tc fundamentals 2011 grd basic selection and application (1)

65
Basic Selection & Proper Application of Overhead Air Distribution Devices

Upload: fghabboon

Post on 01-Jun-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 1/65

Basic Selection & Proper Application

of Overhead Air Distribution Devices

Page 2: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 2/65

GRD Selection & Application

• Terms

• Selection

 – Throw – Sound

• Installation Variations affect Performance

• Inlet Effects

Page 3: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 3/65

Basics

Coanda

Total

Air 

Primary Air 

Induced

Room Air 

Entrained

Room Air 

Return Air 

Page 4: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 4/65

Basics

•  ASHRAE Standard 70-2006

 – Standard Defines Testing Procedures,

Spaces, and Equipment

 – Isothermal Testing

 – Non-Turbulent, Smooth Inlet Conditions

 – Obtain Catalog Data

Page 5: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 5/65

Selection – Throw

1) Throw – Distance to a specified Vt

2) Terminal Velocity (Vt) – Maximum

airstream velocity at the end of a throw.

50 fpm TV

100 fpm TV150 fpm TV

Page 6: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 6/65

Selection – Throw

• Outlet Patterns – 150 cfm – 6” Inlet

Plaque-  6’

Slot -  19’ Slot -  29’

Perf -  10’Louver

Face -  16’

Page 7: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 7/65

Selection – Throw

• 380 cfm, 10” Neck, 700 fpm, T50

10‟ Square Cone

9‟ Round Cone

14‟ 4 Way - Perf Curved Vane

33‟ 1 Way - Perf Curved Vane

24‟ 4 Way - Louver Face

Page 8: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 8/65

Selection – Throw

• Deflection and Spread

Page 9: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 9/65

Selection – Throw

• Throw Boundaries – Mapping

Vt Maximum of 75 fpm

Page 10: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 10/65

Page 11: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 11/65

Page 12: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 12/65

Selection – Throw

Tested in accordance with ASHRAE Standard 70-2006 “Method ofTesting for Performance of Air Outlets and Inlets.”

Radii of diffusion are given in feet to terminal velocities of 150 fpm (minimum),100 fpm (middle) and 50 fpm (maximum).

Throw data is based on supply air and room air being at isothermal conditions.

Page 13: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 13/65

Selection – Throw

• Non-Isothermal Effects

 Adjust Throw at V t = 50 fpm

1% Per° F of Differential 

Cooling Heating

Horizontal   – +

Vertical +   –

Page 14: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 14/65

Selection – Throw

• Exposed Mount vs. Surface Mount

Exposed MountReduce Throw

30%

Page 15: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 15/65

• Locate in from wall

• Discharge to perimeter • Generally slot diffusers

• Cooling Airflow – 50 fpm at

floor 

• Heating Airflow – 50 fpm at2/3 down the wall

Heating & Cooling w/ OHAD

Selection – Throw

Page 16: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 16/65

Selection – Throw

• Obstructions

 – Air jet will typically remain on surface, if angle

created by the ceiling, diffuser, and bottom of

obstruction is <10°. – From testing, angle can be as great as 15°.

<10°

Page 17: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 17/65

Selection – Sound

• Catalog Data

 – NC Rating

•  Average Room Size

• Distance from Source

 – Assumes 10 dB Room Absorption

 – Single Diffuser or Standard Length

Page 18: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 18/65

Selection – Sound

Page 19: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 19/65

Selection – Sound

Page 20: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 20/65

Selection – Sound

Page 21: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 21/65

24” x 24” Diffuser, 380cfm, 700 fpm Neck Velocity

3-21

Selection – Sound

Page 22: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 22/65

NC 45

3-22

Selection – Sound

NC 37

NC 36NC 31

1 - 1”Slot, 4‟, 270cfm, 800 fpm Neck Velocity

Page 23: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 23/65

3-23

Installation – Sound

Page 24: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 24/65

3-24

Installation – Sound

Page 25: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 25/65

Balancing Dampers

• Some outlets cataloged with damper in open position

• Sound Increase depends on:

 – damper design

 – ratio of throttled pressure over cataloged pressure drop

3-25

Installation – Sound

Pressure Ratio 1.5 2 3 4

dB/NC Increase 4 6 13 18

Page 26: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 26/65

Damper Location

Pressure Ratio = 2

(normal pressure

drop X 2)

3-26

Installation – Sound

0 dB

+ 3 dB

+ 9 dB

Page 27: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 27/65

Page 28: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 28/65

 ASHRAE Standard 70 – Throw Room

• Measurements taken in a „Standard Test Room‟

 – Height => 9‟

 – Minimum Length = 24‟

 – Minimum Width = 18‟

 –  All lights and windows shall be flush to the surface they

are attached.

 –  Air exhausted away from supply path.

Page 29: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 29/65

• 2 Different Types of Test Ducts

 – Large Pressurized plenum

 – 3 Diameters Straight duct•  Air outlet device is to receive uniformly

distributed air from the supply duct.

 ASHRAE Standard 70 – Inlet Conditions

Page 30: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 30/65

Effect of Inlet Conditions on Throw

• Test Standard Installation

 – Repeatable, uniform throw distances

 – Repeatable, drop

 – Repeatable, discharge pattern

• Hard 90 Degree Elbow

• Flex Duct 90 Degree Elbow

• Radial Opposed Blade Damper • Butterfly Damper 

• Bowtie Damper 

Page 31: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 31/65

 A “Special” Field Installation

Page 32: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 32/65

Page 33: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 33/65

More Poor Workmanship Examples

Page 34: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 34/65

Page 35: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 35/65

Louver Face Ceiling Diffuser 

Page 36: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 36/65

L F C ili Diff

Page 37: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 37/65

Louver Face Ceiling Diffuser - Test Standard Installation

350 CFM

Page 38: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 38/65

Louver Face Ceiling Diffuser - Hard 90 Degree Elbow

350 CFM

Page 39: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 39/65

Louver Face Ceiling Diffuser - Flex Duct 90 Degree Elbow

350 CFM

Page 40: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 40/65

 AHHHH!! FLEX MONSTER!!

Page 41: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 41/65

Louver Face Ceiling Diffuser

Page 42: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 42/65

Louver Face Ceiling Diffuser  -

Butterfly Damper 

350 CFM  – Damper set for 0.25 inches of water 

L F C ili Diff

Page 43: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 43/65

Louver Face Ceiling Diffuser  -

Bowtie Damper 

350 CFM  – Damper set for 0.25 inches of water 

Page 44: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 44/65

More Poor Workmanship Examples

Page 45: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 45/65

Plaque Ceiling Diffuser 

C ff

Page 46: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 46/65

Plaque Ceiling Diffuser 

Pl C ili Diff

Page 47: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 47/65

Plaque Ceiling Diffuser 

Plaque Ceiling Diffuser

Page 48: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 48/65

Plaque Ceiling Diffuser - Test Standard Installation

350 CFM

Plaque Ceiling Diffuser

Page 49: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 49/65

Plaque Ceiling Diffuser - Hard 90 Degree Elbow

350 CFM

Plaque Ceiling Diffuser

Page 50: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 50/65

Plaque Ceiling Diffuser - Flex Duct 90 Degree Elbow

350 CFM

Plaque Ceiling Diffuser

Page 51: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 51/65

Plaque Ceiling Diffuser - Radial Opposed Blade Damper 

350 CFM  – Damper set for 0.25 inches of water 

Page 52: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 52/65

Plaque Ceiling Diffuser

Page 53: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 53/65

Plaque Ceiling Diffuser - Bowtie Damper 

350 CFM  – Damper set for 0.25 inches of water 

Page 54: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 54/65

Ceiling Slot Diffuser 

Square Plenum

Sloped Plenum

Page 55: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 55/65

Ceiling Slot Diffuser 

Ceiling Slot Diffuser

Page 56: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 56/65

Ceiling Slot Diffuser

- Test Standard Installation

350 CFM with straight plenum

350 CFM with sloped plenum

Ceiling Slot Diffuser

Page 57: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 57/65

Ceiling Slot Diffuser- Hard 90 Degree Elbow

350 CFM with straight plenum

350 CFM with sloped plenum

Ceiling Slot Diffuser

Page 58: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 58/65

g- Flex Duct 90 Degree Elbow

350 CFM with straight plenum

350 CFM with sloped plenum

Ceiling Slot Diffuser

Page 59: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 59/65

Ceiling Slot Diffuser- Radial Opposed Blade Damper 

350 CFM with straight plenum (dpr set to .25inWC)

350 CFM with sloped plenum

(dpr set to .25inWC)

Ceiling Slot Diffuser

Page 60: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 60/65

g- Butterfly Damper 

350 CFM with straight plenum (dpr set to .25inWC)

350 CFM with sloped plenum

(dpr set to .25inWC)

C ili Sl t Diff

Page 61: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 61/65

Ceiling Slot Diffuser- Bowtie Damper 

350 CFM with straight plenum (dpr set to .25inWC)

350 CFM with sloped plenum(dpr set to .25inWC)

W k hi C t !

Page 62: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 62/65

Workmanship Counts!

Page 63: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 63/65

Sidewall Grille Video (12X6)

Page 64: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 64/65

Sidewall Grille Video (12X6)

0 Dia 1 Dia

2 Dia 3 Dia

Page 65: Tc Fundamentals 2011 Grd Basic Selection and Application (1)

8/9/2019 Tc Fundamentals 2011 Grd Basic Selection and Application (1)

http://slidepdf.com/reader/full/tc-fundamentals-2011-grd-basic-selection-and-application-1 65/65

GRD Selection & Application

• Terms

• Selection

 – Throw

 – Sound

• Installation Variations affect Performance

• Inlet Effects