  • System Display and Controller

  • Contents

    Basic Navigation…………………………………………………..…... 2

    Menu Maps -MATE System Display and Controller Basic Setup……………. 2MATE System Display and Controller Advanced Setup………. 3MATE System Display and Controller AGS Menu………….. 4-5Inverter Setup…………………………………………………….. 6-7Charge Controller Setup………………………………………… 8FLEXnet DC Setup………………………………………………. 9-10

    900-0131-01-00 Rev A.vsd\TOC\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved.

    WARNING: SHOCK HAZARD

    Consult the MATE Owner’s Manual for detailed information on safety and installation procedures.

  • 900-0131-01-00 Rev A.vsd\Menu Map Basics\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 1

    BA

    SIC

    NA

    VIG

    ATI

    ON

    The following pages are intended as a quick reference guide for the menu map of the MATE Series System Display and Controller. This document is for use with the products MATE and MATE2. It cannot be used with the MATE3.

    See the MATE Series Owner’s Manual for detailed information about the menu structure, MATE features, and hot/soft key functions. See the inverter, charge controller, and DC monitor manuals for detailed information about specific features and functions that are controlled by the menus.

    ------------------choose device:

    FX MATE

    Selection from Main Menu

    Device Selection Menu

    SETUP/FX----------------choose categoryDevice Menu Title(s)

    SETUP/FX/SEARCH------P016

    DOWN INC DEC PORT

    Menu Item

    SETUP/FX/SEARCH------P01searchsensitivityDOWN INC DEC PORT

    Setpoint or function for the Menu Item

    SETUP/FX/SEARCH------search 6sensitivityDOWN INC DEC PORT

    Port

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    Main Screen

    Main MenuSoft Keys

    To cycle through the devices connected to the HUB, press the soft key.

    Select this option to proceed

    Available menus

    Adjusts the set points value

    Switches between devices on the ports of the Communications HUB

    Soft Key Color Code:

    Navigation colors

    Selects a function (e.g., ON, OFF, AUTO)

    Soft key functions will vary depending on the selected menu and are defined by the word above the key in the LCD.

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

    If accompanied by a dashed line, pressing that soft key will return the user to the location identified by the dashed line. This will vary depending on the devices in the system.

    Indicates a 1-screen movement within a Menu. These are color coded according to their function or purpose.

    Navigation:

    Soft Keys

    Soft Keys

    LCD Screen

    LCD Screen

    INV Hot Key

    AC IN Hot Key

    AC IN Hot Key

    INV LED

    INV Hot Key

    INV LED

    AC IN LED

  • 900-0131-01-00 Rev A.vsd\MATE Basic Setup\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 2

    (C)2009OutBack

    PowerSystems

    VersionCode a.a.aSerial #xxxxxxxxScreen EE b.bb

    Searching for Devices

    FX Found

    Searching for Devices

    CC Found

    Searching for Devices

    DC Found

    Port Assignment1> FX 2>CC 3> DC 4>5> 6> 7> 8>9> 10> 2M>

    Searching for Devices

    HUB Found

    SETUP/MATE/PAGE1-------mate code rev: 4.1.3choose category:CLOCK CNT GLOW PG2

    Current DayTu 01/01/09

    INC SETDAY MONTH

    Current MonthTu 01/01/09

    INC SETMONTH DATE

    Current DateTu 01/01/09

    INC SETDATE YEAR

    Current YearTu 01/01/09

    INC DECYEAR YEAR DONE

    Current Minute12:00:00P

    INC DEC RESETMIN MIN SEC DONE

    Current Hour12:00:00P

    INC SETHOUR MIN

    SETUP/MATE/CNT-------contrast 30%

    BACK INC DEC

    SETUP/MATE/GLOW-------backlight controls

    BACK LEVEL MODE TIME

    SETUP/MATE/GLOW/LEVELbacklight 100%

    BACK INC DEC

    SETUP/MATE/GLOW/MODEcurrent code: AUTO

    BACK OFF AUTO ON

    SETUP/MATE/GLOW/TIMEglow Off 5 minstimeBACK INC DEC

    SETUP/MATE/CLOCK-------Tu 1/01/09

    12:00:00PBACK DATE TIME

    SETUP/MATE/SUM-------summary control

    BACK TYPE DELAY ROLL

    SETUP/MATE/SUM/TYPE----summary screen typeBACK INC DEC

    SETUP/MATE/SUM/DELAY-Sum screen 19 minsDelay timeBACK INC DEC

    SETUP/MATE/SUM/DELAY-Sum screen 10 secondsRoll rateBACK INC DEC

    SETUP/MATE/COMM/PC------PC communications: OFF

    BACK OFF ON

    SETUP/MATE/COMM--------Comm errors:

    BACK VIEW RSET

    00:000 01:000 02:00003:000 04:000 05:00006:000 07:000 08:00009:000 10:000 2M:000

    After Resetting Comm Errors

    SETUP/MATE/PAGE2-------choose category:

    PG1 SUMRY COMM PG3

    SETUP/MATE/PAGE3-------choose category:

    PG2 BEEP MAIN

    SETUP/MATE/COMM--------Choose category:

    BACK REPOLL PC DEBUG

    00:000 01:000 02:00003:000 04:025 05:00106:001 07:001 08:00109:001 10:001 2M:001

    Viewing Comm Errors

    11

    2

    3

    4

    5

    6

    Setting up the MATE or MATE2 includes:1. Setting the Clock (date and time)2. Setting the screen contrast.3. Setting the Glow time.4. Setting how the Summary screens are

    displayed.5. Setting communication options.6. Setting Beep tone functions.

    Setpoints:NoneRoll: rotates between devicesFX OnlyCC OnlyDC OnlyDC Simple

    1

    Main ScreenMAIN----------------

    3:02:14P

    SUM STATUS SETUP ADV

    Setpoints (Current Day):Monday through Sunday

    Setpoints (Current Month):01 through 12

    Setpoints (Current Date):01 through 31

    Setpoints (Current Year):09 through xx

    Setpoints (Current Hour):01-12AM or 01-12PM

    Setpoints (Reset Sec):Resets seconds to 00

    1

    2

    3

    4

    5

    6

    Varies depending on attached devices. Automatically returns

    to the Main Screen.

    Repolling

    SETUP------------------choose device:

    FX MATE

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    Main Screen

    Startup ScreensMAIN----------------

    3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

    Port Assignment1> FX 2>CC 3> DC 4>5> 6> 7> 8>9> 10> 2M>

    Searching for Devices

    HUB Found

    SETUP/MATE/BEEP--------button beep tone ON

    BACK OFF ON

    MA

    TE

    AC IN INV

    MAIN----------------3:02:14P

    SUM STATUS SETUP ADV

    G'day Mate

  • MA

    TE

    (continued)

    900-0131-01-00 Rev A.vsd\MATE ADV Setup\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 3

    Accessing the Advanced Menu:

    ADV--------------------choose device

    FX CC DC MATE

    Changing more detailed operating parameters requires access to the

    Advanced Setup Menu.

    ADV/MATE/HBX------------hbx-use 24.0 Vdcgrid set pointDOWN ADV INC DEC

    ADV/MATE/HBX------------hbx-use 1.0 hrsgrid delayDOWN UP INC DEC

    ADV/MATE/HBX------------hbx-drop 26.0 Vdcgrid set pointDOWN UP INC DEC

    ADV/MATE/HBX------------hbx-drop 1.0 hrsgrid delayDOWN UP INC DEC

    ADV/MATE/HBX------------ac input USEcontrolDOWN UP CHANGE

    ADV/MATE/HBXend of hbx menu

    UP TOP ADV

    ADV/MATE/GRIDUSE--------griduse enable: OFF

    DOWN ADV OFF ON

    ADV/MATE/GRIDUSEend of griduse menu

    UP TOP ADV

    ADV/MATE/HBX------------ac input USEcontrolDROP USE HBX DONE

    ADV/MATE/PAGE1choose category

    HBX GRIDUSE AGS PG2

    ADV/MATE/PAGE3------------advanced chargerfloat control

    PG2 CC FN-DC PG4

    ADV/MATE/PG3/CC-----------enable CC floatcoordination: Yes

    PG3 YES NO ADV

    ADV/MATE/PG3/FN-DC--------enable FN-DC chargetermination: YesPG3 YES NO ADV

    ADV/MATE/PAGE2----------choose category:

    PG1 DEFAULTS PG3

    ADV/MATE/DEFAULT----------reset MATE to factory defaultRESET NO

    Page 1 Page 2 Page 3

    Page 4

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    Charge Controller and FLEXnet DC Menus

    Resetting the MATE2 to Factory Defaults

    1

    1 The AGS Menu is shown on the next page….

    ADV/MATE/DEFAULT----------Are you sure?

    YES NO

    ADV/MATE/GRIDUSE--------weekday 12:00Agriduse start timeDOWN UP CHANGE

    ADV/MATE/GRIDUSE--------weekday 12:00Agriduse stop timeDOWN UP CHANGE

    ADV/MATE/GRIDUSE--------weekend 12:00Agriduse start timeDOWN UP CHANGE

    ADV/MATE/GRIDUSE--------weekend 12:00Agriduse stop timeDOWN UP CHANGE

    WEEKDAY GRIDUSE STARTadj hour 12:00A

    DOWN INC DEC

    WEEKDAY GRIDUSE STARTadj min 12:00A

    INC DEC DONE

    WEEKDAY GRIDUSE STOPadj hour 12:00A

    DOWN INC DEC

    WEEKDAY GRIDUSE STOPadj min 12:00A

    INC DEC DONE

    WEEKEND GRIDUSE STARTadj hour 12:00A

    DOWN INC DEC

    WEEKEND GRIDUSE STARTadj min 12:00A

    INC DEC DONE

    WEEKEND GRIDUSE STOPadj hour 12:00A

    DOWN INC DEC

    WEEKEND GRIDUSE STOPadj min 12:00A

    INC DEC DONE

    ADV/MATE/PG4-------------FN-DC advanced gridtie authorityPG3 MODE ADV MAIN

    ADV/MATE/AGS/PG4/MODE--FN-DC enable

    disabledPG4 IN DEC ADV

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    ADV/SETTINGS/WARNINGchanges made could adversely affect

    system performance

    ADV/PASSOWRD------------Enter the password

    132ENTER INC DEC EXIT

    ADV/PASSOWRD------------Enter the password

    141ENTER INC DEC EXIT

    A 1. Press the soft key until “141” is displayed on the LCD.

    2. Press the soft key to accept the password and move forward to the Device Selection Menu.

    A

    B

    B

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • MA

    TE

    (continued)

    900-0131-01-00 Rev A.vsd\MATE ADV Setup 2\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 4

    ADV/MATE/AGS/SETUP------ags enabled: No

    DOWN UP NO YES

    ADV/MATE/AGS/SETUP------ags control: MAN-OFF

    DOWN UP CHANGE

    ADV/MATE/AGS/SETP-------dc genset: No

    DOWN UP NO YES

    ADV/MATE/AGS/SETUP------Vdc genstop 38.0 Vdc

    DOWN UP INC DEC

    ADV/MATE/AGS/SETUP------ags fault time 17

    minutesDOWN UP INC DEC

    ADV/MATE/AGS/SETUP------cool down time 0

    minutesDOWN UP INC DEC

    ADV/MATE/AGS/SETUP------warm up time 0

    minutesDOWN UP INC DEC

    ADV/MATE/AGS/SETP-------end of AGS Setup

    menuUP TOP AGS

    ADV/MATE/PAGE1choose category

    HBX GRIDUSE AGS PG2

    ADV/MATE/AGS------------choose category:

    QUIET VOLTSETUP TIME START PG2

    ADV/MATE/AGS/QUIETTIME--weekday 12:00Aquiet time startDOWN UP CHANGE

    ADV/MATE/AGS/QUIETTIME--weekday 12:00Aquiet time stopDOWN UP CHANGE

    ADV/MATE/AGS/QUIETTIME--weekend 12:00Aquiet time startDOWN UP CHANGE

    ADV/MATE/AGS/QUIETTIME--weekend 12:00Aquiet time stopDOWN UP CHANGE

    ADV/MATE/AGE/QUIETTIME--end of quiet time

    menuUP TOP AGS

    ADV/MATE/AGS/VSTART-----volt start 24.4 Vdc24 hr settingDOWN AGS INC DEC

    ADV/MATE/AGS/VSTART-----volt start 23.6 Vdc2 hr settingDOWN UP INC DEC

    ADV/MATE/AGS/VSTART-----volt start 22.0 Vdc2 min settingDOWN UP INC DEC

    ADV/MATE/AGE/QTend of VOLTAGE

    START menuUP TOP AGS

    GEN START CONTROLcurrently: MAN-OFF

    OFF AUTO ON OK

    WEEKDAY QT STARTadj hour 12:00A

    DOWN INC DEC

    WEEKDAY QT STARTadj min 12:00A

    INC DEC DONE

    WEEKDAY QT STOPadj hour 12:00A

    DOWN INC DEC

    WEEKDAY QT STOPadj min 12:00A

    INC DEC DONE

    WEEKEND QT STARTadj hour 12:00A

    DOWN INC DEC

    WEEKEND QT STARTadj min 12:00A

    INC DEC DONE

    WEEKEND QT STOPadj hour 12:00A

    DOWN INC DEC

    ADV/MATE/AGS/SETUP------ags port: 1

    DOWN AGS INC DEC

    WEEKEND QT STOPadj min 12:00A

    INC DEC DONE

    Continued on the next page...

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • MA

    TE

    (continued)

    900-0131-01-00 Rev A.vsd\MATE ADV Setup 3\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 5

    Advanced Setup Menu

    (Continued)

    ADV/MATE/AGS/LS---------load start 0 kw

    DOWN AGS INC DEC

    ADV/MATE/AGS/LS---------load start 1 mindelayDOWN UP INC DEC

    ADV/MATE/AGE/LSend of LOAD START menuUP TOP AGS

    ADV/MATE/AGS/LS---------load stop 0 kw

    DOWN UP INC DEC

    ADV/MATE/AGS/PAGE2---------choose category

    LOAD MUSTPG1 START RUN PG3

    ADV/MATE/AGS/MR---------weekday 12:00 Amust run start timeDOWN AGS CHANGE

    ADV/MATE/AGS/MR---------weekday 12:00 Amust run stop timeDOWN UP CHANGE

    ADV/MATE/AGE/MRend of MUST RUN menuUP TOP AGS

    ADV/MATE/AGS/MR---------weekend 12:00 Amust run start timeDOWN UP CHANGE

    ADV/MATE/AGS/MR---------weekend 12:00 Amust run stop timeDOWN UP CHANGE

    ADV/MATE/AGS/LS---------load stop 1 mindelayDOWN UP INC DEC

    WEEKDAY MR STARTadj hour 12:00A

    DOWN INC DEC

    WEEKDAY MR STOPadj hour 12:00A

    DOWN INC DEC

    WEEKEND MR STARTadj hour 12:00A

    DOWN INC DEC

    WEEKEND MR STOPadj hour 12:00A

    DOWN INC DEC

    WEEKEND MR STARTadj min 12:00A

    INC DEC DONE

    WEEKEND MR STOPadj min 12:00A

    INC DEC DONE

    WEEKDAY MR STARTadj min 12:00A

    INC DEC DONE

    WEEKDAY MR STOPadj min 12:00A

    INC DEC DONEADV/MATE/AGS/%SOC-------

    end of %SOC START MenuUP TOP AGS

    ADV/MATE/AGS/PAGE3------choose category

    %socPG2 START TIMERS PG4

    ADV/MATE/AGS/TIMERS-----ags state 0

    DOWN AGS

    ADV/MATE/AGS/TIMERS-----agsgenfault 0

    DOWN UP

    ADV/MATE/AGS/TIMERS-----24 hr 1440 minvs timeDOWN UP

    ADV/MATE/AGS/TIMERS-----2 hr vs time 120 min

    DOWN UP

    ADV/MATE/AGS/TIMERS-----2 min 2 minvs timeDOWN UP

    ADV/MATE/AGS/TIMERS-----lsstart timer 0 min

    DOWN UP

    ADV/MATE/AGS/TIMERS-----lsstop timer 0 min

    DOWN UP

    ADV/MATE/AGS/PAGE4------choose category:

    PG3 EXERCISE ADV

    ADV/MATE/AGS/EX---------ex start day ---

    DOWN AGS INC DEC

    ADV/MATE/AGS/EX---------ex start time 12:00A

    DOWN UP INC DEC

    ADV/MATE/AGS/EX---------ex period 15 min

    DOWN UP INC DEC

    ADV/MATE/AGS/%SOC----------%SOC start 0%

    DOWN AGS INC DEC

    ADV/MATE/AGS/%SOC-------%SOC stop 90%

    DOWN UP INC DEC

    ADV/MATE/AGS/FULLCHG---charge to 100% fullevery 15 daysDOWN UP INC DEC

    ADV/MATE/AGS/TIMERS-----exstop timer 0 min

    DOWN UP

    ADV/MATE/AGS/ES---------end of

    exercise MenuUP TOP AGS

    ADV/MATE/AGS------------choose category:

    QUIET VOLTSETUP TIME START PG2

    ADV/MATE/PAGE1choose category

    HBX GRIDUSE AGS PG2

    Continued from the previous page.

    ADV/MATE/AGS/TIMERS-----Vdcstop timer 0 min

    DOWN UP

    ADV/MATE/AGS/TIMERS-----end of TIMERS

    MenuUP TOP AGS

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • INVE

    RTE

    R

    900-0131-01-00 Rev A.vsd\INV Setup\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 6

    Setting up the basic Inverter functions includes:1. Selecting the AC input (Grid or Gen).2. Setting the Search function.

    SETUP/FX/INPUTAc1/grid 60.0 aaclimitDOWN INC DEC PORT

    SETUP/FX/SEARCH------P01search 6sensitivityDOWN INC DEC PORT

    SETUP/FX/SEARCH------P01search 8 cyclespulse lengthDOWN INC DEC PORT

    SETUP/FX/SEARCH------P01search 60 cyclespulse spacingDOWN INC DEC PORT

    SETUP/FX----------------choose category

    SRCH INPUT

    SETUP------------------choose device:

    FX MATE

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    SETUP/FX/SEARCH---------search setup completed

    TOP SETUP MAIN

    ADV/FX/PAGE1choose category

    ADV INV CHRG PG2

    ADV/FX/INVERTER------P01press button 2

    DoneEXIT 1 2

    ADV/FX/INVERTER------P01press button 2

    ReadyEXIT 1 2

    ADV/FX/INVERTER------P01press button 1

    ReadyEXIT 1 2

    ADV/FX/INVERTER------P01choose fx portthen press nextEXIT PORT NEXT

    ADV/FX/INVERTER---------reset FX to factorydefaultsDOWN MORE

    ADV/FX/INVERTER---------inverter programming completed

    TOP ADV MAIN

    ADV/FX/CHARGER-------P01charger 12.0AaclimitDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01charger 12.0 AaclimitDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01absorb 28.8 Vdcset pointDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01absorb 1.0 hrstime limitDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01float 27.2 Vdcset pointDOWN INC DEC PORT

    Continued on next page….

    NOTE: The values shown in this illustration will vary depending on the model of inverter.

    Setpoints:GridGenerator

    1

    ADV/FX/INVERTER-----P01search 6sensitivityDOWN INC DEC PORT

    ADV/FX/INVERTER-----P01search 8pulse lengthDOWN INC DEC PORT

    ADV/FX/INVERTER-----P01search 8 cyclespulse lengthDOWN INC DEC PORT

    ADV/FX/INVERTER------P01search 60 cyclespulse spacingDOWN INC DEC PORT

    ADV/FX/INVERTER------P01low battery 21.0 Vdccutout set pointDOWN INC DEC PORT

    ADV/FX/INVERTER------P01low battery 25.0 Vdccutin set pointDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01float 1.0 hrstime limitDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01equalize 1.0 hrstime limitDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01equalize 28.8 Vdcset pointDOWN INC DEC PORT

    ADV/FX/CHARGER-------P01charger programming

    completedTOP ADV MAIN

    Main Screen

    ADV/FX/INVERTER------P01adjust 120 Vacoutput voltageDOWN INC DEC PORT

    Accessing the Advanced Menu:

    ADV--------------------choose device

    FX CC DC MATE

    Changing more detailed operating parameters requires access to the Advanced Setup Menu.

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    Main Screen

    Advanced Menu for Inverter (Page 1 of 3)

    ADV/FX/CHARGER-------P01refloat 25.0 Vdcset pointDOWN INC DEC PORT

    Resetting the Inverter to Factory Defaults

    SETUP/FX/INPUT-------P01ac transfer controlDOWN GRID GEN PORT

    1

    SETUP/FX/INPUTAc2/gen 30.0 aaclimitDOWN INC DEC PORT

    SETUP/FX/INPUT---------Input setup completed

    TOP SETUP MAIN

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    ADV/SETTINGS/WARNINGchanges made could adversely affect

    system performance

    ADV/PASSOWRD------------Enter the password

    132ENTER INC DEC EXIT

    ADV/PASSOWRD------------Enter the password

    141ENTER INC DEC EXIT

    A 1. Press the soft key until “141” is displayed on the LCD.

    2. Press the soft key to accept the password and move forward to the Device Selection Menu.

    A

    B

    B

    To return to the Main screen at any time:

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • INVE

    RTE

    R

    (continued)

    900-0131-01-00 Rev A.vsd\INV Setup 2\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 7

    ADV/FX/PAGE2--------P01choose category

    ADV GRID GEN PG3

    ADV/FX/GRID---------P01ac 1/grid 108 Vac lower limitDOWN INC DEC PORT

    ADV/FX/GRID---------P01ac 1/grid 140 Vacupper limitDOWN INC DEC PORT

    ADV/FX/GRID---------P01ac 1/grid 48.0 Aacinput limitDOWN INC DEC PORT

    ADV/FX/GRID---------P01ac 1/grid 6 cyclestransfer delayDOWN INC DEC PORT

    ADV/FX/GRID---------P01grid programming

    completedTOP ADV MAIN

    ADV/FX/GEN----------P01gen input 00.5 minconnect delayDOWN INC DEC PORT

    ADV/FX/GEN----------P01ac 2/gen 108 Vaclower limitDOWN INC DEC PORT

    ADV/FX/GEN----------P01ac 2/gen 140.0 Aacupper limitDOWN INC DEC PORT

    ADV/FX/GEN----------P01ac 2/gen 48.0 Aacinput limitDOWN INC DEC PORT

    ADV/FX/GEN----------P01ac 2/gen ONsupportDOWN INC DEC PORT

    ADV/FX/GEN----------P01ac 2/gen 60cycles transfer delayDOWN INC DEC PORT

    ADV/FX/GEN----------P01gen programming

    completedTOP ADV MAIN

    ADV/FX/PAGE4---------P01choose category

    PG3 SELL CAL MAIN

    ADV/FX/SELL----------P01sell re 23.6 VdcvoltsDOWN INC DEC PORT

    ADV/FX/SELL----------P01grid tie IEEEwindowDOWN IEEE USER PORT

    ADV/FX/SELL----------P01selling

    setup completedTOP ADV MAIN

    ADV/FX/SELL----------P01grid tie GRIDTIEauthorityDOWN IEEE USER PORT

    ADV/FX/AUX-----------P01loadshed 22.0 Vdcoff set pointDOWN INC DEC PORT

    ADV/FX/AUX-----------P01vent fan 26.0 Vdcon set pointDOWN INC DEC PORT

    ADV/FX/AUX-----------P01vent fan off 5 minperiodDOWN INC DEC PORT

    ADV/FX/AUX-----------P01diversion 29.2 Vdcon set pointDOWN INC DEC PORT

    ADV/FX/AUX-----------P01diversion 30 secoff delayDOWN INC DEC PORT

    ADV/FX/AUX-----------P01aux output

    setup completedTOP ADV MAIN

    ADV/FX/PAGE3---------P01choose category

    PG2 AUX STACK PG4

    ADV/FX/AUX-----------P01aux output AUTOcontrolDOWN INC DEC PORT

    ADV/FX/AUX-----------P01aux output cool fanfunctionDOWN INC DEC PORT

    ADV/FX/AUX-----------P01genalert 22.0 Vdcon setpointDOWN INC DEC PORT

    ADV/FX/AUX-----------P01genalert 4 minon delayDOWN INC DEC PORT

    ADV/FX/AUX-----------P01genalert 28.0 Vdcoff set pointDOWN INC DEC PORT

    ADV/FX/AUX-----------P01genalert 9 minoff delayDOWN INC DEC PORT

    ADV/FX/CALIBRATE-----P01Vac input 120 vacadjustmentDOWN INC DEC PORT

    ADV/FX/CALIBRATE-----P01Vac output 120 VacadjustmentDOWN INC DEC PORT

    ADV/FX/CALIBRATE-----P01calibration

    setup completedTOP ADV MAIN

    ADV/FX/CALIBRATE-----P01battery Vdc 25.4 VdcadjustmentDOWN INC DEC PORT

    Advanced Inverter Setup Menu (continued)

    NOTE: The values shown in this illustration will vary depending on the model of inverter.

    ADV/FX/PAGE1choose category

    ADV INV CHRG PG2

    ADV/FX/STACK---------P01stack 1-2PH MasterphaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01stack Classic SlavephaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01stack OB Slave L1phaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01stack OB Slave L2phaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01stack 3PH MasterphaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01stack 3 PH SlavephaseDOWN INC DEC PORT

    ADV/FX/STACK---------P01power save level 0master adjust onlyDOWN INC DEC PORT

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    ADV/FX/STACK---------P01stacking

    setup completedTOP ADV MAIN

    ADV/FX/STACK---------P01power save level 0slave adjust onlyDOWN INC DEC PORT

    Continued from previous page….

    Page 2

    Page 3

    Page 4

    Page 1MAIN-------------------

    3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • CH

    AR

    GE

    CO

    NTR

    OLL

    ER

    900-0131-01-00 Rev A.vsd\CC Setup on MATE\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 8

    Accessing the Advanced Menu:

    Changing more detailed operating parameters requires access to the Advanced Setup Menu. Advanced Menu for the

    FLEXmax Charge Controller (Page 1 of 2)

    ADV/CC/CHGR----------P02output current 80.0 A limitDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02MPPT mode auto trackDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02grid tie mode

    nonGTDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02park MPP 77.0%

    DOWN INC DEC PORT

    ADV/CC/ADVANCED------P02Mpp range limit %VOCmaximum 90%DOWN INC DEC PORT

    ADV/CC/ADVANCED------P02rebulk voltage

    24.8 VdcDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02vbatt calibration

    29.3 Vdc 0.0 VdcDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02RTS compensation

    wideDOWN INC DEC PORT

    ADV/CC/ADVANCED------P02RTS comp limitupper limit 28.2 VdcDOWN INC DEC PORT

    ADV/CC/EQ------------P02eq voltage 28.8 VOC

    DOWN INC SETUP ADV

    ADV/CC/EQ------------P02eq time 1 hours

    DOWN INC SETUP ADV

    ADV/CC/EQ------------P02 end CC eq menu

    TOP ADV MAIN

    ADV/CC/EQ------------P02eq auto eq interval

    0 daysDOWN INC SETUP ADV

    ADV/CC/AUX-----------P02vent fan

    DOWN INC SET PORT

    ADV/CC/AUX-----------P02aux control OFF

    DOWN ON OFF PORT

    ADV/CC/aux-----------P02 end of menu

    TOP ADV MAIN

    ADV/CC/CHRG----------P02absorb voltage 28.8 V

    DOWN INC DEC PORT

    ADV/CC/CHRG----------P02float voltage 27.2 V

    DOWN INC DEC PORT

    ADV/FX/CHRG----------P02 end charger menu

    TOP ADV MAIN

    ADV/CC/ADVANCED------P02snooze mode

  • FLEX

    net D

    C

    900-0131-01-00 Rev A.vsd\FNDC\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 9

    Main ScreenMAIN----------------

    3:02:14P

    SUM STATUS SETUP ADV

    E -------------- FBattery Discharging

    State of Charge 100%

    DC Now 25.4V 100%IN 0.4A 0.010kWOUT 1.6A 0.040kWBAT -1.2A -0.030kW

    DC Today minSOC 97%In 247AH 12.84kWHOut 240AH 12.50kWHBat 7AH 0.34kWH

    DC BAT 25.4V 100%Bat -0.3A -0.010kWNet 0.4AH 0.00kWHDays Since Full 1.1

    FX Total 25.4V 97%Inverting 0.000kWAC Loads 0.000kWBuying $ 0.000kW

    State-of-Charge Screen

    Summary Screen #1

    Summary Screen #2

    Summary Screen #3

    Summary Screen #4

    Press this soft key to proceed. This screen will also automatically move forward after a user-defined period of time.

    1

    1

    1

    1

    STATUS------------------choose device:

    FX CC DC MAIN

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    Main Screen

    NOTE: The values shown in this illustration will vary depending on the model of inverter.

    STATUS/DC/PAGE 1-------

    STATSMETER SHUNT BATT PG2

    A: 0.1 A 0.001 kWB: 0.0 A 0.000 kWC: 0.0 A 0.000 kWDOWN STATUS

    A: -1 Ah 0.100 kWHB: 0 Ah 0.000 kWHC: 0 Ah 0.000 kWHDOWN UP TOP

    METER/DC/SHUNT Aremoved

    12 AH 0.16 kWHDOWN UP TOP

    METER/DC/SHUNT Acharged

    12 AH 0.16 kWHDOWN UP TOP

    STATUS/DC/SHUNT Amax removedamps 0.9DOWN UP RESET TOP

    STATUS/DC/SHUNT Amax removedkWatts 0.010DOWN UP RESET TOP

    STATUS/DC/SHUNT Amax chargedamps 10.1DOWN UP RESET TOP

    STATUS/DC/SHUNT Amax chargedkWatts 0.129DOWN UP RESET TOP

    STATUS/DC/SHUNT Bmax removedamps 0DOWN UP RESET TOP

    STATUS/DC/SHUNT Bmax chargedamps 30.2DOWN UP RESET TOP

    STATUS/DC/SHUNT Bmax chargedkWatts 2.040DOWN UP RESET TOP

    STATUS/DC/BATTtotal days at 100%

    0.5DOWN UP RESET TOP

    STATUS/DC/BATTdays since chargeparameters met 5.9DOWN UP TOP

    STATUS/DC/BATTbattery min today

    24.8 VdcDOWN UP RESET TOP

    STATUS/DC/SHUNT Bmax chargedamps 39.8DOWN UP RESET TOP

    METER/DC/SHUNT Bremoved

    0 AH 0 kWHDOWN UP TOP

    METER/DC/SHUNT Bcharged

    12 AH 0.16 kWHDOWN UP TOP

    METER/FN/METERDC firmware revision

    000.00/040DOWN UP TOP

    STATUS/DC/SHUNTend of shuntstatus menu

    UP TOP STATUS

    STATUS/DC/BATTbattery max today

    25.4 VdcDOWN UP RESET TOP

    STATUS/DC/BATTtemp comp’d battsetpoint 28.4 VdcDOWN UP TOP

    STATUS/DC/BATTsystem batterytemperature 29°CDOWN UP TOP

    STATUS/DC/BATTcycle chargefactor 78%DOWN UP TOP

    STATUS/DC/BATTcycle kWhr chargeefficiency 65%DOWN UP TOP

    STATUS/DC/BATTlifetime kAH removed 5

    DOWN UP RESET TOP

    STATUS/DC/BATTend of batterystatus menuUP TOP STATUSMETER/FN/METER

    end of meter menu

    UP TOP STATUS

    STATUS/DC/SHUNT Cmax removedamps 0DOWN UP RESET TOP

    STATUS/DC/SHUNT Cmax chargedamps 30.2DOWN UP RESET TOP

    STATUS/DC/SHUNT Cmax chargedkWatts 2.040DOWN UP RESET TOP

    STATUS/DC/SHUNT Cmax chargedamps 39.8DOWN UP RESET TOP

    METER/DC/SHUNT Cremoved

    0 AH 0 kWHDOWN UP TOP

    METER/DC/SHUNT Ccharged

    0 AH 0.00 kWHDOWN UP TOP

    STATUS/DC/PAGE2--------

    PG1 AUX MAIN

    STATUS/DC/AUX---------aux control

    manualDOWN STATUS

    STATUS/DC/PAGE2-------aux relay state: OFF

    UP STATUS

    These screens are informational only. No changes can be made from this location in the Menu Map.

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • (continued)

    900-0131-01-00 Rev A.vsd\FNDC Adv\2012-03-21©2012 OutBack Power Technologies. All Rights Reserved. Page 10

    NOTE: The values shown in this illustration will vary depending on the model of inverter.

    ADV/DC/BAT----------P03battery capacity110 amphoursTOP INC DEC ADV

    ADV/DC/PAGE1choose category

    ADV BAT SHUNT PG2

    ADV/DC/SHUNT--------P03shunt A mode enabled

    DOWN EN DIS TOP

    ADV/DC/SHUNT--------P03shunt B mode enabled

    DOWN EN DIS TOP

    ADV/DC/SHUNT--------P03shunt C mode disabled

    DOWN EN DIS TOP

    ADV/DC/SHUNT--------P03shunt setup complete

    TOP ADV MAIN

    ADV/DC/PG2choose category

    PG1 CHARGE AUX PG3

    ADV/DC/CHARGEreturn amps 10.4

    DOWN INC DEC TOP

    ADV/DC/CHARGEbattery voltage 26.0

    DOWN INC DEC TOP

    ADV/DC/CHARGEparameters met time

    1 minutesDOWN INC DEC TOP

    ADV/DC/CHARGEcharge factor 93%

    DOWN INC DEC TOP

    ADV/DC/AUXCONTROLcurrently MAN-OFF

    DOWN OFF AUTO ON

    ADV/DC/AUXCONTROLhigh volts 29.0 Vdc

    DOWN INC DEC TOP

    ADV/DC/AUXCONTROLlow volts 22.0 Vdc

    DOWN INC DEC TOP

    ADV/DC/AUXCONTROLSOC high 90%

    DOWN INC DEC TOP

    ADV/DC/AUXCONTROLSOC low 59%

    DOWN INC DEC TOP

    ADV/DC/AUXCONTROLhigh set point delay

    1 minutesDOWN INC DEC TOP

    ADV/DC/AUXCONTROLlow set point delay

    1 minutesDOWN INC DEC TOP

    ADV/DC/AUXCONTROLinvert logic YES

    DOWN YES NO TOP

    ADV/DC/AUXCONTROLaux parameterscomplete

    TOP ADV MAIN

    Accessing the Advanced Menu:

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    ADV/SETTINGS/WARNINGchanges made could adversely affect

    system performance

    ADV/PASSWORD------------Enter the password

    132ENTER INC DEC EXIT

    ADV/PASSWORD------------Enter the password

    141ENTER INC DEC EXIT

    ADV--------------------choose device

    FX CC DC MATE

    MAIN--------------------3:02:14P

    SUM STATUS SETUP ADV

    ADV/DC/PG3---------P03choose category

    PG2 RESET CLR MAIN

    ADV/DC/RESET-------P03reset DC to factorydefaults?

    NO YES TOP

    ADV/DC/CLEARclear data logmemory?

    YES NO TOP

    FLEX

    net D

    C

    ADV/DC/CHARGEcharge parameterscomplete

    TOP ADV MAIN

    MAIN-------------------3:02:14P

    SUM STATUS SETUP ADV

    To return to the Main screen at any time:

    Press and hold the 2 left soft keys at the same time. Release when the Main screen appears.

  • About OutBack Power TechnologiesOutBack Power Technologies is a leader in advanced energy conversion technology. Our products include true sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems.

    Contact InformationTelephone: +1.360.435.6030 (Main)

    +1.360.618.4363 (Technical Support)+1.360.435.6019 (Fax)

    Mailing Address: OutBack Power Technologies Sales & Marketing5917 - 195th Street N.E. 6115 – 192nd Street NEArlington, WA 98223 USA Arlington, WA 98223 USA

    E-mail: [email protected]

    Web Site: www.outbackpower.com

    DisclaimerUNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES:

    (a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.

    (b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.

    Warranty SummaryOutBack Power Technologies warrants that the products it manufactures will be free from defects in materials and workmanship for a period of five (5) years subject to the conditions set forth in the warranty detail, found in the product manual.

    OutBack Power Technologies cannot be responsible for system failure, damages, or injury resulting from improper installation of their products.

    Notice of CopyrightMATE Series Overview © January 2012 by OutBack Power Technologies. All Rights Reserved.

    TrademarksOutBack Power is a registered trademark of OutBack Power Technologies.

    Date and RevisionJanuary 2012, Revision A

    Part Number900-0131-01-00 Rev A

  • North America:5917 - 195th Street N.E. Arlington, WA USA+1.360.435.6030900-0131-01-00 Rev A

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 150 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages false /GrayImageDownsampleType /Bicubic /GrayImageResolution 150 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages false /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description >>> setdistillerparams> setpagedevice