2011 nec code changes handbook

33
Overview of 2011 Related to Electrical Wiring Devices NEC ® Code Changes Cablofil Pass & Seymour Wiremold

Upload: blackie-knight

Post on 21-Apr-2015

358 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2011 NEC Code Changes Handbook

Overview of 2011

Related to Electrical Wiring Devices

NEC® Code Changes

Cablofil

Pass & Seymour

Wiremold

Page 2: 2011 NEC Code Changes Handbook

Today’s NEC® regulations have new safety requirements. We have new ways to help you meet them.

In 1971, Pass & Seymour introduced the first in-wall GFCI receptacle. Soon, our invention was preventing injuries and saving lives throughout North America.

Today, you’ll find P&S innovations and safety throughout a broad range of GFCI products – products that offer new versatility, save installation time and solve problems. And products that continue a proud safety tradition that we began over 35 years ago.

Choose P&S GFCI products for innovation – and for all your ground-fault protection needs.

P&S Tamper-Resistant Receptacles - the full line to meet the NEC® and enhance child safety.

P&S Tamper-Resistant Receptacles

protect children by letting plugs in, but keeping keys and other objects out with automatic shutters that block access. Safer and more convenient than plastic outlet caps, this proven safety solution provides a simple way to prevent painful injuries. And because tamper-resistant receptacles provide a real solution to a real problem, they’re required in new residential construction by the National Electrical Code®.

You’ll find everything you’re looking for in the broad P&S Tamper-Resistant Receptacle line. Protection and traditional style in our 3232 TradeMaster® Duplex Receptacle. Unique models like the P&S Nightlight/GFCI Combination. Fresh style in our P&S Signature™ choices. And much more!

For more information, ask your Pass & Seymour distributor or visit www.legrand.us/passandseymour.

Legrand/Pass & Seymour®: your source for safety.

Page 3: 2011 NEC Code Changes Handbook

National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA 02269.

Page i

TABLE OF CONTENTSNEC SECTION DESCRIPTION PAGE210.7 Disconnection of Multiple Branch Circuits and 1

Multiwire Branch Circuits210.8 Readily Accessible GFCIs 2210.8(A)(7) GFCI Protection of Receptacles Near Sinks in Dwellings 3210.8(B)(5) Exception no. 2 to (5) GFCI Protection of Receptacles 4

Near Sinks in Health Care Facilities210.8(B)(6) GFCI Protection of Indoor Wet Location Receptacles 5210.8(B)(7) GFCI Protection of Receptacles in Locker Rooms 6210.8(B)(8) GFCI Protection for Receptacles in Commercial Garages 7210.12(A) Exception 1 & 2 Arc Fault Circuit Interrupter (AFCI) 8

Protection of Outlets in Dwellings210.12(B) Arc Fault Circuit Interrupter (AFCI) Protection of 9

Outlets in Dwellings210.52(A)(2)(1) Receptacle Spacing in Dwelling Units 10210.52(A)(4) Countertop Receptacles 11210.52(C)(4) Separate Countertop Spaces 12210.52(C)(5) & 210.52(D) Receptacles in Kitchen and Bathroom Countertops 13210.52(E)(3) Receptacles on Balconies, Decks and Porches 14210.52(G) Receptacles in Basements, Garages and 15

Accessory Buildings210.52(I) Receptacle Outlets in Dwelling Unit Foyers 16285.25 Type 3 Surge-Protective Devices 17

(Transient Voltage Surge Suppressors)310 Conductors for General Wiring 18314.24 Outlet and Device Box Depth 19314.27(A) Outlet Boxes for Luminaires 20314.27(C) Outlet Boxes for Ceiling Fans 21380.1 & 380.23 Multioutlet Assemblies 22390.2 Underfloor Raceways 23404.2(C) Switches Controlling Lighting Loads 24404.9(B) Exceptions nos. 1, 2, & 3 Grounding of Snap Switches, 25

Page 4: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 1

P&S Cat. #s: 5262, 3232, 8200HI

SECTION 210.7

� Ungrounded conductors must be simultaneously disconnected when two ormore branch circuits supply devices on the same yoke.

Disconnection of Multiple Branch Circuits andMultiwire Branch Circuits

Section 210.7 is intended to reduce the likelihood of unexpected shockhazards for persons working on devices on the same yoke that areconnected to multiple branch circuits.

A means to simultaneously disconnect the ungrounded conductors must beprovided at the point where the branch circuits originate when two or morebranch circuits supply devices on the same yoke. Although the title in the2011 NEC® for Section 210.7 has changed to clearly state this section dealswith Multiple Branch Circuits, the requirement remains the same.

Section 210.4(B) addresses a similar hazard when a multiwire branch circuitsupplies devices on the same yoke. The ungrounded conductors must alsobe simultaneously disconnected at the point where the branch circuitoriginates.

An informational note was added to Section 404.8(C) as a reminder thatSection 210.7 applies if multiple circuits are supplying a multipole switch.

TABLE OF CONTENTS

Page ii

Dimmers and Similar Control SwitchesNEC SECTION DESCRIPTION PAGE404.14(F) Snap Switch Rating for Plug and Cord Connected Loads 26406.2 & 406.14 Tamper-Resistant Receptacles in Child Care Areas 27406.4(D)(4) Arc Fault Circuit Interrupter Protection of 28

Replacement Receptacles406.4(D)(5) Tamper-Resistant Replacement Receptacles 29406.4(D)(6) Weather-Resistant Replacement Receptacles 30406.6 Recessed Receptacle Faceplates 31406.9(B)(1) Receptacles in Wet Locations 32406.12 Tamper-Resistant Receptacles for Dwelling Units 33406.13 Tamper-Resistant Receptacles in Guest Rooms 34

and Guest Suites430.42(C), 430.81(B), Cord and Plug Connected Motors 35430.109(F)517.13(B)(1)(2) Grounding of Receptacles in Patient Care Areas of 36

Health Care Facilities517.16 Isolated Ground Receptacles in Health Care Facilities 37517.18(B) & 517.19(B)(2) Patient Bed Location Receptacles in Health Care Facilities 38517.20(A) Receptacles in Wet Procedure Location Patient Care Areas 39518.3(B) Temporary Wiring in Exhibition Halls 40525.23 GFCI Protection for Carnivals, Circuses, Fairs 41550.13(B) GFCI Protection of Receptacles in 42

Mobile/Manufactured Homes550.13(F)(1) Receptacles Near Bathtubs and Shower Stalls in 43

Mobile/Manufactured Homes550.25 AFCI Protection of Branch Circuits in 44

Mobile/Manufactured Homes551.47(L) & 552.48 (K) Receptacle Faceplates in Recreational Vehicles 45

and Park Trailers552.59(A) Park Trailer Outdoor Receptacles and Switches 46590.4(D)(2) Receptacles in Temporary Installations 47604.6(A)(5) Manufactured Wiring Systems 48625 Electric Vehicle Charging System 49680.21(C) GFCI Protection of Pool Pump Motors 50680.32 Receptacles Near Storable Pools 51

Page 5: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 3

P&S Cat #s: 1595, 2095Technical Support 800-223-4185 www.legrand.us

Page 2

Ground Fault Circuit Interrupters that provide protection forreceptacles as specified in Sections 210.8 (A), (B) and (C) must nowbe installed in a readily accessible location. GFCIs are marked “testmonthly” and are provided with a test button that must be operatedmonthly to insure that the GFCI is functioning properly. Locating aGFCI where it is accessible will increase the likelihood that the GFCIwill be tested by the user. A location that is Readily Accessible isdefined in Article 100 of the NEC®.

Readily Accessible GFCIs

SECTION 210.8

� GFCIs installed per 210.8 must be readily accessible.

P&S Cat. #s: 1595, 2095v

GFCI protection must be provided for receptacles within 6 feet of all sinksin a dwelling. Previously, the requirement applied only to laundry, wet barand utility sinks. This revision to the 2011 NEC® parallels the requirementin Section 210.8(B)(5) to provide GFCI protection for receptacles within6 feet of sinks in commercial and other non-dwelling installations. Thecode now insures that the same level of GFCI protection is provided forreceptacles near sinks in all installations.

Although Section 210.8(A)(7) states that the requirement applies to sinksother than those in kitchens, the intent is not to exempt countertopreceptacles near kitchen sinks from having GFCI protection. Kitchencountertop receptacles are to required to have GFCI protection per Section210.8(A)(6). As a result, receptacles that serve countertops located nearkitchen sinks will have GFCI protection. The wording of Section 210.8(A)(7)is intended to make it clear that other receptacles, such as dishwasher anddisposal receptacles that may be within 6 feet of a kitchen countertop sink,are not required to have GFCI protection.

SECTION 210.8(A)(7)GFCI protection of Receptacles Near Sinks in Dwellings

6'

� 15A and 20A, 125V receptacles within 6 feet of a sink in a dwelling mustbe GFCI protected.

Page 6: 2011 NEC Code Changes Handbook

PZ1624

Technical Support 800-223-4185 www.legrand.us

Page 4

P&S Cat #s: 1595HG, 2095HG

This new section has been added to the 2011 NEC® to require GFCIprotection for receptacles located in indoor wet locations in other thandwellings. An indoor wet location is an area such as a car wash or foodprocessing facility.

Receptacles located in indoor wet locations are exposed to the samepotentially hazardous conditions that exist in outdoor wet locations.Section 210.8(B)(4) requires outdoor receptacles to be GFCI protected.This new requirement will insure that receptacles in indoor wetlocations are provided with the same level of GFCI protection.

SECTION 210.8(B)(6)GFCI Protection of Indoor Wet Location Receptacles

� 15A and 20A, 125V receptacles located in indoor wet locations arerequired to be GFCI protected.

The exception to Section 210.8(B)(5) has been revised to make it clearthat GFCI protection is not required for receptacles located near sinksin patient bed locations of general care or critical care areas. There isconcern that receptacles located near hand washing sinks in theseareas may be used for patient care life support, monitoring, and otherportable patient care equipment that should not be plugged into areceptacle protected by a GFCI.

Patient Bed Locations, Critical Care Areas and General Care Areas aredefined in Article 517 of the code.

This exception does not apply to other locations in Health CareFacilities. The exception is specific to General and Critical Care Areas.A receptacle located within 6 feet of a sink in other areas must beGFCI protected.

SECTION 210.8(B)(5) Exception No.2 to (5)GFCI Protection of Receptacles Near Sinks in

Health Care Facilities

� GFCI protection is required for 15A and 20A, 125V receptacles within 6feet of sinks except in patient bed locations in general care or criticalcare areas.

P&S Cat #s: 1595, 2095

Page 5

Technical Support 800-223-4185 www.legrand.us

Page 7: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 6

GFCI protection for receptacles in dwelling unit garages is requiredby Section 210.8(A)(2). Section 511.12 requires GFCI protection forreceptacles in commercial service and repair garages where volatileflammable liquids or gases are used for vehicle fuel or power.This new Section, 210.8(B)(8), ensures that the same level of GFCIprotection for receptacles will be provided in all garages, service baysand similar areas where electrical diagnostic equipment, electricalhand tools and portable lighting equipment are used. An example ofa garage or service area not previously covered is a service facility forplug-in electric hybrid vehicles.

SECTION 210.8(B)(8)

� 15A and 20A, 125V receptacles in garages where electrical diagnosticequipment, electrical hand tools or portable lighting equipment is usedmust be GFCI protected.

GFCI Protection for Receptacles in Commercial Garages

GFCI protection is now required for receptacles located in lockerrooms that have an associated shower facility. A shower located neara locker room may create a hazardous condition. The damp and wetconditions in a locker room due to proximity to a shower, the use ofelectrical personal grooming equipment, such as a hair dryer, peoplewith bare feet exposed to the damp tile floor of a locker room, allcontribute to the increased risk of electrical shock. GFCI protectedreceptacles will provide a significantly increased level of safety in thistype of environment.

SECTION 210.8(B)(7)GFCI Protection of Receptacles in Locker Rooms

� 15A and 20A, 125V receptacles located in a locker room with anassociated shower facility must be GFCI protected.

P&S Cat #s: 1595, 2095 P&S Cat #s: 1595, 2095

Page 7

Technical Support 800-223-4185 www.legrand.us

Page 8: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 8

Technical Support 800-223-4185 www.legrand.us

Page 9

In the 2008 NEC® the definition for an AFCI was in section 210.12(A). The definitionhas been relocated to Article 100 in the 2011 NEC®.

As a result of moving the AFCI definition to article 100, the requirements for AFCIprotection that were stated in Section 210.12(B) in the 2008 NEC® have beenmoved to section 210.12(A). Section 210.12(A) in the 2011 NEC® requires AFCIprotection for 120 volt, 15 and 20 amp branch circuits supplying outlets in familyrooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms,recreation rooms, closets, hallways, or similar rooms or areas.

The exceptions to 210.12(A) permit a receptacle type Outlet Branch Circuit AFCI toprovide the required protection when located at the first outlet of the branchcircuit under the following conditions:

Exception No. 1 – The branch circuit conductors from the origin of the branchcircuit to the first outlet are installed in RMC, IMC, EMT, MC cable or steelarmored AC cable. Metal outlet and junction boxes must also be used between theorigin of the branch circuit and the first outlet.

Exception No. 2 – The branch circuit conductors from the branch circuitovercurrent device to the first outlet are installed in listed metal or nonmetallicconduit or tubing encased in at least 2 inches of concrete.

SECTION 210.12(A) Exception 1&2Arc-Fault Circuit Interrupter (AFCI) Protection of

Outlets in Dwellings

� A Receptacle Type AFCI may provide protection of the branch circuit.

Section 210.12(A) in the 2011 NEC® requires AFCI protection for120 volt, 15 and 20 amp branch circuits supplying outlets in familyrooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms,sunrooms, recreation rooms, closets, hallways, or similar roomsor areas.

A new section, 210.12(B), has been added to require AFCI protectionfor branch circuit modifications and extensions of the circuits specifiedin Section 210.12(A). The AFCI protection for the modified or extendedcircuits may be a listed Combination AFCI at the origin of the branchcircuit or a listed Outlet Branch Circuit AFCI located at the firstreceptacle outlet of the circuit.

The Combination AFCI located at the origin of the branch circuit istypically a circuit breaker AFCI. The Outlet Branch Circuit AFCI locatedat the first receptacle outlet will be a receptacle type AFCI. Eitherdevice may be used to meet the requirements of 210.12(B).

SECTION 210.12(B)Arc-Fault Circuit Interrupter (AFCI) Protection of

Outlets in Dwellings

� A Circuit Breaker or Receptacle Type AFCI must provide protection ofbranch circuit extensions and modifications.

Page 9: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 10

P&S Cat #s: 885, 3232, 885TR, 3232TR

A new section, 210.52(A)(4), has been added to make it clear that thecountertop receptacles installed to comply with Section 210.52(C) maynot be considered as the receptacles that meet the general provisioninstallation requirements for receptacles in Section 210.52(A). Thecountertop receptacles are intended to serve the appliances that areused on a countertop space.

SECTION 210.52(A)(4)Countertop Receptacles

� Receptacles serving countertops are not considered as meeting thegeneral provisions for receptacle spacing.

Section 210.52(A) provides the spacing requirements for theinstallation of receptacles in dwellings. When measured horizontallyalong the floor line of a wall space no point may be more than 6 feetfrom a receptacle. Section 210.52(A)(2)(1) defines a wall space as anyspace that is at least 2 feet wide and is uninterrupted along the floorline by an opening. In addition to openings, this section has beenrevised to include fixed cabinets. This insures that fixed cabinets, suchas kitchen cabinets, are taken into account and are not included whendetermining the unbroken width of a wall space.

SECTION 210.52(A)(2)(1)Receptacle Spacing in Dwelling Units

� Fixed cabinets are not included in determining the unbroken wallspace for receptacle spacing.

P&S Cat #s: 885, 3232, 885TR, 3232TR

Page 11

Technical Support 800-223-4185 www.legrand.us

Page 10: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 12

P&S Cat #s: 1595, 2095

Section 406.4(E) prohibits the installation of receptacles in a face upposition in countertops. However, sections 210.52(C)(5) and 210.52(D)have been revised to permit listed receptacle outlet assemblies to beinstalled in kitchen and bathroom countertops. This change has beenmade to allow the installation of receptacle assemblies in the topsurface of a countertop. The receptacle assemblies must be listed toinsure that they have been evaluated to function properly whenexposed to conditions likely to be encountered in countertopinstallations, such as liquid spills and splashing. A typical receptacleassembly for this application is a pop up type of receptacle having acover that is flush with the countertop when not in use and pops upwhen operated to reveal the receptacle face.

SECTION 210.52(C)(5) and 210.52(D)Receptacles in Kitchen and Bathroom Countertops

� Listed receptacle assemblies may be installed in kitchen and bathroomcountertops.

The conditions describing when a countertop space is divided intoseparate countertop spaces by a counter-mounted cooking unit,range or sink have been moved from the general Section 210.52(C) tosubsection 210.52(C)(4). Although the requirement has not changed, itwas recognized that Section 210.52(C)(4) is the section that deals withseparate countertop spaces.

SECTION 210.52(C)(4)Separate Countertop Spaces

� Receptacles are required in separate countertop spaces.

Page 13

Technical Support 800-223-4185 www.legrand.us

Wiremold Cat. #s: KP2345, KP9999

Page 11: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 14

P&S Cat #s: 1595TRWR, 2095TRWR, 1595DS, 2095DS, WIUC10Technical Support 800-223-4185 www.legrand.us

Page 15

P&S Cat #s: 1595TRWR, 2095TRWR, 1595DS, 2095DS

At least one 125 volt, 15 or 20 amp outdoor receptacle must beprovided to serve a balcony, deck or porch of a dwelling. Thereceptacle must be located within the perimeter of the balcony, deckor porch. This requirement is intended to avoid the use of extensioncords routed from an inside receptacle through windows or doorwaysto supply holiday lighting and other electrically operated products usedoutdoors. The 2008 NEC® had an exception stating that for areas lessthan 20 ft2 a receptacle was not required. The 2011 NEC® has deletedthis exception recognizing that electrically operated products could beused on decks, porches and balconies having an area less thanspecified in the exception.

SECTION 210.52(E)(3)Receptacles on Balconies, Decks and Porches

� The receptacle must be located within the perimeter of the balcony,deck or porch.

Receptacles in Basements, Garages and Accessory Buildings

Accessory buildings have been added as a location where at leastone receptacle must be installed. Many dwellings have additionalbuildings, other than garages, where electrical equipment is utilized.Section 210.8(A)(2) requires the receptacle to be GFCI protected.

SECTION 210.52(G)

� At least one receptacle outlet is required in each basement, garage andaccessory building in one family dwellings.

Page 12: 2011 NEC Code Changes Handbook

Type 3 Surge Protective Devices (SPD) installed on the load side of the branchcircuit overcurrent protection were required by Section 285.25 of the 2008 NEC®tobe located at least 30 feet from the service. In the 2011 NEC® this section has beenrevised to state that the requirement to install the Type 3 SPD at least 30 feet fromthe service is necessary only when specified in the manufacturers instructions. Thischange recognizes that a Type 3 SPD that has been subjected to additional testingmay be installed anywhere in the branch circuit on the load side of the overcurrentprotection. UL 1449, the Standard for Surge Protective Devices, requires a Type 3SPD that has not been evaluated by the additional testing to be marked “CAUTION –Do not install this device if there is not at least 10 meters (30 feet) or more of wirebetween the electrical outlet and the electrical service panel.” If this marking doesnot appear on the SPD or in the instruction sheet the Type 3 SPD may be installedanywhere in the branch circuit.

Type 3 SPDs are typically cord connected power strips or receptacle type devices.

Technical Support 800-223-4185 www.legrand.us

Page 16

P&S Cat #s: 885TR, 3232TRP&S Cat. #s: 5362GRYSP, TR5362GRYSP, PT5362GRYSP Wiremold Cat. #s: M6BZ, M6S

Receptacle outlets will now be required in foyers. This changerecognizes that many homes are built with large foyers. Lamps andother cord and plug connected electrical equipment will be locatedin these foyers and receptacles are required for connection of thisequipment. A foyer having an area of greater than 60 ft² must have areceptacle located in each continuous wall that has a width of at least3 ft that is unbroken by a floor to ceiling window, a door or othersimilar opening.

SECTION 210.52(I)Receptacle Outlets in Dwelling Unit Foyers

� Receptacles must be installed in foyers.

Page 17

Technical Support 800-223-4185 www.legrand.us

SECTION 285.25

� Type 3 SPDs are permitted to be installed on the load side of the branchcircuit overcurrent protection.

Type 3 Surge-Protective Devices(Transient Voltage Surge Suppressors)

Page 13: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 18

Wiremold Cat #s: V2400D, MC-V2400BCTechnical Support 800-223-4185 www.legrand.us

Page 19

P&S Cat #s: S118R, S122R, P118R, P122R

SECTION 314.24

� A box must have sufficient depth for the installation of a large device orutilization equipment.

Outlet and Device Box Depth

This section of the code requires boxes to have sufficient depth toprevent damage to the conductors when devices or utilizationequipment are installed as intended in the box. Section 314.24 hasbeen revised for the 2011 NEC® to include devices. This requirementpreviously applied only to utilization equipment. Section 314.24specifies the depth of the box and the required clearance, taking intoconsideration a variety of conductor sizes.

The reorganization of Article 310 has resulted in the renumberingof most of the sections and tables and the relocation of some ofthe requirements. One notable change is that Table 310.16 for theallowable ampacities of conductors is now Table 310.15(B)(16) in the2011 NEC®. The ambient temperature correction factors have beenremoved from the allowable ampacity Tables and now appearrelocated to new section 310.15(B)(2) and Tables 310.15(B)(2)(a)and 310.15(B)(2)(b). There have also been changes to the allowableampacities for several different conductor sizes in Table 310.15(B)(16).

ARTICLE 310

� Article 310 has been reorganized and renumbered.

Conductors for General Wiring

Page 14: 2011 NEC Code Changes Handbook

Page 20

P&S Cat #s: 55501, S120RAC, S120HAC, C118WAC, S118W

Page 21

P&S Cat #s: 55025, 55501, 22200

Technical Support 800-223-4185 www.passandseymour.com

When a ceiling box is installed in a location where a ceiling-suspendedfan may be installed and when a spare, separately switched,ungrounded conductor is provided, the box must be listed for supportof a fan. Section 314.27(C) has been revised to recognize that when aceiling box is installed under these conditions it is likely that a ceiling-suspended fan will be installed on the box. This requirement appliesonly to single and multi-family dwellings.

SECTION 314.27(C)Outlet Boxes for Ceiling Fans

� A box listed for support of a ceiling-suspended fan must be installedwhen a spare ungrounded conductor is provided.

Technical Support 800-223-4185 www.passandseymour.com

Section 314.27(A) has been revised to more clearly state the outlet boxrequirements for supporting luminaires at wall and ceiling outlets.Ceiling outlet boxes intended to support a luminaire must be able tosupport at least 50 pounds. A box may be used to support a luminaireweighing more than 50 pounds if the box is listed and marked for themaximum luminaire weight to be supported.

A wall box intended to support a luminaire must be marked to indicatethe maximum weight of the luminaire to be supported, if other than50 pounds. An exception allows wall type luminaires weighing6 pounds or less to be supported by device boxes, plaster rings orother boxes when the luminaire is secured by at least two No. 6 orlarger screws.

SECTION 314.27(A)Outlet Boxes for Luminaires

� Outlet boxes are permitted to support luminaires in walls and ceilings.

Page 15: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 23

Wiremold Cat #s: D21210, D41210, 2-0, 4-0Technical Support 800-223-4185 www.legrand.us

Page 22

Wiremold Cat #s: 20GB306, 20GB506

Although the requirements in Article 390 for Underfloor Racewaysremain the same, Section 390.2 now provides a definition. UnderfloorRaceways are installed flush or beneath the floor surface and areintended for the installation of conductors. The underfloor racewaymay be equipped with junction boxes for access to the conductors aswell as a wide variety of fittings such as floor boxes and pedestals thatallow power, voice and data connectivity.

SECTION 390.2Underfloor Raceways

� A new definition for Underfloor Raceway has been added to the code.

Article 380 provides the installation requirements for MultioutletAssemblies. A new Section, 380.23, specifies the wire bending space andpull requirements for conductors in field assembled multioutlet assemblies.Section 380.23 does not apply to listed, factory assembled multioutletassemblies.

Section 380.23(A) requires insulated conductors installed in a fieldassembled multioutlet assembly to comply with the wire bending spacespecifications in Table 312.6(A). Where a multioutlet assembly is usedas a pull box for 4 AWG or larger insulated conductors, Section 380.23(B)requires compliance with Section 314.28(A)(1) for straight pulls and Section314.28(A)(2) for angle pulls.

Section 380.23 applies only to field assembled multioutlet assemblies.There was concern that conductors could be damaged when installed infield assembled multioutlet assemblies.

Another change to this Article is that Section 380.1 has been revised to addan informational note that directs the user to the definition of a MultioutletAssembly in Article 100.

SECTION 380.1 and SECTION 380.23Multioutlet Assemblies

� Field assembled Multioutlet Assemblies must comply with wire bendingspace and pull box requirements.

Page 16: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 25

P&S Cat #s: PS20AC1, PT20AC1, CSB15AC1, TM870, 660

Page 24

P&S Cat #s: PTWSP250, WDT100, WSP250

Grounding of Snap Switches, Dimmersand Similar Control Switches

SECTION 404.9(B) Exceptions Nos. 1, 2, & 3

� A snap switch, dimmer or similar control switch shall be connected to theequipment grounding conductor.

Technical Support 800-223-4185 www.passandseymour.com

Page 24

This is a new section that requires the grounded circuit conductor of the lightingcircuit to be provided at the switch location. Many lighting control devices, such asan occupancy sensor, require low levels of stand-by current for proper operation.In many installations, the equipment grounding conductor is the only availableconductor that can be used as a circuit conductor for this low level stand-bycurrent. The intent of this change in the code is to be certain that the lightingcircuit grounded conductor is available for the proper operation of the lightingcontrol device. This ensures that operation of the control device does not rely onconnection to the equipment grounding conductor. The result is that there willbe no undesirable current on the equipment grounding conductor. The use ofelectronic lighting control devices is expected to increase due to increasedemphasis on energy efficient lighting systems.

Exceptions to Section 404.2(C) allow for future installation of the grounded circuitconductor where there is access to the switch box in cable installations or whereraceway is used to provide the conductors. In either case, the grounded circuitconductor can be provided after the initial installation.

SECTION 404.2(C)Switches Controlling Lighting Loads

� A grounded circuit conductor shall be provided at the switch location.

This section requires snap switches, dimmers and similar control switches to be connectedto the equipment grounding conductor by the means specified in Section 404.9(B)(1) and(2). This rule ensures that a metal faceplate installed on the switch will be grounded.There are three exceptions to this requirement:

Exception No. 1 – A replacement switch is not required to be connected to the equipmentgrounding conductor where the equipment grounding conductor is not available in theswitch enclosure. Where the replacement switch is installed 8 feet vertically or 5 feethorizontally from ground or grounded metal objects it must have a nonconductingfaceplate secured by nonmetallic screws or the circuit must be protected by a GFCI.

Exception No. 2 – listed switch assemblies of nonmetallic construction as described in thisnew exception are not required to be connected to the equipment grounding conductor.

Exception No. 3 – a snap switch with an integral nonmetallic enclosure as described inSection 300.15(E) is not required to be connected to the equipment grounding conductor.This type of switch is commonly known as a self contained device (SCD).

Page 17: 2011 NEC Code Changes Handbook

Page 27

P&S Cat #s: 3232TR, 885TR, TM8HWLTR, 1595TR, TR5262, TR26262Technical Support 800-223-4185 www.legrand.us

Page 26

P&S Cat #s: PS20AC1, TM870, CSB15AC1, 2621, TM870, 660

Technical Support 800-223-4185 www.passandseymour.com

Section 406.14 has been added to the code to require that all non-locking 125 volt, 15 and 20 amp receptacles installed in child carefacilities must be tamper-resistant. Section 406.2 defines a child carefacility as a location where educational, supervision or personal careservices are provided for more than four children under the age ofseven. This change in the code recognizes that even in supervisedfacilities, such as child care areas, children have access to electricalreceptacles and the potential for shock and burn incidents exist if achild inserts a foreign object into a receptacle.

SECTION 406.2 and 406.14Tamper-Resistant Receptacles in Child Care Areas

� Tamper-resistant receptacles are required in child care facilities.

This new section establishes the rating of a switch used to controlreceptacle outlets. The switch must be rated not less than the rating ofthe overcurrent device protecting the circuit. The exception permits theswitch to be rated not less than the receptacle rating where the switchcontrols only one receptacle.

SECTION 404.14(F)Snap Switch Rating for Plug and Cord Connected Loads

� Snap switches must be rated not less than the rating of the overcurrentdevice protecting the circuit.

Page 18: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 29

P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TRTechnical Support 800-223-4185 www.legrand.us

Page 28

Sections 406.12, 406.13, 406.14 and 517.18(C) require the installationof listed tamper-resistant receptacles in child care facilities, guestrooms, guest suites, specified areas of dwelling units and pediatriclocations. Section 406.4(D)(5) is a new section that requires areplacement receptacle to be tamper-resistant when installed in anyof the locations specified in the code that require a tamper-resistantreceptacle.

SECTION 406.4(D)(5)Tamper-Resistant Replacement Receptacles

� Replacement receptacles must be tamper resistant where tamper-resistant receptacles are required by the code.

Page 28

This new section requires AFCI protection for a replacement receptacle.When a replacement receptacle is installed on a branch circuit thatrequires AFCI protection, the replacement receptacle must be providedwith AFCI protection. Branch circuits that require AFCI protection arespecified in Section 210.12. AFCI protection for the replacementreceptacle may be provided by one of the following methods:- the replacement receptacle is a listed Outlet Branch Circuit type AFCI- the replacement receptacle may be protected by a listed OutletBranch Circuit type AFCI receptacle located upstream from thereplacement receptacle- a listed combination type AFCI circuit breaker providing protection ofthe branch circuit

Section 406.4(D)(4) becomes effective January 1, 2014.

SECTION 406.4(D)(4)Arc Fault Circuit Interrupter Protection of

Replacement Receptacles

� AFCI protection must be provided for replacement receptacles onbranch circuits that require AFCI protection.

Page 19: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 31

Wiremold Cat #s: CRFB4, RFB4, RFB9, RFB11Technical Support 800-223-4185 www.legrand.us

Page 30

This new requirement has been added to section 406.6 to ensure thatfaceplates for receptacles installed in a recessed box effectively closethe opening.

SECTION 406.6Recessed Receptacle Faceplates

� Faceplates for recessed mounted receptacles must effectively close theopening.

P&S Cat. #s: 1595TRWR, 2095TRWR, WIUC10

Section 406.9 requires the installation of listed weather-resistantreceptacles in wet and damp locations. Section 406.4(D)(6) is a newsection that requires a replacement receptacle to be a weather-resistant receptacle when installed in any of the locations specifiedin the code that require a weather-resistant receptacle.

SECTION 406.4(D)(6)Weather-Resistant Replacement Receptacles

� Replacement receptacles must be weather resistant where weather-resistant receptacles are required by the code.

Page 20: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 33

P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TRTechnical Support 800-223-4185 www.legrand.us

Page 32

P&S Cat #s: WIUCAST1, WIUC10

This section was previously added to the code in response to thenumerous reported electrical injuries to children resulting from theinsertion of conductive foreign objects into receptacles. Section 406.12requires that 15 and 20 amp, 125 volt receptacles in all areas ofdwellings specified in Section 210.52 must be tamper-resistant.Section 406.12 has been revised to allow exceptions to the tamper-resistant receptacle requirement. The exceptions include receptacleslocated more than 5-1/2 feet above the floor, receptacles in adedicated space for appliances that cannot be easily moved andreceptacles that are part of a luminaire or appliance. The exceptionsrecognize that there are receptacles that cannot be easily reached bychildren and there are receptacles specified in Section 210.52 that arenot considered to meet the receptacle installation requirements indwellings. In addition, Section 406.12 has been revised to limit thetamper-resistant requirement to the nonlocking type of receptacle.

SECTION 406.12Tamper-Resistant Receptacles for Dwelling Units

� 15A and 20A, 125V receptacles in dwellings must be listedtamper resistant.

Section 406.9(B)(1) requires a weatherproof cover for 15 and 20 amp,125 and 250 volt receptacles installed in wet locations. These covers,commonly referred to as While-In-Use covers, provide protection forthe receptacles both when a plug is inserted and when there is no pluginserted into the receptacle. This section has been revised to requirean “Extra Duty” While-In-Use cover in installations where the box issupported from grade in other than one and two family dwellings. Theintent of this revision in the code is to ensure that covers mounted onboxes supported by conduit, stanchions, wood braces or other freestanding rigid supports can withstand the severe service conditionsexpected in these installations. The “Extra Duty” covers are evaluatedto more demanding test requirements than general purpose covers.The covers must be listed and marked “Extra Duty.”

SECTION 406.9(B)(1)Receptacles in Wet Locations

� Extra Duty While-In-Use Covers are required when the outlet box issupported from grade.

Page 21: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 35

P&S Cat #s: 5262, PS5266XGCM, PS5269XGCM, 5278SS, WPG1Technical Support 800-223-4185 www.legrand.us

Page 34

P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TR, TR5262, TR26262

Both of these sections have been revised to recognize that a motormay be connected to the branch circuit by not only a plug andreceptacle but also by a cord connector. Per Section 210.50(A), a cordconnector may be supplied by a permanently connected cord pendant.

Section 430.109(F) has been revised to include a flanged surface inletand cord connector as a motor disconnect means. Previously, thissection recognized only a plug and receptacle as the disconnectmeans.

SECTIONS 430.42(C), 430.81(B) and 430.109(F)Cord and Plug Connected Motors

� Motors may be connected to the branch circuit by a plug and receptacleor a cord connector. The motor disconnect may be a plug andreceptacle or a flanged surface inlet and a cord connector.

Section 406.13 is a new Section that requires nonlocking 15 and20 amp, 125 volt receptacles in guest rooms and guest suites to betamper-resistant. Guest rooms and guests suites are defined inArticle 100 of the NEC®. These locations are often occupied bychildren and present hazards similar to other locations such asdwellings that require tamper-resistant receptacles.

SECTION 406.13Tamper-Resistant Receptacles in Guest Rooms

and Guest Suites

� 15A and 20A, 125V receptacles in guest rooms and guest suites must belisted tamper-resistant.

Page 22: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 37

P&S Cat #s: TR62HI, 8300HITechnical Support 800-223-4185 www.legrand.us

Page 36

P&S Cat #s: TRIG8300, IG8300

The revisions to Section 517.13(B) are intended to more clearly statethe requirements for the connection of the insulated equipmentbonding conductor to receptacles, metal boxes and non-currentcarrying conductive surfaces. An exception permits an equipmentbonding jumper to connect the receptacle and box to the equipmentgrounding conductor.

SECTION 517.13(B)(1)(2)Grounding of Receptacles in Patient Care Areas of

Health Care Facilities

� This section is restructured to provide the requirements for the connectionof the insulated equipment grounding conductor in patient care areas.

Section 517.16 has been revised to prohibit the use of isolated groundreceptacles in patient care areas. There was concern that theredundant grounding required by Sections 517.13(A) and (B) may notbe adequately achieved when using isolated ground receptacles.

SECTION 517.16

� Isolated ground receptacles are no longer permitted in patient care areas.

Isolated Ground Receptacles in Health Care Facilities

Page 23: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 39

Technical Support 800-223-4185 www.legrand.us

Page 38

P&S Cat #s: 420HI, 8201, 8200HI

The requirements for patient bed receptacles in general care areasand critical care areas have been revised to include quadruplexreceptacles, in addition to single and duplex receptacles, as the typeof receptacles that may be installed to meet the minimum receptaclerequirements for theses areas.

SECTION 517.18(B) and 517.19(B)(2)Patient Bed Location Receptacles in Health Care Facilities

� Patient bed location receptacles may be single, duplex or quadruplex.

Section 517.20(A), titled Receptacles and Fixed equipment, requiresthe power distribution system in wet procedure patient care areas toeither limit the ground fault current due to a first fault to a low valuewithout interrupting the power, or, to interrupt the power supply if theground fault current exceeds 6 mA. The revision to this section closelyparallels the wording in NFPA 99, Section 4.3.2.2.8.1.

SECTION 517.20(A)Receptacles in Wet Procedure Location Patient Care Areas

� The power distribution system must limit the ground fault current.

P&S Cat #s: 8300HI, PTTR8300, 8300W, PT8300

Page 24: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 41

Technical Support 800-223-4185 www.legrand.us

Page 40

P&S Cat #s 1594CMM

Temporary wiring in exhibition halls may be installed in accordancewith Article 590, with the exception that the ground fault circuitinterrupter (GFCI) requirements of 590.6 do not apply. However,section 518.3(B) has been revised to state that all other GFCIrequirements in the code apply in this type of installation. Anadditional revision to this section requires that portable GFCIs mustmeet the requirements for a listed product. This effectively means thatportable GFCIs should be listed products.

SECTION 518.3(B)Temporary Wiring in Exhibition Halls

� Ground fault circuit interrupter protection required in exhibition halls.

Section 525.23(A) has been rewritten to clearly state in enforceablelanguage the requirement for GFCI protection of 15A and 20A, 125Vreceptacles.

Section 525.23(B) previously stated that receptacles are not requiredto be GFCI protected if the receptacles are of the locking type and theyare used for the quick connect and disconnect of equipment. A revisionto this section includes the additional condition that the receptaclesthat are unprotected by a GFCI must also not be accessible from gradelevel.

SECTION 525.23GFCI Protection for Carnivals, Circuses, Fairs

� GFCI protection is required for 15A and 20A, 125V nonlocking receptacles.

P&S Cat #s: 1595, 2095

Page 25: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 43

P&S Cat #s: 1595, 2095Technical Support 800-223-4185 www.legrand.us

Page 42

P&S Cat #s: 1595, 2095

Section 550.13(B) specifies the receptacles that must be GFCIprotected in mobile and manufactured homes. This section has beenrevised to delete the exception which allowed receptacles not to beGFCI protected where the receptacles were installed for use withappliances in a dedicated space. This section now references theexceptions in Section 210.8(A) as the only permitted exceptions.

SECTION 550.13(B)

� 15A and 20A, 125V receptacles requiring GFCI protection.

GFCI Protection of Receptacles in Mobile/Manufactured Homes

This section restricted the installation of a receptacle within a bathtubor shower stall. In addition to the previous wording of the requirement,the section has been revised to make it clear that a receptacle may notbe installed directly over a bathtub or shower stall.

SECTION 550.13(F)(1)Receptacles Near Bathtubs and Shower Stalls in

Mobile/Manufactured Homes

� Receptacles shall not be installed within or directly over a bathtub orshower stall.

Page 26: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 45

P&S Cat #s: 5262, TP8Technical Support 800-223-4185 www.legrand.us

Page 44

This section previously required AFCI protection for 120V branchcircuits that supply 15A and 20A receptacles installed in bedrooms.In addition to the AFCI protection for bedroom branch circuits, Section550.25 has been revised to require AFCI protection for 120 volt branchcircuits supplying 15A and 20A receptacles in family rooms, diningrooms, living rooms, parlors, libraries, dens, sunrooms, recreationrooms, closets, hallways, or similar rooms or areas. The AFCIprotection must comply with Section 210.12(B).

SECTION 550.25AFCI Protection of Branch Circuits in

Mobile/Manufactured Homes

� Additional 15 and 20A, 120V branch circuit outlets must be AFCIprotected.

The title of Section 551.47(L) and Section 552.48(K) has been changedto “Receptacle Faceplates.” Both sections have been revised to refer toSection 406.5(A) and (C) for the specific requirements for metallic andnonmetallic faceplates.

SECTION 551.47(L) and SECTION 552.48(K)Receptacle Faceplates in Recreational Vehicles

and Park Trailers

� Faceplates must comply with Section 406.5(A) and (C).

Page 27: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 47

P&S Cat #s: WR20TR, WR5362Technical Support 800-223-4185 www.legrand.us

Page 46

In the 2008 NEC®, outdoor receptacles on park trailers had to beprovided with a gasketed cover for use in wet locations. Section552.59(A) has been revised to require outdoor receptacles to complywith Sections 406.8(A) and (B). A requirement for outdoor switchesto comply with Section 404.4 has also been added to this section.These revisions make certain that the appropriate protection isprovided for switches and receptacles installed outdoors.

SECTION 552.59(A)Park Trailer Outdoor Receptacles and Switches

� Switches and receptacles must meet outdoor installation requirements.

P&S Cat #s: WR20TR, WR5362

Section 509.6(D)(2) is a new section that requires receptacles thatare in wet locations in temporary installations to comply with Section406.9(B)(1). This change in the code recognizes that receptacles intemporary installations will be exposed to the same wet locationsenvironment as any other outdoor installation and must be providedwith the necessary protection to ensure continued safe operation ofthe receptacle.

SECTION 590.4(D)(2)Receptacles in Temporary Installations

� Receptacles in wet locations in temporary installations must meet therequirements in section 406.9(B)(1).

Page 28: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 49

P&S Cat #s: L1EVSE, L2EVSE16Technical Support 800-223-4185 www.legrand.us

Page 48

Wiremold Cat #s: ALA3800 Series, ALA4800 Series

Section 604.6(A)(5) is a new section that specifies listed prewired, modular,surface raceway as one of the construction components of a manufacturedwiring system. This type of surface raceway construction when used as amanufactured wiring system has a rating of 600 volts, 20 amps. A listedsurface raceway intended for use as a manufactured wiring system isevaluated to UL 183, the Standard for Manufactured Wiring Systems.

The code also covers other types of surface raceway products, such asMultioutlet Assemblies in Article 380 and Surface Metal and NonmetallicRaceways in Articles 386 and 388. These products are evaluated to UL5and UL5A, the standards for metal and nonmetallic surface raceways.

A prewired, modular, surface raceway that is a component of aManufactured Wiring System must meet the requirements of Article 604.Other surface raceway type products must meet the requirements of thecode article that applies, such as, Article 380, Multioutlet Assemblies,Article 386, Surface Metal Raceways and Article 388,Surface Nonmetallic Raceways. Article604 applies only to ManufacturedWiring Systems.

SECTION 604.6(A)(5)Manufactured Wiring Systems

� Section 604.6 provides the construction requirements for ManufacturedWiring Systems.

A PHEV is a type of electric vehicle powered by both an electric motorand an internal combustion engine. Both all-electric vehicles andPHEV’s can be charged using cord connected Electric Vehicle SupplyEquipment. These are electric vehicle chargers that have a plug forconnection to the EV inlet and also have a means for connection tothe premises wiring to provide power. The 120 volt charger is typicallya portable unit that plugs into a standard NEMA 5-15 or 5-20receptacle. There is also a 240 volt charger that provides a fastercharge time. The NEC requires that all chargers have a numberof integral safety features, including personnel protection againstelectric shock.

SECTION 625Electric Vehicle Charging System

� Article 625 includes a definition for the Plug-In Hybrid Electric Vehicle(PHEV).

Page 29: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 51

P&S Cat #s: 1595TRWR, 2095TRWR, WIUC10, 1595DS, 2095DSTechnical Support 800-223-4185 www.legrand.us

Page 50

P&S Cat #s: 1595TRWR, 2095TRWR, WIUC10, 1595DS, 2095DS

The requirement for the GFCI protection of pool pump motor outletshas been moved from Section 680.22(B) to Section 680.21(C). Therequirement remains the same except that the voltage ratings havebeen changed from 120 or 240 volt to 120 through 240 volt. GFCIprotection is required for both plug connected and direct connectedpool pump motors.

SECTION 680.21(C)GFCI Protection of Pool Pump Motors

� Outlets supplying pool pump motors must be GFCI protected.

20'

125 volt, 15 and 20 amp receptacles within 20 feet of the inside wallsof a storable pool must be GFCI protected. The change to this sectionadds the 15 and 20 amp ratings of the receptacle which were notpreviously specified.

SECTION 680.32Receptacles Near Storable Pools

� Receptacles within 20 feet of a storable pool must be GFCI protected.

Page 30: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 53

Technical Support 800-223-4185 www.legrand.us

Page 52

NOTESNOTES

Page 31: 2011 NEC Code Changes Handbook

Technical Support 800-223-4185 www.legrand.us

Page 54

NOTES

Page 32: 2011 NEC Code Changes Handbook

For product and application information, please call the

Legrand/Pass & SeymourTechnical Assistance Group at

1-800-223-4185www.legrand.us/passandseymour

Page 33: 2011 NEC Code Changes Handbook

designed to be better.™©

2011

, Leg

rand

/Pas

s &

Sey

mou

r C

TM10

95 2

/11

AG

I/D

G

P.O. Box 4822Syracuse, NY 13221-4822800-776-4035www.legrand.us/PassandSeymour

Legrand Canada570 Applewood CrescentVaughan, ON, L4K 4B4Phone: 905.738.9195, Fax: 905.738.9721www.legrand.ca

For additional technical or application-specific information, call 800-223-4185 or visit our website at www.legrand.us/PassandSeymour. We’re eager to put our expertise to work for you.

Distributed by:

designed to be better.™©

2011

, Leg

rand

/Pas

s &

Sey

mou

r C

TM10

95 7

/11

AG

I/C

GXT

P

P.O. Box 4822Syracuse, NY 13221-4822800-776-4035www.legrand.us/PassandSeymour

Legrand Canada570 Applewood CrescentVaughan, ON, L4K 4B4Phone: 905.738.9195, Fax: 905.738.9721www.legrand.ca

For additional technical or application-specific information, call 800-223-4185 or visit our website at www.legrand.us/PassandSeymour. We’re eager to put our expertise to work for you.

Distributed by: