stallcup's illustrated code changes 2008

107
©GRAYBOY, Inc. 2007 Illustrated Code Changes Stallcup’s ® 2008

Upload: francis-owusu

Post on 08-Nov-2015

138 views

Category:

Documents


16 download

DESCRIPTION

Stallcup's Illustrated Code Changes 2008

TRANSCRIPT

  • GRAYBOY, Inc. 2007

    Illustrated CodeChanges

    Stallcups

    2008

  • GRAYBOY, Inc. 2007

    INSTALLATIONS UNDER THE EXCLUSIVECONTROL OF AN ELECTRIC UTILITY

    SERVICE DROPS OR SERVICE LATERALS, AND ASSOCIATED METERING

    LOCATED IN LEGALLY ESTABLISHED EASEMENTS, OR RIGHT-OF-WAYSDESIGNATED BY OR RECOGNIZED BY PUBLIC SERVICE COMMISSIONS,OR OTHER REGULATORY AGENCIES HAVING JURISDICTION FOR SUCHINSTALLATIONS

    ON PROPERTY OWNED OR LEASED BY THE ELECTRIC UTILITY FORTHE PURPOSE OF COMMUNICATIONS, METERING, GENERATION,CONTROL, TRANSFORMATION, TRANSMISSION OR DISTRIBUTION OFELECTRIC ENERGY.

    TRANSMISSION

    DISTRIBUTION

    GENERATION

    WORKSPACE OSHA 1910.268(n)(12)(ii)

    GROUND WIRELIGHT ON UTILITY POLEBELOW ATTACHMENTS NESC - 238

    CATV LINE

    TELECOMMUNICATIONSLINE

    NOT COVERED90.2(B)(5)b

    Purpose of Change: This revision clarifies that any agreements will be limited, other than a legally established easementor right-of-way, that a utility company can use to make installations that are outside the scope of the NEC.

    1Ill.: pg. 1-2

    NEC: pg. 21

  • GRAYBOY, Inc. 2007

    L1N

    L2 L3L1

    N

    L2 L3

    L1 NL2

    NEUTRAL SHALL BE GROUNDED

    THIS 3-WIRE DC SYSTEM WITH NEUTRAL SHALL BE GROUNDED PER 250.162(B)

    OCPD

    TO DC POWER SOURCE

    DC POWERSUPPLY

    NEUTRAL CONDUCTORNEUTRAL POINT

    ARTICLE 100

    Purpose of Change: Two new definitions have been added to clarify what constitutes a neutral conductorand a neutral point.

    2Ill.: pg. 1-22NEC: pg. 28

  • GRAYBOY, Inc. 2007

    2000 by James G. Stallcup

    QUALIFIED PERSON ARTICLE 100

    DANGER-TESTINGBEING DONE

    YELLOW TAPE USEDAS GUARD OR BARRIER

    TEST OPERATORREADING INSTRUMENTS

    QUALIFIED PERSON KNOWS CONSTRUCTION, OPERATION,AND HAZARDS OF EQUIPMENT

    TRAINED, SKILLED, WITH KNOWLEDGETO RECOGNIZE AND AVOID HAZARDS

    ELECTRICALEQUIPMENT

    QUALIFIED PERSONARTICLE 100

    Purpose of Change: This revision clarifies that qualified persons that have received safetytraining and knows how to recognize and avoid the hazards involved.

    3Ill.: pg. 1-24NEC: pg. 29

  • GRAYBOY, Inc. 2007

    PRESSURE

    TWO DISKS WITH BOLT

    OPENING IS REQUIRED TO BESEALED WITH ONEOF THE FOLLOWING:

    BLANK TO COVERCB OPENING

    PANELBOARD COVER

    ENCLOSUREOR

    BOX

    UNUSED OPENINGS110.12(A)

    Purpose of Change: This revision indicates all unused openings should be closed,except for those required for the proper mounting of such equipment or enclosure.

    4Ill.: pg. 1-34NEC: pg. 33

  • GRAYBOY, Inc. 2007

    FLASH PROTECTION110.16

    Purpose of Change: This revision now clarifies that flash protection markings are required for large fusibleswitches and similar equipment where a flash hazard may exist.

    5Ill.: pg. 1-36NEC: pg. 34

    ELECTRICAL EQUIPMENTMUST BE MARKED INFIELD TO WARN WORKEROF AN ELECTRIC ARCFLASH

    WORKER

    QUALIFIEDPERSON

    MARKING ONEQUIPMENTWARNS WORKEROF ARC FLASHHAZARD

    NOTE 2: SEE ANSI Z535.4 FOR GUIDELINESPERTAINING TO DESIGNING SAFETY SIGNSAND LABELS TO PROVIDE WARNINGS, ETC.

    NOTE 1: SEE NFPA 70E FOR ASSISTANCE INDETERMINING EXPOSURE, PLANNING SAFEWORK PRACTICES, AND SELECTING PERSONALPROTECTIVE EQUIPMENT.

    SWITCHBOARDSPANELBOARDSINDUSTRIAL CONTROL PANELSMETER SOCKET ENCLOSURESMOTOR CONTROL CENTERSLARGE FUSIBLE SWITCHESSIMILAR ELECTRICAL EQUIPMENT

    ELECTRICAL EQUIPMENT

    LARGEFUSIBLE SWITCH

  • G

    RAYB

    OY,Inc.2007

    GIVEN:APPENDIX, B-5.2 IN NFPA 70E

    EMB = 1038.7 DB -1.4738 tA (.0093 F2 -.3453F + .59675)

    DB = 18 INCHES tA = 1/2 CYCLE OR .0084 SEC. F = 35 kA MVA = 11

    Step 1: EMB = (1038.7)(0.014125)(.0084)(11.3925

    - 12.0855 + 5.9675)Step 2: EMB = (14.671638)(.0084)(5.2745)

    Step 3: EMB = (14.671638)(.0443)

    Step 4: EMB = 0.649954 cal/cm2

    Solution:From Table 3-3.9.3 in Part II of NFPA 70E,

    0.649954 cal/cm2 requires a hazard riskcategory of 0 with one layer of untreated

    cotton (total weight oz/yd2 is 4.5-7).Note: This procedure is used only for 600 volts or lesssystems.

    (Review NFPA 70E carefully)Step 5: Finding flash protection boundary

    Dc = (53 x MVA x t)

    Dc = (53 x 11 x .0084)

    Dc = 2.21 ft.

    Solution:Based on the given parameters, the authorssuggest an arc-flash boundary of 2.21 ftand an incident energy value of

    0.649954 cal/cm2.

    Note: Authors recommend that only engineers orqualified personnel calculate and determine the boundary.

    APPLICATION OF FORMULA:APPENDIX B-5.2 IN PART II OF NFPA 70E

    5.2Ill.: pg. 1-36NEC: pg. 34

  • GRAYBOY, Inc. 2007

    WORKING SPACE

    NOTE THAT THE WORKSPACE IS UNOBSTRUCTEDWITHOUT A COLUMN, ETC. BLOCKING ACCESSAND EXIT ROUTE. IN THIS CASE, SINGLE DOORENTRY IS PERMITTED PER 110.26(C)(2)(a).

    PANIC HARDWAREON INSIDE OF DOOR

    DOOR w/PANIC BARS,PRESSURE PLATES, ETC.

    DOOR OPENSTOWARDS EGRESSOF ROOM

    EXIT ROUTE

    ELECTRICEQUIPMENT

    WORKING SPACE 110.2(C)(3)

    NEC CLEARANCES TABLE 110.26(A)(1)

    (600 V OR LESS) TABLE 110.34(A)

    (OVER 600 V) 110.26(F) 110.34(F)

    FOR EQUIPMENT RATED 1200 A OR MORE AND OVER 6' WIDE (1.8 m) THERE SHALLBE ONE ENTRANCE AND EGRESS FROM AND NOT LESS THAN 24" (610 mm) WIDEAND 6' 6" (2 m) HIGH AT EACH END OR WORKSPACE SHALL BE DOUBLED.

    SWITCHBOARD RATED 1200 A ORMORE AND OVER 6' WIDE (1.8 m)

    EQUIPMENTLARGE

    DOOR SHALL OPEN IN THEDIRECTION OF EGRESS IFLESS THAN 25' FROM THENEAREST EDGE OF THEWORKING SPACE AND BEEQUIPPED WITH PANICBARS, PRESSURE PLATE,OR OTHER DEVICES THATARE NOT NORMALLYLATCHED BUT OPEN UNDERSIMPLE PRESSURE.

    25'

    PERSONNEL DOORS110.26(C)(3)

    Purpose of Change: This revision clarifies that the personnel door(s) shall have panic bars and similar equipmentand open in the direction of egress if located less than 25 ft from the nearest edge of the working space.

    6Ill.: pg. 1-45NEC: pg. 37

  • GRAYBOY, Inc. 2007

    BUILDING

    GROUNDED CONDUCTORTERMINAL BAR 250.24(B)

    EGC TERMINAL BAR 250.24(B)

    LATERAL FROMMASTER METER

    250 KCMIL cu.

    MAIN BONDING JUMPER (MBJ) 250.24(B)

    METAL WATERPIPE SYSTEMS 250.52(A)(1)

    250 KCMIL cu. REQUIRES2 AWG cu. CONDUCTOR

    MBJ IS 2 AWG COPPER

    SIZING (MBJ) 250.24(B); 250.28(D); Table 250.66

    GENERAL200.2

    Purpose of Change: This new subsection clarifies that a busbar or conductor shall be used to makethe connection between the neutral bar and the equipment grounding terminal bar, not the metal ofthe enclosure.

    7Ill.: pg. 2-2

    NEC: pg. 43

  • GRAYBOY, Inc. 2007

    CB DISCONNECT BOTH CIRCUITS1 AND 2 SIMULTANEOUSLY ORIGINATE FROM THE SAME

    PANELBOARD 210.4(A) 210.4(B)

    CIRCUIT 1SUPPLYINGEQUIPMENT

    CIRCUIT 2SUPPLYINGEQUIPMENT

    DEVICEBOX

    GROUPING WIRE TIES OR

    SIMILAR MEANS 210.4(D)

    NOTE: GROUPING SHALL NOT APPLY IFTHE CIRCUIT ENTERS FROM A CABLEOR RACEWAY UNIQUE TO THE CIRCUITTHAT MAKES THE GROUPING OBVIOUS.

    LINK ON RECEPTACLE CONNECTING UNGROUNDED(HOT) TERMINALS (BRASS COLOR) HAS BEEN BROKEN 210.4(B)

    GROUPING210.4(D)

    Purpose of Change: This new subsection requires grouping all the conductors of a multiwire branch circuit tohelp ensure that all ungrounded conductors are disconnected and grounded (neutral) conductor is de-energized,especially during service work.

    8Ill.: pg. 2-6

    NEC: pg. 45

  • GRAYBOY, Inc. 2007

    IDENTIFICATION OF EACH PHASE OR LINE TERMINATIONS SPLICE POINTS CONNECTIONS 210.5(C)

    3-CIRCUITS 480/277 V

    A MEANS OF IDENTIFICATION OFUNGROUNDED CONDUCTORS SHALLBE POSTED AT EACH PANELBOARDOR DOCUMENTED IN A MANNER THATIS READILY AVAILABLE 210.5(C)

    3-CIRCUITS 208/120 V

    IDENTIFICATION OFSYSTEMS ANDCIRCUITS 480/277 V 208/120 V

    PERMITTED METHODS OFIDENTIFICATION SEPARATE COLOR CODING MARKING TAPE TAGGING OTHER APPROVED MEANS 210.5(C)

    UNGROUNDED CONDUCTORS210.5(C)

    Purpose of Change: This revision clarifies that each ungrounded conductor of a branch circuit shall beidentified by phase or line and by system at all termination, connection, and splice points.

    9Ill.: pg. 2-8

    NEC: pg. 46

  • GRAYBOY, Inc. 2007

    NOTE: WHERE RECEPTACLES ARE USED IN INDUSTRIAL ESTABLISHMENTS ONLY, GFCIPROTECTION ON RECEPTACLES SHALL NOT BE REQUIRED WHERE THE CONDITIONS OFMAINTENANCE AND SUPERVISION ENSURE THAT ONLY QUALIFIED PERSONNEL AREINVOLVED, THAT ARE LIMITED TO USE WITH EQUIPMENT QUALIFIED UNDER AN ASSUREDEQUIPMENT GROUNDING CONDUCTOR PROGRAM AS SPECIFIED IN 590.6(B)(2).

    OUTDOORS 210.8(B)(4)

    ALL NON-DWELLINGRECEPTACLE OUTLETSSHALL BE GFCI PROTECTED 210.8(B)(4)

    A PUBLIC SPACE IS ANY SPACE THAT IS FOR USE BY,OR IS ACCESSIBLE TO, THE PUBLIC HAS BEEN DELETED.NOW APPLIES TO ALL 15- AND 20-AMPERE, 125 VOLTSINGLE-PHASE RECEPTACLES 210.8(B)(4)

    OTHER THAN DWELLINGS210.8(B)(4)

    Purpose of Change: This revision requires GFCI protection for all 15- and 20-ampere, 125-voltsingle-phase receptacles installed outdoors.

    10Ill.: pg. 2-14NEC: pg. 47

  • GRAYBOY, Inc. 2007

    AFCI NOT REQUIRED TO BEINSTALLED WITHIN 6' (1.8 m)OF BRANCH CIRCUIT OCPDsMEASURED ALONG CIRCUITCONDUCTORS 210.12(B), Ex. No. 1

    AFCI

    FLOORLAMP

    CHAINLIGHT

    FLUORESCENTFIXTURE

    STEREO

    DRESSERLAMPS

    BEDLAMP

    TELEVISIONTABLELAMP

    METAL RACEWAY OR CABLEW/METALLIC SHEATH (DELETED) 210.12, Ex. - 2005 NEC

    NOTE: AFCI PROTECTION FOR ALL 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE BRANCH CIRCUITSSUPPLYING OUTLETS SHALL BE INSTALLED INDWELLING UNITS IN FAMILY ROOMS, DINING ROOMS,LIVING ROOMS, PARLORS, LIBRARIES, DENS,BEDROOMS, SUN ROOMS, RECREATION ROOMS,CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS.

    DWELLING UNITS210.12(B), Exception

    Purpose of Change: This revision clarified that enclosing the 6 ft (1.8 m) of circuit conductors in a metalraceway or metallic-sheathed cable is not required.

    11Ill.: pg. 2-18NEC: pg. 49

  • GRAYBOY, Inc. 2007

    Purpose of Change: A new Exception No. 2 has been added to permit AFCI protectionto be omitted if the branch circuit to a fire alarm system is installed in RMC, IMC, EMT,or steel armored cable (Type AC).

    DETECTORS

    AFCI PROTECTIONNOT REQUIRED210.12(B), Ex. 2

    WIRING METHOD RMC IMC EMT STEEL ARMORED CABLE

    (TYPE AC) 210.12(B), Ex. 2 250.118

    DWELLING UNITS210.12(B), Exception No. 2

    PERMITTED BOXES METAL OUTLET METAL JUNCTION 210.12(B), Ex. 2

    12Ill.: pg. 2-20NEC: pg. 49

  • GRAYBOY, Inc. 2007

    NOTE: BALCONIES, DECKS, OR PORCHES WITH A USABLE AREA OF LESSTHAN 20 SQ. FT. ARE NOT REQUIRED TO HAVE A RECEPTACLE INSTALLED.

    IllustrationsbyKristaDarnell'96

    Grayboy&Assoc.

    OVER 6' 6" (2 m) SHALL NOT BECONSIDERED TO BE ACCESSIBLE.(CHRISTMAS LIGHTRECEPTACLES)

    IF BALCONY IS NOT ACCESSIBLE RECEPTACLE NOT REQUIRED 210.52(E)(3)

    RECEPTACLE ON OPENFRONT PORCH REQUIRED 210.52(E)(3)

    OUTDOOR OUTLETS210.52(E)(1) THRU (E)(3)

    Purpose of Change: New subsection titles have been added for usability. A new subsection (3) has beenadded to require a receptacle be installed on any porch, deck, or balcony where accessible from inside thedwelling unit. A new Exception to (3) does not require a receptacle on a balcony, deck, or porch with a useablearea of less than 20 sq ft.

    13Ill.: pg. 2-26NEC: pg. 54

  • GRAYBOY, Inc. 2007

    SUBSTATION WITHFEEDER DISCONNECT

    DISCONNECTING MEANS MORE THAN ONE SWITCH

    OR CIRCUIT BREAKER COMBINE THE RATINGSTO DETERMINE THE OVERALLRATING OF THE DISCONNECTINGMEANS

    225.39

    SEPARATE BUILDING 2

    PANEL

    IDENTIFICATION 225.37

    DISCONNECT CONSTRUCTION 225.38

    ACCESSTO OCPDs 225.40

    RATING OF DISCONNECT225.39

    THE RATING SHALL NOT BE LOWER THAN: ONE-CIRCUIT INSTALLATION. NOT LESS THAN 15 AMPERES TWO-CIRCUIT INSTALLATIONS. NOT LESS THAN 30 AMPERES ONE-FAMILY DWELLING. NOT LESS THAN 100 AMPERES ALL OTHERS. NOT LESS THAN 60 AMPERES

    Purpose of Change: This revision clarifies that the ratings of all switches or circuit breakers shall bepermitted to be combined to determine the overall rating of the disconnecting means.

    14Ill.: pg. 2-39NEC: pg. 71

  • GRAYBOY, Inc. 2007

    CABLE TRAY SHALL BE IDENTIFIED WITH

    PERMANENTLY AFFIXED LABELSWITH THE WORDING SERVICE-ENTRANCE CONDUCTORS

    LABEL SHALL BE VISIBLE AFTERINSTALLATION

    READILY TRACEABLE THROUGH THEENTIRE LENGTH OF THE CABLE TRAY

    230.44, Ex.

    CABLE TRAY W/BARRIER 230.44, Ex.

    SERVICE CONDUCTORSIN SINGLE LAYERS4/C - 350 KCMIL THHN cu.

    OTHER THAN SERVICECONDUCTORS, STACKED5 - 4/C - 1/0 AWG THHN cu.INSTALLED PER ARTICLE 392

    SOLIDFIXEDBARRIER 230.44, Ex.

    CABLE TRAYS230.44, Ex.

    Purpose of Change: This revision clarifies that service-entrance conductors installed in cable trays with otherthan service-entrance conductor shall be separated with a barrier and shall be identified with permanently affixedlabels on the cable tray that are readily traced through the entire length.

    15Ill.: pg. 2-45NEC: pg. 77

  • GRAYBOY, Inc. 2007

    PANEL

    DISCONNECT CONSTRUCTION 225.38

    ACCESSTO OCPDS 225.40

    SEPARATE BUILDING 2

    SERVICEDISCONNECT 230.205(A)

    LOCATION230.205(A)

    Purpose of Change: This revision clarifies that on private property, the service disconnectshall be permitted to be in a location that is not readily accessible, such as the top of a pole.

    16Ill.: pg. 2-50NEC: pg. 82

  • GRAYBOY, Inc. 2007

    DEFINITION OFCLASSIFICATION OF CIRCUITS 760.2

    CONDUCTORS 760.82 TABLE 760.61 TABLE 760.82(I) 14 AWG cu. THWN

    ALARM

    CABLE

    ACTIVATEEXTINGUISHER

    CONTROL EQUIPMENTDOORS, FANS, ELEVATORS, ETC.

    OCPDs AND LOCATION 760.23 760.24

    CONDUIT

    DETECTORS

    NPLFA CONDUCTORS 16 AWG cu. TFFN

    POWER LIMITS 760.15

    TOPANEL

    Step 1: Finding conductor A760.23; Table 310.16;14 AWG cu. = 20 A16 AWG cu. = 10 A

    Step 2: Selecting OCPD for alarm circuitsTable 310.16; 760.23; 240.4(D)20 A (14 AWG cu.) requires 15 A OCPD10 A (16 AWG cu.) requires 10 A OCPD

    Solution: The size OCPD for the 14 AWG TFFNcopper conductors is 15 amps and10 amps for the 16 AWG TFFNcopper conductors.

    Sizing OCPD for fire alarm circuits

    APPLYING 240.4(D)

    SMALL CONDUCTORS240.4(D)

    Purpose of Change: This revision adds small conductors in 18 AWG and 16 AWG sizes to correspond to thepermission to use these smaller conductors.

    17Ill.: pg. 2-51NEC: pg. 84

  • GRAYBOY, Inc. 2007

    APPLYING 240.21(C)(2)(4)

    Step 1: Calculating primary FLA240.21(C)(2)(4)

    A = 75 kVA 480 V x 1.732A = 75 kVA 831 V

    A = 90 A

    Step 2: Calculating primary size OCPD90 A x 125% = 112.5 A

    Step 3: Finding primary size OCPD240.6(A)112.5 A requires 125 A

    Step 4: Finding ratio240.21(C)(2)(4)

    Ratio = 480 V / 208 VRatio = 2.31

    Step 5: Calculating secondary FLA240.21(C)(2)(4)

    A = 125 A OCPD x 2.31 ratioA = 288.75

    Step 6: Sizing conductorsA = 288.75 A 10A = 28.875 A28.875 A requires 10 AWG cu.

    Solution: The size THWN copper conductorsis at least 10 AWG copper andcant be longer than 10 ft.

    Sizing primary OCPD

    Sizing secondary conductors

    SERVICE CONDUCTORS 230.42(A)(1)

    OCPD 125 A

    ONE CONDUCTORSHOWN FORSIMPLICITY

    OCPD 240.21(C)(2)(4)

    TRANSFORMER SECONDARY CONDUCTORSNOT OVER 3 m (10 FT) LONG

    240.21(C)(2)(4)

    TRANSFORMER 75 kVA 3 480 V PRI. 208Y/120 V SEC.

    SECONDARY CONDUCTORS NOT OVER 10' (3 m) LONG 240.21(C)(2)

    Purpose of Change: This revision clarifies that this section correlates with the conventional 10-foot tap rule in 240.21(B)(1).

    18Ill.: pg. 2-53NEC: pg. 88

  • GRAYBOY, Inc. 2007

    NOTE: INSTALLATION OF THE OVERCURRENTPROTECTION WITHIN A HAZARDOUS LOCATIONSHALL ALSO BE PERMITTED.

    FUSE PROTECTION

    CIRCUIT BREAKERPROTECTION

    UPS WITH STORAGEBATTERIES

    OCPD INSTALLED AS CLOSEDAS PRACTICABLE TO THEBATTERY TERMINALS PER240.21(H) AND 480.5.

    BATTERY CONDUCTORS240.21(H)

    Purpose of Change: A new subsection has been added to permit overcurrent protection to beinstalled as close as practicable to the storage battery terminals in a non-hazardous location.

    19Ill.: pg. 2-57NEC: pg. 89

  • GRAYBOY, Inc. 2007

    NOTE: FOR CALCULATED APPLICATIONS, THE ENGINEER SHALL ENSURE THAT THEDOWNSTREAM CIRCUIT BREAKER(S) THAT ARE PART OF THE SERIES COMBINATIONREMAIN PASSIVE DURING THE INTERRUPTION PERIOD OF THE LINE SIDE FULLYRATED, CURRENT-LIMITING DEVICE.

    CB WITH A HIGHERAIC RATING 240.86

    CB WITH A LOWER AICRATING 240.86

    LOAD SIDE

    SERIES COMBINATIONRATING SHALL BE MARKED 240.86(A)

    MBJGES

    GEC

    FEEDER

    EXISTING INSTALLATIONS ONLY

    PROCESSINGEQUIPMENT

    SELECTED UNDER ENGINEERING SUPERVISIONIN EXISTING INSTALLATIONS

    240.86(A)

    Purpose of Change: This revision clarifies that for calculated applications, the engineer shall ensure that the downstreamcircuit breaker(s) that are part of the series combination remain passive during the interruption period of the line sidefully rated, current-limiting device.

    20Ill.: pg. 2-59NEC: pg. 92

  • GRAYBOY, Inc. 2007

    MARKING:CAUTION - SERIES COMBINATION RATED _ AMPERES. REPLACEWITH:_ TYPE BREAKER_ TYPE FUSE

    CB WITH A HIGHERAIC RATING 240.86

    CB WITH A LOWER AICRATING 240.86

    PROCESSINGEQUIPMENTLOAD SIDE

    SERIES COMBINATIONRATING MUST BE MARKED 240.86(A)

    MBJGES

    GEC

    SELECTED UNDER ENGINEERING SUPERVISIONIN EXISTING INSTALLATIONS

    240.86(A)

    Purpose of Change: This revision clarifies that specific markings must be readily visible for both theupstream and the downstream devices in series combination systems.

    20.2Ill.: pg. 2-59NEC: pg. 92

  • GRAYBOY, Inc. 2007

    OCPDUNDER SHORT CIRCUIT CONDITIONS,CONDUCTORS MUST NOT EXCEED THEIRSHORT CIRCUIT TEMPERATURE LIMITS

    SORT CIRCUIT FORMULA FOR COPPER CONDUCTORS(I /A)t = 0.0297 LOG10 [(T2 + 234)(T1 + 234)]

    SHORT CIRCUIT FORMULA FOR ALUMINUM CONDUCTORS(I /A)t = 0.0125 LOG10 [(T2 + 228)(T1 + 228)]

    2 2

    2 2

    SHORT-CIRCUIT FORMULA VALUES I = SHORT-CIRCUIT CURRENT IN AMPERES A = CONDUCTOR ARE IN CIRCULAR MILS t = TIME OF SHORT-CIRCUIT IN SECONDS (FOR TIMES LESS THAN OR EQUAL TO 10 SECONDS) T1 = INITIAL CONDUCTOR TEMPERATURE IN DEGREES CELSIUS T2 = FINAL CONDUCTOR TEMPERATURE IN DEGREES CELSIUS COPPER CONDUCTOR WITH PAPER, RUBBER, VARNISHED CLOTH INSULATION, T2 = 200 COPPER CONDUCTOR WITH TERMOPLASTIC INSULATION, T2 = 250 COPPER CONDUCTOR WITH CROSS-LINKED POLYETHYLENE INSULATION, T2 = 250 COPPER CONDUCTOR WITH ETHYLENE PROPYLENE RUBBER INSUALTION, T2 = 250 ALUMINUM CONDUCTOR WITH PAPER, RUBBER, VARNISHED CLOTH INSULATION, T2 = 200 ALUMINUM CONDUCTOR WITH THERMOPLASTIC INSULATION, T2 = 150 ALUMINUM CONDUCTOR WITH CROSS-LINKED POLYETHYLENE INSULATION, T2 = 250 ALUMINUM CONDUCTOR WITH ETHYLENE PROPYLENE RUBBER INSULATION, T2 = 250

    FEEDER TAPS240.92(B)

    Purpose of Change: This new subsection will increase the enforceability necessary by the inspection communityand will limit the application of expanding feeder tap conductors for supervised industrial installations.

    21Ill.: pg. 2-62NEC: pg. 92

  • GRAYBOY, Inc. 2007EBJ

    250.102(D)

    CONNECTION EGC

    CLEANSURFACES 250.12

    EGC

    MBJ 250.28(D)

    GROUND CLAMPSOR FITTINGSCONNECTING THEGEC TO THE RODMUST BE LISTEDFOR DIRECT BURIALAND PROTECTEDFROM PHYSICALDAMAGE

    FITTING GEC

    ROD

    CONNECTION FOR GROUNDINGAND BONDING EQUIPMENT LISTED PRESSURE CONNECTORS TERMINAL BARS PRESSURE CONNECTORS LISTED AS

    GROUNDING AND BONDING EQUIPMENT EXOTHERMAL WELDING PROCESS MACHINE SCREW-TYPE FASTENERSTHAT ENGAGE NOT LESS THAN TWOTHREADS OR ARE SECURED WITH A NUT

    THREAD-FORMING MACHINE SCREWS THAT ENGAGE NOT LESS THAN TWO THREADSIN THE ENCLOSURE

    CONNECTIONS THAT ARE PART OF A LISTEDASSEMBLY

    OTHER LISTED MEANS 250.8(A)

    NOTE: CONNECTION DEVICES OR FITTINGS THATDEPEND SOLELY ON SOLDER SHALL NOT BE USED.

    CONNECTION OF GROUNDING AND BONDING EQUIPMENT250.8(A); (B)

    SELF-TAPPINGSCREWS WITHAT LEAST TWOTHREADS

    Purpose of Change: This revision clarifies the permitted methods for connections of grounding and bonding equipment.

    22Ill.: pg. 2-66NEC: pg. 97

  • GRAYBOY, Inc. 2007

    SERVICECONDUCTORS

    MAKE UP BOX

    METER BASESERVICE PANEL

    TRANSFER SWITCH GROUNDED CONDUCTOR NOT

    SOLIDLY INTERCONNECTEDTO THE SERVICE GROUNDEDCONDUCTOR

    250.20(D)

    GENERATOR SEPARATELY DERIVED

    SYSTEM SHALL BE GROUNDED 250.20(D) 250.30(A)

    TO LOAD

    TO SEPARATELYDERIVED SYSTEM

    TO SERVICEEQUIPMENT

    NEUTRAL NOTSOLIDLY GROUNDED

    CLASSIFIED AS A SEPARATELY DERIVED SYSTEM

    TO LOAD

    TO GENERATOR NOT SEPARATELY

    DERIVED SYSTEM

    TO SERVICEEQUIPMENT

    NEUTRALSOLIDLY GROUNDED

    NOT CLASSIFIED AS A SEPARATELY DERIVED SYSTEM

    SEPARATELY DERIVED SYSTEMS250.20(D)

    Purpose of Change: This revision clarifies that a separately derived systems shall be grounded where transfer equipment isprovided that includes switching the grounded conductor and where the grounded conductor is not solidly interconnectedto the service supplied grounded conductor.

    23Ill.: pg. 2-70NEC: pg. 98

  • GRAYBOY, Inc. 2007

    UTILITYMETER

    MAY BE CONNECTEDGROUNDING ELECTRODEHERE 250.24(A)(1) 250.66

    GEC SIZED PER 250.66 250.24(D)

    LOAD SIDE PANELCONTAINING CBs

    SUPPLY SIDE 250.142(A)

    GROUNDED(NEUTRAL)CONDUCTOR 250.24(C)(1) 250.24(C)(2) 250.24(D)

    TO BRANCH-CIRCUITSOR FEEDER-CIRCUITSWITH PHASE CONDUCTORS 250.142(B)

    SERVICEPANELMAIN OCPD

    MAY BECONNECTED TO GROUNDINGELECTRODE HERE 250.24(A)(1) 250.66

    TO UTILITY XFMR NESC - RULE 92(B)(1)

    GROUNDEDCONDUCTOR

    GROUNDING ELECTRODE CONDUCTOR250.24(D)

    Purpose of Change: This revision clarifies that the grounding electrodeconductors shall be sized in accordance with 250.66.

    23Ill.: pg. 2-76NEC: pg. 99

  • GRAYBOY, Inc. 2007 UNGROUNDED (PHASE) CONDUCTORS 700 KCMIL cu. THWN PARALLELED 3 TIMES

    AUXILIARY GUTTER ARTICLE 366

    GROUNDING ELECTRODECONDUCTOR MAY BE SPLICED TO BUSBARAND GROUNDED (NEUTRAL)CONDUCTOR

    250.64(C), Ex.

    UNGROUNDED(PHASE) CONDUCTORS 250 KCMIL 2 cu. BONDING JUMPER 250.64(D) 250.66

    GROUNDING ELECTRODECONDUCTOR 3/0 AWG cu. 250.66 TABLE 250.66

    PANEL1

    PANEL2

    PANEL3

    PANEL4

    PANEL5

    PANEL6

    MAIN BONDING JUMPER 2 AWG cu. 250.66 TABLE 250.66

    NOTE: ONE LINE DRAWN FOR SIMPLICITY

    SIZE250.28(D)(1) THRU (D)(3)

    Purpose of Change: This revision clarifies how to size main bonding jumpers for services with more than oneenclosure and to size system bonding jumpers for separately derived systems with more than one enlcosure.

    24Ill.: pg. 2-78

    NEC: pg. 100

  • GRAYBOY, Inc. 2007

    NOTE: THE GEC IS SIZED FROMTABLE 250.66 PER 250.32(E).

    BUILDING 2 GROUNDED (NEUTRAL)CONDUCTOR USED ASNEUTRAL AND EGC 250.32(B), Ex.

    MAIN SWITCHGEARBUILDING

    OCPD 225 A

    TO BUILDING

    RMC w/RIGIDELBOW

    GROUNDED NEUTRAL

    PVC

    FEEDER W/NEUTRAL 4 AWG cu.

    GROUNDED SYSTEMS250.32(B) AND EXCEPTION

    EXISTING PREMISES ONLY

    Step 1: Calculating neutral load220.61(A); 225.3(B); 310.15(B)(4)(c)50 A x 100% = 50 A

    Step 2: Sizing neutral250.32(B), Ex.; Table 310.1650 A requires 8 AWG cu.

    Step 3: Sizing neutral to be used as EGC250.32(B), Ex.; Table 250.122225 A OCPD requires 4 AWG cu.

    Solution: The grounded neutral conductor must be4 AWG THNN copper to serve as an EGC.

    WHAT SIZE NEUTRAL IS REQUIRED?

    Purpose of Change: This revision clarifies that the grounded (neutral) conductor for other buildings or structures supplied by feedersor branch circuits shall be permitted to be used as the equipment grounding conductor for existing premises wiring system only.

    25Ill.: pg. 2-86

    NEC: pg. 102

  • GRAYBOY, Inc. 2007

    NOTE 2: THE EQUIPMENT GROUNDING CONDUCTOR ON THELOAD SIDE OF EACH GENERATOR OVERCURRENT DEVICESHALL BE SIZED IN ACCORDANCE WITH 250.102(D) BASED ONTHE RATING OF THE OVERCURRENT DEVICE SUPPLIED.

    NOTE 1: THE EQUIPMENT BONDING JUMPER ON THE SUPPLYSIDE OF EACH GENERATOR OVERCURRENT DEVICE SHALL BESIZED IN ACCORDANCE WITH 250.102(C) BASED ON THE SIZEOF THE CONDUCTORS SUPPLIED BY THE GENERATOR.

    SERVICECONDUCTORS

    MAKE UP BOX

    METER BASESERVICE PANEL

    TRANSFER SWITCH GROUNDED CONDUCTOR

    SOLIDLY INTERCONNECTEDTO THE SERVICE GROUNDEDCONDUCTOR

    250.20(D)

    PERMANENTLY INSTALLEDGENERATOR NON- SEPARATELY

    DERIVED SYSTEM 250.20(D) 250.30(A)

    TO LOAD

    TO SEPARATELYDERIVED SYSTEM

    TO SERVICEEQUIPMENT

    NEUTRAL NOTSOLIDLY GROUNDED

    CLASSIFIED AS A SEPARATELY DERIVED SYSTEM

    PERMANENTLY INSTALLED GENERATORS250.35(A) AND (B)

    Purpose of Change: A new section had been added to address the installation of equipment bondingjumpers and equipment grounding conductors for permanently installed generators that are not separatelyderived systems.

    26Ill.: pg. 2-88

    NEC: pg. 103

  • GRAYBOY, Inc. 2007

    UNGROUNDED (PHASE) CONDUCTORS 250 KCMIL THWN cu. 230.42(A)(1)

    SLAB ANDFOUNDATION

    STRUCTURAL STEEL (GES) 250.52(A)(2) TABLE 250.66

    GROUND RING 2 AWG cu. 30" (750 mm) DEEP 250.52(A)(4) 250.66(C) 250.53(F)

    METAL FRAME OF THE BUILDING OR STRUCTURE250.52(A)(2)

    GROUNDINGELECTRODECONDUCTOR 2 AWG cu.

    EXOTHERMICWELD

    Purpose of Change: This revision clarifies that the structural steel shall be permitted to serve as agrounding electrode if connected to the reinforcing bars of a concrete encased electrode or ground ring.

    27Ill.: pg. 2-92

    NEC: pg. 105

  • GRAYBOY, Inc. 2007

    C

    SERVICE PANELUNGROUNDED (PHASE)CONDUCTORS 250 KCMIL THWN cu. 230.42(A)(1)

    OUTSIDEGRADE SLAB

    GEC 4 AWG cu. 250.52(A)(3) 250.66(B)

    REBAR STEEL AT LEAST20' (6 m) OR MORE IN LENGTH

    OR4 AWG COPPER CONDUCTORAT LEAST 20' (6 m) IN LENGTH 250.52(C)(3)

    CEE GES 250.52(A)(3)

    GEC CONNECTED TO A CONCRETE -ENCASED ELECTRODE (UFERGROUND)

    REINFORCINGREBAR INFOOTING

    MBJ

    GROUNDED (NEUTRAL)CONDUCTOR

    EBJ 250.102(C) TABLE 250.122

    CONCRETE PILING FORROOF OVERHANG HASREBAR BUT DOESNT REQUIRECONNECTION IF REBAR INBUILDING FOOTING IS USED

    CONCRETE-ENCASED ELECTRODE250.52(A)(3)

    Purpose of Change: This revision clarifies that it shall be permissible to bond only one concrete-encased electrode(CEE) into the grounding electrode system (GES) where multiple concrete electrodes are present. This change alsopermits the concrete-encased electrode to be located horizontally near the bottom of the footing or vertically wherefoundation or footing is in direct contact with the earth.

    28Ill.: pg. 2-94

    NEC: pg. 105

  • GRAYBOY, Inc. 2007

    GEC 250.66(A)

    FINISHEDGRADE

    UNGROUNDED (PHASE)CONDUCTORS 4/0 AWG THWN cu. 230.42(A)(1)

    MBJ

    DRIVENROD 250.52(A)(5)

    EBJ

    DRIVEN ROD 5/8" (15.67 mm) STAINLESS STEEL COPPER-COATED STEEL ZINC-COATED STEEL 250.52(A)(5)(b)

    LISTED 1/2" DIAMETER STAINLESS STEEL COPPER-COATED STEEL ZINC-COATED STEEL

    ROD AND PIPE ELECTRODES250.52(A)(5)

    Purpose of Change: This revision clarifies that rod and pipe electrodes can be stainless steel, copper, orzinc-coated steel if at least 5/8 inch in diameter or not smaller than 1/2 inch in diameter if listed.

    29Ill.: pg. 2-96

    NEC: pg. 105

  • GRAYBOY, Inc. 2007

    BUSBARAUXILIARY GUTTER ARTICLE 366

    COMMON GEC W/O SPLICE 3/0 AWG cu. 250.64(D)(1) TABLE 250.66

    TAP CONDUCTORS 4/0 AWG THWN cu. 250.64(D)(1) 250.66

    TAPPED GECs 2 AWG cu. TABLE 250.66

    GE SBS

    4 - 600 KCMIL IN PARALLEL PER PHASE THWN cu. CONDUCTORS

    FUTURE USE

    Given for CGEC:4-600 kcmil in parallel per 310.4

    Solution: Table 250.66600 kcmil x 4 = 2400 kcmil3/0 AWG cu. common GEC required.

    Given for Tap Conductors:4/0 AWG THWN cu. per phase

    Solution: Table 250.664/0 AWG cu.2 AWG GEC taps required.

    NOTE: FOR SIMPLICITY, ONLY ONE SET OF THEPARALLEL CONDUCTORS IS SHOWN.

    SERVICE WITH MULTIPLE DISCONNECTING MEANS ENCLOSURES250.64(D)(1) THRU (D)(3)

    Purpose of Change: This revision clarifies the sizing and installation requirements for the groundingelectrode conductor where multiple disconnecting enclosures are installed.

    30Ill.: pg. 2-102NEC: pg. 107

  • GRAYBOY, Inc. 2007

    BOLTED, RIVETED, OR WELDED

    SERVICEEQUIPMENT

    MECHANICALMEANS NUT AND BOLT 250.68(A), Ex. 2

    WHEN CONNECTED TO FIRE-PROOFED STRUCTURALMETAL, THIS CONNECTION IS NOT REQUIRED TO BEACCESSIBLE PER 250.68(A), Ex. 2.

    CEE

    GEC

    ACCESSIBILITY250.68(A), Ex. 2

    Purpose of Change: This revision clarifies that the mechanical means, such as a nut and bolt,used to connect irreversible compression connectors to the metal structure is not required to beaccessible.

    31Ill.: pg. 2-106NEC: pg. 108

  • GRAYBOY, Inc. 2007

    NOTE 1: THE EGC SHALL BE: CONTINUOUS GREEN COLOR, OR CONTINUOUS GREEN COLOR WITH ONE OR MORE YELLOW STRIPES

    EGCCONDUCTORS CONTAINED WITHIN THE SAME

    RACEWAY, CABLE, CORD, OR

    OTHERWISE RUN WITH THE BRANCH-CIRCUIT CONDUCTORS

    NOTE 2: EGCs LARGER THAN 6 AWG cu. ARE NOT REQUIRED TO BEMARKED WHEN IN CONDUIT BODIES THAT CONTAIN NO SPLICES ORUNUSED HUBS PER 250.119(A)(1), EXCEPTION.

    CONDUITBODY

    IDENTIFICATION SHALL ENCIRCLE THE CONDUCTOR 250.119(A)(2)

    CONDUCTORS LARGER THAN 6 AWG250.119(A)

    LARGER THAN 6 AWG

    Purpose of Change: This revision clarifies that the identification of the equipment groundingconductor (EGC), larger than the 6 AWG, shall encircle the conductor at the termination.

    32Ill.: pg. 2-120NEC: pg. 115

  • GRAYBOY, Inc. 2007

    GECGES

    GROUNDING 392.7 TABLE 392.7(B)

    ASSOCIATEDFITTINGS SHALLBE IDENTIFIED 392.3

    BONDING 392.7(B)(4)

    MULTIPLE CIRCUITS250.122(C)

    NOTE: SINGLE CONDUCTORS USED AS EQUIPMENTGROUNDING CONDUCTORS SHALL BE INSULATED,COVERED, OR BARE, AND THEY SHALL BE 4 AWGOR LARGER.

    Purpose of Change: This revision clarifies that where a single equipment groundingconductor is run with multiple circuits in the same cable tray, the equipment groundingconductor must be sized for the largest OCPD protecting conductors in the cable tray andmust meet the minimum requirements in 392.3(B)(1)(c).

    33Ill.: pg. 2-121NEC: pg. 116

  • GRAYBOY, Inc. 2007

    EXAMPLE

    THE RATING OF THE OCPDPROTECTING THE CIRCUITCONDUCTORS IS 20 AMPS.

    SIZING EBJTABLE 250.12220 A REQUIRES 12 AWG cu.

    NEUTRAL

    EBJ 250.146

    HOT

    SWITCH BOX METAL

    CONNECTING RECEPTACLE GROUNDINGTERMINAL TO BOX

    250.146

    Purpose of Change: This revision clarifies that the sizing of the equipment bondingjumper (EBJ) from the box to the receptacle is based on Table 250.122 for the ratingof the branch circuit overcurrent protective device.

    34Ill.: pg. 2-124NEC: pg. 119

  • GRAYBOY, Inc. 2007NOTE: RIGID METAL CONDUIT AND INTERMEDIATE METAL CONDUITSHALL NOT BE REQUIRED TO COMPLY WITH 300.4(E).

    ROOF DECKING METAL-CORRUGATED

    CABLES ROUTED ALONG SIDE OFRAFTERS NOT LESS THAN 1 1/2"(38 mm) FROM THE ROOF DECKING. 300.4(E)

    CABLES RUN ACROSS RAFTERS WITHGUARD STRIPS NOT LESS THAN 1 1/2"(38 mm) FROM THE NEARESTSURFACE OF THE ROOF DECKING.

    CABLES ROUTED ALONGSIDE OF JOISTS

    CABLES ROUTED ACROSSTOP OF JOISTS WITHGUARD STRIPS USED FORSUPPORTS

    CABLES ROUTED NOT LESS THAN1 1/2" (38 mm) THROUGH JOISTS WITHRUNNING BOARD

    CABLES AND RACEWAY INSTALLEDUNDER ROOF DECKING

    300.4(E)

    Purpose of Change: A new subsection has been added to required at least 1 1/2 in. clearance for a cable- or raceway-typewiring method to be installed in exposed or concealed locations under metal-corrugated sheet roof decking.

    35Ill.: pg. 3-2

    NEC: pg. 128

  • GRAYBOY, Inc. 2007

    SECABLE

    PANELBOARD 408.16(A), Ex. 1

    HANDHOLE ENCLOSURE INTERIOR CONSIDERED

    A WET LOCATION 300.5(B)

    HANDHOLE ENCLOSURE 314.30(A) - (D)

    RACEWAY INTERIOR CONSIDERED A WET LOCATION 300.9

    RACEWAY INTERIOR CONSIDERED

    A WET LOCATION 300.5(B)

    INSULATED CONDUCTORSAND CABLES LISTED FOR USE IN

    WET LOCATIONS 300.5(B) 300.9

    RACEWAYS IN WET LOCATIONS ABOVE GRADE300.9

    Purpose of Change: A new section has been added to clarify that the interior of enclosures or racewaysshall be considered to be a wet location if installed in wet locations above grade. All insulated conductorsand cables shall be listed for use in wet locations.

    36Ill.: pg. 3-8

    NEC: pg. 131

  • GRAYBOY, Inc. 2007

    Purpose of Change: A new exception has been added to clarify that raceways and cables shall not berequired to be mechanically secured to the equipment where installed into the bottom of open bottomequipment.

    MECHANICAL CONTINUITY - RACEWAYS AND CABLES300.12, Ex. 2

    8" 10"

    RACEWAYS

    FITTINGS

    3" (75 mm)OR LESS TABLE 408.5

    BUSBAR INSULATED TABLE 408.5

    BUSBAR NONINSULATED TABLE 408.5

    CLEARANCE 8" (200 mm) TABLE 408.5

    CLEARANCE 10" (250 mm) TABLE 408.5

    OPENBOTTOM

    FLOOR STANDING SWITCHBOARDS, PANELBOARDS,OR SIMILAR ENCLOSURES

    RACEWAYS OR CABLES NOT REQUIRED TO BE MECHANICALLY

    SECURED TO THE EQUIPMENT 300.12, Ex. 2

    37Ill.: pg. 3-9

    NEC: pg. 132

  • GRAYBOY, Inc. 2007

    GRADE

    MIN.BURIALDEPTHS

    30" (750 mm) FOR OVER 600 V TO 22 kV CIRCUITS36" (900 mm) FOR OVER 22 kV TO 40 kV CIRCUITS42" (1000 mm) FOR CIRCUITS OVER 40 kV

    WARNING RIBBON

    12" (300 mm)MINIMUM

    30" (750 mm) TOP OF CONDUIT

    MINIMUM COVERa REQUIREMENTSTABLE 300.50d

    Purpose of Change: A new superscript d has been added to Table 300.50 to require direct-buried cables that are notconcrete-encased, protected by concrete or sleeved with proper protection and are buried at least 30 in. (750 mm) ormore below grade must have location identified by warning ribbon that is installed in the trench at least 12 in. (300mm) above the cables.

    38Ill.: pg. 3-13

    NEC: pg. 137

  • GRAYBOY, Inc. 2007

    NOTE: FEDERAL AVIATION ADMINISTRATION(FAD) ADVISORY CIRCULARS (ACS) PROVIDEADDITIONAL PRACTICES AND METHODS FORAIRPORT LIGHTING.

    AIRFIELD LIGHTING SERIES CIRCUITS 310.7, Ex. 2 AND FPN TO Ex. 2

    5 kV SHIELDED CABLE POWERED BY REGULATORS 310.7, Ex. 2 AND FPN TO Ex. NO. 2

    DIRECT BURIAL CONDUCTORS310.7, Exception No. 2 AND FPN TO EXCEPTION NO. 2

    Purpose of Change: A new exception and FPN has been added to clarify that ungrounded airfieldlighting series circuits may be unshielded where rated up to 5000 volts and powered by regulators.

    39Ill.: pg. 3-14

    NEC: pg. 139

  • GRAYBOY, Inc. 2007

    CB

    ORSWITCH

    ROOF

    EMT ON ROOF 100 F

    DISCONNECTING MEANS W/UNIT 440.14

    CONDUCTORS 10 THWN cu.

    DISTANCE ABOVEROOF TO BOTTOMOF CONDUIT 3" OUTSIDE AMBIENT 100F ADDED TEMPERATURE OF 40F

    TO 100F = 140F FOR RACEWAY

    WHAT IS THE AMPACITY OF THE 10 AWG THWN COPPERCONDUCTOR?

    FINDING AMPACITY OF CONDUCTOR

    STEP 1: FINDING A OF CONDUCTOR110.14(C); TABLE 310.1610 AWG THWN = 35 A

    STEP 2: FINDING DERATING FACTORTABLE 310.16; TABLE 310.15(B)(2)(c)OUTSIDE TEMPERATURE = 100 FDISTANCE ABOVE ROOF (3") = 40 FTOTAL = 140 F

    140 F REQUIRES 58%

    STEP 3: CALCULATING AMPERE VALUE OF CONDUCTOR35 A x 58% = 20.3 A

    SOLUTION: THE 10 AWG THWN COPPER CONDUCTORIS LIMITED TO 20.3 AMPS.

    CONDUITS EXPOSED TO SUNLIGHT ON ROOFTOPS310.15(B)(2)(c)

    Purpose of Change: A new subdivision has been added to require an additional ambient temperature to be applied forconduits exposed to sunlight on rooftops.

    40Ill.: pg. 3-16

    NEC: pg. 146

  • GRAYBOY, Inc. 2007

    120/240 VOLTS, 3-WIRE, SINGLE-PHASEDWELLING SERVICES AND FEEDERS

    310.15(B)(6)

    FEEDER CONDUCTORS SUPPLYING LIGHTING ANDAPPLIANCE BRANCH-CIRCUIT PANELBOARD INSIDEOF DWELLING UNIT COMPLY 4 AWG THWN cu. (PHASES) 8 AWG THWN cu. (NEUTRAL) TABLE 310.15(B)(6) 310.15(B)(6)

    SERVICE-ENTRANCECONDUCTORS 400 KCMIL THWN cu.

    INDIVIDUAL DWELLING UNITS IN AMULTIFAMILY DWELLING COMPLEX 310.15(B)(6)

    MAIN FEEDER-CIRCUITTO EACH APARTMENT 310.15(B)(6)

    LOAD IN EACH APARTMENT 90 A PER PHASE

    (PHASE-TO-PHASE PLUS NEUTRAL) 40 A PER NEUTRAL REQUIRES 100 AMP SERVICE TABLE 310.15(B)(6)

    Purpose of Change: This revision clarifies that the main power feeder can be the feeder(s) between themain disconnect and the panelboards (Loads associated with the dwelling unit).

    41Ill.: pg. 3-20

    NEC: pg. 147

  • GRAYBOY, Inc. 2007

    DEVICE BOX

    COIL OR LOOP OF CONDUCTORSMUST BE COUNTED TWICE 314.16(B)(1)

    NOTE: THE CALCULATION PROCEDURE IS WHERE A LOOP ORCOIL IS TWICE THE MINIMUM LENGTH REQUIRED FOR FREECONDUCTORS PER 300.14 AND SHALL BE COUNTED TWICE.

    CONDUCTOR FILL314.16(B)(1)

    Purpose of Change: This revision clarifies that each loop or coil of conductors shall be counted twice.

    42Ill.: pg. 3-24

    NEC: pg. 168

  • GRAYBOY, Inc. 2007

    20 A CBs

    MAIN

    DIRECTORY 110.22 230.70(B) 408.4

    2 GANG = 4 CONDUCTOR ALLOWANCE

    6 AWG cu. CONDUCTORS4 x 5.00 in.3 = 20 in.3 FOR DEVICE PLUSCONDUCTOR ALLOWANCE FOR EACHCONDUCTOR IN BOX

    DEVICE OR EQUIPMENT FILL314.16(B)(4)

    Purpose of Change: This revision clarifies that a device or utilization equipment wider than a single (2 in.)device box shall have double volume allowance provided for each gang.

    43Ill.: pg. 3-26

    NEC: pg. 168

  • GRAYBOY, Inc. 2007

    CONDUCTORS LARGER THAN 4 AWG BOXES SHALL BE IDENTIFIED FOR

    THEIR SPECIFIC FUNCTION 314.24(C)(2)CONDUCTORS 8, 6, OR 4 AWG BOXES SHALL HAVE AN INTERNAL

    DEPTH THAT IS NOT LESS THAN2 1/16" (52.4 mm)

    314.24(C)(3)

    CONDUCTORS 12 OR 10 AWG BOXES SHALL HAVE AN INTERNAL

    DEPTH THAT IS NOT LESS THAN1 3/16" (30.2 mm)

    WHERE THE EQUIPMENT PROJECTS REARWARDFROM THE MOUNTNG PLANE OF THE BOX BYMORE THAN 1" (25 mm), THE BOX SHALL HAVEA DEPTH NOT LESS THAN THAT OF THE EQUIPMENTPLUS 1/4" (6 mm)

    314.24(C)(4)CONDUCTORS 14 AWG AND SMALLER BOXES SHALL HAVE A DEPTH THAT IS NOT LESS

    THAN 15/16" (23.8 mm) 314.24(C)(5)

    F I R E

    DEPTH OF BOX SHALL NOT BE LESS

    THAN THE DEPTH OFTHE EQUIPMENT PLUS 1/4" (6 mm)

    314.24(C)(1)MOUNTINGPLATE

    DEPTH PROJECTS MORE THAN

    1 7/8" REARWARD FROMTHE MOUNTING PLATE

    314.24(C)(1)

    MINIMUM DEPTH OF BOXES FOR OUTLETS, DEVICES,AND UTILIZATION EQUIPMENT

    314.24(A) THRU (C)

    Purpose of Change: The rewrite provides requirements for the installation of large switches, receptacles, andutilization equipment into outlet and device boxes.

    44Ill.: pg. 3-28

    NEC: pg. 172

  • GRAYBOY, Inc. 2007

    BRANCH CIRCUITSPECIAL LISTED OUTLETBOX CAN SUPPORT ALUMINAIRE WEIGHING MORETHAN 50 LBS. (23 kg) LISTED AND MARKED FOR THE

    MAXIMUM WEIGHT TO BESUPPORTED

    LISTED BOX SUPPORTINGLUMINAIRE MINIMUM50 LBS. (23 kg) 314.27(A)

    CEILING CHANDELIER

    LAMPS

    BOXES AT LUMINAIRE OUTLETS314.27(A) AND (B)

    Purpose of Change: This revision clarifies the requirements for listed boxes used for luminaire support.

    45Ill.: pg. 3-30

    NEC: pg. 172

  • GRAYBOY, Inc. 2007

    NOTE: UTILIZATION EQUIPMENT HEAVIER THAN 50 LBS. SHALL BESUPPORTED INDEPENDENT OF THE OULET BOX, UNLESS LISTEDFOR GREATER WEIGHT.

    OUTLET BOX SUPPORT OF UTILIZATION EQUIPMENT MEETS

    314.27(A) AND (B) REQUIREMENTS OTHER THAN CEILING-SUSPENDED (PADDLE) FANS 314.27(E)

    UTILIZATION EQUIPMENT 50 LBS OR LESS MOUNTED TO OUTLET BOXES, NOT DEVICE BOXES

    OULET BOX NOT WEIGHING

    MORE THAN 6 LBS (3 kg) AT LEAST 2 - #6 OR

    LARGER SCREWS 314.27(E), Ex.

    UTILIZATION EQUIPMENT314.27(E) AND Ex.

    Purpose of Change: A new subsection and exception have been added to address the installation requirements forutilization equipment used with outlet boxes.

    46Ill.: pg. 3-32

    NEC: pg. 173

  • GRAYBOY, Inc. 2007

    LUMINAIRE 210.70(C)

    SWITCH 210.70(C)

    NM CABLE RUN THROUGH BORED

    HOLES OR ON RUNNING BOARDS 334.15(C)

    CRAWL SPACEENTRANCE 210.70(C)

    HVAC EQUIPMENT

    CRAWL SPACE

    ATTIC 210.70(C)

    IN UNFINISHED BASEMENTS AND CRAWL SPACES334.15(C)

    Purpose of Change: This revision clarifies that NM cable shall be protected in crawl spaces.

    47Ill.: pg. 3-44

    NEC: pg. 186

  • GRAYBOY, Inc. 2007

    CORD-AND-PLUGCONNECTEDAPPLIANCES 210.8(A)(5), Ex. 1

    BASEMENT ORCRAWL SPACE UNFINISHED

    LIGHTING OUTLET 210.70(A)

    NM CABLE (SECURED) WITHIN 12" (300 mm)

    OF THE POINT WHERETHE CABLE ENTERSTHE TUBING OR CONDUIT

    334.15(C)

    EMT(SUPPORTED) NM CABLE SHEATH

    SHALL EXTEND THROUGH CONDUIT OR TUBINGINTO THE OUTLET OR DEVICE BOX NOT LESSTHAN 1/4" (6 mm)

    334.15(C)

    NOTE: METAL CONDUIT, TUBING, AND METALOUTLET BOXES SHALL BE CONNECTED TO ANEQUIPMENT GROUNDING CONDUCTOR.

    IN UNFINISHED BASEMENT AND CRAWL SPACES334.15(C)

    Purpose of Change: This revision clarifies the installation requirements for NM cable in an unfinishedbasement or crawl space where the NM cable is installed in a conduit or tubing for protection.

    48Ill.: pg. 3-46

    NEC: pg. 186

  • GRAYBOY, Inc. 2007

    WOOD FRAMING IS FIRE- ORDRAFT-STOPPED USING THERMALINSULATION, CAULK, OR SEALINGFOAM PER 334.80.

    CABLES

    CABLES WITH CURRENT-CARRYING CONDUCTORSARE INSTALLED, WITHOUTMAINTAINING SPACINGBETWEEN CABLES 334.80

    CONDUCTORS TABLE 310.15(A)(2)(a)

    EACH CABLE HAS TWO OR MORECURRENT-CARRYING CONDUCTORS 334.80

    APPLY THE ADJUSTMENTFACTORS FOR EACH CONDUCTOR 310.15(B)(2)(a)

    NOTE: THE PROVISIONS OF310.15(A)(2), Ex. DOES NOTAPPLY.

    AMPACITY334.80

    Purpose of Change: This revision clarifies that where more than two NM cables containing two or more current-carryingconductors are installed, without maintaining spacing between cables, the provisions of 310.12(A)(2), Ex. shall not apply.The term bundled has been deleted since the use of bundled caused a lot of controversy as to what constitutedbundled conductors. The term caulk was added since it is a common method of fire or draft stopping.

    49Ill.: pg. 3-48

    NEC: pg. 187

  • GRAYBOY, Inc. 2007

    NOTE: IMC SHALL BE PERMITTED TO BE UNSUPPORTED WHERE THERACEWAY IS NOT MORE THAN 18 IN. (450 mm) IN LENGTH ANDREMAINS IN UNBROKEN LENGTHS (WITHOUT A COUPLING).

    DEVICE (RECEPTACLE) 314.23 342.30(C)

    THREADED HUB ORTHREADED ENCLOSURE 314.23

    H

    N

    METER

    SERVICEEQUIPMENT 230.70(A) - (C)

    THREADED HUB ORTHREADED ENCLOSURE 314.23

    SERVICE-ENTRANCECONDUCTORS

    18" (450 mm)OR

    LESS

    UNSUPPORTED RACEWAYS342.30(C)

    Purpose of Change: A new subsection has been added to permit IMC to be unsupported where the raceway isnot more than 18 in. (450 mm) in length and remains in unbroken lengths (without a coupling), where oversized,concentric or eccentric knockouts are not encountered.

    50Ill.: pg. 3-57

    NEC: pg. 192

  • GRAYBOY, Inc. 2007

    CINDER FILL GALVANIZED STEEL,

    STAINLESS STEEL, ANDRED BRASS RMC

    ATMOSPHERIC CONDITIONS AND OCCUPANCIES ALL GALVANIZED STEEL AND STAINLESS STEEL RMC RED BRASS RMC FOR DIRECT BURIAL AND SWIMMING

    POOL APPLICATIONS ALUMINUM RMC WHERE JUDGED SUITABLE FOR THE

    ENVIRONMENT 344.10(A)(1) - (A)(4)

    CORROSIVE ENVIRONMENTS GALVANIZED STEEL, STAINLESS STEEL, AND RED BRASS

    RMC, ELBOWS, COUPLINGS, AND FITTINGS SHALL BEPERMITTED TO BE INSTALLED IN CONCRETE, IN DIRECTCONTACT WITH THE EARTH, OR IN AREAS SUBJECT TOCORROSIVE INFLUENCES WHERE PROTECTED BYCORROSION PROTECTION AND JUDGED SUITABLE FORTHE CONDITION

    ALUMINUM RMC SHALL BE PROVIDED WITH APPROVEDSUPPLEMENTARY CORROSION PROTECTION

    344.10(B)(1); (B)(2)

    USES PERMITTED344.10(A) THRU (C)

    Purpose of Change: This revision clarifies the uses permitted for galvanized, stainless, red brass,and aluminum RMC and the requirements for additional corrosion protection where necessary.

    51Ill.: pg. 3-59

    NEC: pg. 193

  • GRAYBOY, Inc. 2007

    BRICKFMC NOT PERMITTED INSTALLED IN

    WET LOCATION

    SUPPORTS RECEPTACLEBOX

    USES NOT PERMITTED348.12(1)(1)

    Purpose of Change: This revision clarifies that FMC shall not be permitted to be installed in any wet locations.

    52Ill.: pg. 3-63

    NEC: pg. 195

  • GRAYBOY, Inc. 2007

    Purpose of Change: A new article has been added for reinforced thermosetting resin conduit (Type RTRC).

    REINFORCED THERMOSETTINGRESIN CONDUIT: TYPE RTRC

    ARTICLE 355

    TYPE RTRC CONDUIT WITH ASSORTEDFITTINGS PER ARTICLE 355

    LISTING REQUIREMENTS 355.6

    USES PERMITTED 355.10

    SIZE 355.20

    NUMBER OF CONDUCTORS 355.22

    CONSTRUCTION 355.100

    NUMBER OF BENDS 355.26

    JOINTS 355.48

    SPLICES AND TAPS 355.56

    MARKING 355.120

    GROUNDING 355.60

    THIS NEW ARTICLE IS DIVIDED INTO THREE PARTS:

    PART I GENERALPART II INSTALLATIONPART III CONSTRUCTION SPECIFICATIONS

    USES NOT PERMITTED 355.12

    53Ill.: pg. 3-76

    NEC: pg. 203

  • GRAYBOY, Inc. 2007

    COVERS SECURELY FASTENED 376.100(D)

    SMOOTHLY ROUNDED EDGES SUITABLE BUSHINGS SHIELDS FITTINGS HAVING SMOOTH

    ROUNDED EDGES 376.100(C)

    ELECTRICAL ANDMECHANICALCONTINUITY 376.100(A)

    SUBSTANTIALCONSTRUCTION A COMPLETE ENCLOSURE SUITABLY PROTECTED

    FROM CORROSION CORNER JOINTS SHALL

    BE MADE TIGHT 376.100(B)

    CONSTRUCTION376.100(A) THRU (D)

    Purpose of Change: A new section has been added for the construction requirements of a wireway.

    54Ill.: pg. 3-92

    NEC: pg. 220

  • GRAYBOY, Inc. 2007NOTE: CONCEALABLE NONMETALLIC EXTENSIONS AND ASSOCIATED FITTINGS AND DEVICES SHALL BE LISTED.

    OUTER INSULATOR GROUNDING CONDUCTOR G1

    INSULATOR GROUNDED (NEUTRAL) CONDUCTOR H1

    INSULATOR UNGROUNDED (PHASE) CONDUCTOR H

    INSULATOR GROUNDED (NEUTRAL) CONDUCTOR N2

    OUTER INSULATOR GROUNDING CONDUCTOR G2

    CONCEALABLE NONMETALLIC EXTENSION

    PROTECTIVE LAYERED FLATWIRE

    STARTING/SOURCE TAP DEVICE SUPPLEMENTARY OVERCURRENT PROTECTION GFCI-PROTECTION MISWIRE PROTECTION ARC IGNITION PROTECTION 382.6

    LOADSIDE EXTENSIONSAND DEVICES 382.6

    LISTING REQUIREMENTS382.6

    Purpose of Change: New sections have been added to address the listing requirements for concealablenonmetallic extensions and associated fittings and devices.

    55Ill.: pg. 3-94

    NEC: pg. 223

  • GRAYBOY, Inc. 2007

    Purpose of Change: A new subsection has been added to address the installationrequirements for multipole snap switches.

    MULTIPOLE SNAP SWITCHES404.8(C)

    MULTIPOLE SNAP SWITCH LISTED MARKED AS TWO-CIRCUIT

    OR THREE-CIRCUIT SWITCH404.8(C)

    SUPPLIED BY MORETHAN ONE CIRCUIT 404.8(C)

    NOTE 2: WHERE USING TWO CIRCUITS ON A SINGLE MULTIPOLE SWITCH,COMPLIANCE WITH 210.7(B) IS NECESSARY.

    NOTE 1: MULTIPOLE SNAP SWITCHES SHALL ALSO BE PERMITTED IN THISTYPE OF APPLICATION WHERE THE RATING IS NOT LESS THAN THE NOMINALLINE-TO-LINE VOLTAGE OF THE SYSTEM SUPPLYING THE CIRCUITS.

    56Ill.: pg. 4-6

    NEC: pg. 256

  • GRAYBOY, Inc. 2007

    NOTE: ENCLOSURE IS EQUIPPED WITH IDENTIFIED, SECURELY INSTALLEDBARRIERS BETWEEN ADJACENT DEVICES.

    BARRIER 406.4(G) 404.8(B)

    120 VOLTRECEPTACLE 406.4(G)

    SWITCHES 404.8(B)

    480 V

    VOLTAGE BETWEEN ADJACENT DEVICES406.4(G)

    BARRIER 404.8(B)

    277 VOLTPHASE A

    277 VOLTPHASE B

    120-VOLTCIRCUIT

    Purpose of Change: A new subsection has been added to address the hazard for receptacles, switches,and other devices where the voltage exceeds 300 volts between adjacent devices.

    57Ill.: pg. 4-10

    NEC: pg. 260

  • GRAYBOY, Inc. 2007

    TYPES OF RECEPTACLE

    5-15 5-20 6-15 6-20

    SEE ANSI/NEMAWD 6-2002

    TYPICAL DAMPLOCATION

    TYPICAL WETLOCATION

    DAMP LOCATIONS406.8(A)

    NONLOCKINGRECEPTACLES LISTED WEATHER-

    RESISTANT TYPE 406.8(A)

    ALL NONLOCKINGRECEPTACLES LISTEDWEATHER-RESISTANTTYPE

    Purpose of Change: This revision provides requirements that all nonlocking 15- and 20-ampere, 125- and250-volt receptacles must be a listed weather-resistant type.

    58Ill.: pg. 4-12

    NEC: pg. 260

  • GRAYBOY, Inc. 2007

    RECEPTACLE WEATHERPROOF

    ENCLOSURE 406.8(B)(1), Ex.

    15- AND 20-AMPERE, 125- THROUGH 250-VOLTRECEPTACLES IN A WET LOCATION

    406.8(B)(1), Ex.

    Purpose of Change: A new exception has been added to permit receptacles installed in wetlocations subject to high pressure spray washing to have an enclosure that is weatherproofwhen the attachment plug is removed.

    59Ill.: pg. 4-14

    NEC: pg. 261

  • GRAYBOY, Inc. 2007

    TAMPER-RESISTANT RECEPTACLE LOCATIONS

    KITCHEN BATHROOMS FAMILY ROOM OUTDOORS LIVING ROOM LAUNDRY PARLOR BASEMENTS LIBRARY GARAGES DEN HALLWAYS SUNROOM BEDROOMS RECREATION ROOM

    SINK

    OVE

    N

    REF.SPACE

    ISLAND

    KITCHEN

    PANTRYDINING ROOM

    BREAKFAST ROOM

    GFCI

    DW

    RECEPTACLES TAMPER-RESISTANT

    TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS406.11

    Purpose of Change: A new section has been added to require tamper-resistant receptacles in dwellingunits for locations specified in 210.52.

    60Ill.: pg. 4-16

    NEC: pg. 261

  • GRAYBOY, Inc. 2007

    WEATHERHEAD 230.54

    SERVICE DROP 230.23

    POINT OFATTACHMENT 230.26 UTILITY

    TRANSFORMER 3 = 240 V/120 V

    HIGH LEG HIGH LEG =

    208 V TO GROUND

    SERVICE EQUIPMENT 230.70(A) - (C)

    METER BASE 90.2(B)(5)

    HIGH-LEG COLORED ORANGE OR OTHER SUITABLE MEANS

    HIGH-LEG (HL) IS PHASE B THE CENTER LEG LEGIBLY AND PERMANENTLY

    FIELD-MARKED CAUTION ___ PHASE HAS ___

    VOLTS TO GROUND 408.3(F) 230.66

    230.56 215.8 408.3(E)

    HIGH-LEG B-PHASE

    HIGH-LEG B-PHASE

    HIGH-LEG IN PANEL B-PHASE ORANGE

    NEC LOOP

    HIGH-LEG IDENTIFICATION408.3(F)

    HIGH-LEG (HL) IS PHASE CIN SELF-CONTAINEDMETER BASE

    Purpose of Change: A new subsection has been added to require the high-leg to be legibly and permanentlyfield-marked in the switchboard or panelboard.

    61Ill.: pg. 4-18

    NEC: pg. 262

  • GRAYBOY, Inc. 2007

    INDIVIDUAL PROTECTIONNOT REQUIRED PROTECTED ON ITS

    SUPPLY SIDE 408.36, Ex. 2

    OCPD PANELBOARD MORE THAN

    42 OCPDs 408.36, Ex. 2

    CB COUNTINGPROCEDURE

    SP COUNTS AS 1DP COUNTS AS 23P COUNTS AS 3

    SINGLE MAIN DISCONNECTIN ONE ENCLOSURE 230.71(A) 408.36

    PANELS WITH MAINCBs

    TWO TO SIX DISCONNECTSIN SINGLE OR SEPARATE ENCLOSURES 408.36, EX. 1 230.71(A)GROUPING 230.72(A)

    PANEL WITH MAIN CBFUSED DISCONNECT

    OVERCURRENT PROTECTION408.36, Ex. 1 AND Ex. 2

    NOT LIMITED TO 42 CIRCUITS

    Purpose of Change: This revision clarifies the permitted methods for providing protection of a panelboardand deletes the definition of power panelboards and lighting and appliance branch circuit panelboards.

    62Ill.: pg. 4-22

    NEC: pg. 263

  • GRAYBOY, Inc. 2007

    SP COUNTS AS 1DP COUNTS AS 23P COUNTS AS 3

    CB COUNTINGPROCEDURE

    15 A 20 A

    15 A 20 A

    15 A

    15 A 20 A

    20 A

    2PCB

    SPCB

    DPCB

    PANELBOARD DESIGNED, RATED, AND LISTED FOR

    THE MAXIMUM NUMBER OFOVERCURRENT DEVICES

    408.54

    MAXIMUM NUMBER OF OVERCURRENT DEVICES408.54

    Purpose of Change: The maximum number of overcurrent devices that a panel was designed, rated,and listed to contain has been relocated to Part IV dealing with construction of panelboards.

    63Ill.: pg. 4-25

    NEC: pg. 264

  • GRAYBOY, Inc. 2007

    NOTE 2: LUMINAIRES LOCATED IN THIS ACTUAL DIMENSIONOF TUB OR SHOWER AND WITHIN 8 FEET SHALL BE MARKEDFOR DAMP OR MARKED FOR WET LOCATIONS WHERE SUB-JECT TO SHOWER SPRAY.

    NOTE 1: NO CORD, CHAIN, OR CABLE TYPE LUMINAIRESSHALL BE INSTALLED PER 410.10(D).

    BATHTUB

    VERTICAL

    LUMINAIRE

    8' (2.5 m)

    VERTICAL ACTUAL OUTSIDE DIMENSION

    OF THE BATHTUB OR SHOWER 410.10(D)

    MUST BE MARKEDDAMP OR WET

    BATH AND SHOWER AREAS410.10(D)

    Purpose of Change: This revision clarifies that the luminaires located within the actual outside dimension of thebathtub or shower to a height of 8 ft. (2.5 m) vertically from the top of the bathtub rim or shower threshold to bemarked damp or if subject to shower spray, marked wet location.

    64Ill.: pg. 4-32

    NEC: pg. 268

  • GRAYBOY, Inc. 2007

    RECESSEDINCANDESCENT,

    FLUORESCENT, OR LEDLUMINAIRES

    12" MIN

    6" MIN

    SOLIDLENS

    24"

    NEC 410.8(D)(3); (4)ST

    OR

    AGE

    AREA

    SURFACE-MOUNTEDINCANDESCENT OR

    LED LUMINAIRES

    SURFACE-MOUNTEDFLUORESCENT

    LUMINAIRES

    12" MIN 12" MIN

    SHELF

    24" 24"

    SHELF12" MIN 6" MIN

    NEC 410.8(D)(1) NEC 410.8(D)(2)

    ENCLOSEDTYPE

    STO

    RAG

    EAR

    EA

    UN

    OBS

    TRU

    CTE

    DTO

    FLO

    OR

    STO

    RAG

    EAR

    EA

    SURFACE-MOUNTEDFLUORESCENT OR LED

    LUMINAIRES

    NEC 410.8(D)(5)

    STO

    RAG

    EAR

    EA

    SHELF

    IDENTIFIEDFOR THIS USE

    LUMINAIRES IN CLOTHES CLOSETS410.16(D)(1) THRU (D)(5)

    CLOTHING RODSURFACE-MOUNTEDFLUORESCENTIDENTIFIED FORTHIS USE

    Purpose of Change: This revision clarifies the installation requirements for surface-mounted incandescent,fluorescent, or LED luminaires, and surface-mounted fluorescent or LED luminaires identified for the use whereinstalled within the storage space.

    65Ill.: pg. 4-34

    NEC: pg. 269

  • GRAYBOY, Inc. 2007

    INCANDESCENTLIGHTS 410.130(G)

    DOESNT APPLY

    FLUORESCENTLIGHTS

    MULTIWIRE BRANCH CIRCUITS 410.130(G)

    LOCKOUT/TAGOUTOF SWITCH NFPA 70E

    PERSONNEL REPLACINGDEFECTIVE BALLAST 410.130(G), Ex. 5

    DISCONNECTING MEANS EXTERNAL TO LUMINAIRE SHALL BE A SINGLE DEVICE LOCATED IN SIGHT OF LUMINAIRE SHALL SIMULTANEOUSLY BREAK ALL THE

    SUPPLY CONDUCTORS OF THE BALLAST,INCLUDING THE GROUNDED (NEUTRAL) CONDUCTOR

    410.130(G)

    BALLAST

    DISCONNECTING MEANS410.130(G)

    Purpose of Change: This revision clarifies that the disconnecting means for multiwire branch circuits shallsimultaneously break all the supply conductors of the ballast, including the grounded (neutral) conductor.

    66Ill.: pg. 4-40

    NEC: pg. 275

  • GRAYBOY, Inc. 2007

    NOTE: THE LUMINAIRES, POWER SUPPLY,AND LUMINAIRE FITTINGS (INCLUDINGTHE EXPOSED BARE CONDUCTORS) OFAN EXPOSED BARE CONDUCTOR LIGHT-ING SYSTEM SHALL BE LISTED FOR THEUSE AS PART OF THE SAME IDENTIFIEDLIGHTING SYSTEM.

    ASSEMBLY OF LISTED PARTS

    LOW VOLTAGE LUMINAIRES LOW VOLTAGE LUMINAIRE POWER SUPPLY CLASS 2 POWER SUPPLY LOW VOLTAGE LUMINAIRE FITTINGS CORD (SECONDARY CIRCUIT) THAT THE LUMINAIRES AND POWER SUPPLY

    ARE LISTED FOR USE WITH CABLE, CONDUCTORS IN CONDUIT, OR OTHER FIXED WIRING METHOD FOR

    THE SECONDARY CIRCUIT

    LIGHTING SYSTEMS RATED AT 30 VOLTS OR LESSSHALL BE LISTED AS A COMPLETE SYSTEM. 411.3BRANCH-CIRCUIT SHALLBE 20 A OR LESS

    210.19(A) 210.20(A) 411.6

    PRIMARY SECONDARY SEC. CIRCUITS 411.2

    ISOLATINGTRANSFORMER 411.3

    LAMPSONE OR MORESECONDARYCIRCUITS

    ISOLATEDPOWERSUPPLY 30 V OR LESS 411.3

    411.3 110.3(B) 90.7 ARTICLE 100

    LOAD OF SECONDARY CIRCUIT 25 A OR LESS 411.2

    NEC LOOP

    LISTING REQUIRED411.3(A); (B)

    Purpose of Change: This revision clarifies that the various types of lighting systems operating at 30 volts or less are either alisted low voltage lighting system or a lighting system assembled from listed parts.

    67Ill.: pg. 4-46

    NEC: pg. 278

  • GRAYBOY, Inc. 2007

    OLDER VENDING MACHINE MANUFACTURED OR REMANUFACTURED

    PRIOR TO JANUARY 1, 2005 SHALL BE CONNECTED TO GFCI-PROTECTED OUTLET 422.51

    VENDING MACHINE SELF-SERVICE DEVICE THAT DISPENSES

    PRODUCTS OR MERCHANDISE WITHOUT THENECESSITY OF REPLENISHING THE DEVICEBETWEEN EACH VENDING OPERATION

    DESIGNED TO REQUIRE INSERTION OF ACOIN, PAPER CURRENCY, TOKEN, CARD,KEY, OR RECEIPT OF PAYMENT BYOTHER MEANS

    422.51

    CORD-AND-PLUG CONNECTED VENDING MACHINES422.51

    Purpose of Change: This revision clarifies that older vending machines manufactured or remanufacturedbefore January 1, 2005, must be connected to a GFCI-protected outlet.

    68Ill.: pg. 4-52

    NEC: pg. 283

  • GRAYBOY, Inc. 2007

    Step 1: Finding FLA430.6(A)(1); Table 430.25050 HP = 65 A

    Step 2: Finding percentage430.52(C)(1), Ex. 2(c); Table 430.52Max. size = 400%

    Step 3: Calculating max. size430.52(C)(1), Ex. 2(c)Max. size = 65 A x 400% = 260 A

    Step 5: Selecting inverse time circuit breaker240.6(A)Max. size = 250 A

    Solution: The maximum size inverse time circuitbreaker is 250 amps.

    INVERSE TIME CIRCUIT BREAKER

    INVERSE TIMECIRCUIT BREAKER 430.52(C)(1), Ex. 2(c)

    OLs 430.32(A)(1) 430.32(C) 430.35

    CB 430.52(C)(1) TABLE 430.52 240.4(G) 240.6(A)

    NONFUSEDDISCONNECT 430.110(A)

    50 HP MOTOR3, 460 VDESIGN B

    NAMEPLATE 62 A

    ORGEC

    GES

    MBJ

    IN ACCORDANCE WITH TABLE 430.52430.52(C)(1), Ex. 2

    Purpose of Change: This revision clarifies that where the rating specified in Table 430.52 or the ratings modified by ExceptionNo. 1 is not sufficient for the starting current of the motor, the Exception No. 2 shall be permitted to be applied.

    69Ill.: pg. 4-61

    NEC: pg. 310

  • GRAYBOY, Inc. 2007

    ALTERNATEPOWER SOURCE

    SWITCHBOARD SEPARATE VERTICAL

    SECTIONS 700.9(B)(5)(a)

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    GENERATOR 445.19(1)

    TRANSFEREQUIPMENT

    EMERGENCY NORMALLEGALLYREQUIREDSTANDBY

    70Ill.: pg. 4-82

    NEC: pg. 335

  • GRAYBOY, Inc. 2007

    ALTERNATEPOWER SOURCE WIREWAY

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    GENERATOR 445.19(2)

    TRANSFEREQUIPMENT

    EMERGENCY NORMALLEGALLYREQUIREDSTANDBY

    SEPARATE ENCLOSURES 700.9(B)(5)(b)

    GENERATORS SUPPLYING MULTIPLE LOADS445.19

    Purpose of Change: A new section has been added to provide requirements for a single generatorsupplying more than one load or multiple generators operating in parallel.

    70.2Ill.: pg. 4-82

    NEC: pg. 335

  • GRAYBOY, Inc. 2007

    FACILITY SITE HAS RESTRICTED PUBLIC ACCESS.

    QUALIFIED PEOPLESERVICE EQUIPMENT

    FACTORY ELBOWAND MARKED WITH - XWASSOCIATED FITTINGS

    SUPERVISIONON SITE

    ENCLOSURE #2 FACTORY SEALED

    CLASS 1, DIVISION 2INDUSTRIALESTABLISHMENT

    FACTORY SEALEDENCLOSURE #1

    RTRC WITH FACTORY ELBOWSAND ASSOCIATED FITTINGSMARKED WITH SUFFIX - XW

    SCH. 80 PVC CONDUIT WITHFACTORY ELBOWS ANDASSOCIATED FITTINGS.

    WIRING METHOD CAN BE

    CLASS I, DIVISION 2501.10(B)(7)

    Purpose of Change: To permit reinforced thermosetting resin conduit (RTRC) and Schedule 80 PVC incorrosion areas where RMC does not provide adequate corrosion resistance.

    71Ill.: pg. 5-9

    NEC: pg. 363

  • GRAYBOY, Inc. 2007

    WIRINGMETHODS RMC IMC MI CABLE MC/HL CABLE

    FMC OR LFMC DOES NOTCOMPLY WITH Ex. TO501.30(B) IN CLASS I,DIVISION 1 INSTALLATIONS

    LISTEDFITTINGS

    FMC OR LFMC SHALL NOT BEUSED AS THE SOLE G-FCP. EBJSHALL BE INSTALLED PER 250.102.

    TYPES OF EQUIPMENT GROUNDING CONDUCTORS501.30(B)

    CLASS I, DIVISION 1 AND 2

    Purpose of Change: To clarify the use of flexible metal conduit (FMC) and liquidtightflexible metal conduit (LFMC) as an equipment grounding conductor in classifiedlocations.

    72Ill.: pg. 5-12

    NEC: pg. 367

  • GRAYBOY, Inc. 2007

    NOTE 2: SINGLE-COMPONENTSTORED ENERGY SOURCES WITH: WELL-DEFINED PARAMETERS

    SUCH AS SMALL CAPACITORSAND INDUCTORS CAN BE SIMPLEAPPARATUS

    NOTE 3: FOR OVERALL SAFETY OFTHE SYSTEM, THE VALUES OFSUCH COMPONENTS SHALL BE

    NOTE 1: THE TERM BE HASBEEN DELETED FROM THE FPN.

    FUSE RESISTOR

    ENERGY PATH TO GROUNDUNDER FAULT CONDITION

    ZENERDIODE

    HAZARDOUSLOCATION

    NON-HAZARDOUSLOCATION

    GES

    INTRINSICALLY SAFECIRCUIT LOOP

    SIMPLE APPARATUS504.2

    Purpose of Change: To include single components in simple circuits well-defined parameters.

    73Ill.: pg. 5-26

    NEC: pg. 381

  • GRAYBOY, Inc. 2007

    BARRIER

    GES

    RACEWAY

    CABLES

    CABLE TRAY

    NOTE 1: IF PASSING THROUGH A DIVISION 2 OR ZONE 2LOCATION INTRINSICALLY SAFE AND NONINCENDIVE FIELDWIRING CIRCUITS CAN BE RUN IN THESE WIRING METHODS.

    CLASS I, DIVISION 2(CI, D2) LOCATION

    RACEWAY, CABLETRAY OR CABLE 504.30(A)(1), Ex. 3

    INTRINSICALLY SAFECIRCUITS AND NONINCENDIVECIRCUITS ROUTED TOGETHER

    HAZARDOUS LOCATION SAFE AREA

    NOTE 2: WIRINGMETHODS AREPASSING THROUGHCLASS I, DIVISION 2LOCATION.

    NOTE 3: NONINCENDIVE FIELDWIRING CIRCUITS ARE DESCRIBEDIN: 501.10(B)(3) 502.10(B)(3) 503.10(B)(3) 505.15(C)(1)(g) AND 506.15(C)(7)SEE FPN TO 504.30(A)(1), Ex. 4

    FROM NONINTRINSICALLY SAFE CIRCUIT CONDUCTORS504.30(A)(1), Ex. 3

    Purpose of Change: To provide requirements for running intrinsically safe circuits (ISCs) and nonincendive (NCCS) circuits together.

    74Ill.: pg. 5-28

    NEC: pg. 382

  • GRAYBOY, Inc. 2007NOTE: SEALS SHALL BE IDENTIFIED FOR THE PURPOSE OF MINIMIZING PASSAGEOF GASES, VAPORS, OR DUST UNDER NORMAL OPERATING CONDITIONS.

    HAZARDOUS LOCATION 504.70 TABLE 514.3(B)(1)

    NONHAZARDOUS LOCATION

    READOUT PANELWITH BARRIERS

    SEAL 514.9(B)

    SEAL 504.70

    SEALS 504.70 514.9(A)

    SEALS ARE NOT REQUIREDTO BE EXPLOSIONPROOFOR FLAMEPROOF 504.70

    POWER-CIRCUIT 430.22(A)

    INTRINSICALLYSAFE CIRCUIT 504.2

    SEALING504.70

    Purpose of Change: This revision clarifies that seals do not have to be explosionproof or flameproof.

    75Ill.: pg. 5-32

    NEC: pg. 383

  • GRAYBOY, Inc. 2007

    DEDICATED VENTILATIONAND EXHAUST SYSTEM

    AIRCRAFT HANGAR

    SPRAYING

    DIPPINGPROCESS

    TANK

    COATINGPROCESS

    EXHAUST DUCT

    NOTE: AN AIRCRAFT HANGERCONSTRUCTED FOR THE EXPRESSPURPOSE OF:

    SPRAY COATING DIPPING

    MUST BE PROVIDED WITH

    DEDICATED VENTILATIONSUPPLY AND

    EXHAUST BASED ON DEFINITIONIN 513.2

    AIRCRAFT PAINTING HANGER513.2

    Purpose of Change: To include requirements for painting processes in aircraft hangars.

    76Ill.: pg. 5-52

    NEC: pg. 407

  • GRAYBOY, Inc. 2007

    10' 5'

    5'5'

    5'

    ALSO, SEENFPA 33

    5' ABOVE ENGINEENCLOSURE AND WING 513.3(C)

    5' FROM FUELTANK IN WINGS 513.3(C)

    SPRAY OPERATIONS IN AIRCRAFT HANGARCONSTRUCTED LIKE A HUGE PAINT BOOTH 513.3(C)(2)

    VICINITY OF AIRCRAFT513.3(C)(2)

    Purpose of Change: To include requirements for large aircraft hangars constructed like a paint booth.

    77Ill.: pg. 5-53

    NEC: pg. 408

  • GRAYBOY, Inc. 2007

    TASK ILLUMINATION BATTERY CHARGER FORBATTERY POWERED LIGHTS AND SELECTEDRECEPTACLES FOR GENERATOR SET ANDTRANSFER SWITCH LOCATIONS

    ALARM AND ALERTING SYSTEMS(1) FIRE ALARMS(2) ALARMS REQUIRED FOR SYSTEMS USED

    FOR THE PIPING OF NONFLAMMABLEMEDICAL GASES

    (3) MECHANICAL CONTROL, AND OTHERACCESSORIES REQUIRED FOR EFFECTIVELIFE SAFETY SYSTEMS OPERATION

    GENERATOR SET ACCESSORIES

    THE FOLLOWING SHALL BE PERMITTED TO BECONNECTED TO THE LIFE SAFETY BRANCH:

    LIFE SAFETY BRANCH517.32(C); (E); (F)

    Purpose of Change: There revisions clarify the items permitted to be connected to the life safety branch.

    78Ill.: pg. 5-58

    NEC: pg. 433

  • GRAYBOY, Inc. 2007

    COLOR CODEGREEN, GREEN WITHYELLOW STRIPE 517.13(B) 517.18(B) 517.19(B)(2)

    GROUNDED (N) SLOTLONG SLOT

    SILVER TERMINAL (N)

    COLOR CODE ORANGE WITH A

    DISTINCTIVECOLORED STRIPEOTHER THAN WHITE,GREEN, OR GRAY

    517.160(A)(5)(1)

    UNGROUNDED (PHASE) SLOTSHORT SLOT

    BRASS TERMINAL (H)

    COLOR CODE BROWN WITH A

    DISTINCTIVE COLOREDSTRIPE OTHER THANWHITE, GREEN, OR GRAY

    517.160(A)(5)(2)GREENTERMINAL

    CONDUCTOR IDENTIFICATION517.160(A)(5)

    Purpose of Change: This revision clarifies that striped isolated conductors providesproper identification for isolated power systems.

    79Ill.: pg. 5-62

    NEC: pg. 442

  • GRAYBOY, Inc. 2007

    PART III - CONTROL CIRCUIT WIRING METHODS

    522.20522.21522.22522.23522.24

    522.25522.28

    CONDUCTORS, BUSBARS, AND SLIP RINGSCONDUCTOR SIZINGCONDUCTOR AMPACITYOVERCURRENT PROTECTION FOR CONDUCTORSCONDUCTORS OF DIFFERENT CIRCUITS IN THE SAME CABLE, CABLE TRAY, ENCLOSURE,OR RACEWAYUNGROUNDED CONTROL CIRCUITSCONTROL CIRCUITS IN WET LOCATIONS

    PART II - CONTROL CIRCUIT

    522.10 POWER SOURCES FOR CONTROL CIRCUITS

    ARTICLE 522 - CONTROL SYSTEMS FOR PERMANENT AMUSEMENT ATTRACTIONS

    PART I - GENERAL

    SECTION HEADING

    SCOPEDEFINITIONSOTHER ARTICLESVOLTAGE LIMITATIONSMAINTENANCE

    SECTION

    522.1522.2522.3522.5522.7

    CONTROL SYSTEMS FOR PERMANENTAMUSEMENT ATTRACTIONS

    ARTICLE 522

    Purpose of Change: A new article has been added to address the requirements for control systems forpermanent amusement attractions.

    80Ill.: pg. 5-68

    NEC: pg. 453

  • GRAYBOY, Inc. 2007

    NOTE: WHERE MORE THEN FIVE CIRCUITS WITHOUT A LISTED ENERGY MANAGEMENT SYSTEMARE EMPLOYED, A 50-AMPERE 120/240 VOLT POWER SUPPLY ASSEMBLY AND A MINIMUM 50-AMPERE RATED DISTRIBUTION PANELBOARD SHALL BE USED PER 551.42(D).

    DISTRIBUTION PANELBOARDS 120 VOLTS MAXIMUM 120/240 VOLTS MAXIMUM

    LISTED FOR 30 AMP APPLICATIONS 551.42(C)

    ELECTRICAL SYSTEM 120 VOLTSMAXIMUM TWO TO FIVE 15 OR 20 AMPERE 551.42(C)

    POWER SUPPLY 30 AMPERE 551.42(C)

    TWO TO FIVE 15- OR 20-AMPERE CIRCUITS551.42(C)

    Purpose of Change: This revision clarifies that a 120 volt or 120/240 volt rated distribution panelboards shall bepermitted with a 30 amp power supply assembly.

    81Ill.: pg. 5-84

    NEC: pg. 479

  • GRAYBOY, Inc. 2007

    LIQUIDPIPING

    ELECTRICALEQUIPMENT

    WIRING METHODAND CONDUIT

    DISPENSINGUNIT

    ON SHOREGENERAL 555.21(A)CLASSIFICATION OF CLASS I,DIVISION 1 AND 2 AREAS 555.21(B)CLOSED CONSTRUCTION 555.21(B)(1)(a); (b)OPEN CONSTRUCTION 555.21(B)(2)(a); (b)

    CLASSIFICATION OF CLASS I, DIVISION 1 AND 2 AREAS555.21(B)(1); (B)(2)

    Purpose of Change: To include requirements to provide coverage of open and closed constructionmethods for docks, marinas, and piers.

    82Ill.: pg. 5-90

    NEC: pg. 501

  • GRAYBOY, Inc. 2007

    SPORTSTORE

    SHOESTORE

    CLOTHESSTORE

    BEAUTYSALON

    DRUGSTORE

    SECTION SIGN 600.2

    SECTION SIGNS SHALL BE MARKEDTO INDICATE THAT FIELD-WIRINGAND INSTALLATION INSTRUCTIONSARE REQUIRED

    1 5

    ELECTRIC SIGN SECTION

    OF

    1 5

    ELECTRIC SIGN SECTION

    2 5

    ELECTRIC SIGN SECTION

    3 5

    ELECTRIC SIGN SECTION

    4 5

    ELECTRIC SIGN SECTION

    5 5

    ELECTRIC SIGN SECTION

    OF

    OF

    OF

    OF

    OF

    SUBASSEMBLIES

    SECTION SIGNS600.4(C)

    Purpose of Change: A new section has been added to require section signs to be marked toindicate that field-wiring and installation instructions are required.

    83Ill.: pg. 6-4

    NEC: pg. 504

  • GRAYBOY, Inc. 2007

    DRIVE THRU

    ACCESS DOORWAY 3' x 2' (900 mm x 600 mm)PERMANENT WALKWAY 600.21(E)

    LIGHTING OUTLET CONTAINING A SWITCH

    OR CONTROLLED BY AWALL SWITCH

    600.21(E)

    ATTIC AND SOFFIT LOCATIONS600.21(E)

    Purpose of Change: This revision clarifies that at least one lighting outlet containing aswitch or controlled by a wall switch shall be installed in attic and soffit locations.

    84Ill.: pg. 6-15

    NEC: pg. 507

  • GRAYBOY, Inc. 2007

    FIELD INSTALLED SKELETON TUBING

    1/4" (6 mm) SPACING 600.41(C)

    DISCONNECT 600.6 404.14

    TRANSFORMER

    TRANSFORMER ENCLOSUREFLEXIBLE METALCONDUIT ARTICLE 348

    PK HOUSING

    EXTERIOR WALL

    BRANCH-CIRCUIT 600.5(A); (B) 210.19(A)(1)

    TUBE SUPPORT WITHIN 6" (150 mm)

    FROM THE ELECTRODECONNECTION

    600.41(B)

    SUPPORT600.41(B)

    1 1/2" (38 mm) SEPARATIONFROM TUBE SUPPORT FORTERMINALS 600.32(E)

    Purpose of Change: This revision clarifies that neon tubing shall be supported within 6 in. (150 mm)from the electrode connection.

    85Ill.: pg. 6-21

    NEC: pg. 509

  • GRAYBOY, Inc. 2007

    HOISTWAY

    CORD HARD USAGE OIL

    RESISTANT TYPE 6' (1.8 m) MAX 620.21(A)(1)(e)

    SUMP PUMP OROIL RECOVERY PUMP 620.21(A)(1)(e)

    PIT

    WIRING METHODS620.21(A)(1)(e)

    Purpose of Change: A new subdivision has been added to permit a sumppump or oil recovery pump to be cord- and plug-connected.

    86Ill.: pg. 6-28

    NEC: pg. 520

  • GRAYBOY, Inc. 2007

    MACHINE ROOM ARTICLE 620, PART VIII

    DISCONNECTING MEANS SHALL BE LISTED CAPABLE OF BEING LOCKED IN THE

    OPEN POSITION PROVISIONS FOR LOCKING OR ADDING A

    LOCK TO THE DISCONNECTING MEANSSHALL BE INSTALLED AND REMAIN INPLACE WITH OR WITHOUT THE LOCKINSTALLED

    620.51(A)

    10TH FLOOR

    ELEVATOR CAR

    CONTROLLER LOCATED IN HOISTWAY 620.51(C)(1)

    DISCONNECTING MEANS (ADDITIONAL) NON-FUSED LISTED CAPABLE OF BEING LOCKED IN THE

    OPEN POSITION LOCATED WITHIN SIGHT OF THE

    MOTOR CONTROLLER PROVISIONS FOR LOCKING OR

    ADDING A LOCK TO THEDISCONNECTING MEANS SHALL BEINSTALLED AND REMAIN IN PLACEWITH OR WITHOUT THE LOCK INSTALLED

    620.51(C)(1)

    NOTE: PORTABLE MEANS FOR ADDINGA LOCK TO THE SWITCH OR CIRCUITBREAKER SHALL NOT BE PERMITTED.

    ON ELEVATORS WITHOUT GENERATOR FIELD CONTROL620.51(C)(1)

    Purpose of Change: This revision clarifies that where the motor controller is located in the elevator hoistway, the disconnectingmeans required by 620.51(A) shall be located in a machinery space, machine room, control space or control room outside thehoistway; and as additional disconnecting means (non-fused) shall be located within sight of the motor controller.

    87Ill.: pg. 6-34

    NEC: pg. 524

  • G

    RAYB

    OY,Inc.2007

    POSTS

    OVERHEAD GANTRY

    ARTICLE 626 - ELECTRIFIED TRUCK PARKING SPACES

    PART I - GENERAL

    SECTION HEADING

    626.1626.2626.3626.4

    SCOPEDEFINITIONSOTHER ARTICLESGENERAL REQUIREMENTS

    PART II - ELECTRIFIED TRUCK PARKING SPACE ELECTRICAL WIRING SYSTEMS

    626.10626.11

    BRANCH CIRCUITFEEDER AND SERVICE LOAD CALCULATIONS

    PART III - ELECTRIFIED TRUCK PARKING SPACE SUPPLY EQUIPMENT

    626.22626.23626.24626.25626.26626.27

    WIRING METHODS AND MATERIALSOVERHEAD GANTRY OR CABLE MANAGEMENT SYSTEMELECTRIFIED TRUCK PARKING SPACE SUPPLY EQUIPMENT CONNECTION MEANSSEPARABLE POWER-SUPPLY CABLE ASSEMBLYLOSS OF PRIMARY POWERINTERACTIVE SYSTEMS

    PART IV - TRANSPORT REFRIGERATED UNITS (TRUs)

    626.30626.31626.32

    TRANSPORT REFRIGERATED UNITSDISCONNECTING MEANS AND RECEPTACLESSEPARABLE POWER SUPPLY CABLE ASSEMBLY

    ELECTRIFIED TRUCK PARKING SPACESARTICLE 626

    Purpose of Change: A new article has been added to address requirements for electrified truck parkingspaces.

    88Ill.: pg. 6-38

    NEC: pg. 531

  • GRAYBOY, Inc. 2007

    MAINTENANCE DISCONNECTINGMEANS SHALL BE PROVIDED FOR ALL

    UTILIZATION EQUIPMENT OTHERTHAN LIGHTING

    SHALL BE READILY ACCESSIBLEAND WITHIN SIGHT

    680.12

    DISCONNECT MUST BE LOCATED ATLEAST 5' (1.5 m) HORIZONTALLY FROMTHE INSIDE WALL OF POOL, SPA, ORHOT TUB 680.12

    5' (1.5 m)

    NOTE: A PERMANENTLY INSTALLED BARRIER BETWEENTHE OPEN WATER AND DISCONNECTING MEANS SHALL BEPERMITTED TO REDUCE THE 5 FT (1.5 m) REQUIREMENTSBUT STILL REQUIRES A 5 FT REACH PATH OR GREATER.

    MAINTENANCE DISCONNECTING MEANS680.12

    Purpose of Change: This revision clarifies the distance for the disconnecting means from open water.

    89Ill.: pg. 6-51

    NEC: pg. 561

  • GRAYBOY, Inc. 2007

    Purpose of Change: This revision clarifies the requirements for inspections, relamping or othermaintenance for underwater wet-niche luminaires.

    SERVICING680.23(B)(6)

    CABLE LENGTH SHALL ALLOWREMOVED LUMINAIRE ON POOLDECK FOR INSPECTION, RELAMPINGOR OTHER MAINTENANCE680.23(B)(6)

    WATER LEVEL

    DECK BOX 680.24(A)(2)

    TO PANELBOARD 680.23(F)

    CONDUIT 680.23(B)(2)

    WET-NICHE POOL LIGHT 680.23(B)

    NOTE: THE LUMINAIRE MAINTENANCELOCATION SHALL BE ACCESSIBLEWITHOUT ENTERING OR GOING INTHE POOL WATER.

    90Ill.: pg. 6-56

    NEC: pg. 563

  • G

    RAYB

    OY,Inc.2007

    8AWG cu. BONDINGCONDUCTOR 680.26(B)(1)(b)

    METALPOST

    METAL LADDERS,SLIDES, POSTS, ETC. 680.26(B)(3)

    WATERCIRCULATINGPUMP 680.26(B)(6)

    METALSKIMMER 680.26(B)(3)

    DIVING BOARD

    DECK

    METALDRAIN 680.26(B)(3)

    METAL LIGHTFORMING SHELL 680.26(B)(3) 8 AWG BARE SOLID CONDUCTOR INSTALLED TO

    PROVIDE A 12 IN. (300 mm) x 12 IN. (300 mm)NETWORK UNDER THE POOL AND DECK PER680.26(B)(1)(b)

    DECK BOX(IF WITHIN 5' (1.5 m) OFINSIDE WALL OF POOL) 680.26(B)(7)

    BOND POOLIN WATER 600.26(C)(3)b

    EQUIPOTENTIAL BONDING680.26(A) THROUGH (C)

    COPPER CONDUCTOR GRID

    BE CONSTRUCTED OF MINIMUM 8 AWG BARE SOLIDCOPPER CONDUCTORS BONDED TO EACH OTHER ATALL POINTS OF CROSSING

    CONFORM TO THE CONTOUR OF THE POOL AND THEPOOL DECK

    BE ARRANGED IN A 12 IN. (300 mm) BY 12 IN. (300 mm)NETWORK OF CONDUCTORS IN A UNIFORMLYSPACED PERPENDICULAR GRID PATTERN WITHTOLERANCE OF 4 IN. (100 mm)

    CONDUCTIVE POOL SHELLS

    POURED CONCRETE PNEUMATICALLY APPLIED OR SPRAYED CONCRETE CONCRETE BLOCK WITH PAINTED OR PLASTERED

    COATINGS

    ALTERNATE MEANS

    AT LEAST ONE MINIMUM 8 AWG BARE SOLID COPPERCONDUCTOR SHALL BE PROVIDED THE CONDUCTORS SHALL FOLLOW THE CONTOUROF THE PERIMETER SURFACE THE REQUIRED CONDUCTOR SHALL BE 18 TO 24 IN.(450 mm TO 600 mm) FROM THE INSIDE WALL OF THEPOOL THE REQUIRED CONDUCTOR SHALL BE SECUREDWITHIN OR UNDER THE PERIMETER SURFACE 4 TO 6IN. (100 mm TO 150 mm) BELOW THE SUBGRADE

    ALTERNATE MEANS

    VINYL LINERS FIBERGLASS COMPOSITE

    Purpose of Change: This revision clarifies the equipotential bonding requirements.

    91Ill.: pg. 6-61

    NEC: pg. 566

  • GRAYBOY, Inc. 2007

    POOL FILTER PUMP ISDOUBLE INSULATED

    NO BONDING REQUIREDFOR THESE ITEMS

    42"(1 m)MAX.

    STORABLE POOL MAXIMUM DEPTH

    42 IN. 680.2

    RECEPTACLE LOCATED AT LEAST

    6' (1.8 m) FROM THEINSIDE WALLS OFTHE POOL

    680.34

    GFCI-PROTECTION PROVIDE WITH A GFCI THAT IS AN

    INTEGRAL PART OF THE ATTACHMENTPLUG OR

    LOCATED IN THE POWER SUPPLYCORD WITHIN 12 (300 mm) OF THEATTACHMENT PLUG

    680.31

    PUMPS680.31

    Purpose of Change: This revision clarifies that storable pool cord-connected filter pumps shall be protectedwith a GFCI that is an integral part of the attachment plug or located in the power supply cord within 12 inchesof the attachment plug.

    92Ill.: pg. 6-63

    NEC: pg. 568

  • GRAYBOY, Inc. 2007

    GENERATOR 695.2

    PIPING

    FIRE PUMP

    FIRE PUMPCONTROLLER

    2-HOUR FIRERESISTANT RATING 695.6(B)(1); (B)(2)LISTING

    695.10

    CIRCUIT CONDUCTORS695.6(B)(1), (B)(2), AND (B)(3)

    Purpose of Change: This revision clarifies that fire pump supply conductors shall be protected by a 2-hour fireresistance rating if not encased in a minimum of 2 in. (50 mm) of concrete or by a listed electrical protectivesystem with a 2-hour minimum fire rating.

    93Ill.: pg. 6-80

    NEC: pg. 594

  • GRAYBOY, Inc. 2007

    EMERGENCYPOWER SOURCE 700.5(B)

    SWITCHBOARD SEPARATE VERTICAL SECTIONS 700.9(B)(5)(a)

    GENERATOR 445.19(1)

    TRANSFEREQUIPMENT

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    EMERGENCY LEGALLYREQUIREDSTANDBY

    OPTIONALSTANDBY

    94Ill.: pg. 7-3

    NEC: pg. 597

  • GRAYBOY, Inc. 2007

    EMERGENCYPOWER SOURCE 700.5(B) WIREWAY

    GENERATOR 445.19(2)

    TRANSFEREQUIPMENT

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    EMERGENCY LEGALLYREQUIREDSTANDBY

    OPTIONALSTANDBY

    FEEDER (SINGLE) SEPARATE ENCLOSURE 700.9(B)(5)(b)

    94.2Ill.: pg. 7-3

    NEC: pg. 597

  • GRAYBOY, Inc. 2007

    FEEDER (MULTIPLE)

    GENERATOR 445.19(2)

    TRANSFEREQUIPMENT

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    EMERGENCY LEGALLYREQUIREDSTANDBY

    OPTIONALSTANDBY

    FEEDER (SINGLE) SEPARATE ENCLOSURE 700.9(B)(5)(b)

    WIRING700.9(B)(5)

    Purpose of Change: A new subdivision has been added to provide wiring requirements for the emergency source.

    94.3Ill.: pg. 7-3

    NEC: pg. 597

  • GRAYBOY, Inc. 2007

    NOTE 2: IF NORMAL POWER FAILS, DIMMER SYSTEM SHALLSELECTIVELY ENERGIZE EMERGENCY BRANCH-CIRCUITS TOSUPPLY MINIMUM EMERGENCY ILLUMINATION.

    NOTE 1: LISTED CONTROL DEVICE USED TO ENERGIZEEMERGENCY LIGHTING CIRCUITS PER 700.23.

    MORE THANONE DIMMER 700.23

    DIMMER SYSTEM 700.23

    LABEL IDENTIFYINGCIRCUITS

    DIMMER SYSTEMDISCONNECTS

    FLOURESCENT LIGHTING

    HIGH-INTENSITYDISCHARGE LIGHTING

    DIMMER SYSTEMS700.23

    Purpose of Change: A new section has been added to address a dimmer systemcontaining more than one dimmer and listed for use for emergency systems.

    95Ill.: pg. 7-9

    NEC: pg. 600

  • GRAYBOY, Inc. 2007

    SERVICEEQUIPMENT

    NORMALPOWERSOURCE

    FEEDER (MULTIPLE)

    GENERATOR 445.19(2)

    AUTOMATICTRANSFERSWITCH

    ALLLOADS

    ALTERNATEPOWERSOURCE 702.5(B)

    OPTIONAL STANDBY SYSTEM

    WHERE A SYSTEM IS EMPLOYED THAT WILL AUTOMATICALLYMANAGE THE CONNECTED LOAD, THE STANDBY SOURCESHALL HAVE A CAPACITY SUFFICIENT TO SUPPLY THEMAXIMUM LOAD THAT WILL BE CONNECTED BY THE LOADMANAGEMENT SYSTEM

    702.5(B)(2)(b)

    SYSTEM CAPACITY702.5(B)

    Purpose of Change: This revision clarifies the installation of manual transfer and automatic transfer applicationsfor optional standby systems.

    96Ill.: pg. 7-11

    NEC: pg. 604

  • GRAYBOY, Inc. 2007 ARTICLE 708 - CRITICAL OPERATIONS POWER SYSTEMS (CDPS)

    PART I - GENERAL

    SECTION HEADING

    708.1708.2708.3708.4708.5708.6708.8

    SCOPEDEFINITIONSAPPLICATION OF OTHER ARTICLESRISK ASSESSMENTPHYSICAL SECURITYTESTING AND MAINTENANCECOMMISSIONING

    708.10708.11708.12708.14

    FEEDER AND BRANCH-CIRCUIT WIRINGBRANCH CIRCUIT AND FEEDER DISTRIBUTION EQUIPMENTFEEDERS AND BRANCH CIRCUITS SUPPLIED BY COPSWIRING OF HVAC, FIRE ALARM, SECURITY, EMERGENCY COMMUNICATIONSAND SIGNALING SYSTEMS

    708.20708.22708.24708.30

    SOURCES OF POWERCAPACITY OF POWER SOURCESTRANSFER EQUIPMENTBRANCH CIRCUITS SUPPLIED BY COPS

    708.50708.52708.54

    ACCESSIBILITYGROUND-FAULT PROTECTION OF EQUIPMENTCOORDINATION

    708.64 EMERGENCY OPERATIONS PLAN

    PART II - CIRCUIT WIRING AND EQUIPMENT

    PART III - POWER SOURCES AND CONNECTION

    PART IV - OVERCURRENT PROTECTION

    PART V - SYSTEM PERFORMANCE AND ANALYSIS

    Purpose of Change: A new article has been added dealing with mission critical power systems withdetailed installations for electrical power for vital infrastructures.

    97Ill.: pg. 7-13

    NEC: pg. 609

  • GRAYBOY, Inc. 2007

    CONDUCTORS(NOT FUNCTIONALLYASSOCIATED) CLASS I POWER-SUPPLY 725.48(B)(4)(1)

    NOTE: IF A BARRIER IS NOT INSTALLED, ALLOF THE CONDUCTORS SHALL BE INSTALLEDWITHIN SEPARATE MULTICONDUCTOR TYPEAC, TYPE MC, TYPE MI, OR TYPE TC CABLESAND ALL OF THE CONDUCTORS IN THECABLES SHALL BE INSULATED AT 600 VOLTS.

    BARRIER 725.48(4)

    IN CABLE TRAYS725.48(B)(4)

    Purpose of Change: This revision clarifies the permitted methods of installation for Class Icircuit conductors and power-supply conductors that are not functionally associated.

    98Ill.: pg. 7-17

    NEC: pg. 617

  • GRAYBOY, Inc. 2007

    ABANDONED CABLES SHALL BE REMOVED COMMUNICATIONS CABLES COAXIAL CABLES NETWORK-POWERED BROADBAND CABLES 800.25 820.25 830.25

    FIREWALL PENETRATIONS OPENINGS SHALL BE FIRE STOPPED

    USING APPROVED METHODS TOMAINTAIN THE FIRE RESISTANCE RATING

    800.26 820.26 830.26

    CABLE PENETRATIONS COMMUNICATIONS CABLES COAXIAL CABLES NETWORK-POWERED

    BROADBAND CABLES

    OKAY

    ABANDONED CABLES AND SPREAD OFFIRE OR PRODUCTS OF COMBUSTION

    800.25800.26

    Purpose of Change: A new section has been added to address the requirements for the prevention of thespread of fire and one has been added dealing with abandoned cables.

    99Ill.: pg. 8-4

    NEC: pg. 641

  • GRAYBOY, Inc. 2007

    Purpose of Change: A new section has been added to require a minimum of onecommunications outlet within a dwelling unit for new construction.

    DWELLING UNIT COMMUNICATIONS OUTLET800.156

    LIVINGROOM

    BD 2

    BD 3 BR 1

    BR 2BD 1

    DEN

    KITCHEN

    ATTIC

    COMMUNICATIONS OUTLET NEW CONSTRUCTION AT LEAST ONE INSTALLED CABLED TO THE SERVICE

    PROVIDER DEMARCATION POINT 800.156

    100Ill.: pg. 8-10

    NEC: pg. 647

    '2008.Changes.Ch.01.pdfSlide #190.2(B)(5)bBonded (Bonding)Branch-Circuit Overcurrent DeviceClothes ClosetElectrical Power ProductionEquipmentGrounding Conductor, EquipmentGroundGroundedGrounded, EffectivelyGrounding ElectrodeGrounding Electrode ConductorIntersystem Bonding TerminationLuminaireManufactured HomesNeutral ConductorQualified PersonShort-Circuit Current Rating.1Short-Circuit Current Rating.2Short-Circuit Current Rating.3Surge ArresterUngroundedUtility-Interactive Inverter110.12(A)110.16.1110.16.2110.20.1110.20.2110.22(A)-(C)110.26(C)(1); (C)(2)110.26(C)(3)110.33(A)110.33(A)(3)

    '2008.Changes.Ch.02-1.pdf200.2210.4(B)210.4(D)210.5(C)210.8(A)(2)-(A)(5)Slide #6210.8(B)(4)210.12(B)210.12(B), Ex.210.12(B), Ex. 2210.19(A)(1), EX. 2210.52(C)210.52(E)(1) - (E)(3)210.62215.2(A)(1), Ex. 2-1215.2(A)(1), Ex. 2-2215.6.1215.6.2215.12(C)225.18225.39230.24(B)230.40, Ex. 1230.44, Ex.230.71(B)230.95, Ex. 2230.205(A)240.4(D)240.21(C)(2)(4)240.21(C)(3)240.21(H)240.24(F)240.86(A).1240.86(A).2240.91(A); (B)240.92(B)250.6(A)250.8(A); (B)250.20(A)(3)250.20(D)250.21(B)250.22(5)250.24(D)250.28(D)(1) - (D)(3)250.30(A)250.30(A)(4)250.32(A)250.32(B); Ex.

    '2008.Changes.Ch.02-2.pdf250.35250.36250.52(A)(2)250.52(A)(3)250.52(A)(5)250.54250.56250.64(D)(1) - (D)(3)250.64(E)250.68(A), Ex. 2250.94250.104(A)(2)250.104(D)(1), Ex. 1250.106, FPN 1250.112(I)250.119, Ex.250.119(A)250.122(C)250.122(F)250.146250.146(A)250.146(D)250.166280.2285.23(A); (B)285.24285.25

    '2008.Changes.Ch.03.pdf300.4(E)300.4(G)300.5(B)300.9300.12, Ex. 2300.11(A)(2)Table 300.50, Note 3Table 300.50d310.7, FPN310.15(B)(2)(c).1310.15(B)(3)310.15(B)(6)314.16314.16(B)(1)314.16(B)(4)314.24(A)-(C)314.27(A); (B)314.27(E); Ex.314.28(A)320.10(1)328.10(3); Ex.330.10(B)(4)334.12(A)(1), Ex.334.15(B)334.15(C).1334.15(C).2334.80.1334.80.2336.10(7), Ex.338.12(A); (B)342.30(C)344.10(A)-(C)344.30(C)348.12(1)(1)348.30(A), Ex. 1348.60350.30(A), Ex. 1350.30(A), Ex. 2350.60352.30(C)Article 355356.10(7)358.30(C)362.30(A), Ex. 3366.2366.23(A)376.22(A); (B)376.56(B)(4)376.100382.6382.10(A)382.10(C)382.42(B)392.8(A)392.9(A)(1)392.11(C)(1); (C)(2)396.30(A)-(C)

    '2008.Changes.Ch.04.pdf402.11404.4404.8(C)404.9(B)(1)406.4(G)406.8(A)406.8(B)(1), Ex.406.11408.3(F)408.4408.36, Ex. 1; Ex. 2408.54408.55, Ex. 1408.58409.2410.10(D)410.16(D)(1) - (D)(5)410.62(C)(1)(2)c410.130(A)410.130(G)410.141(B)410.151(B), FPN411.3(A); (B)411.4(A); (B)411.5(D)(1) - (D)(3)422.51424.19426.50(A)427.13430.32(C)430.52(C)(1), Ex. 2430.81(A)430.102(B)(1); (B)(2)430.103430.110(C)(1).1430.126430.227440.14, Ex.1445.13445.18445.19.1445.19.2450.5(B)(2)(b), Ex.490.44(C)490.46

    '2008.Changes.Ch.05.pdf500.7(K)(1)-(K)(3)500.8(A), FPN501.10(B)(7)(7)501.30(B)501.100(A)(2)502.30(B)502.120(B)(2)502.130(B)(2)502.150(B)(1)503.30(B)504.2504.30(A)(1), Ex. 3504.30(A)(2)504.70505.2505.8(K)(1)-(K)(3)505.9(F)505.17(6)505.25(B)506.2Table 506.9506.9(C)(1)&(C)(2)506.9(F)506.25(B)513.2513.3(C)(2)517.2517.19(D)517.32(C); (E); (F)517.34(A)&(B)517.160(A)(5)518.3(B)518.5; Ex.Article 522525.5(B)(1); (B)(2)547.5(F)547.5(G)547.9(E)547.10(A)(1); (A)(2)550.2550.20(A)550.25(B)551.42(C)551.47(S)555.9555.21(B)(1); (B)(2)

    '2008.Changes.Ch.06.pdf600.2600.4(C)600.5(C)(3)600.6(A)(1)600.6(A)(2)(3)600.7(A); (B)600.12(A)-(C)600.21(E)600.24(A)-(C)600.32(K)600.41(B)600.41(D)600.42(G)(1); (G)(2)610.31(2)620.21(e)620.21(A)(3)(e)620.51(A)620.51(C)(1)625.23626.1-32.1640.6(A)-(D)645.5(F); (G)647.8(A)665.12675.8(B)680.10680.12680.22(A)(1)-(A)(3)680.22(E); FPN680.23(B)(6)680.26(A)-(C).1680.31680.43(D), Ex. 2680.71680.74690.4(D)690.5(A)-(C)690.43690.62695.6(B)(1); (B)(2)