Chapman BDSP Plantroom & Riser Schedule Heating Plantroom 5700 mm wide x 5300 mm deep x 3000 mm high (overall)

Upload: viena74

Post on 27-Dec-2015

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Heating Plantroom 5700 mm wide x 5300 mm deep x 3000 mm high (overall)

Page 2: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Heating Plantroom 30 m² Ground Floor -

Equipment

Reference Duty Selection

Sidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high, 100 kg, 100 kgEnwamatic, TBCwww.enwamatic.com

Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacityVenting: unventedArrangement: vertical

Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060 mm deep x 2050 mm high, 850 kgIMI Rycroft semi storage vertical, model MX440V, 1760 litres/hrhttp://www.rycroft.com/HRS semi storage vertical, model Aquasave AS515, 2500 litres/hrhttp://www.hrs.co.uk/

Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519 mm high, 56 kgArmstrong in-line vertical pump, model Starline50-150www.armstrongpumps.com

Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753 mm high, 120 kgArmstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com

Calorifiers expansion vessels 2 No. expansion vessels3350 litres system volume3.00 bar g feed pressure3.55 bar g final pressure75ºC maximum system temperature0% glycol370 litres expansion volume

Generic expansion vessel, 500 litres, 581 kgRycroft expansion vessel, model EXP500V, 500 litreshttp://www.rycroft.com/Smedegaard expansion vessel, model Type 2 500, 500 litreshttp://www.smedegaard.com/

Ground energy Storage Pump 1 No. duty / 1 No. standby @ 0 l/s, 180 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446 mm high, 21 kgArmstrong in-line vertical pump, model Starline32-120www.armstrongpumps.com

Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg, 100 kg

Page 3: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg, 100 kg

MCC 200 Amp incomer, 5 starters415 V, TP&N, 50 Hz

Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm highABB MCC, model MNShttp://www.abb.co.uk/Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp

Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomerhttp://www.moeller.co.uk/MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomerhttp://www.eaton.com/uk

Heating pressurisation unit(upper floors)

1 No. pressurisation unit9000 litres system volume8.0 bar g maximum working pressure1.6 bar g maximum system pressure60ºC maximum system temperature0% glycolPressurisation unit types: standard, compressor

Generic standard pressurisation unit, 1170 mm wide x 800 mm deep x 1660 mm high, 802 kgHoval standard pressurisation unit, model PressVal Micron SM600, 600 litreshttp://www.hoval.co.uk/

Boilers vents Vent type: Natural high level, natural low levelHigh level vents to provide 0 m³/s ventilation air exhaustLow level vents to provide 0 m³/s combustion and ventilation air intake(Based on BS6644, BS5410-2 and manufacturer recommendations)

1 No. generic vent at high level, 200 mm wide x 100 mm high, 50 % free area1 No. generic vent at low level, 200 mm wide x 100 mm high, 50 % free area

Page 4: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Auditorium AHU 8800 mm wide x 3500 mm deep x 2900 mm high

Page 5: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Auditorium AHU 30 m² Ground Floor -

Equipment

Reference Duty Selection

Basement AHU Air flow 3 m³/sConfiguration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - ConnectionExtract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Fan (backward curved) - Panel filter - Access (short) - Attenuator (600 mm) - Connection

Generic modular AHU, SFP 1.9 W/l/s (estimated), 7600 mm wide x 1404 mm deep x 2748 mm high, 3040 kgFlakt Woods modular AHU, model EU40http://www.flaktwoods.com/products/air-handling-units/

Page 6: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Main (option!) AHU 11300 mm wide x 8500 mm deep x 5400 mm high

Page 7: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Main AHU 96 m² Ground Floor -

Equipment

Reference Duty Selection

Basement AHU Air flow 8.5 m³/sConfiguration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - ConnectionExtract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Access (short) - Fan (backward curved) - Panel filter - Attenuator (600 mm) - Connection

Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x 2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62http://www.flaktwoods.com/products/air-handling-units/

Page 8: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Basement AHU Air flow 8.5 m³/sConfiguration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - ConnectionExtract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Access (short) - Fan (backward curved) - Panel filter - Attenuator (600 mm) - Connection

Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x 2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62http://www.flaktwoods.com/products/air-handling-units/

Page 9: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)

Page 10: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

HV Plantroom 35 m² Ground Floor -

Equipment

Reference Duty Selection

RMU Rating 200 Amps12000 V, TP&N, 50 Hz

Generic RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300 kgABB RMU, model SafeRinghttp://www.abb.com/Schneider RMU, model Ringmaster RN2http://www.schneider-electric.co.uk/Minimum connection space above: 600 mm

HV switchpanel 12000 V, TP&N, 50 HzModule type: withdrawableModules: - Incomer - Bus section - FeederFuture expansion 25%Note: For some manufacturers VTs are integral to other components

Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300 mm highABB HV switchpanel, model Unigear ZS1http://www.abb.com/Schneider HV switchpanel, model MCSethttp://www.schneider-electric.co.uk/Minimum connection space above: 600 mm

Page 11: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)

Plantroom

Reference Area Location Notes

LV Plantroom 21 m² Ground Floor -

Equipment

Reference Duty Selection

LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg, 100 kg

Page 12: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)

Plantroom

Reference Area Location Notes

Life Safety LV Plantroom 21 m² Ground Floor -

Equipment

Reference Duty Selection

LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg, 100 kg

Page 13: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)

Page 14: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Generators Plantroom 38 m² Ground floor -

Equipment

Reference Duty Selection

LV generators board 1 No. incomer1 No. feeder415 V, TP&N, 50 HzAccess: front

Generic generators LV switchboard, 2650 mm wide x 655 mm deep x 2429 mm highGE Power Controls generators LV switchboard, model System 4http://www.ge.com/Eaton generators LV switchboard, model Bill Classic Form 4http://www.eaton.com/Minimum connection space above: 600 mm

Generators 1 No. generators @ 400 kVA415 V, TP&N, 50 Hz

Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mm deep x 2158 mm high, 3700 kgBroadcrown diesel generator, model BCC 440-50 E2, 440 kVA, Emissions compliance EU Stage 2http://www.broadcrown.com/FG Wilson diesel generator, model P350P4, 400 kVA, Emissions compliance EU Stage 2http://www.fgwilson.com/

Day tanks 1 No. day tanks @ 8 hours storageGenerator fuel tank capacity : 650 litresDay tank capacity (nett): 38 litres

Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x 1250 mm highJoseph Ash day tank, model D01, 1364 litreshttp://www.jaenvirotanks.com/Blake day tank, model TEBU FO 1000, 1000 litreshttp://www.blakegroup.co.uk/

Page 15: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)

Plantroom

Reference Area Location Notes

Gas Meter Plantroom 3 m² Ground Floor -

Equipment

Reference Duty Selection

Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg, 100 kg

Page 16: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall)

Plantroom

Reference Area Location Notes

Telecoms Plantroom 8 m² Ground Floor -

Equipment

Reference Duty Selection

Copper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100 kg

Page 17: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)

Page 18: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Transformers Plantroom 22 m² Ground Floor -

Equipment

Reference Duty Selection

Transformers supply duct 0.82 m³/s @ 10.0 m/s maximum, 1.0 Pa/m maximumMaximum aspect ratio: 4.0Insulation: none(Air flow requirement based on transformers losses)

500 mm wide x 300 mm deepNo insulation

Transformers 1 No. @ 800 kVAHV 12000 V, LV 415 V, TP&N, 50 HzTransformer type: dryDerating factor: 1.25

Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deep x 2400 mm high, 2870 kgABB dry transformer, model Cast resin 1000, 1000 kVAhttp://www.abb.com/Schneider dry transformer, model Cast Resin 1000, 1000 kVAhttp://www.schneider-electric.co.uk/Minimum connection space above: 600 mm

Transformers extract duct 0.82 m³/s @ 10.0 m/s maximum, 1.0 Pa/m maximumMaximum aspect ratio: 4.0Insulation: none(Air flow requirement based on transformers losses)

500 mm wide x 300 mm deepNo insulation

Page 19: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Fire Fighting Riser 2 2275 mm wide x 650 mm deep x 4000 mm high (overall)

Riser

Reference Area Location Notes

Fire Fighting Riser 2 1.5 m² Fire Fighting Core2 Sprinkler valves and wet riser valves may be provided in one of the two riser only.

Equipment

Reference Duty Selection

Dry riser 1 No. dry riser @ 100 mm diameter 100 mm diameter riser pipeCabinet 510 mm wide x 325 mm deep x 720 mm high

Page 20: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Mechanical Riser 1 3125 mm wide x 450 mm deep x 4000 mm high

Riser

Reference Area Location Notes

Mechanical Riser 1 1.4 m² Core 1 To serve the floors of the tower and the roof condensers

Equipment

Reference Duty Selection

LPHW F&R 400 kW @ 3.0 m/s maximum, 240 Pa/m maximumPipe configuration: flow and returnInsulation: mineral wool (e=0.05), heating water 75ºC, internal

100 mm diameter60 mm mineral wool (e=0.05) insulation

CHW F&R 600 kW @ 3.0 m/s maximum, 240 Pa/m maximumPipe configuration: flow and returnInsulation: mineral wool (e=0.05), chilled water 5ºC, internal

125 mm diameter60 mm mineral wool (e=0.05) insulation

Condensate 54 mm diameterPipe configuration: singleInsulation: none

54 mm diameterNo insulation

VP (SVP) 54 mm diameterPipe configuration: singleInsulation: none

54 mm diameterNo insulation

RWP 150 mm diameterPipe configuration: singleInsulation: none

150 mm diameterNo insulation

Condenser Water 150 mm diameterPipe configuration: flow and returnInsulation: mineral wool (e=0.05), chilled water 5ºC, internal

150 mm diameter60 mm mineral wool (e=0.05) insulation

24/7 cooling 150 kW @ 3.0 m/s maximum, 240 Pa/m maximum 80 mm diameter

Page 21: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Pipe configuration: flow and returnInsulation: mineral wool (e=0.05), chilled water 5ºC, internal

50 mm mineral wool (e=0.05) insulation

Page 22: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Public Health Risers 1 2475 mm wide x 525 mm deep x 4000 mm high

Riser

Reference Area Location Notes

Public Health Risers 1 1.3 m² WC Riser core 1 To serve WC'sPrefab (100 mm frame included in dimensions)

Equipment

Reference Duty Selection

MWS 54 mm diameterPipe configuration: singleInsulation: none

54 mm diameterNo insulation

BCWS 54 mm diameterPipe configuration: singleInsulation: none

54 mm diameterNo insulation

HWS F 54 mm diameterPipe configuration: singleInsulation: mineral wool (e=0.05), hot water 60ºC, internal

54 mm diameter50 mm mineral wool (e=0.05) insulation

HWS R 28 mm diameterPipe configuration: singleInsulation: mineral wool (e=0.05), hot water 60ºC, internal

28 mm diameter40 mm mineral wool (e=0.05) insulation

RWP 150 mm diameterPipe configuration: singleInsulation: none

150 mm diameterNo insulation

SVP 100 mm diameter 100 mm diameter

Page 23: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Pipe configuration: singleInsulation: none No insulation

VP (SVP) 110 mm diameterPipe configuration: singleInsulation: none

110 mm diameterNo insulation

VP (interceptor) 100 mm diameterPipe configuration: singleInsulation: none

100 mm diameterNo insulation

Page 24: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

WC Extract 800 mm wide x 825 mm deep x 4000 mm high

Riser

Reference Area Location Notes

WC Extract 0.7 m² WC Riser -

Equipment

Reference Duty Selection

Extract duct 1.80 m³/s @ 7.5 m/s maximum, 1.0 Pa/m maximumMaximum aspect ratio: 3.0Insulation: none

600 mm wide x 500 mm deepNo insulation

Page 25: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)

Page 26: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

MER Room 25 m² Ground Floor -

Equipment

Reference Duty Selection

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack, Rack

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack, Rack

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack

Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100 kg

AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg, 500 kg

AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg, 500 kg

Electrical board 160 Amp incomer, 12 waysType: MCCB415 V, TP&N, 50 Hz

Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mm wide x 230 mm deep x 1605 mm high, 168 kgMoeller mccb electrical board, model PB12-400, 12 way, 400 Amp incomerhttp://www.moeller.co.uk/MEM mccb electrical board, model PBJG1240M, 12 way, 400 Amp incomerhttp://www.eaton.com/uk

UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100 kg

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgrack

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg

Page 27: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

rack

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgrack

Page 28: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)

Page 29: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Security Room 20 m² Ground Floor

Equipment

Reference Duty Selection

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack, Rack

IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack, Rack

IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack

Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100 kg

AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg

Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100 kg

Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomerhttp://www.moeller.co.uk/MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomerhttp://www.eaton.com/uk

Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg

AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg

Page 30: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)

Page 31: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

AV Room 7 m² Ground Floor

Equipment

Reference Duty Selection

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kgRack, Rack

Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg

Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100 kg

Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomerhttp://www.moeller.co.uk/MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomerhttp://www.eaton.com/uk

AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg

AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg

Page 32: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)

Page 33: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

BEMS and Maintenance Room 9 m² Ground Floor

Equipment

Reference Duty Selection

Desk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100 kg

Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg

AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg

Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomerhttp://www.moeller.co.uk/MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomerhttp://www.eaton.com/uk

Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg

Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg

Page 34: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Ventilation distributed fans 9100 mm wide x 8300 mm deep x 1000 mm high (overall)

Page 35: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Ventilation distributed fans 76 m² Every floor -

Equipment

Reference Duty Selection

Floor void unit (approx 4No per floor)

1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kgNuaire , Xbober XB55www.nuaire.co.uk

Floor void unit (approx 4No per floor) Copy 1

1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kgNuaire , Xbober XB55www.nuaire.co.uk

Floor void unit (approx 4No per floor) Copy 2

1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kgNuaire , Xbober XB55www.nuaire.co.uk

Floor void unit (approx 4No per floor) Copy 3

1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kgNuaire , Xbober XB55www.nuaire.co.uk

Page 36: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)

Plantroom

Reference Area Location Notes

Satellite 9 m² Roof -

Equipment

Reference Duty Selection

SATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100 kg, 100 kg

SATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100 kg, 100 kg

Page 37: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Computer AC Units 4100 mm wide x 2200 mm deep x 1200 mm high

Plantroom

Reference Area Location Notes

Computer AC Units 9 m² Roof -

Equipment

Reference Duty Selection

Computer Room AC units 2 No. condensers @ 10 kWCondenser type: vertical air flowMean condensing temperature: 50ºCAmbient temperature: 35ºCNoise: 70 dBA @ 10 m

Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mm deep x 1076 mm high, 62 kgAiredale vertical condenser, model CR12, 14 kWhttp://www.airedale.com/

Page 38: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Air Cooled Chillers Heat pump 11300 mm wide x 6000 mm deep x 2400 mm high

Plantroom

Reference Area Location Notes

Air Cooled Chillers Heat pump 67 m² Roof Air Cooled Chillers Heat pump to operate with ground storagecomplete with hydronic kit

Equipment

Reference Duty Selection

Air cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total loadMinimum EER (or CoP): - 2.50 kW/kW <750 kW - 2.60 kW/kW =>750 kWChiller types: scroll, screwChilled water: 12ºC on / 7ºC offAmbient temperature: 35ºCNoise: 70 dBA @ 10 m

Generic air cooled chiller, 220 kW, 3400 mm wide x 2300 mm deep x 2297 mm high, 2245 kgTrane scroll air cooled chiller, model CGAN800, 220 kWhttp://www.trane.com/Carrier scroll air cooled chiller, model 30RB232, 227 kWhttp://www.carrieraircon.co.uk/

Page 39: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Solar Collector Plantroom 3700 mm wide x 2100 mm deep x 1000 mm high

Page 40: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Plantroom

Reference Area Location Notes

Solar Collector Plantroom 8 m² Roof Composed of multiple solar panels: numbers to be confirmed (by ICAX at www.icax.co.uk) for collecting heat from the sun an storing it to minipiles or piles or horizontal slinkies.

Equipment

Reference Duty Selection

Solar Panels (number TBC) 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Black tarmac'd roof surface as solar collector

1 No. ancillary item(s) Ancillary item, 600 mm wide x 600 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 1

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 2

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 3

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 4

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 5

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 6

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 7

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 8

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 9

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 10

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 11

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 12

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Page 41: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Solar Panels (number TBC) Copy 13

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 14

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 15

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 16

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 17

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 18

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 19

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Solar Panels (number TBC) Copy 20

1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg

Page 42: Solutions Schedule4

Chapman BDSP Plantroom & Riser Schedule

Landlord Electrical Riser 1875 mm wide x 475 mm deep x 4000 mm high

Riser

Reference Area Location Notes

Landlord Electrical Riser 0.9 m² Core -

Equipment

Reference Duty Selection

Main tray - Generic tray, 450 mm wide

Dist bd 1 100 Amp incomer, 24 waysType: MCB415 V, TP&N, 50 Hz

Generic mcb electrical board, 24 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 1180 mm high, 44 kgMoeller mcb electrical board, model FG-B-24, 24 way, 100 Amp incomerhttp://www.moeller.co.uk/MEM mcb electrical board, model EBM242, 24 way, 125 Amp incomerhttp://www.eaton.com/uk

Lighting panel 1 No. lighting panel(s) Lighting panel, 450 mm wide x 150 mm deep x 450 mm high, 100 kg, 100 kg