symbols list abbreviations wiring devices power

5
WIRING DEVICES JUNCTION BOX, WALL MOUNTED, +18" UON. JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX. JUNCTION BOX, MOUNTED FLUSH IN CEILING. JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO STRUCTURE IN ACCESSIBLE CEILING SPACE. JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON. SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON. DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON. DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON. DENOTES WALL MOUNTED OVER COUNTER, 6" ABOVE BACK SPLASH UON. BUT NO HIGHER THAN ADA REQUIREMENTS. 'G' DENOTES GROUND FAULT CURRENT INTERRUPTER (GFCI), 'A' DENOTES ARC FAULT CURRENT INTERRUPTER (AFCI). DUPLEX CONVENIENCE RECEPTACLE DEVICE WITH INTEGRAL USB PORTS, WALL MOUNTED,+ 18" UON. DUPLEX RECEPTACLE, WEATHER RESISTANT WITH GROUND FAULT CURRENT INTERRUPTER 'GFCI', WITH WEATHERPROOF COVER, WALL MOUNTED, +18" UON. SHADING DENOTES SPLIT WIRED DEVICE. SHADING DENOTES DEVICE CONNECTED TO EMERGENCY POWER CIRCUIT. SHADING DENOTES DEVICE CONTROLLED PER CA T24 130.5(d). HORIZONTALL MOUNTED DUPLEX RECEPTACLE, +18" UON. SHADING DENOTES SPECIALTY DEVICE, TYPE AS NOTED ON PLANS. DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX. DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX. DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING. DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE- THRU FLOOR FITTING. DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING. DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING. DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON. DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLOOR MONUMENT. COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS. DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE ABOVE. TYPE AS NOTED ON PLANS. ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON. CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP JUNCTION BOX, SINGLE GANG RING, AND STAINLESS STEEL COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP. ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION FEEDS, MOUNTED IN FLUSH FLOOR BOX WITH KO'S IN COVER TO ACCEPT FURNITURE WHIPS ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE- THRU FLOOR FITTING WITH KO IN COVER TO ACCEPT FURNITURE WHIP. POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING. TYPE AS NOTED ON PLANS. SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON. THREE-WAY SWITCH, WALL MOUNTED, +42" UON. FOUR-WAY SWITCH, WALL MOUNTED, +42" UON. KEY-OPERATED, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON. PILOT LIGHT, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON. MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD ELEMENT, MOUNTED ADJACENT TO MOTOR. MANUAL MOTOR STARTER/DISCONNECT SWITCH, MOUNTED ADJACENT TO MOTOR. SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER THIS DIVISION, WALL MOUNTED, +42" UON. WALLBOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DERATING WHEN INSTALLED GANGED LOCATIONS. SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON. SINGLE-POLE, SINGLE-THROW, EXPLOSION PROOF SWITCH, WALL MOUNTED, +42" UON. LINE VOLTAGE SINGLE RELAY VACANCY SENSOR, WALL MOUNTED, +42" UON. SINGLE-POLE SWITCH WITH WEATHERPROOF COVER, WALL MOUNTED, +42" UON. LINE-VOLTAGE MULTIPLE GANG SWITCHING STATION, WALL MOUNTED, 42" UON. REFER TO PLANS FOR DEVICE QUANTITIES AND TYPES. LOW-VOLTAGE LIGHTING CONTROL SWITCHING STATION, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR DEVICE QUANTITIES AND RELAYS CONTROLLED LIGHTING CONTROL OCCUPANCY SENSOR WITH DUAL LEVEL SWITCHING, WALL MOUNTED, +42" UON. LIGHTING CONTROL OCCUPANCY SENSOR WITH SINGLE LEVEL SWITCHING, WALL MOUNTED, +42" UON. LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED FOR AREA COVERAGE. PRESET SCENE CONTROL LIGHTING STATION WITH DIMMING CAPABILITIES, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR CONTROL. EGRESS LIGHTING TRANSFER DEVICE CONTROL STATION, WALL MOUNTED, +42" UON. PHOTOELECTRIC CELL DAYLIGHT SENSOR SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED. SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING. COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED. COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING. REMOTE 2-WAY COMMUNICATION STATION, MOUNTED +42" AFF. J J J J J G P P T P S S S S S S S S S S S S 3 4 K P T M F D TC EP L M M1 M D ETD PC DS WP U S S EP V S S S/C S/C RACEWAYS CONDUIT RUN EXPOSED ON WALL OR CEILING. CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND. CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING. CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET. CONDUIT FLEXIBLE METALLIC CONDUIT. CONDUIT TURNED UP CONDUIT TURNED DOWN. CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS. CONDUIT SLEEVE, WITH INSULATING BUSHINGS. CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS): 1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON. 2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG CONDUCTORS, UON. 3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10 AWG CONDUCTORS, UON. SYMBOLS LIST NUMBERED NOTE, APPLIES TO ALL DRAWINGS. NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY. OVERCURRENT PROTECTIVE DEVICE SPACE IDENTIFICATION TAG. REFERS TO LOCATION OF PROTECTIVE OR CONTROL DEVICE WITHIN SWITCHBOARDS, DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC. EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER ANOTHER SECTION AND WIRED UNDER THIS SECTION. CABLE AND/OR RACEWAY TAG, FUNCTION AS NOTED BELOW: P = POWER T = TELEPHONE C = COMMUNICATION FEEDER SIZE. REFER TO FEEDER SCHEDULE. DETAIL REFERENCE: SHEET NUMBER DETAIL DESIGNATION FIXTURE IDENTIFICATION TAG: FIXTURE TYPE QUANTITY 1 1 1 NAME 2004 E-801 A 2-F3 P2 CONVENTIONS A AMPERES AFI ARC FAULT CIRCUIT INTERRUPTER AF AMPERE OVERCURRENT FRAME SIZE (WHEN APPLIED TO CIRCUIT BREAKERS) OR AMPERE FUSE SIZE (WHEN APPLIED TO FUSES) AFF ABOVE FINISHED FLOOR AIC ASYMMETRIC INTERRUPTING CURRENT AL ALUMINUM AT AMPERE OVERCURRENT TRIP (WHEN APPLIED TO CIRCUIT BREAKERS) ATS AUTOMATIC TRANSFER SWITCH BAS BUILDING AUTOMATION SYSTEM BPS BOLTED PRESSURE CONTACT SWITCH C CONDUIT CCTV CLOSED CIRCUIT TELEVISION CEC CALIFORNIA ELECTRICAL CODE CL CURRENT LIMITING CIRCUIT BREAKER OR FUSE CP CIRCULATION PUMP CT CURRENT TRANSFORMER CU COPPER DF DRINKING FOUNTAIN DW DISH WASHER (E) EXISTING TO REMAIN EC ELECTRICAL CONTRACTOR EF EXHAUST FAN EP EXPLOSION PROOF EPO EMERGENCY POWER OFF EMCS ENERGY MANAGEMENT CONTROLS SYSTEM EMT ELECTRICAL METALLIC TUBING ETD EMERGENCY TRANSFER DEVICE EWH ELECTRIC WATER HEATER F FUSED (F) FUTURE FACP FIRE ALARM CONTROL PANEL FFCP FIREMAN'S FAN CONTROL PANEL FLA FULL LOAD AMPERES FMC FLEXIBLE METAL CONDUIT FSD FIRE/SMOKE DAMPER FRAP FIREMAN'S REMOTE ANNUNCIATOR PANEL G GROUND GB GROUND BUS GD GARBAGE DISPOSAL GFCI GROUND FAULT CIRCUIT INTERRUPTER GND GROUND GRAP GENERATOR REMOTE ANNUNCIATOR PANEL HNC HOME NETWORK CABINET HPC HIGH PRESSURE CONTACT SWITCH IMC INTERMEDIATE METAL CONDUIT IWH INSTANTANEOUS OR POINT OF USE WATER HEATER LCP LIGHTING CONTROL PANEL MBGB MAIN BUILDING GROUND BUS MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MLO MAIN LUGS ONLY MT EMPTY MTC EMPTY CONDUIT MTS MANUAL TRANSFER SWITCH MW MIRCOWAVE (N) NEW NC NORMALLY CLOSED NF NON-FUSED NIEC NOT IN ELECTRICAL CONTRACT NO NORMALLY OPEN NTS NOT TO SCALE OC ON CENTER OFCI OWNER FURNISHED CONTRACTOR INSTALLED PDZ PRIMARY DAYLIGHT ZONE PNL PANEL PT POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE RF REFRIGERATOR (R) EXISTING TO BE REMOVED (RR) REMOVE AND RELOCATE RGB REFERENCE GROUND BUS RSC RIGID STEEL CONDUIT SAD SEE ARCHITECTURAL DRAWINGS TC TIME CLOCK TP TWISTED-PAIR SDZ SECONDARY DAYLIGHT ZONE SPD SURGE PROTECTION DEVICE TX TRANSFORMER TYP TYPICAL UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UR UNDERCOUNTER REFRIGERATOR V VOLTS VA VOLTS-AMPS VFD VARIABLE FREQUENCY DRIVE VM VENDING MACHINE WAP WIRELESS ACCESS POINT WP WEATHERPROOF 2SP TWO SPEED 1 PHASE 3 PHASE 1P 1 POLE 2P 2 POLE 3P 3 POLE 3W 3 WIRE 4W 4 WIRE ABBREVIATIONS SOME OF THE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECT POWER DISTRIBUTION SWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL CENTER, FLOOR MOUNTED. PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL. PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL. PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL. PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL. DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 3θ,480-120/208V, UON. ELECTRIC MOTOR, NIEC. MAKE POWER CONNECTIONS ONLY AS NOTED ON PLANS. INDOOR EXHAUST FAN MOTOR, SINGLE PHASE. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTED MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO FAN WITH 2 #12 CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR. INDOOR FAN POWERED VAV BOX MOTOR, SINGLE PHASE, MOUNTED FROM STRUCTURE ABOVE, NIEC. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTED MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO VAV BOX WITH 2 #12 CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR. PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS. SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS: A: 30A, NON-FUSED AF: 30A, FUSED B: 60A, NON-FUSED BF: 60A, FUSED C: 100A, NON-FUSED CF: 100A, FUSED D: 200A, NON-FUSED DF: 200A, FUSED E: 400A, NON-FUSED EF: 400A, FUSED F: 600A, NON-FUSED FF: 600A, FUSED G: 800A, NON-FUSED GF: 800A, FUSED MAGNETIC MOTOR STARTER. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER. COMBINATION MAGNETIC MOTOR STARTER/SAFETY DISCONNECT SWITCH. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER. PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS. VARIABLE FREQUENCY DRIVE FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS. VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS. ELECTRONICALLY COMMUTATED MOTOR CONTROLLER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS. ELECTRONICALLY COMMUTATED MOTOR CONTROLLER WITH INTEGRAL CIRCUIT BREAKER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS. DRIVEN GROUND ROD. DRIVENG ROUND ROD IN GROUND WELL WITH COVER. ELECTRICAL VEHICLE CHARGING STATION, WALL MOUNTED. ELECTRICAL VEHICLE CHARGING STATION, PEDESTAL MOUNTED. INDICATES TERMINATION POINT FOR POWER CABLE & BUS. BOLTED PRESSURE OR HIGH PRESSURE CONTACT SWITCH OR FUSED SWITCH. MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH. GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER. INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER. INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER. MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER. INDICATES INTEGRAL GROUND FAULT RELAY WHEN ASSOCIATED WITH CIRCUIT BREAKER. INDICATES COMMUNICATION NETWORK WIRING WHEN ASSOCIATED WITH CIRCUIT BREAKER. INDICATES ELECTRICALLY OPERATED WHEN ASSOCIATED WITH CIRCUIT BREAKER. INDICATES SHUNT TRIP WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES. INDICATES KIRK-KEY INTERLOCK WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES. ADJACENT NUMBER CORRESPONDS WITH DEVICE INTERLOCK. GROUND FAULT RELAY WITH SHUNT TRIP. GROUND FAULT ALARM, NO SHUNT TRIP. UTILITY METER. PRIVATE METER. TRANSFORMER. CONNECTION TO GROUND. CURRENT TRANSFORMERS. POTENTIAL TRANSFORMERS. AUTOMATIC OR MANUAL TRANSFER SWITCH. AUTOMATIC TRANSFER/BY-PASS ISOLATION SWITCH. EMERGENCY GENERATOR. BATTERIES. NEUTRAL SERVICE DISCONNECT LINK. SURGE PROTECTION DEVICE, 'SPD'. CONTROL CONTACTOR. NORMALLY OPEN CONTACT. NORMALLY CLOSED CONTACT. DIGITAL METERING UNIT. GROUND BUS. WATT HOUR METER. NEUTRAL BUS. F V P AF A 1 1 VFD VFD WHM NEU DMU GND C SPD G M GFA GFR 1 K ST EO C 52 G M ECM ECM Sheet Index SHEET NO. SHEET NAME SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS SUBMITTAL 04 E001 SYMBOLS, ABBREVIATIONS AND SHEET INDEX E002 SCHEDULES & PROJECT NOTES E100 ELECTRICAL SITE PLAN E200 POWER ONE-LINE E300 ROOM/AREA DETAILS R S R E G I S T E R E D P R O F ES S I O N A L E N G I N E E A T A T E O F C A L I F O R N I ELECTRICAL CONSULTING ENGINEERS REVISIONS DESIGNER: SCALE: DATE: TITLE: DRAWING NO. 1125 HIGH STREET AUBURN, CA 95603 (530) 886 - 8556 #E015491 Exp. 06/30/21 SCOTT WHEELER Designer 06 - 15 - 2020 SYMBOLS, ABBREVIATIONS AND SHEET INDEX E001 NEVADA UNION HIGH SCHOOL CAMPUS POWER ONE LINE AND SITE DISTRIBUTION PHASE - 2 FEEDER SCHEDULE FEEDER SCHEDULE GENERAL NOTES 1. COPPER FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH THHN/THWN-2 INSULATION IN EMT CONDUIT. 2. ALUMINUM FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH XHHW-2 INSULATION IN EMT CONDUIT. 3. FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON AN AMBIENT TEMPERATURE OF 30 DEGREES C (86 DEGREES F). 4. FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED SIZE GROUND CONDUCTOR IN EACH CONDUIT. 5. PER CEC ARTICLE 110.14, ALL FEEDERS SIZED AT #2 AWG OR LESS ARE CALCULATED PER 60 DEGREE TABLE. FEEDERS GREATER THAN #2 AWG ARE RATED 75 DEGREE. FEEDER SCHEDULE REMARKS A. OVERSIZED 150% NEUTRAL, SUITABLE FOR SERVICE FROM K-13 RATED TRANSFORMERS. B. FEEDER APPROVED FOR USE WITH SEPARATELY DERIVED SYSTEM; GROUNDING AS REQUIRED BY CEC ARTICLES 240 AND 250. C. FEEDER GROUND AND BONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OF THE AREA OF THE LARGEST PHASE CONDUCTOR. D. INCREASE CONDUIT TO THE NEXT LARGER TRADE SIZE WHEN USING SCHEDULE 40 OR 80 PVC CONDUIT. E. PER CEC SECTION 240.4(B), THE NEXT HIGHER STANDARD OVERCURRENT DEVICE RATING (ABOVE THE AMPACITY OF THE CONDUCTORS) CAN BE USED. RULE CAN NOT BE APPLIED IF 100% RATED BREAKERS ARE USED. F. PER CEC 240.21(C), THE PROVISIONS OF 240.4(B) SHALL NOT BE PERMITTED FOR TRANSFORMER SECONDARY CONDUCTORS. FEEDER TAG FEEDER DESCRIPTION CONDUIT CONDUCTORS SEPARATELY DERIVED SYSTEM REMARKS PHASE/NEUTRAL GROUND GROUNDING ELECTRODE BONDING JUMPER 153 15 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - - 203 20 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - - 204 20 AMP, 3 PHASE, 4 WIRE 1-0.75" 4 #12 CU 1 #12 CU - - 403 40 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #8 CU 1 #10 CU - - - 504 50 AMP, 3 PHASE, 4 WIRE 1-1.00" 4 #6 CU 1 #8 CU #8 CU IN 0.75" C. #8 CU B 703 70 AMP, 3 PHASE, 3 WIRE 1-1.00" 3 #4 CU 1 #8 CU - - D 704 70 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #4 CU 1 #10 CU - - - 904 90 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #3 CU 1 #8 CU - - - 1004 100 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #2 CU 1 #8 CU - - E 1254 125 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #1 CU 1 #6 CU - - - 1503 150 AMP, 3 PHASE, 3 WIRE 1-1.50" 3 #1/0 CU 1 #6 CU - - - 1504 150 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #1/0 CU 1 #6 CU - - D 1754 175 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #2/0 CU 1 #6 CU - - - 2004 200 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #3/0 CU 1 #6 CU - - - 2254 225 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #4/0 CU 1 #4 CU - - - 2504 250 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #250 KCMIL CU 1 #4 CU - - D 3004 300 AMP, 3 PHASE, 4 WIRE 1-3.00" 4 #350 KCMIL CU 1 #4 CU - - D 4003 400 AMP, 3 PHASE, 3 WIRE 1-3.00" 3 #500 KCMIL CU 1 #2 CU - - D 4004 400 AMP, 3 PHASE, 4 WIRE 1-4.00" 4 #500 KCMIL CU 1 #2 CU - - D 4503 450 AMP, 3 PHASE, 3 WIRE 2-2.50" 2 SETS OF 3 #4/0 CU 1 #2 CU/SET - - - 6004 600 AMP, 3 PHASE, 4 WIRE 2-3.00" 2 SETS OF 4 #350 KCMIL CU 1 #1 CU/SET - - D 8004 800 AMP, 3 PHASE, 4 WIRE 2-3.50" 2 SETS OF 4 #600 KCMIL CU 1 #1/0 CU/SET - - D T4004 400 AMP, 3 PHASE, 4 WIRE 2-2.00" 2 SETS OF 4 #4/0 CU 1 #1/0 CU/SET #1/0 CU IN 0.75" C. #1/0 CU B,F T10004 1032 AMP, 3 PHASE, 4 WIRE 3-3.00" 3 SETS OF 3 #500 KCMIL CU, 2 #300 KCMIL CU NEU./SET #3/0 CU/SET #3/0 CU IN 1.00" C. #3/0 CU A,B,C,D,F # DESCRIPTION DATE

Upload: others

Post on 26-Jan-2022

23 views

Category:

Documents


0 download

TRANSCRIPT

WIRING DEVICESJUNCTION BOX, WALL MOUNTED, +18" UON.

JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX.

JUNCTION BOX, MOUNTED FLUSH IN CEILING.

JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO STRUCTURE IN ACCESSIBLE CEILING SPACE.

JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.

SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.

DENOTES WALL MOUNTED OVER COUNTER, 6" ABOVE BACK SPLASH UON. BUT NO HIGHER THAN ADA REQUIREMENTS.

'G' DENOTES GROUND FAULT CURRENT INTERRUPTER (GFCI), 'A' DENOTES ARC FAULT CURRENT INTERRUPTER (AFCI).

DUPLEX CONVENIENCE RECEPTACLE DEVICE WITH INTEGRAL USB PORTS, WALL MOUNTED,+ 18" UON.

DUPLEX RECEPTACLE, WEATHER RESISTANT WITH GROUND FAULT CURRENT INTERRUPTER 'GFCI', WITH WEATHERPROOF COVER, WALL MOUNTED, +18" UON.

SHADING DENOTES SPLIT WIRED DEVICE.

SHADING DENOTES DEVICE CONNECTED TO EMERGENCY POWER CIRCUIT.

SHADING DENOTES DEVICE CONTROLLED PER CA T24 130.5(d).

HORIZONTALL MOUNTED DUPLEX RECEPTACLE, +18" UON.

SHADING DENOTES SPECIALTY DEVICE, TYPE AS NOTED ON PLANS.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLOOR MONUMENT.

COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE ABOVE. TYPE AS NOTED ON PLANS.

ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON. CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP JUNCTION BOX, SINGLE GANG RING, AND STAINLESS STEEL COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP.

ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION FEEDS, MOUNTED IN FLUSH FLOOR BOX WITH KO'S IN COVER TO ACCEPT FURNITURE WHIPS

ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING WITH KO IN COVER TO ACCEPT FURNITURE WHIP.

POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING. TYPE AS NOTED ON PLANS.

SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.

THREE-WAY SWITCH, WALL MOUNTED, +42" UON.

FOUR-WAY SWITCH, WALL MOUNTED, +42" UON.

KEY-OPERATED, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.

PILOT LIGHT, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.

MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD ELEMENT, MOUNTED ADJACENT TO MOTOR.

MANUAL MOTOR STARTER/DISCONNECT SWITCH, MOUNTED ADJACENT TO MOTOR.

SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER THIS DIVISION, WALL MOUNTED, +42" UON.

WALLBOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DERATING WHEN INSTALLED GANGED LOCATIONS.

SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON.

SINGLE-POLE, SINGLE-THROW, EXPLOSION PROOF SWITCH, WALL MOUNTED, +42" UON.

LINE VOLTAGE SINGLE RELAY VACANCY SENSOR, WALL MOUNTED, +42" UON.

SINGLE-POLE SWITCH WITH WEATHERPROOF COVER, WALL MOUNTED, +42" UON.

LINE-VOLTAGE MULTIPLE GANG SWITCHING STATION, WALL MOUNTED, 42" UON. REFER TO PLANS FOR DEVICE QUANTITIES AND TYPES.

LOW-VOLTAGE LIGHTING CONTROL SWITCHING STATION, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR DEVICE QUANTITIES AND RELAYS CONTROLLED

LIGHTING CONTROL OCCUPANCY SENSOR WITH DUAL LEVEL SWITCHING, WALL MOUNTED, +42" UON.

LIGHTING CONTROL OCCUPANCY SENSOR WITH SINGLE LEVEL SWITCHING, WALL MOUNTED, +42" UON.

LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED FOR AREA COVERAGE.

PRESET SCENE CONTROL LIGHTING STATION WITH DIMMING CAPABILITIES, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR CONTROL.

EGRESS LIGHTING TRANSFER DEVICE

CONTROL STATION, WALL MOUNTED, +42" UON.

PHOTOELECTRIC CELL

DAYLIGHT SENSOR

SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED.

SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING.

COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED.

COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING.

REMOTE 2-WAY COMMUNICATION STATION, MOUNTED +42" AFF.

J

J

J

J

J

G

P

P T

P

S

S

S

S

S

S

S

S

S

S

S

S

3

4

K

P

T

M

F

D

TC

EP

L

M

M1

M

D

ETD

PC

DS

WP

U

S

SEP

V

S

S

S/C

S/C

RACEWAYSCONDUIT RUN EXPOSED ON WALL OR CEILING.

CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.

CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING.

CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET.

CONDUIT

FLEXIBLE METALLIC CONDUIT.

CONDUIT TURNED UP

CONDUIT TURNED DOWN.

CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS.

CONDUIT SLEEVE, WITH INSULATING BUSHINGS.

CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS):

1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON.2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG CONDUCTORS, UON.3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10 AWG CONDUCTORS, UON.

SYMBOLS LIST

NUMBERED NOTE, APPLIES TO ALL DRAWINGS.

NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY.

OVERCURRENT PROTECTIVE DEVICE SPACE IDENTIFICATION TAG. REFERS TO LOCATION OF PROTECTIVE OR CONTROL DEVICE WITHIN SWITCHBOARDS, DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC.

EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER ANOTHER SECTION AND WIRED UNDER THIS SECTION.

CABLE AND/OR RACEWAY TAG, FUNCTION AS NOTED BELOW:

P = POWER T = TELEPHONE C = COMMUNICATION

FEEDER SIZE. REFER TO FEEDER SCHEDULE.

DETAIL REFERENCE:

SHEET NUMBERDETAIL DESIGNATION

FIXTURE IDENTIFICATION TAG:

FIXTURE TYPEQUANTITY

1

1

1

NAME

2004

E-801

A

2-F3

P2

CONVENTIONS A AMPERES

AFI ARC FAULT CIRCUIT INTERRUPTER

AF AMPERE OVERCURRENT FRAME SIZE (WHEN APPLIED TO CIRCUIT BREAKERS) OR AMPERE FUSE SIZE (WHEN APPLIED TO FUSES)

AFF ABOVE FINISHED FLOOR

AIC ASYMMETRIC INTERRUPTING CURRENT

AL ALUMINUM

AT AMPERE OVERCURRENT TRIP (WHEN APPLIED TO CIRCUIT BREAKERS)

ATS AUTOMATIC TRANSFER SWITCH

BAS BUILDING AUTOMATION SYSTEM

BPS BOLTED PRESSURE CONTACT SWITCH

C CONDUIT

CCTV CLOSED CIRCUIT TELEVISION

CEC CALIFORNIA ELECTRICAL CODE

CL CURRENT LIMITING CIRCUIT BREAKER OR FUSE

CP CIRCULATION PUMP

CT CURRENT TRANSFORMER

CU COPPER

DF DRINKING FOUNTAIN

DW DISH WASHER

(E) EXISTING TO REMAIN

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EP EXPLOSION PROOF

EPO EMERGENCY POWER OFF

EMCS ENERGY MANAGEMENT CONTROLS SYSTEM

EMT ELECTRICAL METALLIC TUBING

ETD EMERGENCY TRANSFER DEVICE

EWH ELECTRIC WATER HEATER

F FUSED

(F) FUTURE

FACP FIRE ALARM CONTROL PANEL

FFCP FIREMAN'S FAN CONTROL PANEL

FLA FULL LOAD AMPERES

FMC FLEXIBLE METAL CONDUIT

FSD FIRE/SMOKE DAMPER

FRAP FIREMAN'S REMOTE ANNUNCIATOR PANEL

G GROUND

GB GROUND BUS

GD GARBAGE DISPOSAL

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRAP GENERATOR REMOTE ANNUNCIATOR PANEL

HNC HOME NETWORK CABINET

HPC HIGH PRESSURE CONTACT SWITCH

IMC INTERMEDIATE METAL CONDUIT

IWH INSTANTANEOUS OR POINT OF USE WATER HEATER

LCP LIGHTING CONTROL PANEL

MBGB MAIN BUILDING GROUND BUS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MLO MAIN LUGS ONLY

MT EMPTY

MTC EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MW MIRCOWAVE

(N) NEW

NC NORMALLY CLOSED

NF NON-FUSED

NIEC NOT IN ELECTRICAL CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

PDZ PRIMARY DAYLIGHT ZONE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

RF REFRIGERATOR

(R) EXISTING TO BE REMOVED

(RR) REMOVE AND RELOCATE

RGB REFERENCE GROUND BUS

RSC RIGID STEEL CONDUIT

SAD SEE ARCHITECTURAL DRAWINGS

TC TIME CLOCK

TP TWISTED-PAIR

SDZ SECONDARY DAYLIGHT ZONE

SPD SURGE PROTECTION DEVICE

TX TRANSFORMER

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UR UNDERCOUNTER REFRIGERATOR

V VOLTS

VA VOLTS-AMPS

VFD VARIABLE FREQUENCY DRIVE

VM VENDING MACHINE

WAP WIRELESS ACCESS POINT

WP WEATHERPROOF

2SP TWO SPEED

1Ø 1 PHASE

3Ø 3 PHASE

1P 1 POLE

2P 2 POLE

3P 3 POLE

3W 3 WIRE

4W 4 WIRE

ABBREVIATIONSSOME OF THE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECT

POWER DISTRIBUTIONSWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL CENTER, FLOOR MOUNTED.

PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL.

PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL.

PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL.

PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL.

DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 3θ,480-120/208V, UON.

ELECTRIC MOTOR, NIEC. MAKE POWER CONNECTIONS ONLY AS NOTED ON PLANS.

INDOOR EXHAUST FAN MOTOR, SINGLE PHASE. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTED MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO FAN WITH 2 #12 CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR.

INDOOR FAN POWERED VAV BOX MOTOR, SINGLE PHASE, MOUNTED FROM STRUCTURE ABOVE, NIEC. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTEDMANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO VAV BOX WITH 2 #12CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR.

PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS.

SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS:A: 30A, NON-FUSED AF: 30A, FUSEDB: 60A, NON-FUSED BF: 60A, FUSEDC: 100A, NON-FUSED CF: 100A, FUSEDD: 200A, NON-FUSED DF: 200A, FUSEDE: 400A, NON-FUSED EF: 400A, FUSEDF: 600A, NON-FUSED FF: 600A, FUSEDG: 800A, NON-FUSED GF: 800A, FUSED

MAGNETIC MOTOR STARTER. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER.

COMBINATION MAGNETIC MOTOR STARTER/SAFETY DISCONNECT SWITCH. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER.

PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDERANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

VARIABLE FREQUENCY DRIVE FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

ELECTRONICALLY COMMUTATED MOTOR CONTROLLER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

ELECTRONICALLY COMMUTATED MOTOR CONTROLLER WITH INTEGRAL CIRCUIT BREAKER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

DRIVEN GROUND ROD.

DRIVENG ROUND ROD IN GROUND WELL WITH COVER.

ELECTRICAL VEHICLE CHARGING STATION, WALL MOUNTED.

ELECTRICAL VEHICLE CHARGING STATION, PEDESTAL MOUNTED.

INDICATES TERMINATION POINT FOR POWER CABLE & BUS.

BOLTED PRESSURE OR HIGH PRESSURE CONTACT SWITCH OR FUSED SWITCH.

MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH.

GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER.

INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.

INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.

MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER.

INDICATES INTEGRAL GROUND FAULT RELAY WHEN ASSOCIATED WITH CIRCUIT BREAKER.

INDICATES COMMUNICATION NETWORK WIRING WHEN ASSOCIATED WITH CIRCUIT BREAKER.

INDICATES ELECTRICALLY OPERATED WHEN ASSOCIATED WITH CIRCUIT BREAKER.

INDICATES SHUNT TRIP WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES.

INDICATES KIRK-KEY INTERLOCK WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES. ADJACENT NUMBER CORRESPONDS WITH DEVICE INTERLOCK.

GROUND FAULT RELAY WITH SHUNT TRIP.

GROUND FAULT ALARM, NO SHUNT TRIP.

UTILITY METER.

PRIVATE METER.

TRANSFORMER.

CONNECTION TO GROUND.

CURRENT TRANSFORMERS.

POTENTIAL TRANSFORMERS.

AUTOMATIC OR MANUAL TRANSFER SWITCH.

AUTOMATIC TRANSFER/BY-PASS ISOLATION SWITCH.

EMERGENCY GENERATOR.

BATTERIES.

NEUTRAL SERVICE DISCONNECT LINK.

SURGE PROTECTION DEVICE, 'SPD'.

CONTROL CONTACTOR.

NORMALLY OPEN CONTACT.

NORMALLY CLOSED CONTACT.

DIGITAL METERING UNIT.

GROUND BUS.

WATT HOUR METER.

NEUTRAL BUS.

F

V

P

AFA

1

1

VFD

VFD

WHM

NEU

DMU

GND

C

SPD

G

M

GFA

GFR

1K

ST

EO

C

52

G

M

ECM

ECM

Sheet Index

SHEET NO. SHEET NAME SC

HE

MA

TIC

DE

SIG

N

DE

SIG

N D

EV

EL

OP

ME

NT

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

SU

BM

ITT

AL 0

4

E001 SYMBOLS, ABBREVIATIONS AND SHEET INDEX

E002 SCHEDULES & PROJECT NOTES

E100 ELECTRICAL SITE PLAN

E200 POWER ONE-LINE

E300 ROOM/AREA DETAILS

R

S

REGIS

TERED

PROFESS I ONAL

ENGINEE

ATATE OF CAL I FORN IELECTRICAL

CONSULTING ENGINEERS

REVISIONS

DESIGNER:

SCALE:

DATE:

TITLE:

DRAWING NO.

1125 HIGH STREETAUBURN, CA 95603(530) 886-8556

#E015491Exp. 06/30/21

SCOTT WHEELER

Designer

06-15-2020

SYMBOLS,ABBREVIATIONS

AND SHEET INDEX

E001

NE

VA

DA

UN

ION

HIG

H S

CH

OO

LC

AM

PU

S P

OW

ER

ON

E L

INE

AN

D S

ITE

DIS

TR

IBU

TIO

N P

HA

SE

-2

FEEDER SCHEDULEFEEDER SCHEDULE GENERAL NOTES

1. COPPER FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH THHN/THWN-2 INSULATION IN EMT CONDUIT.

2. ALUMINUM FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH XHHW-2 INSULATION IN EMT CONDUIT.

3. FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON AN AMBIENT TEMPERATURE OF 30 DEGREES C (86 DEGREES F).

4. FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED SIZE GROUND CONDUCTOR

IN EACH CONDUIT.

5. PER CEC ARTICLE 110.14, ALL FEEDERS SIZED AT #2 AWG OR LESS ARE CALCULATED PER 60 DEGREE TABLE. FEEDERS GREATER THAN #2 AWG

ARE RATED 75 DEGREE.

FEEDER SCHEDULE REMARKS

A. OVERSIZED 150% NEUTRAL, SUITABLE FOR SERVICE FROM K-13 RATED TRANSFORMERS.

B. FEEDER APPROVED FOR USE WITH SEPARATELY DERIVED SYSTEM; GROUNDING AS REQUIRED BY CEC ARTICLES 240 AND 250.

C. FEEDER GROUND AND BONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OF THE AREA OF THE LARGEST PHASE CONDUCTOR.

D. INCREASE CONDUIT TO THE NEXT LARGER TRADE SIZE WHEN USING SCHEDULE 40 OR 80 PVC CONDUIT.

E. PER CEC SECTION 240.4(B), THE NEXT HIGHER STANDARD OVERCURRENT DEVICE RATING (ABOVE THE AMPACITY OF THE CONDUCTORS) CAN BE USED.

RULE CAN NOT BE APPLIED IF 100% RATED BREAKERS ARE USED.

F. PER CEC 240.21(C), THE PROVISIONS OF 240.4(B) SHALL NOT BE PERMITTED FOR TRANSFORMER SECONDARY CONDUCTORS.

FEEDERTAG

FEEDERDESCRIPTION

CONDUITCONDUCTORS

SEPARATELY DERIVEDSYSTEM

REMARKS

PHASE/NEUTRAL GROUNDGROUNDINGELECTRODE

BONDINGJUMPER

153 15 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - -

203 20 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - -

204 20 AMP, 3 PHASE, 4 WIRE 1-0.75" 4 #12 CU 1 #12 CU - -

403 40 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #8 CU 1 #10 CU - - -

504 50 AMP, 3 PHASE, 4 WIRE 1-1.00" 4 #6 CU 1 #8 CU #8 CU IN 0.75" C. #8 CU B

703 70 AMP, 3 PHASE, 3 WIRE 1-1.00" 3 #4 CU 1 #8 CU - - D

704 70 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #4 CU 1 #10 CU - - -

904 90 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #3 CU 1 #8 CU - - -

1004 100 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #2 CU 1 #8 CU - - E

1254 125 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #1 CU 1 #6 CU - - -

1503 150 AMP, 3 PHASE, 3 WIRE 1-1.50" 3 #1/0 CU 1 #6 CU - - -

1504 150 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #1/0 CU 1 #6 CU - - D

1754 175 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #2/0 CU 1 #6 CU - - -

2004 200 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #3/0 CU 1 #6 CU - - -

2254 225 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #4/0 CU 1 #4 CU - - -

2504 250 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #250 KCMIL CU 1 #4 CU - - D

3004 300 AMP, 3 PHASE, 4 WIRE 1-3.00" 4 #350 KCMIL CU 1 #4 CU - - D

4003 400 AMP, 3 PHASE, 3 WIRE 1-3.00" 3 #500 KCMIL CU 1 #2 CU - - D

4004 400 AMP, 3 PHASE, 4 WIRE 1-4.00" 4 #500 KCMIL CU 1 #2 CU - - D

4503 450 AMP, 3 PHASE, 3 WIRE 2-2.50" 2 SETS OF 3 #4/0 CU 1 #2 CU/SET - - -

6004 600 AMP, 3 PHASE, 4 WIRE 2-3.00" 2 SETS OF 4 #350 KCMIL CU 1 #1 CU/SET - - D

8004 800 AMP, 3 PHASE, 4 WIRE 2-3.50" 2 SETS OF 4 #600 KCMIL CU 1 #1/0 CU/SET - - D

T4004 400 AMP, 3 PHASE, 4 WIRE 2-2.00" 2 SETS OF 4 #4/0 CU 1 #1/0 CU/SET #1/0 CU IN 0.75" C. #1/0 CU B,F

T10004 1032 AMP, 3 PHASE, 4 WIRE 3-3.00"3 SETS OF 3 #500 KCMIL CU, 2#300 KCMIL CU NEU./SET

#3/0 CU/SET #3/0 CU IN 1.00" C. #3/0 CU A,B,C,D,F

# DESCRIPTION DATE

PROJECT GENERAL NOTES*EXISTING CONDITIONS

1. THE EXISTING CONDITIONS INDICATED IN THIS DRAWING SET WERE DEVELOPED FROM VARIOUS SOURCESWHICH WERE NOT ALL FIELD VERIFIED AND NOT ALL CONDITIONS ARE SHOWN. LOCATIONS, ROUTING,ELEVATIONS, SIZES, ETC. ARE SHOWN SCHEMATICALLY. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS

PRIOR TO CONSTRUCTION.

2. DRAWINGS INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT

WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS. FINAL LOCATIONS SHALLBE ADJUSTED TO MEET FIELD CONDITIONS.

*DEMO & GENERAL CONDITIONS3. CONTRACTOR SHALL REMOVE ALL LEFT OVER CONDUIT, WIRE, SCRAPS, ETC. AND LEAVE PREMISES CLEAN

AND FREE OF TRASH OR DEBRIS RESULTING FROM THEIR WORK.

4. CONTRACTOR SHALL DISCONNECT AND REMOVE ALL DEMOLISHED DEVICES AND FIXTURES AS SHOWN ON

DEMOLITION PLAN. TURN OVER TO OWNER EXISTING DEVICES AND FIXTURES THAT ARE NOT REUSED.PROPERLY DISCARD IF THE OWNER DOES NOT WANT.

5.

6.

*SITE

7.

THERE SHALL BE A MINIMUM OF 18" OF COVER OVER UNDERGROUND CONDUITS, UON. INCLUDE A MINIMUM12" SEPARATION BETWEEN ALL LOW VOLTAGE AND LINE VOLTAGE RACEWAYS. INSTALL A WARNING/MARKER

TAPE 12 INCHES OVER THE CONDUIT.

8.

9.

CONTRACTOR SHALL SIZE ALL EXTERIOR JUNCTION/PULLBOXES PER THE MINIMUM CODE REQUIREMENTS

OF CEC ARTICLE 314, WHEN NOT INDICATED ON THE PLANS.

*EQUIPMENT, CONDUIT, WIRE, BOXES & DEVICES

PROVIDE INDIVIDUAL GFCI RECEPTACLES AT EACH LOCATION SHOWN, DO NOT USE FEED-THRU GFCI TYPE

RECEPTACLES. LOCATE RECEPTACLE AT END OF A BRANCH CIRCUIT WIRE.

14.

WHERE RECEPTACLES ARE LOCATED OUTSIDE OR IN WET/DAMP LOCATIONS PROVIDE WEATHER RESISTANT

TYPE, UON.

15.

CONDUIT SIZE SHALL BE 0.75 MINIMUM, U.O.N.

16.

ALL CONDUCTORS ON THIS PROJECT SHALL BE COPPER.

17.

18.

INSTALL AND CONNECT A CODE SIZED INSULATED OR BARE COPPER GROUNDING CONDUCTOR IN ALL BRANCHCIRCUITS AND FEEDERS.

19.

ALL DEVICES SHALL HAVE TYPE ON TAPE LABELS INDICATING THE PANELBOARD AND CIRCUIT SERVING EACHDEVICE, TYPICAL OF ALL DEVICES INCLUDED ON THIS PROJECT.

20.

PROVIDE INSULATING BUSHINGS OR INSULATED THROAT ON THE ENDS OF ALL EMPTY CONDUIT SLEEVES ANDINSTALL A POLYETHYLENE PULLING ROPE.

21.

WHERE CIRCUITS ARE SHOWN ON THE DRAWINGS WITH HOMERUNS THAT SHARE NEUTRAL CONDUCTORS THECONTRACTOR SHALL PROVIDE HANDLE TIES BETWEEN ALL BRANCH CIRCUIT BREAKER LOADS WHICH SHARE A

NEUTRAL.

22.

ALL OUTDOOR ELECTRICAL EQUIPMENT SHALL BE WEATHER-PROTECTED AND LISTED FOR EXTERIOR USE.

23.

PROVIDE TYPE WRITTEN PANEL SCHEDULES UPDATED TO INCLUDE ALL FIELD MODIFICATIONS AND SCOPEITEMS ASSOCIATED WITH THIS PROJECT.

24.

PROVIDE ENGRAVED NAMEPLATES FOR ELECTRICAL BOARDS, DISCONNECTS, AND SWITCHGEAR.

*CODE REQUIREMENTS & ELEC. CLEARANCES

25.

ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE(CEC).

26.

CONTRACTOR IS RESPONSIBLE TO SUBMIT REVISED LAYOUT OF EQUIPMENT IN ELECTRICAL SPACES FORWRITTEN APPROVAL BY ENGINEER IF PROPOSED INSTALLATION LAYOUT DIFFERS FROM CONSTRUCTIONDOCUMENTS. SUBMISSION MUST BE APPROVED PRIOR TO RELEASE OF ORDER FOR EQUIPMENT AND PRIOR

TO INSTALLATION.

27.

REQUIRED ELECTRICAL EQUIPMENT WORKING SPACE DEPTH SHALL NOT BE LESS THAN THAT INDICATED IN

CEC TABLE 110.26. THE WIDTH OF THE WORKING SPACE IN FRONT OF THE ELECTRICAL EQUIPMENT SHALL BETHE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS GREATER. THIS REQUIREMENT ALSO APPLIES TODISCONNECT SWITCHES.

28.

ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES AND BEARTHEIR LABEL, OR ETL.

29.

WIRING SPACE IN PANELBOARDS, DISTRIBUTION PANES AND SWITCHBOARDS SHALL BE DEDICATED TOCONDUCTORS TERMINATED IN THAT ENCLOSURE. PANELBOARDS, DISTRIBUTION PANELS ANDSWITCHBOARDS SHALL NOT BE USED AS PULL AND/OR SPLICE BOXES FOR CONDUCTORS THAT TERMINATE IN

OTHER ENCLOSURES. DO NOT SPLICE CONDUCTORS IN EQUIPMENT.

30.

NEW CIRCUIT BREAKERS INSTALLED IN EXISTING EQUIPMENT SHALL BE PROVIDED TO MATCH THE kAIC

RATINGS AND THE MANUFACTURER OF THE EXISTING.

PROVIDE CLEAR SIGNAGE ON ALL ELECTRICAL EQUIPMENT PER CEC TO INDICATE THE ARC FLASH HAZARD

WARNING, AND THE MAXIMUM AVAILABLE FAULT CURRENT. WHEN MODIFICATIONS OCCUR THAT AFFECT THEMAXIMUM FAULT CURRENT THE CONTRACTOR SHALL RECALCULATE AS NECESSARY AND REMARK THEEQUIPMENT.

*COORDINATION

PROVIDE FUSES IN DISCONNECTS FOR MECHANICAL EQUIPMENT AS COORDINATED WITH THE UNITSNAMEPLATE AND MANUFACTURERS INSTALLATION INSTRUCTIONS. FUSES SHALL BE CURRENT LIMITING TYPE.

PROVIDE A GFCI TYPE DEVICE WITH WEATHER PROOF WHILE IN USE COVER WITHIN 25' OF ALL EXTERIORHVAC/PLUMBING EQUIPMENT.

WORK PERFORMED FROM THESE DRAWINGS SHALL ALSO COMPLY WITH THE PROJECT SPECIFICATIONS. INTHE EVENT THAT THERE IS A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MORE

STRINGENT REQUIREMENT SHALL TAKE PRECEDENT.

*MISC.35. CONTRACTOR SHALL PREPARE RED LINED AS-BUILT DOCUMENTS REPRESENTING THE ACTUAL FIELD

ROUTINGS AND INSTALLATION LOCATIONS FOR ALL ITEMS ON THIS PROJECT.

36. SURFACE MOUNTED CONDUIT WHERE APPROVED, AND INSTALLED, SHALL BE PAINTED TO MATCH THEARCHITECTURAL FINISHES IN THAT AREA.

37. CONDUIT ROUTING (WHERE SHOWN) IS ESSENTIALLY DIAGRAMMATIC. CONTRACTOR SHALL LAYOUT RUNS TOSUIT FILED CONDITIONS AND THE COORDINATION REQUIREMENTS OF OTHER TRADES.

38. DRAWINGS INDICATE JUNCTION BOXES WITH HOMERUNS ON THE PLANS, BUT THE CONTRACTOR SHALLPROVIDE ALL INTERMEDIATE RACEWAY WORK AND CONDUCTORS/CABLING BETWEEN THE DEVICES,

FIXTURES, AND JUNCTION BOXES AS COORDINATED WITH ALL FIELD CONDITIONS AND TRADES.

10.

USE RIGID STEEL CONDUIT WRAPPED IN 10 MIL TAPE FOR ALL UNDERGROUND 90'S EXTENDING TO 6" ABOVE

THE GROUND.

11.

USE SCHEDULE 40 PVC FOR ALL UNDERGROUND CONDUITS, UON.

12.

USE RIGID STEEL CONDUIT FOR ALL EXPOSED INSTALLATIONS.

13.

NUMBERED SHEET NOTES#

3

1.

2. #4 REINFORCING BARS AT 12" MAXIMUM SPACING IN EACH DIRECTION. BARS SHALL BE AS PER ASTMA615, GRADE 40 MINIMUM.

3.

4.

5/8" DIAMETER X 8'-0" LONG COPPER GROUND ROD WITH GROUND ROD CLAMP.

SOLID BARE COPPER GROUND CONDUCTOR.

PLAN VIEW

SECTION A-A

10"

6"

12

"

8"

3"

3"

10"

FRONT

A A

4

1

2

CONCRETE PAD SHALL BE DESIGNED TO ATTAIN A STRENGTH OF 3000 PSI IN 28 DAYS. SURFACE SHALL HAVE A LIGHT BROOM OR WOOD FLOAT FINISH. ALL EXPOSED EDGES SHALL HAVE A 3/4" CHAMFER OR RADIUS. PAD DIMEMENSIONS SHALL BE DETERMINED BY EQUIPMENT DIMENSIONS AND LAYOUT ON E300. PAD SHALL EXTEND A 8" ON SIDES, FRONT AND BACK OF EQUIPMENT.

1/2" ∅ HILTI KWIK-BOLT TZ,INSTALL PER ICC ESR-1917MIN. 3.25" EMBED

EQUIPMENT ENCLOSURE

SPACING TO SUIT EQUIP. DIMENSION

BOTTOM OF PAD

2" MIN.

DISTRIBUTION BOARD: 2 PER SIDE PER CUBICLE, MAX WEIGHT 900#TRANSFORMER : 2 PER SIDE PER CUBICLE, MAX WEIGHT 1,250#

CONCRETEPAD/SLAB. REFERTO 1/E002.

R

S

REGIS

TERED

PROFESS I ONAL

ENGINEE

ATATE OF CAL I FORN IELECTRICAL

CONSULTING ENGINEERS

REVISIONS

DESIGNER:

SCALE:

DATE:

TITLE:

DRAWING NO.

1125 HIGH STREETAUBURN, CA 95603(530) 886-8556

#E015491Exp. 06/30/21

SCOTT WHEELER

Designer

06-15-2020

SCHEDULES &PROJECT NOTES

E002

NE

VA

DA

UN

ION

HIG

H S

CH

OO

LC

AM

PU

S P

OW

ER

ON

E L

INE

AN

D S

ITE

DIS

TR

IBU

TIO

N P

HA

SE

-2

SCALE:NTS1

EQUIPMENT PAD DETAIL

Notes:

Total Est. Demand: 397 A

Total Conn.: 397 A

Total Est. Demand: 330.00 kVA

Other 330 kVA 100.00% 330 kVA Total Conn. Load: 330.00 kVA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total... 397 A 397 A 397 A

Total Load: 110.00 kVA 110.00 110.00

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

--- -- -- 11 0.00 0.00 12 -- -- ---

--- -- -- 9 0.00 0.00 10 -- -- ---

space -- -- 7 0.00 0.00 8 -- -- space

-- -- -- 5 66.67 43.33 6 -- -- --

-- -- -- 3 66.67 43.33 4 -- -- --

TX-C 450 A 3 1 66.67 43.33 2 3 175 A (F) CHILLER

LOAD SERVED Amp P... # A (kVA) B (kVA) C (kVA) # P... Amp LOAD SERVED

Mounting: PAD Volts: 480V Wires 3 Main Type: MCB Main Rating: 500 A

Location: Southwest Pad Serv... MSB-2 Phases 3 A.I.C. Rating: 42KAIC Bus Rating 600 A

DISTRIBUTION BOARD: HDA

SCALE:NTS2

EQUIPMENT ATTACHMENT AT PAD

# DESCRIPTION DATE

(E)

P P

P

P

P

P

P

P

P

P

P

PP

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

PP

P

P

P

P

P

P

P

P

(E)3-2" MTC

(E)2-2" MTC

(E)2-2" MTC

(E)2-2" MTC

(E)1-2" MTC

(E)2-2" MTC

(E)3-4" MTC

(E)2-4" MTC

(E)2-4" MTC

2-2" COM

2710

BLDG. 'A'

MUSIC BLDG. L

BUS LOADING ZONE

MA

TH

/ A

RT

S B

LD

G. 'J

'

BLDG. 'G' -

BOYS GYM

CLASSROOM BLDG. 'D'

CLASSROOM BLDG. 'E'

CLASSROOM BLDG. 'C'

SCIENCE /

LIBRARY

"S"

BLDG. 'B'

THEATER

BLDG. 'K'

INDUSTRIAL

ARTS

AGRICULTURE. 'F'

DANCE

POOL

WRESTLING

SHOP BLDG.

MAINT.

SH

OW

ER

S

STADIUM

BLDG. 'A'

BLDG. I -

LANGUAGE

BLDG. 'B'

THEATER

BLDG. 'K'

8 .5'

1 7'

1 2.5'

1 2'

1 2'

1 2'

1 2'

1 2.5'

1 2.5'

1 2.5'

1 2'

1 2'

1 2'

1 2'

1 2.5'

1 2.5'

1 8'

9 '

8 '

3

A

A

A

A

AF

AF

AF

AFAF

AF

AF

T

T

A

T

F

18'-4"

13'-4"

5'-0"

13'-4"

16'-8"

16'-8"

16'-8"

16'-8"

16'-8"

16'-8"

8'-4"

16'-8"

16'-8"

16'-8"

CUT AN

D FLAT TE

N (E) SL

AB

NEW FL

OOR DR

AIN

NEW FL

OOR DR

AIN

BENCH

WD

ICE

2

6

N

G1

G2

G3

G4

G5

G6

G7

G8

G9

G10

G11

G12

G13

G16

G18A

G19

G18

G15

G17

G21

G203

G22

G26

G25

G23G24

G27

G15A

LOCKER

ROOM

CORRIDO

R

VESTIBU

LE

COACH-

1

COACH-

2

LOCKER

S

SHOWER

S

COACH-

3

EQUIPME

NT

DRYING

ROOM

SHOWER

EQUIP.

LAUNDR

Y

TOILET

WEIGHT

ROOM

BOILER

ROOM

WEIGHT

ROOM

CORRIDO

R

VESTIBU

LE

SNACK

BAR

STOR.

LOBBY

STORAG

E

GIRLS

TOILET

JANITORBOY

S

TOILET

GYMNAS

IUM

JAN.

J

S

J

S

J

S

(E) MSB-E

(E) MSB-4

(E) PANEL-E

(E) 5TX-U

(E) MSB-1

(E) #T1122

(E) LDA

(E) 5TX-C

(E) MSB-3

(E) #T1192

MSB-2#T0005

(E) DIST BOARD

PANEL-EK HOUSE DIMMER D1 PANEL-K3

PANEL-K1

PANEL-K2

PANEL-L2

PANEL-L1

PANEL-F1

PANEL-F2

PANEL-F3

PANEL-H1

PANEL-H2

PANEL-H3

PANEL-H4

EXIT LTG SWX PANEL

PANEL-G2

PANEL-D6

PANEL-D4

PANEL-D5

PANEL-D2

PANEL-D3

PANEL-D1

EMERGENCY CONTROL PANEL

PANEL-EMI

EMERGECNY DIST. PANEL

PANEL-B3

PANEL-B2

PANEL-B1

DIST. PANEL-A5

PANEL-A3

PANEL-A2

PANEL-C3

PANEL-C2

PANEL-C1

PANEL-E1PANEL-E6

PANEL-E7PANEL-E3

PANEL-E4

PANEL-E8

PANEL-E5

PANEL-E2

PANEL-E9

PANEL-J1PANEL-J2

DIST. PANEL

PANEL-J3PANEL-J4

P

E3001

E3002

E3003

P(E)

2

4

3

HDATX-C

2

(E) VAULT

Work to be completed under phase 1

Work to be completed under phase 2

R

S

REGIS

TERED

PROFESS I ONAL

ENGINEE

ATATE OF CAL I FORN IELECTRICAL

CONSULTING ENGINEERS

REVISIONS

DESIGNER:

SCALE:

DATE:

TITLE:

DRAWING NO.

1125 HIGH STREETAUBURN, CA 95603(530) 886-8556

#E015491Exp. 06/30/21

SCOTT WHEELER

Designer

06-15-2020

ELECTRICAL SITEPLAN

E100

NE

VA

DA

UN

ION

HIG

H S

CH

OO

LC

AM

PU

S P

OW

ER

ON

E L

INE

AN

D S

ITE

DIS

TR

IBU

TIO

N P

HA

SE

-2

SCALE: 1" = 60'-0"1

OVERALL SITE PLAN

LOCATE AND INTERCEPT EXISTING FEEDER WITH A 4’ X 6’ PULLBOX. EXTEND FEEDER ASSHOWN. REFER TO POWER ONE LINE DIAGRAM (E200) FOR ADDITIONAL INFORMATION.

1

EXTEND CONDUIT FROM EXISTING PULLBOX TO ELECTRICAL EQUIPMENT AND PROVIDE NEWWIRE. REFER TO POWER ONE LINE DIAGRAM (E200) FOR ADDITIONAL INFORMATION.

2

PROVIDE NEW UNDERGROUND FEEDER. REFER TO POWER ONE LINE DIAGRAM (E200) FORADDITIONAL INFORMATION. SAWCUT EXISTING CONRETE AND PATCH TO MATCH EXISTING.

3

PROVIDE NEW WIRE IN EXISTING CONDUIT. REFER TO POWER ONE LINE DIAGRAM (E200) FORADDITIONAL INFORMATION.

4

NUMBERED SHEET NOTES

1" = 60'-0"

1

ALL CONCRETE PULL BOXES SHALL BE PROVIDED WITH TRAFFIC RATED LID AND TAMPERPROOF HARDWARE.

1.

GENERAL SHEET NOTES

# DESCRIPTION DATE

XXX

APANEL

BPANEL

CPANEL

DPANEL

EPANEL

FPANEL

BOARD

LEDMESS

M

PG&E XFMR75kVA

#T-1351

904 1004 904 904 904 904

1,2,3BLDG

4,5,6BLDG

(?)PARF

9,10,11BLDG

13,14,15BLDG

M

XXX

??

PG&E XFMR75kVA

#T-1192

1004 1254 2254 2254 4004

E-2PANEL

E-3PANEL

E-4PANEL

E-5PANEL

E-1PANEL

M

#T-6717-7381PG&E XFMR, POLE MOUNTED

50kVA x 3

E-3PANEL

E-5PANEL

E-1PANEL

J1PANEL

J2PANEL

J3PANEL

J4PANEL

J5PANEL

JMPANEL

ERTERINV-

1004 1254 2254 2254 4004

1004 1254 1004 1254 1004 1004 204

LIGHTSPARKING

BOXPRESS

BOXPRESS

PANEL

SNACKBAR

CLASS

PORT-ABLE

BOARDSCORE-

XXX

HOUSEGREEN

SOUTH

POLELIGHTS

NORTH

POLELIGHTS

GYMWRESTLING

PG&E TRANSFORMERT-5

M

203 153 153 703 403 1503 703 2004 2254

PANELE-WING

PANELMCC-2

PANELJ-WING

LIGHTS

THEATERPARKING

PANELTHEATER

#2CHILLER

#1CHILLER

M

PG&E XFMR1000kVA

#T-1122

??

PANELS-WING

NPANEL

D-4PANEL

B-2PANEL

B-3PANEL

B-1PANEL

D-2PANEL

A-1PANEL

D-3PANEL

D-1PANEL

B-2PANEL

#137

PANELLB RM

#207

PANELLD RM

#205

PANELLF RM

#122

PANELLF RM

#223

PANELLL RM

#209

PANELS2 RM

#202

PANELS1 RM

#137

PANELHA RM

#207

PANELHC RM

A-4PANEL

STAGEPANEL

D-4PANEL

D-4PANEL

C-2PANEL

C-1PANEL

A-3PANEL

C-3PANEL

A-2PANEL

H1PANEL

H2PANEL

H3PANEL

HH1PANEL

4003

8004

G3PANEL

T4004

T10004

MAINPANEL

1PANEL

2PANEL

7PANEL

8PANEL

13PANEL

14PANEL

6004 2504 2254 4004 704 204 3004 4003 4004 8004 6004 6004

2004 2004

1004 504 504 504204 204 204

2004 2004 2004 2004 2004

1004 4004 1754 1004 1004 10041504 8004 3004 1254 8004

4503

4003

90A3P

100A3P

90A3P

90A3P

90A3P

90A3P

0A1P

MSB-4Northpoint

400A,120/208V,3Φ,4W Meter # 1006727937Load: 61kW, 169A

400A3P

100A3P

125A3P

225A3P

225A3P

400A3P

0A3P

MSB-3G-Wing

1000A,120/208V,3Φ,4WMeter# 1009985101Load: 20KW, 56A

PG&E PRIMARY

400A3P

225A3P

225A3P

125A3P

100A3P

MSB-EShop

800A,120/240V,3Φ,4W

20A3P

100A3P

100A3P

125A3P

100A3P

125A3P

100A3P

400A3P

PANEL J

120/240V,3Φ,4W

400A3P

Meter# 1003716856Load: XXKW, XXA

PG&E PRIMARY

225A3P

200A3P

70A2P

150A2P

40A2P

70A2P

15A2P

15A1P

20A1P

MSB-2Stadium

1200A, 277/480V,3Φ,4W, 65KAIC Meter# 1009510316Load: 118kW, 142A

1200A3P

PG&E PRIMARY

(N)500A

3P1

(N)5

250A3P

225A3P

20A3P

300A3P

400A3P

400A3P

MSB-1Upper Parking

3000A,277/480V,3Φ,4W

800A3P

600A3P

600A3P

100A3P

400A3P

175A3P

100A3P

150A3P

100A3P

800A3P

300A3P

100A3P

125A3P

800A3P

LDAC-Wing

1600A,120/208V,3Φ,4W

400A3P

70A3P

ALI GYM

200A3P

200A3P

200A3P

600A,277/480V,3Φ,4W

DPL

200A3P

200A3P

600A3P

MUSICBUILDING

200A3P

200A3P

300A3P

600A,277/480V,3Φ,4W

DPH

600A3P

PANEL A-5

225kVA XMFR 208/480V

Meter# 1010080211Load: 622kW, 748A

2500A3P

800A3P

225A3P

225A3P

225A3P

400A3P

225A3P

225A3P

225A3P

225A3P

225A3P

225A3P

225A3P

225A3P

225A3P

225A3P

600A3P

5TX-G112.5KVA

4160V Δ - 120/208V Y

5TX-C300KVA XMFR

4160V Δ - 120/208V Y

5TX-U500KVA XMFR

4160V Δ - 277/480V Y

112.5KVA4160V Δ - 120/208V Y

AG BLDG

TESTPOWER

PG&E PRIMARY

(N) TX-G112.5 KVA

480V Δ - 120/208V Y

2

3

3

(N) TX-C300KVA

480V Δ - 120/208V Y

(N)

2

(N)

SPARE(GREEN HOUSE)

SPARE(PORTABLES)

225KVA

1000A3P

100A3P

50A3P

50A3P

20A3P

50A3P

20A3P

EMERGENCY PANEL (AG)Upper Parking

20A3P

100A,277/480V,3Φ,4W

WORK TO BE COMPLETED UNDER THE AG SHOP PROJECT

(E) VAULT

5

P

6

(N)DIST

BOARDHDA

4(N)

(N)

400A3P

7

(N)

(N)

(E) VAULT

Work to be completed under phase 1

Work to be completed under phase 2

3

3

R

S

REGIS

TERED

PROFESS I ONAL

ENGINEE

ATATE OF CAL I FORN IELECTRICAL

CONSULTING ENGINEERS

REVISIONS

DESIGNER:

SCALE:

DATE:

TITLE:

DRAWING NO.

1125 HIGH STREETAUBURN, CA 95603(530) 886-8556

#E015491Exp. 06/30/21

SCOTT WHEELER

Designer

06-15-2020

POWER ONE-LINE

E200

NE

VA

DA

UN

ION

HIG

H S

CH

OO

LC

AM

PU

S P

OW

ER

ON

E L

INE

AN

D S

ITE

DIS

TR

IBU

TIO

N P

HA

SE

-2

1POWER ONE LINE - NORTHPOINT

3POWER ONE LINE - PORTABLES/G WING

2POWER ONE LINE - SHOPS/J WING

4POWER ONE LINE - STADIUM

5POWER ONE LINE - UPPER PARKING/MAIN CAMPUS

PROVIDE NEW BREAKER IN EXISTING BOARD. BREAKER SHALL BE LISTED FOR USE IN EXISTINGEQUIPMENT, WHICH IS CUTLER-HAMMER POW-R-LINE C.

1

PROVIDE NEW TRANSFORMER AS SHOWN.2

DISCONNECT AND REMOVE EXISTING PAD MOUNTED, OIL FILLED TRANSFORMER. DISPOSE OFEQUIPMENT. DISCONNECT AND SAFE OFF WIRE. LEAVE WIRE ABANDONED IN CONDUIT.COORDINATE DEMOLITION AND REMOVAL WITH DISTRICT, OTHER CONTRACTORS, PVCONTRACTORS, ETC. THE CONTRACTOR IS RESPONSIBLE TO DISPOSE OF TRANSFORMERS INACCORDACE WITH ALL APPROPRIATE LAWS AND REGULATIONS.

3

PROVIDE THREE SETS OF 3 #750KCMIL CU AND 1 #2/0 CU GROUND IN THE EXISTING 4"CONDUITS.

4

PROVIDE THREE SETS OF 3 #750KCMIL CU AND 1 #2/0 CU GROUND IN NEW 4" CONDUITS.5

CHILLER TO BE REMOVED UNDER ANOTHER PROJECT.6

PROVIDE INTEGRAL SECONDARY CIRCUIT BREAKER TRANSFORMER.7

NUMBERED SHEET NOTES

ALL EQUIPMENT, FEEDERS, ETC. IS EXISTING UNLESS NOTED OTHERWISE.1.

GENERAL SHEET NOTES

# DESCRIPTION DATE

A

A

A

A

A

I

J

H

G

CHP-2

CH-1

CH-2

CHP-5

CHP-3

CHP-4

(E)MCC

-2(E)

PANEL 'L

CY'

7.5HP,48

0V,3∅

7.5HP,48

0V,3∅

5HP,480

V,3∅

5HP,480

V,3∅CHP-1

LCV-1

J

AF

AF

AF

AFAF

AF

AF

T

T

T

1.5 HP,

230V, 3∅

1.5 HP,

230V, 3∅

1.5 HP,

230V, 3∅

3 HP, 2

30V, 3∅

3 HP, 2

30V, 3∅

1.5 HP,

208V, 3∅

1.5 HP,

208V, 3∅

N

HWP-G3

B/G1FAN

B/G2FAN

HWP-G2

HWP-G1

HWP-J2

HWP-J1

G3A-21

G3A-15

G3A-27

G3A-39

G3A-33

G3A-3

G3A-9

(N)PANE

L G3A

G3A-2

G19

BOILER

ROOM

J

S

J

S

S

P

P

(E)

(E)

(E)

(E)

(E)

(E)

(E)

3

5

REFER TO E100 FOR CONTINUATION

(N) TX-G

5TX-G

1

6

7

(E) PNL G4

(E) PNL G3

(E) 5TX-C

TX-C

(F) CHILLER LOCATION

(E) VAULT

(E) LDA

3

3

1HDA

REFER TO E100 FOR CONTINUATION

8

2

R

S

REGIS

TERED

PROFESS I ONAL

ENGINEE

ATATE OF CAL I FORN IELECTRICAL

CONSULTING ENGINEERS

REVISIONS

DESIGNER:

SCALE:

DATE:

TITLE:

DRAWING NO.

1125 HIGH STREETAUBURN, CA 95603(530) 886-8556

#E015491Exp. 06/30/21

SCOTT WHEELER

Designer

06-15-2020

ROOM/AREADETAILS

E300

NE

VA

DA

UN

ION

HIG

H S

CH

OO

LC

AM

PU

S P

OW

ER

ON

E L

INE

AN

D S

ITE

DIS

TR

IBU

TIO

N P

HA

SE

-2

SCALE: 1/4" = 1'-0"1

North 'G' Equipment YardSCALE: 1/4" = 1'-0"

2South 'G' Boiler RM

SCALE: 1/4" = 1'-0"3

Southwest Campus Pad

REMOVE EXISTING EQUIPMENT. REFER TO E200 FOR ADDITIONAL INFORMATION.1

PROVIDE NEW CONCRETE PAD. REFER TO DETAIL 1/E002. PAD SHALL FILL IN THE AREA WITHCONCRETE TO CREATE ONE CONTIGUOUS CONCRETE MAINTENANCE PAD.

2

PROVIDE NEW UNDERGROUND FEEDER TO EXISTING DISTRIBUTION BOARD LDA. RISE UP ANDTERMINATE INTO THE BOARD AT 6" ABOVE GRADE. AS AN ALTERNATE, INTERCEPT EXISTINGFEEDER ENTERING THE GEAR, REMOVE WIRE AND PULL NEW WIRE INTO THE EQUIPMENT.

3

PROVIDE NEW UNDEGROUND FEEDER.4

PROVIDE NEW N36 PULLBOX TO INTERCEPT EXISTING FEEDER AS SHOWN ON E100.5

PROVIDE 90 UP AT WALL AND PENETRATE WALL AT +8" ABOVE GRADE. CORE WALL ANDPENETRATE WALL WITH LB'S. EXTEND FEEDER TO TRANSFORMER AS SHOWN.

6

PROVIDE A TRANSFORMER WITH AN INTEGRAL SECONDARY CIRCUIT BREAKER.7

RAISE VAULT LID TO MATCH GRADE OF FINISHED CONCRETE PAD.8

NUMBERED SHEET NOTES

# DESCRIPTION DATE

PHASE 2

PHASE 2

PHASE 1