NYC Department of Education Building Condition Assessment Survey 2018-2019 M389 Architectural Inspection Inspection Type Last Edited Time In InspectionId SUCCESS ACADEMY HARLEM CENTRAL - MANHATTAN, 461 WEST 131 STREET, MANHATTAN, NY, 10027 School: 2693 2019-02-27 07:11AM 2019-03-04 10:04AM ARCHITECTURAL - ASSOCIATE 2733 2019-02-27 08:19AM 2019-03-04 02:32PM ARCHITECTURAL - SENIOR Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Emily Rezin Principal Organization Success Academy Charter School - Harlem 6 Meeting with Principal? Yes Principal Feedback The Principal had no comments regarding the buildings Physical condition at this time. Custodian Was not present Fireman Franklin Suero Building Square Footage 39,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 5+B Comments on the Year Built 1907 Comments on the Student Population 210 Comments on the Staff Population 41 Comments on the Number of Classrooms 18 Weather Fair Facade Photo West 131st Street - East view Main Entrance Photo Facade A - West 131st Street Page 1 of 19 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)

Upload: others

Post on 05-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Inspection Type Last EditedTime InInspectionId

SUCCESS ACADEMY HARLEM CENTRAL - MANHATTAN, 461 WEST 131 STREET, MANHATTAN, NY, 10027School:

2693 2019-02-27 07:11AM 2019-03-04 10:04AMARCHITECTURAL - ASSOCIATE

2733 2019-02-27 08:19AM 2019-03-04 02:32PMARCHITECTURAL - SENIOR

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Emily Rezin

Principal Organization Success Academy Charter School

- Harlem 6

Meeting with Principal? Yes

Principal Feedback The Principal had no comments regarding the buildings Physical

condition at this time.

Custodian Was not present

Fireman Franklin Suero

Building Square Footage 39,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 5+B

Comments on the Year Built 1907

Comments on the Student Population 210

Comments on the Staff Population 41

Comments on the Number of Classrooms 18

Weather Fair

Facade Photo

West 131st Street - East view

Main Entrance Photo

Facade A - West 131st Street

Page 1 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural InspectionRoof Photo Not taken

Have any Systems/Major Building Components been upgraded? Systems: Complete Interior renovation for conversion to

Classroom use

Years: 2014

Systems: Limited Exterior Masonry, Stair, Cheek Walls and

Soffit repairs; Limited Exterior Masonry waterproofing

Years: 2015

Systems: 1st and 2nd Floors Toilet renovation

Years: 2017

Systems: 3rd and 4th Floors Toilet renovation

Years: 2018

1964 ( + 16000)Have there been any New Building Additions?

Tandem No Tandem

Leased Space? Yes

Year Leased 2014

Inspection Type Partial Inspection

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

Broken Glass Cracked Window Pane Windows 1st Floor

Windows

facing the

schoolyard

Franklin

Suero

Yes Fireman

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

NoExterior Entrances & Exits

DISTANCE BETWEEN OPEN DOORS < 4'

SADDLE HEIGHT > 1/2"

NoNoExterior H/C Lifts

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

NoInterior Corridors & Lobbies

CHANGE IN ELEVATION

NoYesInterior Elevators

CAB SIZE < 51 IN. DEEP

DOOR SIZE < 36 IN.

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

Art Rooms

Yes NoRoom 102

NOT ON ACCESSIBLE ROUTE

Page 2 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

NoAuditorium

Cafeteria

Yes No1st Floor

NOT ON ACCESSIBLE ROUTE

Classrooms

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

NoComputer Rooms

NoGymnasium

NoLibrary

Main Office

Yes NoRoom 105

NOT ON ACCESSIBLE ROUTE

NoMulti-purpose Room

Nurse's Office

Yes No1st Floor

NOT ON ACCESSIBLE ROUTE

NoPool

NoScience Lab

Toilet Rooms (boys)

Yes NoNone on accessible route

NOT ON ACCESSIBLE ROUTE

Toilet Rooms (girls)

Yes NoNone on accessible route

NOT ON ACCESSIBLE ROUTE

Toilet Rooms (staff)

Yes NoNone on accessible route

NOT ON ACCESSIBLE ROUTE

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

Page 3 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR Inspected

InspectedAREAWAY

Instance on AW1 to AW5 Inspected

3- FairInstance Condition

Instance Quantity 5

Instance Quantity Uom EACH

AREAWAY GRATINGS:MINOR RUSTINGDeficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

AW1

Violations No violations recorded

AREAWAY DRAINS:DETERIORATEDDeficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

AW5

Violations No violations recorded

InspectedAWNINGS AND CANOPIES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Not requiredCHIMNEY

Page 4 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

Not requiredCOPING

InspectedCORNICE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL CLAD:DETERIORATED DOOR AND FRAME -

MINOR DETERIORATION

Deficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Door Northwest corner Cafeteria Shown,

Similar condition from Room 104

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR WALLS

MasonryMaterial Type(s)

35,000Replacement Quantity

Replacement Uom S.F.

Instance on All Facades Inspected

3- FairInstance Condition

Instance Quantity 35,000

Instance Quantity Uom S.F.

BRICK:DETERIORATED MASONRY SILLSDeficiency

Page 5 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan Reference

Elevation

Elevation Reference West 131st Street

10Deficiency Quantity

Quantity Uom L.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

STONE:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Elevation Reference West 131st Street

30Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 6 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo 1

Facade A

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade B, C and E

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Roof Plan Reference

Page 7 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Elevation Reference Facade A

10Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

BRICK:WATER INFILTRATION IN NON-INSTRUCTIONAL

SPACE

Deficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Nurses Room

Violations No violations recorded

Page 8 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Not requiredPARAPETS

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Not requiredLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

Not requiredROOF BARRIER

Not requiredROOF CAGE

Not requiredROOF FENCE

Not requiredROOF HATCH/SMOKE HATCH

Not requiredROOFING

Not requiredROOFING DRAINS

InspectedSPECIALTIES

Not requiredBULKHEAD/PENTHOUSE

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

Not requiredDUNNAGE STEEL

Does not existROOF/GRAVITY TANK

Not requiredSKYLIGHT/ROOF VENT

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 3- Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair at Exit 3

Violations No violations recorded

InspectedRAILINGS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 9 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

InspectedWINDOWS

5,500Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 3- Fair

STEEL:MAJOR RUSTINGDeficiency

Roof Plan Reference

Elevation

150Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

InspectedWINDOWS

Material Type(s) Aluminum, Steel, Solid Wood

Instance on Steel:Facade E Inspected

5- PoorInstance Condition

Instance Quantity 500

Instance Quantity Uom S.F.

Installation Year 1964

Source of Installation Year Inspector Estimate

STEEL:DETERIORATEDDeficiency

Roof Plan Reference

Page 10 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Elevation

Elevation Reference Facade C

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected

5- PoorInstance Condition

Instance Quantity 1,000

Instance Quantity Uom S.F.

Installation Year 1907

Source of Installation Year Inspector Estimate

WOOD:DETERIORATEDDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

600Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Instance on Aluminum - Double Hung:Facades A, B, C and D1 Inspected

2- Between Good and FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom S.F.

Installation Year 2014

Source of Installation Year Inspector Estimate

ALUMINUM - DOUBLE HUNG:BROKEN PANEDeficiency

Page 11 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan Reference

Elevation

Elevation Reference Facade D1

5Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

1st Floor Window Facing Schoolyard

Violations No violations recorded

INTERIOR Inspected

Does not existAUDITORIUM

CAFETERIA

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 1st Floor Does not exist

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Inspected

Page 12 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Stage

Stage

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtains

Instance on 1st Floor Inspected

3- FairInstance Condition

WORN/DETERIORATEDDeficiency

Left Side of StageDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Left Side of Stage

Violations No violations recorded

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency

Nurse’s OfficeDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Page 13 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Nurse’s Office

Violations No violations recorded

Does not existGYMNASIUM

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

Does not existINTERIOR GUARDS

KITCHEN

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

North of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North of Room

Violations No violations recorded

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Page 14 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

INTERIOR

Does not existLIBRARY

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Not requiredFOUNDATION WALLS

Not requiredROOF STRUCTURE

Not requiredVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 15 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

INTERIOR

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Does not existCONTAINERIZATION

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 2- Between Good and Fair

CHAIN LINK:DAMAGED/DETERIORATEDDeficiency

Southeast corner of School YardDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Southeast corner of School Yard

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

Page 16 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

3- FairCondition

DAMAGED CURBSDeficiency

Along West 131st StreetDeficiency Location/Instance

45Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 131st Street

Violations No violations recorded

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along West 131st Street, Amsterdam AvenueDeficiency Location/Instance

350Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 131st Street

Deficiency Photo 2

Along Amsterdam Avenue

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Non-Use

Page 17 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

SITE

PAVING

Student Non-Use

Gravel Exists? No

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Use

Gravel Exists? No

InspectedAsphalt

3- FairCondition

CRACKS - MAJORDeficiency

SchoolyardDeficiency Location/Instance

600Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard

Violations No violations recorded

Does not existConcrete

Does not existPavers

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

InspectedRETAINING WALLS

Condition 2- Between Good and Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

No deficiencies recordedDeficiency

Does not existSEATING

InspectedSITE WALLS (NOT RETAINING WALLS)

Condition 3- Fair

BRICK:CRACKS/SPALLING - MAJORDeficiency

Along Amsterdam AvenueDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 18 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: SUCCESS ACADEMY HARLEM CENTRAL - …Instance on Wood:Solid Wood Window Frame at Facade A and B Inspected Instance Condition 5- Poor Instance Quantity 1,000 Instance Quantity Uom S.F

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M389Architectural Inspection

Question Response

SITE

SITE WALLS (NOT RETAINING WALLS)

Deficiency Photo 1

Along Amsterdam Avenue

Violations No violations recorded

Does not existSTAIRS/RAMPS: EXTERIOR

Page 19 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)