street lighting specification march 2016...requirements of bs en 40 and pd 6547: 2004. please refer...
TRANSCRIPT
STREET LIGHTING SPECIFICATION March 2016
Milton Keynes Council Civic Offices 1 Saxon Gate East Central Milton Keynes MK9 3HQ T+44 (0) 1908 691691 www.miltonkeynes.gov.uk
1 PREAMBLE ................................................................................................................................................ 1
2 DESIGN APPROACH ................................................................................................................................. 1
3 LUMINAIRES AND CONTROLS ................................................................................................................ 2
4 COLUMNS AND BRACKETS .................................................................................................................... 5
5 HINGED COLUMNS ................................................................................................................................... 7
6 PASSIVELY SAFE COLUMNS .................................................................................................................. 8
7 SITING OF STREET LIGHTING COLUMN ................................................................................................ 8
8 PROTECTIVE SYSTEMS – FOR COLUMN AND BRACKETS AND ON SITE PAINTING. .................................................................................................................................................. 8
9 FEEDER PILLARS.................................................................................................................................... 11
10 ISOLATION ............................................................................................................................................... 12
11 ISOLATOR ENCLOSURES ...................................................................................................................... 13
12 SWITCH DISCONNECTORS .................................................................................................................... 13
13 ROTARY FUSE CARRIER ....................................................................................................................... 14
14 FUSES ....................................................................................................................................................... 14
15 CABLES .................................................................................................................................................... 14
16 INSTALLTION AND ERECTION OF EQUIPMENT .................................................................................. 15
17 LUMINAIRE TO ISOLATOR ..................................................................................................................... 15
18 CABLE AND EARTHING ......................................................................................................................... 15
19 FASTENINGS ........................................................................................................................................... 16
20 NUMBERING OF COLUMNS ................................................................................................................... 16
21 CABLE AND DUCT LAYING (Private Supply) ....................................................................................... 17
22 CABLE TERMINATIONS .......................................................................................................................... 18
23 EARTH RODS ........................................................................................................................................... 19
24 ELECTRICAL TEST INSTRUMENTS ...................................................................................................... 19
25 ELECTRICAL INSPECTION & TESTING ................................................................................................ 19
26 WORKING ON DNO NETWORKS ........................................................................................................... 19
27 COMPETENT PERSON’S AUTHORISATION CERTIFICATE FOR WORK ON..................................... 19
Appendix A Columnn/Lantern Matrix
Appendix B Compliance
Appendix C Schedule of preferred materials
Appendix D Outline guidance – Description of inspection and testing
Appendix E DNO requirements – Eng. Recommendation G39
Appendix F SSP4 Indemnity Form
Appendix G and H Milton Keynes Borough Map/Standard detail drawings
1 PREAMBLE
(i) Milton Keynes Council has produced this specification to aid designers for
developers seeking adoption by the Council. For clarification on any areas
prior to submission please contact [email protected]
(ii) All proposed materials must be supported by a full manufacturers guarantee.
The guarantee must be under-written by an accredited financial institution,
and the contractor must provide the council with written details before any
work commences.
(iii) Notwithstanding the following specification, Milton Keynes Council also has
a purchasing policy formulated to achieve standardisation and best value.
Contractors are free to propose materials of equivalent or better performance,
but they must demonstrate to the council that this will be achieved.
(iv) All materials equipment shall be manufactured such that they are fully
compliant with the appropriate standards and directives, including WEEE and
RHOS Regulations.
(v) All installation works shall be carried out by an accredited Contractors
operative in accordance with the National highway Sector Scheme for Quality
Management in Highway Works section 8, 9a and 10. Operatives should hold
an appropriate CSCS card and the appropriate G39.
2 DESIGN APPROACH
(i) Milton Keynes are currently improving their network by converting existing
asset stock to LED on the Grid Road network, Residential Areas, Industrial
Estates, Town Centres and Redways. We will continue this programme onto
the rest of the existing network in line with its capital programme linked to
“prudential borrowing” investment.
(ii) Specific Lighting designs shall be carried out by a competent designer and in
accordance with BS5489-2012 and BSEN13201 2014. A risk base assessment
is required and this will be outlined within the Lighting report along with any
ecological concerns that may have been highlighted in the ecological impact
report and how those factors have been mitigated if any. The report is to be
submitted with the lighting design. Please refer to Appendix B for the
approved product list or the tables below. Alternatives will be considered but
this product needs to meet the specification outlined in this document and also
requires approval in writing by the Milton Keynes Street Lighting Manager.
(iii) Reality calculations will be required to support the Lighting Report showing
lighting levels on the road and footpaths. Also the dimmed level from
10.30pm to 5.30am Lighting Reality calculations. We also require 0 degree tilt
on the LED luminaire.
(iv) An Isolux drawing overlaid onto an OS map along with any neighbouring
areas that may be affected by the addition of the street lighting such as railway
lines nearby housing and hedgerows.
(v) A Section 38 drawing with the lanterns and columns positioned with
identification for ease of reference is also required.
3 LUMINAIRES AND CONTROLS
(i) Luminaires for new installations shall be as stated in TABLE 1 below. An
alternative will be considered and but is required to comply with the below
requirements , approval for an alternative luminaire will require written
approval from Milton Keynes Council.
(ii) Luminaires for road lighting shall have a minimum degree of protection rating
IP65 to BS EN 60529 1992 for luminaire optics and IP54 to BS EN 60529
1992 for luminaire control gear.
(iii) The Luminaire shall be designed for universal mounting with attitude
adjustment. Tilt angle should be 0 degrees unless otherwise approved.
(iv) Comply with BS EN 60598-2-3 and BS 4533, be compatable with the
columns and brackets specified in section 4.
(v) The cast aluminium parts of the luminaire are to be manufactured from LM6
aluminium housing ((EN AC-44100) (AL.Si12)) (low copper content).
(vi) The gear box and LED engines are to be sealed to IP66.
(vii) The luminaire is expected to have a services life of 100,000 hours and will
achieve 50,000 hours at 85% lumen maintenance (L85B50) at any of the
offered drive currents.
(viii) Luminaire should be suitable for post mounting (60/76mm) and side entry
(34/42/60mm) with the ability to adjust onsite to 0°.
(ix) Colour temperature of LED must be between 4000-4200 degrees kelvin with a
CRI of not less than 70. A maximum SP ratio of 1.5 will be allowed.
(x) All combinations of luminaires, lamps and electronic LED drivers, shall be
included in Elexon’s list of approved equipment and be allocated a valid
Unmetered Supplies (“UMS”) charge code and should be CE marked.
(xi) The luminaire shall be offered with a driver that is DALI enabled and is
capable of connecting to any DALI enabled CMS System. Residential roads
will require a step dim of 30% between 22.30 and 05.30 this is to be pre-
programmed at time by manufacturer when the order is place.
(xii) The luminaire shall be thermally managed such that a predicted driver life is
in excess of 100,000 hours.
(xiii) Warranties shall be offered for the luminaire body, light engines, and driver
life and be a minimum of 10 years plus:
a) The warranty shall clearly state any exclusions and general terms such as
maintenance regimes, records of maintenance, personnel training, etc
which may be required to validate any warranty claim. This information
will be required for the planning application review
b) The manufacturer will clearly indicate the basis of the warranty in terms
of length of warranty, the basis of liability, the amount of the cost of the
repair/replacement which the warranty offers throughout the predicted
life of the luminaire or the maximum period of the warranty.
c) The procedure to be implemented in the case of a dispute regarding any
warranty claim.
d) Whether the warranty is carried by the product itself irrespective of the
purchasing path, such that any claim may be registered by the “owner” of
the product at any point during the warranty, irrespective of who
purchased, installed, or “owned” the product in the past, or whether the
warranty is only held by the “original purchaser”.
(xiv) Luminaire shall be constructed so as to accept a photocell. The Nema socket
will be 7 pins for future conversion to CMS. Photocell specification Selc 8481
series 35/18
(xv) The fitting of all lantern components (e.g. LED panels, drivers, glazing, etc.)
shall allow for easy on-site replacement without compromise of water/dust
ingress seals in the event of component failure or future upgrade.
(xvi) Luminaires may be:
a) Class I where the luminaire has an integral earth terminal linked to all
exposed metalwork. This allows an earth connection to be made to the
b) metalwork of the supporting Structure and to the earth conductor of the
supply cable. Fortuitous earth connection provided by connection to
mechanical fixings shall not be relied upon.
Or c) Class II where there is no earth terminal provided for connection of the
luminaire’s exposed metalwork to the circuit protective conductor;
Area Mounting Height Luminaire Type
Residential - Primary 6m Tubular SE/PT
mounted
Holophane Vmax V1 or
V2
Residential – Non
Primary
5m Tubular Steel Column
SE/PT mounted
Holophane Vmax V1
Link Roads 8m Octagonal Steel
columns
Holophane Vmax V2 or
Urbis Ampera
Grid Roads Dual 12m Octagonal Steel
Column/1m Bracket
Holophane Vmax or Urbis
Ampera
Grid Road Single 10m Octagonal Steel
Column/1m Bracket
Holophane Vmax or Urbis
Ampera
Grid Road Roundabouts 12m Conical Steel
Column/ 1m bracket
Holophane Vmax
Rural 12m Octagonal Steel
Columns/1m Bracket
Holophane Vmax or Urbis
Ampera
Industrial 8m ROSA Steel Columns Holophane Vmax V2
Conservation areas Heritage columns agreed
in writing by MK Street
Lighting Manager. Please
refer to section 5 for when
to use Hinged Columns
Heritage lanterns LED
agreed in writing by MK
Street Lighting Manager
City Centre Please contact the Street
Lighting Manager at
Milton Keynes Council
Please contact the Street
Lighting Manager at
Milton Keynes Council
Redways 5m Tubular SE/PT
mounted, Please see
section 5 for when to use
Hinged Columns
Holophane Factor
Table 1 – Luminaire Selection Chart
(The above table is a guide only and not prescriptive: any special applications should be
discussed with Milton Keynes Council) Appendix A – Column/Lantern Matrix
4 COLUMNS AND BRACKETS
(i) Columns shall generally be painted galvanised steel as specified and meet the
requirements of BS EN 40 and PD 6547: 2004. Please refer to Table one for
the column style information. Root to be protected with 2 pack glass flake,
finished colour to be RAL 7037 – Grey, factory applied PSX.
(ii) The appropriate terrain category for lighting columns shall
a) Category I for all columns
(iii) The Ground Factor shall be taken as Poor (as shown in Table 2 of PD 6547:
2004) unless confirmed otherwise on site.
(iv) Columns of 5m and 6m mounting height shall be designed to support a Road
sign class A (as shown in Table 3 of PD 6547: 2004).
(v) Columns greater than 6m mounting height shall be designed to support a Road
sign class B (as shown in Table 3 of PD 6547: 2004)
(vi) The Rationalised Wind Loading factor shall be taken from PD 6547: 2004
Table A.1 for Buckinghamshire – Light
(vii) The Maximum Altitude shall be taken from PD 6547: 2004 Table A.1 for
Buckinghamshire – 202m
(viii) The mean hourly wind velocity shall be taken from PD 6547: 2004 Table A.1
for Buckinghamshire – 21.0m/sec.
(ix) The luminaire windage area shall be obtained for the proposed scheme
luminaire.
(x) The luminaire weight shall be obtained for the proposed scheme luminaire this
information will be passed to the column manufacturer using XXXX form
(xi) Partial Load Factors shall be taken from Table 1 of EN 40-3-3: 2003 as
recommended by PD 6547: 2004 - 5.2 – Class B.
(xii) Deflection class shall be taken from Table 3 of EN 40-3-3 2003 Class 3 as
recommended by PD 6547: 2004 - 5.3 - Deflection class 3.
(xiii) Fatigue requirements for columns of 8m and above shall comply to the
requirements of BD94/07.
(xiv) Street lighting columns shall be free from irregularities and burrs.
(xv) All columns and brackets must be constructed, and quality records
maintained, to comply with BS EN 40 and BS 729.
(xvi) The securing arrangement of the bracket arm to the column shall ensure that
the arm does not rotate and shall be such that the bracket can be fixed on any
one of the 4 x 90° positions in relation to the column door opening. Bracket
fixing screws shall be of stainless steel.
(xvii) Bracket arms shall be so designed that when assembled with the column shaft
the arm and spigot shall give the required angle of tilt required by the design.
(xviii) Each column shaft shall be suitable for use with the projection required by the
design. Each column shaft shall have a base compartment large enough to
offer easy access to the equipment housed therein. A baseboard of non-
hygroscopic material, minimum thickness 15mm, 90 mm wide shall be
securely fixed in each compartment and shall be of sufficient size to
accommodate the cable terminations and isolator.
(xix) The base compartment shall have weatherproof access doors fitted with
tamperproof and corrosion resistant locks of similar patterns. The door
arrangement shall be such as that it can be only opened by releasing a single
equilateral triangular headed (with 10mm diameter rounded corners) captive
stainless steel bolt screwing into a door locking bar. When the door is secured
the bolt head shall be completely recessed into a 26mm diameter access hole.
Doors shall be interchangeable for similar columns without adaptations.
(xx) An 8mm diameter 30mm long brass earth terminal complete with two brass
washers and 2 brass nuts and locknut shall be provided in the base
compartment, and therefore the requirements of BS EN 40 Part 5 shall apply.
The terminal shall be positioned so as to be readily accessible through the
door opening. The Brass Earthing terminals shall be provided on the column
size M8*30mm long complete with two brass hexagon nuts and two plain
washers. These shall be welded or brazed to the access door and inside walls
of the base compartment and shall be fitted with a distinctly and durable
marked metal label marked - SAFETY ELECTRICAL CONNECTION – DO
NOT REMOVE.
(xxi) Spare Column Door keys shall be provided on the basis of one per 10
columns.
(xxii) Columns shall have door openings arranged so that when the column is in the
erected position an operative facing the door opening will also normally be
facing oncoming traffic.
(xxiii) Columns located in the centre reserve shall have their door openings facing in
a consistent direction.
(xxiv) Columns located on bridge parapets shall have the door openings facing away
from the drop so that operatives working on the column will be facing the
drop.
(xxv) Columns to be mounted on bridge parapets shall be fitted with a door retaining
device to ensure that the door cannot be dropped over the parapet. Any steel
wire or chain used to achieve captivity shall be galvanised or stainless steel.
(xxvi) Columns located at the rear of the footpath with boundary walls and hedges
shall have the door openings facing away from the obstruction so that
operatives working on the columns will have a clear unobstructed working
area.
(xxvii) When mounted on structures or as otherwise indicated on the drawings
columns shall have flange bases.
(xxviii) The cable entry slot shall be positioned directly below the door opening and
have minimum dimensions of 75mm x 150mm and the lower edge of the slot
shall be 500mm below ground level. The slot shall be free from sharp edges
and burrs
5 HINGED COLUMNS
(i) Specification shall be as standard columns with the exception that base hinged
columns shall have no door with access to the electrical compartment only
possible in the lowered position.
(ii) Hinged columns shall be used on all footpaths, redways and other areas
without suitable vehicular access for maintenance vehicles.
6 PASSIVELY SAFE COLUMNS
(i) Where required by the Council passively safe lighting columns shall be
installed subject to a safety audit. These shall be manufactured from
aluminium and be of similar appearance to other ‘non – passive’ lighting
columns in the vicinity.
(ii) In addition to meeting the standards required by BS EN 40 passively safe
columns documentation should identify the passive safety class to EN 12767.
7 SITING OF STREET LIGHTING COLUMN
Please refer to Milton Keynes Code of Practice for Street Lighting Maintenance
2016/2017
8 PROTECTIVE SYSTEMS – FOR COLUMN AND BRACKETS AND ON SITE
PAINTING.
(i) Mild steel columns and brackets that are to be galvanised shall be
manufactured from steel with high silicon content required to afford the
correct finished galvanised coating. New columns must be hot-dip galvanised
internally and externally to BS EN ISO 1461 1999 and in accordance with the
recommendations of the Galvanisers Association.
(ii) Steel columns to be painted shall be ‘T’ washed using a blend of copper
carbonate, phosphoric acid, water and alcohols.
(iii) Painting, where required shall be to HA G2b finished with 2 coats semi gloss
of the required RAL colour.
(iv) The contractor shall provide data sheets to the council to indicate the
following information:
• Location.
• Date of painting.
• Weather conditions.
• Humidity.
• Air temperature.
(v) During application of any paint or associated product all necessary means
shall be taken to ensure that wind blown spray or droplets do not fall or carry
onto persons or property. The application of any paint or associated product
shall only be undertaken following the approval by the council of the
proposed paint system and of the applicable Method Statement. All necessary
precautions should be taken to prevent paint and ancillary materials from
contaminating other surfaces.
(vi) It shall be ensured that all paint or associated products are compatible and
that, as far as possible, all products are from the same manufacturer. All
painting works shall be carried out in accordance with the manufacturer’s
instructions, especially the restrictions on weather conditions, air temperature
and humidity and column temperature.
(vii) Prior to application the batch number and date of manufacture of the paint
material shall be recorded. Any liquid paint materials for which the “Use By
Life” declared by the manufacturer has expired, or which after stirring exhibit
signs of separation of resin, skinning, thickening or lumps before the expiry of
the “Use By Life” shall not be used.
(viii) Each coat of paint in a system shall be applied uniformly and without defects
so that its film thickness falls within the minimum and maximum range
recommended by the manufacturer. Dry film thickness which can be measured
by suitable instruments when the paint is cured will be specified by the
manufacturer. However, wet film thickness, which can be directly related to
dry film thickness, can be simply measured during application using a gauge
such as a steel comb. Account must be taken of any paint thinners used when
calculating the necessary wet film thickness.
(ix) Each coat of paint in the system shall be completed and shall be allowed to
dry in accordance with the manufacturer’s recommendations before the
subsequent coat is applied. Subsequent coats should be of a contrasting colour
to the previous one to clearly show any areas which are missed when over-
coating.
(x) The minimum and maximum intervals between the applications of individual
coats shall be those recommended by the paint manufacturer with due regard
to film thickness, temperature and relative humidity.
(xi) Stripe coats are required to be applied by brush to areas of difficult or
restricted access, corrosion traps, edges of flanges and stiffeners, ends of
sections, weld areas and any other specified areas.
(xii) The following procedures are to be followed for preparing existing damaged
paint surfaces of lighting columns for maintenance painting:
a) Remove any loose and/or flaking paint surrounding damaged areas and
feather back to sound paint work.
b) Abrade all areas of loose paint and corrosion, feathering back to sound
paint work.
c) Thoroughly wash all areas to be coated using proprietary detergent to
remove oil, grease and any other contamination. Lighting columns must
not be just wiped with a solvent soaked cloth as this will only redistribute
and contamination and leave a film that will inhibit adhesion.
d) Rinse/wash all areas to be coated using fresh cleaning water. Rinse water
should be changed frequently to avoid the re-deposition of contamination.
Any stubborn contamination that cannot be removed by washing should
be removed using mechanical means.
e) Allow all areas to be painted to dry.
f) Any areas that have been damaged back to bare steel, or show corrosion
must be: - Manually cleaned to St3 (BS 7079: pt A1: 1989) to ensure the
resulting surface will provide a good key for coating.
g) As soon as possible but within 4 hours patch prime using a proprietary
zinc rich primer applied to achieve the minimum dry film thickness in
accordance with the manufacturer’s instructions. The patch primer must
overlap the sound paint work by a minimum of 50mm all around the
patch.
h) Any areas that have been damaged or eroded back to sound galvanised
steel must be lightly abraded to provide a suitable key taking care not to
damage adjacent galvanised coatings. As soon as possible but within 4
hours patch prime using a proprietary zinc rich primer applied to achieve
the minimum dry film thickness in accordance with the manufacturer’s
instructions. The patch primer should overlap the sound paint work by a
minimum of 50mm all around the patch.
i) Lightly abrade sound paint work to provide a suitable key for subsequent
painting. Abrading must only be carried out locally in the case of a repair,
and overall in the case of a complete repaint.
j) Apply one coat of primer to achieve the minimum dry film thickness in
accordance with the manufacturer’s instructions.
k) Apply one coat of finish to achieve the minimum dry film thickness in
accordance with the manufacturer’s instructions.
l) The application of the primer and finish coats must be carried out locally
in the case of a repair and overall in the case of a complete repaint.
m) All paint coats must be applied such that the edges of the sound paint
work are fully enveloped.
n) Care should be taken to ensure that the correct minimum and maximum
over-coating times (as well as application conditions) are observed. To
short a time and the underlying paint may be dissolved by the new coat,
too long a time and inadequate adhesion may occur without further
surface preparation (e.g. abrading).
(xiii) The application of any paint or associated product shall only be undertaken
following the approval by the Council of the proposed paint system and of the
Method Statement.
9 FEEDER PILLARS
(i) Pillars shall be manufactured in two sections, a cabinet (above ground) and a
root (below ground level) or plinth that is bolted to a concrete foundation
constructed to manufacturers requirements and bolted together.
(ii) Feeder pillars shall be constructed in cast iron or galvanised sheet steel
construction. They shall include a full size back board of varnished marine
plywood at least 15mm thick or other suitable non-hygroscopic material.
Alternatively, a purpose-designed equipment mounting system may be used.
The entry for cables shall be via the root.
(iii) Circuit details and labelling shall be provided in each feeder pillar with
engraved plastic labels to identify which columns, signs, etc. they feed and the
fuse rating. A circuit schematic diagram label showing the outgoing circuits
shall be mounted on the inside of the pillar door. The label to be manufactured
from rigid plastic, pre-printed and adhesive mounted. Lettering to be 3.5mm
high in black on a white backboard. A clear plastic resealable holder shall be
fitted onto the inside of the door of each feeder pillar. An “as constructed”
drawing identifying all the equipment that the feeder pillar supplies shall be
placed in this holder. The manufacturer and the catalogue number shall be
specified for each feeder pillar. Feeder pillars shall be identified by a white
plastic plaque with 40mm high black letters. The plaque must be fixed to the
top half of the pillar door with adhesive. Feeder Pillars shall be identified in
accordance with the schedule provided.
(iv) The main earthing terminal in each feeder pillar shall be connected to the
earth via earth electrodes and shall have a maximum acceptable value of
earth electrode resistance of 20 Ohms. Earth electrodes shall also be
provided as the last item of highway electrical equipment on each circuit.
(v) Access to the enclosure shall be by means of a hinged door(s) opening to a full
180 degrees at the front.
(vi) There shall be facilities to mount electrical equipment by means of a
backboard which shall be manufactured from hardwood which is substantially
non hygroscopic or equivalent.
(vii) The enclosure shall be designed to prevent the ingress of water, snow or
foreign bodies and shall have a minimum ingress protection as specified in
BSEN60529:1992 of IP65 except for, if fitted, a ventilator at the rear of the
enclosure which will have an ingress protection of IP42.
(viii) Third party certification should be provided with or prior to the first delivery.
(ix) The top of the enclosure shall be angled to shed water.
(x) The security of the enclosure shall be ensured by locks with an additional hasp
arrangement which allows the door to be secured to the case with an external
lock.
(xi) The final paint finish shall be site applied and shall be RAL7037 (Grey),
RAL9007 (Silver Grey) or RAL8017 (Brown) as required and guaranteed for
a period of 8 years, subject to normal operating conditions in the environment
of the Buckinghamshire area.
(xii) The main earth terminal size M8* 32mm long shall be provided at a readily
accessible position within the cabinet section of the pillar.
(xiii) The earth terminal shall be brass and supplied complete with one full nut, 2
half nuts and 2 washers all brass.
(xiv) The internal minimum dimensions are as follows: Single Door Standard Width 800mm Height 1194mm Depth 350mm
10 ISOLATION
(i) Lockable double pole isolators which act upon the phase and neutral poles
must be used.
(ii) Circuit protective conductors must achieve continuity at all times.
(iii) The Isolator unit shall contain a modular double pole switch disconnector and
a modular rotary fuse carrier pre wired and assembled in an enclosure. It shall
be suitably designed for Electrical Distribution Control of street lighting
equipment.
(iv) All isolator units and associated functional equipment must comply with the
relevant British standards as stated in BS 7671 (2001): Appendix 1. All units
must be KEMA tested to IEC/EN 60947-3.
(v) All isolator units and their associated functional equipment must be CE
marked in line with the requirements of the low voltage Directive (73/23/EEC,
as amended 93/68/EEC).
(vi) The assembled isolator units must comply with the applicable clauses of
BSEN60439-1: 1999 and BSEN60439-3: 1991.
(vii) The supplier must ensure all isolator units are batch labelled and are fully
traceable.
(viii) All isolators must be of modular construction and accept din-rail mounted
accessories.
(ix) Isolators shall be suitable for 2, 3 and 4 Din rail mounting modules.
11 ISOLATOR ENCLOSURES
(i) The Isolator enclosures shall be constructed to achieve IP43 ingress rating
when the fuse cover is in place and IP2X when the fuse cover is removed, as
per BS EN 60529: 1992. All live terminals must be shrouded to avoid the
danger of shock.
(ii) The isolator enclosure must comply with the material requirements of clause
8.2.12 of BSEN60439-3: 1991. The main body shall be of a colour that easily
allows tracking faults to be seen.
(iii) The enclosure must be fitted with a hinged, lockable transparent safety lid
which requires the use of a tool to gain access to functional equipment.
Electrical components in the enclosure must not be accessible unless the
transparent lid is opened.
(iv) The enclosure shall contain a clearly marked sliding interlock which ensures
the fuse link can only be removed when the main switch disconnector is in the
off position. The interlock must be fully retained (not removable) when the
transparent cover is open.
(v) The IP rating of the enclosure must comply with the requirements of BS EN
60529: 1992.When fully assembled with functional equipment the minimum
acceptable IP rating of the sealed enclosure is IP43. With the covers removed
the minimum acceptable IP rating is IP2X.
(vi) Independent third party certification showing the complete test results must be
produced on request.
(vii) The enclosure must be labelled to the requirements of BS EN 60439-1: 1999
Clause 5. The product must be labelled as stated in BS EN 60947-3: 1999
(including Amendment 1: 2001) Clause 5.
12 SWITCH DISCONNECTORS
(i) The switch disconnector must be manufactured to and comply with the
requirements of BS EN 60947-3: 1999 (including Amendment 1: 2001).
(ii) The switch disconnector must be independently tested to the requirements of
BS EN 60947-3: 1999 (including Amendment 1: 2001) Clause 8.
13 ROTARY FUSE CARRIER
(i) The rotary fuse carrier must be manufactured to and comply with the
requirements of BS EN 60269-1: 1999.
(ii) The rotary fuse carrier must be independently tested to the requirements of BS
EN 60269-1: 1999 Clause 8.
(iii) The rotary fuse carrier must be designed to accept gG Fuse links measuring
12.7mm by 23.0mm complying with the requirements of BS EN 60269-1:
1999.
(iv) The product must be labelled as stated in BS EN 60269-1: 1999 Clause 5.
(v) Independent third party certification showing the complete test results must be
produced on request.
14 FUSES
(i) All fuses shall be of the HRC type and be in accordance with BS 7671:2008
Parts 1 & 5.
(ii) Fused links shall comply with BS 88 and BS EN 60269:1999 Notes 1 & 2 of
Paragraph 5.3 of BS 88-6 shall be taken to be the required current ratings.
(iii) Fuse ratings shall be in suitable for the lamp wattage and type and shall
generally be in accordance with Appendix C Table: C1 – Typical Fuse
Ratings.
(iv) Fuse discrimination must be designed to ensure over-current protection, in
accordance with Regulation 531 of BS 7671:2008
15 CABLES
(i) Cables to be laid underground shall be of armoured construction and have a
minimum conductor size of 6 mm2. Single phase cable shall be three-core
copper XLPE insulated and PVC sheathed copper cable conforming to BS
6004 2000 and BS 6346 1997.
(ii) Installations shall comply with the colour coding as shown in Table 51of BS
7671. For the purposes of voltage rating for street lighting cable, Category A
(Annex ‘A’ of BS 6346 1997) will apply.
(iii) For wall brackets only, the routes and type of any surface cables must be
agreed with the Council prior to their installation.
16 INSTALLTION AND ERECTION OF EQUIPMENT
(i) The holes for the planted root columns shall be excavated to a depth as
recommended by the column manufacturer and to provide the designed
luminaire mounting height. All columns may be erected with bracket attached
only. Luminaires shall only be fitted after the column has been erected for at
least 24 hours All columns shall be placed centrally in the hole in a vertical
position on a pad of concrete and the hole filled with Class ST1 concrete in
150mm layers up to a depth of 150mm below ground level. The excavation
shall be backfilled and evenly rammed. An orange polyethylene 5mm wall
thickness smooth bore duct of 50mm internal diameter shall be installed
through the concrete surround into the column via the cable entry hole to
provide a clear route for the supply cable.
(ii) Flange-plate columns, where required shall be carefully lowered onto the
foundation base prepared for it and shall be set vertically using metal shims
where necessary. The nuts shall be made tight to a torque setting in
accordance with the manufacturers recommendations to secure the column to
the foundation and the nuts and exposed bolts shall be coated with ‘Denso
paste’ and protected with ‘Denso tape’. The space between the flange-plate
and foundation base shall be grouted. The foundation bases shall be purpose
designed and constructed in accordance with the column manufacturer’s
recommendations. Concrete bases must not be loaded until 28 days strength
has been achieved.
(iii) The bracket arms shall be fixed in accordance with the manufacturer’s
instructions to prevent rotation in service. The door locking device shall be
lubricated.
17 LUMINAIRE TO ISOLATOR
(i) The circuit from the luminaire (and photocell) to the isolator shall be wired
with 1.5sq.mm or 2.5sq.mm (depending on load) 300/500V grade single core
XLPE sheathed and PVC served single core copper cables conforming to BS
6004.2000
(ii) A data cable will be run from electronic dimmable driver to base compartment
on residential roads to allow for reprogramming of driver from time to time.
This cable requires to be sleeved to stop ingress of water.
18 CABLE AND EARTHING
(i) The installation must be earthed and labelled in accordance with BS 7430
1998 and BS 7671 and labelled accordingly.
(ii) Armoured cables shall not rely upon the steel wire armour alone for the return
path to earth. The steel armour shall be bonded throughout the cable to a
dedicated core to earth in accordance with Annex B – Compliance and
Paragraph B.5 of BS 6346 1997.
(iii) A separate dedicated earth terminal block shall be fixed to the baseboard of
each column and the earthing terminals of all equipment shall be bonded
separately to this terminal block. Crimped connections are to be used
wherever possible.
(iv) This dedicated earth terminal shall be supplied irrespective of any other earth
terminal, e.g. within the cut-out or on the column.
(v) The terminal block shall be connected to the DNO earth terminal and the main
earthing conductor.
(vi) Any off-cuts or unused cable must be disposed of to scrap by a Contractor
licensed by the Local Authority and in accordance with Environmental
Agency Regulations. Waste Transfer Notes must be obtained and retained for
inspection in respect of all materials transferred for waste. All waste being
carried must be transported by a waste carrier approved by the Environmental
Regulator. Neither cable nor cable drums must be disposed of by burning,
apart from incineration by a licensed waste Contractor.
(vii) All bare earth conductors shall be sleeved with green and yellow PVC
sheathing. All screwed earth connections shall be made between two brass
washers.
(viii) Where the DNO’s service cables are of the Protective Multiple Earth type, the
Contractor shall ensure that the DNO fit the correct Protective Multiple
Earthing label.
(ix) Earth warning labels shall be fitted at every main or supplementary earth
bonding point. Labels shall be in accordance with BS-EN 951 and Regulation
514-13-01 of BS7671:2008
19 FASTENINGS
(i) All Earthing screws, washers and bolts shall be manufactured from brass
20 NUMBERING OF COLUMNS
(i) Columns for Grid roads and link roads shall be numbered by the fixing of
aluminium plates attached with steel band.
(ii) Residential roads and Redways shall be numbered with traditional stick on
numbers, Column numbers to be confirmed by the street lighting manager.
The adhesive number brand and type needs to be approved by the street
lighting manager.
(iii) Each column shall be numbered in accordance with a numbering schedule to
be provided by the council. This will normally be provided after streets have
been named.
(iv) Numbers shall be provided on a consistent side of columns. Columns mounted
on a central reservation shall have a number applied to each side so as it can
be viewed from both sides.
21 CABLE AND DUCT LAYING (Private Supply)
(i) A trench shall be excavated so as to provide a minimum cover to the cable of
450mm to invert except in the case of carriageways where cable shall be laid
at 750mm to invert. The cable shall be laid on a 75mm bed of imported sand,
free from any impurities likely to cause damage to the cable and covered with
a layer of the same material to a depth of 75mm. All unsuitable material shall
be removed and be disposed of to a licensed tip. The trench shall be re-
instated with suitable material only.
(ii) All private cables exceeding a linear length of 3m must be contained in
smooth bore medium density polyethylene duct, colour coded orange of
minimum wall thickness 5mm, and marked ‘STREET LIGHTING’ at
intervals of 900-1000mm. 100mm diameter duct shall be used, except for road
crossings and where particularly specified that 100mm or 150mm diameter
shall be used.
(iii) If the council has notified the contractor that trench inspection is required,
cable trenches shall be left open for inspection the same day that the council
has been notified that the cable is laid and shall not be backfilled without the
council’s permission. Failure to notify the council will result in the trench
being re-opened at the contractor’s expense. Any damage or rectification
works required will also be carried out at the contractor’s expense. Otherwise
all trenches shall be backfilled and re-instated immediately after cable laying.
All open trenches must be barriered and guarded in accordance with Chapter 8
of the Traffic Signs Manual.
(iv) The trench shall be backfilled and reinstated in compliance with the HAUC
specification contained within the New Roads and Street Works Act 1991 and
Chapter 8 of the Traffic Signs Manual.
(v) For private cables a 150mm wide by 0.1mm thick orange PVC tape marked
“Street Lighting Cable” shall be laid along the cable length above the line of
the cable 150mm below finished ground level. Cable tiles must be used where
cable is laid in carriageway.
(vi) No cable joints will be permitted.
(vii) Cables must be laid at an ambient temperature above 0°C.
(viii) The entire length of the duct shall be properly abutted and jointed in
accordance with manufacturers’ instructions to give a smooth bore. The
conduit shall be impact resistant, impervious to water and flexible enough to
follow undulations in the trench bottom and be able to withstand minor earth
movements.
(ix) All ducts shall be provided with a nylon draw rope which shall remain in-situ
upon completion of ducting prior to the installation of the cable. Where
appropriate the draw rope shall be brought to the surface, secured and marked
by a permanent marker. When cables are drawn into a duct an additional draw
rope shall be drawn in parallel with the cable and a 3 metre loop buried at
each duct end.
(x) Duct positions shall be indicated on the kerb line by permanent duct markers.
Unless otherwise directed, all ducts shall project a minimum of 100mm
beyond the edge of the carriageway construction with its draw rope firmly
secured to a crosspiece to prevent accidental withdrawal. All ducts shall be
plugged to prevent ingress of soil or other matter. The contractor shall inform
the council when he intends to install the duct, draw rope, plugs and markings
to enable the council to inspect before backfilling. Where more than two ducts
converge, a suitable inspection chamber shall be fitted.
(xi) On final completion of works the contractor shall furnish the council with as
built drawings indicating the location of all relevant installed ducting and
cable networks.
22 CABLE TERMINATIONS
(i) Every out-going circuit shall be protected by a lockable double pole isolator,
fused to achieve prescribed discrimination. Each isolator shall be fitted with
High Breaking Capacity fuse(s) complying with BS88 and of the appropriate
rating for the circuit load.
(ii) Lockable double pole isolators shall be fitted in the base compartment of each
lighting column or traffic sign into which cables are to be terminated.
(iii) Armoured cables shall be terminated by means of a 3-part compression gland
comprising armour locking ring, locknut, earth terminal and CET.
(iv) The cable armour shall be bonded to the earth terminal block in each column
and continuity achieved throughout the earth loop, including the column.
(v) Where dissimilar metals are in contact, the whole area of each contact surface
shall be cleaned and dried and shall then be coated with jointing paste to avoid
electrolytic action.
23 EARTH RODS Liaise with Milton Keynes Street Lighting department regarding the installation of any / all earth rods / Mats before commissioning of the street lighting equipment.
24 ELECTRICAL TEST INSTRUMENTS
(i) Test instruments shall possess a unique serial number. They shall be correctly
calibrated to National Physical Laboratory Standards and be in accordance
with the manufacturers published specifications, with testing procedures to
comply with BS EN ISO 10012/1.1992.
25 ELECTRICAL INSPECTION & TESTING
(i) The contractor shall undertake all tests prescribed in BS 7671:2008 for all new
circuits or alterations to circuits. Inspection and testing must all be carried out
as prescribed by BS 7671:2008 need to reference to the ILE electrical safety
document and the standard street lighting electrical test record sheets.
(ii) For ease of reference an outline of prescribed inspection and testing is given in
Appendix C – ‘Outline Guidance: Description of Inspection & Testing
required by BS 7671:2008’.
26 WORKING ON DNO NETWORKS
(i) No work shall be undertaken on any DNO plant or apparatus unless specific
personnel are approve to so work by the Regional Electricity Company under
Engineering Recommendation G39/1. Attention is particularly drawn to the
need for the contractor to obtain formal written approval from the DNO before
any authorised work on their plant is carried out. Contractors need to be aware
that authorisation will include indemnifying the DNO against claims and
certifying the competence of their staff to perform prescribed tasks. All
contractors should possess SSD18 accreditation.
(ii) DNO for Milton Keynes is Western Power email address.
27 COMPETENT PERSON’S AUTHORISATION CERTIFICATE FOR WORK ON
ELECTRITY COMPANY’S LIVE EQUIPMENT
(i) The contractor is responsible for notifying the DNO of the names and work
areas and responsibilities of all personnel working on or near the DNO’s plant.
The contractor must have the DNO’s prior written approval before work is
carried out.
(ii) An outline of the local DNO Electric’s training and competency requirements
are given in Appendix D – training For G39/1. However, the requirements
should be confirmed with the DNO prior to the commencement of any work.
All contractors should possess SSD18 accreditation.
APPENDIX B
COMPLIANCE
It is for the private developer to ensure that designs are submitted which provide for compliance with all appropriate legislation and regulations, and the Technical Reports, Codes and Guides produced by the Institution of Lighting Engineers.
The following is given as a brief indicative guide only and must not be regarded as an inclusive or comprehensive list:
Title
Published By
BS5489:2003 Specification and Codes of Practice
British Standards Institute
BS7671:2008 Regulations for Electrical Installations
The Institution of Electrical Engineers
National Joint Utilities Group Guidelines on the Positioning and Colour Coding of Utilities Apparatus
Special Requirements of the Statutory Undertakers
Appropriate Statutory Undertaker
Traffic Signs Regulations and General Directions 2002
The Stationary Office
Traffic Safety Code for Roadworks The Stationary Office
Engineering Recommendation G39/1 Electricity Council
New Roads and Street Works Act 1991(inc. HAUC Specification)
HMSO
Design Manual for Roads and Bridges: Technical Memorandum BD26/99 – Design for Lighting Columns
Department for Transport
Electricity at Work Regulations 1989 Health and Safety Executive
Specification for Highway Works Department for Transport
Waste from Electronic and Electrical Equipment and Recycling Regulations (WEEE)
Restriction Of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment (ROHS)
Appendix C
SCHEDULE OF PREFERRED MATERIALS
The following is a guide only and is not prescriptive: any special applications should be discussed with Milton Keynes Council.
Columns & Bracket Arms, Sign Posts
4m – 8m: Tubular Galvanised factory painted. 10m + 12m Octagonal or Conical Galvanised and painted Steel. Sign Posts : Large Based Tubular, Galvanised and painted. Refer Appendix C standard detail drawings
Hinged Columns Galvanised and painted steel.
Luminaires Refer to table 1 in section 1 or Column/lantern matrix in appendix A
Lamps LED.
Control Gear Philips Electronic Dimmable Ballasts. Philips Dali enabled LED Drivers.
Cut Outs, Isolators Charles Endirect
Photocells Selc 8481 one part photocell 35/18
Feeder Pillars Pudsey Diamond or Lucy. 5mm steel thickness. Vandal Resistant or similar approved.
Belisha Beacons Simmonsigns plus Modupost with Modubel LED’s or similar approved.
External Illumination Units for Signs
Simmonsigns LU Range Signlight or similar approved.
Flashing Amber Signs (For School Crossings)
Simmonsigns Pulsa 4004 LED’s or similar approved.
Enclosures Within Feeder Pillars
Fibox “Ex” Range or similar approved.
Fuse Carriers, MCB’s Charles Endirect, Hagar/MK or similar approved - all suitable for ‘top hat’ DIN rail.
Subway Fittings Designplan Curve
Plate Numbering System
Fabrikat / Eurosigns composite material (No scrap value) refer Appendix C - standard detail drawings
Appendix D
OUTLINE GUIDANCE: DESCRIPTION OF INSPECTION AND TESTING
REQUIRED BY BS 7671: 2008
The following are prescribed by BS7671 and must be adhered to where appropriate. This a summarised Outline Guidance only, and is for ease of reference only and does not excuse the designer and contractor from his own responsibility to refer to and adhere to BS7671:
INSPECTION i) Connection of conductors.
ii) Identification of conductors. iii) Routing of cables in safe zones or protection against mechanical damage.
iv) Selection of conductors for current carrying capacity.
v) Selection of conductors for volt drop.
vi) Connection of single pole devices for protection or switching in phase conductors only.
vii) Correct connection of accessories or equipment.
viii) Presence of fire barriers, suitable seals and protection against thermal effects.
ix) Methods of protection against electric shock.
x) Prevention of mutual detriment influence.
xi) Presence of appropriate devices for isolation and switching correctly located.
xii) Presence of under-voltage protective devices.
xiii) Choice and setting of protective and monitoring devices (for protection against indirect contact and/or protection against over-current).
xiv) Labelling of protective devices, switches and terminals.
xv) Selection of equipment and protective measures appropriate to external influences.
xvi) Adequacy of access to switchgear and equipment. xvii) Presence of danger notices and other warning signs. xviii) Presence of diagrams, instructions and similar information. xix) Erection methods.
TESTING
i) Continuity of protective conductors including main and supplementary equipotential bonding.
ii) Continuity of final circuit conductors. iii) Insulation resistance. iv) Site applied insulation resistance. v) Protection by separation of circuits. vi) Protection against direct contact by a barrier or an enclosure provided
during erection . vii) Insulation of non-conducing floors and walls. viii) Polarity. ix) Earth electrode resistance. x) Earth fault loop impedance. xi) Prospective fault current xii) Functional testing
REPORTING
All prescribed results shall be recorded in full accordance with the requirements of BS7671. The developer’s attention is drawn to the fact that It is particularly pointed out that any error whatsoever will result in the certificate being rejected.
The developer shall give not less than 7 days’ notice to the council of his
intention to carry out any of the tests specified and the council shall be given the opportunity to witness such test.
The Contractor shall furnish the council with the original completed certificate, to verify compliance with BS7671 upon satisfactory completion of the inspection and tests.
CERTIFICATION
(a) Following the inspection and testing of new and altered installations, a test and inspection certificate shall be submitted to the council on Forms SSP1 and SSP2. The certificate shall include the serial numbers of the instruments used for the tests.
(a) Any defects or omissions revealed by the tests shall be reported to the council without delay and no certificate will be issued until the defects or omissions have been made good. (b) In the event of any test indicating failure to comply, that test and those preceding, the results of which may have been influenced by the fault indicated, shall be repeated after the fault has been rectified.
TEST AND INSPECTION CERTIFICATE - HIGHWAY POWER SUPPLIES AND STREET FURNITURE - INTERNAL WIRING
ROUTE / SEQ: STREET NAME / SITE: AREA:
Column/Sign/Bollard and Location
Visual Inspection Satisfactory?
System Earthing Type
Circuit Protection Continuity of Protective Conductors Satisfactory?
Insulation Resistance MegOhms (min value) 500 volt test
Polarity Satisfactory?
Phase/Earth Fault Loop Impedance (Ohms0
Any Other comments
Fuse BS No/MCB Class
Rating (amps)
TEST INSTRUMENT NUMBERS:
TEST AND INSPECTION CERTIFICATE- CABLE NETWORKS ROUTE/SEQ: AREA: STREET NAME/SITE: SOURCE: CIRCUIT: CABLE TYPE:
CIRCUIT PROTECTION: Fuse BS No MCB Class: Rating (A): Ext. Impedance (Ze): Ohms
PROSPECTIVE SHORT CIRCUIT CURRENT AT ORIGIN: kA
HOW DETERMINED: Calculation / Measurement / Enquiry
INITIAL VERIFICATION: Satisfactory: YES NO COMMENTS:
CONTINUITY OF PROTECTIVE CONDUCTORS: Satisfactory: YES NO COMMENTS:
INSULATION RESISTANCE (Meg.Ohms): Test Instrument No. COMMENTS:
POLARITY: Satisfactory: Yes NO Test Instrument No.
EARTH FAULT LOOP IMPEDANCE (Ohms): Test Instrument No. Source: Remote End: Volt Drop:
VOLTAGE: Test Instrument No. Source: Remote End: Volt Drop:
COMMENTS:
I CERTIFY TO THE BEST OF MY KNOWLEDGE AND BELIEF THAT THE CABLE NETWORK AT THE ABOVE SITE HAS BEEN INSPECTED AND TESTED IN ACCORDANCE WITH BS 7671 AND THE ILE CODE OF PRACTICE FOR ELECTRICAL SAFETY IN PUBLIC LIGHTING OPERATIONS AND THAT THE RESULTS ARE SATISFACTORY IN RESPECT OF THE ITEMS DETAILED ABOVE. SIGNED__________________________________ DATE_________________________ PRINT NAME___________________________
APPENDIX ‘E’ – DNO REQUIREMENTS: ENG. RECOMMENDATION G39 Course 1 Attendance at DNO Approved Insertion and Removal of Fuse Course (Engineering Recommendation G39/1) Date Attended: NOTE: ONLY OPERATIVES WHO HAVE SUCCESSFULLY COMPLETED THE ABOVE COURSE WILL BE ALLOWED TO WORK ON STREET LIGHTING INSTALLATIONS. Level of Authorisation (Delete whichever of the following items is not applicable). Level 1 (A) (i) Lamp replacement and cleaning purposes
(ii) Painting of structures
(B) (i) Replacement of the local fuses protecting the equipment
(ii) Replacement and connecting control gear and associated components, including controllers
Level 2 (All work in Level 1 plus:) (A) (i) The supervision of erection of lighting columns and fittings in the vicinity
of the DNO's overhead lines
(B) (i) The installation of cables, lighting columns, signs, etc., where live underground cables may be present.
Level 3 (All work in Levels 1 and 2 plus:) (A) (i) Testing of installations
(ii) Wiring of installations to the outgoing side of the DNO's cutout. (iii) Maintenance of installations (iv) Initial insertion, removal and replacement of the DNO's cutout fuses,
subject to the DNO’s direction (limited to public lighting fuses only).
(B) (i) Necessary work on live equipment
(ii) Nominated special duties for which they have received training
Name of Competent Person (BLOCK LETTERS) Name and Address of Employer Approved by .................................................................................. Position ............................................................... Dated... ... ... Received .......................................................... Dated... ... ...
APPENDIX ‘F’ – SSP4 INDEMNITY FORM In consideration of (Insert name of DNO) .......................................................................... permitting(Company Name).............................................................................................. to do work on or affecting (DNO)....................................................................................... equipment at ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… The Company hereby indemnify (DNO)............................................................................... from and against any actions, costs, claims or demands, howsoever and from whomsoever arising, directly or indirectly as a result of work undertaken by the Local Authority or company or their delegates on or affecting the above mentioned equipment, unless resulting from the negligence of (DNO)...........................or its servants or agents. And from and against all costs, damages and expenses arising as a result of damage to any (DNO).....................................equipment caused directly or indirectly as result of work undertaken by the Company or their delegates on or affecting the above mentioned equipment. Signed…………………………………… Authorised to sign on behalf of and to bind
(Company Name)…………………………………………………………………..
APPENDIX G - MILTON KEYNES BOROUGH MAP