Asset: P.S. 228 (ECC) - QUEENS, 32-63 93RD STREET, New York, 11369 Inspection Id Inspection Type Time In Last Edited SA : Q228 Architectural - Senior 2019-12-02 10:48 AM 2019-12-09 3:19 PM AA : Q228 Architectural - Associate 2019-12-02 11:23 AM 2019-12-02 5:46 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Olga Guzman Organization P.S. 228 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. Some thermostats are not working. 2. The toilet in Principal's Toilet Room is leaking. 3. There are roof leaks in Room 312. 4. There is water infiltration through the windows at Rooms 201 and 203. Custodian Was not present Fireman Salvatore Taibi Building Square Footage 45,000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B+PH Comments on the Number of Classrooms 16 Comments on the Year Built 2001 Student Population 290 Staff Population 80 Weather Fair Facade Photo Corner of 93rd Street and Northern Boulevard - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q228 PB/A&W Print Date: 9/14/2020 Page 1 of 27

Upload: others

Post on 06-Oct-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Asset: P.S. 228 (ECC) - QUEENS, 32-63 93RD STREET, New York, 11369

Inspection Id Inspection Type Time In Last Edited

SA : Q228 Architectural - Senior 2019-12-02 10:48 AM 2019-12-09 3:19 PM

AA : Q228 Architectural - Associate 2019-12-02 11:23 AM 2019-12-02 5:46 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Olga Guzman

Organization P.S. 228 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. Some thermostats are notworking. 2. The toilet in Principal's Toilet Room is leaking. 3. Thereare roof leaks in Room 312. 4. There is water infiltration through thewindows at Rooms 201 and 203.

Custodian Was not present

Fireman Salvatore Taibi

Building Square Footage 45,000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B+PH

Comments on the Number of Classrooms 16

Comments on the Year Built 2001

Student Population 290

Staff Population 80

Weather Fair

Facade Photo

Corner of 93rd Street and NorthernBoulevard - Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 1 of 27

Page 2: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Main Entrance Photo

Facade A - 93rd Street

Roof Photo

Roof 1 - North View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Limited Structural repairs

Year: 2018

Systems: Limited Roofing repairs; limited Window recaulking;limited waterproofing at Coping

Year: 2017

Systems: Limited Coping, Parapet, Roofing repairs

Year: 2012

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 2 of 27

Page 3: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

DeterioratedSteel

Deterioratedmetal decking

INTERIOR |STRUCTURAL| FLOORSTRUCTURE

Basement -Boiler Roomabove BoosterPumps

Salvatore Taibi Fireman

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria 1st Floor Yes Yes Yes Yes

Classrooms 1st - 3rd Floor Yes Yes

Computer Rooms No

Gymnasium No

Library Room 215 Yes Yes

Main Office Room 121 Yes Yes

Multi-purpose Room 3rd Floor Yes Yes Yes Yes

Nurse's Room Room 217 Yes Yes

Pool No

Science Lab No

Toilet Rooms (Boys) 1st - 3rd Floor Yes Yes

Toilet Rooms (Girls) 1st - 3rd Floor Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 3 of 27

Page 4: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Toilet Rooms (Staff) Basement - 2nd Floor Yes Yes

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1 - AW2

Instance Condition 2 - Between Good and Fair

Instance Quantity 2

Instance Quantity Uom EACH

Deficiency No deficiencies recorded

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Metal

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 4 of 27

Page 5: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

COPING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Exit 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 5 of 27

Page 6: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES Inspected

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Steel

Replacement Quantity 22,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 22,000

Instance Quantity Uom S.F.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 6 of 27

Page 7: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade C

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 2,500

Replacement Uom C.F.

InspectedInstance on Roof 1

Instance Condition 4 - Between Fair and Poor

Instance Quantity 2,500

Instance Quantity Uom C.F.

Deficiency BRICK: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 7 of 27

Page 8: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

PARAPETS

Deficiency Photo1

Roof 1 - Facade A

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Facade C

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 11,500

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Does not Exist

ROOF BARRIER Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 8 of 27

Page 9: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

ROOF

Roofing

ROOF BARRIER

Condition 3 - Fair

Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING

Roof Plan reference

Deficiency Quantity 280

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: Roof 1

Instance Condition 4 - Between Fair and Poor

Instance Quantity 7,500

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2001

Source of Installation Custodial Staff

Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 9 of 27

Page 10: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Room 312

Violations No violations recorded.

InspectedInstance on Modified Bitumen: Roof 2

Instance Condition 5 - Poor

Instance Quantity 4,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2001

Source of Installation Custodial Staff

Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION

Roof Plan reference

Deficiency Quantity 600

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Center of Roof 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 10 of 27

Page 11: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

ROOF

Roofing

ROOFING Inspected

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 5 - Poor

Deficiency DETERIORATED

Roof Plan reference

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

WINDOWS Inspected

Replacement Quantity 2,500

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 11 of 27

Page 12: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Deficiency RUST - MINOR

Roof Plan reference

Elevation

Deficiency Quantity 900

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: Facades A, C, D

Instance Condition 3 - Fair

Instance Quantity 2,500

Instance Quantity Uom S.F.

Installation Year 2001

Source of Installation Custodial Staff

Deficiency ALUMINUM - DOUBLE HUNG: AIR AND WATERINFILTRATION, OPEN JOINTS WITH DAMAGED CAULKING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 12 of 27

Page 13: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan reference

Elevation

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 4

Deficiency Photo1

Facade A - Room 203 shown, Facade A - Room 201 similar

Violations 35402546L

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS

Deficiency Location/Instance Basement - Mechanical Room B15

Deficiency Quantity 30

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 13 of 27

Page 14: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Mechanical Room B15

Violations No violations recorded.

Deficiency METAL DECK AND CONCRETE: DETERIORATED

Deficiency Location/Instance Basement - Boiler Room above Booster Pumps

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

Deficiency Photo1

Basement -Boiler Room above Booster Pumps

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement - Boiler Room, Corridor near Rooms B02, B23

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 14 of 27

Page 15: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE Inspected

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Near Center columns

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Center columns

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 15 of 27

Page 16: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

CAFETERIA

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near Room 101B

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Rear 101B

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Room 312

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 16 of 27

Page 17: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo1

Room 312

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Corridor near 1st Floor Staff Toilets, Corridor near Room 204

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near 1st Floor Staff Toilets

Violations No violations recorded.

Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED

Deficiency Location/Instance Main Entrance Lobby

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Lobby

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 17 of 27

Page 18: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Main Entrance Vestibule, Corridor near Room 118, Room 212

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Room 209

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 209

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 18 of 27

Page 19: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED

Deficiency Location/Instance Rooms 107A,108

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 108

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 108

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 108

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 19 of 27

Page 20: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

KITCHEN

Floor Finish

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 215

Built-in Furnishing

Does not ExistInstance on Room 215

Ceiling

InspectedInstance on Room 215

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 215

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 215

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 215

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on 3rd Floor

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Near Stage

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 20 of 27

Page 21: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Ceiling

Deficiency Photo1

Near Stage

Violations No violations recorded.

Door(s)

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 3rd Floor

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 3rd Floor

Stage

InspectedInstance on 3rd Floor

Stage Does not Exist

Does not ExistInstance on 3rd Floor

Stage Curtain Rigging Inspected

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 21 of 27

Page 22: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED

Deficiency Location/Instance Stair B/3

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/3

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Does not Exist

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 22 of 27

Page 23: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency WROUGHT IRON: RUST - MAJOR

Deficiency Location/Instance Northern Boulevard

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Northern Boulevard

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 23 of 27

Page 24: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

SITE

FENCES

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance Northeast Playground

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Northeast Playground

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Does not Exist

Student Use Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Main Entrance

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 24 of 27

Page 25: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

SITE

PAVING

DOT Sidewalk

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency HEAVING

Deficiency Location/Instance Northern Boulevard

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Northern Boulevard

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 93rd Street

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

93rd Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on East side

InspectedInstance on Northeast side

Benches

InspectedInstance on East side

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 25 of 27

Page 26: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

SITE

PLAYGROUNDS

Benches

InspectedInstance on Northeast side

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fence

InspectedInstance on East side

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Does not ExistInstance on Northeast side

Pavement

InspectedInstance on East side

Condition 3 - Fair

Deficiency CONCRETE: CRACKS - MAJOR

Deficiency Location/Instance Near entrance

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near entrance

Violations No violations recorded.

Play Equipment

InspectedInstance on East side

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Does not ExistInstance on Northeast side

Safety Surfacing

InspectedInstance on East side

Condition 3 - Fair

Deficiency DETERIORATED/MISSING

Deficiency Location/Instance North side

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228

PB/A&W Print Date: 9/14/2020Page 26 of 27

Page 27: NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2 Inspected Instance Condition 5 - Poor Instance Quantity 4,000 Instance Quantity Uom S.F

Question Response

SITE

PLAYGROUNDS

Safety Surfacing

Deficiency Photo1

North side

Violations No violations recorded.

Unpaved Area

InspectedInstance on East side

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Does not ExistInstance on Northeast side

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 2 - Between Good and Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance East side Playground

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East side Playground

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q228