Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE 15, Safety Code for Mechanical Refrigeration and replace with ASHRAE STD 15 & 34, Safety Standard for Refrigeration Systems, 2015. (3) ANSI/ASHRAE/ASHE Standard 170 and replace with ASHRAE STD 170. Statement of Problem and Substantiation for Public Input Corresponds with PI-2 and PI-3 revisions. Related Public Inputs for This Document Related Input Relationship Public Input No. 2-NFPA 90A-2015 [Section No. 2.3] Referenced current SDO names, addresses, standard names, numbers, and editions. Public Input No. 3-NFPA 90A-2015 [Section No. C.1.2] Referenced current SDO names, addresses, standard names, numbers, and editions. Submitter Information Verification Submitter Full Name: Aaron Adamczyk Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Sun Feb 08 02:53:09 EST 2015 Committee Statement Resolution: See FR#1 National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 35 12/3/2015 7:13 AM

Upload: hoangliem

Post on 17-Apr-2018

226 views

Category:

Documents


2 download

TRANSCRIPT

Public Input No. 1-NFPA 90A-2015 [ Global Input ]

Throughout standard remove references to the following and replace with thefollowing:

(1) ANSI/UL and replace with UL.

(2) ANSI/ASHRAE 15, Safety Code for Mechanical Refrigeration and replace with ASHRAE STD 15& 34, Safety Standard for Refrigeration Systems, 2015.

(3) ANSI/ASHRAE/ASHE Standard 170 and replace with ASHRAE STD 170.

Statement of Problem and Substantiation for Public Input

Corresponds with PI-2 and PI-3 revisions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 2-NFPA 90A-2015[Section No. 2.3]

Referenced current SDO names, addresses, standard names,numbers, and editions.

Public Input No. 3-NFPA 90A-2015[Section No. C.1.2]

Referenced current SDO names, addresses, standard names,numbers, and editions.

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Feb 08 02:53:09 EST 2015

Committee Statement

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 35 12/3/2015 7:13 AM

Public Input No. 2-NFPA 90A-2015 [ Section No. 2.3 ]

2.3 Other Publications.

2.3.1 ASHRAE Publications.

American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, NE,Atlanta, GA 30329-2305.

ANSI/ ASHRAE STD 15 & 34 , Safety Code Standard for Mechanical Refrigeration Systems ,2001. 2015 . (This is an combined standard.)

ASHRAE Handbook — HVAC Systems and Equipment, 2000 2012 .

2.3.2 ASTM International Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM C 411 C411 , Standard Test Method for Hot-Surface Performance of High-Temperature ThermalInsulation, 2011.

ASTM D 93 D93 , Standard Test Methods for Flashpoint by Pensky-Martens Closed Cup Tester, 20122013 e1 .

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of Building Materials, 2013a2014 .

ASTM E 119 E119 , Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a2014 .

ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C,2012.

ASTM E 2231 E2231 , Standard Practice for Specimen Preparation and Mounting of Pipe and DuctInsulation Materials to Assess Surface Burning Characteristics, 2009 2014 .

ASTM E 2652 E2652 , Standard Test Method for Behavior of Materials in a Tube Furnace with aCone-Shaped Airflow Stabilizer, at 750°C, 2012.

2.3.3 GA Publications.

Gypsum Association, 6525 Belcrest Road, Suite 480, Hyattsville, MD 20782.

GA 600, Fire Resistance Design Manual Sound Control , 19th 12 th edition, 2009 2012 .

2.3.4 NAIMA Publications.

North American Insulation Manufacturers Association, 44 11 Canal Center Plaza, Suite 310 103 ,Alexandria, VA 22314.

NAIMA AH116 Fibrous Glass Duct Construction Standards , 5th edition, 2002.

2.3.5 SMACNA Publications.

Sheet Metal and Air Conditioning Contractors' National Association, 4201 Lafayette Center Drive, Chantilly,VA 20151-1209.

Fibrous Glass Duct Construction Standards, 7th edition, 2003.

HVAC Air Duct Leakage Test Manual, 1st 2nd edition, 1985 2012 .

HVAC Duct Construction Standards — Metal and Flexible, 3rd edition, 2005.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 35 12/3/2015 7:13 AM

2.3.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/ UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2013.

ANSI/ UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2013.

ANSI/ UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors,2013.

ANSI/ UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, Revised 2014 .

ANSI/ UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 201 4 .ANSI/

UL 555C, Standard for Safety Ceiling Dampers, 2006, Revised 2010 2014 .

ANSI/ UL 555S, Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

ANSI/ UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2013.

ANSI/ UL 867, Standard for Safety Electrostatic Air Cleaners, 2011, Revised 2013.

ANSI/ UL 900,Standard for Safety Air Filter Units, 2004, Revised 2012.

ANSI/ UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics,2004, Revised 2013.

ANSI/ UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics, 2004, Revised 2013.

ANSI/ UL 1995, Standard for Safety Heating and Cooling Equipment, 2011, Revised 2014 .ANSI/

UL 2024,Standard for Signaling, Optical Fiber Cable Routing Assemblies and CommunicationsRaceways and Cable Routing Assemblies , 2011, Revised 2015 .

ANSI/ UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Productsand Their Accessories Installed in Air-Handling Spaces, 2008 2013 .

UL 2518, Outline of Investigation for Air Dispersion System Materials, 2005.

2.3.7 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

Statement of Problem and Substantiation for Public Input

Referenced current SDO addresses, standard names, numbers, and editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 1-NFPA 90A-2015 [Global Input]

Public Input No. 3-NFPA 90A-2015 [Section No. C.1.2]

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Feb 08 03:02:56 EST 2015

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 35 12/3/2015 7:13 AM

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 35 12/3/2015 7:13 AM

Public Input No. 10-NFPA 90A-2015 [ Section No. 2.3.2 ]

2.3.2 ASTM International Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM C 411 C411 , Standard Test Method for Hot-Surface Performance of High-Temperature ThermalInsulation, 2011.

ASTM D 93 D93 , Standard Test Methods for Flashpoint by Pensky-Martens Closed Cup Tester,2012 2015 .

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of Building Materials,2013a 2015a .

ASTM E 119 E119 , Standard Test Methods for Fire Tests of Building Construction and Materials,2012a 2014 .

ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C,2012.

ASTM E 2231 E2231 , Standard Practice for Specimen Preparation and Mounting of Pipe and DuctInsulation Materials to Assess Surface Burning Characteristics, 2009 2015 .

ASTM E 2652 E2652 , Standard Test Method for Behavior of Materials in a Tube Furnace with aCone-Shaped Airflow Stabilizer, at 750°C, 2012.

Statement of Problem and Substantiation for Public Input

standards date update

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sat Apr 25 10:43:38 EDT 2015

Committee Statement

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 35 12/3/2015 7:13 AM

Public Input No. 29-NFPA 90A-2015 [ Section No. 2.3.6 ]

2.3.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2013.

ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2013.

ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors,2013.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, Revised 2014 .

ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 2014 .

ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2006, Revised 2010 2014 .

ANSI/UL 555S, Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2013.

ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2011, Revised 2013.

ANSI/UL 900, Standard for Safety Air Filter Units, 2004, Revised 2012.

ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics,2004, Revised 2013.

ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics, 2004, Revised 2013.

ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2011 2015 .

ANSI/UL 2024, Standard for Signaling, Optical Fiber and Communications Raceways and Cable RoutingAssemblies, 2011 2015 .

ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products andTheir Accessories Installed in Air-Handling Spaces, 2008 2013 .

UL 2518, Outline of Investigation for Air Dispersion System Materials, 2005.

Statement of Problem and Substantiation for Public Input

The proposed changes updated UL Standards to the most recent edition.

Submitter Information Verification

Submitter Full Name: RONALD FARR

Organization: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 09:15:46 EDT 2015

Committee Statement

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 35 12/3/2015 7:13 AM

Public Input No. 43-NFPA 90A-2015 [ Section No. 2.3.6 ]

2.3.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2013.

ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2013.

ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors,2013.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, Revised 2015 .

ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 2014 .

ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2006, Revised 2010 2014 .

ANSI/UL 555S, Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2013.

ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2011, Revised 2013.

ANSI/UL 900, Standard for Safety Air Filter Units, 2004, 2015.

ANSI/UL 1598, Luminaires, 2008, Revised 2012.

ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics,2004, Revised 2013.

ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics, 2004, Revised 2013.

ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2011.

ANSI/UL 2024, Standard for Signaling, Optical Fiber and Communications Raceways and Cable RoutingAssemblies, 2011 2014, Revised 2015 ..

ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products andTheir Accessories Installed in Air-Handling Spaces, 2008 2013 .

UL 2518, Outline of Investigation for Air Dispersion System Materials, 2005.

ANSI/UL 2846, Fire Test of Plastic Water Distribution Plumbing Pipe for Visible Flame and SmokeCharacteristics , 2014

Statement of Problem and Substantiation for Public Input

This proposal provides updates to referenced UL standards. Also, ANSI/UL 2846 and ANSI/UL 1598 are added due to related Public Inputs 38, 39, and 40.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 38-NFPA 90A-2015 [Section No. 4.3.11.2.6.6] Proposes UL 2846

Public Input No. 39-NFPA 90A-2015 [Section No. 4.3.11.5.5.7] Proposes UL 2846

Public Input No. 40-NFPA 90A-2015 [Section No. 4.3.11.2.2] Proposes UL 1381

Submitter Information Verification

Submitter Full Name: John Taecker

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 35 12/3/2015 7:13 AM

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 16:04:55 EDT 2015

Committee Statement

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 35 12/3/2015 7:13 AM

Public Input No. 6-NFPA 90A-2015 [ Section No. 2.3.6 ]

2.3.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2013.

ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2013.

ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors,2013.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011.

ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012.

ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2006, Revised 2010.

ANSI/UL 555S, Standard for Safety Smoke Dampers, 1999, Revised 2012.

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2013.

ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2011, Revised 2013.

ANSI/UL 900, Standard for Safety Air Filter Units, 2004, Revised 2012.

ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics,2004, Revised 2013.

ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics, 2004, Revised 2013.

ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2011.

ANSI/UL 2024, Standard for Signaling, Optical Fiber STANDARD FOR SAFETY, Cable RoutingAssemblies and Communications Raceways and Cable Routing Assemblies , 2011 2015 .

ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products andTheir Accessories Installed in Air-Handling Spaces, 2008.

UL 2518, Outline of Investigation for Air Dispersion System Materials, 2005.

Statement of Problem and Substantiation for Public Input

UL 2024 has been revised and reissued. The fifth edition was initially issued on March 24, 2014 and then revised and reissued on January 9, 2015. Signaling and optical fiber raceways were dropped from the standard to correlate with the 2014 edition of the National Electrical Code (NFPA 70). The 2015 edition of UL 2024 has been revised to correlate with the testing requirements in sections 4.3.11.2.6 and 4.3.11.5.5 of NFPA 90A-2015.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 7-NFPA 90A-2015 [Section No. 4.3.11.2.6.4]

Public Input No. 8-NFPA 90A-2015 [Section No. 4.3.11.5.5.4]

Public Input No. 9-NFPA 90A-2015 [Section No. 4.3.11.5.5.5]

Submitter Information Verification

Submitter Full Name: DAVID KIDDOO

Organization: CCCA

Affilliation: CCCA

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 35 12/3/2015 7:13 AM

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 12 10:36:14 EDT 2015

Committee Statement

Resolution: See FR#1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 35 12/3/2015 7:13 AM

Public Input No. 36-NFPA 90A-2015 [ New Section after 4.3.1.2 ]

4.3.1.2.1

The requirement of 4.3.1.2 that vertical ducts serve not more than two adjacent stories in height shall notapply to phenolic duct constructed to ANSI/SMACNA 2015 Phenolic Duct Construction Standards.

Statement of Problem and Substantiation for Public Input

Creates a new section to accommodate phenolic ducts, a new air distribution material and the corresponding new industry consensus standard, ANSI/SMACNA 2015 Phenolic Duct Construction Standards. Phenolic ducts, when constructed vertically and when constructed to ANSI/SMACNA 2015 Phenolic Duct Construction Standards do not have limitations of not more than two adjacent stories in height.

Submitter Information Verification

Submitter Full Name: ELI HOWARD

Organization: SHEET METAL AIR CONDITIONING

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:14:41 EDT 2015

Committee Statement

Resolution: No data was submitted to support allowing these ducts or any UL 181 Class 0 or Class 1 ducts toexceed two stories in height. The committee suggests that such data be submitted at the commentstage.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 35 12/3/2015 7:13 AM

Public Input No. 35-NFPA 90A-2015 [ Section No. 4.3.1.2 ]

4.3.1.2

Class 0 or Class 1 rigid or flexible air ducts tested in accordance with ANSI/UL 181, Standard for SafetyFactory-Made Air Ducts and Air Connectors, and installed in conformance with the conditions of listing shallbe permitted to be used for ducts where air temperature in the ducts does not exceed 121°C (250°F) orwhere used as vertical ducts serving not more than two adjacent stories in height unless otherwisespecified in 4 .3.1.2.1.

Statement of Problem and Substantiation for Public Input

Added language creates a new section to accommodate recognition of phenolic ducts, a new air distribution material.

Submitter Information Verification

Submitter Full Name: ELI HOWARD

Organization: SHEET METAL AIR CONDITIONING

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:12:04 EDT 2015

Committee Statement

Resolution: See the committee's response to PI-36

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 35 12/3/2015 7:13 AM

Public Input No. 37-NFPA 90A-2015 [ Section No. 4.3.1.5.1 ]

4.3.1.5.1

Air ducts shall be considered to be in compliance with 4.3.1.5 where constructed and installed inaccordance with the ASHRAE Handbook — HVAC Systems and Equipment and with one with one of thefollowing as applicable:

(1) NAIMA Fibrous Glass Duct Construction Standards

(2) SMACNA Fibrous Glass Duct Construction Standards

(3) SMACNA HVAC Duct Construction Standards — Metal and Flexible

(4) SMACNA HVAC Air Duct Leakage Test Manual

Statement of Problem and Substantiation for Public Input

The ASHRAE Handbook & HVAC Systems Equipment are not industry consensus based documents. Neither provides the technical and tested data to provide a fully compliant air distribution system, nor are either applicable to any reference or use in the Model Building Codes (ICC, IAPMO, NFPA 500, etc.)

Submitter Information Verification

Submitter Full Name: ELI HOWARD

Organization: SHEET METAL AIR CONDITIONING

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:18:47 EDT 2015

Committee Statement

Resolution: The committee finds that this language is very awkward and not ready for approval. The committeesuggests that the submitter rework the language and submit it at the public comment stage.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 35 12/3/2015 7:13 AM

Public Input No. 31-NFPA 90A-2015 [ Section No. 4.3.2.1 ]

4.3.2.1

Air connectors are limited-use, flexible air ducts that shall not be required to conform to the provisions forair ducts where they meet the requirements of 4.3.2.1.1 through 4.3.2.1.5 6 .

4.3.2.1.1

Air connectors shall conform to the requirements for Class 0 or Class 1 connectors when tested inaccordance with ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors.

4.3.2.1.2

Class 0 or Class 1 air connectors shall not be used for ducts containing air at temperatures in excess of121°C (250°F).

4.3.2.1.3

Air connector runs shall not exceed 4.27 m (14 ft) in length.

4.3.2.1.4

Air connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required tohave a fire resistance rating of 1 hour or more.

4.3.2.1.5

Air connectors shall not pass through floors.

4.3.2.1.6

An air connector shall not be interrupted by a short collar or any other fitting on one side and thenconnected to another air connector on the other side when penetrating (a) a floor or (b) a wall, partition orenclosure of a vertical shaft that is required to have a fire resistance rating of 1 hour.

Statement of Problem and Substantiation for Public Input

The requirement that “Air Connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required to have a fire resistance rating of 1 hour or more” and “Air Connectors shall not pass through floors” is not sufficiently clear.

The confusion comes in understanding exactly what is considered “passing through”? ASHRAE’s TC 5.2’s Codes & Standards Interaction Sub-Committee extensively discussed this in meetings recently and they plan to request an interpretation from NFPA 90A & 90B about this.

It is known that Air Connectors are being used to transport air up to the plane of a floor or wall, then interrupted by a short collar or other metal fitting, and then continued on the opposite side. Many inspectors consider this as “not passing through” and thus are allowing it to be done. This should not be acceptable to NFPA 90A or 90B.

It is also known that Air Connectors are being used in basement applications where the ceiling is then finished out in gypsum board. Is this considered acceptable? In what plane is the “passing through” limitation considered? Can an Air Connector pass through floors in the horizontal plane?

It is important that the correct information is provided to users of NFPA 90A & 90B. It seems that some clarification is needed for this important aspect of Air Connector use limitation to be properly understood and conveyed.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 35 12/3/2015 7:13 AM

City:

State:

Zip:

Submittal Date: Thu Jul 02 16:35:10 EDT 2015

Committee Statement

Resolution: See FR#2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 35 12/3/2015 7:13 AM

Public Input No. 40-NFPA 90A-2015 [ Section No. 4.3.11.2.2 ]

4.3.11.2.2

Light diffusers, other than those made of metal or glass, used in air-handling light fixtureshandling luminaires shall be listed in accordance with ANSI/UL 1598, Luminaires , and marked“Fixture “ Light Diffusers for Air-Handling Fixtures Luminaires .”

Statement of Problem and Substantiation for Public Input

The international term for a lighting fixture is luminaire and is defined as a complete lighting unit consisting of a lamp or lamps together with the parts designed to distribute the light, to position and protect the lamps, and to connect the lamps to the power supply. The term “light fixture” was replaced with the term “luminaire” in the National Electrical Code (NFPA 70) in the 2002 edition. The terminology for this type of product should be consistent in all of the NFPA codes and standards. UL 1598 is the standard used to list the light diffusers used for air-handling luminaires.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 43-NFPA 90A-2015 [Section No. 2.3.6]

Submitter Information Verification

Submitter Full Name: John Taecker

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:28:09 EDT 2015

Committee Statement

Resolution: FR-3-NFPA 90A-2015

Statement: The international term for a lighting fixture is luminaire and is defined as a complete lighting unitconsisting of a lamp or lamps together with the parts designed to distribute the light, to position andprotect the lamps, and to connect the lamps to the power supply. The term “light fixture” was replacedwith the term “luminaire” in the National Electrical Code (NFPA 70) in the 2002 edition. Theterminology for this type of product should be consistent in all of the NFPA codes and standards. UL1598 is the standard used to list the light diffusers used for air-handling luminaires.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 35 12/3/2015 7:13 AM

Public Input No. 7-NFPA 90A-2015 [ Section No. 4.3.11.2.6.4 ]

4.3.11.2.6.4

Signaling, optical fiber, and communications Commmunications raceways shall be listed as having amaximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximumflame spread distance of 1.5 m (5 ft) or less when tested in accordance with ANSI/UL 2024,Standard forSignaling, Optical Fiber STANDARD FOR SAFETY, Cable Routing Assemblies and Communications Raceways

and Cable Routing Assemblies, 2015 . Cables installed within these raceways shall be listed as plenum cable in accordance with therequirements in 4.3.11.2.6.1 .

Statement of Problem and Substantiation for Public Input

Signaling and optical fiber raceways were dropped from the 2014 edition of the National Electrical Code (NFPA 70) and replaced with communications raceways. UL 2024 has been revised; part of the revision is a change in the title of the standard.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 6-NFPA 90A-2015 [Section No. 2.3.6]

Public Input No. 8-NFPA 90A-2015 [Section No. 4.3.11.5.5.4]

Public Input No. 9-NFPA 90A-2015 [Section No. 4.3.11.5.5.5]

Submitter Information Verification

Submitter Full Name: DAVID KIDDOO

Organization: CCCA

Affilliation: CCCA

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 12 10:39:27 EDT 2015

Committee Statement

Resolution: FR-4-NFPA 90A-2015

Statement: Signaling and optical fiber raceways were dropped from the 2014 edition of the National ElectricalCode (NFPA 70) and replaced with communications raceways. UL 2024 has been revised; part of therevision is a change in the title of the standard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 35 12/3/2015 7:13 AM

Public Input No. 38-NFPA 90A-2015 [ Section No. 4.3.11.2.6.6 ]

4.3.11.2.6.6

Plastic piping and tubing used in plumbing systems shall be permitted to be used within a ceiling cavityplenum if it exhibits a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials, at full width of the tunnel and with no water or any other liquid in the pipe during the test.

Exception: Plastic water distribution piping and tubing listed as having a maximum peak optical density of0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.5 m (5 ft)or less when tested in accordance with ANSI/UL 2846, Fire Test of Plastic Water Distribution PlumbingPipe for Visible Flame and Smoke Characteristics , and installed in accordance with its listing, shall bepermitted to be used within a ceiling cavity plenum.

Statement of Problem and Substantiation for Public Input

This proposal allows an option for water distribution piping and tubing to be listed to the UL 2846 criteria noted. UL 2846 is an ANSI standard that includes a test method for determining values of flame propagation distance and optical smoke density for individual pairs of plastic plumbing pipes for distribution of potable water that can be installed in ducts, plenums, and other spaces used for environmental air. The scope of this standard can be viewed at http://ulstandards.ul.com/standard/?id=2846. The acceptance criteria specified (peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread distance not greater than 5 feet) is consistent with values in Sections 4.3.11.2.6.1 through 4.3.11.2.6.4.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 43-NFPA 90A-2015 [Section No. 2.3.6]

Submitter Information Verification

Submitter Full Name: John Taecker

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:22:29 EDT 2015

Committee Statement

Resolution: FR-5-NFPA 90A-2015

Statement: This proposal allows an option for water distribution piping and tubing to be listed to the UL 2846criteria noted. UL 2846 is an ANSI standard that includes a test method for determining values offlame propagation distance and optical smoke density for individual pairs of plastic plumbing pipes fordistribution of potable water that can be installed in ducts, plenums, and other spaces used forenvironmental air. The scope of this standard can be viewed at http://ulstandards.ul.com/standard/?id=2846. The acceptance criteria specified (peak optical density not greater than 0.50, an averageoptical density not greater than 0.15, and a flame spread distance not greater than 5 feet) isconsistent with values in Sections 4.3.11.2.6.1 through 4.3.11.2.6.4.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 35 12/3/2015 7:13 AM

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 35 12/3/2015 7:13 AM

Public Input No. 8-NFPA 90A-2015 [ Section No. 4.3.11.5.5.4 ]

4.3.11.5.5.4

Signaling, optical fiber, and communications Communications raceways shall be listed as having amaximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximumflame spread distance of 1.5 m (5 ft) or less when tested in accordance with ANSI/UL 2024, Standard forSignaling, Optical Fiber STANDARD FOR SAFETY, Cable Routing Assemblies and CommunicationsRaceways and Cable Routing Assemblies , 2015 . Cables installed within these raceways shall be listedas plenum cable in accordance with the requirements in 4.3.11.5.5.1.

Statement of Problem and Substantiation for Public Input

Signaling and optical fiber raceways were dropped from the 2014 edition of the National Electrical Code (NFPA 70) and replaced with communications raceways. UL 2024 has been revised; part of the revision is a change in the title of the standard.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 6-NFPA 90A-2015 [Section No. 2.3.6]

Public Input No. 7-NFPA 90A-2015 [Section No. 4.3.11.2.6.4]

Public Input No. 9-NFPA 90A-2015 [Section No. 4.3.11.5.5.5]

Submitter Information Verification

Submitter Full Name: DAVID KIDDOO

Organization: CCCA

Affilliation: CCCA

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 12 10:43:24 EDT 2015

Committee Statement

Resolution: FR-6-NFPA 90A-2015

Statement: Signaling and optical fiber raceways were dropped from the 2014 edition of the National ElectricalCode (NFPA 70) and replaced with communications raceways. UL 2024 has been revised; part of therevision is a change in the title of the standard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 35 12/3/2015 7:13 AM

Public Input No. 9-NFPA 90A-2015 [ Section No. 4.3.11.5.5.5 ]

4.3.11.5.5.5

Raised floors, intermachine cables, electrical wires, listed plenum optical fiber, communications andsignaling communications raceways, and optical-fiber cables in computer/data processing rooms wherethese rooms are designed and installed in accordance with NFPA 75, Standard for the Protection ofInformation Technology Equipment, shall be permitted.

Statement of Problem and Substantiation for Public Input

Signaling and optical fiber raceways were dropped from the 2014 edition of the National Electrical Code (NFPA 70) and replaced with communications raceways.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 6-NFPA 90A-2015 [Section No. 2.3.6]

Public Input No. 7-NFPA 90A-2015 [Section No. 4.3.11.2.6.4]

Public Input No. 8-NFPA 90A-2015 [Section No. 4.3.11.5.5.4]

Submitter Information Verification

Submitter Full Name: DAVID KIDDOO

Organization: CCCA

Affilliation: CCCA

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 12 10:45:55 EDT 2015

Committee Statement

Resolution: FR-7-NFPA 90A-2015

Statement: Signaling and optical fiber raceways were dropped from the 2014 edition of the National ElectricalCode (NFPA 70) and replaced with communications raceways.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 35 12/3/2015 7:13 AM

Public Input No. 39-NFPA 90A-2015 [ Section No. 4.3.11.5.5.7 ]

4.3.11.5.5.7

Plastic piping and tubing used in plumbing systems shall be permitted to be used within a raised floorplenum if it exhibits a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials, at full width of the tunnel and with no water or any other liquid in the pipe during the test.

Exception: Plastic water distribution piping and tubing listed as having a maximum peak optical density of0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.5 m (5 ft)or less when tested in accordance with ANSI/UL 2846, Fire Test of Plastic Water Distribution PlumbingPipe for Visible Flame and Smoke Characteristics , and installed in accordance with its listing, shall bepermitted to be used within a raised floor plenum.

Statement of Problem and Substantiation for Public Input

Reason: This proposal allows an option for water distribution piping and tubing to be listed to the UL 2846 criteria noted. UL 2846 is an ANSI standard that includes a test method for determining values of flame propagation distance and optical smoke density for individual pairs of plastic plumbing pipes for distribution of potable water that can be installed in ducts, plenums, and other spaces used for environmental air. The scope of this standard can be viewed at http://ulstandards.ul.com/standard/?id=2846. The acceptance criteria specified (peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread distance not greater than 5 feet) is consistent with values in Sections 4.3.11.5.5.1 through 4.3.11.5.5.4.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 43-NFPA 90A-2015 [Section No. 2.3.6]

Submitter Information Verification

Submitter Full Name: John Taecker

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:25:11 EDT 2015

Committee Statement

Resolution: FR-8-NFPA 90A-2015

Statement: Reason: This proposal allows an option for water distribution piping and tubing to be listed to the UL2846 criteria noted. UL 2846 is an ANSI standard that includes a test method for determining valuesof flame propagation distance and optical smoke density for individual pairs of plastic plumbing pipesfor distribution of potable water that can be installed in ducts, plenums, and other spaces used forenvironmental air. The scope of this standard can be viewed at http://ulstandards.ul.com/standard/?id=2846. The acceptance criteria specified (peak optical density not greater than 0.50, an averageoptical density not greater than 0.15, and a flame spread distance not greater than 5 feet) isconsistent with values in Sections 4.3.11.5.5.1 through 4.3.11.5.5.4.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 35 12/3/2015 7:13 AM

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 35 12/3/2015 7:13 AM

Public Input No. 44-NFPA 90A-2015 [ Section No. 4.3.11.6.2 ]

4.3.11.6.2

Foam plastic insulation shall not be used as wall or ceiling finish in plenums unless the insulation meetsany one of the criteria shown in 4.3.11.6.2.1,through 4.3.11.6.2.2 , or 4. 3.11.6.2.3.

4.3.11.6.2.1

The foam plastic insulation material shall exhibit a flame spread index of 25 or less and a smoke developedindex of 50 or less when tested in accordance with ASTM E 84 E84 , Standard Test Method for SurfaceBurning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials, at the maximum thickness intended for use, and shall also complywith the following criteria, when tested in accordance with NFPA 286, Standard Methods of Fire Tests forEvaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth ( where the testng shall beperformed on the finished foam plastic assembly related to the actual end-use configuration and on themaximum thickness intended for use) :

(1) Flame does not spread to the ceiling during the 40 kW exposure.

(2) Flame does not spread to the outer extremities of the sample.

(3) Flashover, based on the criteria from NFPA 286, does not occur.

(4) The peak heat release rate does not exceed 800 kW.

(5) The total smoke release does not exceed 1000 m2 (1196 yd2) when tested in accordance with NFPA286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish toRoom Fire Growth (where the testing shall be performed on the finished foam plastic assemblyrelated to the actual end-use configuration and on the maximum thickness intended for use) .

4.3.11.6.2.2

The foam plastic insulation material shall be covered by corrosion-resistant steel having a base metalthickness of not less than 0.4 mm (0.0160 in.) and shall exhibit a flame spread index of 75 or less and asmoke developed index of 450 or less when tested in accordance with ASTM E 84 E84 , Standard TestMethod for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test forSurface Burning Characteristics of Building Materials, at the maximum thickness intended for use.

4.3.11.6.2.3

The foam plastic insulation material shall be separated from the plenum by an approved thermal barrierconsisting of 12.7 mm (0.5 in.) gypsum wallboard or a material that is tested in accordance with and meetsthe acceptance criteria of both the temperature transmission fire test and the integrity fire test of NFPA 275,Standard Method of Fire Tests for the Evaluation of Thermal Barriers Used Over Foam Plastic Insulation,and shall exhibit a flame spread index of 75 or less and a smoke developed index of 450 or less whentested in accordance with ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics ofBuilding Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials, at the maximum thickness intended for use.

4.3.11.6.2.4

The foam plastic insulation material shall be separated from the plenum by not less than 25.4 mm (1.0 in.)of masonry or concrete and shall exhibit a flame spread index of 75 or less and a smoke developed indexof 450 or less when tested in accordance with ASTM E84, Standard Test Method for Surface BurningCharacteristics of Building Materials , or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials , at the maximum thickness intended for use.

Statement of Problem and Substantiation for Public Input

This public input does three things.

1. It clarifies that it is unnecessary to test a barrier that is masonry or concrete at 1 inch or more in thickness to

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 35 12/3/2015 7:13 AM

assess whether it complies with NFPA 275. Clearly such a thickness of concrete will be at least as good a thermal barrier as 1/2 inch gypsum board. Some users were demanding NFPA 275 testing.

2. The reference to NFPA 286 is being moved to where it belongs, in the charging paragraph, because items 1 through 5 are based on testing to NFPA 286 and not testing to ASTM E84.

3. The criteria for flashover need to be those from NFPA 286.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 16:34:45 EDT 2015

Committee Statement

Resolution: FR-9-NFPA 90A-2015

Statement: This public input does three things.

1. It clarifies that it is unnecessary to test a barrier that is masonry or concrete at 1 inch or more inthickness to assess whether it complies with NFPA 275. Clearly such a thickness of concrete will beat least as good a thermal barrier as 1/2 inch gypsum board. Some users were demanding NFPA 275testing.

2. The reference to NFPA 286 is being moved to where it belongs, in the charging paragraph,because items 1 through 5 are based on testing to NFPA 286 and not testing to ASTM E84.

3. The criteria for flashover need to be those from NFPA 286.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 35 12/3/2015 7:13 AM

Public Input No. 28-NFPA 90A-2015 [ Section No. 5.4.5.4 [Excluding any Sub-Sections] ]

Dampers Where an air handling system is designed to operate during a fire event, dampers shall closeagainst the maximum calculated airflow of that portion of the air duct system in which they are installed.

Statement of Problem and Substantiation for Public Input

Some interpret the section to require dynamic fire dampers when an air handling system is designed to shut down during a fire event. This change will help clarify that, where a system is designed to shut down during a fire event (duct detector in discharge), no dynamic fire dampers are required. Another option would be to add an annex note if this verbiage is not acceptable.

Submitter Information Verification

Submitter Full Name: PETER LARRIMER

Organization: US DEPARTMENT OF VETERANS AFFA

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 25 14:26:14 EDT 2015

Committee Statement

Resolution: The committee finds that there is insufficient justification for this change. The committee intends for allrequired dampers to work against any system pressure.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 35 12/3/2015 7:13 AM

Public Input No. 32-NFPA 90A-2015 [ Section No. 6.4.3.1 ]

6.4.3.1

Smoke detectors provided as required by 6.4.2 shall automatically stop and instantaneously stop theirrespective fan(s) on detecting the presence of smoke.

Statement of Problem and Substantiation for Public Input

With the introduction of automated energy management systems it is possible to have extensive time delays inherent to shutting down air handlers. Currently there is no maximum time specified to which fans must stop upon detection of smoke. Time durations in excess of 60-90 seconds have been observed in order to have a sequential and orderly shut down for the protection of the equipment. In a fire/smoke condition the air handler is the threat and should NOT be protected at the risk of the building occupants, first responders, or the protected property itself. Perhaps the Technical Committee would be more familiar with using the term “shunt” rather than “stop” which implies instantaneous shut down. The TC may also be more comfortable adding a time limit for the shut off.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Sat Jul 04 16:12:40 EDT 2015

Committee Statement

Resolution: The committee finds that this wording is not practicable or even possible to achieve.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 35 12/3/2015 7:13 AM

Public Input No. 33-NFPA 90A-2015 [ Section No. 7.2 ]

7.2 * Fire Dampers, Smoke Dampers, and Ceiling Dampers.

All fire dampers, smoke dampers, and ceiling dampers shall be operated prior via the finished access doorwhen provided, prior to the occupancy of a building to determine that they function in accordance with therequirements of this standard and are accessible for inspection, testing and maintenance .

Statement of Problem and Substantiation for Public Input

To ensure that adequate access is provided for proper inspection, testing and maintenance. See related PI to A7.2.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 34-NFPA 90A-2015 [Section No. A.7.2]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Sat Jul 04 16:20:05 EDT 2015

Committee Statement

Resolution: FR-11-NFPA 90A-2015

Statement: The committee changes provide clearer language in order to ensure that adequate access is providedfor proper inspection, testing and maintenance.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 35 12/3/2015 7:13 AM

Public Input No. 41-NFPA 90A-2015 [ New Section after A.4.3.3.1 ]

TITLE OF NEW CONTENT

Type your content here ...

A.4.3.3.2 Aerosol duct sealants for use with sheet metal ducts are not addressed within the scope ofANSI/UL181A or ANSI/UL181B, Aerosol duct sealants intended for use with sheet metal ducts areaddressed by UL1381, Outline of Investigation for Aerosol Duct Sealant .

Statement of Problem and Substantiation for Public Input

Aerosol duct sealants are intended to seal minor holes and gaps within sheet-metal air ducts fabricated and installed in accordance with ANSI/SMACNA "HVAC Duct Construction Standards - Metal and Flexible.". UL 1381, Outline of Investigation for Aerosol Duct Sealant, provides requirements to evaluate these sealants for this application, including surface burning characteristics, mold growth and humidity, erosion, interior duct burning, leakage reduction, and durability. These tests are based on requirements in ANSI/UL 181, ANSI/UL 181A, ANSI/UL 181B and ASTM E2342. UL 1381 requirements are limited to application in ducts with individual openings no greater than 5/8 in. diameter, and seam/joint openings no greater than 5/8 in. across. These sealants are not intended for use as a substitute or to supplement mechanical attachment in the sheet-metal duct systems. These sealants are not intended for use with rigid fiberglass ducts, flexible-wire helix ducts, or spirally wound metal ducts not complying with SMACNA Standards.Aerosol duct sealants are intended to be applied by trained professionals and specifically in accordance with accompanying installation instructions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 42-NFPA 90A-2015 [Section No. C.1.2.6]

Submitter Information Verification

Submitter Full Name: John Taecker

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:32:37 EDT 2015

Committee Statement

Resolution: Not needed. See FR#10

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 35 12/3/2015 7:13 AM

Public Input No. 34-NFPA 90A-2015 [ Section No. A.7.2 ]

A.7.2

See NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives, for testingrequirements for smoke dampers and combination fire and smoke dampers. See NFPA 80, Standard forFire Doors and Other Opening Protectives, for testing requirements for fire dampers. AMCA International’sGuide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety RelatedDampers provides guidelines from damper manufacturers on how to test dampers for acceptance testingand for follow-up periodic testing. The testing should be performed under normal conditions therefore therequirement has been added to test them via any access doors to ensure that they are truly accessible forservice.

Statement of Problem and Substantiation for Public Input

To ensure that adequate access is provided for proper inspection, testing and maintenance. See related PI to Section 7.2.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 33-NFPA 90A-2015 [Section No. 7.2]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Sat Jul 04 16:23:10 EDT 2015

Committee Statement

Resolution: See FR#11

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 35 12/3/2015 7:13 AM

Public Input No. 3-NFPA 90A-2015 [ Section No. C.1.2 ]

C.1.2 Other Publications.

C.1.2.1 ASHRAE Publications.

American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, NE,Atlanta, GA 30329-2305.

ANSI/ASHRAE/ASHE Standard ASHRAE STD 170, Ventilation of Health Care Facilities, 2008, withapproved addendum. 2013, 2014 Errata. .

ASHRAE Handbook — Fundamentals, 2009 2013 .

C.1.2.2 AMCA Publications.

Air Movement and Control Association (AMCA), 30 West University Drive, Arlington Heights, IL 60004.

Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety RelatedDampers, 2011.

C.1.2.3 ASTM International Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2013a 2015 .

ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C, 2012.

ASTM E 2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct InsulationMaterials to Assess Surface Burning Characteristics, 2009 2014 .

ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-ShapedAirflow Stabilizer, at 750°C, 2012.

C.1.2.4 NAIMA Publications.

North American Insulation Manufacturers Association, 44 11 Canal Center Plaza, Suite 310 103 ,Alexandria, VA 22314.

NAIMA AH124, Fibrous Glass Duct Liner Standard, 3rd edition, 2002.

NAIMA AH116, Fibrous Glass Duct Construction Standards, 5th 7 th edition, 2002 200 3 .

C.1.2.5 SMACNA Publications.

Sheet Metal and Air-Conditioning Contractors' National Association, Inc., 4201 Lafayette Center Drive,Chantilly, VA 22021-1209.

Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems, 2002.

C.1.2.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/ UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 201 4 .ANSI/

UL 555S,Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

ANSI/ UL 1565, Positioning Devices, 2002, Revised 2008 2013 .

ANSI/ UL 2043, Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and TheirAccessories Installed in Air-Handling Spaces, 2008 2013 .

UL Subject 2424 Outline , Outline of Investigation for Cable Marked Limited Combustible, 2006.

Building Materials Directory, 2012.

Fire Resistance Directory, 2012.

Heating, Cooling, Ventilating and Cooking Equipment Directory, 2012.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 35 12/3/2015 7:13 AM

Statement of Problem and Substantiation for Public Input

Referenced current SDO addresses, standard names, numbers, and editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 2-NFPA 90A-2015[Section No. 2.3]

Referenced current SDO names, addresses, standards names,numbers, and editions.

Public Input No. 1-NFPA 90A-2015[Global Input]

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Feb 08 04:11:47 EST 2015

Committee Statement

Resolution: See FR#10

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 35 12/3/2015 7:13 AM

Public Input No. 11-NFPA 90A-2015 [ Section No. C.1.2.3 ]

C.1.2.3 ASTM International Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of Building Materials,2013a 2015a .

ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C,2012.

ASTM E 2231 E2231 , Standard Practice for Specimen Preparation and Mounting of Pipe and DuctInsulation Materials to Assess Surface Burning Characteristics, 2009 2015 .

ASTM E 2652 E2652 , Standard Test Method for Behavior of Materials in a Tube Furnace with aCone-Shaped Airflow Stabilizer, at 750°C, 2012.

Statement of Problem and Substantiation for Public Input

standards date updates

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sat Apr 25 10:46:50 EDT 2015

Committee Statement

Resolution: See FR#10

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 35 12/3/2015 7:13 AM

Public Input No. 30-NFPA 90A-2015 [ Section No. C.1.2.6 ]

C.1.2.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 2014 .

ANSI/UL 555S,Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

ANSI/UL 1565, Positioning Devices, 2002, Revised 2008 2013 .

ANSI/UL 2043, Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and TheirAccessories Installed in Air-Handling Spaces, 2008, Revised 2013 .

UL Subject 2424, Outline of Investigation for Cable Marked Limited Combustible, 2006.

Building Materials Directory, 2012.

Fire Resistance Directory, 2012.

Heating, Cooling, Ventilating and Cooking Equipment Directory, 2012.

Statement of Problem and Substantiation for Public Input

The proposed changes reflect updated editions of the UL Standards.

Submitter Information Verification

Submitter Full Name: RONALD FARR

Organization: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 09:20:56 EDT 2015

Committee Statement

Resolution: See FR#10

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 35 12/3/2015 7:13 AM

Public Input No. 42-NFPA 90A-2015 [ Section No. C.1.2.6 ]

C.1.2.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2012 2014 .

ANSI/UL 555S,Standard for Safety Smoke Dampers, 1999, Revised 2012 2014 .

UL1381, Outline of Investigation for Aerosol Duct Sealant , 2013

ANSI/UL 1565, Positioning Devices, 2002, Revised 2008 2013 .

ANSI/UL 2043, Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and TheirAccessories Installed in Air-Handling Spaces, 2008.

UL Subject 2424, Outline of Investigation for Cable Marked Limited Combustible, 2006.

Building Materials Directory, 2012 2015 .

Fire Resistance Directory, 2012 2015 .

Heating, Cooling, Ventilating and Cooking Equipment Directory, 2012 2015 .

Statement of Problem and Substantiation for Public Input

This proposal updates the referenced UL publications to the most current editions. This proposal adds the new Outline of Investigation proposed to Section A.4.3.3.2 (Public Input 41).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 41-NFPA 90A-2015 [New Section after A.4.3.3.1] Propose new UL standard

Submitter Information Verification

Submitter Full Name: John Taecker

Organization: UL LLC

Affilliation: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:35:11 EDT 2015

Committee Statement

Resolution: See FR#10

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 35 12/3/2015 7:13 AM