PROGRAMMING
MANUAL
www.elmeasure.com
T Srue RMS measurements. imultaneous sampling of Volts & Amps.
3 4 2 Phase, channels or Single phase 1 channels
Displays Basic, Power and Energy parameters.
3P.4W/3P.3W(Star/Delta) Programmable
Universal Auxiliary (80 - 300 VAC / DC) supply
PT & CT ratio programmable including secondary for all channels independently
“OLD” Register for storing Cleared Energy through communication
User configurable (Editable) password
Energy resetting @ 999999 KVAh × Transformer ratio.
O Pluggable or Ethernet ptional Zigbee communication ( Default RS 485).
1. FEATURES
2. KEY & LED INDICATION
Channel Indication
Channel selection
To view the parametersdownwards
3.1 Key Functions
3. PROGRAMMING MODE
In SET (Programming) mode In RUN (Measurement) mode
To select, edit and save thevalue/parameter
Channel Selection.
To view the parameters downwards.
Key
UP
DOWN To decrement the value/parameter
Press Down Up key to view and press key to edit the parameter.Press to decrement values or to select from available options. DownPress to save the value parameter.Up /Press to edit next till end of last parameter & display screen Downwill prompt display reads (YES). Press to change to (NO) . DownPress to save. Up
3.3 Clear Mode : Clear Integrator Press key Up
Press KeyDown
Press keyUpto accept the edited option
Meter displays CL r EA ‘n’(with n is blinking)
Option : (YES)/(NO)‘y’(for clearing )‘n’ (for not clearing)
Comes back to Default page(Clear Mode ends here)XXXX.LL
Displays options‘n’ can be changed by pressing
Key. Display willDownprompt to (or) ‘y’ ‘n’
Downwhile pressing key.
Options: 3P.4W/3P.3W
3.4 Display Programming Parameter
Default Option/Range
3P.4W.EL ELEMENT( )
415.0 P.P (PT Primary)
415.0 P.S (PT Secondary)
5.000 P.1(Channel-1 CT Primary)
Range: V100V-999k
Range: -50V 550V
Range: 0.5A - 99KA
Range: 0.5A - 6A
Range: 0.5A - 99KA
5.000 P.1(Channel-1 CT Secondary)
5.000 P.22(Channel- CT Primary)
Range: 0.5A - 6A5.000 P.22(Channel- CT Secondary)
+91 639-1010-320
PG/BM/V0/0518
BM 5140 Branch Circuit Monitor
3.2 Setup Procedure
Press + to enter setup mode .Up DownEnter Password (default 1000) blinking of digit indicates Edit is possible. Press to decrement value from 9 1.Down to Press to move to the next digit till 4th digit .UpIf Password is correct, editing is possible.Enters into clear mode and meter displays CLEAr
Range: 0.5A - 6A
Range: 0.5A - 6A
5.000 P.3(Channel-3 CT Primary)
5.000 P.3(Channel-3 CT Secondary)
UEC.H VA (Method of VASelection).
Option: Arithmetic (Arit), Vector harmonics, Vector
Option : 1200,2400, 4800, 9600, 19.20k, 38.40k
EVEn Pr. (Parity) Option: , ,EUEn odd no
1.000 d.I. (Device ID) : 1-247Range
Range: 0.5A - 99KA
Range: 0.5A - 6A
- - - - PW (Password) Range: 1000 -9999.
9600. bA (baud rate)
5.000 P.4(Channel-4 CT Primary)
5.000 P.4(Channel-4 CT Secondary)
LED STATUS Meaning
K - ON
M - ON
K & M ON
K & M OFF
Kilo
Mega
Giga
Direct Reading
Parameter Indica�on
1.000 U.r. (Update rate) Range: 1 to 5 Seconds
5.000 A.S.(Auto Scroll rate) Range: 1 to 10 Seconds
0.400 S.A.(Starting Current) Range: (0.2 to 10% of FS)
Once the required parameter is programmed press the DOWN key continuouslytill it reaches SAVE page
Enabling auto scrolling: Press Down key continuously for 5 seconds or until display shows ‘EnAbLE’ for scrolling. Display starts to scroll pages in downward direction forthe set Auto scroll time and different parameters can be viewed for the selectedChannel.Disabling auto scrolling: Press any key (UP/DOWN) display show ‘dlSAbL’ and returnsto normal mode.
3.5. Enabling and disabling of Auto scrolling:
Display Meaning Meaning Display Voltage line to line Voltage YB Phase
Voltage line to Neutral Voltage BR Phase
Current Y phase
Voltage RY Phase
Wa�s Total B Phase
Total VA Voltage
Power Factor Device ID
R phaseFrequency
5. Wiring Diagram:
3 Phase 4 Wire system (Star Connection(3E)Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2C
H1
CH
3
V1V2V3N
V1 V2 V3 NAUX _RS485
+
A1 A2 A3 A1 A2 A3
A1 A2 A3 A1 A2 A3
3 Phase 3 Wire system (Delta Connection(2E)
Dimension : 90 x 72 mm (Depth 67mm)
6. MECHANICAL SPECIFICATION:
Mount : DIN Rail
1 Phase 2 Wire system (Single phase)
Turn OFF the power to the circuit, when wiring the circuit. Connecting or removing measurement cables while the power is turned ON is dangerous.
Take special caution not to wire a current measurement circuit to the voltage input terminal or vice-versa.
Strip the insulation cover of the measurement cable so that when it is wired to the input terminal, the conductive parts (bare wires) do not protrude from the terminal. It is recommended to use appropriate pre lug after crimping the wire. Also, make sure to fasten the input terminal screws securely so that the cable does not come loose.
Use cables with safety terminals that cover the conductive parts for connecting to the voltage input terminals. Using a terminal with bare conductive parts is dangerous if the terminal comes loose.
After connecting the measurement cable, attach the current input protection cover for your safety. Make sure that the conductive parts are not exposed from the protection cover.
Use the suitable star screw driver and apply optimum torque to prevent damage to the meter terminals.
7. PRECAUTIONARY MEASURES TO BE TAKEN WHILE WIRING THE CIRCUIT:
4. Display of Parameter:
Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
CH
2
CH
4A1 A2 A3 A1 A2 A3
A1 A2 A3 A1 A2 A3
Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
CH
1
CH
3A1 A2 A3 A1 A2 A3
A1 A2 A3 A1 A2 A3
Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
CH
2
CH
4A1 A2 A3 A1 A2 A3
A1 A2 A3 A1 A2 A3
V1V2V3N
V1 V2 V3 NAUX _RS485
+
V1
N
V1 V2 V3 NAUX _RS485
+
Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
CH
1
CH
3A1 A2 A3 A1 A2 A3
A1 A2 A3 A7 A8 A9
Load Load
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
CH
2
CH
4A1 A2 A3 A1 A2 A3
A4 A5 A6 A10 A11 A12
8. CAUTION