Drawing Description Drawing No.
Drawing Register ST 001 - 005Introduction Series 000StoTherm Insulated Facade System Introduction ST 006StoTherm Insulated Facade System Reinforcing Mesh Application ST 007StoTherm Insulated Facade System Panel Information ST 008
Panel Layout Series 100StoTherm Insulated Facade System SS 106 StoTherm StoArmat Render System ST 100StoTherm Insulated Facade System SS 105 StoTherm StoMiral Render System ST 101StoTherm Insulated Facade System EPS sheet and Fixing Layout Typical Elevation ST 102StoTherm Insulated Facade System StoTherm Panel Layout ST 103
Foundation Series 200StoTherm Insulated Facade System Foundation Slab-on-Ground ST 200StoTherm Insulated Facade System Insulated Slab-on-Ground ST 201StoTherm Insulated Facade System Rebated Slab-on-Ground - Render Finish ST 202StoTherm Insulated Facade System Ribraft Floor System/Edge Detail ST 203StoTherm Insulated Facade System Conc.Block Foundation Edge Detail ST 204StoTherm Insulated Facade System EPS Block Foundation Detail ST 205StoTherm Insulated Facade System Solid Conc. Foundation Edge Detail ST 206StoTherm Insulated Facade System Conc. Continuous Perimeter Foundation Wall ST 207StoTherm Insulated Facade System Maxraft Floor System/Edge Detail ST 208 StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (parallel wall) ST 209StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (right angled wall) ST 210StoTherm Insulated Facade System Timber Subfloor With Jackstuds ST 211StoTherm Insulated Facade System Masonry Conc. Block in Ground Wall ST 212StoTherm Insulated Facade System Concrete Block Interstorey Drained Junction ST 213
Walls Series 300StoTherm Insulated Facade System StoTherm Panel Layout ST 300StoTherm Insulated Facade System Panel Fixing Vertical ST 301 StoTherm Insulated Facade System Panel Fixing Horizontal ST 302StoTherm Insulated Facade System External Corner ST 303StoTherm Insulated Facade System Internal Corner ST 304StoTherm Insulated Facade System Vertical Control Joint ST 305StoTherm Insulated Facade System Horizontal Inter Storey ST 306StoTherm Insulated Facade System Horizontal Inter Storey Control Joint ST 307StoTherm Insulated Facade System Drained Junction at Third Storey ST 308StoTherm Insulated Facade System Boxed Beam ST 309StoTherm Insulated Facade System Post Detail ST 310
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.
STO DRAWING REGISTER
PAGE 1 OF 6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAWING REGISTER
ST 001
2017
-
Drawing Description Drawing No.
Wall Penetrations & Fittings Series 350StoTherm Insulated Facade System Pipe Penetration Detail ST 350StoTherm Insulated Facade System Light Fitting/Fixing Detail ST 351StoTherm Insulated Facade System Tap Fitting/Fixing Detail ST 352StoTherm Insulated Facade System Handrail Bracket/Fixing Detail ST 353StoTherm Insulated Facade System Meterbox - Isometric ST 354StoTherm Insulated Facade System Meterbox - Cross Section ST 355StoTherm Insulated Facade System Downpipe Saddle Fixing & Wiring Details ST 356StoTherm Insulated Facade System Fan Vent Detail ST 357StoTherm Insulated Facade System Inter-Storey Junction with Poly Profile ST 358StoTherm Insulated Facade System Joint at Third Storey with Poly profile ST 359
Joinery Series 400StoTherm Insulated Facade System Alu.Joinery - Head Detail - Stick on Jamb ST 400StoTherm Insulated Facade System Alu.Joinery - Head Detail - Cavity Jamb ST 401StoTherm Insulated Facade System Alu.Joinery - Sill Detail - Sto uPVC Stick on Sill ST 402StoTherm Insulated Facade System Alu.Joinery - Jamb Detail - Sto uPVC Cavity Jamb ST 403StoTherm Insulated Facade System Alu.Joinery - Jamb Detail - Sto uPVC Stick on Jamb ST 404StoTherm Insulated Facade System Int.Cnr Alu.Window/Door Joinery - Jamb Detail ST 405StoTherm Insulated Facade System Entry Door Threshold Detail ST 406StoTherm Insulated Facade System Entry Door/Deck Threshold Detail ST 407StoTherm Insulated Facade System Bifold Door/Threshold Detail ST 408StoTherm Insulated Facade System Level Entry Threshold Detail ST 409StoTherm Insulated Facade System Garage Door - Timber Head Detail ST 410StoTherm Insulated Facade System Garage Door - Timber Jamb Detail ST 411StoTherm Insulated Facade System Garage Door - Rendered Head Detail ST 412StoTherm Insulated Facade System Garage Door - Rendered Jamb Detail ST 413StoTherm Insulated Facade System Sto uPVC Head and Jamb Flashing Isometric ST 414
Parapets, Balustrades, Decks Series 500StoTherm Insulated Facade System Parapet/Metal Flashing Detail ST 500StoTherm Insulated Facade System Rendered Parapet/Balustrade Detail ST 501StoTherm Insulated Facade System Parapet and/or Encl.Balustrade Wall Junction - Plan View ST 502StoTherm Insulated Facade System Flexible Flashing Install - Isometric ST 503StoTherm Insulated Facade System Metal Saddle Flashing & Cap Install - Isometric ST 504StoTherm Insulated Facade System StoFlexyl Meshed Saddle Flashing Install - Isometric ST 505StoTherm Insulated Facade System StoFlexyl Meshed Waterproofing Cap - Isometric ST 506StoTherm Insulated Facade System Balustrade/Encl.Deck Detail ST 507StoTherm Insulated Facade System Enclosed Deck Detail ST 508StoTherm Insulated Facade System Cantilevered Slatted Deck ST 509StoTherm Insulated Facade System Non Cantilevered Slatted Deck ST 510StoTherm Insulated Facade System Timber Beam/Pergola Detail ST 511StoTherm Insulated Facade System Parallel Deck Joist Bracket ST 512StoTherm Insulated Facade System RWH/Scupper Opening ST 513
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.
PAGE 2 OF 6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAWING REGISTER
ST 002
2017
-
Drawing Description Drawing No.
Soffit Series 600StoTherm Insulated Facade System Flat Soffit/Wall Junction Timber Fascia ST 600 StoTherm Insulated Facade System Raking Soffit/Wall Junction Timber Fascia ST 601StoTherm Insulated Facade System Face Fixed Timber Fascia ST 602StoTherm Insulated Facade System Reverse Raking Soffit to wall with Flashing ST 603 StoTherm Insulated Facade System Raking Soffit - Sto uPVC Control Joint ST 604 StoTherm Insulated Facade System Soffit to Cladding Detail ST 605StoTherm Insulated Facade System Gutter/Wall Apron Flashing Junction ST 606 StoTherm Insulated Facade System Soffit at Window/Door Head ST 607StoTherm Insulated Facade System Metal Fascia Face Fixed Membrane Roof ST 608StoTherm Insulated Facade System Metal Fascia Barge Detail ST 609StoTherm Insulated Facade System Metal Fascia Face Fixed Barge Detail ST 610StoTherm Insulated Facade System Flat Soffit/Wall Junction Metal Fascia ST 611StoTherm Insulated Facade System Raking Soffit/Wall Junction Metal Fascia ST 612StoTherm Insulated Facade System Face Fixed Metal Fascia ST 613
Roof Series 700StoTherm Insulated Facade System Apron Flashing ST 700StoTherm Insulated Facade System Parallel Apron Flashing ST 701StoTherm Insulated Facade System Inter-storey Transverse (Apron) Roof/Stopend ST 702 StoTherm Insulated Facade System Inter-storey Deck or Roof/Stopend Flashing ST 703StoTherm Insulated Facade System Inter-storey Roof Stop End Flashing - Plan View ST 704StoTherm Insulated Facade System Roof Penetration/Gutter (Masonry Tile) ST 705StoTherm Insulated Facade System Roof Parallel/Hidden Gutter ST 706StoTherm Insulated Facade System Face Fixed Fascia/Barge ST 707StoTherm Insulated Facade System Face Fixed Fascia/Membrane Roof ST 708StoTherm Insulated Facade System Roof/Wall Ridge ST 709StoTherm Insulated Facade System Framed Chimney ST 710
Dissimilar Material
Weatherboard Series 800StoTherm Insulated Facade System Ext.Corner Weatherboard/StoTherm - Opt 1 ST 800StoTherm Insulated Facade System Ext.Corner Weatherboard/StoTherm - Opt 2 ST 801StoTherm Insulated Facade System Ext.Corner Direct Fixed Weatherboards/StoTherm ST 802StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Opt 1 ST 803StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Opt 2 ST 804StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Direct Fix ST 805StoTherm Insulated Facade System Vertical Joint Weatherboard/StoTherm - Opt 1 ST 806StoTherm Insulated Facade System Vertical Joint Weatherboard/StoTherm - Opt 2 ST 807StoTherm Insulated Facade System Horizontal Junction Weatherboard/StoTherm ST 808StoTherm Insulated Facade System Gable End Weatherboard/StoTherm ST 809StoTherm Insulated Facade System Internal Corner Direct Fixed EIFS to StoTherm ST 810.1
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.
PAGE 3 OF 6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAWING REGISTER
ST 003
2017
-
Drawing Description Drawing No.
Continuation Dissimilar Material
Brick Series 810StoTherm Insulated Facade System External Corner Brick Veneer/StoTherm ST 810StoTherm Insulated Facade System Internal Corner Brick Veneer/StoTherm - Opt 1 ST 811StoTherm Insulated Facade System Internal Corner Brick Veneer/StoTherm - Opt 2 ST 812StoTherm Insulated Facade System Vertical Junction Brick Veneer/StoTherm ST 813StoTherm Insulated Facade System Horizontal Junction Brick Veneer/StoTherm ST 814
Fibre Cement Sheet Series 820StoTherm Insulated Facade System External Corner FC Sheet/ StoTherm ST 820StoTherm Insulated Facade System Internal Corner FC Sheet/ StoTherm - Opt 1 ST 821StoTherm Insulated Facade System Internal Corner FC Sheet/ StoTherm - Opt 2 ST 822StoTherm Insulated Facade System FC Sheet - Framed Sub Floor Cladding ST 823StoTherm Insulated Facade System FC Sheet Gable End ST 824
Concrete Block Series 830StoTherm Insulated Facade System External Corner Concrete Block/StoTherm ST 830StoTherm Insulated Facade System Internal Corner Concrete Block/StoTherm ST 831StoTherm Insulated Facade System Vertical Joint Concrete Block/StoTherm ST 832StoTherm Insulated Facade System Horizontal Junction Concrete Block/StoTherm ST 833
Manufactured Stone - Schist & Natural Stone Series 840StoTherm Insulated Facade System Ext.Cnr Manuf.Stone/StoTherm - Opt 1 ST 840StoTherm Insulated Facade System Ext.Cnr Manuf.Stone/StoTherm - Opt 2 ST 841StoTherm Insulated Facade System Ext.Cnr Schist or Stone Veneer/StoTherm ST 842StoTherm Insulated Facade System Boxed Ext.Cnr Stone Veneer/StoTherm ST 843StoTherm Insulated Facade System Internal Cnr. Manuf.Stone/StoTherm ST 844StoTherm Insulated Facade System Internal Cnr. Schist or Stone Veneer/StoTherm ST 845StoTherm Insulated Facade System Vertical Junction Manuf.Stone/StoTherm ST 846StoTherm Insulated Facade System Vertical Junction Schist or StoneVeneer/StoTherm ST 847StoTherm Insulated Facade System Horiz.Junction Manuf.Stone/StoTherm ST 848StoTherm Insulated Facade System Horiz.Junction Schist or StoneVeneer/StoTherm ST 849
Profile Metal Series 850StoTherm Insulated Facade System Ext.Cnr Horiz.Profiled Metal/StoTherm ST 850StoTherm Insulated Facade System Int.Cnr Horiz.Profiled Metal/StoTherm ST 851StoTherm Insulated Facade System Vertical Junction Horiz.Profiled Metal/StoTherm ST 852StoTherm Insulated Facade System Horizontal Junction Horiz.Profiled Metal/StoTherm ST 853StoTherm Insulated Facade System External Corner Vertical Profiled Metal/StoTherm ST 854StoTherm Insulated Facade System Internal Corner Vertical Profiled Metal/StoTherm ST 855StoTherm Insulated Facade System Horiz.Junction Vertical Profiled Metal/StoTherm ST 856
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.
PAGE 4 OF 6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAWING REGISTER
ST 004
2017
-
Drawing Description Drawing No.
Continuation Dissimilar Material
StoTherm Panel EIFS Series 860StoTherm Insulated Facade System Ext.Cnr StoPoren/StoTherm ST 860StoTherm Insulated Facade System Int.Cnr StoPoren/StoTherm ST 861StoTherm Insulated Facade System Vertical Joint 50mm StoPoren/StoTherm ST 862StoTherm Insulated Facade System Vertical Joint 80mm StoPoren/StoTherm ST 863StoTherm Insulated Facade System Inter-Storey Junction StoPoren/StoTherm ST 864StoTherm Insulated Facade System Inter-Storey Third Storey Drained Inter-storey Junction ST 865
DISSIMILAR JOINERY Series 870TIMBER JOINERYStoTherm Insulated Facade System Timber Window Joinery - Head Detail ST 870StoTherm Insulated Facade System Timber Window Joinery - Sill Detail ST 871StoTherm Insulated Facade System Timber Window Joinery - Jamb Detail ST 872StoTherm Insulated Facade System Timber Door Joinery - Timber Floor/Threshold Detail ST 873StoTherm Insulated Facade System Timber Door Joinery - Concrete Floor/Threshold Detail ST 874NK PVCu JOINERYStoTherm Insulated Facade System NK PVCu - Head Detail ST 875StoTherm Insulated Facade System NK PVCu - Sill Detail ST 876StoTherm Insulated Facade System NK PVCu - Jamb Detail ST 877FLASHMAN JOINERY FLASHING SYSTEMStoTherm Insulated Facade System Flashman Head Flashing ST 878StoTherm Insulated Facade System Flashman Sill Flashing ST 879StoTherm Insulated Facade System Flashman Jamb Flashing ST 880HOMERIT PVC JOINERYStoTherm Insulated Facade System Homerit PVC Joinery - Head Detail ST 881StoTherm Insulated Facade System Homerit PVC Joinery - Sill Detail ST 882StoTherm Insulated Facade System Homerit PVC Joinery - Jamb Detail ST 883
Rusticated Weatherboard Series 890StoTherm Insulated Facade System Ext.Corner Rusticated Weatherboard/StTherm - Opt 1 ST 890StoTherm Insulated Facade System Ext.Corner Rusticated Weatherboard/StoTherm - Opt 2 ST 891StoTherm Insulated Facade System Ext.Corner Direct Fixed Rusticated Weatherboards/StoTherm ST 892StoTherm Insulated Facade System Int.Corner Rusticated Weatherboard/StoTherm - Opt 1 ST 893StoTherm Insulated Facade System Int.Corner Rusticated Weatherboard/StoTherm - Opt 2 ST 894StoTherm Insulated Facade System Int.Corner Direct Fixed Rusticated Weatherboard/StoTherm ST 895StoTherm Insulated Facade System Vertical Joint Rusticated Weatherboard/StoTherm - Opt 1 ST 896StoTherm Insulated Facade System Vertical Joint Rusticated Weatherboard/StoTherm - Opt 2 ST 897StoTherm Insulated Facade System Horizontal Junction Rusticated Weatherboard/StoTherm ST 898StoTherm Insulated Facade System Gable End Rusticated Weatherboard/StoTherm ST 899
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.
PAGE 5 OF 6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAWING REGISTER
ST 005
2017
-
STOTHERM INSULATED FACADE SYSTEM
SS105 STOTHERM STOMIRAL RENDER SYSTEM BRANZ APPRAISAL CERTIFICATE NO. 478INCORPORATING:1. STOLEVELL NOVO, STOLEVELL UNI or MULTISCREED 25kg BAG EUROPEAN FIBRE
REINFORCED CEMENT BASED RENDER USED WITH EUROPEAN MESH AS A REINFORCINGBASECOAT RENDER.
2. STOPLEX W SEALER - 10lt CONTAINER EUROPEANACYLIC/SILANE PRIMER TO SEAL MINERALSURFACES
3. STOLIT K COLOURED - 25kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT COLOUREDFINISHING RENDER AVAILABLE IN 1.0/1.5/2.0/3.0mm SIZED TEXTURE IN A PAIL
4. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL: LASTIC SATIN FACADE PAINT 15lt PAIL: LOTUSAN MINERAL RESIN PAINT 15lt PAIL
SS106 STOTHERM STOARMAT RENDER SYSTEM BRANZ APPRAISAL CERTIFICATE NO. 478INCORPORATING:1. STOLEVELL NOVO, STOLEVELL UNI or MULTISCREED 25kg BAG BASECOAT RENDER TO
STRAIGHTEN AND PROVIDE A SOLID THICKER BASECOAT2. STOARMAT CLASSIC RENDER 23kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT BASED
CRACKED RESISTANT RENDER USED WITH EUROPEAN MESH AS A REINFORCEMENT RENDER3. STOLIT K or MP COLOURED RENDER 25kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT
COLOURED FINISHING RENDER AVAILABLE IN 1.0/1.5/2.0/3.0mm SIZED TEXTURE AND MP or MPNATURAL SPONGE FINISHED RENDER
4. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL: LASTIC SATIN FACADE PAINT 15lt PAIL: LOTUSAN MINERAL RESIN PAINT 15lt PAIL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
INTRODUCTION
ST 006
2017
-
ALU.WINDOW JOINERY
STO COATINGSTOLIT COLOUREDFINISHING RENDER
6mm SEALANT GAPBETWEEN JOINERY AND
uPVC FLASHING
NOTE:1. PROPRIETARY ALUMINUM HEAD FLASHING AND
STO uPVC SILL & JAMB FLASHINGS AREREQUIRED
2. MS SEALANT APPLIED TO JAMBS & WINDOWSILL TO CLADDING JUNCTION
STO ARMAT MESHEDRENDER
STOTHERM PANEL
NOTE: STO uPVCFLASHING NOT SHOWNFOR CLARITY AREMESHED IN STOARMAT
MESH WRAPPEDAROUND REVEALSAND ONTO STO uPVCFLASHINGS
MESH 50mm MIN. INEACH DIRECTION TOREINFORCE MESH SEAMAT INSIDE CORNER
DIAGONALREINFORCEMENT/BUTTERFLY USING STOMESH - 200X100mm OVERWALL MESHSTOLEVELL NOVO, STO
LEVELL UNI orMULTISCREED
BASECOAT
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
REINFORCING MESH APPLICATION
ST 007
2017
-
SCALE 1:20
STOTHERM PANELS
H GRADE WHITE SELF EXTINGUISHINGPOLYSTYRENE MANUFACTURED TO COMPLYWITH AS1366.3
SIZES - STANDARD PANEL 2700 x 1200mm
THICKNESS AND R VALUE NZS4214 REQUIRES A45% REDUCTION OF R VALUE ON A CAVITY
cavity + 50mm - RV 0.76cavity + 60mm - RV 0.91cavity + 80mm - RV 1.22cavity + 100mm - RV 1.52
STOTHERM+ PANELS
GREY GRAPHITE INFUSED SELF EXTINGUISHINGPOLYSTYRENE COMPLYING WITH AS1366
SIZES - STANDARD PANEL 2700 x 1200mm
cavity + 40mm - RV 0.72cavity + 60mm - RV 1.06cavity + 80mm - RV 1.41
1200
2700
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
PANEL INFORMATION
ST 008
2017
-
SCALE 1:20
TIMBER FRAMINGTO NZS 3604
STOTHERM ARMAT CLASSICRENDER SYSTEM - SS106
STO uPVC ADJUSTABLE FOOTTRAY - incl.base/extension/base
WALL UNDERLAY MEETINGREQUIREMENTS E2/AS1
CONCRETE FOUNDATION AS PER NZS3604 ORSPECIFIC ENGINEERING REQUIREMENTS
FINISHING RENDER: STOLIT K &MP RANGE
INSULATION:SELF-EXTINGUISHINGPOLYSTYRENE SHEET
SELECTED COATING:STOCOLOR: MAXICRYL MATT FACADE PAINT: LASTIC SATIN PAINT: LOTUSAN MINERAL RESIN
BASECOAT: STOLEVELL NOVO,STOLEVELL UNI or MULTISCREED 4-5mm
STOTHERM 20mm VH CAVITYBATTENS
REINFORCEMENT: STOARMAT
PLUS STO MESH
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
SS106 STOTHERM STOARMAT RENDER SYSTEM
ST 100
2017
-
SCALE 1:20
TIMBER FRAMINGTO NZS 3604
STOTHERM STOMIRALRENDER SYSTEM - SS105
STO uPVC ADJUSTABLE FOOTTRAY - incl.base/extension/base
WALL UNDERLAY MEETINGREQUIREMENTS E2/AS1
CONCRETE FOUNDATION AS PER NZS3604 ORSPECIFIC ENGINEERING REQUIREMENTS
FINISHING RENDER: STOLIT K &MP RANGE
SELECTED STOTHERM PANEL
COATING/STOCOLOR: MAXICRYL MATT FACADE PAINT: LASTIC SATIN PAINT: LOTUSAN MINERAL RESIN PAINT
BASECOAT: STOLEVELL NOVO,STOLEVELL UNI or MULTISCREEDPLUS: STO EUROPEAN MESHSEALED WITH STOPLEX WPRIMER
STOTHERM 20mm VH CAVITYBATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
SS105 STOTHERM STOMIRAL RENDER SYSTEM
ST 101
2017
-
N.T.S
300600
DOORWINDOW
NOTE: SHEET JOINTS AROUNDOPENINGS ARE GLUED or FOAMFUSED FOR STABILITY
STOTHERM 20mm VH FIXEDOVER FRAME & BUILDING
UNDERLAY
REFER TO WIND ZONES FORREQUIRED HORIZONTAL
SPACERS 100mm LONG - MUSTBE SET TO A FALL 5° MIN.
NOTE: CAVITY SYSTEM IS A VENTED DRAINAGE SYSTEM.FIX STO uPVC FOOT TRAY BEFORE BATTENS.
FIXINGS IN WIND ZONES
LOW, MEDIUM & HIGHStuds 300mm fixing ctrs top & bottom plates and dwangs. Onefixing between studs
VERY HIGHStuds, plates and dwangs 200mm fixing ctrsEXTRA HIGHStuds, plates and dwangs 150mm fixing ctrs
WHERE STUD SPACINGS ARE GREATER THAN 450mmCTRS FIX ADDITIONAL INTERMEDIATE BATTEN TOPREVENT INSULATION ENCROACHING INTO CAVITY SPACE
2nd LEVEL
300
A A A A
A A
A
NO INTER-STOREY JOINTREQUIRED AT 2nd LEVEL
VERTICAL CONTROL JOINTS REQUIREDFOR WALLS OVER 20 METERS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
EPS SHEET & FIXING LAYOUT - TYPICAL (Elevation)
ST 102
2017
-
N.T.S
SHEET LAYOUT - LINE UPSHEETS WITH OPENINGS.FLUSH FILL ANY JOINTGAPS WITH STO FOAMTAKING CARE NOT TOFILL CAVITY
STOARMAT CLASSICMESHED HEAD, SILL& JAMB FLASHINGS
100x200mm MIN. DIAGONALBUTTERFLY REINFORCEMENT
STO uPVC PREMESHEDCORNER ANGLE
SELECTED EPSSHEETS -2700x1200mm
NOTE: USE FULL SHEETS WHERE POSSIBLE ALL CUT SHEETS SHALLBE CAREFULLY MADE TO ACHIEVE A GOOD FIT. ALL SHEET JOINTSSHOULD BE FLUSHED FILLED WITH STO ADHESIVE FOAM - TAKINGCARE NOT TO FILL CAVITY
200
STO MESH JOINTSOVERLAPPED 75mm MIN.STO LEVELL UNI/MESHMULTI SCREED ORSTOARMAT CLASSICMESH COAT
H GRADE EPS SHEETS NORMALLY - 2700 x 1200mm
NOTE: USE FULL SHEETS WHERE POSSIBLEALL SHEET EDGES MUST BE SUPPORTED BY A FRAMING MEMBERALL SHEETS CUTS SHALL BE MADE CAREFULLY TO ACHIEVE A TIGHT BUTT FIT.
ANY GAPS IN THE EPS SHEET MUST BE FILLED WITH STO FOAM ON HORIZONTAL JOINTS CARE MUST BE TAKEN TO AVOID FOAM FILLING THE CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
STOTHERM PANEL LAYOUT
ST 103
2017
-
STO uPVC VENTEDADJUSTABLE FOOT TRAY
SCALE 1:5
6mm OVERHANGRECOMMENDED TOAVOID VARIANCES INFOUNDATION
TIMBER FRAMINGTO NZS 3604
DPC
INTERIOR LINING
225m
m M
IN.
TO U
NP
AV
ED
GR
OU
ND
LE
VE
L
50m
mcl
ad.
150m
m M
IN.
TO P
AV
ED
GL
WALL UNDERLAY
STOTHERM RENDER SYSTEM
CAVITY SPACERS TO SUITFIXINGS
AS PER NZS 3604
STOTHERM PANELFIXING
6
STO RENDER SYSTEMON FOUNDATION
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN
FOR CLARITY
DPM
INSULATIONAS PER NZBC
H1/AS1
100m
m M
IN.
Sto
Pla
ster
50m
mFl
exyl
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM PANEL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
FOUNDATION SLAB-ON-GROUND
ST 200
2017
-
SCALE 1:5
5mm MIN GAP
STO uPVC VENTED BASE CAP
6mm OVERHANGRECOMMENDED TO AVOIDVARIANCES IN FOUNDATION
TIMBER FRAMINGTO NZS 3604
DPC
225m
m M
IN.
TO U
NP
AV
ED
GR
OU
ND
LE
VE
L
150m
m M
IN.
TO P
AV
ED
GL
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
STOTHERM PANEL FIXING
CAVITY SPACERS TO SUIT FIXINGS
AS PER NZS 3604
5
STOTHERM PANEL
STO FLEXYL WATERPROOFINGTO REBATE
INSULATED FOUNDATION WITHSTOTHERM RENDER SYSTEM ONSTOFLEXYL WATERPROOFING
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN
FOR CLARITY
DPM
INSULATION ASPER NZBC -
Clause H1
100m
m M
IN.
Sto
Ren
der
50m
mC
lad.
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
INSULATED SLAB-ON-GROUND
ST 201
2017
-
SCALE 1:5
TIMBER FRAMINGTO NZS 3604
DPC
STO RENDER SYSTEM
INTERNAL LINING
DPM
AS PER NZS 3604
75mmrebate
BUILDING UNDERLAY
20mm DRAINED CAVITY
STOTHERM PANEL
STO FLEXYL OR LIQUID DPM ONREBATE
STO uPVC CONTROL JOINT ORFINISHING EDGE AT JUNCTIONTO FOUNDATION
WEATHER PROTECTED VENTSTO ACHIEVE MIN. VENTILATIONOF 1000mm²/LINEAL METERPOSITIONED HARD ON REBATE1
0
INSULATION TO EXTERIORWALLS
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN
FOR CLARITY
STOTHERM PANELFIXING
INSULATION ASNZBC H1/AS1
100m
m M
IN.
Sto
Ren
der
50m
mfle
xyl
50m
mC
lad.
100m
mto
pav
ing
STOTHERM RENDERSYSTEM
STO uPVC END CAP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
REBATED SLAB-ON-GROUND - RENDERED FINISH
ST 202
2017
-
SCALE 1:5
50m
mcl
addi
ng15
0mm
to p
avin
g
225m
m u
npav
ed G
L
DPC
GL
WALL UNDERLAY
STOTHERM PANELFIXING
STOTHERM PANEL
STO uPVC VENTEDBASE CAP
STOTHERM 20mm VHCAVITY BATTENSSTOTHERM RENDERSYSTEM
CAVITY SPACERS TOSUIT FIXINGS
RIBRAFT POLYSTYRENE PODINSTALLATION IN ACCORDANCE TO FIRTHRIBRAFT CONSTRUCTION DETAILS
8522
0
CONCRETE SLAB/REINFORCINGAS PER NZS 3604, SPECIFIC
DESIGN OR ENGINEER (SED)Reinforcing not shown for clarity
300
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
RIBRAFT FLOOR SYSTEM / EDGE DETAIL
ST 203
2017
-
225m
m u
npav
ed G
L
SCALE 1:5
CONCRETE FOOTING ASPER NZS 3604 OR ENGINEER
SPECIFIC DESIGN
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEER
SPECIFIC DESIGN
DPC
NOTE:SHELL OF BLOCK CAN SUPPORT
BOTTOM PLATE WHEN SLAB ISTIED TO FOUNDATION
50m
mcl
addi
ng15
0mm
to p
aved
GLINSULATION AS PERNZBC - Clause H1
DPM
STO uPVC VENTEDBASE CAP
WALL UNDERLAY
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
CAVITY SPACERS TOSUIT FIXINGS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
CONC.BLOCK FOUNDATION EDGE DETAIL
ST 204
2017
-
SCALE 1:5
CONCRETE FOOTING ASPER NZS 3604 OR ENGINEER
SPECIFIC DESIGN
DPM REQUIRED ONFOUNDATION FOR POORLYDRAINED SITES OTHERWISETERMINATE AT BOTTOMEXTERNAL CORNER OFFOUNDATION
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEER
SPECIFIC DESIGN
DPC
NOTE:INSTALL STOFLEXYL UNDER DPM AT TRANSITION IF REQUIRED FOR POORLYDRAINED SITES.
STO uPVC VENTED BASECAP - 5mm MIN.GAP
WALL UNDERLAY
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
CAVITY SPACERS TOSUIT FIXINGS
DPM
INSULATION AS PERNZBC - Clause H1
STOFLEXYL WATERPROOFINGTO REBATE, CONTINUE TO50mm PAST STO RENDERTERMINATION POINT
100m
mS
to R
ende
r50
mm
Flex
yl50
mm
clad
ding
150m
mTO
PA
VE
D G
L22
5mm
TO U
NP
AV
ED
GR
OU
ND
LE
VE
L
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
EPS BLOCK FOUNDATION DETAIL
ST 205
2017
-
SCALE 1:5
50m
mcl
addi
ng15
0mm
to p
aved
225m
m u
npav
ed G
L
INSULATION AS PERNZBC - Clause H1
DPM
DPC10mm INSULATION
IF REQUIRED
GL
CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR SPECIFIC
ENGINEER DESIGN (SED)
Var
ies
refe
r to
NZS
3604
or S
ED
WALL UNDERLAY
STOTHERM PANEL FIXING
STOTHERM PANEL
STO uPVC VENTEDBASE CAP
STOTHERM 20mm VHCAVITY BATTENSSTOTHERM RENDERSYSTEM
CAVITY SPACERS TOSUIT FIXINGS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
SOLID CONC.FOUNDATION EDGE DETAIL
ST 206
2017
-
SCALE 1:5
TIMBER FRAMING/STUCTURETO NZS 3604
DPCSTO uPVC VENTEDADJUSTABLE FOOT TRAY
SELECTEDFLOORING
50
NOTE:1. CONTINUOUS PERIMETER FOUNDATION
WALL WITH VENTILATION OPENINGS2. CLEARANCE BETWEEN CLADDING AND
ADJACENT GROUND - REFER NZS3604SED - Specific Engineer Design
100mm DRAPE TO DBL SIDEDPERFORATED FOIL INSUL.R = 0.9
- REFER NZBC - Clause H1
as p
er N
ZS36
04or
SE
D
as p
er N
ZS36
04or
SE
D
CGL
FGL
as per NZS3604
MA
X.H
EIG
HT
- NZS
3604
6.1
1.2
MIN
.HE
IGH
T 6.
11.2
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
CONC.CONTINOUS PERIMETER FOUND.WALL
ST 207
2017
-
DPC
WALL UNDERLAY
STOTHERM PANEL FIXING
STOTHERM PANEL
STO uPVC VENTED BASE CAP
20mm DRAINED CAVITY
STOTHERM RENDERSYSTEM
CAVITY SPACERS TO SUITFIXINGS
1. CONCRETE SLAB/REINFORCING AS PER NZS 3604, SPECIFIC DESIGN ORENGINEER (SED)
Reinforcing not shown for clarity2. WHERE INSULATION OS BELOW GROUND, APPLY TWO (2) COATS OF
STOFLEXYL TO MAXRAFT INSULATION BEFORE COMMENCING3. 150mm MIN. CLEARANCE FROM SLAB LEVEL TO EXTERIOR PAVING,
225mm MIN. CLEARANCE FROM SLAB LEVEL TO UNPAVED GROUND TOE2/AS1
4. AS REQUIRED, SECURE THE DPM TO THE MAXRAFT EDGE INSULATIONUSING AN EIFS FLASHING TAPE 50mm ON MAXRAFT AND 100MM ONTOUNDERSLAB DPM
SOLID COMPACTION 800mmMIN.PAST EDGE OFFOUNDATION
100
100
50
250 50
10450
STOMULTI SCREED MESHEDBASECOAT FINISHED IN1.0mm FLOAT or STOLIT KFINISHING RENDER,PAINTED IN STOCOLORMAXICRYL
SCALE 1:10
DPM REFER NOTE 4
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
MAXRAFT FLOOR SYSTEM / EDGE DETAIL
ST 208
2017
-
MIN. H1.2 TREATEDFLOOR JOISTS
2020
50
100mm DRAPE TODOUBLE-SIDED PERFORATED
FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1
2/NAIL LAMINATED FLOOR JOISTSUNDER LOAD BEARING WALLS
STO uPVC VENTEDADJUSTABLE FOOT TRAY
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOPOREN RENDER SYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
H4 TREATED BASEBOARDSWITH 20mm CONTINUOUS SUBFLOOR VENTILATION GAPBETWEEN
H3.2 TREATED BEARER, H5TREATED PILE - REFER NZS 3604
FOR TIMBER & PILE SETOUT
STOTHERM PANELFIXING
NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENT GROUND- REFER NZS3604
SCALE 1:5
STOTHERM RENDERSYSTEM
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
TIMBER PILE/SUBFLOOR VENTILATION (Parallel Wall)
ST 209
2017
-
50
100mm DRAPE TODOUBLE-SIDED PERFORATED
FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1
MIN. H1.2 TREATEDFLOOR JOISTSTRIMMER JOIST
2020
H4 TREATED BASEBOARDSWITH 20mm CONTINUOUS SUBFLOOR VENTILATION GAPBETWEEN
SELECTED FLOORING
TIMBER FRAMINGTO NZS 3604
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
STO uPVC VENTEDADJUSTABLE FOOT TRAY
H5 TREATED PILE - REFERNZS 3604 FOR TIMBER & PILE
SET OUT
SCALE 1:5
STOTHERM PANELFIXING
NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
TIMBER PILE/SUBFLOOR VENTILATION (Right Angled Wall)
ST 210
2017
-
SCALE 1:5
OVERHANG TRIMMER JOISTTO ALLOW CLADDING TO LAPSUBFLOOR CLADDING
100mm DRAPE TODOUBLE-SIDED PERFORATED
FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1
JACK FRAMING IN AS PERNZS3604 6.10.2
DPC
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
STOTHERM PANEL
STO uPVC VENTEDADJUSTABLE FOOT TRAY
PROVIDE SHEET BRACINGMATERIAL and VENTILATION AS PERNZS 3604
STOTHERM PANELFIXING
STOTHERM PANELFIXING
NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
TIMBER SUBFLOOR WITH JACK STUDS
ST 211
2017
-
SCALE 1:10
STO FLEXYL MESHED WATERPROOFINGFROM 150mm ABOVE GROUND ANDDOWN OVER COMPRESSION BAR
SLAB-ON-GROUND FLOOR & CONC.MASONRY WALLS AS PER NZS4210/4229/4230 & AND ENGINEERS DRAWINGS
ALLOW ADEQUATE TIME FOR BLOCK TO DRY/STABALISE BEFOREPLASTERING NORMALLY FROM 4-8 WEEKS IN AVERAGE DRYINGCONDITIONS.
STOARMAT RENDER SYSTEM
TIMBER FRAMINGTO NZS 3604
50m
mDPC
SELECTEDINTERIOR LINING
CONCRETE FLOOR SLAB,FOOTING & WALL TO SPECIFIC
DESIGN
SELECTED INTERIORRENDER/FINISH
FILTER FABRIC
SLOTTED DRAIN LAIDTO A FALL
WALL UNDERLAY
NOMINAL 20x45mm H3.1 TIMBERCAVITY BATTENSSTOTHERM PANEL FIXING
STOTHERM PANELSTOTHERM RENDER SYSTEM
STO uPVC VENTEDADJUSTABLE FOOT TRAY
NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604:2011
TANKING SEALANT
COMPRESSION BAR MECHANICALLYFIXED TO CONC.BLOCK. TRANSITIONAPPROX 100mm BELOW GROUND
GRANDULAR FILL RECOMMENDED
SELECTED BITUMOUS PEEL &STICK TANKING MEMBRANE WITHPROTECTION MATERIAL
INSULATE BLOCKWORK IFNEEDED
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
MASONRY CONC.BLOCK IN-GROUND WALL
ST 212
2017
-
SCALE 1:2
STOFLEXYL WATERPROOFING TOCONCRETE REBATE SURFACES ANDRENDER INTO REBATE
STOARMAT RENDER SYSTEM
TIMBER FRAMINGTO NZS 3604
DPC
NOTE:CUT SLOPE AT 15° OR CUTREBATE AND PLASTER 15°SLOPE IN.
WALL UNDERLAY
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
STOTHERM PANEL FIXING
STOTHERM PANEL
STO uPVC VENTED BASECAP
50m
m
REINFORCED CONCRETE BLOCKWALLS IN ACCORDANCE WITH NZS4230, 4229, 4218 & 4210
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
CONCRETE BLOCK INTER-STOREY DRAINED JUNCTION
ST 213
2017
-
NOTE: USE FULL PANELS WHERE POSSIBLE.ALL PANEL CUTS SHALL BE CAREFULLY MADE TO ACHIEVE A TIGHT BUTT FIT.ALL PANEL JOINTS MUST BE FLUSH FILLED WITH STO FOAM TAKING CARE NOT TO FILL THE CAVITY.MECHANICALLY FIX ALL PANELS WITH STOTHERM FIXINGS AT MAXIMUM 300mm CENTRES.PANELS TO BE SUPPORTED BY MINIMUM TWO STUDS OR BLOCKING.VERTICAL CONTROL JOINTS ARE REQUIRED ON WALLS OVER 20 METRES LONG, SEE STO DETAILS.HORIZONTAL CONTROL JOINTS AT INTERSTOREY JUNCTION IF UNSEASONED JOISTS USED. HORIZONTAL DRAINED JUNCTION REQUIRED AT THIRD STOREY OR 7 METERS INCLUDING GABLES.
N.T.S
600
Panel thicknessPanel thickness
STAGGERCORNERS
TO SPANMINIMUM OFTWO STUDS
FILL IN JOINERY SILLAND HEAD PANELSAFTER JAMB PANELSFITTED
AVOID NARROWPANEL WIDTHS
GENERALLY BUTT JOINPANELS ON STUDS
Equal 1200Equal
2700
H GRADE EPS SHEETS NORMALLY - 2700 x 1200mm
NOTE: USE FULL SHEETS WHERE POSSIBLEALL SHEET EDGES MUST BE SUPPORTED BY A FRAMING MEMBERALL SHEETS CUTS SHALL BE MADE CAREFULLY TO ACHIEVE A TIGHT BUTT FIT.
ANY GAPS IN THE EPS SHEET MUST BE FILLED WITH STO FOAM ON HORIZONTAL JOINTS CARE MUST BE TAKEN TO AVOID FOAM FILLING THE CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
STOTHERM PANEL LAYOUT
ST 300
2017
-
SCALE: 1:2
TIMBER FRAMING TO NZS3604 REQUIREMENTS
WALL UNDERLAY/RAB ASSPECIFIED - ENSUREUNDERLAY RUNSCONTINUOUS OVER JOINT
STOTHERM PANEL
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANEL FIXING
FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
STOTHERM PANEL FIXING VERTICAL
ST 301
2017
-
SCALE: 1:2
TIMBER FRAMING TO NZS3604 REQUIREMENTS
WALL UNDERLAY/RAB ASSPECIFIED
STOTHERM PANEL
STOTHERM RENDERSYSTEM
STOTHERM PANEL FIXING
FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY
BLOCKING/DWANGS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
STOTHERM PANEL FIXING HORIZONTAL
ST 302
2017
-
SCALE 1:2
TIMBER FRAMINGTO NZS 3604
WALL UNDERLAY/RABCONTINUOUS AROUNDCORNERS
STO PREMESHEDCORNER ANGLE
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
FLUSH FILL WITHADHESIVE FOAMTAKING CARE NOT TOFILL CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
EXTERNAL CORNER
ST 303
2017
-
SCALE: 1:2
WALL UNDERLAY/RAB CONTINUOUSAROUND CORNERS
INTERNAL CORNERS AREDOUBLE LAPPED MESHED
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STO THERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
INTERNAL CORNER
ST 304
2017
-
SCALE: 1:2
TIMBER FRAMINGTO NZS 3604
WALL UNDERLAY/RABCONTINUOUS
10mm GAP IN PANEL
NOTE:ENSURE STOTHERM PANELS ARE SUPPORTED BY A MIN. OF 2/STUDS. VERTICALCONTROL JOINTS ARE REQUIRED AT 20 LINEAL METRES MAX. OR AT ENGINEEREDFRAMING EXPANSION JOINTS and at DISSIMILAR MATERIAL JUNCTIONS. SET STOCONTROL JOINT AND REMOVE TAB CAREFULLY AS SOON AS THE JOINT IS SET TOAVOID CRACKS
IN MESHCOAT, INSTALL STO uPVCCONTROL JOINT WITH MS SEALANT
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANELFIXING
STOTHERM PANEL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
VERTICAL CONTROL JOINT
ST 305
2017
-
SCALE: 1:2
DRY or SEASONED TIMBERFRAMING TO NZS 3604 OR
PROPRIETARY FLOORJOISTS
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
WALL UNDERLAY/RAB -ENSURE UNDERLAY RUNSCONTINUOUS OVER JOINT
STOTHERM PANEL
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
NOTE: INTERSTOREY CONTROL JOINT NOT REQUIRED ON SEASONED TIMBER OR PROPRIETARY FLOOR JOISTS, CONTINUOUS CAVITY CONSTRUCTION IS LIMITEDTO TWO STORIES OR 7 METRES BEFORE A DRAINED CAVITY JUNCTION IS REQUIRED
NOTE: SEASONED (dry) TIMBER OR PROPRIETARY FLOOR JOIST DETAIL
STOTHERM PANEL FIXING
STOTHERM PANEL FIXING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
HORIZONTAL INTER-STOREY (on dry or proprietary joists)
ST 306
2017
-
SCALE: 1:2
A
A: INTERSTOREYPANEL JOINT CENTRED
1/3 WAY DOWN FROMTOP OF THE JOIST.
IN MESH COAT INSTALL STOuPVC 12mm CONTROL JOINTWITH MS SEALANT
15
10m
m G
AP
STOTHERM PANEL
STOTHERM 20mm VH CAVITYBATTENS
15mm GAP BETWEENCAVITY BATTENS
STOTHERM RENDERSYSTEM
WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT
STOTHERM PANEL
STOTHERM 20mm VH CAVITYBATTENS
STOTHERM RENDER SYSTEM
NOTE: INTERSTOREY CONTROL JOINT NOT REQUIRED ON SEASONED TIMBER OR PROPRIETARY FLOOR JOISTS. CAVITY CONSTRUCTION LIMITED TO TWO STORIES OR 7 METERS, BEFORE A DRAINED INTERSTOREY JUNCTION IS REQUIRED
NOTE: UNSEASONED TIMBER FLOOR JOIST DETAIL.
STOTHERM PANEL FIXING
STOTHERM PANEL FIXING
UNSEASONED TIMBERFLOOR FRAMING TO NZS
3604
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
HORIZONTAL INTER-STOREY CONTROL JOINT
ST 307
2017
-
STO THERM 20mm VH CAVITYBATTEN
FLASHING TAPE OVER
STO uPVC VENTEDBASE CAP
ALLOW TO RENDER BEHINDTHEN SEAL WITH MS SEALANTor STO SEAL TAPE
1. AS REQUIRED TO LIMITCONTINUOUS CAVITYCONSTRUCTION TO TWOSTOREYS OR MAX. 7METERS. FLASHING BACKAND FRONT COVER TO BEA MINIMUM 35mmEXCLUDING DRIP EDGES.
2. IN EXTRA HIGH WIND ZONEINCREASE FLASHINGCOVER TO 60mm MIN. ANDUSE A RIGID AIR BARRIER.
SCALE: 1:2
MIN
.CO
VE
R T
O B
OTT
OM
OF
CLA
DD
ING
MIN
.CO
VE
R35
mm
STOTHERM RENDER SYSTEM
STOTHERM PANEL
WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT
WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT
5
35m
m
STOTHERM FIXING
STOTHERM PANEL FIXING
DRY OR SEASONED TIMBER ORPROPRIETARY FLOOR JOISTS
100mm HORIZONTAL CAVITYBATTEN SET TO A FALL OF 5O
100mm HORIZONTAL CAVITYBATTEN SET TO A FALL OF 5O
STO uPVC 6mm FINISHING EDGE
STO uPVC END CAP
STOTHERM RENDER SYSTEM
IF NON-HEMMED FLASHINGUSED, INCREASE UPSTANDHEIGHT BY 25mm.
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DRAINED JUNCTION AT THIRD STOREY
ST 308
2017
-
SCALE 1:2
MIN. 35mm HIGHBACK FLASHING
6mm FIBRE CEMENT SOFFIT.STOARMAT RENDER FC SOFFIT& uPVC STO CLIP ON TRAYS
STOTHERM 20mmVH CAVITY BATTEN
WALL UNDERLAY
FLASHING TAPEONTO WALLUNDERLAY
5mm GAP 5mm GAP
STO uPVC VENTEDBASE CAP
STOTHERMRENDERSYSTEM
STOTHERM PANEL
STOTHERM PANELFIXING
MIN. 35mm HIGH BACK FLASHING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
BOXED BEAM
ST 309
2017
-
STOTHERM PANEL
1025
POST ANCHOR BRACKET
STOTHERM RENDERSYSTEM
STOTHERM 20mm VHCAVITY BATTEN
STOTHERMPANEL FIXING
SCALE 1:5
STO PREMESHED CORNER
STOTHERM RENDER SYSTEM
STOTHERM PANEL FIXING
H3.2 TIMBER POST
STOTHERM 20mm VHCAVITY BATTENS
25mm HIGH CONCRETEPLINTH
10mm GAP BETWEEN PANELAND CONCRETE - SLOPECONCRETE OUT
STO uPVC VENTEDBASE CAP
FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
POST DETAIL
ST 310
2017
-
100mm min.
SCALE 1:5
FLASHING TAPE
STAR CUT
CUT LINES TO SUITPIPE DIAMETER
8/10mm SEALANT BEAD ON PEF RODBETWEEN PIPE AND RENDER
PIPE OR OTHER PENETRATIONSLOPED DOWNWARDS MIN 5O
NOTE: INSTALL FLASHING TAPE WITH 100mm CLEARANCE AROUND PIPE ONTO WALLUNDERLAY AND WRAP 25mm AROUND PIPE.
WHERE MIN 75mm BLOCKING SUPPORTS THE WALL UNDERLAY AROUND THEPENETRATION THE FLASHING TAPE CAN BE OMITTED BUT A FACE FIXEDEXTERIOR FLANGE WITH SEALANT IS REQUIRED AS PER E2AS1 FIG.68
TIMBERFRAMING TO
NZS3604
STOTHERM PANEL
STOTHERM RENDER SYSTEM
STOTHERM 20mm VH CAVITYBATTEN
WALL UNDERLAY/RAB
Bottom
ADDITIONAL FLASHING TAPEWRAPPED OVER STAR CUT AROUNDPIPE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
PIPE PENETRATION DETAIL
ST 350
2017
-
SCALE 1:2
50 x 3mm EPDM WASHER GASKETSREQUIRED AROUND FIXINGS AND PLATETO PROVIDE WATERTIGHTNESS
TIMBER PACKER SLOPED AT 5°50mm min CLEARANCE FROM
CAVITY BATTENS
TIMBER BLOCKING BETWEENSTUDS AS REQUIRED
ALL WIRING SHOULD BEENCLOSED IN CONDUIT
STOTHERM PANELSTOTHERM RENDER SYSTEM
STOTHERM 20mm VH CAVITYBATTEN
WALL UNDERLAY/RAB
ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL
SLOPE CONDUIT
NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x145x60/FOUR SECTIONSPER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
LIGHT FITTING/FIXING DETAIL
ST 351
2017
-
SCALE 1:2
PROVIDE TIMBERBLOCKING AT TAP
FLASHING TAPE100mm ONTO UNDERLAY
25mm ONTO TAP CONNECTION
TAP FITTING ON EPDMRUBBER WASHER
WALL UNDERLAY
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM PLASTERSYSTEM
STOTHERM PANEL
ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL
STO QUADERBLOCK FIXING
NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x145x60/FOUR SECTIONSPER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS
MS SEALANTAROUND PIPE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
TAP FITTING/FIXING DETAIL
ST 352
2017
-
SCALE 1:2
SELECTED HANDRAIL
TIMBER PACKER AT FIXINGSPOINTS - SLOPED AT 5
DEGREES min. 50mmCLEARANCE FROM CAVITY
BATTENS
50 x 3 mm EPDM WASHER GASKETSREQUIRED AROUND FIXINGSBETWEEN PLATE AND RENDER TOPROVIDE WATERTIGHTNESSTIMBER BLOCKING
BETWEEN STUDS ASREQUIRED
100mm MAX.NZBC D1 clause 1.5.2
INSTALL HANDRAIL PLATESOVER STO RENDER SYSTEMUSING METAL BUSHES TO TAKELOAD IF REQUIRED
WALL UNDERLAY
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM RENDERSYSTEM
STOTHERM PANEL
NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x645x145x60/FOURSECTIONS PER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS
ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL
STO QUADER BLOCK FIXING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
HANDRAIL BRACKET/FIXING DETAIL
ST 353
2017
-
STO JOINT SEAL TAPEOR PEF RODMS SEALANT
POLY WEDGE OR BATTENFULL WIDTH OF METER BOX
AT min. 10° SLOPE WITHFLASHING TAPE OVER.
EXTEND WEDGE 100mmPAST SIDE OF METER BOX
LEAVE min. 50mm GAP IN CAVITYBATTEN FOR DRAINAGE
STO JOINT SEALTAPE OR PEF RODAPPLY 6mm BEAD OF MS SEALANTOVER STO JOINT SEAL TAPE TOTOP, SIDES AND BOTTOM
STOTHERM 20mm VH CAVITYBATTENS TO BE 8mm FROM
SIDES OF METERBOX
STOTHERMPANEL
SCALE 1:10
FLEXIBLE FLASHING TAPE 50mmOUT OVER THE METERBOX
PERIMETER ALL AROUND AND100mm ONTO UNDERLAY
STOTHERM uPVC END CAP
STOTHERM uPVC END CAP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
METERBOX - ISOMETRIC
ST 354
2017
-
SCALE 1:2
WEDGE OR BATTEN SLOPEDAT 10° MIN.EXTENDING INTOCAVITY
METERBOX
88
INTERNAL LINING
TIMBER FRAMINGTO NZS3604
INTERNAL LINING
TIMBER FRAMINGTO NZS3604
MS SEALANT OVER STO JOINT SEALTAPE TO PERIMETER OF METERBOX
STOTHERM RENDERSYSTEM
STOTHERM 20mm VH CAVITYBATTEN WITH 50mm GAP FROMHORIZONTAL SLOPED BATTENAT BOTTOM JUNCTION
8mm AIRSEAL ONPEF ROD BY
BUILDER
8mm AIRSEAL ONPEF ROD BY
BUILDER
FLASHING TAPE OVER SLOPEDPOLY WEDGE OR BATTEN ONTOWALL UNDERLAY
STO uPVC END CAP
METERBOX FLASHING TAPED 50mmONTO BOX AND 100mm ONTO WALL
UNDERLAY ALL ROUND
STO 6mm PRE MESHEDFINISHING EDGE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
METERBOX - CROSS SECTION
ST 355
2017
-
SCALE 1:2
uPVC OR OTHERDOWNPIPE -SIZE REFERNZBC E1 Table 5
STOTHERM 20mm VH CAVITYBATTENS
DOWNPIPE/CLIP -SADDLE @ 1.2MCTRS MAX.FIXEDINTO STO SPIRALFIXING
MS SEALANT ALL AROUND
CABLE/WIRING
PVC CONDUIT SLEEVE INSTALLEDAT 5 DEGREES DOWNWARDSLOPE
1. DOWNPIPE/CLIP - SADDLE DETAIL
2. WIRING PENETRATION DETAILNOTE: ENSURE THE NUMBER OF PENETRATIONS THROUGH THESYSTEM IS KEPT TO A MINIMUM. THE WEATHER SEALING OF ALLWIRING, ETC AS SHOWN, IS THE RESPONSIBILITY OF THE APPLICABLETRADE
STOTHERM RENDER SYSTEM
STOTHERM 20mm VHCAVITY BATTENS
TIMBER FRAMINGTO NZS3604
STOTHERM PANEL
STOTHERM RENDER SYSTEM
STO SPIRAL FIXING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
DOWNPIPE SADDLE FIXING & WIRING DETAILS
ST 356
2017
-
SCALE 1:2
EXTRACTION PIPE SLOPEDOWNWARDS AT MINIMUM 5°
FAN
CO
VE
R
TIMBER BLOCKING ASREQUIRED
NOTE:LEAVE 40mm DRAINAGE GAP IN SEALANT AT BOTTOM OF FAN COVER.INSTALL FLASHING TAPE 100mm AROUND PIPE ONTO WALL UNDERLAY AND WRAP25mm ROUND PIPE.FOR FLEXIBLE PIPES, TAPE PIPE TO FAN COVER, APPLY STO JOINT SEAL, TAPEAROUND TAPE BEFORE PLACING IN HOLE. ALWAYS FINISH RENDER BEFOREINSTALLING FAN COVER
TIMBER FRAMING ASPER NZS 3604
STOTHERM 20mm VHCAVITY BATTENS
STOTHERM PANEL
STOTHERM RENDER SYSTEM
TIMBER BLOCKING ASREQUIRED
FLEXIBLE FLASHINGTAPE
MS SEALANT TO HEAD &SIDES
MS SEALANT/PEF RODAT PIPE JUNCTION (STOSEAL TAPE ON FLEXIBLEPIPES)
STO uPVC 6mmFINISHING EDGE
STO uPVC END CAP
LEAVE 40mm GAP INSEALANT FOR EXIT OFMOISTURE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
FAN VENT DETAIL
ST 357
2017
-
PREMESHEDARCHITECTURAL PROFILEOVER INTERSTOREY JOINTFIXED OVER MESH COAT
STOTHERM RENDERSYSTEM
SCALE 1:2
A: INTERSTOREYPANEL JOINT
CENTRED 1/3 WAYDOWN FROM TOP
OF JOIST
NOTE:1. VERTICAL CAVITY BATTENS AREINSTALLED WITH A 15mm GAP ATINTER-STOREY JOINT2. INSTALL STO uPVC 12mm CONTROLJOINT3. ONLY SUITABLE FOR 2 STOREY - REFERDRAWING SHEET ST 359 FOR THIRDSTOREY4. ENSURE THERE ARE NO FIXINGS INTOFLOOR JOIST
A15
WALL UNDERLAY - ENSUREUNDERLAY RUNSCONTINUOUS OVER JOINT
STOTHERM PANEL
min.10°FALL
STOTHERMN RENDERSYSTEM
5mm GAP
STOTHERM 20mm VHCAVITY BATTEN
10°
DRY OR SEASONEDTIMBER OR
PROPRIETARY FLOORJOISTS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
INTER-STOREY JUNCTION WITH POLY PROFILE
ST 358
2017
-
STOTHERM RENDERSYSTEM
SCALE 1:2
WALL UNDERLAY -ENSURE UNDERLAY RUNSCONTINUOUS OVER JOINT
STOTHERM RENDERSYSTEM
1. AS REQUIRED TO LIMITCONTINUOUS CAVITYCONSTRUCTION TO TWOSTOREYS or 7 METERS.FLASHING BACK ANDFRONT COVER TO BE AMINIMUM 35mmEXCLUDING DRIP EDGES
2. IN EXTRA HIGH WINDZONES INCREASEFLASHING COVER TO60mm AND USE A RIGIDUNDERLAY
35m
m M
IN.
35m
m M
IN.
CO
VE
R F
RO
MB
OTT
OM
OF
PA
NE
LC
OV
ER
STOTHERM 20mm VHDRAINED CAVITYSTOTHERM PANEL
INTER-STOREYFLASHING15°MIN.SLOPEAND 5mmMIN.GAP
ADDITIONAL WALLUNDERLAY DRESSED
OVER FLASHING5
STO VENTEDBASE CAP
ATTACH WITH EPSSUITABLE ADHESIVE -TOPSIDE ONLY
STOTHERM RENDERMESHED BASECOATBEHIND PROFILE
PREMESHEDARCHITECTURALPROFILE
min.10°FALL
10°
DRY OR SEASONEDTIMBER OR PROPRIETARY
FLOOR JOISTS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
JOINT AT THIRD STOREY WITH POLY PROFILE
ST 359
2017
-
1. FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERYOPENINGS AS PER E2/AS1 DETAILS
2. STO UPVC CAVITY VENTED HEAD FLASHING CAN BE USEDWHERE A RENDERED HEAD IS DETAILED - REFER DWG PP 401
3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO60mm MIN.AND USE A RIGID UNDERLAY
4. 10mm MINIMUM HEAD FLASHING OR PROPRIETARY STOP ENDSREQUIRED
SCALE 1:2
TIMBER LINTEL ASPER NZS 3604
STOTHERM RENDERSYSTEM
STOTHERM 20mm VHCAVITY BATTEN
WALL UNDERLAY
FLASHING TAPE ONTOWALL UNDERLAY
STOTHERM PANEL
ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD
MIN. 5mm GAP REQUIRED
SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES
35m
m M
IN.
50m
m
ALUMINIUM WINDOWJOINERY
INTERIOR LINING
AIRSEAL ON PEFROD GAP
7.5-8mm APPROX
5
STO uPVC VENTEDBASE CAP
STOTHERM PANEL FIXING
HEAD FLASHING WITH 10mmSTOPENDS POSITIONED10mm PAST WINDOW JAMBS
STO STICK ON JAMBFLASHING. FINISH AT HEADFLASHING WITH PUNCHEDRENDER LEG CONTINUING30mm ABOVE
10 s
tope
nd
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ALU.JOINERY - HEAD DETAIL - STICK ON JAMB
ST 400
2017
-
SCALE 1:2
TIMBER LINTEL ASPER NZS 3604
STOTHERM RENDERSYSTEM
STOTHERM 20mm VHCAVITY BATTEN
WALL UNDERLAY
FLASHING TAPE ONTOWALL UNDERLAY
STOTHERM PANEL
ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD
MIN. 5mm GAP REQUIRED
SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES
35m
m M
IN.
50m
m
ALUMINIUM WINDOWJOINERY
INTERIOR LINING
AIRSEAL ON PEFROD GAP
7.5-8mm APPROX
1. FLASHING TAPE SYSTEM TO BE INSTALLEDAROUND JOINERY OPENINGS AS PER E2/AS1DETAILS.
2. THE ALUMINUM WINDOW HEAD FLASHING BUTTSINTO THE STO CAVITY JAMB TO PROVIDESTOPEND AFTER REMOVING THE JAMB TAB ANDFITTING TO JOINERY BEFORE FITTING WINDOWHEAD FLASHING TIGHT AND MS SEALANT THEJUNCTIONS - SEE DETAIL PP402
3. IN EXTRA HIGH WIND ZONES INCREASE FLASHINGCOVER TO 60mm MIN. AND USE A RIGID UNDERLAY
STO uPVC MESHEDDRIP EDGE
STOTHERM PANELFIXING
5
STO uPVC VENTEDHEAD FLASHING
STO CAVITY JAMBFLASHING 30mm ABOVEHEAD FLASHING FLASHINGTO FORM STOPENDS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ALU.JOINERY - HEAD DETAIL - CAVITY JAMB
ST 401
2017
-
SCALE 1:2
NOTE: OPENINGS OVER 600mm REQUIRE JOINERY SUPPORT BAR USE STO uPVC ADHESIVE SILL AND JAMB FLASHING WITH WANZ JOINERY SUPPORT BAR
JOINERY SUPPORT MUST BE CUT 15mm SHORT OF JOINERY JAMBS TO ALLOW FOR STO uPVC FLASHINGS1. SEALANT IS APPLIED TO THE SILL AND JAMB FLASHINGS2. WINDOW HEADS ARE LEFT OPEN3. FLEXIBLE FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1 DETAILS
WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.
JOINERY SUPPORT BARREQUIRE FOR OPENINGSOVER 600mm
PROPRIETARY ALUM.WINDOW JOINERY
MS SEALANT
STOTHERM RENDERSYSTEM
STOTHERM PANEL
TIMBER FRAMINGTO NZS 3604
AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.
WALL UNDERLAY RETURNEDINTO OPENINGS & FLASHINGTAPE CONTINUOUS ALONGSILL MIN 100mm UP JAMBS &50mm ONTO FACE OF WALLUNDERLAY
STOTHERM PANEL FIXING
STOTHERM 20mm VHCAVITY BATTEN
STO uPVC ADHESIVE SILLAND JAMB FLASHING.ADHESIVE FIX TO PANELAT min.15° SLOPE
STO PRE-MESHEDADJUSTABLE CORNER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ALUMINIUM JOINERY - SILL DETAIL - STICK ON SILL
ST 402
2017
-
SCALE 1:2
23 -
25m
m G
AP
10mm
20m
m C
AV
ITY
BA
TTE
N+/
- 3-5
mm
TO
ALL
OW
FOR
FLA
SH
ING
TA
PE
SA
T JO
INE
RY
ALUMINIUM WINDOWJOINERY
MS SEALANT TO JAMBS
6
FLASHING TAPE(100mm UP JAMBS)
H1.2 PACKER TOSUPPORT JOINERY
AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.
LINE OF HEAD FLASHINGBUTT INTO JAMBS TOFORM STOPENDS
WALL UNDERLAY RETURNED INTORECESS WITH FLASHING TAPE
SYSTEM. FLASHING TAPE RETURNEDmin 100mm UP JAMBS AS PER E2/AS1
STOTHERM RENDER SYSTEM
STOTHERM PANEL
STOTHERM PANEL FIXING
STOTHERM 20mm VHCAVITY BATTEN
STO uPVC CAVITY JAMBAND SILL FLASHING
STO PRE-MESHED ANGLE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ALU.JOINERY - JAMB DETAIL - STO uPVC CAVITY JAMB
ST 403
2017
-
NOTE: INSTALL STOTHERM JOINERY FLASHINGS DURING STOTHERM PANEL CONSTRUCTION
SCALE 1:2
23 -
25m
m G
AP
10mm20
mm
CA
VIT
Y B
ATT
EN
+/- 3
-5m
m T
O A
LLO
WFO
R F
LAS
HIN
G T
AP
ES
AT
JOIN
ER
Y
ALUMINIUMWINDOW JOINERY
MS SEALANT TO JAMBS
6
FLASHING TAPE(100mm UP JAMBS)
H1.2 PACKER TOSUPPORT JOINERY
AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.
LINE OF HEAD FLASHING10mm OVER WITH STOPEND
WALL UNDERLAY RETURNED INTORECESS WITH FLASHING TAPE
SYSTEM. FLASHING TAPE RETURNEDmin 100mm UP JAMBS AS PER E2/AS1
STOTHERM RENDER SYSTEM
STOTHERM PANEL
STOTHERM PANEL FIXING
STOTHERM 20mm VHCAVITY BATTEN
STO uPVC ADHESIVE SILL ANDJAMB FLASHING
STO PRE-MESHEDANGLE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ALU.JOINERY - JAMB DETAIL - STO uPVC STICK ON JAMB
ST 404
2017
-
MS SEALANT TO JAMBS
SCALE 1:2
TIMBER FRAMINGTO NZS 3604
20
FLASHING TAPE(100mm UP JAMBS)
H1.2 PACKER TOSUPPORT JOINERY
AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.
LINE OF HEAD FLASHINGOVER WITH STOPEND
STO UPVC CAVITY JAMBAND SILL FLASHINGSTOTHERM PANEL FIXING
STOTHERM 20mm VHCAVITY BATTEN
STOTHERM PANEL
STOTHERM RENDERSYSTEM
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
INT.CNR ALU.WINDOW/DOOR JOINERY - JAMB DETAIL
ST 405
2017
-
SCALE 1:5
SILL SUPPORT BAR
LINE OF CLADDINGBEYONDALUMINIUM DOORJOINERY
FLASHING TAPE TAPE OVER SILL ANDMIN. 100mm UP FRAME FINISH AT
BOTTOM EDGE OF SILL SUPPORT BAR
UNDER DOORTRIM BY BUILDER
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .GROUND LEVELS 150mm MIN.FROM TOP OF FINISHED FLOOR COVERING TOPAVED GROUND
100
SELECTED FLOORFINISH
FLASHING TAPE
CONTINUOUSAIR SEAL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ENTRY DOOR THRESHOLD DETAIL
ST 406
2017
-
SCALE 1:5
LINE OF STOTHERM PANEL CLADDINGBEYOND - SHOWN DASHED
SELECTED ALU.DOOR JOINERYINSTALLED TO MANUFACTURERSRECOMMENDATIONS
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10MIN.THRESHOLD 100mm FROM FLOOR TO FINISHED DECK
NOTE: ADJUST 35mm TO ALLOW FOR SELECTED TILES AS REQUIRED, UNDERDOOR TRIM BY BUILDER
100
35 m
in to
fini
shed
surfa
ce
SELECTED FLOORING WANZ SUPPORT BAR COMPLETE WITHVENTILATION/DRAINAGE HOLESINSTALLED TO MANUFACTURERSRECOMMENDATIONS
SELECTED MEMBRANE FINISH OVER H3 "C"FACED PLYWOOD LAID TO 1:40MIN.FALL.GLUE & SCREW TO TIMBER JOISTS, ALLEDGES SUPPORTED ON TIMBER
TIMBER STRUCTUREAS PER NZS3604
20mm MIN.ANGLE FILLET
TURN-UP FLASHINGTAPE 100mm MIN. AT
TRIMMER STUDS
MEMBRANE REINFORCING STRIP
CONTINUOUSAIR SEAL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.
STOTHERMSYSTEM
STOTHERM INSULATED FACADE SYSTEM
ENTRY DOOR/DECK THRESHOLD DETAIL
ST 407
2017
-
SCALE 1:5
WANZ SUPPORT BAR COMPLETE WITHVENTILATION/DRAINAGE HOLES,INSTALLED TO MANUFACTURERSRECOMENDATIONS
SELECTED ALU. BIFOLD DOOR JOINERYINSTALLED TO MANUFACTURERSRECOMMENDATIONS
FLASHING TAPE TAPE OVER SILL ANDMIN. 100mm UP FRAME FINISH AT
BOTTOM EDGE OF SILL SUPPORT BAR
100
8
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .150mm MIN. FROM TOP OF FFL COVERING TO PAVED GROUND
LINE OF STOTHERM CLADDINGSYSTEM BEYOND
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on