general notes abbreviations & symbols...

8
ABBREVIATIONS: A/E ARCHITECT/ENGINEER ADDN'L ADDITIONAL B BOTTOM B.O. BOTTOM OF BLDG BUILDING C.L. CENTER LINE CMU CONCRETE MASONRY UNIT CONC. CONCRETE CONN. CONNECTION CONT. CONTINUOUS COORD. COORDINATE DIM. DIMENSION DWG DRAWING E.F. EACH FACE EL. ELEVATION ELEC. ELECTRICAL EXT. EXTERIOR FDN FOUNDATION FTG FOOTING GALV. GALVANIZED HSS HOLLOW STRUCTURAL SECTION K KIP, KIPS (1 KIP = 1000 LBS) LB, LBS POUND, POUNDS LFH LONG FACE HORIZONTAL (TUBES) LFV LONG FACE VERTICAL (TUBES) LLH LONG LEG HORIZONTAL (L-ANGLES) LLV LONG LEG VERTICAL (L-ANGLES) MAX. MAXIMUM MECH. MECHANICAL MIN. MINIMUM N.T.S. NOT TO SCALE O.C. ON CENTER O.H. OPPOSITE HAND OEI ODEH ENGINEERS, INC. OPN'G OPENING P.E. PROFESSIONAL ENGINEER PL. PLATE PSF POUNDS PER SQUARE FOOT P.T. PRESERVATIVE TREATED (WOOD) REINF. REINFORCED, REINFORCEMENT, ETC. REQ'D REQUIRED SIM. SIMILAR SPECS SPECIFICATIONS SS STAINLESS STEEL STL STEEL T&B TOP AND BOTTOM T.O. TOP OF T.O.W. TOP OF WALL T.O.S. TOP OF STEEL TYP. TYPICAL U.N.O. UNLESS NOTED OTHERWISE VERT. VERTICAL V.I.F. VERIFY IN FIELD w/ WITH @ AT - INDICATES CONCRETE MASONRY UNIT (CMU). SECTION VIEW - INDICATES BRICK VENEER SECTION VIEW - INDICATES SECTION OR DETAIL ABBREVIATIONS & SYMBOLS LEGEND - INDICATES COLUMN GRID. SECTION DESIGNATION, SECTION APPEARS ON SAME SHEET - ## - INDICATES SECTION OR DETAIL SHEET NUMBER WHERE SECTION APPEARS SECTION DESIGNATION ## S#.## STRUCTURAL DRAWING LIST GENERAL NOTES I. GENERAL 1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL APPLICABLE STATE AND LOCAL CODES AND STANDARDS, INCLUDING BUT NOT LIMITED TO: ...INTERNATIONAL BUILDING CODE 2009 WITH AMENDMENTS AND ITS APPLICABLE REFERENCED STANDARDS. ...INTERNATIONAL EXISTING BUILDING CODE 2009 (ORDINARY REPAIR PROVISIONS) ...ANSI/ASCE 7-05 ...OTHER CODES AND STANDARDS AS LISTED UNDER OTHER SECTIONS OF THESE GENERAL NOTES AND SPECIFICATIONS. 2. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AS THEY RELATE TO NEW CONSTRUCTION. REPORT TO THE ARCHITECT/ENGINEER ALL OBSERVATIONS AND ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK. 3. WHERE DETAILS FOR SPECIFIC CONDITIONS ARE NOT SHOWN ON THESE PLANS, USE DETAILS FOR THE MOST NEARLY SIMILAR CONDITIONS SHOWN ON THE STRUCTURAL DRAWINGS AS DETERMINED BY THE OWNER AND STRUCTURAL ENGINEER OF RECORD. REPORT ANY COORDINATION ISSUES IMMEDIATELY TO THE OWNER FOR REVIEW. 4. 5. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDE FOR A SAFE AND EFFICIENT METHOD OF SHORING AND/OR BRACING THE STRUCTURE DURING ALL CONSTRUCTION PHASES. SUBMIT AN OUTLINE OF PROPOSED PROCEDURE TO THE OWNER AND ENGINEER BEFORE CONSTRUCTION COMMENCES. 6. ALL WORK SHALL BE CONTINUOUSLY MONITORED AND INSPECTED BY AN INDEPENDENT TESTING AGENCY. SUBMIT ALL TEST AND INSPECTION REPORTS FOR REVIEW. 7. STRUCTURAL MEMBERS SHALL NOT BE MODIFIED IN THE FIELD WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER. IN THE EVENT OF A CONSTRUCTION OR FABRICATION ERROR, THE CONTRACTOR SHALL PREPARE A SKETCH WITH A PROPOSED REPAIR, AND SUBMIT IT FOR APPROVAL PRIOR TO PERFORMING ANY CORRECTIVE WORK. 10. THE TRADE CONTRACTORS SHALL SUBMIT SHOP AND ERECTION DRAWINGS (COLLECTIVELY KNOWN HEREIN AS "SHOP DRAWINGS") FOR REVIEW PRIOR TO PROCEEDING WITH FABRICATION AND/OR CONSTRUCTION. a. 8. ANY ANTICIPATED MODIFICATIONS TO THE CONSTRUCTION DOCUMENTS MUST BE SUBMITTED TO THE OWNER AND STRUCTURAL ENGINEER FOR REVIEW AND COMMENTS. THIS OFFICE CANNOT CERTIFY ANY UNAUTHORIZED DEVIATIONS TO THE CONSTRUCTION DOCUMENTS. THIS OFFICE RESERVES THE RIGHT TO REQUEST THE CONTRACTOR TO OBTAIN THE SERVICES OF AN INDEPENDENT STRUCTURAL ENGINEER REGISTERED IN THE STATE OF NEW HAMPSHIRE TO VISIT THE PROJECT SITE AND TO DESIGN ANY REQUIRED REPAIRS OR TO JUSTIFY THE INSTALLED MODIFICATION. ALL ENGINEERING CALCULATIONS AND SKETCHES MUST BE SUBMITTED TO THE DESIGN TEAM FOR REVIEW AND APPROVAL. 9. PRIOR TO A GENERAL CONTRACTOR/CONSTRUCTION MANAGER REQUEST FOR AN INSPECTION BY ODEH ENGINEERS FOR A COMPLETED STAGE OF CONSTRUCTION, THE GENERAL CONTRACTOR/ CONSTRUCTION MANAGER SHALL SUBMIT A STATEMENT STATING THAT “ALL WORK HAS BEEN COMPLETED IN CONFORMANCE WITH THE STRUCTURAL CONTRACT DRAWINGS AND SHOP DRAWINGS WITHOUT EXCEPTION OR HAS BEEN PERFORMED WITH FORMAL WRITTEN EXCEPTIONS ORIGINATING FROM OR AUTHORIZED BY ODEH ENGINEERS, INC.”. PRIOR TO RELEASE OF THE FINAL PROJECT CERTIFICATION TO THE BUILDING OFFICIAL, ODEH ENGINEERS REQUIRES A LETTER FROM THE PRINCIPAL OF THE GENERAL CONTRACTOR/CONSTRUCTION MANAGER STATING THAT “ALL WORK INDICATED ON THE STRUCTURAL DRAWINGS HAS BEEN PERFORMED WITHOUT EXCEPTION OR WAS PERFORMED WITH FORMAL WRITTEN EXCEPTIONS ORIGINATING FROM OR AUTHORIZED BY ODEH ENGINEERS, INC.”. 50 PSF d. MECHANICAL ROOMS ....................................................................... 150 PSF II. DESIGN LOADS 2. 3. a. b. e. a. CLASSROOMS....................................................................................... CORRIDORS....................................................................................... LIVE LOAD REDUCTION PER IBC 2009 SECTION 1607.9 APPLIED TO COLUMNS ONLY ROOF LIVE LOAD (PER IBC 2009 SECTION 1608 & 780 CMR TABLE 1604.11) FLOOR LIVE LOADS (PER IBC 2009 SECTION 1607) GROUND SNOW LOAD, Pg ............................................................... 40 PSF 100 PSF 50 PSF b. SNOW EXPOSURE FACTOR, Ce ....................................................... 1.0 c. THERMAL FACTOR, Ct ........................................................................ 1.0 d. SNOW LOAD IMPORTANCE FACTOR, Is .......................................... 1.15 1. a. OCCUPANCY CATEGORY ................................................................. GENERAL DESIGN REQUIREMENTS USED TO DESIGN REINFORCING AND OTHER REPAIRS (PER IEBC 2009 ) III c. OFFICES............................................................................................. e. MINIMUM FLAT ROOF SNOW LOAD, Pf ............................................ 40 PSF* IV. REPAIR OF CAST-IN-PLACE CONCRETE 1. b. c. ALL CONCRETE WORK SHALL CONFORM TO ACI 318 AND 301 REQUIREMENTS. 2. 3. 4. 5. CONCRETE RESTORATION MATERIALS: PRETHREADED ARMATURES SHALL BE 1/4" DIA. STAINLESS STEEL HEAVY GAUGE WIRE SHALL BE 16 GAUGE STAINLESS STEEL WIRE. REFER TO DETAILS, SPECIFICATIONS AND PLAN NOTES FOR CONCRETE REPAIR AND RESTORATION PROCEDURES. a. CONCRETE BONDING PRIMER: SIKA ARMATEC 110 OR APPROVED EQUAL. V. CLAY BRICK MASONRY 1. IT IS THE INTENT OF THIS WORK TO REPLACE FAILED AND DAMAGED STRUCTURAL CLAY TILE MASONRY WITH NEW LOAD BEARING CLAY BRICK MASONRY WHERE INDICATED. 2. MORTAR MATERIALS: VI. STRUCTURAL STEEL 1. ALL WORK SHALL CONFORM TO THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION SPECIFICATIONS AND ITS CODE OF STANDARD PRACTICE. 2. MATERIAL SPECIFICATIONS: 3. ALL WELDING OPERATIONS SHALL BE PERFORMED BY AWS CERTIFIED WELDERS IN CONFORMANCE WITH ALL APPLICABLE REQUIREMENTS. USE E-70XX WELDING ELECTRODES. 4. STRUCTURAL STEEL CONNECTIONS SHALL DEVELOP THE GREATER OF THE FOLLOWING: THE ASD LOADS LISTED ON THE DRAWINGS. (1/2) OF MEMBERS' TOTAL UNIFORM LOAD CAPACITY AS DETERMINED FROM THE AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION (ASD). 5. ALL STEEL TO STEEL BOLTED CONNECTIONS SHALL USE ASTM A325-F (SLIP CRITICAL) BOLTS (3/4"ø MINIMUM), UNLESS NOTED OTHERWISE. BOLTED CONNECTIONS SHALL BE DESIGNED PER THE AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION (ASD) AND THE AISC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS (ASD). 6. 7. AFTER ERECTION IS COMPLETE, TOUCH-UP ALL GALVANIZED SURFACES DAMAGED DURING TRANSPORTATION, ERECTION,AND FIELD WELDING USING APPROVED ZINC RICH PAINTING SYSTEM SUCH AS ZRC OR ZIRP. MOMENT CONNECTIONS, IF REQUIRED, SHALL BE DESIGNED TO DEVELOP THE FULL MOMENT CAPACITY OF THE MEMBERS. ALL MOMENT CONNECTIONS SHALL BE DESIGNED BY A P.E. REGISTERED IN THE STATE OF NEW HAMPSHIRE. SUBMIT STAMPED DRAWINGS AND CALCULATIONS FOR REVIEW. W, WT SHAPES ...................................................................... S, M, HP, C, MC SHAPES ....................................................... SQUARE & RECTANGULAR HSS .......................................... ROUND HSS ........................................................................... L SHAPES, MISC. PLATES & BARS....................................... THREADED RODS, THREADED FASTENERS ..................... BOLTS ..................................................................................... ASTM A500, GRADE C (50 KSI) ASTM A500, GRADE C (46 KSI) ASTM A36 ASTM A36 ASTM A325 OR A490 ASTM A572, GRADE 50 ASTM A992 (50 KSI) THE WORK UNDER THIS CONTRACT IS ORDINARY REPAIR WORK TO THE SOUTH CLASSROOM WING OF THE PORTSMOUTH MIDDLE SCHOOL TO REINFORCE AND TO REPAIR AND RESTORE THE EXISTING FIRST LEVEL FLOOR FRAMING AND TO REPAIR BEARING WALL DAMAGE IN THE ATTIC. THE SOUTH CLASSROOM WING OF THE PORTSMOUTH MIDDLE SCHOOL IS AN EXISTING STRUCTURE BUILT IN 1930 AND RENOVATED IN 2013. THE WORK OF THIS CONTRACT ARE CLASSIFIED AS ORDINARY REPAIRS AND THE RESULTING WORK WILL NOT MODIFY THE EXISTING RESISTANCE TO LATERAL WIND AND EARTHQUAKE LOADS. RUST INHIBITIVE PRIMER: SIKA ARMATEC 110 OR APPROVED EQUAL. REPAIR AND RESTORATION MORTAR: SIKATOP 123 OR APPROVED EQUAL. b. c. a. PORTLAND CEMENT: ASTM C150, TYPE II OR II. HYDRATED LIME: ASTM C207, TYPE S MIX MORTAR WITH EQUAL PARTS OF PORTLAND CEMENT AND HYDRATED LIME. VIII. COORDINATION OF ASSOCIATED PLUMBING WORK 1. IT IS THE INTENT OF THIS WORK TO TEMPORARILY CUT EXISTING SANITARY WASTE, DRAINAGE AND WATER SUPPLY LINES IN THE CRAWL SPACE, AS REQUIRED TO INSTALL THE NEW STRUCTURAL STEEL REINFORCING; AND TO REINSTALL PORTIONS OF LINES REMOVED USING THE SAME MATERIALS. 2. ALL PLUMBING WORK, INCLUDING ALL TEMPORARY INTERRUPTION, DISCONNECTION AND RECONNECTION IS TO BE PERFORMED BY PLUMBERS LICENSED BY THE STATE OF NEW HAMPSHIRE. ALL PLUMBING WORK, INCLUDING ALL TEMPORARY INTERRUPTION DISCONNECTION AND RECONNECTION, IS TO BE CONDUCTED IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL CODES, LAWS AND ORDINANCES. IX. COORDINATION OF ASSOCIATED ELECTRICAL WORK IT IS THE INTENT OF THIS WORK TO NOT DISTURB EXISTING MAIN ELECTRICAL CONDUIT IN THE CRAWL SPACE. WHERE THE SMALLER ELECTRICAL BRANCH CONDUIT AND CONNECTIONS MUST BE TEMPORARILY OR PERMANENTLY REMOVED AND RELOCATED IN THE CRAWL SPACE TO INSTALL THE NEW STRUCTURAL STEEL REINFORCING, ELECTRICAL CONDUIT, WIRING AND THEIR PROPER CONNECTIONS ARE TO BE REINSTALLED USING THE SAME MATERIALS. 3. ALL ELECTRICAL WORK, INCLUDING ALL TEMPORARY INTERRUPTION, DISCONNECTION AND RECONNECTION IS TO BE PERFORMED BY ELECTRICIANS LICENSED BY THE STATE OF NEW HAMPSHIRE. ALL ELECTRICAL WORK, INCLUDING ALL TEMPORARY INTERRUPTION DISCONNECTION AND RECONNECTION, IS TO BE CONDUCTED IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL CODES, LAWS AND ORDINANCES. 2. DATA CABLE MAY NOT BE DISCONNECTED, BUT MAY BE TEMPORARILY SHIFTED TO INSTALL NEW STRUCTURAL STEEL REINFORCING. X. GENERAL NOTES REGARDING DEMOLITION 1. ALL WORK SHALL CONFORM TO APPLICABLE PROVISIONS OF ALL STATE AND LOCAL CODES AND ORDINANCES. 2. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AS THEY RELATE TO CONSTRUCTION AND DEMOLITION. REPORT TO THE OWNER AND STRUCTURAL ENGINEER ALL OBSERVATIONS AND ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK. IN AREAS OF DISCREPANCY, DEMOLITION SHALL NOT PROCEED WITHOUT WRITTEN APPROVAL FROM THE OWNER AND ENGINEER OF RECORD. 3. WHERE DETAILS FOR SPECIFIC CONDITIONS ARE NOT SHOWN ON THESE PLANS, USE DETAILS FOR THE MOST NEARLY SIMILAR CONDITIONS SHOWN ON THE STRUCTURAL DRAWINGS AS DETERMINED BY THE OWNER AND STRUCTURAL ENGINEER OF RECORD. REPORT ANY COORDINATION ISSUES IMMEDIATELY TO THE ARCHITECT FOR REVIEW. 5. 6. IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDE FOR A SAFE AND EFFICIENT METHOD OF SHORING AND/OR BRACING THE EXISTING STRUCTURE AS REQUIRED DURING ALL DEMOLITION AND CONSTRUCTION PHASES. NOTE THAT TEMPORARY BRACING IS REQUIRED FOR ALL COLUMNS AND WALLS TO REMAIN WHERE INTERCONNECTED FRAMING MEMBERS ARE TO BE REMOVED. 4. DEMOLITION OF FRAMING ELEMENTS SHOWN ON THESE DRAWING MAY VARY BASED ON THE CONSTRUCTION SEQUENCE AND THE SCHOOL REQUIREMENTS TO REMAIN OPERATIONAL DURING CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ADEQUATE CONTINGENCY IN BUDGET AND SCHEDULE TO ALLOW FOR MODIFICATIONS AND REVISIONS AS REQUIRED DUE TO THESE SPECIAL CONDITIONS. 7. THE CONTRACTOR SHALL ENGAGE A STRUCTURAL ENGINEER, LICENSED IN THE STATE OF NEW HAMPSHIRE TO PROVIDE STAMPED STRUCTURAL CALCULATIONS AND DRAWINGS FOR ALL TEMPORARY SHORING AND BRACING SYSTEMS, AS WELL AS AN ANALYSIS OF ANY TEMPORARY LOADS THAT THE CONTRACTOR CHOOSES TO IMPOSE UPON THE EXISTING STRUCTURE. 8. 9. DEMOLITION WORK SHALL BE PERFORMED IN SUCH A MANNER AS TO PRESERVE THE INTEGRITY OF ALL ADJACENT STRUCTURAL ELEMENTS. WHERE NECESSARY, PRECUT CONNECTIONS TO STRUCTURAL ELEMENTS TO REMAIN IN ORDER TO AVOID DAMAGE DURING REMOVAL OF CONNECTED FRAMING MEMBERS. UTILIZE HAND TOOLS WHERE REQUIRED. THE CONTRACTOR SHALL TAKE ALL NECESSARY MEASURES TO PROTECT THE EXISTING BUILDING ELEMENTS TO REMAIN DURING DEMOLITION. DO NOT CUT OR ALTER ANY OF THE EXISTING STRUCTURE OR ARCHITECTURAL ELEMENTS TO REMAIN WITHOUT PRIOR WRITTEN APPROVAL FROM THE ARCHITECT OR ENGINEER OF RECORD. PROVIDE PROTECTION FOR EXISTING WALLS, COLUMNS, BRACES, AND OTHER BUILDING ELEMENTS TO REMAIN FROM FALLING DEBRIS. ANY DAMAGE TO EXISTING ELEMENTS TO REMAIN SHALL BE REPAIRED BY THE CONTRACTOR AT HIS OWN EXPENSE. ALL BIDDERS SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING FACILITY, LIMITATIONS TO ACCESS THE BUILDING FOR PERSONNEL AND EQUIPMENT, AND OTHER COORDINATION RELATED ISSUES. ANY DISCREPANCIES, OMISSIONS, OR VARIATIONS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS THAT ARE DISCOVERED DURING THE BIDDING PERIOD SHALL BE IMMEDIATELY COMMUNICATED IN WRITING TO THE OWNER AND ENGINEER. VII. STRUCTURAL LUMBER (PSL COLUMN) 1. ALL WORK SHALL BE IN CONFORMANCE WITH THE STANDARDS, SPECIFICATIONS, & REQUIREMENTS OF THE AMERICAN FOREST & PAPER ASSOCIATION (AF&PA) AND APA - THE ENGINEERED WOOD ASSOCIATION (APA). 2. ALL LUMBER USED IN A STRUCTURAL CAPACITY SHALL BE S-P-F No.1/No.2 OR BETTER FOR ALL APPLICATIONS. 3. ANY WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY, EXPOSED TO UNHEATED BASEMENT AND CRAWL SPACES, OR EXPOSED TO THE EXTERIOR SHALL BE PRESERVATIVE-TREATED. 4. ALL WOOD CONNECTORS (JOIST & BEAM HANGERS, POST CAPS & BASES, HURRICANE STRAPS, ETC.) SHALL BE GALVANIZED STEEL CONNECTORS AS MANUFACTURED BY "SIMPSON STRONG-TIE" OF PLEASANTON, CA (OR AN APPROVED EQUAL). ALL ENGINEERED WOOD COLUMN MEMBERS SHALL BE "WOLMANIZED" PRESERVATIVE TREATED PARALLEL STRAND LUMBER (PSL) AS MANUFACTURED BY "iLEVEL by WEYERHAEUSER" OF BOISE, IDAHO. 5. 6. A CONTINUOUS LOAD PATH MUST BE PROVIDED TO THE BUILDING FOUNDATION AT ALL CONCENTRATED LOADS. INCLUDING BUT NOT LIMITED TO PROVIDING SOLID BLOCKING AT THE INTERSTITIAL FLOOR STRUCTURE SPACE BETWEEN A POST FROM THE LEVEL ABOVE SUPPORTED BY A POST FROM THE LEVEL BELOW. CLAY BRICK UNITS SHALL BE ASTM C216, GRADE SW, TYPE FBS. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 3. 4. REFER TO DETAILS, SPECIFICATIONS AND PLAN NOTES FOR ADDITIONAL CLAY BRICK MASONRY INSTALLATION REQUIREMENTS. 1. IT IS NOT THE INTENT OF THIS WORK TO REDESIGN OR REDIRECT THE TEMPORARILY INTERRUPTED PLUMBING SYSTEMS. IT IS THE INTENT OF THIS WORK TO RESTORE THE TEMPORARILY INTERRUPTED SYSTEMS TO THEIR PREVIOUS ROUTES AND FUNCTIONS AFTER COMPLETION OF THE INSTALLATION OF THE NEW STRUCTURAL STEEL REINFORCING. 3. XII. SPECIAL NOTES REGARDING THE USE OF THESE DRAWINGS 3. VERIFY IN FIELD ALL DIMENSIONS AND LOCATIONS AND GEOMETRY OF EXISTING STRUCTURES PRIOR TO CONSTRUCTION. ALL EXISTING DIMENSIONS ARE APPROXIMATE. NOTIFY THE A/E IMMEDIATELY OF ANY DISCREPANCY BETWEEN THE FIELD CONDITIONS AND THE CONTRACT DRAWINGS. 4. CONTRACTOR SHALL CARRY A CONTINGENCY FOR ADDITIONAL SCOPE ITEMS NOT SHOWN ON THESE DRAWINGS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: a. ENCOUNTERED SITE CONDITIONS. b. ADDITIONAL FRAMING TO SUPPORT MECHANICAL EQUIPMENT AND PENETRATIONS THROUGH STEEL BEAMS DUE ENCOUNTERED CONDITIONS. 7. IT IS RECOMMENDED THAT A PRE-CONSTRUCTION MEETING BE HELD WITH ALL SUBCONTRACTORS TO REVIEW THE PROJECT REQUIREMENTS AND POTENTIAL DESIGN AND CONSTRUCTION ISSUES. 2. ALL REQUESTS FOR INFORMATION SHALL BE COORDINATED THROUGH THE OWNER AND ENGINEER. 1. THIS BID SET OF DRAWINGS IS BEING PROVIDED FOR PRELIMINARY MAJOR STRUCTURAL STEEL AND CONCRETE REPAIR BIDDING PURPOSES ONLY. THESE DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION. WHILE THESE DRAWINGS CAN BE USED TO OBTAIN A GENERAL UNDERSTANDING OF THE STRUCTURAL SYSTEMS INVOLVED, OMISSIONS AND INCONSISTENCIES BETWEEN SHEETS AND BETWEEN DIFFERENT TRADES WILL EXIST. XI. ENGINEERING REQUIREMENTS FOR CONTRACTOR 5. IF THE CONTRACTOR DEEMS IT NECESSARY TO MODIFY OR REMOVE ANY PORTION OF THE EXISTING STRUCTURE IN ORDER TO PERFORM THE WORK DESCRIBED WITHIN THE CONTRACT DOCUMENTS, THEN SUCH PORTIONS OF THE STRUCTURE SHALL BE REPAIRED OR REPLACED WITH EQUAL MATERIALS AND DETAILS TO MATCH THE EXISTING CONDITIONS AT NO ADDITIONAL COST TO THE OWNER; THIS WORK SHALL BE INCLUDED IN THE BASE PRICE OF THE CONTRACT. 6. ALL BEAM PENETRATIONS MAY NOT BE SHOWN ON STRUCTURAL DRAWINGS. STEEL CONTRACTORS, IN THE BASE CONTRACT, SHALL PROVIDE A UNIT ADD & DEDUCT PRICE PER PENETRATION FOR EACH PENETRATION TYPE SHOWN. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE ACTUAL QUANTITY, SIZE, AND LOCATION OF ALL REQUIRED PENETRATIONS, AND TO OBTAIN WRITTEN CONFIRMATION OF ALL PENETRATIONS FROM THE ARCHITECT, MEP ENGINEER, AND STRUCTURAL ENGINEER PRIOR TO FABRICATION. ALL CONNECTIONS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED FOR THE LOADS INDICATED ON THE GENERAL NOTES AND ON TYPICAL DETAILS. 1. THE EXISTING STRUCTURAL FRAMING SYSTEM MAY REQUIRE SHORING DURING CONSTRUCTION. THE CONTRACTOR MUST PROVIDE A TEMPORARY SHORING SYSTEM DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED FOR FLOOR AND ROOF FRAMING AS REQUIRED DURING DEMOLITION. THE CONTRACTOR MUST SUBMIT SIGNED, STAMPED DRAWINGS AND CALCULATIONS FOR REVIEW PRIOR TO BEGINNING WORK. 2. III. EXISTING CONDITIONS 1. THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FOR DIFFERENCES IN CONDITIONS SHOWN, INCLUDING BUT NOT LIMITED TO: a) DIFFERENT FRAMING CONDITIONS b) DIFFERENT FOUNDATION CONDITIONS c) HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS 2. WHERE DISCREPANCIES BETWEEN THE DESIGN DRAWINGS AND FIELD CONDITIONS ARE FOUND, OR EXISTING STRUCTURAL MEMBERS AND CONNECTIONS ARE FOUND TO BE DAMAGED OR DETERIORATED TO A DIMINISHED CAPACITY AND ARE NOT SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL SUBMIT DETAILED SKETCHES OF THE EXISTING CONDITIONS TO THE OWNER AND ENGINEER FOR REVIEW PRIOR TO COMMENCING WITH WORK. MODIFICATIONS TO CURRENT DETAILS OR ADDITIONAL NEW DETAILS MAY BE REQUIRED BASED ON THE ACTUAL FIELD CONDITIONS. 3. 4. EXISTING FRAMING MEMBERS SHOWN ON THESE DRAWINGS ARE DESIGNATED BY THEIR NOMINAL SIZE, UNLESS NOTED OTHERWISE. ACTUAL MEMBER SIZES SHALL BE VERIFIED IN THE FIELD. EXISTING CONDITIONS ON THESE DRAWINGS ARE REPRODUCED, IN WHOLE OR IN PART, FROM EXISTING DRAWINGS AND LIMITED VISUAL OBSERVATIONS OF THE EXISTING STRUCTURE AND SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING WITH WORK. THE SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE LATEST EDITION OF THE CODE OF STANDARD PRACTICE FOR EACH RESPECTIVE TRADE IN CONJUNCTION WITH ADDITIONAL SHOP DRAWING REQUIREMENTS INDICATED ON THESE DRAWINGS. ALL SUBMITTALS SHALL BE IN UNLOCKED PDF FORMAT WITH SEARCHABLE TEXT. ALL SHOP DRAWINGS SHALL BE FULLY DEVELOPED BY THE TRADE CONTRACTORS OR BY AGENTS OF THE CONTRACTORS. CAD FILES, PHOTOCOPIES, OR OTHER REPRODUCTIONS OF THE CONTRACT DRAWINGS IN WHOLE OR IN PART SHALL NOT BE USED BY THE TRADE CONTRACTORS OR THEIR AGENTS FOR THE PREPARATION AND DEVELOPMENT OF SHOP DRAWINGS WITHOUT THE EXPRESSED WRITTEN CONSENT OF ODEH ENGINEERS, INC. b. c. IF DURING THE PROGRESS OF THE ASSOCIATED WORK, REDESIGN OF THE PLUMBING SYSTEMS BECOMES NECESSARY, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE SERVICES OF A PROFESSIONAL PLUMBING ENGINEER LICENSED BY THE STATE OF NEW HAMPSHIRE TO PERFORM THE DESIGN AND STAMP ALL SUCH DESIGN WORK. 4. IF DURING THE PROGRESS OF THE ASSOCIATED ELECTRICAL WORK, REDESIGN OF THE ELECTRICAL SYSTEMS BECOMES NECESSARY, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE SERVICES OF A PROFESSIONAL ELECTRICAL ENGINEER LICENSED BY THE STATE OF NEW HAMPSHIRE TO PERFORM THE DESIGN AND STAMP ALL SUCH DESIGN WORK. 4. www.odehengineers.com Fax: Phone: 401.724.1981 401.724.1771 Avenue Spring Mineral 1223 02904 RI Providence, North PROJECT TITLE SHEET CONTENTS DRAWING NO. PROJECT NO. DRAWN BY SCALE DATE CHECKED BY 1/2" = 1'-0" GENERAL NOTES 155 Parrott Ave. Portsmouth, NH 03801 PORTSMOUTH MIDDLE SCHOOL S0.0 2015-00097 MTS/CGS MARCH 11, 2016 DJO S0.0 GENERAL NOTES S1.0 JOIST REINFORCING PLAN S1.0A ALTERNATE 1 - JOIST REINFORCING PLAN S1.1 ROOF AND ATTIC FRAMING PART PLAN AND DETAILS S2.0 TYPICAL REINFORCING DETAILS S2.0A ALTERNATE 1 - TYPICAL REINFORCING DETAILS S2.1 REINFORCING DETAILS S2.1A ALTERNATE 1 - REINFORCING DETAILS

Upload: vanbao

Post on 13-Apr-2018

258 views

Category:

Documents


3 download

TRANSCRIPT

ABBREVIATIONS:A/E ARCHITECT/ENGINEERADDN'L ADDITIONALB BOTTOMB.O. BOTTOM OFBLDG BUILDINGC.L. CENTER LINECMU CONCRETE MASONRY UNITCONC. CONCRETECONN. CONNECTIONCONT. CONTINUOUSCOORD. COORDINATEDIM. DIMENSIONDWG DRAWINGE.F. EACH FACEEL. ELEVATIONELEC. ELECTRICALEXT. EXTERIORFDN FOUNDATIONFTG FOOTINGGALV. GALVANIZEDHSS HOLLOW STRUCTURAL SECTIONK KIP, KIPS (1 KIP = 1000 LBS)LB, LBS POUND, POUNDSLFH LONG FACE HORIZONTAL (TUBES)LFV LONG FACE VERTICAL (TUBES)LLH LONG LEG HORIZONTAL (L-ANGLES)LLV LONG LEG VERTICAL (L-ANGLES)MAX. MAXIMUMMECH. MECHANICALMIN. MINIMUMN.T.S. NOT TO SCALEO.C. ON CENTERO.H. OPPOSITE HANDOEI ODEH ENGINEERS, INC.OPN'G OPENINGP.E. PROFESSIONAL ENGINEERPL. PLATEPSF POUNDS PER SQUARE FOOTP.T. PRESERVATIVE TREATED (WOOD)REINF. REINFORCED, REINFORCEMENT, ETC.REQ'D REQUIREDSIM. SIMILARSPECS SPECIFICATIONSSS STAINLESS STEELSTL STEELT&B TOP AND BOTTOMT.O. TOP OFT.O.W. TOP OF WALLT.O.S. TOP OF STEELTYP. TYPICALU.N.O. UNLESS NOTED OTHERWISEVERT. VERTICALV.I.F. VERIFY IN FIELDw/ WITH@ AT

- INDICATES CONCRETE MASONRY UNIT (CMU).SECTION VIEW

- INDICATES BRICK VENEERSECTION VIEW

- INDICATES SECTION OR DETAIL

ABBREVIATIONS & SYMBOLS LEGEND

- INDICATES COLUMN GRID.

SECTION DESIGNATION,SECTION APPEARS ON SAME SHEET

-

##

- INDICATES SECTION OR DETAIL

SHEET NUMBER WHERE SECTION APPEARS

SECTION DESIGNATION

##

S#.##

STRUCTURAL DRAWING LIST

GENERAL NOTESI. GENERAL

1.

ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL APPLICABLE STATE AND LOCAL CODESAND STANDARDS, INCLUDING BUT NOT LIMITED TO:...INTERNATIONAL BUILDING CODE 2009 WITH AMENDMENTS AND ITS APPLICABLE REFERENCEDSTANDARDS....INTERNATIONAL EXISTING BUILDING CODE 2009 (ORDINARY REPAIR PROVISIONS)...ANSI/ASCE 7-05...OTHER CODES AND STANDARDS AS LISTED UNDER OTHER SECTIONS OF THESE GENERAL NOTESAND SPECIFICATIONS.

2.

IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS ANDDIMENSIONS AS THEY RELATE TO NEW CONSTRUCTION. REPORT TO THE ARCHITECT/ENGINEER ALLOBSERVATIONS AND ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK.

3.

WHERE DETAILS FOR SPECIFIC CONDITIONS ARE NOT SHOWN ON THESE PLANS, USEDETAILS FOR THE MOST NEARLY SIMILAR CONDITIONS SHOWN ON THE STRUCTURALDRAWINGS AS DETERMINED BY THE OWNER AND STRUCTURAL ENGINEER OFRECORD. REPORT ANY COORDINATION ISSUES IMMEDIATELY TO THE OWNER FORREVIEW.

4.

5. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDE FOR A SAFE ANDEFFICIENT METHOD OF SHORING AND/OR BRACING THE STRUCTURE DURING ALLCONSTRUCTION PHASES. SUBMIT AN OUTLINE OF PROPOSED PROCEDURE TO THE OWNER ANDENGINEER BEFORE CONSTRUCTION COMMENCES.

6. ALL WORK SHALL BE CONTINUOUSLY MONITORED AND INSPECTED BY AN INDEPENDENT TESTINGAGENCY. SUBMIT ALL TEST AND INSPECTION REPORTS FOR REVIEW.

7. STRUCTURAL MEMBERS SHALL NOT BE MODIFIED IN THE FIELD WITHOUT WRITTEN APPROVALFROM THE STRUCTURAL ENGINEER. IN THE EVENT OF A CONSTRUCTION OR FABRICATION ERROR,THE CONTRACTOR SHALL PREPARE A SKETCH WITH A PROPOSED REPAIR, AND SUBMIT IT FORAPPROVAL PRIOR TO PERFORMING ANY CORRECTIVE WORK.

10. THE TRADE CONTRACTORS SHALL SUBMIT SHOP AND ERECTION DRAWINGS (COLLECTIVELYKNOWN HEREIN AS "SHOP DRAWINGS") FOR REVIEW PRIOR TO PROCEEDING WITH FABRICATIONAND/OR CONSTRUCTION.

a.

8. ANY ANTICIPATED MODIFICATIONS TO THE CONSTRUCTION DOCUMENTS MUST BE SUBMITTED TO THEOWNER AND STRUCTURAL ENGINEER FOR REVIEW AND COMMENTS. THIS OFFICE CANNOT CERTIFYANY UNAUTHORIZED DEVIATIONS TO THE CONSTRUCTION DOCUMENTS. THIS OFFICE RESERVES THERIGHT TO REQUEST THE CONTRACTOR TO OBTAIN THE SERVICES OF AN INDEPENDENT STRUCTURALENGINEER REGISTERED IN THE STATE OF NEW HAMPSHIRE TO VISIT THE PROJECT SITE AND TODESIGN ANY REQUIRED REPAIRS OR TO JUSTIFY THE INSTALLED MODIFICATION. ALL ENGINEERINGCALCULATIONS AND SKETCHES MUST BE SUBMITTED TO THE DESIGN TEAM FOR REVIEW ANDAPPROVAL.

9. PRIOR TO A GENERAL CONTRACTOR/CONSTRUCTION MANAGER REQUEST FOR AN INSPECTION BY ODEHENGINEERS FOR A COMPLETED STAGE OF CONSTRUCTION, THE GENERAL CONTRACTOR/CONSTRUCTION MANAGER SHALL SUBMIT A STATEMENT STATING THAT “ALL WORK HAS BEENCOMPLETED IN CONFORMANCE WITH THE STRUCTURAL CONTRACT DRAWINGS AND SHOP DRAWINGSWITHOUT EXCEPTION OR HAS BEEN PERFORMED WITH FORMAL WRITTEN EXCEPTIONS ORIGINATINGFROM OR AUTHORIZED BY ODEH ENGINEERS, INC.”. PRIOR TO RELEASE OF THE FINAL PROJECTCERTIFICATION TO THE BUILDING OFFICIAL, ODEH ENGINEERS REQUIRES A LETTER FROM THE PRINCIPALOF THE GENERAL CONTRACTOR/CONSTRUCTION MANAGER STATING THAT “ALL WORK INDICATED ONTHE STRUCTURAL DRAWINGS HAS BEEN PERFORMED WITHOUT EXCEPTION OR WAS PERFORMED WITHFORMAL WRITTEN EXCEPTIONS ORIGINATING FROM OR AUTHORIZED BY ODEH ENGINEERS, INC.”.

50 PSF

d. MECHANICAL ROOMS ....................................................................... 150 PSF

II. DESIGN LOADS

2.

3.

a.b.

e.

a.

CLASSROOMS.......................................................................................CORRIDORS.......................................................................................

LIVE LOAD REDUCTION PER IBC 2009 SECTION 1607.9 APPLIED TO COLUMNS ONLY

ROOF LIVE LOAD (PER IBC 2009 SECTION 1608 & 780 CMR TABLE 1604.11)

FLOOR LIVE LOADS (PER IBC 2009 SECTION 1607)

GROUND SNOW LOAD, Pg ...............................................................

40 PSF

100 PSF

50 PSF

b. SNOW EXPOSURE FACTOR, Ce ....................................................... 1.0

c. THERMAL FACTOR, Ct ........................................................................ 1.0

d. SNOW LOAD IMPORTANCE FACTOR, Is .......................................... 1.15

1.

a. OCCUPANCY CATEGORY .................................................................

GENERAL DESIGN REQUIREMENTS USED TO DESIGN REINFORCING AND OTHER REPAIRS (PER IEBC 2009 )

III

c. OFFICES.............................................................................................

e. MINIMUM FLAT ROOF SNOW LOAD, Pf ............................................ 40 PSF*

IV. REPAIR OF CAST-IN-PLACE CONCRETE

1.

b.c.

ALL CONCRETE WORK SHALL CONFORM TO ACI 318 AND 301 REQUIREMENTS.

2.

3.

4.

5.

CONCRETE RESTORATION MATERIALS:

PRETHREADED ARMATURES SHALL BE 1/4" DIA. STAINLESS STEEL

HEAVY GAUGE WIRE SHALL BE 16 GAUGE STAINLESS STEEL WIRE.

REFER TO DETAILS, SPECIFICATIONS AND PLAN NOTES FOR CONCRETE REPAIR ANDRESTORATION PROCEDURES.

a. CONCRETE BONDING PRIMER: SIKA ARMATEC 110 OR APPROVED EQUAL.

V. CLAY BRICK MASONRY

1. IT IS THE INTENT OF THIS WORK TO REPLACE FAILED AND DAMAGED STRUCTURAL CLAY TILEMASONRY WITH NEW LOAD BEARING CLAY BRICK MASONRY WHERE INDICATED.

2.

MORTAR MATERIALS:

VI. STRUCTURAL STEEL

1. ALL WORK SHALL CONFORM TO THE AMERICAN INSTITUTE OF STEEL CONSTRUCTIONSPECIFICATIONS AND ITS CODE OF STANDARD PRACTICE.

2. MATERIAL SPECIFICATIONS:

3. ALL WELDING OPERATIONS SHALL BE PERFORMED BY AWS CERTIFIED WELDERS INCONFORMANCE WITH ALL APPLICABLE REQUIREMENTS. USE E-70XX WELDING ELECTRODES.

4. STRUCTURAL STEEL CONNECTIONS SHALL DEVELOP THE GREATER OF THE FOLLOWING:THE ASD LOADS LISTED ON THE DRAWINGS.(1/2) OF MEMBERS' TOTAL UNIFORM LOAD CAPACITY AS DETERMINED FROM THE AISC STEELCONSTRUCTION MANUAL, 13TH EDITION (ASD).

5. ALL STEEL TO STEEL BOLTED CONNECTIONS SHALL USE ASTM A325-F (SLIP CRITICAL) BOLTS(3/4"ø MINIMUM), UNLESS NOTED OTHERWISE. BOLTED CONNECTIONS SHALL BE DESIGNED PERTHE AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION (ASD) AND THE AISC SPECIFICATION FORSTRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS (ASD).

6.

7.

AFTER ERECTION IS COMPLETE, TOUCH-UP ALL GALVANIZED SURFACES DAMAGED DURINGTRANSPORTATION, ERECTION,AND FIELD WELDING USING APPROVED ZINC RICH PAINTING SYSTEMSUCH AS ZRC OR ZIRP.

MOMENT CONNECTIONS, IF REQUIRED, SHALL BE DESIGNED TO DEVELOP THE FULL MOMENTCAPACITY OF THE MEMBERS. ALL MOMENT CONNECTIONS SHALL BE DESIGNED BY A P.E.REGISTERED IN THE STATE OF NEW HAMPSHIRE. SUBMIT STAMPED DRAWINGS ANDCALCULATIONS FOR REVIEW.

W, WT SHAPES ......................................................................S, M, HP, C, MC SHAPES .......................................................SQUARE & RECTANGULAR HSS ..........................................ROUND HSS ...........................................................................L SHAPES, MISC. PLATES & BARS.......................................THREADED RODS, THREADED FASTENERS .....................BOLTS .....................................................................................

ASTM A500, GRADE C (50 KSI)

ASTM A500, GRADE C (46 KSI)ASTM A36ASTM A36ASTM A325 OR A490

ASTM A572, GRADE 50

ASTM A992 (50 KSI)

THE WORK UNDER THIS CONTRACT IS ORDINARY REPAIR WORK TO THE SOUTH CLASSROOM WING OFTHE PORTSMOUTH MIDDLE SCHOOL TO REINFORCE AND TO REPAIR AND RESTORE THE EXISTING FIRSTLEVEL FLOOR FRAMING AND TO REPAIR BEARING WALL DAMAGE IN THE ATTIC.

THE SOUTH CLASSROOM WING OF THE PORTSMOUTH MIDDLE SCHOOL IS AN EXISTINGSTRUCTURE BUILT IN 1930 AND RENOVATED IN 2013. THE WORK OF THIS CONTRACT ARECLASSIFIED AS ORDINARY REPAIRS AND THE RESULTING WORK WILL NOT MODIFY THE EXISTINGRESISTANCE TO LATERAL WIND AND EARTHQUAKE LOADS.

RUST INHIBITIVE PRIMER: SIKA ARMATEC 110 OR APPROVED EQUAL.

REPAIR AND RESTORATION MORTAR: SIKATOP 123 OR APPROVED EQUAL.

b.c.

a. PORTLAND CEMENT: ASTM C150, TYPE II OR II.HYDRATED LIME: ASTM C207, TYPE S

MIX MORTAR WITH EQUAL PARTS OF PORTLAND CEMENT ANDHYDRATED LIME.

VIII. COORDINATION OF ASSOCIATED PLUMBING WORK

1. IT IS THE INTENT OF THIS WORK TO TEMPORARILY CUT EXISTING SANITARY WASTE, DRAINAGEAND WATER SUPPLY LINES IN THE CRAWL SPACE, AS REQUIRED TO INSTALL THE NEWSTRUCTURAL STEEL REINFORCING; AND TO REINSTALL PORTIONS OF LINES REMOVED USINGTHE SAME MATERIALS.

2.

ALL PLUMBING WORK, INCLUDING ALL TEMPORARY INTERRUPTION, DISCONNECTION ANDRECONNECTION IS TO BE PERFORMED BY PLUMBERS LICENSED BY THE STATE OF NEWHAMPSHIRE. ALL PLUMBING WORK, INCLUDING ALL TEMPORARY INTERRUPTION DISCONNECTIONAND RECONNECTION, IS TO BE CONDUCTED IN ACCORDANCE WITH ALL APPLICABLE STATE ANDLOCAL CODES, LAWS AND ORDINANCES.

IX. COORDINATION OF ASSOCIATED ELECTRICAL WORK

IT IS THE INTENT OF THIS WORK TO NOT DISTURB EXISTING MAIN ELECTRICAL CONDUIT IN THECRAWL SPACE. WHERE THE SMALLER ELECTRICAL BRANCH CONDUIT AND CONNECTIONS MUSTBE TEMPORARILY OR PERMANENTLY REMOVED AND RELOCATED IN THE CRAWL SPACE TOINSTALL THE NEW STRUCTURAL STEEL REINFORCING, ELECTRICAL CONDUIT, WIRING AND THEIRPROPER CONNECTIONS ARE TO BE REINSTALLED USING THE SAME MATERIALS.

3. ALL ELECTRICAL WORK, INCLUDING ALL TEMPORARY INTERRUPTION, DISCONNECTION ANDRECONNECTION IS TO BE PERFORMED BY ELECTRICIANS LICENSED BY THE STATE OF NEWHAMPSHIRE. ALL ELECTRICAL WORK, INCLUDING ALL TEMPORARY INTERRUPTIONDISCONNECTION AND RECONNECTION, IS TO BE CONDUCTED IN ACCORDANCE WITH ALLAPPLICABLE STATE AND LOCAL CODES, LAWS AND ORDINANCES.

2. DATA CABLE MAY NOT BE DISCONNECTED, BUT MAY BE TEMPORARILY SHIFTED TO INSTALLNEW STRUCTURAL STEEL REINFORCING.

X. GENERAL NOTES REGARDING DEMOLITION

1. ALL WORK SHALL CONFORM TO APPLICABLE PROVISIONS OF ALL STATE AND LOCALCODES AND ORDINANCES.

2. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO VERIFY ALL EXISTINGCONDITIONS AND DIMENSIONS AS THEY RELATE TO CONSTRUCTION AND DEMOLITION. REPORTTO THE OWNER AND STRUCTURAL ENGINEER ALL OBSERVATIONS AND ANY DISCREPANCIESBEFORE PROCEEDING WITH WORK. IN AREAS OF DISCREPANCY, DEMOLITION SHALL NOTPROCEED WITHOUT WRITTEN APPROVAL FROM THE OWNER AND ENGINEER OF RECORD.

3. WHERE DETAILS FOR SPECIFIC CONDITIONS ARE NOT SHOWN ON THESE PLANS, USE DETAILSFOR THE MOST NEARLY SIMILAR CONDITIONS SHOWN ON THE STRUCTURAL DRAWINGS ASDETERMINED BY THE OWNER AND STRUCTURAL ENGINEER OF RECORD. REPORT ANYCOORDINATION ISSUES IMMEDIATELY TO THE ARCHITECT FOR REVIEW.

5.

6.

IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDE FOR A SAFEAND EFFICIENT METHOD OF SHORING AND/OR BRACING THE EXISTING STRUCTURE ASREQUIRED DURING ALL DEMOLITION AND CONSTRUCTION PHASES. NOTE THATTEMPORARY BRACING IS REQUIRED FOR ALL COLUMNS AND WALLS TO REMAIN WHEREINTERCONNECTED FRAMING MEMBERS ARE TO BE REMOVED.

4. DEMOLITION OF FRAMING ELEMENTS SHOWN ON THESE DRAWING MAY VARY BASED ONTHE CONSTRUCTION SEQUENCE AND THE SCHOOL REQUIREMENTS TO REMAINOPERATIONAL DURING CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ADEQUATECONTINGENCY IN BUDGET AND SCHEDULE TO ALLOW FOR MODIFICATIONS ANDREVISIONS AS REQUIRED DUE TO THESE SPECIAL CONDITIONS.

7.

THE CONTRACTOR SHALL ENGAGE A STRUCTURAL ENGINEER, LICENSED IN THE STATE OFNEW HAMPSHIRE TO PROVIDE STAMPED STRUCTURAL CALCULATIONS AND DRAWINGS FORALL TEMPORARY SHORING AND BRACING SYSTEMS, AS WELL AS AN ANALYSIS OF ANYTEMPORARY LOADS THAT THE CONTRACTOR CHOOSES TO IMPOSE UPON THE EXISTINGSTRUCTURE.

8.

9.

DEMOLITION WORK SHALL BE PERFORMED IN SUCH A MANNER AS TO PRESERVE THEINTEGRITY OF ALL ADJACENT STRUCTURAL ELEMENTS. WHERE NECESSARY, PRECUTCONNECTIONS TO STRUCTURAL ELEMENTS TO REMAIN IN ORDER TO AVOID DAMAGE DURINGREMOVAL OF CONNECTED FRAMING MEMBERS. UTILIZE HAND TOOLS WHERE REQUIRED.

THE CONTRACTOR SHALL TAKE ALL NECESSARY MEASURES TO PROTECT THE EXISTINGBUILDING ELEMENTS TO REMAIN DURING DEMOLITION. DO NOT CUT OR ALTER ANY OF THEEXISTING STRUCTURE OR ARCHITECTURAL ELEMENTS TO REMAIN WITHOUT PRIOR WRITTENAPPROVAL FROM THE ARCHITECT OR ENGINEER OF RECORD. PROVIDE PROTECTION FOREXISTING WALLS, COLUMNS, BRACES, AND OTHER BUILDING ELEMENTS TO REMAIN FROMFALLING DEBRIS. ANY DAMAGE TO EXISTING ELEMENTS TO REMAIN SHALL BE REPAIRED BYTHE CONTRACTOR AT HIS OWN EXPENSE.

ALL BIDDERS SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING FACILITY,LIMITATIONS TO ACCESS THE BUILDING FOR PERSONNEL AND EQUIPMENT, AND OTHERCOORDINATION RELATED ISSUES. ANY DISCREPANCIES, OMISSIONS, OR VARIATIONS NOTED ONTHE DRAWINGS OR IN THE SPECIFICATIONS THAT ARE DISCOVERED DURING THE BIDDINGPERIOD SHALL BE IMMEDIATELY COMMUNICATED IN WRITING TO THE OWNER AND ENGINEER.

VII. STRUCTURAL LUMBER (PSL COLUMN)

1. ALL WORK SHALL BE IN CONFORMANCE WITH THE STANDARDS, SPECIFICATIONS, &REQUIREMENTS OF THE AMERICAN FOREST & PAPER ASSOCIATION (AF&PA) AND APA -THE ENGINEERED WOOD ASSOCIATION (APA).

2. ALL LUMBER USED IN A STRUCTURAL CAPACITY SHALL BE S-P-F No.1/No.2 OR BETTER FOR ALLAPPLICATIONS.

3. ANY WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY, EXPOSED TO UNHEATED BASEMENTAND CRAWL SPACES, OR EXPOSED TO THE EXTERIOR SHALL BE PRESERVATIVE-TREATED.

4.

ALL WOOD CONNECTORS (JOIST & BEAM HANGERS, POST CAPS & BASES, HURRICANE STRAPS,ETC.) SHALL BE GALVANIZED STEEL CONNECTORS AS MANUFACTURED BY "SIMPSON STRONG-TIE"OF PLEASANTON, CA (OR AN APPROVED EQUAL).

ALL ENGINEERED WOOD COLUMN MEMBERS SHALL BE "WOLMANIZED" PRESERVATIVE TREATEDPARALLEL STRAND LUMBER (PSL) AS MANUFACTURED BY "iLEVEL by WEYERHAEUSER" OF BOISE,IDAHO.

5.

6. A CONTINUOUS LOAD PATH MUST BE PROVIDED TO THE BUILDING FOUNDATION AT ALLCONCENTRATED LOADS. INCLUDING BUT NOT LIMITED TO PROVIDING SOLID BLOCKING AT THEINTERSTITIAL FLOOR STRUCTURE SPACE BETWEEN A POST FROM THE LEVEL ABOVESUPPORTED BY A POST FROM THE LEVEL BELOW.

CLAY BRICK UNITS SHALL BE ASTM C216, GRADE SW, TYPE FBS. REFER TO SPECIFICATIONS FORADDITIONAL REQUIREMENTS.

3.

4. REFER TO DETAILS, SPECIFICATIONS AND PLAN NOTES FOR ADDITIONAL CLAY BRICK MASONRYINSTALLATION REQUIREMENTS.

1.

IT IS NOT THE INTENT OF THIS WORK TO REDESIGN OR REDIRECT THE TEMPORARILYINTERRUPTED PLUMBING SYSTEMS. IT IS THE INTENT OF THIS WORK TO RESTORE THETEMPORARILY INTERRUPTED SYSTEMS TO THEIR PREVIOUS ROUTES AND FUNCTIONS AFTERCOMPLETION OF THE INSTALLATION OF THE NEW STRUCTURAL STEEL REINFORCING.

3.

XII. SPECIAL NOTES REGARDING THE USE OF THESE DRAWINGS

3. VERIFY IN FIELD ALL DIMENSIONS AND LOCATIONS AND GEOMETRY OF EXISTING STRUCTURESPRIOR TO CONSTRUCTION. ALL EXISTING DIMENSIONS ARE APPROXIMATE. NOTIFY THE A/EIMMEDIATELY OF ANY DISCREPANCY BETWEEN THE FIELD CONDITIONS AND THE CONTRACTDRAWINGS.

4. CONTRACTOR SHALL CARRY A CONTINGENCY FOR ADDITIONAL SCOPE ITEMS NOT SHOWN ONTHESE DRAWINGS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING:

a. ENCOUNTERED SITE CONDITIONS.

b. ADDITIONAL FRAMING TO SUPPORT MECHANICAL EQUIPMENT AND PENETRATIONSTHROUGH STEEL BEAMS DUE ENCOUNTERED CONDITIONS.

7. IT IS RECOMMENDED THAT A PRE-CONSTRUCTION MEETING BE HELD WITH ALLSUBCONTRACTORS TO REVIEW THE PROJECT REQUIREMENTS AND POTENTIAL DESIGNAND CONSTRUCTION ISSUES.

2. ALL REQUESTS FOR INFORMATION SHALL BE COORDINATED THROUGH THE OWNER ANDENGINEER.

1. THIS BID SET OF DRAWINGS IS BEING PROVIDED FOR PRELIMINARY MAJOR STRUCTURAL STEELAND CONCRETE REPAIR BIDDING PURPOSES ONLY. THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION. WHILE THESE DRAWINGS CAN BE USED TO OBTAIN A GENERAL UNDERSTANDINGOF THE STRUCTURAL SYSTEMS INVOLVED, OMISSIONS AND INCONSISTENCIES BETWEEN SHEETSAND BETWEEN DIFFERENT TRADES WILL EXIST.

XI. ENGINEERING REQUIREMENTS FOR CONTRACTOR

5. IF THE CONTRACTOR DEEMS IT NECESSARY TO MODIFY OR REMOVE ANY PORTION OF THEEXISTING STRUCTURE IN ORDER TO PERFORM THE WORK DESCRIBED WITHIN THE CONTRACTDOCUMENTS, THEN SUCH PORTIONS OF THE STRUCTURE SHALL BE REPAIRED OR REPLACEDWITH EQUAL MATERIALS AND DETAILS TO MATCH THE EXISTING CONDITIONS AT NO ADDITIONALCOST TO THE OWNER; THIS WORK SHALL BE INCLUDED IN THE BASE PRICE OF THE CONTRACT.

6. ALL BEAM PENETRATIONS MAY NOT BE SHOWN ON STRUCTURAL DRAWINGS. STEELCONTRACTORS, IN THE BASE CONTRACT, SHALL PROVIDE A UNIT ADD & DEDUCT PRICE PERPENETRATION FOR EACH PENETRATION TYPE SHOWN. IT IS THE RESPONSIBILITY OF THECONTRACTOR TO COORDINATE ACTUAL QUANTITY, SIZE, AND LOCATION OF ALL REQUIREDPENETRATIONS, AND TO OBTAIN WRITTEN CONFIRMATION OF ALL PENETRATIONS FROM THEARCHITECT, MEP ENGINEER, AND STRUCTURAL ENGINEER PRIOR TO FABRICATION.

ALL CONNECTIONS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED INTHE STATE IN WHICH THE PROJECT IS LOCATED FOR THE LOADS INDICATED ON THEGENERAL NOTES AND ON TYPICAL DETAILS.

1.

THE EXISTING STRUCTURAL FRAMING SYSTEM MAY REQUIRE SHORING DURINGCONSTRUCTION. THE CONTRACTOR MUST PROVIDE A TEMPORARY SHORING SYSTEMDESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT ISLOCATED FOR FLOOR AND ROOF FRAMING AS REQUIRED DURING DEMOLITION. THECONTRACTOR MUST SUBMIT SIGNED, STAMPED DRAWINGS AND CALCULATIONS FOR REVIEWPRIOR TO BEGINNING WORK.

2.

III. EXISTING CONDITIONS

1.

THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FOR DIFFERENCES IN CONDITIONSSHOWN, INCLUDING BUT NOT LIMITED TO: a) DIFFERENT FRAMING CONDITIONS b) DIFFERENT FOUNDATION CONDITIONS c) HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS

2.

WHERE DISCREPANCIES BETWEEN THE DESIGN DRAWINGS AND FIELD CONDITIONS ARE FOUND, OREXISTING STRUCTURAL MEMBERS AND CONNECTIONS ARE FOUND TO BE DAMAGED ORDETERIORATED TO A DIMINISHED CAPACITY AND ARE NOT SHOWN ON THESE DRAWINGS, THECONTRACTOR SHALL SUBMIT DETAILED SKETCHES OF THE EXISTING CONDITIONS TO THE OWNER ANDENGINEER FOR REVIEW PRIOR TO COMMENCING WITH WORK. MODIFICATIONS TO CURRENT DETAILSOR ADDITIONAL NEW DETAILS MAY BE REQUIRED BASED ON THE ACTUAL FIELD CONDITIONS.

3.

4. EXISTING FRAMING MEMBERS SHOWN ON THESE DRAWINGS ARE DESIGNATED BY THEIR NOMINALSIZE, UNLESS NOTED OTHERWISE. ACTUAL MEMBER SIZES SHALL BE VERIFIED IN THE FIELD.

EXISTING CONDITIONS ON THESE DRAWINGS ARE REPRODUCED, IN WHOLE OR IN PART, FROMEXISTING DRAWINGS AND LIMITED VISUAL OBSERVATIONS OF THE EXISTING STRUCTURE AND SHALLBE VERIFIED IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING WITH WORK.

THE SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE LATEST EDITION OF THECODE OF STANDARD PRACTICE FOR EACH RESPECTIVE TRADE IN CONJUNCTION WITHADDITIONAL SHOP DRAWING REQUIREMENTS INDICATED ON THESE DRAWINGS.

ALL SUBMITTALS SHALL BE IN UNLOCKED PDF FORMAT WITH SEARCHABLE TEXT.

ALL SHOP DRAWINGS SHALL BE FULLY DEVELOPED BY THE TRADE CONTRACTORS OR BYAGENTS OF THE CONTRACTORS. CAD FILES, PHOTOCOPIES, OR OTHER REPRODUCTIONS OFTHE CONTRACT DRAWINGS IN WHOLE OR IN PART SHALL NOT BE USED BY THE TRADECONTRACTORS OR THEIR AGENTS FOR THE PREPARATION AND DEVELOPMENT OF SHOPDRAWINGS WITHOUT THE EXPRESSED WRITTEN CONSENT OF ODEH ENGINEERS, INC.

b.

c.

IF DURING THE PROGRESS OF THE ASSOCIATED WORK, REDESIGN OF THE PLUMBING SYSTEMSBECOMES NECESSARY, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE SERVICESOF A PROFESSIONAL PLUMBING ENGINEER LICENSED BY THE STATE OF NEW HAMPSHIRE TOPERFORM THE DESIGN AND STAMP ALL SUCH DESIGN WORK.

4.

IF DURING THE PROGRESS OF THE ASSOCIATED ELECTRICAL WORK, REDESIGN OF THEELECTRICAL SYSTEMS BECOMES NECESSARY, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TOENGAGE THE SERVICES OF A PROFESSIONAL ELECTRICAL ENGINEER LICENSED BY THE STATE OFNEW HAMPSHIRE TO PERFORM THE DESIGN AND STAMP ALL SUCH DESIGN WORK.

4.

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

1/2" = 1'-0"

GENERAL NOTES

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S0.0

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

S0.0 GENERAL NOTES

S1.0 JOIST REINFORCING PLAN

S1.0A ALTERNATE 1 - JOIST REINFORCING PLAN

S1.1 ROOF AND ATTIC FRAMING PART PLAN AND DETAILS

S2.0 TYPICAL REINFORCING DETAILS

S2.0A ALTERNATE 1 - TYPICAL REINFORCING DETAILS

S2.1 REINFORCING DETAILS

S2.1A ALTERNATE 1 - REINFORCING DETAILS

15X

CX

DX

14X

13X

12X

11X

10X

9X

8X

7X

6X

5X

4X

3X

2X

1X

21X

22X

17X

18X

19.5X

16X

W14x30(-2' - 1")

W14x38(-1' - 11")

W14x38(-1' - 11")

W14x38(-2' - 0")

W14x38(-1' - 11")

W14x38(-2' - 0")

W16x40(-1' - 2")

W16x36(-1' - 2")

W16x26(-0' - 10")

W16x26(-0' - 10")

W10x22(-0' - 8")

W10x22(-0' - 8")

W10x22(-0' - 8")

W10x22(-2' - 4")

W10x22(-2' - 3")

W10x22(-1' - 10")

W14x43(-1' - 3")

W14x34(-1' - 1")

W14x34(-0' - 11")

W14x34(-0' - 11")

W10x22

(-0' - 9")

W10x2

2(-

0' -

9")

W10x2

2(-

0' -

9")

W10x22(-0' - 9")

W10

x22

(-0' -

11")

W10x2

2(-

0' -

9")

W10x22(-0' - 11")

W10

x22

(-0' -

11")

W10x2

2(-

0' -

9")

W10x22(-0' - 10")

W10x2

2(-

0' -

10")

W10x2

2(-

0' -

9")

W10x22(-0' - 9")

W10x22(-0' - 10")

W10x22(-0' - 9")

W16x3

6(-

0' -

9")

W10x2

2(-

0' -

8")

W10x2

2(-

0' -

9")

W10x2

6(-

1' -

0")

W10x2

6(-

1' -

1")

W10x2

6(-

1' -

1")

W10

x26

(-0' -

11")

W10x2

2(-

0' -

8")

W10x2

2(-

0' -

8")

W10

x22

(-0' -

11")W

10x2

2(-

0' -

8")W

10x2

6(-

0' -

10")

W10x2

6(-

1' -

1")

W10x2

6(-

1' -

1")

W10

x26

(-0' -

11")

W10x2

2(-

0' -

8")

W10x2

2(-

1' -

0")

W10x2

2(-

1' -

2")

W10

x22

(-0' -

11")

W10x2

2(-

1' -

1")

W10x2

2(-

1' -

4")

W10x2

2(-

1' -

1")W

10x2

2(-

0' -

9")W

10x2

6(-

1' -

0")

W10x2

6(-

1' -

2")

W10x2

2(-

1' -

2")

W10x2

2(-

1' -

1")

W12x2

2(-

0' -

10")

W10x2

2(-

1' -

0")

W10x2

2(-

1' -

5")

W10x2

2(-

1' -

3")

W10x2

2(-

1' -

4")

W10x2

2(-

1' -

5")

W10x2

2(-

1' -

0")W10

x22

(-0' -

11")

W10x2

2(-

1' -

1")

W10x2

2(-

1' -

3")

W16x36

(-1' - 1

")

W16x36(-1' - 1")

2

S2.0

_____________________

W16x4

0(-

1' -

2")

22' - 7" ±

15' - 0" ±

22' - 9" ±

4' - 0"

15' - 7"

1' - 9"

1' - 3"

W14x22(-0' - 11")

W10

x22

(-0' -

11")

W10x2

2(-

1' -

0")

W16x3

6(-

0' -

10")

1' - 11"

W14x22

(-0' - 1

1")

W14x22

(-0' - 1

0")

W10x2

2

(-1' - 1

")

W10x2

2

(-0' - 1

0")

3' - 0"

1' - 10"

1' - 10"3' - 0"

4' - 0"

1' - 10"

1' - 10"

5' - 6"

3' - 0"

5' - 6"3' - 0"

3' - 0"

1' - 10"

1' - 10"

3' - 0"

3' - 0"

3' - 0"

3' - 0

"

RELATIVE ELEVATION USED FOR NEW STEELBEAM PLACEMENT = 0-0" AT THE UNDERSIDEOF THIS JOIST. SEE NOTES.

11' -

7 1

/8" ±

11' -

1 3

/4" ±

14' -

3" ±

14' -

3 1

/2" ±

14' -

2 3

/4" ±

14' -

2 3

/4" ±

15' -

3" ±

26' -

5 3

/4" ±

15' -

3" ±

14' -

2" ±

14' -

3 1

/16" ±

14' -

3 1

1/1

6" ±

14' -

2 1

/4" ±

12' -

4" ±

12' - 0

3/8

" ±

12' - 0

" ±

28' - 7

3/4

" ±

18' - 0

1/4

" ±

22' - 7" ±

15' - 0" ±

29' - 0 1/2" ±

6' - 3 1/2" ±

22' - 8 1/8" ±

15' - 0" ±

22' - 7 7/8" ±

1

S2.0

_____________________

1

S2.0

_____________________

SIM.

1

S2.0

_____________________

SIM

.

TYP.

TYP.

COPE EXIST. WF STEEL BEAM AT EA. END ANDREFRAME AND CONNECT TO NEW WF STEEL BEAM.

SHORE AS REQUIRED DURING CONSTRUCTION.

EXIST. W14EXIST. W14

15X

CX

DX

14X

13X

12X

11X

10X

9X

8X

7X

6X

5X

4X

3X

2X

1X

21X

22X

17X

18X

19.5X

16X

EXIST. REINF. CONCRETEFOUNDATION WALL, TYP.

EXIST. 8" REINF. CONC. JOIST, TYP.

EXIST. 8" REINF. CONC. JOIST, TYP.

EXIST. 6" REINF.

CONC. JOIST, TYP.

EXIST. REINF. CONCRETEFOUNDATION WALL, TYP.

EXIST. REINF. CONCRETECOLUMN, TYP.

11' -

7 1

/8" ±

11' -

1 3

/4" ±

14' -

3" ±

14' -

3 1

/2" ±

14' -

2 3

/4" ±

14' -

2 3

/4" ±

15' -

3" ±

26' -

5 3

/4" ±

15' -

3" ±

14' -

2" ±

14' -

3 1

/16" ±

14' -

3 1

1/1

6" ±

14' -

2 1

/4" ±

12' -

4" ±

12' - 0

3/8

" ±

12' - 0

" ±

28' - 7

3/4

" ±

18' - 0

1/4

" ±

22' - 7" ±

15' - 0" ±

29' - 0 1/2" ±

22' - 8 1/8" ±

15' - 0" ±

22' - 7 7/8" ±

6' - 3 1/2" ±

ALL EXISTING CONDITIONS ON THE PLANS ARE ASSUMED BASED ONLIMITED VISUAL INSPECTIONS AND/OR ORIGINAL DESIGN DRAWINGS.THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FORDIFFERENCES IN CONDITIONS SHOWN, INCLUDING BUT NOT LIMITED TO:a) DIFFERENT FRAMING CONDITIONSb) DIFFERENT FOUNDATION CONDITIONSc) HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS

NOTES REGARDING EXISTING CONDITIONS

ALL 3D VIEWS ARE FOR REFERENCE ONLY. THE 3D VIEWS ONLYSHOW BASIC STRUCTURAL ELEMENTS; THEY DO NOT INCLUDE

DETAILS SUCH AS EXTERIOR RAMPS AND STAIRS, SLAB AND ROOFPITCHES, OR SPECIFIC STRUCTURAL DETAILS. REFER TO ALL PLANS,DETAIL SHEETS, AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL

INFORMATION. DO NOT SCALE OFF OF THIS DRAWING.

NOTES REGARDING 3D VIEWS

NOTES:

EXISTING CONDITIONS SHOWN ON THIS DRAWINGS ARE BASED ON LIMITED FIELDINVESTIGATION OF THE AS-BUILT STRUCTURE. MEMBER FRAMING SIZES MAY VARY IN THEFIELD FROM THOSE SHOWN HEREIN. ALL CONTRACTORS SHALL VERIFY ALL EXISTINGCONDITIONS AND DIMENSIONS RELATING TO NEW WORK PRIOR TO COMMENCING WITHFABRICATION AND ERECTION OF NEW STRUCTURAL ELEMENTS.

ALL INFORMATION ON THIS DRAWING IS "NEW", UNLESS NOTED OTHERWISE.

ALL DIMENSIONS AND SIZES SHOWN WITH "±" ARE FOR SCHEMATIC PURPOSES ONLY ANDSHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING WITHWORK.

- INDICATES T.O. STEEL ELEVATIONS. ALL TOP OF STEEL ELEVATIONS ARERELATIVE TO UNDERSIDE OF JOIST ELEVATION ALONG NORTH EASTFOUNDATION WALL AT GRID LINE 18X. ALL ELEVATIONS SHALL BE FIELDVERIFIED WITH EXISTING CONDITIONS.

- INDICATES LOCATION WHERE PENETRATION WILL BE REQUIRED IN NEWBEAM TO ACCOMMODATE EXISTING PLUMBING. SEE DETAILS FOR ADDITIONALINFORMATION REGARDING BEAM PENETRATIONS.

(-X'-XX")

1.

2.

3.

4.

5.

ALL EXISTING TEMPORARY ADJUSTABLE SHORES AND CRIBBING SHALL BE REMOVEDAFTER INSTALLATION OF NEW LEVEL 1 JOIST REINFORCING HAS BEEN COMPLETED ANDACCEPTED.

6.

CONCRETE DETERIORATION SCHEDULE (SEE PLAN)CONDITION # OF REPAIRS REPAIR DETAIL

VISIBLE SHEAR CRACK AT UNDERSIDE OF CONCRETE SLABOR JOIST

EXPOSED REINFORCING STEEL AT UNDERSIDE OFCONCRETE JOIST

MARK QUANTITY UNITS

REPAIR QUANTITIES ARE ESTIMATES ONLY, BASED UPON LIMITED VISUAL OBSERVATIONS. PRIOR TO CONSTRUCTION AND REPAIR, AN ADDITIONALSTUDY SHOULD BE CONDUCTED AND ALL AREAS OF DAMAGED CONCRETE SHALL BE IDENTIFIED AND REPAIRED. PROVIDE ADEQUATE CONTINGENCY

FOR ADDITIONAL REPAIRS DUE TO HIDDEN OR OTHERWISE UNFORESEEN CONDITIONS. IN ADDITION TO PROVIDING A BASE BID FOR THE QUANTITIES OFCAST-IN-PLACE CONCRETE REPAIR SCHEDULED, REFER TO THE GENERAL REQUIREMENTS AND THE BID FORM TO PROVIDE UNIT PRICES FOR

ADDITIONAL LINEAL FOOTAGE (ADD) OF REPAIRS AND UNIT PRICE FOR LESS LINEAR FOOTAGE (DEDUCT).

109 705 LF

0 N/A 0 LF

/5 S2.1

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

As indicated

JOISTREINFORCINGPLAN

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S1.0

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

SCALE: 3/32" = 1'-0"2

LEVEL 1 JOIST REINFORCING PLANSCALE: 3/32" = 1'-0"

1LEVEL 1 JOIST DEFICIENCY PLAN

N.T.S.3

3D VIEW

15X

CX

DX

14X

13X

12X

11X

10X

9X

8X

7X

6X

5X

4X

3X

2X

1X

21X

22X

17X

18X

19.5X

16X

W16x36(-1' - 2")

W10x2

2(-

0' -

9")

W10x2

2(-

0' -

9")

W10

x22

(-0' -

11")

W10x2

2(-

0' -

9")

W10

x22

(-0' -

11")

W10x2

2(-

0' -

9")

W10x2

2(-

0' -

10")

W10x2

2(-

0' -

9")

W10x22(-0' - 9")

W16x3

6(-

0' -

9")

W10x2

2(-

0' -

8")

W10x2

2(-

0' -

9")

W10x2

6(-

1' -

0")

W10x2

6(-

1' -

1")

W10x2

6(-

1' -

1")

W10

x26

(-0' -

11")

W10x2

2(-

0' -

8")

W10x2

2(-

0' -

8")

W10

x22

(-0' -

11")W10x2

2(-

0' -

8")

W10x2

6(-

0' -

10")

W10x2

6(-

1' -

1")

W10x2

6(-

1' -

1")

W10

x26

(-0' -

11")

W10x2

2(-

0' -

8")

W10x2

2(-

1' -

0")

W10x2

2(-

1' -

2")

W10

x22

(-0' -

11")

W10x2

2(-

1' -

1")

W10x2

2(-

1' -

4")

W10x2

2(-

1' -

1")W

10x2

2(-

0' -

9")

W10x2

6(-

1' -

0")

W10x2

6(-

1' -

2")

W10x2

2(-

1' -

2")

W10x2

2(-

1' -

1")

W12x2

2(-

0' -

10")

W10x2

2(-

1' -

0")

W10x2

2(-

1' -

5")

W10x2

2(-

1' -

3")

W10x2

2(-

1' -

4")

W10x2

2(-

1' -

5")

W10x2

2(-

1' -

0")

W10

x22

(-0' -

11")W10x2

2(-

1' -

1")

W10x2

2(-

1' -

3")

W16x36

(-1' - 1

")

W16x36(-1' - 1")

1

S2.0A

_____________________

W16x4

0(-

1' -

2")

22' - 7" ±

15' - 0" ±

22' - 9" ±

4' - 0"

15' - 7"1' - 9"

1' - 3"

W10

x22

(-0' -

11")

W10x2

2(-

1' -

0")

W16x3

6(-

0' -

10")

1' - 11"

W10x2

2

(-1' - 1

")

W10x2

2

(-0' - 1

0")

3' - 0"1' - 10"

1' - 10"

3' - 0"

4' - 0"

1' - 10"

1' - 10"

5' - 6"

3' - 0"

5' - 6"3' - 0"

3' - 0"

1' - 10"

1' - 10"

3' - 0"

3' - 0"

3' - 0"

3' - 0

"

RELATIVE ELEVATION USED FOR NEW STEELBEAM PLACEMENT = 0-0" AT THE UNDERSIDEOF THIS JOIST. SEE NOTES.

11' -

7 1

/8" ±

11' -

1 3

/4" ±

14' -

3" ±

14' -

3 1

/2" ±

14' -

2 3

/4" ±

14' -

2 3

/4" ±

15' -

3" ±

26' -

5 3

/4" ±

15' -

3" ±

14' -

2" ±

14' -

3 1

/16" ±

14' -

3 1

1/1

6" ±

14' -

2 1

/4" ±

12' -

4" ±

12' - 0

3/8

" ±

12' - 0

" ±

28' - 7

3/4

" ±

18' - 0

1/4

" ±

22' - 7" ±

15' - 0" ±

29' - 0 1/2" ±

6' - 3 1/2" ±

22' - 8 1/8" ±

15' - 0" ±

22' - 7 7/8" ±

2

S2.0A

_____________________

1

S2.0A

_____________________

SIM.

1

S2.0A

_____________________

SIM

.

TYP.

TYP.

W10x22(-0' - 11")

W10x22(-0' - 11")

W10x22(-0' - 11")

W10x22(-1' - 1")

W10x22(-1' - 3")

W10x22(-2' - 1")

W10x22(-1' - 11")

C12X25(-1' - 7")

C12X25(-1' - 8")

C12X25(-2' - 9")

C12X25(-1' - 10")

C12X25(-2' - 0")

C12X25(-2' - 2")

C12X25(-2' - 3")

C12X25(-2' - 6")

C12X25(-2' - 0")

C15x50(-1' - 11")

C12X25(-1' - 9")

C12X25(-1' - 9")

C12X25(-1' - 10")

C15x50(-2' - 1")

W10x22(-2' - 0")

W10x22(-2' - 0")

W10x22(-1' - 1")

W10x22(-1' - 1")

W16x36(-1' - 1")

C12X25(-1' - 11")

C15x50(-1' - 11")

C12X25(-1' - 10")

C12X25(-1' - 9")

C12X25(-1' - 9")

C15x50(-2' - 0")

C12X25(-1' - 10")

C12X25(-0' - 10")

C12X25(-1' - 8")

C12X25(-1' - 8")

C12X25(-1' - 8")

C12X25(-1' - 7")

W10x22(-0' - 10") C12X25

(-1' - 7")

C12X25(-1' - 7")

C12X25(-1' - 7")

C12X25(-1' - 7")

W10x22(-0' - 11")

C12X25(-1' - 7")

C12X25(-1' - 7")

C12X25(-1' - 7")

C12X25(-1' - 9")

W10x2

2(-

0' -

9")

C12X25(-1' - 8")

C12X25(-1' - 7")

W10x22(-1' - 1")

C12X25(-1' - 8")

W10x22(-0' - 10")

W10x22(-1' - 1")

C12X25(-1' - 7")

C12X25(-1' - 10")

C12X25(-2' - 3")

C12X25(-2' - 10")

DEMOLISH TOP OF CONCRETECOLUMN "WRAP" AS REQUIREDTO INSTALL NEW CHANNEL.

COPE EXIST. WF STEEL BEAM AT EA. END ANDREFRAME AND CONNECT TO NEW WF STEEL BEAM.

SHORE AS REQUIRED DURING CONSTRUCTION.

EXIST. W14EXIST. W14

15X

CX

DX

14X

13X

12X

11X

10X

9X

8X

7X

6X

5X

4X

3X

2X

1X

21X

22X

17X

18X

19.5X

16X

EXIST. 8" REINF. CONC. JOIST, TYP.

EXIST. 8" REINF. CONC. JOIST, TYP.

EXIST. 6" REINF.

CONC. JOIST, TYP.

EXIST. REINF. CONCRETEFOUNDATION WALL, TYP.

11' -

7 1

/8" ±

11' -

1 3

/4" ±

14' -

3" ±

14' -

3 1

/2" ±

14' -

2 3

/4" ±

14' -

2 3

/4" ±

15' -

3" ±

26' -

5 3

/4" ±

15' -

3" ±

14' -

2" ±

14' -

3 1

/16" ±

14' -

3 1

1/1

6" ±

14' -

2 1

/4" ±

12' -

4" ±

12' - 0

3/8

" ±

12' - 0

" ±

28' - 7

3/4

" ±

18' - 0

1/4

" ±

22' - 7" ±

15' - 0" ±

29' - 0 1/2" ±

22' - 8 1/8" ±

15' - 0" ±

22' - 7 7/8" ±

6' - 3 1/2" ±

EXIST. REINF. CONCRETEFOUNDATION WALL, TYP.

EXIST. REINF. CONCRETECOLUMN, TYP.

ALL 3D VIEWS ARE FOR REFERENCE ONLY. THE 3D VIEWS ONLYSHOW BASIC STRUCTURAL ELEMENTS; THEY DO NOT INCLUDE

DETAILS SUCH AS EXTERIOR RAMPS AND STAIRS, SLAB AND ROOFPITCHES, OR SPECIFIC STRUCTURAL DETAILS. REFER TO ALL PLANS,DETAIL SHEETS, AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL

INFORMATION. DO NOT SCALE OFF OF THIS DRAWING.

NOTES REGARDING 3D VIEWS

ALL EXISTING CONDITIONS ON THE PLANS ARE ASSUMED BASED ONLIMITED VISUAL INSPECTIONS AND/OR ORIGINAL DESIGN DRAWINGS.THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FORDIFFERENCES IN CONDITIONS SHOWN, INCLUDING BUT NOT LIMITED TO:a) DIFFERENT FRAMING CONDITIONSb) DIFFERENT FOUNDATION CONDITIONSc) HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS

NOTES REGARDING EXISTING CONDITIONS

NOTES:

EXISTING CONDITIONS SHOWN ON THIS DRAWINGS ARE BASED ON LIMITED FIELDINVESTIGATION OF THE AS-BUILT STRUCTURE. MEMBER FRAMING SIZES MAY VARY IN THEFIELD FROM THOSE SHOWN HEREIN. ALL CONTRACTORS SHALL VERIFY ALL EXISTINGCONDITIONS AND DIMENSIONS RELATING TO NEW WORK PRIOR TO COMMENCING WITHFABRICATION AND ERECTION OF NEW STRUCTURAL ELEMENTS.

ALL INFORMATION ON THIS DRAWING IS "NEW", UNLESS NOTED OTHERWISE.

ALL DIMENSIONS AND SIZES SHOWN WITH "±" ARE FOR SCHEMATIC PURPOSES ONLY ANDSHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING WITHWORK.

- INDICATES T.O. STEEL ELEVATIONS. ALL TOP OF STEEL ELEVATIONS ARERELATIVE TO UNDERSIDE OF JOIST ELEVATION ALONG NORTH EASTFOUNDATION WALL AT GRID LINE 18X. ALL ELEVATIONS SHALL BE FIELDVERIFIED WITH EXISTING CONDITIONS.

- INDICATES LOCATION WHERE PENETRATION WILL BE REQUIRED IN NEWBEAM TO ACCOMMODATE EXISTING PLUMBING. SEE DETAILS FOR ADDITIONALINFORMATION REGARDING BEAM PENETRATIONS.

(-X'-XX")

1.

2.

3.

4.

5.

ALL EXISTING TEMPORARY ADJUSTABLE SHORES AND CRIBBING SHALL BE REMOVEDAFTER INSTALLATION OF NEW LEVEL 1 JOIST REINFORCING HAS BEEN COMPLETED ANDACCEPTED.

6.

CONCRETE DETERIORATION SCHEDULE (SEE PLAN)CONDITION # OF REPAIRS REPAIR DETAIL

VISIBLE SHEAR CRACK AT UNDERSIDE OF CONCRETE SLABOR JOIST

EXPOSED REINFORCING STEEL AT UNDERSIDE OFCONCRETE JOIST

MARK QUANTITY UNITS

REPAIR QUANTITIES ARE ESTIMATES ONLY, BASED UPON LIMITED VISUAL OBSERVATIONS. PRIOR TO CONSTRUCTION AND REPAIR, AN ADDITIONALSTUDY SHOULD BE CONDUCTED AND ALL AREAS OF DAMAGED CONCRETE SHALL BE IDENTIFIED AND REPAIRED. PROVIDE ADEQUATE CONTINGENCY

FOR ADDITIONAL REPAIRS DUE TO HIDDEN OR OTHERWISE UNFORESEEN CONDITIONS. IN ADDITION TO PROVIDING A BASE BID FOR THE QUANTITIES OFCAST-IN-PLACE CONCRETE REPAIR SCHEDULED, REFER TO THE GENERAL REQUIREMENTS AND THE BID FORM TO PROVIDE UNIT PRICES FOR

ADDITIONAL LINEAL FOOTAGE (ADD) OF REPAIRS AND UNIT PRICE FOR LESS LINEAR FOOTAGE (DEDUCT).

109 705 LF

0 N/A 0 LF

/5 S2.1

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

As indicated

ALTERNATE 1 -JOISTREINFORCINGPLAN

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S1.0A

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

N.T.S.3

3D VIEW

SCALE: 3/32" = 1'-0"2

ALTERNATE 1 - LEVEL 1JOIST REINFORCING PLAN

SCALE: 3/32" = 1'-0"1

LEVEL 1 JOIST DEFICIENCY PLAN

15X

CX

DX

14X

13X

12X

21X

22X

17X

16X

EXIST. CEILING JOIST, V.I.F., TYP.

EXIST. CEILING JOIST, V.I.F. TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. STEEL COLUMN, TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. STEEL COLUMN, TYP.

EXIST. MASONRYBEARING WALL, ABOVE

DAMAGED PORTION OF BASE OF

EXISTING MASONRY BEARING WALL.

4

S1.1

_____________________

15X

CX

DX

14X

13X

12X

21X

22X

17X

16X

INSTALL NEW 8x8 (MIN.)PSL COLUMN.

DEMOLISH AND REMOVE CRUSHED BOTTOMCOURSE OF STRUCTURAL TERRA COTTAWALL BELOW (APPROX. 4'-0" LENGTH) ANDREPLACE WITH SOLID BRICK MASONRY.

4

S1.1

_____________________

15X

CX

DX

14X

13X

12X

21X

22X

17X

16X

DEMOLISH AND REMOVE 16" OF MASONRY

BEARING WALL. SHORE EXISTING ROOF

FRAMING PRIOR TO DEMOLITION , SEE NOTES.

EXIST. SLOPED TIMBER ROOF BEAM, V.I.F.

EXIST. TIMBER ROOFRIDGE BEAM, V.I.F.

EXIST. TIMBERPOST, V.I.F., TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. BRICK MASONRYBEARING WALL, TYP.

EXIST. MASONRYBEARING WALL

EXIST. ROOF RAFTER, TYP. V.I.F. (ALLRAFTERS NOT SHOWN FOR CLARITY)

EXIST. ROOF RAFTER, TYP. V.I.F. (ALLRAFTERS NOT SHOWN FOR CLARITY)

EXIST. ROOF RAFTER, TYP. V.I.F. (ALLRAFTERS NOT SHOWN FOR CLARITY)

EXIST. ROOF RAFTER, TYP. V.I.F. (ALLRAFTERS NOT SHOWN FOR CLARITY)

4

S1.1

_____________________

ALL EXISTING CONDITIONS ON THE PLANS ARE ASSUMED BASED ONLIMITED VISUAL INSPECTIONS AND/OR ORIGINAL DESIGN DRAWINGS.THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FORDIFFERENCES IN CONDITIONS SHOWN, INCLUDING BUT NOT LIMITED TO:a) DIFFERENT FRAMING CONDITIONSb) DIFFERENT FOUNDATION CONDITIONSc) HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS

NOTES REGARDING EXISTING CONDITIONS

NOTES REGARDING RESUPPORT OFEXISTING ROOF

IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDEFOR A SAFE AND EFFICIENT METHOD OF SHORING AND/OR BRACINGTHE STRUCTURE DURING CONSTRUCTION.

ODEH ENGINEERS RECOMMENDS THE FOLLOWING PROCEDURE FORRESUPPORTING THE EXISTING ROOF FRAMING.THE CONTRACTOR SHALLSUBMIT AN OUTLINE OF ANY PROPOSED MODIFICATIONS TO THEPROCEDURE TO THE ENGINEER BEFORE CONSTRUCTION COMMENCES.

SHORE THE END OF EXISTING TIMBER BEAM TO ATTIC FRAMING ANDCOLUMN BELOW.

1.

DEMOLISH AND REMOVE 16" OF EXISTING BRICK ANDSTRUCTRUAL TERRA COTTA MASONRY FROM THE END OF THEEXISTING LOAD BEARING MASONRY WALL.

2.

INSTALL NEW 8x8 (MIN.) PSL COLUMN.3.

DEMOLISH AND REMOVE CRUSHED BOTTOM COURSE OFSTRUCTURAL TERRA COTTA (APPROX. 4'-0" LENGTH) ANDREPLACE WITH SOLID BRICK MASONRY.

4.

AREA OF EXISTING CRUSHEDCOURSES OF STRUCTURAL CLAY TILE

EXISTING CELLULOSE AND SPRAY FOAMINSULATION IN DEPTH OF ATTIC JOIST FRAMING

EXISTING ATTIC JOIST

PORTION OF WALL TO BEDEMOLISHED AFTER SHORING

FOR NEW PSL COLUMN

SHORE END OF TIMBER ROOFGIRDER DOWN TO THE TOP OF

THE ATTIC GIRDER BELOW.

EXISTING ROOF SHEATHING AND ROOFING

EXISTING ROOF RAFTERS

EXISTING BRICK ANDSTRUCTURAL CLAY

TILE MASONRY WALLBETWEEN ROOF AND

ATTIC TO REMAIN

EXISTING TIMBER EDGE BEAM AT WALL

EXISTING TIMBER ROOF GIRDERFRAMING INTO THE END OF THE

MASONRY WALL (SKEW)

SIMPSON STRONG-TIECOLUMN BASE MODEL ABU88Z

SIMPSON STRONG-TIECOLUMN CAP MODEL CC88

NEW SOLID CLAY BRICK BEARINGWALL TO REPLACE CRUSHEDSTRUCTURAL CLAY TILE. LAY WITHHEADER STRETCHER COUSES ONEACH SIDE EVERY THIRD COURSE

EXISTING CONDITIONS AND DEMOLITION NEW WORK

EXISTING BRICK ANDSTRUCTURAL CLAY

TILE MASONRY WALLBETWEEN ROOF AND

ATTIC TO REMAIN

NEW 7 1/2" x 7 1/2" PSL COLUMN

EXISTING ATTIC GIRDER, V.I.F.

EXISTING ATTIC JOIST UNDER WALL OR WALLEXTENSION TO THIRD LEVEL CEILING BEAM, V.I.F.

EXISTING BRICK CORBEL AT TOPOF WALL (BEYOND END OF BEAM)

22X21X

17X

16X

15X

14X

13X

DX

CX

12X

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

As indicated

ROOF AND ATTICFRAMING PARTPLAN ANDDETAILS

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S1.1

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

SCALE: 1/8" = 1'-0"1

EXIST. ATTIC LEVEL PART PLAN

SCALE: 1/8" = 1'-0"3

NEW ROOF FRAMING PART PLAN

SCALE: 1/8" = 1'-0"2

EXISTING ROOF FRAMING PART PLAN

SCALE: 3/4" = 1'-0"4

WALL REPAIR IN ATTICN.T.S.

KEY PLAN

CRAWL SPACE GRADE VARIES

* FIELD VERIFY LOCATION OF NEW BEAMS BASED UPON LOCATION OF EXISTING CRACKING

1" DIA. HOLE IN HSSE.S. AT BASE PLATE

S2.1

2

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"

BOLTED BASE PLATES - TYP.

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"BOLTED BASE PLATES - TYP.

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"BOLTED BASE PLATES - TYP.

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"

BOLTED BASE PLATES - TYP.

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

WF BEAM SEE PLAN

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"BOLTED BASE PLATES - TYP.

L BRACE - SEE DETAIL

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

WF BEAM SEE PLAN

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"

BOLTED BASE PLATES - TYP.

L BRACE - SEE DETAIL

WF GIRDER SEE PLAN

3/8" STIFF. PLATES E.S.

SEE PLAN

FIELD MEASUREFIELD MEASUREFIELD MEASURE

SEE PLAN

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

3' - 0" ±*

CX DX

NOTE: THIS DETAIL APPLIES AT ALL LOCATIONS WHERE NEW WIDE FLANGE STEEL GIRDERS ARE LOCATEDBELOW WIDE FLANGE STEEL BEAMS TO ACCOMMODATE THE EXISTING ELECTRICAL AND PLUMBING. THEFRAMING CONDITION IN EACH BAY MAY VARY - SEE PLANS FOR TOP OF STEEL BEAM ELEVATIONS.

CRAWL SPACE GRADE VARIES

* FIELD VERIFY LOCATION OF NEW BEAMS BASED UPON LOCATION OF EXISTING CRACKING

1"

+/-

TY

P.

S2.1

1

WF BEAM - SEE PLANWF BEAM - SEE PLANWF BEAM - SEE PLANWF BEAM - SEE PLAN

WF BEAM - SEE PLAN WF BEAM - SEE PLAN WF GIRDER - SEE PLAN

SEE PLAN

FIELD MEASUREFIELD MEASUREFIELD MEASURE

SEE PLAN

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

3' - 0" ±*

CX DX

WF GIRDER -SEE PLAN

WF GIRDER -SEE PLAN

NOTE: AT ALL LOCATIONS WHERE NEW WIDE FLANGE STEEL GIRDERS ARE LOCATED BELOW WIDE FLANGESTEEL BEAMS TO ACCOMMODATE THE EXISTING ELECTRICAL AND PLUMBING SEE DETAILS BELOW. THEFRAMING CONDITION IN EACH BAY MAY VARY - SEE PLANS FOR TOP OF STEEL BEAM ELEVATIONS.

DESIGN ALL CONNECTIONS TO EXISTINGCONCRETE USING HILTI HIT-HY200 ADHESIVEANCHORING SYSTEM WITH 3/4" DIA. MINIMUMHIT-Z-R THREADED RODS (9" MIN. EMBEDMENT)- OR APPROVED EQUAL ADHESIVE ANCHORINGSYSTEM AND MATERIALS.

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

1/2" = 1'-0"

TYPICALREINFORCINGDETAILS

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S2.0

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

SCALE: 1/2" = 1'-0"2

TYPICAL SECTION AT JOISTREINFORCING WITH GIRDER LOW

SCALE: 1/2" = 1'-0"1

TYPICAL SECTIONAT JOIST REINFORCING

CRAWL SPACE GRADE VARIES

* FIELD VERIFY LOCATION OF NEW BEAMS BASED UPON LOCATION OF EXISTING CRACKING

SEE PLAN

FIELD MEASUREFIELD MEASUREFIELD MEASURE

SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN.PLATES DESIGN FOR 50KCOMPRESSION

DESIGNCONN. FOR30K TENSION

DESIGN CONN. FOR 30K COMPRESSIONAND 40K SHEAR

CHANNEL E.S. SEE PLAN

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLANWF BEAM SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES

DESIGN FOR 50K COMPRESSION

DESIGN CONN. FOR 30KCOMPRESSION AND 40K SHEAR

L4x4x1/4 L4x4x1/4

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLAN

CHANNEL E.S. SEE PLAN

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATESDESIGN FOR 50K COMPRESSION

DESIGN CONN. FOR 30KCOMPRESSION AND 40K SHEAR

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES DESIGN

FOR 50K COMPRESSION

DESIGN CONN. FOR 30K COMPRESSIONAND 40K SHEAR

DESIGNCONN. FOR

30K TENSION

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

3' - 0" ±*

CX DX

NOTE: THIS DETAIL APPLIES AT ALL LOCATIONS WHERE NEW STEEL CHANNELS OR BRACKETS ARE LOCATEDBELOW WIDE FLANGE STEEL BEAMS TO ACCOMMODATE THE EXISTING ELECTRICAL AND PLUMBING. THEFRAMING CONDITION IN EACH BAY MAY VARY - SEE PLANS FOR TOP OF STEEL BEAM ELEVATIONS.

S2.1A

1

WT8x18 w/ 3/8" FITTEDSTIFF. PLATES E.S. - TYP.SHOP WELD TO CHANNEL

WT8x18 w/ 3/8" FITTEDSTIFF. PLATES E.S. - TYP.

SHOP WELD TO CHANNEL WT8x18 w/ 3/8" FITTEDSTIFF. PLATES E.S. - TYP.

SHOP WELD TO CHANNEL

WT8x18 w/ 3/8" FITTEDSTIFF. PLATES E.S. - TYP.SHOP WELD TO CHANNEL

* FIELD VERIFY LOCATION OF NEW BEAMS BASED UPON LOCATION OF EXISTING CRACKING

CRAWL SPACE GRADE VARIES

SEE PLAN

FIELD MEASUREFIELD MEASUREFIELD MEASURE

SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES DESIGNFOR 50K COMPRESSION

DESIGN CONN.FOR 30K TENSION

DESIGN CONN. FOR 30K COMPRESSIONAND 40K SHEAR

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES DESIGN

FOR 50K COMPRESSION

DESIGN CONN. FOR 30K COMPRESSIONAND 40K SHEAR

DESIGN CONN.FOR 30K TENSION

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

1' - 10" ±*

TYP. SEE PLAN

3' - 0" ±*

CHANNEL E.S. SEE PLAN

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLANWF BEAM SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES

DESIGN FOR 50K COMPRESSION

DESIGN CONN. FOR 30KCOMPRESSION AND 40K SHEAR

L4x4x1/4 L4x4x1/4

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLAN

CHANNEL E.S. SEE PLAN

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATESDESIGN FOR 50K COMPRESSION

DESIGN CONN. FOR 30KCOMPRESSION AND 40K SHEAR

CX DX

NOTE: AT ALL LOCATIONS WHERE NEW STEEL CHANNELS OR BRACKETS ARE LOCATED BELOW WIDEFLANGE STEEL BEAMS TO ACCOMMODATE THE EXISTING ELECTRICAL AND PLUMBING SEE DETAILS BELOW.THE FRAMING CONDITION IN EACH BAY MAY VARY - SEE PLANS FOR TOP OF STEEL BEAM ELEVATIONS.

S2.1A

1

DESIGN ALL CONNECTIONS TO EXISTINGCONCRETE USING HILTI HIT-HY200 ADHESIVEANCHORING SYSTEM WITH 3/4" DIA. MINIMUMHIT-Z-R THREADED RODS (9" MIN. EMBEDMENT)- OR APPROVED EQUAL ADHESIVE ANCHORINGSYSTEM AND MATERIALS.

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

1/2" = 1'-0"

ALTERNATE 1 -TYPICALREINFORCINGDETAILS

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S2.0A

2015-00097

MTS/CGS

MARCH 11, 2016

DJOSCALE: 1/2" = 1'-0"

2

ALTERNATE 1 -TYPICAL SECTION AT JOISTREINFORCING WITH CHANNEL LOW

SCALE: 1/2" = 1'-0"1

ALTERNATE 1 - TYPICALSECTION AT JOIST REINFORCING

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1'-10" +/-

3

S2.1

_____________________

CX

WF BEAM - SEE PLAN

WF GIRDER, AS OCCURS -SEE PLAN

1"

± T

YP

.

EXIST. REINF. CONC. JOIST

EXIST. REINF. CONC. COLUMN

WF GIRDER, AS OCCURS- SEE PLAN

EXIST. REINF. CONC. JOIST

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACK

WELD TO BEAM AFTER GROUTING

3

S2.1

_____________________

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACKWELD TO BEAM AFTER GROUTING

NOTE: THE DETAILS SHOWN HERE ARE FOR THE PRIMARY DESIGN OPTION. SIMILAR JOIST SUPPORT DETAILS SHALL APPLYFOR THE ALTERNATE 1 REINFORCING SCHEME. SEE ALTERNATE TYPICAL REINFORCING DETAILS FOR MORE INFORMATION.

TYP. SEE PLAN

3' - 0" ±*

TYP. SEE PLAN

1'-10" +/-

4

S2.1

_____________________

1" DIA. HOLE IN HSSE.S. AT BASE PLATE

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"

BOLTED BASE PLATES - TYP.

WF GIRDER, ASOCCURS - SEE PLAN

3/8" STIFF. PLATES E.S.

CX

1" DIA. HOLE IN HSSE.S. AT BASE PLATE

WF BEAM SEE PLAN

L BRACE - SEE DETAIL

HSS6x3x1/4 w/ THROUGHPLATE SHEAR CONN. AND 1/2"BOLTED BASE PLATES - TYP.

WF GIRDER, ASOCCURS - SEE PLAN

3/8" STIFF. PLATES E.S.

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACK

WELD TO BEAM AFTER GROUTING

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACKWELD TO BEAM AFTER GROUTING

4

S2.1

_____________________

NOTE: THE DETAILS SHOWN HERE ARE FOR THE PRIMARY DESIGN OPTION. SIMILAR JOIST SUPPORT DETAILS SHALL APPLYFOR THE ALTERNATE 1 REINFORCING SCHEME. SEE ALTERNATE TYPICAL REINFORCING DETAILS FOR MORE INFORMATION.

NEW WF GIRDER - SEE PLAN

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

5/16" FITTED STIFF. PLATES E.S.

L3x3x5/16 BRACE

NEW REINFORCINGBEAM - SEE PLAN

NEW WF GIRDER - SEE PLAN

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. SHORT SLOTHOLES IN BEAM AND VERTICALSHORT SLOT HOLES IN PLATE

3/8" x 1'-0" WELDEDTHROUGH-PLATE - TYP

5/16" FITTED STIFF. PLATES E.S.

L3x3x5/16 BRACE

HSS3x6x6/16 w/ 1/2" x 6" x 1'-0"BOLTED BASE PLATE - TYP.

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACK

WELD TO BEAM AFTER GROUTINGGROUT - TYP.GROUT - THICKNESSVARIES

NEW REINFORCINGBEAM - SEE PLAN

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. SHORT SLOTHOLES IN BEAM AND VERTICALSHORT SLOT HOLES IN PLATE

3/8" x 1'-0" WELDEDTHROUGH-PLATE - TYP

HSS3x6x6/16 w/ 1/2" x 6" x 1'-0"BOLTED BASE PLATE - TYP.

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP. TACK

WELD TO BEAM AFTER GROUTINGGROUT - TYP.GROUT - THICKNESSVARIES

EXISTING CORRIDOR SLABSYSTEM ELEVATION VARIES

NEW REINFORCINGBEAM - SEE PLAN

NEW WF GIRDER - SEE PLAN

GROUT - THICKNESSVARIES

NEW REINFORCINGBEAM - SEE PLAN

NEW WF GIRDER - SEE PLAN

1/8" PERIMETER GROUTRESTRAINING PLATE -

TYP. TACK WELD TOBEAM AFTER GROUTING

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. SHORT SLOT HOLESIN BEAM AND VERTICAL SHORT SLOTHOLES IN PLATE

3/8" x 3" FITTEDSTIFF PLATES E.S.

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. SHORT SLOT HOLESIN BEAM AND VERTICAL SHORT SLOTHOLES IN PLATE

3/8" x 3" FITTEDSTIFF PLATES E.S.

GROUT - TYP.

1/8" PERIMETER GROUTRESTRAINING PLATE - TYP.

TACK WELD TO BEAM AFTERGROUTING

GROUT - THICKNESSVARIES

CONSTRUCT SAMPLES OF EACH TYPE OF REPAIR, FOR APPROVAL PRIOR TOCOMMENCING REPAIR WORK.

REINFORCING ARMATURES SHALL BE STAINLESS STEEL THREADED 1/4" DIA.ROD DRILLED-IN AND EPOXY-SET, INDIVIDUALLY SIZED AND CHOSEN ASREQUIRED FOR EACH REPAIR CONDITION.

CONCRETE BONDING PRIMER SHALL BE SIKA ARMATEC 110 EPOCEM, CONPROPRIMER, SONOPREP PLUS, OR APPROVED EQUAL.

RUST INHIBITIVE PRIMER FOR EXPOSED STEEL ELEMENTS SHALL BE SIKAARMATEC 110 EPOCEM, ECB BY CONPROCO, SONOPREP PLUS, OR APPROVEDEQUAL.

REPAIR MORTAR FOR MISSING OR DETERIORATED CONCRETE SHALL BESIKATOP-123 PLUS, CONPROSET, OR APPROVED EQUAL.

DRILLED-IN EPOXY SET ARMATURES AS REQUIRED

SAW CUT MIN. 1/2".

DEMOLISH AND REMOVE SPALLED DAMAGED OR OTHERWISESEPARATED CONCRETE TO SOUND, UNDAMAGED CONCRETE. EXPOSEENTIRE PERIMETER OF PARTIALLY EXPOSED REINFORCING BARS.

POWER WIRE BRUSH EXPOSED STEEL REINFORCEMENT IN ACCORDANCEWITH SSPC-SP-3 TO BRIGHT ORIGINAL METAL. COAT EXPOSED STEELREINFORCEMENT SURFACES WITH APPROVED RUST INHIBITIVE PRIMER.

PRIME CONCRETE SURFACES TO RECEIVE REPAIR MORTAR WITH APPROVEDCONCRETE BONDING PRIMER.. REPLACE DEMOLISHED AND MISSINGCONCRETE WITH NEW APPROVED REPAIR MORTAR IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS AND APPROVED SAMPLE REPAIRS.

X

X

PROVIDE 1 1/2"COVER OVERBARS TYP.

X

PROVIDE 1 1/2"COVER OVER

BARS TYP.

X

MIN. SPACING 3x DIA.OF LARGER ADJACENT

HOLE (TYPICAL)

SHADED REGION INDICATES ALLOWABLEAREA FOR BEAM PENETRATIONS(TYPE-A PENETRATIONS ALLOWEDMIDDLE THIRD OF BEAM SPAN ONLY)

D/3

D/3

D/3BE

AM

DE

PT

H (

D)

MIDDLE THIRDOF BEAM SPAN

NO TYPE-AOPENINGS ALLOWEDOUTSIDE OF MIDDLE

THIRD OF BEAM SPAN

CL

SUPPORT

PENETRATION TYPE-A

NOTES:1.2.3.4.5.

6.

TYPE-A PENETRATIONS ALLOWED IN MIDDLE THIRD OF BEAM DEPTH (D/3) ONLY.TYPE-A PENETRATIONS ALLOWED IN MIDDLE THIRD OF BEAM SPAN (L/3) ONLY.TYPE-A PENETRATIONS MAXIMUM ALLOWABLE ROUND FINISHED HOLE SIZE = D/3 OR 4"ø.FINISH LAST 1/8" OF HOLE BY REAMING OR GRINDING.ALL OPENINGS OUTSIDE MIDDLE THIRD OF BEAM SPAN OR LARGER THAN 4"ø.REQUIRE REINFORCEMENT TYPE-B OR TYPE-C DETAIL.L - INDICATES BEAM SPAN LENGTH.

OPENINGDIAMETER(D/3 MAX.)

REINF. HOLES: WELD 4" LONGSCHEDULE 40 SLEEVES EA.

SIDE OF WEB. SEE TYPE I

OP

EN

ING

DIA

ME

TE

R(D

/3 M

AX

.)

C L

D/2

D/2

BE

AM

DE

PT

H (

D)

CL

OPENING

CENTER LINEOF SUPPORT

OR POINT LOAD

CENTER LINE OFPENETRATION TO

SUPPORT OR POINTLOAD =

3 TIMES OPENINGDIAMETER (MINIMUM)

SCHEDULE 80PIPE SLEEVE

STEEL BEAM

SECTION

ELEVATION

PENETRATION TYPE-B

NOTES:

1.2.

3.4.

5.

6.

TYPE-B PENETRATIONS ALLOWED IN MIDDLE THIRD OF BEAM DEPTH (D/3) ONLY.TYPE-B PENETRATIONS ALLOWED OUTSIDE THE MIDDLE THIRD OF THE BEAM SPAN,BUT MUST BE A MINIMUM OF 3 TIMES THE OPENING DIAMETER FROM ALLSUPPORTS AND POINT LOADS

TYPE-B PENETRATIONS MAXIMUM ALLOWABLE ROUND FINISHED HOLE SIZE = D/3 OR 6"ø.FINISH LAST 1/8" OF HOLE BY REAMING OR GRINDING.

ALL OPENINGS NOT MEETING THE REQUIREMENTS FOR REINFORCEMENT TYPE-AOR TYPE-B REQUIRE REINFORCEMENT TYPE-C DETAIL.L - INDICATES BEAM SPAN LENGTH.

ELEVATION

TW/25/16"MIN.

TYPICAL BEAM PENETRATION DETAILSNO SCALE

W OR CHANNEL SECTION

DESIGN ALL CONNECTIONS TO EXISTINGCONCRETE USING HILTI HIT-HY200 ADHESIVEANCHORING SYSTEM WITH 3/4" DIA. MINIMUMHIT-Z-R THREADED RODS (9" MIN. EMBEDMENT)- OR APPROVED EQUAL ADHESIVE ANCHORINGSYSTEM AND MATERIALS.

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

As indicated

REINFORCINGDETAILS

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S2.1

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

SCALE:

SECTION 1 1/2" = 1'-0"

1SCALE:

SECTION 1 1/2" = 1'-0"

2

SCALE:

SECTION 1 1/2" = 1'-0"

4SCALE:

SECTION 1 1/2" = 1'-0"

3

SCALE: 1 1/2" = 1'-0"5

TYP. JOISTREINFORCING REPAIR DETAIL 6

CHANNEL E.S. SEE PLAN

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

L6x6x1/2 W/ 3/8" STIFF. PLATESDESIGN CONN. FOR 75K SHEAR

WF BEAM SEE PLANWF BEAM SEE PLAN

HSS3x3x3/8 BRACE w/ 1/2"CENTERED CONN. PLATES

DESIGN FOR 50K COMPRESSION

L4x4x1/4KEEPERANGLE

EXISTING REINFORCED CONCRETE PIER

EXISTING REINFORCED CONCRETEREINFORCING COLLAR AROUND PIERS

3

S2.1A

_____________________2

S2.1A

_____________________

WT8x18 w/ 3/8" FITTEDSTIFF. PLATES E.S. - TYP.SHOP WELD TO CHANNEL

1'-10" +/- TYP. SEE PLAN3'-0" +/- TYP. SEE PLAN

NEW C GIRDER - SEE PLANw/ DRILLED IN ANCHORSINTO EXISTING PIER

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

1/2" GUSSET PLATESHOP WELDED TO HSS

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

EXISTING CONCRETECOLLAR AROUND PIER

CRAWL SPACEGRADE VARIES

1 1

/2"

MIN

IMU

M

L6x6x1/2 ATTACHED TOFACE OF EXISTING PIER

L4x4x1/4 KEEPER ANGLEATTACHED TO FACE OFEXISTING PIER

DESIGN CONN. FOR 30KCOMPRESSIONS AND

40 K SHEAR

FACE OF EXISTING PIER

1/2" GUSSET PLATESHOP WELDED TO HSS

EXISTING CONCRETECOLLAR AROUND PIER

CRAWL SPACEGRADE VARIES

1 1

/2"

MIN

IMU

M

DESIGN CONN. FOR 30KCOMPRESSIONS AND

40 K SHEAR

NEW C GIRDER - SEE PLANw/ DRILLED IN ANCHORSINTO EXISTING PIER

L6x6x1/2 ATTACHED TOFACE OF EXISTING PIER

L4x4x1/4 KEEPER ANGLEATTACHED TO FACE OFEXISTING PIER

FACE OF EXISTING PIER

NEW REINFORCINGBEAM (BEYOND)

NEW REINFORCINGBEAM - SEE PLAN

NEW C GIRDER - SEE PLAN

1/8" PERIMETER GROUTRESTRAINING PLATE -

TYP. TACK WELD TOBEAM AFTER GROUTING

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. &VERT. SHORT SLOTHOLES IN PLATES

3/8" x 3" FITTEDSTIFF PLATES

E.S. -TYP.

GROUT - TYP.GROUT - THICKNESSVARIES

EXISTING CONCRETEPIER BEYOND

1/2" GUSSET PLATESHOP WELDED TOCHANNEL

HSS3x3x3/8 BRACE w/ 1/2"SHOP WELDED CENTEREDCONN PLATES

3/8" FITTED STIFF.PLATE - TYP.

NEW REINFORCINGBEAM - SEE PLAN

NEW C GIRDER - SEE PLAN

1/8" PERIMETER GROUTRESTRAINING PLATE -

TYP. TACK WELD TOBEAM AFTER GROUTING

EXISTING CLASSROOM SLABSYSTEM ELEVATION VARIES

3/4" A325-F BOLTS-TYPPROVIDE HORIZ. &VERT. SHORT SLOTHOLES IN PLATES

3/8" x 3" FITTEDSTIFF PLATES

E.S. -TYP.

GROUT - TYP.GROUT - THICKNESSVARIES

EXISTING CONCRETEPIER BEYOND

1/2" GUSSET PLATESHOP WELDED TOCHANNEL

HSS3x3x3/8 BRACE w/ 1/2"SHOP WELDED CENTEREDCONN PLATES

3/8" FITTED STIFF.PLATE - TYP.

WT8x18 MIN. w/ 3/8"STIFF PLATES SHOPWELDED TO CHANNEL

EXISTING CONCRETECOLLAR BEYOND

EXISTING CONCRETECOLLAR BEYOND

DESIGN ALL CONNECTIONS TO EXISTINGCONCRETE USING HILTI HIT-HY200 ADHESIVEANCHORING SYSTEM WITH 3/4" DIA. MINIMUMHIT-Z-R THREADED RODS (9" MIN. EMBEDMENT)- OR APPROVED EQUAL ADHESIVE ANCHORINGSYSTEM AND MATERIALS.

www.odehengineers.comFax:

Phone:

401.724.1981

401.724.1771

AvenueSpringMineral1223

02904RIProvidence,North

PROJECT TITLE

SHEET CONTENTS

DRAWING NO.

PROJECT NO.

DRAWN BY

SCALE

DATE

CHECKED BY

As indicated

ALTERNATE 1 -REINFORCINGDETAILS

155 Parrott Ave.Portsmouth, NH 03801

PORTSMOUTHMIDDLESCHOOL

S2.1A

2015-00097

MTS/CGS

MARCH 11, 2016

DJO

SCALE:

SECTION 1 1/2" = 1'-0"

1

SCALE:

SECTION 1 1/2" = 1'-0"

3SCALE:

SECTION 1 1/2" = 1'-0"

2