115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS SECTION DESCRIPTION PAGE I Installation Instructions 1 II Calibration Instructions 3 III Operation Instructions 5 IV Troubleshooting Guide 6 V Replacement Parts 7 List of Figures / Tables Figure 1 Flow Sensor Figure 2 A,B,C, Typical Valve Installations Figure 3 Saddle Clamps Figure 4 Pressure Transducer Figure 5 Meter Installation Guide Figure 6 Meter Functions Table 1 Flow Chart

Upload: others

Post on 15-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

115669

STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPaINSTALLATION CALIBRATION OPERATING INSTRUCTIONS

TABLE OF CONTENTS

Section DeScription page

i installation instructions 1

ii calibration instructions 3

iii operation instructions 5

iV troubleshooting guide 6

V replacement parts 7

List of Figures / Tables

Figure 1 Flow Sensor

Figure 2 a,B,c, typical Valve installations

Figure 3 Saddle clamps

Figure 4 pressure transducer

Figure 5 Meter installation guide

Figure 6 Meter Functions

table 1 Flow chart

Page 2: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Figure 6a

2

Page 3: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Figure 6

3

Page 4: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

SECTION IINSTALLATION INSTRUCTIONS

A. SYSTEM COMPONENTS

• DisplayMeter(Figure6) • FlowSensor(Figure1) • PressureTransducer(Figure4) • InterconnectCables5,10or20' • SensorHolder 1. ValveInletAdapters(Figure2A,B&C) 2. Saddles(Figure3)

B. FLOW SENSOR LOCATION

primary 1. Akron'sspeciallydesignedinletadaptersforSwing-outValves.Size2"-4". 2. SaddleClamps.Size2"-5"(Schedule40pipe) Note:Horizontallineinstallationsmustpositionthesensorportwithin180˚ontopside(9:00-3:00).

Avoid

• Installationswherethesensorwouldbelocatedinalinewhereasmallerlineprecedesit. • Installationswheresensorwouldbepositionedfollowingavalveorelbow.Neverinstallflowportvalveadapteron dischargesideofvalve.

• Installationswheresensorwoulddirectlyprecedebypasseductor. Note:Intightinstallationswherewaterflowisturbulent,customcalibrationisrequiredformaximumaccuracy.

c. FLOW SENSOR INSTALLATION

1. Akron Valve Adapter

a. Simply remove retainer nut or plug. b. GreaseO-RingsonsensorwithO-Ringlubeorsiliconegrease.(Removeplasticpaddlewheelprotector.) c. insert sensor into port and push in. d. Alignpin"A"(Figure1)withlocatorholeandpushin. e. replace the retainer nut or plug and tighten with a wrench.

Sensor installation complete

2. Saddle Clamp

a. Determine the location on the pipe. b. Drilla1-1/4"holeinthepipewithaholesaw.Horizontalpipingontopsidefrom9:00-3:00. c. Deburrtheedgeoftheholeandcleantheareawherethegasketseals. d. Centersaddlewithholeinpipe(Sensorlocatorhole"A"(Figure3)maybeoneithersideofpipehole.)

4

Page 5: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

e. insert strap into saddle and tighten nuts hand tight. f. Usingatorquewrenchtightennutsalternatelyto80footpounds. g. Followstepsa-einC.1toaddsensor. Sensor installation complete

D. PRESSURE TRANSDUCER INSTALLATION

ThePressureTransducer(Figure4)hasa1/4"NPTmalethread.

1. apply pipe sealant to the thread and insert into provided tapped hole in valve discharge adapter on discharge sideofvalve.

2. Tightenwithwrenchtotorqueusedforsmallpipefittings.

pressure transducer installation is now complete

E. METER INSTALLATION

CAUTION:Alwaysdisconnectallwiringandcablesfromthemeterbeforeelectricarcweldingatanypointon apparatus. Failure to do so will result in damage to meter.

1. Selectmountinglocation(s)formeter(s).Themeteristobemountedfromtheoutsideofthepanelandwill needclearancebehindof3-15/16"widthby2-1/2"depth.

SeeFigure5forcutoutandscrewmountingdimensions.

WARNING:Themeterisasealedunitandthebezelshouldnotbedisassembledfromthecase.

2. Afterthecutoutandmountingholesarefinished,mountthemeterusingtheprovidedfasteners.

3. it is now time to connect the red power wire and, the Black ground wire, to the truck system.

CAUTION:Exercisecautionwhenworkingwiththeelectricalsystem.Disconnectcablefrombatterypositive terminalbeforeconnectingpowertometer.Seetruckmanualforadditionalinformationon electrical system.

CAUTION:Donotconnectmetertoflowsensorortransducercablesuntilpowerhookupisverifiedcorrect anddisplayisworking.Themeterhasreversepolarityprotection,butthetransducerandflow sensordonot,sincetheyrequireshielding.Theywillbegroundedtothepiping.Anymis-wiring could damage all components.

note: Itisessentialthattheconnectorsusedbewater-tighttopreventwaterfromwickingupwiresandinto the meter. always use sealed connectors or splices and the adhesive lined shrink tube provided, or other suitable connectors.

4. Using16or18AWGwire,connecttheRedpositivewiretothe12or24VDCpowersupply.ConnecttheBlack negative wire to a suitable ground.

SPECIFICATIONS:

Sensor Types

FlowMeter-Paddlewheel PressureTransducer-RatioMetric,0.5-4.5VDC,1/4"NPT,Male,0-42bar/0-4200kPa

Meter

operating Voltage 12 or 24 VDc MinimumOperationsVoltage-9.5VDC MaximumOperationsVoltage-32.0VDC OperatingCurrent-150mA DisplayType-LED Enclosure-NEMA4X OperatingTemperature-40˚F-140˚F

F. kPa/LPM POWER-UP OPTION

AkronFlow/PressureMeters,equippedwiththekPaorLPMselectionfeature,allowstheusertoselectthedisplayfunctiontoappearonpower-up.Tomakethisselection,usethefollowingprocedure.

Step 1- PressandholdBOTHbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashes“CAL” (calibration).Releasebuttons.Afterafewseconds“SIZE”willappearonthedisplayandallmodelightswill be lluminated.

5

Page 6: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

SADDLE CLAMP ASSEMBLY

PRESSURE TRANSDUCER & CONNECTOR

Figure 3

Figure 4

6

Page 7: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Figure 2c

inle

ta

ttac

h Va

lve

this

Side

to p

ower

Su

pply

neg

ativ

e(Black)

(Red)

posit

ive

12-24VDC

3”HD21SF

5 3 / 4

7

Page 8: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Step 2- Scrolltheleftbuttonuntil“diSP”appears.

Step 3- Pressandreleaserightbutton.“PPPP”or“rrrr”willappear.“PPPP”signifieskPaand“rrrr”signifiesLPM.

Step 4-Pressandreleaseleftbuttontoselectwhatindicationisdesiredatpower-up.(kPaorLPM)

Step 5-Whenselectionismade,pressandreleaserightbuttontoenterandlock.

Systemwillthenalwaysreturntoyourselectionatpower-up.Tochangemodes,repeatSteps1-5.

SECTION IICALIBRATION INSTRUCTIONS

GENERAL-WhenunitisinCalibrationmode,allmodelightsonleftsideofdisplaywillbeilluminated.Aflashingmodelight indicateswhatfunctionisbeingcalibrated.

A. PRESSURE CALIBRATION

1. prior to calibration, the pressure transducer (Figure 4) must be installed into provided 1/4"NPTpressureport. typically in a valve discharge adapter or piping.

2. open the valve and drain to eliminate any pressure in line. 3. power up the meter. (Figure 5) 4. Afterthedisplayhasgonethroughasequenceofmessages,0 will appear on the display, or an error message mayappearifinthepressuremode.Also,amodelightwillappearontheleftsideofthedisplay.

The unit is now ready for Pressure Calibration

Step 1- PressandholdBOTHbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashesCAL (calibration).Releasebuttons.AfterafewsecondsSIZEwillappearondisplayandallmodelightswill be illuminated.

Step 2- PressandreleasetheLEFT button. PRES(pressure)willappearonthedisplay.

Step 3- PressandreleaseRIGHT button. the word “ZERO”shouldappearandPSImodelightwillflash.Note:If “ZERO” does not appear, the messages dEAd, EPrL, or EPrH may appear on the display. they indicate possibletransmissionerrorsbetweenthepressuretransducerandthemeter.(Seetroubleshooting guide-SectionIVtoresolve)

Step 4-With“ZERO”appearingondisplay,pressandreleaseright(pressure)button.ZEROwillstartflashing. Afteramoment,0 will appear on display.

note: on digital display, the word “ZERO”isdisplayedas“2Ero”.

Unitisnowreadytoprovidepressurereadingsforoperations.Thisprocedureneednotberepeatedunlessthetransducerormeter is replaced.

B. FLOW CALIBRATION - PIPE SIZE

Typicallyaneworrefurbishedapparatuswillbepre-calibratedusingpipesizemode.Thiscanalsobedonewithanyfieldconversion installing the akron Flow/pressure Systems.

Note:AkronFlow/Pressureunitscanbeinstalledintoexistingflowmeterinstallationsifasaddleclampinstallationexists.(TheAkronsaddleclampwilladapttoholesupto1-3/4"diameter.)Thepanelmeterwillalsofitinplaceofmostflowmeterorpressuregagecutouts.Moststandardpressuregagecutoutscanalsobeusedoreasilymodified.

Step 1- Powerupunit.Noflowisrequiredthroughsystem.

Step 2- Pressandholdbothbuttonssimultaneouslyfor15secondsuntilthedisplayflashesCAL(calibration) releasebuttons.AfterafewsecondsSIZE will appear on the display.

Step 3- Pressandreleaserightbutton,ifunithadpreviouslybeenprogrammedwithapipesize,thatsizewill appear.(SeeNote)

Step 4-Pressandreleaseleftbuttonuntildesiredpipesizeappears.

Step 5-Withcorrectpipesizedisplayed,pressandreleaserightbutton,thepipesizewillflash,then0 will appear ondisplay.Unitisnowcalibratedforpipesize.

note:Ifunitwasnotcalibratedwithpipesize,CUS (custom)willappear.Pressandreleaseleftbutton. FRE(frequency)willappear.Proceedwithsteps4&5.

8

Page 9: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

PipeSize Display 2” 0020

2-1/2” 0025 3” 0030 4” 0040 5” 0050

Step 6-Theaccuracyoftheinstallationshouldbechecked,duetopossiblevariationsassociatedwithindividual installations.UseofanAkronStyle9015orFK-25orequiliventWaterFlowTestDeviceisrecommended asthebasisforcomparison.Ifrecalibrationisnecessaryusethecustomflowsettingcoveredinthe nextsection.

C. FLOW CALIBRATION - CUSTOM FLOW SETTINGS (HIGH/LOW)

Formaximumaccuracyofeachflowline,(especiallywithelbowsinline)itmaybedesirabletoseteachdischargelinetoagivenhighflow/lowflowrangeratherthanusingpipesizemode,thiscanbedoneutilizingawaterflowtestkit.(AULclassifiedWaterFlowTestDeviceisrecommended.)Useincludedflowchartprovided.(TABLEI)

Suggested Flow ranges

LineSize LPMLowFlow LPMHighFlow 2” 115 950 2-1/2” 230 2280 3” 600 4880 4” 950 7600 5” 950 7600

Toexplainthisprocedure,a2-1/2”linewitha230LPMlowflowand2280LPMhighflowwillbeused.Seenote followingthisprocedureforotherlinesizesandflows.

Step 1-Powerupunit.

Step 2-Pressandholdbothbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashesCAL (calibration).Releasebuttons.AfterafewsecondsSIZE will appear on the display.

Step 3- PressandreleaseleftbuttonuntilFLO(flow)appearsonthedisplay.

Step 4-Pressandreleaserightbutton.HIFL(highflow)willappearonthedisplay.

Step 5- Startuppumpandcommencedischargethroughselecteddischargelinewithwaterflowtestkit connectedaccordingtoinstructionsprovidedforitsuse.

Step 6-Bringflowupto2280LPMandmaintainasteadyflow.UsethePressure/FlowConversionSheetprovided withthewaterflowtestkit,orthesheetprovidedinthisprocedure.(TableI)

Step 7- Pressandreleaserightbutton.Themeterwillbegintocountpulsesupto1000.Itwillthenstopand HEND(highend)willappearondisplay.Ifsteadyflowisnotmaintainedduringpulsecounting,press andreleaseleftbutton.HIFL will appear on the display. press and release right button to recollect1000pulses.)

Step 8-Afterensuringthatasteadyreadinghasbeenmaintainedthroughthecountsequence,pressandrelease right button to accept pulse data. 0000 willappearonthedisplay,withfarleft0flashing.

Step 9-Sincethedisplaywillshowfourcharactersandthehighflowis2280,presstheleftbuttonuntil2appears.

Step 10-Pressandreleaserightbutton.Thesecond0fromleftwillbeginflashing.

Step 11-Pressandreleasetheleftbuttonuntil2appears.

Step 12-Pressandreleaserightbutton.Thethird0fromleftwillbeginflashing.Displayshouldread2200. press theleftbuttonuntil8appears.

Step 13-Pressandreleaserightbutton.Theright0willbeginflashing.Thedisplayshouldread2880.

Step 14-Pressandreleaserightbutton.2880willflash.

Ifotherthan2880isdesired,usetheleftbuttontochangenumbersandrightbuttontochangefields,as steps9-13explain.

9

Page 10: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Figure 2b

Att

ach

Valv

e Th

is

Side

Inle

t

4” P

20SF

To P

ower

Su

pply

Neg

ativ

e(B

lack

)

(Red

)Po

siti

ve

12-2

4 V

DC

3 15

/ 16

TYPI

CAL

VALV

E IN

STA

LLAT

ION

10

Page 11: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Figure 2a

ATTACH

VALVE

THIS

SiD

eINLET

2”P20SF

to p

ower

Su

pply

neg

ativ

e(Black)

(Red)

posit

ive

12-24VDC

3 5/ 3

2

TYPI

CAL

VALV

E IN

STA

LLAT

ION

11

Page 12: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

Step 15-Ifvalueiscorrect,pressandreleaserightbutton. LOFL(lowflow)willnowappearonthedisplay.Using thePressure/FlowConversionSheetprovidedwiththewaterflowtestkit,holdflowat230LPM and maintain steadyflow.

Step 16-Pressandreleaserightbutton.Themeterwillbegintocountpulsesto1000.Note:TheLowflowpulse collectionwilltakelongerthanhighflowduetolowervelocity.

Step 17-When1000pulseshavebeenreached,thecountingwillstop.LEND(lowend)willappearondisplay.

Step 18-Pressandreleaserightbutton.0000willappearonthedisplay.Proceedasyoudidinsteps9-13,display should show 0230afterstep12using0230insteadof2280.

Step 19-Pressandreleaserightbutton.0230 willflash.

Step 20-Pressandreleaserightbutton.CAL(calibration)willflashmomentarily,indicatingthatthemeteris calibrated. Display will then show 0 with a mode indicator light.

Step 21 -VerifyFlowMetercalibrationbycomparingflowstoaWaterFlowTestDevice.

Unitisnowreadyforuse

NOTE: Thehighflowsettingsshouldbe7-10timesthelowflowsettings.

SECTION IIIOPERATION INSTRUCTIONS

A. GENERAL

Theseinstructionsdescribefeaturesandoperationalstepsforgeneralserviceafterthesystemissetupandcalibrated.(SeeinstallationandcalibrationsectionsI&IIifthishasnotbeendone.)

Themeterconsistsofthedisplayscreenandtwooperationbuttonslocateddirectlybeneaththedisplay.(SeeFigure6)

Whenunitispowered,therearethreeredLEDmodelightsontheleftsideofdisplay.Eachoftheselightsalignwithparticularfunctionmarkedonthebezelface.(SeeFigure6)Theywillonlybeilluminatedindividually,exceptduringpowerupsequenceand calibration.

Theunithasfouroperationfunctions:

1. Flow LPM-ActualLitersperminuteflowing.(Willreadinsingleliterincrementsto1200.Above1200,10liter incrementswillappear.)

2. Flow TOTAL-Totallitersflowedsinceunitwaspoweredup.(FiguredisplayedmustbemultipliedX100togettotal)

3. pressure bar or kPa.

4.LEDINTENSITY-Brightnessofdisplay.

B. OPERATION (SeeFigure6)

Atthetimeofpowerup,allthreemodelightswillappearwithfourZEROS.Insequenceanumbervaluewillappear,followedbyLI, bar or kPa, CUS or PIPE andfinally0.Thiswillbecompleteinafewseconds.

Theunitisnowreadyforoperation

TO READ:

LPM-Pressandreleaseleft(flow)buttontoplacemodelightonLPM. actual LPM will appear on display.

TOTAL FLOW-Pressandreleaseleft(flow)buttontoplacemodelightonTOTAL.Thefiguresdisplayedmustbe multipliedby100togivelitersflowed.

bar or kPa-Pressandreleaseright(pressure)buttontoplacemodelightonbarorkPa.Actualpressurewillappear on display.

LED INTENSITY-TobrightenordimLED,pressandholdleftbuttonuntildesiredbrightnessisdisplayed.

RefertoSectionIV,Troubleshootingguideifproblemsoccur.

12

Page 13: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

SECTION IVTROUBLESHOOTING GUIDE

PROBLEM

Display does not illuminate

LPMshows0-waterisflowing

dEAD,EprL,EprHappears on display

LEDDim

LENSFoggy

CHECK

1. power connection2. power Source

1. cable connections2.Shutdownpump-removesensor- spin paddlewheel3.Removesensorfromcableconnect direct to meter spin paddlewheel

1. check pressure transducer connections2. Shutdown pump remove transducer and connect directly to meter

ShoulddissipateshortlyafterusewithLED’slighted.

ACTION

Ifproblemsexistwithpowercheck,correctthem.ReplaceMeterifpowercheck is ok.

Ifdisplayshowsreading,replacecable.Ifnot, replace sensor.

Ifdisplayclears,replacecable.Ifitdoesnot, replace transducer.

Holdleftbuttondownfor5seconds.Should brighten.

Willcausenoharm.Thiswillhappenifmeter is not assembled in a humidity freearea.

dEAd- Hardwareproblem.Probablymeter.EprL- 1.Shorttoground.Checkcable.

2.NotZEROEDat0barorkPa. 3.CheckforvacuuminlineEprH- 1.Transducernotinstalled.

2. Short to power. check cable. 3.NotZEROEDto0barorkPa.

NOTE:Eddycurrentsindischargemanifoldsystemsmaycauseflowsensorpaddlewheelstomoveandsendasignaltothemeterdisplay.Thiscouldregisteraflowreadingwhenthevalveisactuallyclosed.Toeliminatethisfalsereading,wehaveinitiatedaprogramforourflowmetersthatwillnotdisplayareadinguntilaminimumflowisattained.Basedondischargelinesize,theminimumshavebeenestablishedbasedonlogicalflowsforeachsizeline.

LINE SIZE DISPLAY WILL READ ABOVE 2” 75LPM 2 1/2” 95LPM 3” 113LPM 4” 300LPM 5” 340LPM

13

Page 14: STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS …115669 STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPa INSTALLATION CALIBRATION OPERATING INSTRUCTIONS TABLE OF CONTENTS Section DeScription

WARRANTY AND DISCLAIMER: We warrant Akron Brass products for a period of five (5) years after purchase against defects in materials or workmanship. Akron Brass will repair or replace product which fails to satisfy this warranty. Repair or replacement shall be at the discretion of Akron Brass. Products must be promptly returned to Akron Brass for warranty service.

We will not be responsible for: wear and tear; any improper installation, use, maintenance or storage; negligence of the owner or user; repair or modification after delivery; damage; failure to follow our instructions or recommendations; or anything else beyond our control. WE MAKE NO WARRANTIES, EXPRESS OR IMPLIED, OTHER THAN THOSE INCLUDED IN THIS WARRANTY STATEMENT, AND WE DISCLAIM ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Further, we will not be responsible for any consequential, incidental or indirect damages (including, but not limited to, any loss of profits) from any cause whatsoever. No person has authority to change this warranty.

REvISED: 7/11

ISO 9001 REGISTERED COMPANY

PHONE:330.264.5678or800.228.1161IFAX:330.264.2944or800.531.7335Iakronbrass.com

©AkronBrassCompany.2011Allrightsreserved.NoportionofthiscanbereproducedwithouttheexpresswrittenconsentofAkronBrassCompany.

SECTION VREPLACEMENT PARTS

FLOW SENSOR

5”

2-11/16”REF.

Item Part Number

5’Cable 93000013

10’Cable 93000002

20’Cable 93000014

50’Cable 93000015

transducer 93000030

Meter(kPa) 93000005

Meter(bar) 93000010

Sensor(Flow) 93000004

2”Saddle 93000006

21/2”Saddle 93000007

3”Saddle 93000008

4”Saddle 93000011

5”Saddle 93000016