  • February 2007

    CA08101001E For more information visit:

    www.eaton.com

    Contents

    Power Breakers, Contactors & Fuses 13-1

    13

    Po

    wer

    Bre

    aker

    s,C

    on

    tact

    ors

    & F

    use

    s

    Description Page

    Power Circuit Breakers

    Low Voltage Power Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-2

    Magnum Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-2

    Magnum DS Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . .

    13-6

    Magnum SB Insulated Case Circuit Breakers . . . . . . . . . . . . . . . . . . . .

    13-8

    Magnum IEC Rated Air Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . .

    13-10

    Medium Voltage Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-17Power Contactors

    Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-26

    Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-30

    Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-31

    SL Series (160 400 Amperes). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-32

    SL Series (800 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-34

    Lug Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-35

    Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-36Expulsion Fuses

    Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-39

    Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-41

    Type RBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-42

    Type RDB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-46

    Type DBU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-50

    Type DBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-53Current Limiting Fuses

    Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-55

    Type CLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-56

    Type HLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-60

    Type BHLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-62

    Types BHLE and HCL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-63

    Type CLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-67

    Type CLPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-71

    Type CX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-74

    Type CXN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-76

    Type DSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-77

    Type CXF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-78

    Typical Fuse Mounting for Current Limiting Fuses . . . . . . . . . . . . . . .

    13-79

    Pricing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-80

    Power Breakers, Contactors and Fuses Family

  • February 2007

    13-2

    For more information visit:

    www.eaton.com

    CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit Breakers

    Low Voltage Power Circuit Breakers

    Magnum Low Voltage Power Circuit Breakers for Global Application

    Magnum

    Low Voltage Power Circuit Breakers enable comprehensive solutions to meet and exceed the unique and wide-ranging requirements of todays global power distribution systems. This powerful circuit breaker offering is designed for ultimate custom configuration and applica-tion flexibility, with the needs of the power distribution equipment user and the electrical equipment manufacturer in mind.

    Three Product Families

    Magnum consists of three product families; each provides specific ratings features and approvals to optimize perfor-mance when applied in power distribution equipment and custom enclosures:

    Magnum DS Low Voltage Power Circuit Breakers for ANSI Rated Switchgear Applications

    Up to 635 Vac.

    200 to 6000 A continuous.

    42 to 200 kA interrupting.

    Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications

    Magnum SB Low Voltage Insulated Case Circuit Breakers for Switchboard Applications

    Up to 635 Vac.

    200 to 5000 A continuous.

    50 to 150 kA interrupting.

    Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications

    Magnum IEC Air Circuit Breakers for IEC Rated Switchboards

    Up to 690 Vac.

    200 to 6300 A continuous.

    40 to 100 kA I

    cu

    /I

    cs.

    Magnum IEC Low Voltage Air Circuit Breaker Family

  • February 2007

    CA08101001E For more information visit:

    www.eaton.com

    13-3Power Breakers, Contactors & Fuses

    13

    Power Circuit Breakers

    Low Voltage Power Circuit Breakers

    Features, Benefits and Functions

    200 kA interruption ratings

    with current limiting perfor-mance and low current let-through to reduce damaging energy to downstream equipment at high fault levels.

    Withstand ratings up to 100 kA

    to maximize system coordination and selectivity.

    Three physical frame sizes

    (Narrow, Standard and Double) to promote breaker application in compact modular enclosures.

    Continuous current ratings from 800 to 6300 A

    with 100% rating at 40C and no derating on most ratings up to 50C.

    Fixed breaker mounting configurations

    with horizontal and optional vertical and front connected terminal connections.

    Drawout breaker mounting configurations

    with cassette and optional safety shutters.

    3- and 4-pole breaker configurations.

    Through-the-door design

    for human interface with the breaker compartment door closed.

    Two-step stored energy mechanism

    for manually and electrical operated breakers.

    Digitrip RMS Trip Unit family

    with four models, each providing increasing levels of features:

    Basic to advanced programmable overcurrent protection

    with communications, power metering and power quality

    New Arcflash Reduction Maintenance Switch

    setting (enabled locally or remotely) to reduce arc flash potential on downstream circuits during maintenance operations

    Field installable accessories

    (UL

    approved) common across the breaker frames and designed to be easily installed in the field to service or modify the breaker at the point of use.

    Secondary terminal contacts

    mounted at the top front of the breaker and away from the primary voltage areas for improved safety and access. Finger-proof terminal blocks accommodate ring-tongue or spade type terminals as standard.

    Through-the-Door Design for Human Interface with the Breaker Compartment Door Closed

    High Technology Microprocessor-Based Digitrip RMS 1150+ Trip Units are Available With Advanced Features Like Programmable Overcurrent Settings, Power Metering, Power Quality and Communications

  • February 2007

    13-4

    For more information visit:

    www.eaton.com

    CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit Breakers

    Low Voltage Power Circuit Breakers

    Breaker Features on Front Cover

    The controls and indicators are func-tionally grouped on the breaker face-plate to optimize the human interface, visibility, and ease of use. For maxi-mum safety, a modern, through-the-door design permits access to the breaker levering system, trip unit, controls and indicators with the door closed.

    Mechanical Trip Flag Pop-out Indicator (Optional) Red

    Accessory Viewing Windows for:

    Shunt Trip Attachment (STA)

    Spring Release Device (SR)

    Undervoltage Release (UVR) Device or Second STA

    Digitrip RMS Trip Unit (Model 520M Shown) Protected by Clear Cover

    Contact Status Indicators:

    OPEN Green

    CLOSED Red

    Spring Status Indicators:

    Charged Yellow

    Discharged White

    Push OFF (Open) Pushbutton Red

    Push ON (Close) Pushbutton Green

    Manual Spring Charging Handle for Manually Charging the Stored Energy Springs

    Mechanical Operations Counter (Optional)

    Key Off Lock (Optional)

    Padlockable Levering Device Shutter for Drawout Breakers

    Color-Coded Position Indicator for Drawout Breakers:

    CONNECT Red

    TEST Yellow

    DISCONNECT Green

    Magnum DS Drawout Breaker

    Accessory Viewing Windows Visibly Confirm the Breaker Shunt Trip, Spring Release, and UVR Installation and Their Control Voltage Rating

    Through-the-Door Design for Human Interface with the Breaker Compartment Door Closed, for Example, Manually Charging the Stored Energy Springs

    Drawout Breaker Levering Can be Accomplished With the Compartment Door Closed Without the Need for a Special Levering Tool

  • February 2007

    CA08101001E For more information visit:

    www.eaton.com

    13-5Power Breakers, Contactors & Fuses

    13

    Power Circuit Breakers

    Low Voltage Power Circuit Breakers

    Breaker Internal Features

    Magnum is designed for ease of access for inspection, modification and maintenance at the point of use. The breaker front cover is easily removed with four captive bolts, revealing the modular internal breaker features.

    Secondary Terminal Points for Internal Breaker Wiring Connections

    Breaker Accessory Mounting Deck with Three Positions for Mounting:

    Shunt Trip Attachment (STA)

    Spring Release Device (SR)

    Undervoltage Release (UVR) Device or Second STA

    Digitrip RMS Trip Unit (Model 1150+ Shown)

    Spring Charging Motor (Optional) for Electrically Charging the Stored Energy Springs

    Manual Spring Charging Handle for Manually Charging the Stored Energy Springs

    Padlockable Levering Device Shutter for Drawout Breakers

    Color-Coded Position Indicator forDrawout Breakers:

    CONNECT Red TEST Yellow DISCONNECT Green

    Secondary Contact Blocks for Connection to External Cell Control Wiring

    Removable Arc Chute Covers for Easy Access to Breaker Main Contacts

    Primary Finger Cluster Disconnect-ing Contacts for Drawout Breaker are Mounted on the Breaker Ele-ment (Not in the Breaker Compart-ment) for Ease of Access for Inspection and Maintenance

    Current Sensor Viewing Windows to View and Confirm Breaker Sensor Rating

    Rigid Frame Housing (Thermoset Composite Resin) Providing Increased Strength and Durability

    Magnum Drawout Breaker Front View With Front Cover Removed Showing Easy Access to the Breaker Internal Devices

    Magnum Drawout Breaker Rear View Showing Primary Disconnecting Finger Clusters Mounted on the Breaker for Ease of Inspection

  • February 2007

    13-6

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum DS Low Voltage Power Circuit BreakersMagnum DS is a true UL 1066 listed low voltage power circuit breaker family, designed for the highest perfor-mance requirements of switchgear and specialty enclosure applications.

    Magnum DS Low Voltage Power Circuit Breakers have short time withstand and interruption ratings up to 100 kA at 635 Vac with continuous current ratings up to 6000 amperes to maximize system coordination and selectivity.

    Magnum MDSX Current Limiting Power Circuit Breakers have 200 kA interrupting ratings at 480 Vac with continuous current ratings up to 5000 amperes.

    Magnum MDSL Current Limiting Power Circuit Breakers have 200 kA interrupting ratings at 600 Vac with continuous current ratings up to 2000 amperes.

    UL and ANSI Test CertificationsMagnum DS meets or exceeds the applicable ANSI, NEMA, UL and CSA standards, including:

    ANSI C37.13 (Low Voltage ac Power Circuit Breakers Used in Enclo-sures).

    ANSI C37.16 (Preferred Ratings, Related Requirements, and Application Recommendations for Low Voltage Power Circuit Breakers and ac Power Circuit Breakers).

    ANSI C37.17 (Trip Devices for ac and General Purpose dc Low Voltage Power Circuit Breakers).

    ANSI C37.50 (Test Procedures for Low Voltage ac Power Circuit Break-ers Used in Enclosures).

    UL 1066 (Standard for Low Voltage ac and dc Power Circuit Breakers Used in Enclosures).

    NEMA SG3 (This standard adopts ANSI C37.16 in its entirety).

    Comprehensive Enclosure SolutionsMagnum DS has proven performance in Eaton manufactured switchgear and switchboards with the following test certifications:

    UL 1558 (Certified Magnum DS Low Voltage Metal-Enclosed Switchgear).

    UL 891 (Certified Pow-R-Line C Low Voltage Switchboards).

    UL 1008 Standard for Transfer Switch Equipment.

    UL, CSA 22.2.31 Low Voltage Assemblies.

    Approvals

    UL listed: Magnum DS Breaker UL File No. E52096 and Cassette UL File No. E204565.

    ABS (American Bureau of Shipping) Type Listed Certificate Number 04-HS422844A-DUB.

    Magnum DS, MDSL and MDSX Circuit Breakers

    Magnum DS Low Voltage Power Circuit Breakers have high withstand ratings from 42 kA to 100 kA to provide for maximum system coordination and selectivity.

    The new Magnum MDSL Current Limiting Power Circuit Breakers have integral current limiters to provide interrupting ratings of 200 kA at 600 Vac.

    The new Magnum MDSX Current Lim-iting Power Circuit Breakers have fast opening contacts to provide interrupt-ing ratings up to 200 kA at 480 Vac without fuses.

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-7Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum DS Switchgear Class UL 1066

    Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications

    Table 13-1. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers

    Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods.

    Magnum MDSL Current Limiting Power Circuit Breaker With Integral Current Limiters. Current Limiter selected determines short time and fixed instan-taneous trip rating. Maximum voltage rating is 600 Vac.

    Magnum MDSX Current Limiting Power Circuit Breaker With Fast Opening Contacts. Product to be tested. Contact Eaton for product rating. Breaker applied in a tested fan-cooled enclosure.

    Frame Amperes

    Breaker Type

    Frame Type

    rms Symmetrical Current Ratings kA 50/60 Hz Short Time Withstand Rating

    Fixed Internal Instantaneous Trip

    Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In rating)

    Interrupting at 254 Vac

    Interrupting at 508 Vac

    Interrupting at 635 Vac

    800 MDN-408MDN-508MDN-608MDN-C08

    NarrowNarrowNarrowNarrow

    42 50 65100

    42 50 65100

    42 50 65 65

    42 50 65 20

    18 x In

    200, 250, 300, 400, 600, 800

    MDS-408MDS-608MDS-808MDS-C08MDS-L08 MDS-X08

    StandardStandardStandardStandardStandardStandard

    42 65 85100200200

    42 65 85100200200

    42 65 85100200

    42 65 85 85 30

    8530

    1600 MDN-416MDN-516MDN-616MDN-C16

    NarrowNarrowNarrowNarrow

    42 50 65100

    42 50 65100

    42 50 65 65

    42 50 65 30

    18 x In

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600

    MDS-616MDS-816MDS-C16MDS-L16 MDS-X16

    StandardStandardStandardStandardStandard

    65 85100200200

    65 85100200200

    65 85100200

    65 85 85 30

    8530

    2000 MDN-620MDN-C20

    NarrowNarrow

    65100

    65100

    65 65

    65 35

    18 x In

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000

    MDS-620MDS-820MDS-C20MDS-L20 MDS-X20

    StandardStandardStandardStandardStandard

    65 85100200200

    65 85100200200

    65 85100200

    65 85 85 30

    8530

    3200 MDS-632MDS-832MDS-C32

    StandardStandardStandard

    65 85100

    65 85100

    65 85100

    65 85 85

    85

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000, 3200

    MDS-X32 Double 200 200 50 50

    4000 MDS-840MDS-C40MDS-X40

    DoubleDoubleDouble

    85100200

    85100200

    85100

    85100 50

    50

    2000, 2500, 3200, 4000

    5000 MDS-850MDS-C50MDS-X50

    DoubleDoubleDouble

    85100200

    85100200

    85100

    85100 50

    50

    2500, 3200, 4000, 5000

    6000 MDS-C60 Double 100 100 100 100 3200, 4000, 5000, 6000

  • February 2007

    13-8

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum SB Low Voltage Insulated Case Circuit Breakers

    Magnum SB Low Voltage Insulated Case Circuit Breakers are Designed for the Performance and Economic Requirements of UL 891 Switchboards

    Typical Magnum SB Low Voltage Insulated Case Circuit Breaker Nameplate

    Magnum SB is a Low Voltage Insulated Case Circuit breaker family designed for the performance and economic requirements of UL 891 switchboards.

    Magnum SB Insulated Case Circuit Breakers have Interruption ratings up to 100 kA at 635 Vac with continuous current ratings up to 5000 amperes.

    Magnum SB Insulated Case Circuit Breakers have lighter-duty Short Time Withstand ratings and fixed internal instantaneous trips on most ratings, which is characteristic of UL 489 molded case breakers commonly used in UL 891 switch-boards. This provides for greater economy and excellent coordination and selectivity for most commercial applications.

    Fixed internal instantaneous trips will be phased in on all SB Insulated Case Circuit Breakers rated 3200 amperes and below to provide an extra safety factor by reducing the energy let-through to downstream circuits at the maximum instanta-neous trip point and to facilitate feeder circuit breaker protection in UL 891 switchboards with 3-cycle bus bracing.

    Magnum SBSE Current Limiting Power Circuit Breakers have 150 kA Interrupting Ratings at 480 Vac with continuous current ratings up to 5000 amperes. The Short Time Withstand Rating is 30 kA for standard frame and 50 kA for double frame breakers.

    UL & ANSI Test CertificationsMagnum SB meets or exceeds the applicable ANSI, NEMA, UL and CSA standards, including:

    ANSI C37.13 (Low Voltage AC Power Circuit Breakers Used in Enclosures)

    ANSI C37.16 (Preferred Ratings, Related Requirements, and Application Recommendations for Low Voltage Power Circuit Breakers and AC Power Circuit Breakers)

    ANSI C37.17 (Trip Devices for AC and General Purpose DC Low Voltage Power Circuit Breakers)

    ANSI C37.50 (Test Procedures for Low Voltage AC Power Circuit Breakers Used in Enclosures)

    UL 1066 (Standard for Low Voltage AC and DC Power Circuit Breakers Used in Enclosures)

    NEMA SG3 (This standard adopts ANSI C37.16 in its entirety)

    Comprehensive Enclosure SolutionsMagnum DS has proven performance in Eaton manufactured switchgear and switchboards with the following test certifications:

    UL 1558 (Certified Magnum DS Low Voltage Metal-Enclosed switchgear)

    UL 891 (Certified Pow-R-Line C Low Voltage Switchboards)

    UL, CSA 22.2.31 Low Voltage Assemblies

    Approvals UL listed: Magnum DS Breaker

    UL File E52096 and Cassette UL File E204565.

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-9Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum SB Switchboard Class UL 1066 Insulated Case

    Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications

    Table 13-2. Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breaker

    Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods.

    Fixed Internal Instantaneous Trip set at approximately 18 x In symmetrical will be phased into the product. Product to be tested. Contact Eaton for product rating. Magnum SBSE Current Limiting Power Circuit Breaker With Fast Opening Contacts. Breaker applied in a tested fan-cooled enclosure.

    FrameAmperes

    Breaker Type

    FrameType

    rms Symmetrical Current Ratings kA 50/60 Hz Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In rating)

    Interruptingat 254 Vac

    Interruptingat 508 Vac

    Interruptingat 635 Vac

    Short TimeWithstand Rating

    Fixed InternalInst Trip

    800 SBN-508SBN-608SBN-C08

    NarrowNarrowNarrow

    50 65100

    50 65100

    35 42 65

    20 20 20

    18 x In

    200, 250, 300, 400, 600, 800

    SBS-608SBS-C08SBS-E08

    StandardStandardStandard

    65100200

    65100150

    65 85

    20 20 30

    30

    1200 SBN-512SBN-612SBN-C12

    NarrowNarrowNarrow

    50 65100

    50 65100

    35 42 65

    25 25 25

    18 x In

    200, 250, 300, 400, 600, 800, 1000, 1200

    SBS-612SBS-C12SBS-E12

    StandardStandardStandard

    65100200

    65100150

    65 85

    25 25 30

    30

    1600 SBN-516SBN-616SBN-C16

    NarrowNarrowNarrow

    50 65100

    50 65100

    35 42 65

    30 30 30

    18 x In

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600

    SBS-616SBS-C16SBS-E16

    StandardStandardStandard

    65100200

    65100150

    65 85

    30 30 30

    30

    2000 SBN-620SBN-C20

    NarrowNarrow

    65100

    65100

    65 65

    35 35

    18 x In200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000

    SBS-620SBS-C20SBS-E20

    StandardStandardStandard

    65100200

    65100150

    65 85

    35 35 30

    30

    2500 SBS-625SBS-C25

    StandardStandard

    65100

    65100

    65 85

    45 45

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500

    SBS-E25 Double 200 150 50 50

    3000 SBS-630SBS-C30

    StandardStandard

    65100

    65100

    65 85

    50 50

    200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000

    SBS-E30 Double 200 150 50 50

    4000 SBS-840SBS-C40SBS-E40

    DoubleDoubleDouble

    85100200

    85100150

    85100

    85100 50

    50

    2000, 2500, 3000, 4000

    5000 SBS-850SBS-C50SBS-E50

    DoubleDoubleDouble

    85100200

    85100150

    85100

    85100 50

    50

    2500, 3000, 4000, 5000

    6000 SBS-C60 Double 100 100 100 100 3000, 4000, 5000, 6000

  • February 2007

    13-10

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum IEC RatedAir Circuit Breakers

    Magnum Narrow Frame Drawout Air Circuit Breaker With Cassette

    The KEMA Keur Mark on the Magnum ACB Label Confirms Third-Party Witness and Follow-up Testing

    Magnum Air Circuit Breakers are designed to enable global power distribution solutions in IEC switch-boards and other custom enclosures.

    Magnum IEC Air Circuit Breakers have interruption ratings up to 100 kA at 690 Vac with continuous current ratings up to 6300 amperes.

    Magnum IEC Air Circuit Breaker continuous current frames are 100% rated. No thermal de-rating is required when applying the breaker in the low voltage systems enclosure at ambient temperatures of 40C.

    Magnum IEC Breakers carry the KEMA Keur Mark, which requires periodic follow-up testing, wit-nessed by KEMA, to demonstrate our product performs to its pub-lished nameplate ratings. This differentiates Magnum Air Circuit Breakers from competition, who generally self-tests their product when it is first introduced and is not bound to perform subsequent follow-up third-party testing.

    IEC Test CertificationsMagnum Air Circuit Breakers meet or exceed the applicable IEC standards, including:

    EN/IEC 60947-2. KEMA third-party witness and

    follow-up testing.

    Comprehensive Enclosure SolutionsMagnum Air Circuit Breakers have proven performance in IEC switch-boards and custom enclosures manu-factured by Eaton and Low Voltage Systems Builders (OEMs) to the following standards:

    EN/IEC 60947-1. EN/IEC 60439-1. Eaton manufactured IEC Low Volt-

    age Switchboard solutions include: Eaton MEM M-Form (UK)

    Low Voltage Switchboards Eaton Holec Capitole 40 and

    Capitole 20 (Holland) Low Voltage Switchboards

    Eaton Tabula Low Voltage Switchboard Systems (Global) for Low Voltage Systems Builders

    Eaton Elatis (Germany) Low Voltage Switchboards

    Approvals and MarksMagnum Air Circuit Breakers carry the following approvals and approval marks:

    CE. KEMA Keur mark. ABS (American Bureau of Shipping)

    Type Listed Certificate Number 04-HS422844B-PDA-DUB.

    CCC (Certificate for China Compulsory Product Certification) to GB14048.2-2001, Certificate Numbers: 2005010307139381 2003010307094561 2003010307094558

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-11Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Magnum IEC 60947-2 Rated

    Magnum IEC Low Voltage Air Circuit Breaker Family

    Table 13-3. Magnum IEC 60947-2 Rated Air Circuit Breakers

    Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published breaker Icw Rating.

    Frame Amperes

    Breaker Type

    Frame Type

    rms Symmetrical Current Ratings kA Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In Rating)

    Interrupting at 240 VacIcu = Ics

    Interrupting at 440 VacIcu = Ics

    Interrupting at 690 VacIcu = Ics

    Withstand RatingIcw1-Sec / 3-Sec

    FixedInternalInst. Trip

    800 MWN-408MWN-508MWN-608

    NarrowNarrowNarrow

    40 50 65

    40 50 65

    40 50 65

    40 / 50 / 65 / 40

    200, 250, 300, 400, 630, 800

    MWI-608MWI-808MWI-C08

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 85 / 65 85 / 65

    85

    1000 MWN-410MWN-510MWN-610

    NarrowNarrowNarrow

    40 50 65

    40 50 65

    40 50 65

    40 / 50 / 65 / 40

    200, 250, 300, 400, 630, 800, 1000

    MWI-610MWI-810MWI-C10

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 85 / 65 85 / 65

    85

    1250 MWN-412MWN-512MWN-612

    NarrowNarrowNarrow

    40 50 65

    40 50 65

    40 50 65

    40 / 50 / 65 / 40

    200, 250, 300, 400, 630, 800, 1000, 1250

    MWI-612MWI-812MWI-C12

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 85 / 65 85 / 65

    85

    1600 MWN-516MWN-616

    NarrowNarrow

    50 65

    50 65

    50 65

    50 / 65 / 40

    200, 250, 300, 400, 630, 800, 1000, 1250, 1600

    MWI-616MWI-816MWI-C16

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 85 / 65 85 / 65

    85

    2000 MWN-520MWN-620

    NarrowNarrow

    50 65

    50 65

    50 65

    50 / 30 65 / 40

    200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000

    MWI-620MWI-820MWI-C20

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 50 85 / 65 85 / 65

    85

    2500 MWI-625MWI-825MWI-C25

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 85 / 65 85 / 65

    85

    200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000, 2500

    3200 MWI-632MWI-832MWI-C32

    StandardStandardStandard

    65 85100

    65 85100

    65 85 85

    65 / 50 85 / 65 85 / 65

    85

    200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200

    4000 MWI-64NMWI-84NMWI-C4N

    DoubleDoubleDouble

    65 85100

    65 85100

    65 85100

    65 / 85 / 100 /

    2000, 2500, 3200, 4000

    5000 MWI-85NMWI-C5N

    DoubleDouble

    85100

    85100

    85100

    85 / 100 /

    2500, 3200, 4000, 5000

    6300 MWI-86NMWI-C6N

    DoubleDouble

    85100

    85100

    85100

    85 / 100 /

    3200, 4000, 5000, 6300

  • February 2007

    13-12

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Table 13-4. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers

    Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase Rotation Alarm are included.

    1200 ampere maximum ground fault setting per UL/NEC.

    Test set for secondary injection. Contact Eaton for availability.

    Legend: In = Rating Plug and Sensor Rating.Ir = Long Delay Pickup setting.

    Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+

    Ampere RangeInterrupting Rating at 480 Vrms Sensing

    200 A 6000 A42 through 200 kA Yes

    200 A 6000 A42 through 200 kAYes

    200 A 6000 A42 through 200 kAYes

    200 A 6000 A42 through 200 kAYes

    Protection and CoordinationProtection Ordering Options

    Fixed Rating Plug (In)Overtemperature Trip

    LI, LSI, LSIGYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    Long DelayProtection (L)

    Long Delay Pickup Long Delay Time I2t at 6 x Ir Long Delay Time I4t IEEE Curves

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 Seconds1 5 SecondsYes

    Long Delay Thermal MemoryHigh Load Alarm

    YesNo

    YesNo

    YesNo

    Yes0.5 1.0 x (Ir)

    Short DelayProtection (S)

    Short Delay PickupShort Delay Time I2t at 8 x Ir Short Delay Time FlatShort Delay Time ZSI

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    200 1000% x (Ir) & M1 100 500 ms100 500 msYes

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    Instanta-neousProtection (I)

    Instantaneous PickupMaking Current ReleaseOff Position

    200 1000% x (In) & M1YesLSI & LSIG

    200 1000% x (In) & M1YesYes

    200 1000% x (In) & M1YesYes

    200 1000% x (In) & M1YesYes

    GroundFaultProtection (G)

    Ground Fault AlarmGround Fault PickupGround Fault Delay I2t at .625 x In

    No25 100% x (In)100 500 ms

    Yes25 100% x (In) 100 500 ms

    Yes25 100% x (In)100 500 ms

    Yes24 100% x (In)100 500 ms

    Ground Fault Delay FlatGround Fault ZSIGround Fault Thermal Memory

    100 500 msYesYes

    100 500 msYesYes

    100 500 msYesYes

    100 500 msYesYes

    Disable Ground Fault Protection No No No No

    Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI

    System DiagnosticsCause of Trip LEDsMagnitude of Trip Information

    Yes No

    YesYes

    Yes Yes

    Yes Yes

    Remote Signal ContactsProgrammable Contacts

    NoNo

    Yes No

    Yes No

    YesYes

    System MonitoringDigital DisplayCurrent (% ) Full Scale Sensor

    NoNo

    4-Character LCDYes +/- 2%

    4-Character LCDYes +/- 2%

    24-Character LEDYes +/- 1%

    Voltage (%) L to L Power and Energy (%) Apparent Power kVA and Demand

    NoNoNo

    NoNoNo

    NoNoNo

    Yes +/- 1%Yes +/- 2%Yes

    Reactive Power kvarPower FactorCrest Factor

    NoNoNo

    NoNoNo

    NoNoNo

    YesYesYes

    Power Quality Harmonics% THD

    NoNo

    NoNo

    NoNo

    YesYes

    System CommunicationsTypePower Supply in Breaker

    NoN/A

    NoOptional

    INCOM/PowerNetStandard

    INCOM/PowerNet/TripLinkStandard

    Additional FeaturesTrip Log (3 Events)Electronic Operations Counter

    NoNo

    NoNo

    NoNo

    YesYes

    Testing Method Waveform Capture

    Test SetNo

    Test SetNo

    Test SetNo

    Integral and Test SetYes

    ARMs (Arc Flash Reduction Mode)Breaker Health MonitorProgrammable Relay Functions

    NoNoNo

    NoNoNo

    YesNoNo

    Yes YesYes

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-13Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Table 13-5. Digitrip Trip Units for Magnum IEC Rated Air Circuit Breakers

    Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase Rotation Alarm are included.

    Test set for secondary injection. Contact Eaton for availability. Legend: In = Rating plug rating.

    Ir = LDPU setting.

    Note: i Trip units are only used on IEC breakers with earth fault.

    Trip Unit Type Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+

    Ampere RangeInterrupting Rating at 690 Vrms Sensing

    200 A 6300 A40 100 kAYes

    200 A 6300 A40 100 kAYes

    200 A 6300 A40 100 kAYes

    200 A 6300 A40 100 kAYes

    Protection and CoordinationProtection Ordering Options

    Fixed Rate Plug (In)Overtemperature Trip

    LI, LSI, LSIGYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    LongDelayProtection(L)

    Long Delay SettingLong Delay Time I2t at 6 x IrLong Delay Time I4tIEC Type A, B, C Curves

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 SecondsNoNo

    0.4 1.0 x (In)2 24 Seconds1 5 SecondsYes

    Long Delay Thermal MemoryHigh Load Alarm

    YesNo

    YesNo

    YesNo

    Yes0.7 1.0 x Ir

    ShortDelayProtection(S)

    Short Delay PickupShort Delay Time I2t at 8 x IrShort Delay Time FlatShort Delay Time ZSI

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    200 1000% x (Ir) & M1100 500 ms100 500 msYes

    150 1000% x (Ir) & M1100 500 ms100 500 msYes

    Instanta-neousProtection(I)

    Instantaneous PickupMaking Current ReleaseOff Position

    200 1000% x (In) & M1Yes Yes

    200 1000% x (In) & M1Yes Yes

    200 1000% x (In) & M1Yes Yes

    200 1000% x (In) & M1Yes Yes

    EarthFaultProtection(G)

    Earth Fault AlarmEarth Fault PickupEarth Fault Delay I2t at .625 x In

    No25 100% x (In)100 500 ms

    Yes25 100% x (In)100 500 ms

    Yes25 100% x (In)100 500 ms

    Yes24 100% x (In)100 500 ms

    Earth Fault Delay FlatEarth Fault ZSIEarth Fault Memory

    100 500 msYes Yes

    100 500 msYes Yes

    100 500 msYes Yes

    100 500 msYes Yes

    Disable Ground Fault Protection No No No Yes

    Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI

    System DiagnosticsCause of Trip LEDsMagnitude of Trip Information

    YesNo

    YesNo

    YesNo

    YesYes

    Remote Signal ContactsProgrammable Contacts

    NoNo

    YesNo

    YesNo

    Yes2

    System MonitoringDigital DisplayCurrent (%) Full Scale Sensor

    NoNo

    4 Character LCD Yes +/- 2%

    4 Character LCD Yes +/- 2%

    24 Character LED Yes +/- 1%

    Voltage (%) L to LPower and Energy (%)Apparent Power kVA and Demand

    NoNoNo

    NoNoNo

    NoNoNo

    Yes +/- 1%Yes +/- 2%Yes

    Reactive Power kvarPower FactorCrest Factor

    NoNoNo

    NoNoNo

    NoNoNo

    YesYesYes

    Power Quality Harmonics% THD

    NoNo

    NoNo

    NoNo

    YesYes

    System CommunicationsTypePower Supply in Breaker

    NoN/A

    NoOptional

    INCOM/PowerNetStandard

    INCOM/PowerNet/TripLinkStandard

    Additional FeaturesTrip Log (3 Events)Electronic Operations Counter

    NoNo

    NoNo

    NoNo

    YesYes

    Testing Method Waveform Capture

    Test SetNo

    Test SetNo

    Test SetNo

    Integral and Test SetYes

    ARMs (Arc Flash Reduction Mode)Breaker Health MonitorProgrammable Relay Functions

    NoNoNo

    NoNoNo

    YesNoNo

    Yes YesYes

  • February 2007

    13-14

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Breaker-Mounted Options and Accessories

    Arc Chutes are Easily Removable for Inspection and Access to Breaker Contacts

    Heel-Toe Contact Design Provides Demonstrated Long Life and Includes Wear Indicator for Visual Inspection

    Magnum breakers are available with a comprehensive array of factory-installed breaker options to enable configured-to-order solutions for spec-ified customer requirements. Field option kits are available to provide easy service, modification and customization of the breaker at the point of use.

    Shunt Trip device (ST). Provides for remote electrically controlled breaker opening when energized by a rated voltage input.

    Spring Charge Motor (MOT).Charges the breaker closing springs automatically, facilitating remote or local closing. The motor assembly includes its own cut-off switch that changes state at the end of the charging cycle. This contact can be wired out for external indication.

    Spring Release device (SR). Provides for remote electrically controlled breaker closing when its coils are energized by a rated voltage input.

    Undervoltage Release (UVR). Trips the breaker when an existing voltage signal is lost or falls below an established threshold.

    Auxiliary Switch. Up to 6a/6b auxiliary individual dedicated con-tacts are available for customer use to indicate if the breaker is in the OPEN or CLOSE position.

    Mechanical Trip Indicator Flag. The red trip indicator flag pops out to provide local visual indication when the Digitrip RMS trip unit acts to trip the breaker on an overcurrent condition.

    Bell Alarm/Overcurrent Trip Switch (OTS). Provides 2 Form C (changeover) contacts that change state when the Digitrip RMS trip unit acts to trip the breaker on an over-current condition. The contacts are available for external indication or customer use and are manually reset by the Mechanical Trip Indicator.

    Padlockable Pushbutton Cover.Permits padlocking hinged cover plates to block access to the PUSH ON and PUSH OFF buttons on the breaker faceplate.

    Mechanical Operations Counter. Records mechanical operations of the breaker over its installed life.

    Key Off Lock Provisions. Enables mounting of a single cylinder Kirk, Castell, or Ronis Key Lock to lock the breaker in the OPEN position.

    Latch Check Switch. Provides 1 Form C (changeover contact) that changes state when the breaker is ready to close. Can be wired to the Spring Release Device for fast transfer applications or wired for external ready-to-close indication.

    Shunt Trip, Spring Release and Undervoltage Release Device Installed on Accessory Deck

    Auxiliary Switches Come in Modular 2a/2b Contact Stages Providing up to 6a/6b Dedicated Contacts

    Mechanical Trip Indicator With Bell Alarm (OTS) Switches Mounted

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-15Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Table 13-6. Magnum Breaker Control Device Application Guide Vdc

    Table 13-7. Magnum Breaker Control Device Application Guide Vac

    Breaker Control Device Nominal Voltage

    24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc

    Shunt Trip (ST) Operational Voltage Range Power Consumption (Inrush) Opening Time

    Trip Circuit70 to 110%(Required for 35 ms)Seconds

    17 26 Vdc250 Watts35 ms

    34 53 Vdc250 Watts35 ms

    77 138 Vdc450 Watts35 ms

    154 275 Vdc450 Watts35 ms

    Spring Release (SR) Operational Voltage RangePower Consumption (Inrush) Closing Time

    Close Circuit70 to 110%(Required for 200 ms)Seconds

    17 26 Vdc250 Watts40 ms

    34 53 Vdc250 Watts40 ms

    77 138 Vdc450 Watts40 ms

    154 275 Vdc450 Watts40 ms

    Spring Charge Motor (MOT)Operational Voltage RangeAmps (Running)Amps (Inrush)Power ConsumptionCharging Time

    85 to 110% VoltageRunning% of Running

    Seconds

    20 26 Vdc12.0 Amps300%300 Watts5 Sec

    41 53 Vdc5.0 Amps500%250 Watts5 Sec

    94 138 Vdc2.0 Amps600%250 Watts5 Sec

    187 225 Vdc1.0 Amp600%250 Watts5 Sec

    Undervoltage Release (UVR)Operational Voltage RangeDrop-out Voltage RangePower Consumption (Inrush)Power Consumption (Continuous)Opening Time

    85 to 110% Voltage30 to 60% VoltageRequired for 200 msRequired for 400 msSeconds

    20 26 Vdc 7 14 Vdc250 Watts18 Watts70 ms

    27 35 Vdc10 19 Vdc275 Watts15 Watts70 ms

    41 53 Vdc14 29 Vdc275 Watts18 Watts70 ms

    94 138 Vdc33 75 Vdc450 Watts10 Watts70 ms

    187 275 Vdc 66 150 Vdc450 Watts10 Watts70 ms

    Auxiliary SwitchesMinimum LoadContact Rating Inductive Load 0.5 Amps

    0.5 Amps 0.5 Amps 0.25 Amps

    Breaker Control Device Nominal Voltage

    120 Vac 240 Vac 415 Vac 480 Vac 600 Vac

    Shunt Trip (ST) Operational Voltage Range Power Consumption (Inrush) Opening Time

    Trip Circuit70 to 110%(Required for 35 ms)Seconds

    77 140 Vac450 VA35 ms

    146 264 Vac450 VA35 ms

    Spring Release (SR) Operational Voltage RangePower Consumption (Inrush) Closing Time

    Close Circuit70 to 110%(Required for 200 ms)Seconds

    77 140 Vac450 VA40 ms

    146 264 Vac450 VA40 ms

    Spring Charge Motor (MOT)Operational Voltage RangeAmps (Running)Amps (Inrush)Power ConsumptionCharging Time

    85 to 110% VoltageRunning% of Running

    Seconds

    93 140 Vdc2.0 Amps600%250 VA5 Sec

    177 264 Vdc1.0 Amp600%250 VA5 Sec

    Undervoltage Release (UVR)Operational Voltage RangeDrop-out Voltage RangePower Consumption (Inrush)Power Consumption (Continuous)Opening Time

    85 to 110% Voltage30 to 60% VoltageRequired for 200msRequired for 400 msSeconds

    94 140 Vac33 76 Vac450 VA10 VA70 ms

    177 264 Vac62 144 Vac400 VA10 VA70 ms

    323 457 Vac114 249 Vac480 VA10 VA70 ms

    408 528 Vac144 288 Vac400 VA10 VA70 ms

    510 660 Vac180 360 Vac400 VA10 VA70 ms

    Auxiliary SwitchesMinimum LoadContact Rating Inductive Load 10 Amps 10 Amps

  • February 2007

    13-16

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersLow Voltage Power Circuit Breakers

    Figure 13-1. Typical Magnum Breaker Control Circuit Diagram

    Control Power

    Close

    B12

    Lever in Door Switch (Draw- out Only)

    L.S. b.

    a.

    a.OTS 1*OTS 2*

    B15 B26

    MDSEOBKR

    B10 B24 A7

    B13 B14 B27 B11 B25 A8

    A1 A2 A3

    A4 A5 A6

    Open OpenG R

    SR

    MOT

    UVRST

    Legend:LS Limit Switch for Closing SpringMOT Motor for Spring ChargingST Shunt TripSR Spring ReleaseUVR Undervoltage ReleaseOTS Overcurrent Trip Switch

    Description of Operation:1 Motor is energized through

    LS contact.2 Motor runs and charges closing

    spring.3 When closing spring is fully charged,

    LS contacts change state.4 Close contacts energize SR coil.5 When breaker closes, b opens.6 LS contacts change state and motor

    recharges closing springs.

    * Contacts shown for breaker open (not fullycharged), not tripped.

    Dotted line denotes Magnum Breaker.

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-17Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    Medium Voltage Breakers

    Type VCP-W/VCP-T Medium Voltage Vacuum Circuit Breaker

    Product DescriptionBreakers and structures for switchgear assemblies:

    ANSI 4.76 kV, 8.25 kV, 15 kV, 27 kV and 38 kV: 250 to 1500 MVA IEC 3.6 kV thru 17.5 kV 16 kA to 63 kA

    Metal-clad, compartmented design. Power modules. Mini modules. Breaker compartment kits.

    Application DescriptionEatons Cutler-Hammer Type VCP-W, VCP-T, T-VAC and W-VAC vacuum breakers provide centralized control and protection of medium voltage power equipment and circuits in industrial, commercial and utility installations involving generators, motors, feeder circuits, and transmis-sion and distribution lines.

    VCP-W Standard Features Eatons maintenance-free Cutler-

    Hammer vacuum interrupters with visual contact erosion indicator.

    Patented non-sliding/non-rolling V-flex current transfer system.

    Glass polyester insulation. Cycloaliphatic Epoxy Insulation

    (optional with Type VCPW-SE breakers) for 27 kV and 38 kV breakers.

    Front-accessible operating mechanism.

    Electrically operated trip-free, spring stored energy mechanism.

    Interlocks which prevent moving a closed circuit breaker into or out of the connected position.

    Closing springs automatically discharge before moving the circuit breaker into or out of the enclosure.

    Provisions for manual charging of closing springs.

    Manual close and trip pushbuttons. Operations counter. Closing spring charged/discharged

    indicator. Circuit breaker Open/Closed

    indicator. Auxiliary switch with 2A/3B for dc

    and 1A/3B for ac spare contacts. Spring charging motor, close coil,

    trip coil, latch check switch, and anti-pump relay.

    VCP-T Standard Features Grounded steel barrier between

    mechanism and primary conductors. Spring loaded, silver-plated primary

    disconnects (drawout breaker). Silver-plated primary connections

    (fixed circuit breaker). Manual charging of closing springs

    (includes shunt trip). Integral spring charging handle. Auxiliary switch (5a and 5b contacts). Mechanical operations counter. 24, 48, 125 and 250 Vdc, 120 and

    240 Vac control. Shunt trip. ON and OFF pushbuttons. Integral lifting hooks. Through or behind door operation. Identified/dedicated secondaries. Secondary umbilical cord

    (drawout circuit breaker). Secondary disconnect block

    (fixed circuit breaker). Two-step stored energy mechanism. O 0.3s CO 15s CO. Anti-pump. Trip free. Latch check switch. Visible contact erosion indicator. Visible contact wipe indicator. Disconnect, Test and Connect

    (drawout circuit breaker). Integral levering mechanism

    (drawout circuit breaker). Field installable accessories.

    Standards and Certifications Designed, tested and certified

    in accordance with ANSI and IEC standards.

    Applicable ANSI standards C37.04-1979 or 1999, C37.09-1979 or 1999, C37.06-2000 and C37.013.

    Internal arc resistance tested to IEC 298, Appendix AA, 25 kAfor 1 second.

    Drawout circuit breaker fully qualified to IEC 56 by testing inside the IEC 298 switchgear cubicle.

  • February 2007

    13-18

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    ANSI StandardsTable 13-8. ANSI Standard Ratings VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis

    Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings) and C37.09-1999. See Consulting Application Guide for further information.

    Identification Rated Values Weight

    CircuitBreakerType

    Nom

    inal

    Vol

    tage

    Cla

    ss

    Nom

    inal

    3-P

    hase

    MV

    A C

    lass

    Voltage Insulation Level

    Current

    Inte

    rrup

    ting

    Tim

    e

    Perm

    issi

    ble

    Trip

    ping

    Del

    ay

    Max

    imum

    Vol

    tage

    D

    ivid

    ed b

    y K

    Current Values

    Max

    imum

    Vol

    tage

    Vol

    tage

    Ran

    ge F

    acto

    r Withstand Test Voltage

    Contin-uous Current at 60 Hz

    Short Circuit Current (at Rated Max. kV)

    MaximumSymmetricalInterruptingCapability

    Short TimeCurrent

    ClosingandLatchingCapability

    Closing andLatchingMomentaryCapability

    Pow

    er F

    requ

    ency

    (1

    Min

    .)

    Impu

    lse

    E K I Y E/K K x 1

    kV MVA kV rms

    kV rms

    kV Peak

    Amperes kA rms

    Cycles Seconds kV rms

    kA rms kA Peak kA rms Total Lbs. (kg)

    Sta

    ndar

    d C

    ircu

    it B

    reak

    ers

    50 VCP-WND250 4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 97 58 345 (157)

    50 VCP-W250 4.16 250 4.76 1.24 19 60 120020003000

    29 5 2 3.85 36 97 58 350 (159)410 (186)525 (238)

    50 VCP-W350 4.16 350 4.76 1.19 19 60 120020003000

    41 5 2 4.0 49 132 78 460 (209)490 (223)525 (238)

    50 VCP-W500(63 kA)

    4.16 4.76 1.00 19 60 120020003000

    63 5 2 4.76 63 170 101 525 (238)530 (241)550 (250)

    75 VCP-W500 7.2 500 8.25 1.25 36 95 120020003000

    33 5 2 6.6 41 111 66 375 (170)410 (186)525 (238)

    150 VCP-W500 13.8 500 15 1.30 36 95 120020003000

    18 5 2 11.5 23 62 97

    37 58

    350 (159)410 (186)525 (238)

    150 VCP-W750 13.8 750 15 1.30 36 95 120020003000

    28 5 2 11.5 36 97130

    58 77

    350 (159)410 (186)525 (238)

    150 VCP-W1000 13.8 1000 15 1.30 36 95 120020003000

    37 5 2 11.5 48 130 77 460 (209)490 (223)525 (238)

    150 VCP-W1500(63 kA)

    13.8 15 1.00 36 95 120020003000

    63 5 2 15.0 63 170 101 525 (238)530 (241)550 (250)

    Extr

    a C

    apab

    ility

    Bre

    aker

    s

    50 VCP-W25C 4.16 5.95 1.00 24 75 120020003000

    25 3

    Test

    ed fo

    r 3

    Sec

    onds

    2 5.95 25 97 58 350 (159)410 (186)525 (238)

    50 VCP-W40C 4.16 5.95 1.00 24 75 120020003000

    40 3 2 5.95 40 139 83 460 (209)490 (223)525 (238)

    50 VCP-W50C 4.16 5.95 1.00 24 75 120020003000

    50 3 2 5.95 50 139 83 525 (238)530 (241)550 (250)

    50 VCP-W63C 4.16 5.95 1.00 24 75 120020003000

    63 3 2 5.95 63 175 104 350 (159)410 (186)525 (238)

    75 VCP-W50C 7.2 10.3 1.00 42 95 120020003000

    50 3 2 10.3 50 139 83 460 (209)490 (223)525 (238)

    150 VCP-W25C 13.8 17.5 1.00 42 95 120020003000

    25 3 2 17.5 25 97 58 350 (159)410 (186)525 (238)

    150 VCP-W40C 13.8 17.5 1.00 42 95 120020003000

    40 3 2 17.5 40 139 83 350 (159)410 (186)525 (238)

    150 VCP-W50C 13.8 17.5 1.00 42 95 120020003000

    50 3 2 17.5 50 139 83 460 (209)490 (223)525 (238)

    150 VCP-W63C 13.8 15.0 1.00 42 95 120020003000

    63 3 2 15.0 63 175 104 525 (238)530 (241)550 (250)

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-19Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    Table 13-8. ANSI Standards VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis (Continued)

    Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings), and C37.09-1999. See Consulting Application Guide for further information.

    Identification Rated Values Weight

    CircuitBreakerType

    Nom

    inal

    Vol

    tage

    Cla

    ss

    Nom

    inal

    3-P

    hase

    MV

    A C

    lass

    Voltage Insulation Level

    Current

    Inte

    rrup

    ting

    Tim

    e

    Perm

    issi

    ble

    Trip

    ping

    Del

    ay

    Max

    imum

    Vol

    tage

    Div

    ided

    by

    K

    Current Values

    Max

    imum

    Vol

    tage

    Vol

    tage

    Ran

    ge F

    acto

    r Withstand Test Voltage

    Contin-uous Current at 60 Hz

    Short Circuit Current (at Rated Max. kV)

    MaximumSymmetricalInterruptingCapability

    Short TimeCurrent

    ClosingandLatchingCapability

    Closing andLatchingMomentaryCapability

    Pow

    er F

    requ

    ency

    (1

    Min

    .)

    Impu

    lse

    E K I Y E/K K x 1

    kV MVA kV rms

    kV rms

    kV Peak

    Amperes kA rms

    Cycles Seconds kV rms

    kA rms kA Peak kA rms Total Lbs. (kg)

    Gen

    erat

    or B

    reak

    ers

    (to

    AN

    SI C

    37.0

    13) 50 VCP-WG50 4.16 4.76 1.00 19 60 1200

    20003000

    50 3

    Test

    ed fo

    r 3

    Sec

    onds

    1 4.76 50 137 82 525 (238)530 (241)550 (250

    50 VCP-WG63 4.16 4.76 1.00 19 60 120020003000

    63 3 1 4.76 63 173 103 525 (238)530 (241)550 (250

    150 VCP-WG50 13.8 15.0 1.00 36 95 120020003000

    50 3 1 15.0 50 137 82 525 (238)530 (241)550 (250)

    150 VCP-WG63 13.8 15.0 1.00 36 95 120020003000

    63 3 1 15.0 63 173 103 525 (238)530 (241)550 (250)

  • February 2007

    13-20

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    Table 13-9. VCP-W Vacuum Breaker Types rated on Symmetrical Current Rating Basis

    CESI tested to applicable ANSI standards C37.04, C37.09 and C37.06. Consult Eaton for CESI copies of test reports on file. Operating duty cycle CO-15 seconds-CO. Operating time values: Opening 33 55 ms, closing 50 60 ms and reclosing 18 cycles (300 ms).

    Tested at 28.5 kV. K = 1.0, therefore E = E/K and I = KI. Also maximum interrupting rating and short-time current rating. Duration of short-time current = 3 seconds, except as noted in Optional interrupting time of 50 ms (3 cycles) is available.

    Identification Rated Values Weight

    CircuitBreakerType

    No

    min

    alV

    olt

    age

    Cla

    ss

    No

    min

    al 3

    -Ph

    ase

    MV

    A C

    lass

    Voltage InsulationLevel

    Current

    Inte

    rru

    pti

    ng

    Tim

    e

    Max

    imu

    m P

    erm

    issi

    ble

    Trip

    pin

    g D

    elay

    Y

    TransientRecoveryVoltage

    CurrentValues

    Max

    imu

    mV

    olt

    age

    E Vo

    ltag

    e R

    ang

    eFa

    cto

    r

    K

    WithstandTest Voltage

    Co

    nti

    nu

    ou

    s C

    urr

    ent

    at 6

    0 H

    z

    Sh

    ort

    Cir

    cuit

    Cu

    rren

    t(a

    t R

    ated

    max

    . kV

    ) I

    E2 T2

    Clo

    sin

    g a

    nd

    La

    tch

    ing

    Cap

    abili

    ty(2

    .6 K

    Tim

    esR

    ated

    Sh

    ort

    Cir

    cuit

    Cu

    rren

    t)

    Cap

    acit

    or

    Sw

    itch

    ing

    Cab

    le C

    har

    gin

    g

    Po

    wer

    Freq

    uen

    cy(1

    min

    .)

    Imp

    uls

    e

    kV MVA kV rms kV rms kV Peak Amperes kA rms ms (Cy) Seconds kV Peak s kA Peak Amperes lbs.

    270 VCP-W750 27 750 27 1.0 60 125 60012002000

    16 83 (5) 2 51 105 43 31.5 460480500

    270 VCP-W1000 27 1000 27 1.0 60 125 60012002000

    22 83 (5) 2 51 105 60 31.5 460480500

    270 VCP-W1250 27 1250 27 1.0 60 125 60012002000

    25 83 (5) 2 51 105 68 31.5 460480500

    270 VCP-W1600 27 1600 27 1.0 60 125 12002000

    25 83 (5) 2 51 105 85 31.5 545560

    270 VCP-W2000 27 2000 27 1.0 60 125 12002000

    40 83 (5) 2 51 105 106 31.5 545600

    270 VCP-W25C 27 27 1.0 60 125 12001600

    25 50 (3) 2.5 50 50 85 31.5 545560

    270 VCP-W32C 27 27 1.0 60 125 12001600

    31.5 50 (3) 1.6 50 50 100 31.5 545560

    270 VCP-W40C 27 27 1.0 60 125 12001600

    40 50 (3) 1.0 50 50 112 31.5 545560

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-21Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    IEC StandardsTable 13-10. IEC Standards VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis

    IEC Standards 60056 and 60694 apply.

    Identification Rated Values Weight

    Circuit BreakerType

    Voltage Insulation Level NormalCurrent

    Short CircuitBreakingCurrent and3-SecondShort TimeCurrent

    ShortCircuitMakingCurrent

    CableChargingBreakingCurrent

    PowerFrequency

    ImpulseWithstand

    kV rms kV rms Peak kV Peak Amperes kA rms kV Peak Amperes Lbs. (kg)

    36 VCP-WND25 3.6 10 40 6301250

    25 65 10 350 (159)

    36 VCP-WND32 3.6 10 40 6301250

    31.5 82 10 350 (159)

    72 VCP-WND25 7.2 20 60 6301250

    25 65 10 350 (159)

    72 VCP-WND32 7.2 20 60 6301250

    31.5 82 10 350 (159)

    36 VCP-W25 3.6 10 40 63012502000

    25 65 10 414 (188) 430 (195) 496 (225)

    36 VCP-W32 3.6 10 40 12502000

    31.5 82 10 414 (188) 496 (225)

    36 VCP-W40 3.6 10 40 12502000

    40 104 10 496 (225) 550 (250)

    72 VCP-W25 7.2 20 60 63012502000

    25 65 10 414 (188) 414 (188) 496 (225)

    72 VCP-W32 7.2 20 60 12502000

    31.5 82 10 414 (188) 430 (195)

    72 VCP-W40 7.2 20 60 12502000

    40 104 10 430 (195) 496 (225)

    120 VCP-W25 12.0 28 75 63012502000

    25 65 25 430 (195) 496 (225) 496 (225)

    120 VCP-W32 12.0 28 75 12502000

    31.5 82 25 430 (195) 496 (225)

    120 VCP-W40 12.0 28 75 12502000

    40 104 25 496 (225) 550 (250)

    175 VCP-W25 17.5 38 95 63012502000

    25 65 430 (195) 496 (225) 496 (225)

    175 VCP-W32 17.5 38 95 12502000

    31.5 82 430 (195) 496 (225)

    175 VCP-W40 17.5 38 95 12502000

    40 104 496 (225) 550 (250)

    175 VCP-W50 17.5 38 95 125020003150

    50 130 1013 (460)1079 (490)1156 (525)

  • February 2007

    13-22

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    Type VCP-W Vacuum Circuit Breaker RatingsTable 13-11. Type VCP-W Ratings on Symmetrical Current Rating Basis

    KEMA tested to applicable ANSI standards C37.04-1979, C37.09-1979 and C37.06-1979 (operating duty sequence CO - 15s - CO). Typical operating time values: operating 45 ms, closing 75 ms and reclosing 300 ms (18 cycles).

    The standard breaker is not rated for capacitor switching. If you require capacitor switching, please refer to the C breakers. K = 1.0, therefore E = E/K and I = KI. Refer to the Consulting Application Guide for more information. The ANSI C37.06 standard requires 150 kV BIL. If higher BIL levels are required, please refer to the C breakers. For force air cooled fixed breaker applications, consult Eaton. If you require 50 ms (3 cycle) interrupting time, please refer to the C breakers. No-load operations. At 23 kV rms (rated maximum voltage/K). Rated maximum symmetrical interrupting capability = 35kA rms (K x 1).

    CO 15s CO. Rated and tested also for rapid reclosing capability O - 0.3s - CO. Not rated for rapid reclosing.

    Identification Rated ValuesCircuitBreakerType

    Voltage Insulation Level

    Current

    Ope

    rati

    ng D

    uty

    (Dut

    y C

    ycle

    )R

    ated

    Rec

    losi

    ngFa

    ctor

    (R)

    Interr-uptingTime

    Max

    imum

    Per

    mis

    sibl

    eTr

    ippi

    ng D

    elay

    Tran

    sien

    t Rec

    over

    yV

    olta

    ge (R

    RR

    V)

    Mec

    hani

    cal E

    ndur

    ance

    Nom

    inal

    Vol

    tage

    Cla

    ssM

    axim

    umV

    olta

    ge V

    Vol

    tage

    Ran

    ge F

    acto

    r K

    V/K

    Withstand Test

    Con

    tinu

    ous

    Cur

    rent

    at 6

    0 H

    z

    Short Circuit Current

    Pow

    er F

    requ

    ency

    (1 M

    inut

    e)

    Ligh

    tnin

    g Im

    puls

    e1.

    2x50

    Sym

    . Int

    erru

    ptin

    g at

    V(Is

    c)%

    dc

    Com

    pone

    nt (I

    dc)

    Asy

    m. F

    acto

    r S (R

    ef.)

    Asy

    m. I

    nter

    rupt

    ing

    (It)

    Max

    . Asy

    m. I

    nter

    rupt

    ing

    at V

    /K (K

    xlsc

    )

    Max

    . Asy

    m. I

    nter

    rupt

    ing

    at V

    /K (S

    xKxl

    sc)

    Clo

    sing

    and

    Lat

    chin

    gC

    apab

    ility

    Mom

    enta

    ry C

    urre

    ntW

    iths

    tand

    Cap

    abili

    ty

    Sho

    rt T

    ime

    Cur

    rent

    Dur

    atio

    n of

    Sho

    rt T

    ime

    Cur

    rent

    kVrms

    kVrms

    kVrms

    kVrms

    kVPeak

    Ampsrms

    kArms

    % kArmsTotal

    kArms

    kArmsTotal

    kAPeak

    kArmsTotal

    kArms

    s %

    rms

    Cyc

    .

    Sec. kV/s

    380 VCP-W 6and380 VCP-WR 16

    34.5 38 1 38 80 170 600120016002000

    16 47 1.2 19.2 16 19.3 43 26 16 3 100 83 5 2 0.6

    2000

    380 VCP-W 25and380 VCP-WR 25

    34.5 38 1 38 80 170 600120016002000

    25 47 1.2 30.0 25 30.0 68 40 25 3 100 83 5 2 0.6

    2000

    380 VCP-W 32and380 VCP-WR 32

    34.5 38 1 38 80 170 6001200160020003000FC

    31.5 47 1.2 37.8 31.5 37.8 85 50 31.5 3 100 83 5 2 0.6

    2000

    2500

    380 VCP-W 21and380 VCP-WR 21

    34.5 38 1.65

    23

    80 170 120020003000FC

    21 47 1.2 39.5 35

    42.0 95 56 35 3 100 83 5 2 0.6

    2000

    2500

    380 VCP-W 40and380 VCP-WR 40

    34.5 38 1 38 80 170 120020003000FC2500

    40 47 1.2 48.0 40 48.0 107 63 40 3 100 83 5 2 0.6

    2000

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-23Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    T-VAC and T-VACR Vacuum Breaker RatingsTable 13-12. VCP-T and VCP-TR Ratings (ANSI C37.04 and C37.09)

    Use 15 kV breaker and cassette when 95 kV impulse withstand required. 1600 A VCP-T breaker available. Also 2 second short time current rating.

    Table 13-13. T-VAC and T-VACR Ratings (Certified to IEC62271-100)

    Use 17.5 kV breaker and cassette when 95 kV impulse withstand required. 1600 A T-VAC breaker available. Also 3 second short time current rating.

    Identification Rated Values

    CircuitBreakerType

    Vo

    ltag

    eC

    lass

    Insulation Level

    Co

    nti

    nu

    ou

    sC

    urr

    ent

    Sh

    ort

    Cir

    cuit

    B

    reak

    ing

    Cu

    rren

    t

    Sh

    ort

    Cir

    cuit

    Mak

    ing

    Cu

    rren

    t

    Mec

    han

    ical

    En

    du

    ran

    ceC

    0

    Po

    wer

    Freq

    uen

    cy

    Imp

    uls

    eW

    ith

    stan

    dkVrms

    kVrms

    kVPeak

    Amp-eres

    kArms

    kAPeak

    Oper-ations

    50 VCP-T16and50 VCP-TR16

    4.76 19 60 600 80012001600

    16 42 20,00020,00010,00010,000

    50 VCP-T20and50 VCP-TR20

    4.6 19 60 600 80012001600

    16 52 10,00010,00010,00010,000

    50 VCP-T25and50 VCP-TR25

    4.76 19 60 600 80012001600

    25 65 10,00010,00010,00010,000

    75 VCP-T16and75 VCP-TR16

    8.25 20 60 600 80012001600

    16 42 20,00020,00010,00010,000

    75 VCP-T20and 75 VCP-TR20

    8.25 20 60 600 80012001600

    20 52 10,00010,00010,00010,000

    75 VCP-T25and75 VCP-TR25

    8.25 20 60 600 80012001600

    25 65 10,00010,00010,00010,000

    150 VCP-T16and150 VCP-TR16

    15 36 95 600 80012001600

    16 42 10,00010,00010,00010,000

    150 VCP-T20and150 VCP-TR20

    15 36 95 600 80012001600

    20 52 10,00010,00010,00010,000

    150 VCP-T25and150 VCP-TR25

    15 36 95 600 80012001600

    25 65 10,00010,00010,00010,000

    Identification Rated Values

    CircuitBreakerType

    Vo

    ltag

    eC

    lass

    Insulation Level

    No

    rmal

    Cu

    rren

    t (In

    )

    Sh

    ort

    Cir

    cuit

    B

    reak

    ing

    Cu

    rren

    t

    Sh

    ort

    Cir

    cuit

    Mak

    ing

    Cu

    rren

    t(Is

    c)

    Mec

    han

    ical

    En

    du

    ran

    ceC

    0

    Po

    wer

    Fre

    qu

    ency

    Wit

    hst

    and

    Vo

    ltag

    e

    Lig

    htn

    ing

    Imp

    uls

    e(U

    w)

    Wit

    hst

    and

    Vo

    ltag

    e

    kVrms

    kVrms

    kVPeak

    Amp-eres

    kArms

    kAPeak

    Oper-ations

    72 T-VAC16and72 T-VACR16

    7.2 20 60 630 80012501600

    16 40 20,00020,00010,00010,000

    72 T-VAC20and72 T-VACR20

    7.2 20 60 630 80012501600

    20 50 10,00010,00010,00010,000

    72 T-VAC25and72 T-VACR25

    7.2 20 60 630 80012501600

    25 63 10,00010,00010,00010,000

    120 T-VAC16and120 T-VACR16

    12 28 75 630 80012501600

    16 40 20,00020,00010,00010,000

    120 T-VAC20and120 T-VACR20

    12 28 75 630 80012501600

    20 50 10,00010,00010,00010,000

    120 T-VAC25and120 T-VAC25

    12 28 75 630 80012501600

    25 63 10,00010,00010,00010,000

    175 T-VAC16and175 T-VACR16

    17.5 38 95 630 80012501600

    16 40 10,00010,00010,00010,000

    175 T-VAC20and175 T-VACR20

    17.5 38 95 630 80012501600

    20 50 10,00010,00010,00010,000

    175 T-VAC25and175 T-VACR25

    17.5 38 95 630 80012501600

    25 63 10,00010,00010,00010,000

  • February 2007

    13-24

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    Technical Data and Specifications

    Mini Module Type VCP-W Circuit Breaker Shown from Rear

    VCP-W Circuit Breaker with DeadfrontPanel Removed

    5/15 kV VCPW-ND and VCP-W Power Modules Dimensions in Inches (mm)

    Figure 13-2. Power Module, 5/15 kV VCPW-ND 26.00 (660) Wide, VCP-W 36.00 (914) Wide VCPW-ND Dimensions of Breaker Travel 15.00 (381.0 mm).

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-25Power Breakers, Contactors & Fuses

    13

    Power Circuit BreakersMedium Voltage Circuit Breakers

    5/15 kV VCPW-ND and VCP-W Mini Modules Dimensions in Inches (mm)

    Figure 13-3. 5 kV VCPW-ND Mini Module 25.88 (657) Wide Current transformers not supplied.

    5/15 kV VCP-W Mini Module Dimensions in Inches (mm)

    Figure 13-4. 5/15 kV VCP-W Mini-Module 35.88 (911) Wide Current transformers not supplied.

  • February 2007

    13-26

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power ContactorsProduct Description

    SL MV Power Contactor Size 160 400 Amperes

    SL Medium Voltage Contactor

    Product Description A single family of contactors for any

    medium voltage control application. Voltage range of 2200 to 7200 volts.

    Ampere ratings from 160 through 400 amperes with Induction Motor Horsepower ranges from 600 to 5500 hp.

    Three different altitude versions. Leading-edge vacuum technology. Fully complies with global

    standards. Third-party qualified by UL,

    CSA, KEMA. Long life 300,000 electrical

    and over 2 million mechanical. Mounting flexibility panel or

    pedestal mounting provisions are standard. Unit can be mounted in horizontal or vertical position.

    Field-selectable settings for coil voltage, ac/dc, and coil dropout time.

    Field kits available for auxiliary contacts and mechanical latch. Accessories are common for all sizes.

    Special ordering allows unit to be factory pre-set to customer specification, including field kit installation.

    Highest quality available all contactors manufactured within state-of-the-art ISO-Certified facilities. 100% made in America.

    Application DescriptionEatons Cutler-Hammer SL Medium Voltage Contactor starting applications: Squirrel-cage induction motors. Synchronous motors. Wound-rotor.

    Fully applicable to: Full voltage starting. Reduced voltage starting.

    The perfect choice for harsh duty applications: Mining. Pulp and paper. HVAC. Petrochemical. Automotive. Many others.

    Features, Benefits and Functions The SL Contactor Ratings Voltages of 2200 7200 volts. Amperages from 160 400 amperes. Interrupting ratings as high as

    8500 amperes.

    Control Voltages (Field Adjustable) 110, 220 Vac 50 Hz. 120, 240 Vac 60 Hz. 125 Vdc.

    Drop-out Time (Field Adjustable) 30 ms 50 ms 130 ms 250 ms 330 ms

    Global Acceptability NEMA ANSI IEC

    Third-Party Verification UL CSA KEMA

    Easy-to-Install Option Kits (Field Addition) Up to 6 extra auxiliary contacts. Mechanical latch many coil

    voltages.

    Long Life Guarantees High Quality 300,000 electrical operations. 2.5 million mechanical operations.

    Standards and Certifications

    Design and Test Standards UL 347, File No. E63257. CSA T.I.L. D-21, File No. LR28548. IEC No. 60470. ANSI/NEMA ICS 3 1993 (R2000)

    Options and Accessories

    SL Series Accessory Kits

    Mechanical Latch Kit SL Vacuum Contactor Sizes 160 400 AmperesField Mount to 160 400 amperes SL Vacuum Contactor. Coil voltages available in a wide range of ac and dc selections. Easy to install on new and existing units.

    Mechanical Latch Kit

    Auxiliary Contact Kit SL Vacuum Contactor Sizes 160 400 AmperesField Mount auxiliary contact kits for 160 400 amperes SL Vacuum Contactor. Contact kits are available in many configurations of NO-NC.

    Auxiliary Contact Kit

    Mechanical Interlock KitField Mount mechanical interlock kits for 160 400 amperes SL Vacuum Contactor.

    Mechanical Interlock Kit

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-27Power Breakers, Contactors & Fuses

    13

    Power ContactorsProduct Description

    SL MV Power Contactor Size 800 Amperes

    SL Medium Voltage Contactor

    Product Description A single family of contactors for

    any medium voltage control appli-cation. Voltage range of 2200 to 7200 volts.

    Ampere rating of 800 amperes with Induction Motor Horsepower ranges from 3000 to 10,000 hp.

    Two different altitude versions. Leading-edge vacuum technology. Third-party qualified by UL,

    CSA, KEMA. Long life 100,000 electrical

    and over 1 million mechanical. Mounting flexibility panel or

    pedestal mounting provisions are standard. Unit can be mounted in horizontal or vertical position.

    Special ordering allows unit to be factory pre-set to customer specification, including field kit installation.

    Highest quality available all contactors manufactured within state-of-the-art ISO-Certified facilities. 100% made in America.

    Application DescriptionEatons Cutler-Hammer SL Medium Voltage Contactors starting applications: Squirrel-cage induction motors. Synchronous motors. Wound-rotor.

    Fully applicable to: Full voltage starting. Reduced voltage starting.

    The perfect choice for harsh duty applications: Mining. Pulp and paper. HVAC. Petrochemical. Automotive. Many others.

    Features, Benefits and Functions The SL Contactor Ratings Voltages of 2200 7200 volts. 800 amperes (720 amperes

    enclosed). Interrupting rating of

    12,500 amperes.

    Control Voltages 110, 220 Vac 50 Hz. 120, 240 Vac 60 Hz. 125 Vdc.

    Drop-out Time 50 330 ms Field Selectable

    Acceptability NEMA ANSI IEC

    Third-Party Verification UL CSA KEMA

    Factory Installed Option Kit Mechanical latch many coil

    voltages.

    Long Life Guarantees High Quality 100,000 electrical operations. 1 million mechanical operations.

    Standards and Certifications

    Design and Test Standards UL 347, File No. E63257. CSA T.I.L. D-21, File No. LR28548. ANSI/NEMA ICS 3 1993 (R2000) IEC 60470

    SL Series Accessory Options 800 Amperes

    Mechanical Latch Assembly 800 Amperes

    Mechanical Latch Option SL Vacuum Contactor Size 800 AmpereFactory installed for 800 ampere SL Vacuum Contactor. Coil voltages available in a wide range of ac and dc selections.

  • February 2007

    13-28

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power ContactorsSL Series Fuses

    SL Series FusesTable 13-14. Fuse Application Table for SL Contactors

    For FLA > 180, maximum acceleration time = 4.5 seconds.

    Fuse Application Table for SL Contactors (Continued)

    For FLA > 360, maximum acceleration time = 6 seconds.Note: Fuse selections based on LRC = FLA x 6 with acceleration time of 10 seconds except where otherwise noted.

    MotorFLA

    Voltage SuggestedCutler-HammerFuse

    Rating MinimumOpeningTime

    SL-160 11 18 18 31 31 46 46 62 62 74 74 93 93 137137 160

    2400 4800 5BCLS-305BCLS-2R5BCLS-3R5BCLS-4R5BCLS-5R5BCLS-6R5BCLS-9R5BCLS-12R

    30 1R 70 2R100 3R130 4R150 5R170 6R200 9R230 12R

    30 30 30 30 30 30130130

    11 34 34 46 46 56 56 68 68 85 85 137137 160

    5500 6600 7BCLS-2R7BCLS-3R7BCLS-4R7BCLS-5R7BCLS-6R7BCLS-9R7BCLS-12R

    70 2R100 3R130 4R150 5R170 6R200 9R230 12R

    30 30 30 30 30 50250

    SL-200 11 18 18 31 31 46 46 62 62 74 74 93 93 137137 200

    2400 4800 5BCLS-305BCLS-2R5BCLS-3R5BCLS-4R5BCLS-5R5BCLS-6R5BCLS-9R5BCLS-12R

    30 1R 70 2R100 3R130 4R150 5R170 6R200 9R230 12R

    30 30 30 30 30 30130130

    11 34 34 46 46 56 56 68 68 85 85 137137 200

    5500 6600 7BCLS-2R7BCLS-3R7BCLS-4R7BCLS-5R7BCLS-6R7BCLS-9R7BCLS-12R

    70 2R100 3R130 4R150 5R170 6R200 9R230 12R

    30 30 30 30 30 50250

    MotorFLA

    Voltage SuggestedCutler-Hammer Fuse

    Rating Minimum Opening Time

    SL-360 11 18 18 31 31 46 46 62 62 74 74 93 93 137137 187187 200200 360

    2400 4800 5BCLS-305BCLS-2R5BCLS-3R5BCLS-4R5BCLS-5R5BCLS-6R5BCLS-9R5BCLS-12R5BCLS-12RN/A

    30 1R 70 2R100 3R130 4R150 5R170 6R200 9R230 12R230 12R

    30 30 30 30 30 30130130130

    11 34 34 46 46 56 56 68 68 85 85 137137 200187 200200 360

    5500 6600 7BCLS-2R7BCLS-3R7BCLS-4R7BCLS-5R7BCLS-6R7BCLS-9R7BCLS-12R7BCLS-12RN/A

    70 2R100 3R130 4R150 5R170 6R200 9R230 12R230 12R

    30 30 30 30 30 50250250

    SL-400 11 18 18 31 31 46 46 62 62 74 74 93 93 137137 187187 273273 400

    2400 4800 5BCLS-305BCLS-2R5BCLS-3R5BCLS-4R5BCLS-5R5BCLS-6R5BCLS-9R5BCLS-12R5BCLS-18R5BCLS-24R

    30 1R 70 2R100 3R130 4R150 5R170 6R200 9R230 12R390 18R450 24R

    30 30 30 30 30 30 30 30 50130

    11 34 34 46 46 56 56 68 68 85 85 137137 187187 273273 400

    5500 6600 7BCLS-2R7BCLS-3R7BCLS-4R7BCLS-5R7BCLS-6R7BCLS-9R7BCLS-12R7BCLS-18R7BCLS-24R

    70 2R100 3R130 4R150 5R170 6R200 9R230 12R390 18R450 24R

    30 30 30 30 30 30 30 50250

    SL-800 225 360 360 449 450 720

    2400 4800 5BCLS-24R5BCLS-36R5BCLS-44R

    450 24R650 36R800 44R

    50130250

    225 400 400 449 450 720

    5500 6600 7BCLS-24R7BCLS-36R7BCLS-44R

    450 24R650 36R800 44R

    50130250

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-29Power Breakers, Contactors & Fuses

    13

    Power ContactorsSL Series Ratings

    SL Series RatingsTable 13-15. Type SL Vacuum Contactor Ratings

    Table 13-16. Rating Specifications

    RatedUtilizationVoltage

    Interrupting Rating Application Table TransformerkVA

    Capacitorkvar

    Maximum InsulationVoltage

    NEMAUnfused (E1)kA

    NEMAFused (E2)kA

    InductionMotorHorsepower

    Synchronous MotorHorsepower

    (0.8 PF) (1.0 PF)

    160 Ampere Frame2200 25003000 36003800 48006000 6900

    4.5 4.5 4.5 4.5

    50505050

    600 90012001800

    600 90012001800

    800 1000 1400 2200

    600 80010001600

    480 640 9601320

    7200

    200 Ampere Frame2200 25003000 36003800 48006000 6900

    4.5 4.5 4.5 4.5

    50505050

    800110015002250

    800110015002250

    1000 1250 1750 2750

    750100012502000

    600 80012001650

    7200

    360 Ampere Frame2200 25003000 36003800 48006000 6900

    4.5 4.5 4.5 4.5

    50505050

    1500200025004000

    1500200025004000

    1750 2500 3000 5000

    1200160020003200

    1000147521502950

    7200

    400 Ampere Frame2200 25003000 36003800 48006000 6900

    8.5 8.5 8.5 8.5

    50505050

    1750225030004500

    1750225030004500

    2000 2500 3500 5500

    1500200025004000

    1200165024003300

    7200

    800 Ampere Frame2200 25003000 36003800 50006000 7200

    12.5 (50 MVA)12.5 (50 MVA)12.5 (75 MVA)12.5 (100 MVA)

    50 (200 MVA at 2300 V)50 (285 MVA at 3300 V)50 (400 MVA at 4600 V)50 (570 MVA at 6600 V)

    3000400050008000

    3000400050008000

    3500 5000 600010,000

    2500350045006000

    2400320040004800

    7200

    Ampere Rating 160 A 200 A 360 A 400 A 800 A

    Maximum Interrupting Current(3 Operations Amperes)

    4500 4500 4500 8500 12,500

    Rated Current 160 200 360 400 800 (720 Enclosed)

    IEC Make-Break Capability AC4 (Amperes)MakeBreak

    16001280

    20001600

    36002880

    40003200

    8000 6400

  • February 2007

    13-30

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power ContactorsProduct Specifications

    Product Specifications

    Voltage ClassEatons Cutler-Hammer SL Medium Volt-age Vacuum Contactors are designed to operate on voltage systems rated from 2200 to 7200 volts. Typical system volt-ages are 2400, 3300, 4160 and 6600 volts.

    AltitudeSL Contactors are capable of operating in virtually any altitude range. Three versions are offered in Standard, High and Low altitude configurations. No de-rating is necessary for proper oper-ation. Altitude designations are listed in the table below.

    Table 13-17. Altitude

    Control VoltageControl coil voltage should be select-able in the field. Standard voltages available should be 120/60, 110/50, 240/60, 220/50 and 125 Vdc. Coil should pickup at 80% of rated coil voltage and dropout not sooner than 60% of rated coil voltage. Open-ing time should be field selectable within the range of 30 ms 330 ms for 160 400 A and 50 ms 330 ms for 800 A.

    160 400 Amperes Short-time current:

    30 seconds: 2400 amperes 1 second: 6000 amperes 8.7 ms: 63 kA Peak

    (0.5 cycle) Normal service altitude: -3281 to

    +6562 ft. (-1000 to +2000 meters). Mechanical life: 2.5 million. Electrical life:

    6 x Rated Make/1x Rated Break:300,000 operations

    6 x Rated Make/6 x Rated Break:300,000 operations

    BIL (impulse withstand):60 kV (1.2 x 50 microseconds)

    Dielectric strength: 20 kV rms (1 minute)

    Closing time: 80 milliseconds(energization to contact touch).

    Selectable opening times: 30 milliseconds (2 cycles) 50 milliseconds (3 cycles) 130 milliseconds (8 cycles) 250 milliseconds (15 cycles) 330 milliseconds (20 cycles)

    Arcing time:12 ms (0.75 cycle) or less.

    Pickup voltage:80% rated coil voltage.

    Dropout voltage:60% rated coil voltage.

    Control voltages: ac/Hz: 110/50, 120/60, 220/50,

    240/60 dc: 125

    Control circuit burden: Closing: (200 milliseconds)

    110/120 ac, 125 dc 1 kVA 220/240 ac 1.8 kVA

    Holding: 110/120 ac 125 dc 40 VA 220/240 ac 50 VA

    Auxiliary contact rating: 600 volts (maximum) 10 amperes continuous current Making capacity

    ac: 7200 VA dc: 125 VA

    Breaking capacity ac: 720 VA dc: 125 VA

    Latch (when specified) Mechanical life:

    250,000 operations Trip voltage

    dc: 24 volts dc: 125 volts ac: 110/120 volts

    Minimum trip voltage:80% rated coil voltage

    Trip burden 24 Vdc: 400 VA 48 and 125 Vdc: 400 VA 110 and 120 Vac: 400 VA 220 and 240 Vac: 400 VA

    Trip Time (2 cycles): 30 ms Weight

    150 360 A: 47 Lbs. (21.3 kg) 400 A: 49 Lbs. (22.2 kg)

    800 Amperes Short-time current

    30 seconds: 4320 amperes 1 second: 10,800 amperes 8.7 ms (0.5 cycle) 86 kA peak

    Normal service altitude: -3281 to +6562 ft. (-1000 to +2000 meters).

    Mechanical life: 1 million. Electrical life: 100,000 operations. BIL (impulse withstand):

    60 kV (1.2 x 50 microseconds). Dielectric strength:

    18.2 kV rms (1 minute). Closing time (energization

    to contact touch):80 milliseconds.

    Opening times (deenergization to full open): 50 ms (3 cycles) 130 ms (8 cycles) 250 ms (12 cycles) 330 ms (20 cycles)

    Arcing time:12 ms (0.75 cycle) or less.

    Pickup voltage:80% rated coil voltage.

    Dropout voltage:60% rated coil voltage.

    Control voltages: ac/Hz: 110/50, 120/60 Vac, 220/50,

    240/60 dc: 125 Vdc

    Control circuit burden: Closing (120/240): 1700 VA/2600 VA Holding (120/240): 80 VA/100 VA

    Altitude Low Standard High

    160 400 AFeet -11,500 to

    -3300-3300 to+6600

    +6600 to+13,100

    Meters -3500 to -1000

    -1000 to+2000

    +2000 to +4000

    800 AFeet N/A -3300 to

    +11,800+11,800 to+16,000

    Meters N/A -1000 to+3600

    +3600 to +4900

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-31Power Breakers, Contactors & Fuses

    13

    Power ContactorsProduct Specifications

    800 Amperes (Continued) Auxiliary contact rating:

    600 volts (maximum) 10 amperes continuous current Making capacity

    ac: 7200 VA dc: 200 VA

    Breaking capacity ac: 720 VA dc: 200 VA

    Latch (when specified): Mechanical life:

    250,000 operations Trip voltage

    dc: 24, 48, 96 volts ac: 110/120, 220/240 volts

    50/60 Hz Minimum trip voltage:

    80% rated coil voltage Trip burden

    24 Vdc: 1200 VA 48 and 96 Vdc: 400 VA 110 and 220 Vac: 500 VA

    Trip time (2 cycles): 30 milliseconds

    Weight: 95 Lbs. (43.1 kg).

    Technical Data and Specifications

    Electrical Connections Diagrams (160 400 Amperes)

    Figure 13-5. Connection for Magnetically Held Contactor

    Figure 13-6. Connections for Mechanically Latched Contactor M contacts are connected in parallel for 48 V. M contacts are connected in series for > 48 V.

    Table 13-18. Control Voltage Settings

    Note: Stock units pre-set to 120/60 Vac.

    Table 13-19. Dropout Time Settings

    Table 13-20. Altitude Designations

    Setting SW1 SW2 SW3

    110 Vac 50 Hz120 Vac 60 Hz220 Vac 50 Hz

    OffOnOff

    OffOffOn

    OffOffOff

    240 Vac 60 Hz125 Vdc

    OnOff

    OnOff

    OffOn

    Delay Setting SW4 SW5 SW6

    30 ms 50 ms130 ms

    OffOnOff

    OffOffOn

    OffOffOff

    250 ms330 ms

    OnOff

    OnOff

    OffOn

    Altitude Low Standard High

    FeetMeters

    -11,483 to -3281-3500 to -1000

    -3281 to +6562-1000 to +2000

    +6562 to +13,123+2000 to +4000

    ControlVoltage(On/Off)

    White

    Black

    Black

    White

    dcCoil 2

    dcCoil 1

    11

    2

    3

    4

    5

    6

    7

    8

    ControlVoltage(Close)

    White

    Black

    Black

    White

    dcCoil 2

    dcCoil 1

    11

    2

    3

    4

    5

    6

    7

    8ControlVoltage(Open)

    (+)

    ()dc Latch

    Coil

    M

    M

  • February 2007

    13-32

    For more information visit: www.eaton.com CA08101001E

    Power Breakers, Contactors & Fuses

    13

    Power ContactorsSL Series (160 400 Amperes)

    SL Series (160 400 Amperes)

    SL Series Features

    Control Settings

    Panel-Mount Provisions

    Coil Control Board(Behind Control Terminal Strip)

    Pedestal-Mount Provisions

    Magnet Coil

    Vacuum Interrupters

    Mechanical Latch Provision

    Actuator Assembly

    Contactor Nameplate

    Auxiliary Contact Blocks

    Control Terminal Strip

    Panel-Mount Provisions

    Auxiliary Contact Blocks

    Pedestal-Mount Provisions

    Panel-Mount Provisions

    Control Terminal Strip

    Coil Control Board DIP Switches

    Note: Refer to Table 13-18 for Control Voltage Settings and Table 13-19 for Dropout Time Settings.

  • February 2007

    CA08101001E For more information visit: www.eaton.com

    13-33Power Breakers, Contactors & Fuses

    13

    Power ContactorsSL Series (160 400 Amperes)

    Front and Rear View (160 400 Amperes)

    Front View 160 400 Amperes Rear View 160 400 Amperes

    Dimensional Drawings (160 400 Amperes) in Inches (mm)

    Figure 13-7. Front Dimensions 160 400 Amperes

    Figure 13-8. Base Plate Dimensions 160 400 Amperes

    Figure 13-9. Rear Dimensions 160 400 Amperes

    Figure 13-10. Side Dimensions 160 400 Amperes

    14.00(355.6)

    4.38(111.3)

    6.85(174.0)174.0

    4.38(111.3)

    7.36(186.9)186.9

    016.