_COOL Enabled 2 = Cooling and Reheat

0 = HVAC_AUTO

1 = HVAC_HEAT

5 = Cool/Heat 4and Reheat3 = Heating and

1 = HVAC_HEAT Disabled 1 = Heating only 0 = HVAC_AUTO3 = HVAC_COOL

4 = Cool/Heat 40 = Cooling only

1 = HVAC_HEAT Enabled 3 = Heating and Reheat

0 = HVAC_AUTO

3 = HVAC_COOL

5 = Cool/Heat 4and Reheat2 = Cooling and

4 Pipe Application

0 = HVAC_AUTO Disabled 4 = Cooling only 0 = HVAC_HEAT3 = HVAC_COOL

1 = Heating only0 = Cooling only

0 = HVAC_AUTO Enabled 5 = Cooling and Reheat

0 = HVAC_HEAT3 = HVAC_COOL

3 = Heating and2 = Cooling and

Table 4: NVI RemLockoutParameter NV and SNVT

TypesLockout Menu Value

Occupied Temperature Setpoints

System Mode Settings

Fan Mode Settings

UnocOverr

Lockout nviRemLockoutSNVT_count

0 Yes access Yes access Yes access Yes ac

1 Yes access Yes access Yes access No acc

2 Not used No access No access Not us

3 Not used No access No access Not us

4 No access No access No access Yes ac

5 No access No access No access No acc

Note: This NVI enables or disables user access to the thermostat

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

10

Page 11: TEC2245-2 LonWorks Networked Thermostats with Single

) in the

ensor t echoes r that of

)

ves the to (SS)

unit. ontroller ordinate itiated is only enOpts), or an

l input. e of the

Network Variable Outputs (NVOs)Table 5: NVOs (Part 1 of 3)Parameter NVO Name and

SNVT TypeRange and Enumeration Definition

Room Temperature

nvoSpaceTempSNVT_temp_p

Valid Range: 14°F/-10.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7FFFrepresents invalid data. This value is sent as an invalid valueevent of a sensor failure.Note: This NVO monitors the effective space temperature s

that the Space Comfort Controller is using for control. Ithe internal value on the device temperature sensor onviSpaceTemp if it is bound, or a value is written to it.

Supply Temperature

nvoDischAirTempSNVT_temp_p

Valid Range: -40°F/-40.0°C to 122°F/50.0°CDefault Null (release) Value: 621.8°F/327.67.0°C or (0x7FFFrepresents invalid data.Note: This NVO monitors the temperature of the air that lea

Space Comfort Controller. UI3 needs to be configuredsupply air sensor monitoring.

Room Humidity

nviSpaceRHSNVT_lev_percent

Not used.

Occupancy nvoEffectOccupSNVT_occupancy

0 = OC_OCCUPIED1 = OC_UNOCCUPIED2 = OC_BYPASS1

3 = OC_STANDBY (Not used)4 = OC_NULNote: This NVO indicates the actual occupancy mode of the

This information is typically reported to a supervisory cor provided to another Space Comfort Controller to cothe operation of multiple units. OC_BYPASS can be inby either nviOccCmd or a local input. NvoEffectOccupin OC_BYPASS for the duration of the ToccTime (nciGuntil reinitiated by either a transition of the local input update to nviOccCmd.

1OC_BYPASS can be initiated by either nviOccCmd or a locaNvoEffectOccup is only in OC_BYPASS for the duration of thToccTime (nciGenOpts), until reinitiated by either a transitionlocal input or an update to nviOccCmd.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

11

Page 12: TEC2245-2 LonWorks Networked Thermostats with Single

used)

used))

sed))sed)

d)d))

ed) used)ot used)

ce and s the city of and an present

alid)

alid)

alid)

msn

rm ot used.

ntroller f heating present

Unit Status nvoUnitStatusSNVT_hvac_status

Sub Name Valid Value

01 Mode 1 = HVAC_HEAT2 = HVAC_MRNG_WRMUP (Not3 = HVAC_COOL4 = HVAC_NIGHT_PURGE (Not 5 = HVAC_PRE_COOL (Not used6 = HVAC_OFF7 = HVAC_TEST (Not used)8 = HVAC_EMERG_HEAT (Not u9 = HVAC_FAN_ONLY (Not used10 = HVAC_FREE_COOL (Not u11 = HVAC_ICE (Not used)12 = HVAC_MAX_HEAT (Not use13 = HVAC_ECONOMY (Not use14 = HVAC_DEHUMID (Not used15 = HVAC_CALIBRATE (Not us16 = HVAC_EMERG_COOL (Not17 = HVAC_EMERG_STEAM (N18 = HVAC_NUL (Not used)Note: This NVO reports the Spa

Comfort Controller inputs’outputs’ status. It combineoperating mode, the capaheating and cooling used,indication if any alarms arein the object.

02 heat_output_primary 0-100%0xFFF (inv

03 heat_output_secondary Not used.

04 cool_output 0-100%0xFFF (inv

05 econ_output Not used.

06 fan_output 0-100%0xFFF (inv

07 in_alarm 0 = No alar1 = Alarm O0x7FF (Aladisabled) N

Note: This NVO is available to report the Space Comfort Costatus. It combines the operating mode, the capacity oand cooling used, and an indication if any alarms are in the object.

Table 5: NVOs (Part 2 of 3)Parameter NVO Name and

SNVT TypeRange and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

12

Page 13: TEC2245-2 LonWorks Networked Thermostats with Single

ue

ivated

ivated

m

m

m

ntroller

and of s in use ues mfort

Thermostat I/O Status

nvoSccStatusUNVT_fc_thermo

Sub Name Valid Value Default Val

01 State Terminal BO2

0 = Off1 = On

0 = Off

02 State Terminal BO1

0 = Off1 = On

0 = Off

03 State Terminal BO4

0 = Off1 = On

0 = Off

04 State Terminal BO3

0 = Off1 = On

0 = Off

05 State Terminal BO5

0 = Off1 = On

0 = Off

06 Fan Low Not used. N/A

07 Fan Med Not used. N/A

08 Fan High Not used. N/A

09 UI 3 Status -40×F/-40.0×C to122×F/50.0×C40×F = Open122×F = Close

N/A

10 BI 2 Status 0 = Activated1 = Not activated

1 = Not act

11 BI 1 Status 0 = Activated1 = Not activated

1 = Not act

12 Service Alarm 0 = No alarm1 = Alarm On

0 = No alar

13 Filter Alarm 0 = No alarm1 = Alarm On

0 = No alar

14 Window Opened 0 = No alarm1 = Alarm On

0 = No alar

15 Dehumidification Active

Not used. N/A

Note: This NVO reports the status of the Space Comfort Coinputs and outputs.

Heating/Cooling Demand

nvoTerminalLoadSNVT_lev_percent

Valid Range: -100 to +100%Note: This NVO indicates the current heat/cool energy dem

the unit. Positive values indicate that cooling energy iby the space comfort controller, whereas negative valindicate that heating energy is in use by the space cocontroller.

Table 5: NVOs (Part 3 of 3)Parameter NVO Name and

SNVT TypeRange and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

13

Page 14: TEC2245-2 LonWorks Networked Thermostats with Single

rious

by the ode.

efault

5°F/4°C

ot sed.

0°F/6.5°C

2°F/2°C

ot sed.

2°F/6.5°C

efault

/A

/A

/A

Configuration Network VariablesTable 6: Configuration Network Variables (Part 1 of 4)Parameter NCI Name and

SNVT, UNVT or SCPT Name

Range and Enumeration Definition

Temperature Setpoints1

nciSetPtsSNVT_temp_setpt

This CP defines the space temperature setpoints for vaheat, cool and occupancy modes.The stand-by setpoints can be modified but are not usedcontroller, as it does not support Stand-By occupancy m

Sub Mode Min. Max. D

01 occupied_cool 54°F/12°C 100°F/37.5°C

72

02 standby_cool Not used. Not used.

Nu

03 unoccupied_cool 54°F/12°C 100°F/37.5°C

82

04 occupied_heat 40°F/4.5°C 90°F/32°C

72

05 standby_heat Not used. Not used.

Nu

06 unoccupied_heat 40°F/4.5°C 90°F/32°C

61

RH Options nciRHmodelUNVT_gen_opts

Not used

Thermostat’s Common CPs

nciGenOptsUNVT_fc_gen_opts

Sub Name Valid Range D

01 Not used. Not used. N

02 Not used. Not used. N

03 Not used. Not used. N

04 Reverse Acting Output

0 = Direct Acting (DA)1 = Reverse Acting (RA)

0

05 BI12 0 = None1 = Rem NSB2 = Motion NO3 = Motion NC4 = Window

0

06 BI22 0 = None1 = Door Dry2 = Override3 = Filter4 = Service

0

07 UI32 0 = None1 = COC/NH2 = COC/NC3 = COS4 = SS

0

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

14

Page 15: TEC2245-2 LonWorks Networked Thermostats with Single

/A

= eating nly

0°F2°C)

4°F2°C)

hours

inutes

°F °C)

°F°C)

Thermostat’s Common CPs

08 Menu Scroll 0 = No scroll1 = Scroll active

1

09 Not used. Not used. 0

10 Temperature Scale

0 = °C1 = °F

°F

11 Not used. Not used. N

12 Sequence of Operation

0 = Cooling Only1 = Heating Only2 = Cooling & Reheat3 = Heating & Reheat

1HO

13 Fan Menu 0 = On4 = Auto

0

14 Heat Maximum Setpoint

40 to 90°F(4.5 to 32° C)

9(3

15 Cool Minimum Setpoint

54 to 100°F(12 to 37.5° C)

5(1

16 Setpoint Type 0 = Permanent1 = Temporary

0

17 Temporary Occ Time

0, 1, 2, 3, up to 24 hours

2

18 Door Time 1, 2, 3, up to 10 minutes

2m

19 Deadband 2, 3, 4, or 5°F(1.0 to 2.5°C)

2(1

20 Calibration Room Sensor

-5 ° to +5°F(-2.5° to 2.5°C)

0(0

Table 6: Configuration Network Variables (Part 2 of 4)Parameter NCI Name and

SNVT, UNVT or SCPT Name

Range and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

15

Page 16: TEC2245-2 LonWorks Networked Thermostats with Single

uration

efault

epends n model use.

version

Thermostat’s Common CPs

21 Aux Contact Config

0 = Aux Contact function not used or used for reheat.Note: If Sequence is

set to Reheat through network or local, ignore this parameter (Sequence 1, 2, or 5).

The output directly follows the occupancy of the thermostat.1 = Aux N.O., Occupied = Contact Closed2 = Aux N.C. Occupied = Contact OpenThe output follows the secondary network occupancy command.3 = Not used.4 = Not used.5 = Aux On/Off control from a separate and dedicated network variable.

0

22 Reheat Time Base

0 = 15 minutes1 = 10 seconds

0

Note: This CP defines the thermostat’s common configparameters and their settings.

Thermostat’s Model Number

nciSccModelUNVT_model_number

Sub Name Valid Range D

01 Thermostat Model 41 = TEC2216-242 = TEC22216H-243 = Not used44 = TEC2226-245 = Not used46 = TEC2226H-247 = Not used48 = TEC2246-249 = Not used50 = TEC2246H-251 = Not used

Doin

02 Software Version 0 0

Note: This CP defines the model number and software of the thermostat.

Table 6: Configuration Network Variables (Part 3 of 4)Parameter NCI Name and

SNVT, UNVT or SCPT Name

Range and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

16

Page 17: TEC2245-2 LonWorks Networked Thermostats with Single

al

it

tor

ing

g Unit

ned

t being

rtbeat

t ally

)end

een

artbeat

t efore fault

by the

HVAC Unit Type Identifier

nciHvacTypeSNVT_hvac_type

Value Identifier Name

0 HVT_GENERIC - Not used Generic

1 HVT_FAN_COIL Fan Coil

2 HVT_VAV VAV Termin

3 HVT_HEAT_PUMP Heat Pump

4 HVT_ROOFTOP Rooftop Un

5 HVT_UNIT_VENT - Not used Unit Ventila

6 HVT_CHIL_CEIL - Not used Chilled Ceil

7 HVT_RADIATOR Radiator

8 HVT_AHU - Not used Air Handlin

9 HVT_SLF_CONT - Not used Self-ContaiUnit

Invalid HVT_NUL - Not used

Note: This CP helps you identify the type of equipmenmonitored.

Maximum Send Time

nciSendHrtBtSNVT_time_sec

Valid Range: 0 to 6,553.4 secondsDefault Null Value = 0.0 seconds (no automatic update)Note: Setting nciSendHrtBt to 0 disables the Send Hea

mechanism.Note: This CP defines the maximum period of time tha

expires before the specified NVOs are automaticupdated.

Minimum Send Time

nciMinOutTmSNVT_time_sec

Valid Range: 0 to 6,553.4 secondsDefault Null Value: 0.0 seconds (no minimum send timeNote: Setting nciRcvHrtBt to 0 disables the Minimum S

Time mechanism.Note: This CP defines the minimum period of time betw

automatic NVO transmissions.

Minimum Receive Time

nciRcvHrtBtSNVT_time_sec

Valid Range: 0 to 6,553.4 secondsDefault Null Value: 0.0 seconds (no failure detected)Note: Setting nciRcvHrtBt to 0 disables the Receive He

mechanism.Note: This CP is used to control the maximum time tha

elapses after the last update to a specified NVI bthe Space Comfort Controller starts to use its devalues.

Major Hardware or Software Revisions

nciMajVerSCPT_maj_ver

Valid Range: 0 to 255Note: This CP defines the major module hardware and

software revisions.

Minor Hardware or Software Revisions

nciMinVerSCPT_min_ver

Valid Range: 0 to 255Note: This CP defines the minor module hardware and

software revisions.

1. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint andOccupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjustedthermostat to maintain the minimum deadband between the two setpoints.

2. The BI object type status is available even if the configuration is set to None.

Table 6: Configuration Network Variables (Part 4 of 4)Parameter NCI Name and

SNVT, UNVT or SCPT Name

Range and Enumeration Definition

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

17

Page 18: TEC2245-2 LonWorks Networked Thermostats with Single

Commissioning the Thermostat Using a LONWORKS Network Configuration Tool

A thermostat must first be commissioned using a LONWORKS network configuration tool before it can be added to the LON Integration of the Network Automation Engine (NAE). This process implements the initial configuration and assigns the Neuron® ID of the thermostat.

Understanding LONWorks Network Configuration Tools’ Differences

LONWORKS network configuration tools use different numbering schemes in their Status/Command screens. Metasys system Connectivity to LONWORKS network (MCL) Tool begins its first entry with byte 0, while Lonwatcher begins with byte 1. Figure 1 shows the nciGenOpts Status/Command screen in MCL Tool on the left, with the equivalent Lonwatcher screen on the right.

Table 7: LONWORKS Network Configuration Tool Terminology DifferencesLONWORKS Network Configuration Tool

nvoSccStatus Screen nciGenOpts Screen

MCL Tool Bit 0 to Bit 63 Byte 0 to Byte 24

Lonwatcher Bit 1 to Bit 64 Byte 1 to Byte 25

LonMaker Not directly changeable Not directly changeable

Figure 1: MCL Tool and Lonwatcher Status/Command Screens

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

18

Page 19: TEC2245-2 LonWorks Networked Thermostats with Single

Changing the Thermostat’s Settings Using a LONWORKS Network Configuration Tool

Once a thermostat is configured and online, you can use a LONWORKS network configuration tool to change its settings. This means you do not have to go to the thermostat and manually make the changes.

To change most of the thermostat’s configuration properties:

1. Using a LONWORKS network configuration tool, open the thermostat’s nciGenOpts Status/Command screen.

2. From Table 8, find the desired configuration property and enter the corresponding value into its respective byte location in the nciGenOpts Status/Command screen.

Note: Some configuration properties require you to enter a range number in a specific byte location, followed by a corresponding value in the next byte location. You must enter both the range number and value before commanding the thermostat.

3. Enter additional configuration property changes if desired.

4. Command the thermostat. The new configuration changes are implemented.

Note: The Lockout settings must be made at the thermostat.

Service PinTo broadcast the thermostat’s Neuron ID over the LONWORKS network:

1. Simultaneously press and hold the Up Arrow and Down Arrow for 5 seconds. A small green light under the thermostat cover (on the left edge when facing the thermostat) flashes to indicate the thermostat’s Neuron ID is being broadcast on the LONWORKS network.

2. For manual entry, the Neuron ID is also on a label on the Echelon® chip under the thermostat cover.

Adding a Thermostat to the NAEOnce you commission a thermostat, you must add it to the NAE before its points can be mapped. To do this, select the LONWORKS Integration under the NAE (refresh the tree view if required to see a newly added LONWORKS Integration) and choose Field Device from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add a new thermostat online; however, this requires that the new thermostat is connected and ready to communicate. Refer to the LONWORKS Network Integration with NAE Technical Bulletin (LIT-1201668) for instructions on how to add a LONWORKS device.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

19

Page 20: TEC2245-2 LonWorks Networked Thermostats with Single

LONWORKS Thermostat Mapping

PreparationBefore mapping a TEC2245-2 Thermostat into an NAE:

1. Decide which point objects within the thermostat need to be mapped. Only map the point objects that need to be viewed on a regular basis, since excessive mapping lowers system performance. Suggested point objects for mapping include: Room Temp, System Mode, Fan Status, Occupied Heat Setpoint, Occupied Cool Setpoint, Unoccupied Heat Setpoint, and Unoccupied Cool Setpoint. In addition, alarm points may be mapped if they are used, and other point objects may be mapped if required. Use the Engineering view to examine infrequently used point objects.

2. Verify that a LONWORKS Integration is defined in the NAE. The commissioned thermostat is mapped as a LONWORKS device under a LONWORKS Integration. Refer to the LONWORKS® Network Integration with NAE Technical Bulletin (LIT-1201668) for instructions on how to define a LONWORKS network Integration.

At this point, you can map the thermostat and the required point objects inside the thermostat.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

20

Page 21: TEC2245-2 LonWorks Networked Thermostats with Single

Space Comfort Controller Object

Figure 2: TEC2245-2 Space Comfort Controller Object

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

21

Page 22: TEC2245-2 LonWorks Networked Thermostats with Single

ve

tt

r from

r from

r from

r from

Thermostat Command TableUse Table 8 to configure the thermostat with a LONWORKS network configuration tool. Table 8: Thermostat Command Table (Part 1 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)

Stat Menu Name

Description Byte and Range

0 (1) Not used. Not used.

1 (2) Not used. Not used.

2 (3) Not used. Not used.

3 (4) RA/DA Reverse acting output 0 = Direct Acting1 = Reverse Acting

4 (5) BI1 Configuration of Binary Input1. 0 = None1 = Rem NSB2 = Motion NO3 = Motion NC4 = Window

5 (6) BI2 Configuration of Binary Input2. 0 = None1 = Door Dry2 = RemOVR3 = Filter4 = Service

6 (7) UI3 Configuration of Universal Input3. 0 = None1 = COC/NH2 = COC/NC3 = COS4 = SS

7 (8) MenuScro Enables menu scrolling. 0 = Off = Scroll not acti1 = On = Scroll active

8 (9) AutoMode System Mode 0 = Off1= On

9 (10) C or F Displayed temperature scale. 0 = °C1 = °F

10 (11) Not used. Not used.

11 (12) SeqOpera Determines the sequence of operation. 0 = Cooling Only1 = Heating Only2 = Cooling with Rehea3 = Heating with Rehea

12 (13) Fan mode Fan On or Fan Auto 0 = Fan On1 = Fan Auto

13 (14) Heat max Occupied and Unoccupied maximum Heating setpoint range number.

Enter the range numbeTable 9.

14 (15) Heat max Occupied and Unoccupied maximum Heating setpoint value number.

Enter the value numbeTable 9.

15 (16) Cool min Occupied and Unoccupied minimum Cooling setpoint range number.

Enter the range numbeTable 10.

16 (17) Cool min Occupied and Unoccupied minimum Cooling setpoint value number.

Enter the value numbeTable 10.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

22

Page 23: TEC2245-2 LonWorks Networked Thermostats with Single

17 (18) Set type Temporary setpoint enable. 0 = Permanent1 = Temporary

18 (19) TOccTime Minimum occupancy time. 0 = 0 Hours1 = 1 Hours2 = 2 Hours3 = 3 Hours4 = 4 Hours5 = 5 Hours6 = 6 Hours7 = 7 Hours8 = 8 Hours9 = 9 Hours10 = 10 Hours11 = 11 Hours12 = 12 Hours13 = 13 Hours14 = 14 Hours15 = 15 Hours16 = 16 Hours17 = 17 Hours18 = 18 Hours19 = 19 Hours20 = 20 Hours21 = 21 Hours22 = 22 Hours23 = 23 Hours24 = 24 Hours

19 (20) Door Time Engages the Unoccupied mode if the door stays open minimally for the time specified.

1 = 1 minute2 = 2 minutes3 = 3 minutes4 = 4 minutes5 = 5 minutes6 = 6 minutes7 = 7 minutes8 =8 minutes9 = 9 minutes10 = 10 minutes

Table 8: Thermostat Command Table (Part 2 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)

Stat Menu Name

Description Byte and Range

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

23

Page 24: TEC2245-2 LonWorks Networked Thermostats with Single

r from

r from

Closed

t Open

from a

Commanding the Maximum Heating SetpointEnter the range byte (MCL Tool Byte Number 13, Lonwatcher Byte Number 14) and value byte (MCL Tool Byte Number 14, Lonwatcher Byte Number 15) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat. See Table 9.

Note: You must enter both values before commanding the thermostat.

20 (21) Deadband Sets the minimum deadband between the heating and cooling setpoints.

11 = 2°F17 = 3°F22 = 4°F28 = 5°F

21 (22) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.

Enter the range numbeTable 11.

22 (23) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.

Enter the value numbeTable 11.

23 (24) Aux cont Determines the auxiliary contactfunction and configuration.

0 = Used for reheat1 = Aux N.O., Occupied = Contact2 = Aux N.C. Occupied = Contac3 = Not used.4 = Not used.5 = Aux On/Off control separate and dedicatednetwork variable.

24 (25) Reheat Reheat time base 0 = 15 minutes1 = 10 seconds

Table 8: Thermostat Command Table (Part 3 of 3)MCL Tool Byte Number(Lonwatcher Byte Number)

Stat Menu Name

Description Byte and Range

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

24

Page 25: TEC2245-2 LonWorks Networked Thermostats with Single

e 14

sis. l.

Table 9: Maximum Heat Setpoint Range Adjustment ValuesMax-HeatSet-point Setting

Range Byte 13 (14)

Value Byte 14 (15)

Max-Heat Set-point Setting

Range Byte 13 (14)

Value Byte 14 (15)

Max-Heat Set-point Setting

Range Byte 13 (14)

ValuByte(15)

40°F 1 188 57°F 5 108 74°F 9 29

40.5°F 1 216 57.5°F 5 136 74.5°F 9 57

41°F 1 244 58°F 5 164 75°F 9 84

41.5°F 2 15 58.5°F 5 192 75.5°F 9 112

42°F 2 43 59°F 5 220 76°F 9 140

42.5°F 2 71 59.5°F 5 247 76.5°F 9 168

43°F 2 99 60°F 6 19 77°F 9 196

43.5°F 2 126 60.5°F 6 47 77.5°F 9 223

44°F 2 154 61°F 6 75 78°F 9 251

44.5°F 2 182 61.5°F 6 102 78.5°F 10 23

45°F 2 210 62°F 6 130 79°F 10 51

45.5°F 2 238 62.5°F 6 158 79.5°F 10 78

46°F 3 9 63°F 6 186 80°F 10 106

46.5°F 3 37 63.5°F 6 214 80.5°F 10 134

47°F 3 65 64°F 6 241 81°F 10 162

47.5°F 3 93 64.5°F 7 13 81.5°F 10 190

48°F 3 120 65°F 7 41 82°F 10 217

48.5°F 3 148 65.5°F 7 69 82.5°F 10 245

49°F 3 176 66°F 7 96 83°F 11 17

49.5°F 3 204 66.5°F 7 124 83.5°F 11 45

50°F 3 232 67°F 7 152 84°F 11 72

50.5°F 4 3 67.5°F 7 180 84.5°F 11 100

51°F 4 31 68°F 7 208 85°F 11 128

51.5°F 4 59 68.5°F 7 235 85.5°F 11 156

52°F 4 87 69°F 8 7 86°F 11 184

52.5°F 4 114 69.5°F 8 35 86.5°F 11 211

53°F 4 142 70°F 8 63 87°F 11 239

53.5°F 4 170 70.5°F 8 90 87.5°F 12 11

54°F 4 198 71°F 8 118 88°F 12 39

54.5°F 4 226 71.5°F 8 146 88.5°F 12 66

55°F 4 253 72°F 8 174 89°F 12 94

55.5°F 5 25 72.5°F 8 202 89.5°F 12 122

56°F 5 53 73°F 8 229 90°F 12 150

56.5°F 5 81 73.5°F 9 1

Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parentheSee Table 7 for more information on Bit/Byte use in each LONWORKS network configuration too

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

25

Page 26: TEC2245-2 LonWorks Networked Thermostats with Single

ue e 16 )

sis. l.

Commanding the Minimum Cooling SetpointUsing a LONWORKS network configuration tool, enter the range byte (MCL Tool Byte Number 15, Lonwatcher Byte Number 16) and value byte (MCL Tool Byte Number 16, Lonwatcher Byte Number 17) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat.

You must enter both values before commanding the thermostat. Table 10: Minimum Cooling Setpoint Range Adjustment ValuesMinCool Set-point Setting

Range Byte 15 (16)

Value Byte 16 (17)

Min-Cool Set-point Setting

Range Byte 15 (16)

Value Byte 16 (17)

MinCool Set-point Setting

Range Byte 15 (16)

ValByt(17

54°F 4 198 69.5°F 8 35 85°F 11 128

54.5°F 4 226 70°F 8 63 85.5°F 11 156

55°F 4 253 70.5°F 8 90 86°F 11 184

55.5°F 5 25 71°F 8 118 86.5°F 11 211

56°F 5 53 71.5°F 8 146 87°F 11 239

56.5°F 5 81 72°F 8 174 87.5°F 12 11

57°F 5 108 72.5°F 8 202 88°F 12 39

57.5°F 5 136 73°F 8 229 88.5°F 12 66

58°F 5 164 73.5°F 9 1 89°F 12 94

58.5°F 5 192 74°F 9 29 89.5°F 12 122

59°F 5 220 74.5°F 9 57 90°F 12 150

59.5°F 5 247 75°F 9 84 90.5°F 12 178

60°F 6 19 75.5°F 9 112 91°F 12 205

60.5°F 6 47 76°F 9 140 91.5°F 12 233

61°F 6 75 76.5°F 9 168 92°F 13 5

61.5°F 6 102 77°F 9 196 92.5°F 13 33

62°F 6 130 77.5°F 9 223 93°F 13 60

62.5°F 6 158 78°F 9 251 93.5°F 13 88

63°F 6 186 78.5°F 10 23 94°F 13 116

63.5°F 6 214 79°F 10 51 94.5°F 13 144

64°F 6 241 79.5°F 10 78 95°F 13 172

64.5°F 7 13 80°F 10 106 95.5°F 13 199

65°F 7 41 80.5°F 10 134 96°F 13 227

65.5°F 7 69 81°F 10 162 96.5°F 13 255

66°F 7 96 81.5°F 10 190 97°F 14 27

66.5°F 7 124 82°F 10 217 97.5°F 14 54

67°F 7 152 82.5°F 10 245 98°F 14 82

67.5°F 7 180 83°F 11 17 97.5°F 14 110

68°F 7 208 83.5°F 11 45 99°F 14 138

68.5°F 7 235 84°F 11 72 99.5°F 14 166

69°F 8 7 84.5°F 11 100 100°F 14 193

Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parentheSee Table 7 for more information on Bit/Byte use in each LONWORKS network configuration too

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

26

Page 27: TEC2245-2 LonWorks Networked Thermostats with Single

red. Use a ORKS network.

a LONWORKS

Commanding the Cal RS SettingsUsing a LONWORKS network configuration tool, enter the Byte 21 (22) range number and Byte 22 (23) value number (Table 11) in their respective byte entry boxes of the nciGenOpts screen and command the thermostat.

Note: You must enter both values before commanding the thermostat.

Status Light-Emitting Diode (LED)The status LED shows the operational status of the thermostat. The Status LED is a small green light under the thermostat cover (under the LONWORKS daughter board on the left edge when facing the thermostat).

Table 11: Cal RS Command SettingsCal RS Setting Byte 21 (22) Range Byte 22 (23) Value5°F 1 21

4°F 0 222

3°F 0 166

2°F 0 111

1°F 0 55

0°F 0 0

-1°F 255 201

-2°F 255 145

-3°F 255 90

-4°F 255 34

-5°F 255 235

Note: Lonwatcher Range byte location numbers and Value byte location numbers are shown in parenthesis. See Table 7 for more information on byte use in each LONWORKS network configuration tool.

Table 12: Status LED ExplanationStatus LED Condition ExplanationContinuously On The thermostat does not have an application loaded in its memory.

Flashing at a 0.5 Hz Rate The thermostat has an application loaded in its memory but is unconfiguLONWORKS network management tool to bind the thermostat to a LONW

Continuously Off The thermostat has an application loaded in its memory and is bound tonetwork.

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

27

Page 28: TEC2245-2 LonWorks Networked Thermostats with Single

t be the same e before the

table.

to respond.

table.

table.

, Class 2 or

r UI3

WG (1.0 mm

a Repeater;

Troubleshooting

Technical Specifications

Table 13: Troubleshooting DetailsSymptom Probable CausesMultiple Symptoms

Excessive bus errors may be occurring.

A device may have been added or changed with a duplicate Neuron ID (may noaddress as some devices having problems, and may have happened sometimproblem was noticed).

Wiring errors or wire problems may exist.

A download may be in progress.

There may be a fault at a device.

A repeater may be needed or may be configured incorrectly.

Poor Performance See the probable causes listed in the Multiple Symptoms section earlier in this

Excessive bus traffic may exist (bus overload).

There may be too many devices on the network.

There may be unaccounted devices on the network (not mapped to the NAE).

There may be unusually slow devices on the network or devices that are slow

Thermostat Goes Offline

See the probable causes listed in the Multiple Symptoms section earlier in this

A power failure or other failure may have occurred at the thermostat.

Communication may have been disabled at the thermostat.

Thermostat Will Not Come Online.

See the probable causes listed in the Multiple Symptoms section earlier in this

A thermostat may be connected to the wrong bus.

TEC2245-2 LONWORKS Network Thermostat with Single Proportional Output and One-Speed Fan Control (Part 1 of 2)Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal

Safety Extra-Low Voltage (SELV)

Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum)

Fan Relay Output Rating 30 VAC, 1.0 A Maximum, 3.0 A In-Rush

Auxiliary Output Rating

Triac Output 30 VAC, 1.0 A Maximum, 3.0 A In-Rush

Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, o

Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 ADiameter) Recommended

LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with6,250 ft (1,905 m) Maximum (Bus Topology)

Thermostat Measurement Range

-40.0°F/-40.0°C to 122.0°F/50.0°C

Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor

Resolution ±0.2F°/±0.1C°

Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated

Control Range

Heating 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments

Cooling 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments

Minimum Deadband 2F°/1C° between Heating and Cooling

Ambient Conditions

Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing

Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

28

Page 29: TEC2245-2 LonWorks Networked Thermostats with Single

g Equipment

beyond these from misapplication or

FCC Rules. These mmercial

ccordance with the area is likely to cause

.

Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating EquipmentFCC Compliant to CFR 47, Part 15, Subpart B, Class ALONMARK® Certification 3.4 (pending)

Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and RegulatinIndustry Canada, ICES-003

Europe CE Mark, EMC Directive 89/336/EEC

Australia and New Zealand

C-Tick Mark, Australia/NZ Emissions Compliant

Shipping Weight 0.75 lb (0.34 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting misuse of its products.United States Emissions Compliance:This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of thelimits are designed to provide reasonable protection against harmful interference when this equipment is operated in a coenvironment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in ainstruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residentialharmful interference, in which case the user will be required to correct the interference at his/her own expense.Canadian Emissions Compliance:This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada

TEC2245-2 LONWORKS Network Thermostat with Single Proportional Output and One-Speed Fan Control (Part 2 of 2)

Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.

© 2006 Johnson Controls, Inc.

Controls Group507 E. Michigan StreetMilwaukee, WI 53202

Published in U.S.A. www.johnsoncontrols.com

TEC2245-2 LONWORKS® Networked Thermostats with Single Output and One-Speed Fan Control Technical Bulletin

29