szigorúan bizalmas bizalmas csak belső használatra nyilvános cooling/heating and ... · 2020....
TRANSCRIPT
Szigorúan bizalmasBizalmas
Csak belső használatraNyilvános
Cooling/heating and
Air Handling solutions
László TakaricsSales Engineer
2020.02.17.
2
Grouping of cooling solutions
By cooling task:
• High temperature process cooling: above + 30 ° C
• Technology cooling: + 10 ° C - + 30 ° C
• Air-conditioning cooling: + 6 ° C - + 18 ° C
• Commercial refrigeration: -5 ° C to + 10 ° C
• Commercial freezers: -5 ° C to -20 ° C
• Technological freezing / shock freezing: below -20 ° C
3
Grouping of cooling solutions
Depending on the nature of the unit producing the cooling energy:
• Dry coolers: above + 35 ° C
• Adiabatic dry coolers: + 28 ° C to + 35 ° C
• Closed cooling towers: + 28 ° C to + 40 ° C
• Open cooling towers: + 26 ° C to + 40 ° C
• Compressor coolers (HFC and HFO): -12 ° C to + 20 ° C
• Compressor freezers (CO2, NH3): -5 ° C to -35 ° C
• Absorption coolers: + 6 ° C to + 24 ° C
• Adsorption coolers: + 4 ° C to + 20 ° C
4
Dry coolers 150-1000 kW
Pros
Closed circuit
Low operating costs
Extremely low maintenance requirements
Cons
Large installation space
Very limited operating range due to ambient temperature
5
Adiabatic dry coolers 150-1500 kW
1
5
4
3
2
7
6
Pros
Closed circuit
Humidification requirement only above + 25 °CLow operating costs
Low maintenance requirement
Only water softening is required
Cons
Large installation space
Very limited operating range due to ambient temperature
6
Closed cooling towers 400-4000 kW
Pros
Closed circuit
Medium evaporation loss
Favorable operating costs
Cons
Frost protection is required
Costly water treatment, water softening
Regular maintenance needs
Limited operating range due to ambient temperature
7
Open cooling towers 400-…
Pros
Simple structure
Low unit investment cost
Medium space requirement and weight
Favorable noise data
Cons
High evaporation loss
Costly water treatment, water softening
An additional heat exchanger is required
Frost protection is required
Regular maintenance needs
Limited operating range due to ambient temperature
8
Chillers with compressors 70-2500 kW
Pros
Closed circuit
Always safe cooling performance, accurate temperature control
Wide capacity range
Compact structure
Integrated intelligent automation
Heat pump versions also for heating
Cons
Specifically higher investment and operating costs
Regular maintenance needs
9
Principle of compressor coolingQc heat dissipation = „recoverable wasteheat generation"Condenser
Pe drive powerCompressor
Q0 heat absorption = „cold production”Evaporator
pressure relief Expansion valve
Q0 + Pe = Qc
10
Types of Compressor Chillers
Air cooledWater cooled
Split
11
Types of compressors
Alternating piston
Rotating piston R407C
Piston compressor (R22) → R407F refrigerant
GWP 1810 GWP 1825
GWP 1774
12
Types of compressors
SCREW compressor
(R134a) → R1234yf refrigerant
CENTRIFUGAL compressor
(R134a) → R1234ze refrigerant
SCROLL compressor
(R410a) → R32 refrigerantGWP 2088 GWP 675
GWP 1430
GWP 1430
GWP 6
GWP 4
13
Direct eXpansion, DX systems 4-60 kW
Pros
Closed circuit, direct cooling
Always safe cooling performance, accurate temperature control
Compact design with little space required
Integrated intelligent automation
they can also be used for heating
Cons
Limited scope of applications(comfortclimate range + spec. commercial)
Demand for skilled labor
14
Comparison of cooling solutions
According to the nature of heat transfer:
• Air cooling → 1x or 2x heat transformation
• Liquid cooling (water, glycol, freezium, etc.) →min. 1x heat transformation
• Direct expansion (DX-cooling) →minimum intermediate loss
15
Comparison of cooling solutions
Air RefrigerantLiquid
Diameter of pipes
16
Air cooling
Pros
The highest level of comfort
In some application areas this is the only solution (cleanroom, sport)
Humidity control
Can also be combined with a DX heat source
Cons
High investment and operating costs
Large space requirements within the building
Simultaneous heating and cooling is not possible
Slow control response time
Regular maintenance needs
17
Liquid cooling (water, glycol, freezium, etc.)
Pros
Better space requirements within the building
More efficient heat transfer
Proportional operating and investment costs
Wide power range, despite building geometry dimensions
Simultaneous heating and cooling possible with additional heat source (+ 4-pipe)
Cons
Machine house space requirement within the building
Central control is complicated and expensive
Medium control response time
Regular maintenance needs
18
Direct evaporative cooling (DX-cooling)
Pros
Extremely high seasonal efficiency
Extremely small space requirement within a building
Central control and power control
Fast control response time
Simultaneous cooling and heating with heat recovery
(3-pipe) EER + COP = TER
Cons
Requires a qualified installer (with specialist knowledge)
Piping Layout Based on Custom Manufacturer Specifications and Rules (Software Assistance)
Geometric constraints for high power demand
19
Possible combionations
Total solution in 1 system DX heating and cooling
Low temperaturewater heating and cooling
High temperaturewater heating / DHW (up to 80 ° C)
Ventilation systems (Air handling units and / or air curtains)
Heat Recovery (HR) VRV IV+
20
Air handling unit with integrated DX heat exchanger
Cooling / heating changeovercontact
F1/F2 bus communication
Expansion Valve Dimensions EKEXV63 - EKEXV500
21
Air handling unit with integrated DX heat exchanger
22
EWYD-4Z the four pipe chiller / heat pump
23
Two separate circuits can run independently, so the unit can operate
in 5 different modes:
1. Cooling only2. Heating only3. Cooling = Heating4. Cooling < Heating5. Cooling > Heating
Basing on the actual request for heating and cooling the unit controller assigns to each circuit
the related operating mode
1 2
3
45
OFF OFF
EWYD-4Z the four pipe chiller / heat pump
24
EWYD-4Z the four pipe chiller / heat pump
Környezeti hőmérséklet [°C]
25
Cascade solutionFor low capacity heating applicatioins, a cascade system is used on the refrigerant side.
For large systems, this cascade system can be implemented on the water side.
-15°C
50°C
35°C
40°C
CLW
T
Outdoor air temp.
CLW
T 75°C
ELWT4°C 30°C20°C
Upper cycleW/W HP
Lower cycleA/W HP
Outdoor air temp.-15°C 40°C
CLW
T
75°C
Cascade system operationdiagram
Cascade system
Cascade heat pump solutions
26
Existing building1) Replacing gas boiler for high temperature heating water
75°C
chimney
boiler
R32A/W HP
W/W HP R1234ze75°C
Cascade heat pump solutions
New building
27
R32A/W HP
W/W HP OFF
35°C
Heating period
Only heating
35°C
Heating + DHW
35°C
75°C75°C
Only DHW
R32A/W HP
R32A/W HP
W/W HP ON W/W HP ON
Cascade heat pump solutions
New building
28
R32A/W HPCooling
18°C
Cooling period
Cooling only
18°C
Cooling + DHWR32
A/W HPCooling@ partial load
W/W HP ON
75°C
Only DHW
35°C
W/W HP ON
75°C
W/W HP OFF
R32A/W HPheating
Cascade heat pump solutions
W/W HP OFF
29
And if you really need a lot of power…
30
Middle Eastern district cooling projects with WCT equipment
Daikin Ventilation Solutions
Indoor Air Quality & Ventilation
for Commercial Applications
Pollution
level
Higher Pollution
level
Most people are aware that
outdoor pollution can
impact their health but…
Indoor air is (much) more
polluted than Outdoor air!
OUTDOOR VS INDOOR AIR QUALITY
Classification of outdoor air (ODA) ODA 1 - Rural
ODA 3 - Industrial
Low Pollution Level
High Pollution Level
ODA 2 - City
SUP 1
SUP 4
Classification of indoor air (IDA)Low Pollution
Level
High Pollution Level
Filtration requirement
STANDARD EN16798 – VENTILATION FOR NON-RESIDENTIAL BUILDINGS
Outdoor Air QualitySupply air class
SUP 1 SUP 2 SUP 3 SUP 4
ODA (P) 1 88%a 80%a 80%a 80%a
ODA (P) 2 96%a 88%a 80%a 80%a
ODA (P) 3 99%a 96%a 92%a 80%a
aCombined average filtration efficiency over a single or multiple stage filtration
Aerodynamic Diameter (µm) of particles and their region of deposit
5-10 µm
3-5 µm
2-3 µm
1-2 µm
0,1-1 µm
Nose and Pharynx
Trachea
Bronchia
Bronchiole
Alveoli
ISO 16890
Particulate Matter (PM)
Due to their harmfulness, frequency and permanence, particles smaller than 2.5 µm
(PM1 and PM2.5) need highest attention new legislation ISO 16890
PM10
PM1
PM2.5
PARTICULATE MATTERS
G2
2012 (former legislations) July 2018 (New unified legislation)
EN779:2012
ASHRAE 52.2
ISO 16890
No clear correlation
with PM1 – PM2.5 – PM10
Direct correlation with
PM1 – PM2.5 – PM10
Pressure drop
Eff
icie
ncy
G1
G3 G4
M5M
6
F7F8
F9
Gross
Medium
Fine
Eff
icie
ncy
ISO Coarse (%)
ePM10 (%)
ePM2.5 (%)
ePM1 (%)
Pressure drop
NEW FILTRATION LEGISLATION ISO 16890
DAIKIN VENTILATION ANDAIR HANDLING UNITSRange and portfolio
Modular R
Modular P
Professional
Centralized ventilation Decentralized ventilation
Modular LVAM
CENTRALIZED AND DECENTRALIZED SOLUTIONS
ProfessionalUp to 144.000 m3/h
150
125
100
75
50
25
20
15
10
5
0
Modular RUp to 25.000 m3/h
Modular PUp to 15.000 m3/h
Modular LUp to 3.500 m3/h
Up to 2.000 m3/h
VAM
DAIKIN VENTILATION AND AHU PORTFOLIO
MODULAR L SMARTDesigned for the best indoor air
quality
A
B
FRESH AIR
Pre filter: Coarse 55% (G4) or ePM10 75% (M5)
or ePM1 50% (F7)
Filter: ePM1 50% (F7)* or ePM1 80% (F9)
*Minimum requirement EU Reg. 1253
RETURN AIR
Filter: ePM10 75% (M5)* or ePM1 50% (F7)
Pre filter: Coarse 55% (G4) or ePM10 75%
(M5)
* Minimum requirement EU Reg. 1253
D
C
BEST POSSIBLE IAQ – FILTER ARRANGEMENT
• Up to ePM1 50% (F7) + ePM1 80% (F9) filtration level
• Possibility to have pre-filter
• CO2 sensor (optional)
BEST POSSIBLE IAQ ACCORDING TO EN16798
F1-F
2
Direct integration of the Modular L Smart into a DX installation:
• F1-F2 connector: direct integration with Daikin centralised controllers (iTM, iTAB, Daikin Cloud
Service)
• P1-P2 connector: direct integration with Daikin controllers (Madoka BRC1H)
DIRECT CONNECTIVITY AND COMMUNICATION with VRV / SkyAir units
Modular L Smart
iTM
iTab
Daikin Cloud
Service
DIII-Net
P1-P2
Easiness of selection, easiness of installation, easiness of commissioning, less running costs
CONNECTIVITY WITH VRV AND SKYAIR
MODULAR L SMARTProduct overview
Premium efficiency
counter flow
aluminium
Heat Exchanger
(up to 92%
efficiency)
Low pressure
compact filters
(pre-filter/filter stages)
EC centrifugal plug
fans
with IE4 premium
efficiency motor
50 mm mineral wool insulation
Aluzinc inner panel, highest
corrosion resistance (C5 / C4)
100% automatic bypass
damper for free cooling
operation
Rectangular duct
flange (circular
optional)
MODULAR L SMART OVERVIEW
Unique Selling Points for any Ventilation application
• Best possible Indoor Air Quality
• Direct connectivity to VRV / SkyAir
• Space saving solution (from 280 mm height)
• High Efficiency aluminium Heat Exchanger (up to 92%)
• Airflow from 150 up to 3.500 m3/h, maximum available ESP up to 600 Pa
• Low sound level
• 6 standard sizes available from stock
MODULAR L SMART IN A GLANCE
Thank you for your attention!